Meters CTs Protection Relays Automatic Power Factor Controllers


Timers Time Switches PLCs HMI Temperature Controllers
en

Process Indicators Counters


di
Co

www.selec.com
Index
METERS 3
Multifunction Meters
Energy Meters
Digital Panel Meters ( VAF Meters, Voltmeters, Ammeters, Frequency Meters, Power Factor Meters )
Analog Meters
Current Transformers
Automatic Power Factor Controllers

MONITORING / PROTECTION RELAYS 18


Phase Sequence Relay
Voltage Protection Relay
Current Protection Relay
Earth Leakage Relay
Earth Fault Relay
Motor Protection Relay
Water Level Controller

TIME SWITCHES 28
Din Rail Mount
Wall Mount

TIMERS 30
17.5mm DIN Rail Timers
22.5mm DIN Rail Timers
8 Pin Socket / Panel Mount Timers
Digital Timers
Time Totalisers

COUNTERS & RATE INDICATORS 38


Programmable / Preset Counters
Totalisers
Rate Indicators
m

TEMPERATURE CONTROLLERS & PROCESS INDICATORS 42


Advanced PID Controllers
.co

Profile Controller
Economic Temperature Controllers
Analog Temperature Controller
u

Cooling Controller
ia

Process Indicators
ha

PLCs & HMI 50


en

Flexible I/O Solutions


Compact Series
di

Fixed I/O Solutions


HMI
Co

2 www.selec.com ELECTRICAL PANEL METERS


ELECTRICAL PRODUCTS
Meters / APFCs / Current Transformers

METERS AUTOMATIC POWER FACTOR CONTROLLERS CURRENT TRANSFORMERS


Multifunction 8/12 steps in 144 x 144mm size SPCT (Bus Bar type)
Energy 8/12 steps with built in MFM in 144 x 144mm size RCT (Cable type)
DPM 6/8 steps in 96 x 96mm size TWCT (Tape Wound type)
Analog

Applicable EMI / EMC Standards


Product Standard : IEC 61326-1

Category Standards Compliance


ESD Immunity IEC 61000-4-2 Level IV (Air discharge : 15kV), (Contact Discharge : -8kV)
m

+/- 2kV common mode, (Line to ground)


Surge Immunity IEC 61000-4-5
+/- 1kV differential mode, (Line to Line)
.co

Level III, 80 to 1000MHz (10V/m)


Radiated Susceptibility IEC 61000-4-3 Level II, 1.4GHz to 2GHz (3V/m)
Level I, 2GHz to 2.7GHz (1V/m)
u

Conducted Susceptibility IEC 61000-4-6 Level II (3V/m)


ia

Dips : 0% residual voltage / 1 cycle (Criteria B),


ha

Voltage Dips and 40% residual voltage / 10 cycles 50Hz / 12 cycles 60Hz (Criteria C)
IEC 61000-4-11 70% residual voltage / 25 cycles 50Hz / 30 cycles 60Hz (Criteria C)
Interruptions
Interruptions : 0% residual voltage / 250 cycles 50Hz / 300 cycles 60Hz (Criteria C)
en

Conducted Emission CISPR-11


di

Radiated Emission CISPR-11


Co

Electrical Fast Transient IEC 61000-4-4 Level III (2kV)

Note : Above standards are applicable only for CE certified Multifunction Meters, Digital Panel Meters & Automatic Power Factor Controllers

3 www.selec.com
Multifunction Meters

CerMID
tifie
New
d

MFM384 MFM383A MFM376


Size : 96 x 96mm Size : 96 x 96mm Size : 96 x 96mm
! LCD type with Bargraph ! Single Pulse Output ! Single Pulse Output
! Single Pulse Output ! Energy (Active / Reactive / Apparent) ! Max / Min Demand (Power)
st
FEATURES
! THD upto 31 level ! Run Hour
! Max / Min Demand (Power) ! Auxiliary Interrupts
! Max Demand Current ! Phase Angle

DISPLAY LCD with Backlight LCD with Backlight 7 segment LED


4 rows of 4 digits, 3 rows of 4 digits,
DIGITS Bargraph representation for current, 3 rows of 4 digits
1 row of 8 digits for energy display 7½ digits for energy

ELECTRICAL
3Ø - 4W, 3Ø - 3W, 2Ø - 3W, 1Ø - 2W
CONNECTION
RATED INPUT VOLTAGE 11 to 300V AC (L-N), 19 to 519V AC (L-L)

RATED INPUT CURRENT Nominal 5A AC (11mA min ; 6A max) Nominal 5A AC (14mA min ; 6A max)

For energy : 0.01k, 0.1k, 1k, 0.01M, 0.1M, For energy : 0.1k, 1k For energy : 0.01k, 0.1k, 1k, 0.01M, 0.1M,
1M (depending upon CT ratio x PT ratio), (depending upon CT ratio x PT ratio) 1M (depending upon CT ratio x PT ratio),
RESOLUTION For Power, Voltage & Current : Auto For Power, Voltage & Current : Auto For Current, Voltage, Power : Auto
resolution, For Power factor : 0.001 resolution, For Power factor : 0.001 resolution, For Power factor : 0.001

CT PRIMARY 1 / 5A to 10kA (Programmable for any value)

