RIGHT VIEW FRONT VIEW LEFT VIEW


HIGH VOLTAGE SIDE
CL CL CL
42 10 24 26 30

A A

PSP Barrier PSP Barrier


21 16
50 28

49 32 25
19 40
47
2
46
1

100 39
25

25
856

771

100
3638
Sunshade
B B
500
420
25

25
1685

1685
Any unauthorized use, reproduction, distribution or disclosure is strictly forbidden.

420
The information contained in this document is to be kept strictly confidential.

345

29 41 14 General Comments: 44 22 38 18 31 51 27 13 17 34 15
© Copyright Schneider Electric. All rights reserved.

2011 25
1990 25
3422 100
C 4729 100 C
1. TheDETAIL A
internal winding ends shall always remain under the oil/liquid level.
2. HV Side Terminal Box Shall be suitable for 3C x 240 Sq.mm cable.
3. LV Side Terminal box Shall be suitable for 2 Runs /Phase x 1C x 630 Sq.mm cable.
HV CABLE BOX GLAND PLATE LV CABLE BOX GLAND PLATE
TOP VIEW
4. LV Side Neutral point to Neutral grounding resistor terminal shall be suitable for
1C x 70 Sq.mm Cable.
5. Document shall be submitted in project CL template

~530

~470
6.All 9Related comments in 2 MVA GA shall be taken care. 8
610 41 259 300
7. The capacity of the oil conservator tank shall be such that it will cover the expansion of the oil
volume of the transformer under the extremes of ambient temperatures and for all operating ~1660
conditions specified. ~980
kopyalanmasi, dagitilmasi ve ucuncu sahislara devredilmesi yasaktir.

8. The conservator tank shall be equipped with a sealed oil level indicator20gauge. 3C x 240 sq.mm cable
Cable gland plate is 6 mm undrilled (AISI304).
2R x 1C x 630 sq.mm (Per Phase)
5 Cable gland plate is 6 mm undrilled (AISI 304).
Idx Description Details Qty Drawing No 9. At its lowest part, the oil conservator shall have provision to collect and12remove water and
1 AIR VENT PLUG ON RADIATOR - 14 R293169
D sludge. D
Bu belge gizli bilgiler icermektedir. Izinsiz kullanilmasi,

2 BUCHHOLZ RELAY FOR MAINTANK DN50 1 4217159 48 4 LVN CABLE BOX GLAND PLATE
© Copyright Schneider Elektrik. Tum hakki saklidir

3 BUSHING -HV EN 36/1250 3 2040467-03 10. A breather shall be provided with a silica gel dehydrating capsule and an air lock.
4 BUSHING -LV EN 12/2000 3 2040473-01
5 BUSHING -LV - NEUTRAL EN 12/2000 1 2040473-01 45 11. For use in high-humidity areas, a conservator that prevents contact between the oil in the
6 BUTTERFLY VALVE FOR RADIATOR DN80 28 4202616
transformer tank and the ambient air should be used, e.g., either the membrane11 type or multi-
7 CABLE BOX - HV - 1 - 23

