NFPA 12 Technical Suppression Bulletin Rev3 2009
NFPA 12 Technical Suppression Bulletin Rev3 2009
NFPA 12 Technical Suppression Bulletin Rev3 2009
Preface: In the interests of reducing risks to personnel and at the same time maintaining the
reliability of carbon dioxide (CO2) fire extinguishing systems, the NFPA has rewritten, revised
and updated Standard #12 in the 2008 Edition.
The CO2 fire system industry has always been cognizant of the potential risks involved in using
CO2, which extinguishes fire by oxygen deprivation. Since an adequate amount of oxygen is
necessary for sustaining human life, protected spaces must be evacuated before the system is
used. It is important to mitigate this risk in order to be able to utilize the unique fire extinguishing
characteristics of CO2 that have made it the ideal agent to use in many fire suppression
applications.
A rare action by the NFPA in the revised standard is a requirement that existing systems be
upgraded to be in compliance by December 31st, 2008. So even if you only service CO2
systems, these changes offer you the opportunity to increase the safety and reliability of those
systems.
The purpose of the bulletin is to bring to the reader’s attention the more significant new or
enhanced requirements so that planning to accommodate these changes can proceed as
smoothly as possible.
Individual paragraph numbers and related text have been detailed to assist in
identifying/locating the major changes to the standard. In some situations the paragraphs noted
may not follow in numerical order in an attempt to logically present the intent or to emphasize
the extent of the requirements. In addition, annex (appendix) material has been brought forward
to avoid the confusion of relating code requirements to pertinent information shown in the
annex. The new NFPA 12, 2008 edition should be consulted in regards to the specific details of
all the noted changes and the many other alterations included in the revamping of NFPA 12, but
not presented herein.
This bulletin is not intended to take the place of a complete review of the 2008 edition of
NFPA Standard #12.
NEW INSTALLATIONS
4.1.1 New total flooding carbon dioxide systems shall not be installed in normally
occupied enclosures except as permitted in 4.1.1.1, 4.1.1.2, 4.1.1.3, 4.1.1.4, or 4.1.1.5.
4801 Southwick Drive, 3rd Floor Matteson, IL 60443 USA P: 708-8748-1503 F: 708-748-2847
FIRE SUPPRESSION BULLETIN
December 2008
Page 2 of 14
4.1.1.1 New total flooding carbon dioxide systems shall be permitted to be installed in
normally occupied enclosures where it is determined that an inerting concentration is
required and the inerting concentration required using alternate gaseous agents results
in a concentration above the lowest observed adverse effect level (LOAEL) or the
oxygen concentration is less than 8 percent.
4.1.1.2 New total flooding carbon dioxide systems shall be permitted to be installed in
normally occupied enclosures for fires involving energized electrical
equipment >400 volts and grouped electrical cables where no gaseous alternative agent
has been successfully tested.
4.1.1.3 New total flooding carbon dioxide systems shall be permitted to be installed in
normally occupied enclosures where design methods or hardware, or both, for
unencloseable openings or extended discharge are not available for other gaseous
agents.
4.1.1.4 New total flooding carbon dioxide systems shall be permitted to be installed in
marine cargo holds.
4.1.1.5 New total flooding carbon dioxide systems shall be permitted to be installed in
normally occupied enclosures in marine engine rooms where it is determined that an
inerting concentration is required and the inerting concentration required using alternate
gaseous agents results in a concentration above the LOAEL or the oxygen concentration
is less than 8 percent.
DEFINITIONS
3.3.7 Occupiable Enclosure or Space. An enclosure or space that has dimensions and
physical characteristics such that it could be entered by a person.
EXISTING INSTALLATIONS
The current NFPA 12 does not allow the use of Class 150 malleable iron fittings. NFPA
12, 1977 edition and prior editions allowed the use of Class 150 iron fittings for 3/4" and
smaller pipe sizes. All system upgrades should include the use of Class 300 fittings for
the modified portion of the systems.