CT SECONDARY 1 or 5A (Programmable)
100V to 500kV 100V to 10kV 100V to 500kV
PT PRIMARY (Programmable for any value) (Programmable for any value) (Programmable for any value)
PT SECONDARY 100 to 500V AC (L-L) (Programmable for any value)
COMMUNICATION RS485 Communication MODBUS RTU Protocol (Optional)
MEASURING Voltage (L-L / L-N) (Individual / Average), Current (I1, I2, I3) (Individual / Average), Frequency, Power Factor (Individual / Total), Active,
PARAMETER Reactive & Apparent power (Individual / Total), Active, Reactive & Apparent Energy (Total)
Max instantaneous (Current / Voltage),
ADDITIONAL Phase sequence detection --- (Import / Export) Energy, THD upto 31st
FUNCTIONS level (For MFM376-C)
240V AC, ±20% (For MFM376-230VAC),
SUPPLY VOLTAGE 100 to 240V AC, -15% to +12%, 50/60Hz (±5%) (Power consumption : Less than 8VA) 85V to 270V AC & 40 to 270V DC
(For MFM376-C)

Terminal Connections Ordering Information


MFM384 / MFM384-C, MFM383A / MFM383A-C SUPPLY OUTPUT
PRODUCT CODE CERTIFICATION
N
L VOLTAGE PULSE OUTPUT COMMN
valid for
communication MFM384
+

PULSE O/P RS485 model only MFM384-C


MFM384-C-CE RoHS
m

MFM384-MB-CE-RoHS (MBUS) RoHS


100V to 240V AC
L1 L
MID384 -15% to +12% MID RoHS

MFM383A
.co

L2 O
L3 A MFM383A-C
N D
MFM383A-C-CE RoHS

S1 S2 S1 S2 S1 S2 N V1 V2 V3 MFM376-230V 240V AC ± 20%


u

I1 I2 I3
MFM376-C 85 to 270V AC, 40 to 270V DC
ia

MFM376 / MFM376-C
N
valid for L
ha

communication Dimensions (All are in mm)


+
+

PULSE O/P RS485 model only


en

90.5 91.5
99
L1 L
di

L2 O
L3 A
99 50 91.5
N D 5
Co

Front bezel Side view Panel cutout


S1 S2 S1 S2 S1 S2 N V1 V2 V3
I1 I2 I3

4 www.selec.com ELECTRICAL PANEL METERS


Din Rail Multifunction Meters

MFM384-R-C MFM384-R-C-48V DC
Size : 70 x 90mm Size : 70 x 90mm

! Energy (Active, Reactive, Apparent) ! Energy (Active, Reactive, Apparent)


! RS485 Communication MODBUS RTU Protocol ! RS485 Communication MODBUS RTU Protocol
! Import / Export Energy ! Import / Export Energy
FEATURES
! Max / Min Demand (Power) ! Max / Min Demand (Power)
! 85 to 270V AC, 50/60Hz Supply ! DC : 30 to 60V ; AC : 18 to 36V Supply

DISPLAY LCD with backlight

DIGITS 1 Row of 4 digits, 2 Rows of 7 digits


ELECTRICAL
3Ø - 4W, 3Ø - 3W, 2Ø - 3W, 1Ø - 2W
CONNECTION
RATED INPUT VOLTAGE 11 to 300V AC (L-N), 19 to 519V AC (L-L) 2 to 76.2V AC (L-N), 3.5 to 132V AC (L-L)
RATED INPUT CURRENT Nominal 5A AC (11mA min ; 6A max)
FREQUENCY 45Hz to 65Hz
For Energy : 0.01k, 0.1k, 1k, 0.01M, 0.1M, 1M (Depending upon CT ratio x PT ratio), For For Energy : 0.01k, 0.1k, 1k, 0.01M, 0.1M, 1M (Depending upon CT ratio x PT ratio), For
RESOLUTION Power, Voltage, Current : Auto resolution, For Power Factor : 0.01, Frequency : 0.1Hz Power, Voltage, Current : Auto resolution, For Power Factor : 0.01, Frequency : 0.1Hz

Voltage (L-L / L-N), Current : ±0.5% Voltage & Current : ±0.5% of range, Frequency : ±0.15% of mid frequency
Power Factor : ±0.01 of full range, Frequency : ±0.1% of full range Power (Active, Reactive, Apparent) : ±0.5% of range
ACCURACY CLASS Power (kW, kVA, kVAr) : 1% of full range Energy (Active, Reactive, Apparent) : ±0.5%
Energy (Active, Reactive, Apparent) : 1% of full range Power Factor : ±0.5% of unity.

CT PRIMARY 1 / 5A to 10kA (Programmable for any value)


CT SECONDARY 1 or 5A (Programmable)
PT PRIMARY 100V to 500kV (Programmable for any value) 80V to 500kV (Programmable for any value)
PT SECONDARY 100V to 500V AC (L-L) (Programmable for any value) 80V to 140V AC (L-L) (Programmable for any value)
MEMORY RETENTION 10 years
FOR ENERGY
COMMUNICATION RS485 Communication MODBUS RTU Protocol (Optional)

INDICATIONS LCD : Max Demand of Power, Communication in progress ; LED : Integration of Energy.