~470
8 CABLE BOX - LV - 1 - compartment type of split conservator. 6
9 CABLE BOX - NLV - 1 - 70 Sq.mm
10 CONSERVATOR FOR MAINTANK - 1 - 33 12. The radiators shall be provided with isolating valves fitted at the oil inlet(s)
35
and
11 CORE EARTHING TERMINAL - 1 4218548 outlet(s) and with an oil filling plug and oil drain valve. ~380
12 CURRENT TRANSFORMER 10VA 1310/2A CL.3 1 6040458
37 a. This valve shall be provided with cap and padlock, or alternatively designed to
13 DEHYRATING BREATHER FOR CONSERVATOR - 1 2080719
2R x 1C x 630 sq.mm
14 DIAGRAM PLATE - 1 CVP100D283490 Cable gland plate is 6 mm undrilled (AISI304).
15 DRAIN PLUG ON RADIATOR 1/2" 14 2080810-04
require the use of special tools
2N to operate.
2U 2V 2W
16 DRAIN VALVE FOR CONSERVATOR OF TANK DN40 1 2080764-04
CL
13. Each transformer shall be fitted with one filling/filter connection valve near the top of the tank
17 EVACUATING CONNECTION ON CONSERVATOR - 1 -
and one drain/filter valve near1Uthe bottom
1V of1W
the tank.
18 GAS SAMPLING DEVICE FOR BUCHOLZ RELAY - 1 -
TRANSFORMER TECHNICAL SPECIFICATIONS
19 HANDHOLE - 1 - a. The filling and drain valves shall be fitted with sealing caps and padlocks, or
20 HANDHOLE COVER FOR INSTALLING BUSHING - 2 -
alternatively designed to require the use of special tools to operate. Rated Power - kVA 7500
21 HANDHOLE FOR CLEANING CONSERVATOR OF MAINTANK - 2 -
E E
22 JACKING PAD - 4 - 14. A Buchholz relay shall be provided, complete with an air relief valve, flanges and High Voltage - V 33000
23 LIFTING LUG FOR CORE AND COIL ASSEMBLY - 4 -
24 LIFTING LUGS FOR CONSERVATOR - 2 - valves to enable its removal without the need to drain the oil. Low Voltage - V 3450
25 LIFTING LUGS FOR ENTIRE UNIT - 4 -
15. A cable connection shall be installed between the relay and a terminal box, located onthe Tapping Range (on HV side) 2 x 2.5%
26 MANUFACTURER'S NAME PLATE - 1 -
27 MARSHALLING BOX MBX100D283490 1 MBX100D283490 lower part of the tank wall, for the alarm/trip functions.
Figures are not getting tally Vector Group Dyn11
28 NAME PLATE - 1 CTP100D283490 Frequency - Hz 50
29 OFF-LOAD TAPCHANGER - 1 4205211
43 Cooling Method ONAN
30 OIL LEVEL INDICATOR - 1 4215085
31 OIL SAMPLING VALVE OF MAINTANK (BOTTOM) - 1 19301
Active Part Weight (kg) 6850
32 OIL SAMPLING VALVE OF MAINTANK (TOP) - 1 19301
33 PIPE BETWEEN MAINTANK AND CONSERVATOR - 1 -
36 Oil Weight (kg) 5000
34 PIPE FOR DEHYDRATING BREATHER OF MAINTANK - 1 -
35 PRESSURE RELIEF DEVICE FOR TANK T-80 1 4208691
Transport Weight (kg) 13000
7
36 PRESSURE VACUUM GAUGE - 1 4208118 Total Weight (kg) 19000
37 PRESSURE-EQUALISING VALVE DN25 1 2080764-02 3
38 PULLING EYES - 4 -
Oil Type Midel 7131
EARTHING BOSS - M10 F
39 RADIATOR - 14 - Paint Color RAL 7035
40 RATING PLATE - 1 CRP100D283490 450 450
F 41 RESIDUAL OIL DRAIN PLUG FOR MAINTANK - 1 - 4156 100 Paint Finish Process N 2125 0050
42 SIGHT GLASS FOR +20°C OIL LEVEL ON CONSERVATOR - 1 E2040219
43 SPARE THERMOMETER POCKET - 2 E2060640
44 SURGE ARRESTER - 1 4220666 Date 30.01.2023 Project Number 283490 Weight [kg]
45 TERMINAL BOX 6 CONTACT 1 4214714
46 THERMOMETER FOR OIL TEMPERATURE - 1 4218786 Department ADH-E Material Number - -
47 THERMOMETER FOR WINDING TEMPERATURE - 1 4218792
48 THERMOMETER POCKET - 2 E2060640 Prepared O.GUNDAS Description Class
49 VALVE BETWEEN CONSERVATOR AND MAINTANK DN50 2 2060682 DETAIL A
50 VALVE FOR OIL TREATMENT (INLET) - TOP DN50 1 2080764-05 SCALE 0,100
Approved Y.KAYNAR GENERAL ARRANGEMENT D
51 VALVE FOR OIL TREATMENT (OUTLET) - BOTTOM DN50 1 2080764-05
Scale
DESCRIPTION First release. Drawing Number -
BLOCK -
DIM100D283490 Drawing System
DATE / NAME 30.01.23/O.GUNDAS
CAD Model Name / Number Sheet
REVISION NO 00001
INDEX 01 CAYIROVA / KOCAELI GENERAL_ARRANGEMENT 1/1
Print Size: A2

You might also like