4801 Southwick Drive, 3rd Floor Matteson, IL 60443 USA P: 708-8748-1503 F: 708-748-2847
FIRE SUPPRESSION BULLETIN
December 2008
Page 3 of 14
1.3.4 Existing systems shall be upgraded to meet the requirements for safety signs in
4.3.2, lock-out valves in 4.3.3.4 and 4.3.3.4.1, and pneumatic time delays and pneumatic
predischarge alarms in 4.5.6.1.
The installation of the safety signs per 4.3.2 does not require any modifications to the
installation and should be accomplished immediately.
The addition of supervised lock-out valves, per 4.3.3.4 and 4.3.3.4.1, and pneumatic
predischarge alarms and pneumatic time delays, per 4.5.5.7, require that the system
flow calculations be verified and be in accordance with this standard. That is, the
addition of piping equipment (valve and time delays) adds equivalent pipe length to the
system. The pneumatic predischarge alarm requires carbon dioxide flow to sound. The
revised design should be in accordance with the agent quantity requirements of this
standard.
These modifications could necessitate revisions to, upgrading of, or replacement of
system components, including control units.
4.3.3.1 All persons who can at any time enter a space protected by carbon dioxide shall
be warned of the hazards involved and provided with safe evacuation procedures.
4801 Southwick Drive, 3rd Floor Matteson, IL 60443 USA P: 708-8748-1503 F: 708-748-2847
FIRE SUPPRESSION BULLETIN
December 2008
Page 4 of 14
Olfactory indicators could be inappropriate for such applications used in clean rooms,
food processing plants, aluminum rolling mills, and telecommunications facilities
because they could adversely affect the process or equipment.
Provisions to help prevent the entry of persons into areas made unsafe by the discharge
of carbon dioxide could include one or more of the following:
(1) Addition of a distinctive odor to the discharging carbon dioxide, the detection of which
serves as an indication to persons that carbon dioxide gases are present. Personnel
should be trained to recognize the odor and evacuate
spaces wherein the odor is detected.
(2) Provision of automatic alarms at the entry to and within such spaces for which alarms
are activated by carbon dioxide detectors or oxygen detectors.
(3) Establishment and enforcement of confined space entry procedures for such areas.
4.3.3.2 Audible and visible alarms shall be provided in accordance with 4.5.6.
4.3.3.3* All personnel shall be informed that discharge of carbon dioxide gas from either
high- or low-pressure systems directly at a person will endanger the person’s safety by
causing eye injury, ear injury, or even falls due to loss of balance upon the impingement
of the high-velocity discharging gas.
4.3.3.4 A lockout shall be provided on all systems except where dimensional constraints
prevent personnel from entering the protected space.
4.3.3.4.1 Lockout valves shall be installed on all systems where carbon dioxide could
migrate, creating a hazard to personnel.
4.3.3.4.2* A service disconnect switch shall not be used as a means of preventing agent
discharge in lieu of a lockout valve.
4801 Southwick Drive, 3rd Floor Matteson, IL 60443 USA P: 708-8748-1503 F: 708-748-2847
FIRE SUPPRESSION BULLETIN
December 2008
Page 5 of 14
4.5.6.1 Predischarge Alarm and Time Delay. A pneumatic predischarge alarm and
pneumatic time delay and visible predischarge alarm shall be provided for the following
enclosures:
(1) Normally occupied and occupiable enclosures protected by total flooding systems
except as outlined in 4.5.6.1.3.
(2) Local application systems protecting hazards where the discharge exposes
personnel to concentrations of carbon dioxide in excess of 7.5 percent by volume of
agent in air for longer than 5 minutes
4.5.6.1.1 The predischarge alarms, where required, shall be located within the
enclosure.
4.5.6.1.2 The predischarge time delay shall provide a time delay for purpose of
predischarge alarm of sufficient duration to allow evacuation of personnel from areas
within the spaces most remote from the exits.