MEASURING Voltage (L-L / L-N) (Individual / Average), Current (I1, I2, I3) (Individual / Average), Frequency, Power Factor (Individual / Total), Active,
PARAMETER Reactive & Apparent power (Individual / Total), Active, Reactive & Apparent Energy (Total), Demand (Min / Max Active & Reactive Power, Max Apparent Power)

SUPPLY VOLTAGE 85 to 270V AC, 50/60Hz DC : 30 to 60V ; AC : 18 to 36V, 50/60Hz

Terminal Connections Dimensions (All are in mm)


MFM384-R-C MFM384-R-C-48V DC
44
70
O

D
A
L

D
A
L

m
RS485

10
+

RS485

10
+
N
9

11 12 13 14 15 16 17 18 19

.co
11 12 13 14 15 16 17 18 19

45
8

90
L

+
7

7
S1 S2 S1 S2 S1 S2

u
VN

S1 S2 S1 S2 S1 S2
6

N
I3

I3

ia
5

V3

V3

66.3
4

4
I2

ha
I2
3

3
V2

V2

Ordering Information
2

2
I1

I1

PRODUCT CODE SUPPLY VOLTAGE OUTPUT CERTIFICATION


en
1

1
V1

V1

MFM384-R-C
85 to 270V AC Commn (RS485)
MFM384-R-C-CE RoHS
L2
L3
L2
L3

L1
L1

N
N

DC : 30 to 60V
di

MFM384-R-C-48V DC Commn (RS485)


AC : 18 to 36V
Co

5 www.selec.com ELECTRICAL PANEL METERS


Plug-n-Wire Multifunction Meters

MRJ4M MRJ4M-SL MRJ385


Size : 90 x 70mm Size : 90 x 70mm Size : 96 x 96mm
! Energy (Active, Reactive) ! Energy (Active, Reactive) ! Energy (Active, Reactive, Apparent)
! RJ45 Connector current input ! RJ45 Connector current input ! Split load, RJ45 for current input
! Single Pulse Output. ! 2 Pulse Output. ! Single Pulse Output.
FEATURES
! Max Demand of Power ! Max Demand of Power ! Max / Min Demand of Power
! Self powered ! Self powered ! Self Powered
st
! THD upto 31 Level
DISPLAY LCD with backlight
4 rows of 4 digits, Bargraph representation for current,
DIGITS 2 Rows of 4 digits, 1 Row of 7 digits to show electrical parameters
1 row of 8 digits for energy display
ELECTRICAL
3Ø - 4W, 1Ø - 2W
CONNECTION
RATED INPUT VOLTAGE 60 to 300V AC (L-N), 104 to 520V AC (L-L) 100 to 240V AC (L-N ), 173 TO 415V AC (L-L)
For Energy : 0.01K, 0.1K, 1K, 0.01M, 0.1M For Energy : 0.01K, 0.1K, 1K, 0.01M, 0.1M, 1M
(depending upon CT ratio x PT ratio) (depending upon CT ratio x PT ratio)
RESOLUTION
For Power, Voltage, Current : Auto resolution For Power, Voltage, Current : Auto resolution
For Power Factor : 0.01 For Power Factor : 0.01

CT PRIMARY 5A to 10kA (Programmable for any value)

CT SECONDARY 330mV

PT PRIMARY 100V to 10kV 100V to 500kV (Programmable for any value)


PT SECONDARY 100 to 500V AC (L-L) (Programmable for any value) 173 to 415V AC (L-L) (Programmable for any value)

COMMUNICATION RS485 Communication MODBUS RTU Protocol (Optional)


LCD : Max / Min demand of power, communication in
INDICATIONS LCD : Max demand of power, communication in progress ; LED : Integration of energy
progress ; Integration of energy, Unit in Configuration Menu
Voltage (L-L / L-N) (Individual / Average), Current (I1, I2, I3)
Voltage (L-L / L-N) (Individual / Average), Current (I1, I2, I3) (Individual / Average), Frequency, Power factor
Voltage (L-L / L-N) (Individual / Average), Current (I1, I2, I3)
(Individual), Frequency, Power factor (Individual / Average), (Individual / Average), Active, Reactive, Apparent power
(Individual / Average), Frequency, Power factor
MEASURING Active, Reactive, Apparent power (Individual / Total), (Individual / Total), Active, Reactive, Apparent Energy
(Individual / Average), Active, Reactive, Apparent power
PARAMETER Active & Reactive Energy, Total Active & Reactive Energy (Phase wise (Import / Export) & Total (Import / Export)),
(Individual / Total), Active & Reactive Energy, Demand
(Current input-1 plus current Input-2), Demand Demand (Min / Max Active Power, Min / Max Reactive Power,
(Max Active Power, Max Apparent Power)
(Max Active Power, Max Apparent Power) Max Apparent Power), Harmonics individual for voltage &
Current upto 31st level.
SUPPLY VOLTAGE Self powered

Terminal Connections Dimensions (All are in mm)


MRJ4M MRJ385 MRJ4M / MRJ4M-SL
Pulse
RS485 Output 70
44
RJ 45 + +
Current
Input 1 1 2 3 4 5 6 7
m

RJ45 Current Input 45


90
I1 I2 I3
.co

S1 S2 S1 S2 S1 S2

8 7 6 5 4 3 2 1

8 9 10 11 12 13 14 15 16 17 18 19 66.3
u

V3 V2 V1 N N V1 V2 V3
Voltage IN Voltage Out MRJ385
ia

MRJ4M-SL Pulse
90.5 91.5
ha

Output
RS485 1 2 99
RJ 45 + + +
Current Current
Input 1 Input 2 1 2 3 4 5 6 7
99 50 91.5
en

5
Front bezel Side view Panel cutout
RJ45 Current Input
I1 I2 I3
Ordering Information
di

S1 S2 S1 S2 S1 S2
OUTPUT
8 7 6 5 4 3 2 1 PRODUCT CODE CERTIFICATION
PULSE OUTPUT COMMN (RS485)
Co

8 9 10 11 12 13 14 15 16 17 18 19
MRJ4M RoHS

V3 V2 V1 N N V1 V2 V3 MRJ4M-SL RoHS
Voltage IN Voltage Out RoHS
MRJ385-G-PNW

6 www.selec.com ELECTRICAL PANEL METERS


Energy Meters

EM306B EM368 EM4M-412


Size : 96 x 96mm Size : 96 x 96mm Size : 70 x 90mm
! Potential Free Pulse Output for Energy ! Potential Free Pulse Output for Energy ! Four Loads (3 Ø), 12 Loads (1 Ø) Energy Monitoring
! Active Energy ! Power (Active / Reactive) ! Power (Active / Reactive / Apparent)
! Energy (Active / Reactive / Apparent) ! Energy (Active / Reactive / Apparent)
FEATURES

DISPLAY 7 segment LED LCD with Backlight LCD with Backlight

6 digits 8 digits 2 Rows of 4 digits, 1 Row of 7 digits to show


DIGITS electrical parameters
ELECTRICAL
3 Ø - 4 W, 3 Ø - 3 W, 2 Ø - 3 W, 1 Ø - 2 W
CONNECTION
RATED INPUT VOLTAGE 11 to 300V AC (L-N), 19 to 519V AC (L-L)
RATED INPUT CURRENT Nominal 5A AC (min : 11mA ; max : 6A ) Nominal 1A AC (min : 11mA ; max : 1.2A )

0.01K, 0.1K, 1K & 10K For energy : 0.01k, 0.1k, 1k, 0.01M, 0.1M, 1M, 10M
RESOLUTION (depending upon CT ratio x PT ratio) For Energy : 0.01k, 0.1k, 1k, 0.01M, 0.1M, 1M
(depending on CT ratio)
For Power : Auto resolution, For Power factor : 0.01
Active Energy : Class 1, Reactive / Apparent Energy : ±1% Active Energy : 1%
ACCURACY Class 1 Active / Reactive power : ±1%, PF & Avg. PF : ±1%
POWER CONSUMPTION 8VA Max
CT PRIMARY 1 / 5A to 10kA (Programmable for any value) 1A to 10kA (Programmable for any value)
CT SECONDARY 1 or 5A (Programmable) 1A
PT PRIMARY 100V to 500kV (For EM306B) 100V to 500kV (Programmable for any value) 100V to 10kV (Programmable for any value)
PT SECONDARY 100V to 500V AC (L-L) (For EM306B) 100V to 500V AC (L-L) (Programmable for any value) 100V to 500V AC (L-L) (Programmable for any value)

RS485 Communication MODBUS


COMMUNICATION RS485 Communication MODBUS RTU Protocol (Optional)
RTU Protocol (For EM306A-C)

Power (Total Active / Reactive), Energy (Total Active / Voltage, Current, Frequency, PF, 4 Loads &
MEASURING Active Energy (kWh) Resettable 12 Loads Energy, (Active, Reactive, Apparent),
PARAMETER Reactive / Apparent), Power factor (Individual & Average) Power (Active, Reactive, Apparent)
Integration of energy, Resolution is 10, Integration of energy, Resolution is 10, Reverse
LED INDICATIONS connected CT warning, Communication in progress, Integration of energy
Reverse connected CT warning pulse output (All Indications on LCD)
230V AC ±20% (50/60Hz) For EM306B
SUPPLY VOLTAGE 100 to 240V AC, -15% to +12%, 50/60Hz (±5%) 85 to 270V AC, (50/60Hz)
100V to 240V AC, -15% to +12% (50/60Hz) For EM306A-C

Terminal Connections Ordering Information


EM306B / EM306A-C EM4M-412 SUPPLY OUTPUT
PRODUCT CODE CERTIFICATION
VOLTAGE PULSE OUTPUT COMMN. (RS485)
I11 I12 I21 I22 I31 I32 I11 I12 I21 I22 I31 I32
N
L EM368
Valid for
communication CH4 CH3
EM368-C 100 to 240V AC,
+
+

PULSE O/P RS485 model only


RS485 EM368-CU -15% to +12% RoHS C UL US
m

LISTED

L1 L + EM368-C-CU RoHS C UL US
LISTED
L2 O
L3 A
EM306B 230V AC, ±20%
.co

N D

V3 V2 V1 VN N L EM306A - C 100V to 240V AC,


S1
I1
S2 S1
I2
S2 S1
I3
S2 N V1 V2 V3 -15% to +12%
CH1 CH2 EM4M-412 85 to 270V AC
u

EM4M-412-CE 85 to 270V AC RoHS


I11 I12 I21 I22 I31 I32 I11 I12 I21 I22 I31 I32
ia

EM368 / EM368-C
Dimensions (All are in mm)
ha

EM4M-412 EM306B / EM306A-C / EM368


N
L 70 44
Valid for
communication
+
+

en

PULSE O/P RS485 model only

L1 L
L2 O
99 90.5 91.5
45
di

L3 A
90
N D

S1 S2 S1 S2 S1 S2 N V1 V2 V3
Co

I1 I2 I3
99 50 91.5
5
Front bezel Side view Panel cutout
62

7 www.selec.com ELECTRICAL PANEL METERS


VAF Meters - Digital

VAF36A VAF39A-2
Size : 96 x 96mm Size : 96 x 96mm
! 3Ø (True RMS) Voltage & Current ! 3Ø (True RMS) Voltage & Current
! Frequency ! Frequency
! Run Hour (Hour - Mins) ! Run Hour (Hour - Mins)
FEATURES ! RPM ! RPM
! Analog Style Bargraph Indication ! Programmable CT Secondary