4.5.6.1.3* Time delays shall be permitted to be eliminated for occupiable hazard areas
where the provision of a time delay would result in unacceptable risk to personnel or
unacceptable damage to critical pieces of equipment.
4.5.6.1.4 Where time delays are omitted, provision shall be made to ensure that the
carbon dioxide system is locked out at any time that personnel are present in the
protected area or space.
4.5.6.1.5 Dry runs shall be made to determine the minimum time needed for persons to
evacuate the hazard area, allowing time to identify the warning signal.
4.5.6.1.6 Audible signal appliances shall have either sound levels in accordance with
4.5.6.1.6.1 through 4.5.6.1.6.2 or acoustic characteristics in accordance with
7.4.5, Narrow Band Tone Signaling for Exceeding Masked Thresholds, of NFPA72.
4801 Southwick Drive, 3rd Floor Matteson, IL 60443 USA P: 708-8748-1503 F: 708-748-2847
FIRE SUPPRESSION BULLETIN
December 2008
Page 6 of 14
4.5.6.1.6.2 Audible signal appliances shall have a sound level not more than 120 dB at
the minimum hearing distance from the audible appliance.
4.5.6.1.6.3 The predischarge alarm shall have a minimum decibel rating of 90 dBA at 10
ft (3 m).
4.5.6.2 Visible and audible alarms shall be located outside each entrance to the
following:
(1) Normally occupied and occupiable space protected by a total flooding carbon dioxide
system
(2) Normally occupied and occupiable enclosures where the discharge from a local
application system will expose personnel to hazardous concentrations of carbon dioxide
(3) Normally occupied and occupiable spaces where carbon dioxide could migrate,
creating a hazard to personnel
4.5.6.2.1 These alarms shall begin operation prior to or at the start of the discharge.
4.5.6.2.2* These alarms shall continue to operate after agent discharge until one of the
following occurs:
(1) Other positive action has been taken to prevent entry of personnel to the space
containing an atmosphere made unsafe by the carbon dioxide discharge.
(2) The space is ventilated and the safety of the atmosphere for entry by unprotected
persons has been verified.
4801 Southwick Drive, 3rd Floor Matteson, IL 60443 USA P: 708-8748-1503 F: 708-748-2847
FIRE SUPPRESSION BULLETIN
December 2008
Page 7 of 14
4.5.4.13.2 The discharge pressure switch shall provide an alarm-initiating signal to the
releasing panel to operate electric/electronic alarm appliances.
4.4.2.14 The system owner shall maintain an instruction and maintenance manual that
includes a full sequence of operation, and a full set of system drawings and calculations
shall be maintained in a protective enclosure.
4.5.5.1 Supervision of automatic systems and manual lockout valves shall be provided
unless specifically waived by the authority having jurisdiction.
4.5.5.2 Supervision of automatic systems shall be provided, and the lockout required by
4.3.3.4 shall be supervised for both automatic and manual systems unless specifically
waived by the authority having jurisdiction.
4.5.5.3* Interconnections between the components that are necessary for the control of
the system and life safety shall be supervised.
4801 Southwick Drive, 3rd Floor Matteson, IL 60443 USA P: 708-8748-1503 F: 708-748-2847
FIRE SUPPRESSION BULLETIN
December 2008
Page 8 of 14
4.5.5.5 The alarm and trouble signals shall be transmitted by one of the methods
described in NFPA 72.
4.3.3.4.4.1 The fire watch shall have a communication link to a constantly monitored
location.
4.3.3.4.4.2 Authorities responsible for continuity of fire protection shall be notified of the
lockout and subsequent restoration of the system.