DISPLAY LCD (with Backlight) 7 segment LED integrated with parameter units

DIGITS 3 Rows , 3 digits

ELECTRICAL
3Ø - 4W, 3Ø - 3W, 2Ø - 3W, 1Ø - 2W
CONNECTION
RATED INPUT VOLTAGE 11 to 300V AC (L-N), 19 to 519V AC (L-L)

RATED INPUT CURRENT Nominal 5A (min : 20mA , max : 6A) Nominal 5A (min : 30mA , max : 6A)

RESOLUTION Current & Voltage : Depending on CT & PT primary setting, RPM : 0.1, Run Hour : 0.1hr

ACCURACY Voltage(L-N/L-L/ Average) : ± 0.5% of F.S. ± 2 digits, Current & Average Current : ± 1% of F.S. ± 2 digits, Run Hour : ± 1%, RPM : ± 0.5%, Frequency : ± 0.1 Hz ± 1 digit

CT PRIMARY 5A to 10kA (Programmable for any value)

CT SECONDARY 5A fixed 1 or 5A (Programmable)

PT PRIMARY 100V to 500kV (Programmable for any value)

PT SECONDARY 100 to 500V AC (L-L) (Programmable for any value)

MEASURING Voltage (L-N / L-L) (Individual / Average), Current (I1, I2, I3) (Individual / Average), Frequency, RPM , Run Hour
PARAMETER
SUPPLY VOLTAGE 230V AC ±20% (50/60 Hz), 110V AC ±20% (50/60 Hz) 230V AC ±20% (50/60 Hz)

Terminal Connections Dimensions (All are in mm)


VAF36A / VAF39A-2 VAF36A / VAF39A-2
N
L

99 90.5 91.5

99 50 91.5
5
L1 L Front bezel Side view Panel cutout
L2 O
L3 A
N D
m

Ordering Information
S1 S2 S1 S2 S1 S2 N V1 V2 V3 SUPPLY VOLTAGE
I1 I2 I3
PRODUCT CODE CERTIFICATION
.co

110V AC 230V AC
VAF36A-230-CE RoHS
UL US
VAF36A-110V-CU RoHS C
u

LISTED

VAF39A-2-230V AC ---
ia
ha
en
di
Co

8 www.selec.com DIGITAL PANEL METERS


Voltmeter - Digital

MV15 MV15-DC-200V MV15-AC-20/200V MV205 MV305 MV334-230V


Size : 48 x 96mm Size : 48 x 96mm Size : 48 x 96mm Size : 72 x 72mm Size : 96 x 96mm Size : 96 x 96mm
! True RMS Measurement ! True RMS Measurement ! True RMS Measurement ! True RMS Measurement ! True RMS Measurement ! True RMS Measurement
! 1Ø - 2W ! 1Ø - 2W ! 1Ø - 2W ! 1Ø - 2W ! 1Ø - 2W ! 3Ø - 4W, 3Ø - 3W,
Electrical Network Electrical Network Electrical Network Electrical Network Electrical Network 1Ø - 2W Electrical
FEATURES Network
! K LED for Kilo Indication

DISPLAY 7 segment LED

DIGITS 3 digits 3½ digits 3 digits 4 digits


ELECTRICAL 3Ø - 4W, 3Ø - 3W, 1Ø - 2W
1Ø - 2W
CONNECTION
RATED INPUT 50 to 480V AC (516V max) 50 to 480V AC (516V max)
11 to 300V AC (L-N)
0 to ±200V 0 to 20/200V 19 to 516V AC (L-L)
VOLTAGE
RESOLUTION 1V 0.1 0.01 / 0.1 1V Auto Resolution

ACCURACY ± 0.5% of full scale over rated operating condition ± 0.5% of full range

PT PRIMARY -- 100V - 999kV


PT SECONDARY -- 100V - 500V

SUPPLY VOLTAGE 240V AC ±20% (50/60Hz), 110V AC ±20% (60Hz) 230V AC ±20% (50/60Hz)

Terminal Connections Dimensions (All are in mm)


MV15, MV305 AC Models MV15
INPUT 44.8 46
52

N 1 2 L 3 4 102 50 92
Front bezel 4.5 Side view Panel cutout

MV15 DC Models MV205

INPUT 76 67.5 67.5

N 1 2 L
- 3 4 +
76
Front bezel
3.5
50
Side view
67.5
Panel cutout

MV205 MV305
N L N INPUT V
99 91 92
1 2 4 5 6

99 5 46 92
Front bezel Side view Panel cutout
m

Ordering Information
.co

SUPPLY VOLTAGE SUPPLY VOLTAGE


PRODUCT CODE CERTIFICATION PRODUCT CODE CERTIFICATION
110V AC 230V AC 110V AC 230V AC
MV15 MV15-DC-200mV
u

UL US
MV15-110V-CU RoHS C
LISTED MV15-AC-20/200V
ia

MV15-230V-CE RoHS MV15-AC-200/2000mV


MV15-DC-2V MV205
ha

MV15-DC-20V MV305
UL US
MV15-DC-20V-110V-CU RoHS C
LISTED
MV305-110V
en

MV15-DC-200V MV334-230V
UL US
MV15-DC-200V-110V-CU RoHS C
LISTED
di
Co

9 www.selec.com DIGITAL PANEL METERS


Ammeter - Digital

MA12 MA12-DC-2mA MA12-AC-2/20mA MA202 MA302 MA335-230V AC


Size : 48 x 96mm Size : 48 x 96mm Size : 48 x 96mm Size : 72 x 72mm Size : 96 x 96mm Size : 96 x 96mm

! True RMS Measurement ! True RMS Measurement ! True RMS


! 1Ø - 2W Electrical Network ! 1Ø - 2W Electrical Network Measurement
! CT Primary Programmable Upto 4000A ! K LED for Kilo
FEATURES Indication

DISPLAY 7 segment LED

DIGITS 4 digits 3½ digits 4 digits


ELECTRICAL 3Ø - 4W, 3Ø - 3W, 1Ø - 2W
1Ø - 2W
CONNECTION
INPUT TYPE CT Direct CT
RATED INPUT 5A AC 0 to ± 2mA 5A AC (min : 50mA ; max : 6.2A)
(min : 50mA, max : 6.2A) 0 to 2/20mA
CURRENT
0.001, 0.01, 0.1, 1A
0.001, 0.01, 0.1, 1A (depending upon CT primary settings) Auto resolution depend
RESOLUTION (depending upon 0.001 0.001 / 0.01 upon CT ratio
CT primary settings)
ACCURACY ± 0.5% of full scale
5 to 4000A
1 to 999.0kA
CT PRIMARY (Programmable 5 to 4000A (Programmable in steps)
(Programmable for any value)
in steps)
CT SECONDARY 5A Fixed 5A Fixed 1 or 5A (Programmable)

SUPPLY VOLTAGE 240V AC ±20% (50/60Hz), 110V AC ±20% (60Hz) 230V AC ±20% (50/60Hz)
Part No.

Terminal Connections Dimensions (All are in mm)

MA12, MA302 MA12

AC Models (CT Type) AC Models (Direct Type) 52 44.8 46


P1 P2

INPUT 50
102 92
N 1 2 L S1 3 4 S2 N 1 2 L P1 3 4 P2 4.5
Front bezel Side view Panel cutout

MA202
MA12

DC Models (Shunt Type) DC Models (Direct Type) 76 67.5 67.5


P2 P1
INPUT 76 50 67.5
3.5
Front bezel Side view Panel cutout
N 1 2 L 3 4 + N 1 2 L 3 4 +
MA302

MA202 INPUT
0-5A AC 99 91 92
m

P1 P2
N ~ L
99 5 46 92
1 2 4 5 6 Front bezel Side view Panel cutout
.co

Ordering Information
u

SUPPLY VOLTAGE SUPPLY VOLTAGE


PRODUCT CODE CERTIFICATION PRODUCT CODE CERTIFICATION
ia

110V AC 230V AC 110V AC 230V AC


MA12 MA12-DC-20mA
ha

UL US
MA12-110V-CU RoHS C
LISTED
MA12-DC-200mA
MA12-CE-RoHS RoHS MA12-20A-AC-110V
MA12-AC-2/20mA MA202
en

MA12-AC-200/2000mA MA302
MA12-50mV-DC MA335-230V AC
UL US
MA12-50mV-DC-110V-CU RoHS C
di

LISTED

MA12-DC-2mA
Co

10 www.selec.com DIGITAL PANEL METERS


Ammeter - Digital Voltmeter - Digital

MA501 / MA201 MA2301 MV507 / MV207 MV2307


Size : 48 x 48mm / 72 x 72mm Size : 72 x 72mm Size : 48 x 48mm / 72 x 72mm Size : 72 x 72mm
! True RMS Measurement ! True RMS Measurement ! True RMS Measurement ! True RMS Measurement
! 1Ø - 2W Electrical Network ! 3Ø - 4W Electrical Network ! 1Ø - 2W Electrical Network ! 3Ø - 4W, 3Ø - 3W
! Analog Style Bargraph Indication ! Analog Style Bargraph Indication ! Analog Style Bargraph Indication Electrical Network
FEATURES ! Analog Style Bargraph Indication
! CT Primary Programmable Upto ! CT Primary Programmable Upto 5000A
5000A ! Page Selection Using Selector Switch ! Page Selection using Selector Switch

DISPLAY LCD (with analog style bargraph indication)

DIGITS 4 Digits 3 Digits

ELECTRICAL
1Ø - 2W 3Ø - 4W 1Ø - 2W 3Ø - 4W, 3Ø - 3W
CONNECTION
RATED INPUT VOLTAGE -- 50 to 480V AC (max : 516V)

RATED INPUT CURRENT 5A AC (min : 50mA ; max : 6.2A) --

RESOLUTION 0.001, 0.01, 0.1, 1A (Depending on CT primary settings) 1V

ACCURACY ± 0.5% of F.S. ± 0.5% of F.S. Over rated operating condition

CT PRIMARY 5 to 5000A (Programmable in steps) --

CT SECONDARY 5A Fixed --

SUPPLY VOLTAGE 240V AC ±20% (50/60Hz), 110V AC ±20% (60Hz)