4801 Southwick Drive, 3rd Floor Matteson, IL 60443 USA P: 708-8748-1503 F: 708-748-2847
FIRE SUPPRESSION BULLETIN
December 2008
Page 9 of 14
ARRANGEMENT WITH
TIME DELAY
ARRANGEMENT WITHOUT
TIME DELAY
4801 Southwick Drive, 3rd Floor Matteson, IL 60443 USA P: 708-8748-1503 F: 708-748-2847
FIRE SUPPRESSION BULLETIN
December 2008
Page 10 of 14
Master valve with selector arrangement – with time delay – typical low pressure CO2 arrange ment
Required by NFPA 12, 2008 Edition
4801 Southwick Drive, 3rd Floor Matteson, IL 60443 USA P: 708-8748-1503 F: 708-748-2847
FIRE SUPPRESSION BULLETIN
December 2008
Page 11 of 14
4.3.2 Signs.
4.3.2.2 The safety sign format, color, letter style of signal words, message panel
lettering, lettering size, and the safety provisions of symbols shall be in accordance with
ANSI Z535.
4.3.2.3 Safety signs and message wording shall be provided using a three-panel format
as required by 4.3.2.3.1 through 4.3.2.3.6.2.
4.3.2.3.1 The sign in Figure 4.3.2.3.1 shall be used in every protected space.
4.3.2.3.2 The sign in Figure 4.3.2.3.2 shall be used at every entrance to protected
space.
4.3.2.3.3 The sign in Figure 4.3.2.3.3 shall be used at every entrance to protected space
for systems provided with a wintergreen odorizer.
4.3.2.3.4 The sign in Figure 4.3.2.3.4 shall be used in every nearby space where carbon
dioxide could accumulate to hazardous levels.
4.3.2.3.5 The sign in Figure 4.3.2.3.5 shall be used outside each entrance to carbon
dioxide storage rooms.
The installation of safety signs per 4.3.2 does not require any modifications to the
installation and should be added immediately
4801 Southwick Drive, 3rd Floor Matteson, IL 60443 USA P: 708-8748-1503 F: 708-748-2847
FIRE SUPPRESSION BULLETIN
December 2008
Page 12 of 14
4801 Southwick Drive, 3rd Floor Matteson, IL 60443 USA P: 708-8748-1503 F: 708-748-2847
FIRE SUPPRESSION BULLETIN
December 2008
Page 13 of 14
4801 Southwick Drive, 3rd Floor Matteson, IL 60443 USA P: 708-8748-1503 F: 708-748-2847
FIRE SUPPRESSION BULLETIN
December 2008
Page 14 of 14
Bill of Common Materials
DESCRIPTION S/N
Maintenance switch, NEMA 4 w/pilot light & key lockout 70170220
1/4" Ball valve w/DPDT limit switch W/P (timer bypass) 70985018
1/2" Ball valve w/DPDT limit switch W/P 70985020
3/4" Ball valve w/DPDT limit switch W/P 70985021
1" Ball valve w/DPDT limit switch W/P 70985022
1-1/4" Ball valve w/DPDT limit switch W/P 70985023
1-1/2" Ball valve w/DPDT limit switch W/P 70985024
2" Ball valve w/DPDT limit switch W/P 70985025
1/4" Ball valve w/DPDT limit switch X/P (timer bypass) 70985090
1/2" Ball valve w/DPDT limit switch X/P 70985069
3/4" Ball valve w/DPDT limit switch X/P 70985070
1" Ball valve w/DPDT limit switch X/P 70985071
1-1/4" Ball valve w/DPDT limit switch X/P 70985072
1-1/2" Ball valve w/DPDT limit switch X/P 70985073
2" Ball valve w/DPDT limit switch X/P 70985074
3" Wafer valve w/SPDT limit switch (See Note #2) 10610994
4" Wafer valve w/SPDT limit switch (See Note #2) 10610995
6" Wafer valve w/SPDT limit switch (See Note #2) 10610996
3" Wafer valve w/DPDT limit switch (See Note #2) 10611068
4" Wafer valve w/DPDT limit switch (See Note #2) 10611069
6" Wafer valve w/DPDT limit switch (See Note #2) 10611070
4801 Southwick Drive, 3rd Floor Matteson, IL 60443 USA P: 708-8748-1503 F: 708-748-2847