Terminal Connections Dimensions (All are in mm)


MA501 MA201 MA501 / MV507
S1

L
INPUT : 0-5A AC

1 6 7 8
N
L INPUT 45.5 46.5
2 7 0 - 5A AC 52

3 8
S2

N S2 S1 68.5 46.5
52 3.5
4 9 4 5 6
Front bezel Side view Panel cutout
5 10

MA201 / MA2301 / MV207 / MV2307


MA2301
7 8
N
L 67.5 67.5
76
INPUT

76 50 67.5
I1 I2 I3 3.5
S1 S2 S1 S2 S1 S2 Front bezel Side view Panel cutout
1 2 3 4 5 6
m

Ordering Information
MV507 MV207
L SUPPLY VOLTAGE
PRODUCT CODE CERTIFICATION
.co

1 6
50-480V AC

7 8 110V AC 230V AC
INPUT

N
2 7 L MA501
3 8 MA501-110V-CU RoHS C UL US
LISTED
N
u

INPUT MA501-230V-CE RoHS


4 9 50-480V AC
N V MA201
ia

5 10 4 5 6
MA201-110V-CU RoHS C UL US
LISTED

MA201-230V-CE RoHS
ha

MA2301
MV2307
MA2301-110V-CU RoHS C UL US
LISTED
7 8
MA2301-230V-CE
en

N RoHS
L
MV507
L1 L
L2 O MV507-110V-CU RoHS C UL US
LISTED
di

L3 A
N D MV507-230V-CE RoHS
N V1 V2 V3
1 2 3 4 5 6
MV207
MV2307
Co

MV2307-110V-CU RoHS C UL US
LISTED

MV2307-230V-CE RoHS

11 www.selec.com DIGITAL PANEL METERS


Frequency Meter - Digital Power Factor Meters - Digital

MF16 MF216 MF316 MP14 MP214 MP314


Size : 48 x 96mm Size : 72 x 72mm Size : 96 x 96mm Size : 48 x 96mm Size : 72 x 72mm Size : 96 x 96mm
! 4 digits 7 segment LED ! 4 digits 7 segment LED ! 4 digits 7 segment ! 4 digits 7 segment LED ! 4 digits 7 segment ! 4 digits 7 segment LED
Display Display LED Display Display LED Display Display
! 0.01 Resolution ! 0.01 Resolution ! 0.01 Resolution ! 0.001 Resolution ! 0.001 Resolution ! 0.001 Resolution
FEATURES

DISPLAY 7 segment LED

DIGITS 4 digits
ELECTRICAL
1Ø - 2W
CONNECTION
RESOLUTION 0.01Hz 0.001

ACCURACY ± 0.05Hz ± 0.5% ± 1 digit

MEASUREMENT
45 to 65Hz -1.000 to +1.000
RANGE
SUPPLY VOLTAGE 240V AC ±20% (45 to 65Hz), 110V AC ±20% (45 to 65Hz) 240V AC ±20% (50/60Hz), 110V AC ±20% (50/60Hz)

Terminal Connections Dimensions (All are in mm)


MF16 / MF216 / MF316 MF16 / MP14

52 44.8 46
N L
1 2 102 50 92
Front bezel
4.5 Panel cutout
Side view

MF216 / MP214

MP14 / MP214 / MP314 76 67.5 67.5

P1 P2 L 76 50
O 3.5 67.5
A Front bezel Side view Panel cutout
D
N 1 2 L S2 3 4 S1 MF316 / MP314

99 91 92

99 5 46 92
Front bezel Side view Panel cutout

Ordering Information
m

SUPPLY VOLTAGE SUPPLY VOLTAGE


PRODUCT CODE CERTIFICATION PRODUCT CODE CERTIFICATION
110V AC 230V AC 110V AC 230V AC
.co

MF16 MP14
UL US UL US
MF16-110V-CU RoHS C
LISTED MP14-110V-CU RoHS C
LISTED

MF216 MP214
u

MF316 MP314
ia
ha
en
di
Co

12 www.selec.com DIGITAL PANEL METERS


Ammeter - Analog Voltmeter - Analog

New New

AM - I AM - V
Size : 72 x 72mm / 96 x 96mm Size : 72 x 72mm / 96 x 96mm
! Scale Interchangeability ! Near Linear Scale
! Near Linear Scale ! Knife Edge Pointer
! Knife Edge Pointer ! Glass filled Nylon / Polycarbonate Housing
FEATURES ! Glass filled Nylon / Polycarbonate Housing ! Easy Installation / Termination
! Easy Installation / Termination

MEASURING
AC Current AC Voltage
PARAMETER
POINTER 0 to 90º
DEFLECTION
SCALE
Near Linear above 10% of Nominal full scale value
CHARACTERISTICS

SCALE LENGTH 72 X 72mm : 63 mm / 96 X 96mm : 97 mm

MEASURING -- 0 to 300V & 0 to 500V


VOLTAGE RANGE
MEASURING 0 to 5A (CT Secondary) , Suppress scale : 0 to 5 / 30A(CT Secondary) --
CURRENT RANGE

ACCURACY Class 1.5

FREQUENCY 45 to 65Hz

Terminal Connections Dimensions (All are in mm)


AM - I / AM - V
AM - I
a 1
AC Current(Direct connection)
b

AC Current(CT connection) h
f
d
g
e

Product 72x72 96x96


Dimensions (in mm)
a 72 96
AM - V
b 74.50 98.50 Optional parts:
AC Voltage(Direct connection)
m

c 67 90.50 1. Back cover


d 50 50
.co

e 60 60
f 5.50 5.50
u

g 8 8
Ordering Information
ia

30/5A
h 68 92
SCL AM I 2/3 to 6S
4000/5A
ha

AM V 2/3 N/L
6S : 6 times suppressed scale. Keep this cell blank if suppression not required
en

N : 300V L - N, L : 500V L - L (For Voltmeters). Select required available current rating from datasheet (For Ammeters)
2 : 72 x 72 mm housing, 3 : 96 x 96 mm housing
di

I : Ammeter, V : Voltmeter
Example:-
AM : Analog Meter
Co

Separate dial plate Ammeter Voltmeter


SCL : Scale (to order only scale).
Keep it blank if whole product is required. SCL-AM-I-2-30/5A AM-I-2-30/5A AM-V-2-N
SCL-AM-I-2-30/5A-6S AM-I-2-30/5A-6S AM-V-2-L

13 www.selec.com ANALOG PANEL METERS


New
New New

SPCT RCT TWCT


! Use with different Bus Bar Size ! Selable Terminal / Wire type Output ! Terminal Output
! Panel Mount / Din Rail Mount (Require optional ! Panel Mount ! Accuracy : Class 0.5 to 5
accessory) ! Accuracy : Class 1 to 5
FEATURES ! Accuracy : Class 0.5 to 5

RATED PRIMARY
30 to 4000A 30 to 600A 30 to 1600A
RATING
RATED SECONDARY
5A
OUTPUT

RATED BURDEN 1 to 15VA 1.5 to 5VA 1.5 to 10VA

ACCURACY 0.5 to 5 1 to 5 0.5 to 5


OPERATING AC 50/60Hz
FREQUENCY

SYSTEM VOLTAGE 720V maximum

APPLICABLE
IEC 61869-2
STANDARD

Dimensions (All are in mm)


SPCT-62/22 ,62/30, 62/40 SPCT-62/40 SPCT-100/60
41 52 60.50
31 50.50
46
20.50
16
50.50

30.50 120.4

12.50 31 51
80.5
11 21 30.50
43
6

6 41
82
73
101
35 42
67 62 SPCT-140/100 104
57 79

86
31
SPCT-62/22 SPCT-62/30 26
21
11.5

31 41 51 61 71 81
30.5
155
m

22
11.5 21 26 31
47.54
6
.co

35
57
65
73
42 41 81
62 103
42 73 121
62 140
u

RCT-T-D30 RCT-T-D50 RCT-W-D30 RCT-W-D50


ia
ha
en
116
50
30
96

di

82 30 102 50

50 40
Co

50
35 74 40
45 64 74 64
35 45

14 www.selec.com CURRENT TRANSFORMERS


Dimensions (All are in mm)
TWCT PRODUCT A B C D
TWCT-T-D35 35 70 45 80
TWCT-T-D55 150/5 A 55 90 35 100
B D
A TWCT-T-D55 55 90 25 100
TWCT-T-D65 65 95 30 105
TWCT-T-D110 110 35 35 145
C
TWCT-T-D120 120 155 25 165

Ordering Information
SPCT RCT
NO OF
WIRE APERTURE CURRENT BURDEN ACCURACY WIRE APERTURE CURRENT BURDEN ACCURACY PRIMARY
PRODUCT CODE PRODUCT CODE IN VA CLASS
In mm RATIO IN VA CLASS In mm RATIO TURNS
SPCT 62/22 30/5 A VA 1 CL 5 DIA 22 30/5 1 5 RCT-T-D30-30/5 A VA 1.5 CL5 DIA 30 30/5 1.5 5 ---
SPCT 62/30 50/5 A VA 1 CL 3 30x10 50/5 1 3 RCT-T-D30-30/5 A VA 5 (2T) CL5 DIA 30 30/5 5 5 2
SPCT 62/30 50/5 A VA 1.5 CL 3 30x10 50/5 1.5 3 RCT-T-D30-50/5 A VA 5 CL5 DIA 30 50/5 5 5 ---
SPCT 62/30 75/5 A VA 1 CL 3 30x10 75/5 1 3 RCT-T-D30-75/5 A VA 5 CL5 DIA 30 75/5 5 5 ---
SPCT 62/30 75/5 A VA 3 CL 3 30x10 75/5 3 3 RCT-T-D30-100/5 A VA 5 CL1 DIA 30 100/5 5 1 ---
SPCT 62/30 100/5 A VA 1 CL 1 30x10 100/5 1 1 RCT-T-D30-150/5 A VA 5 CL1 DIA 30 150/5 5 1 ---
SPCT 62/30 100/5 A VA 3 CL 1 30x10 100/5 3 1 RCT-T-D50-200/5 A VA 5 CL1 DIA 50 200/5 5 1 ---
SPCT 62/40 100/5 A VA 1 CL 1 40x10 100/5 1 1 RCT-T-D50-250/5 A VA 5 CL1 DIA 50 250/5 5 1 ---
SPCT 62/40 125/5 A VA 1 CL 1 40x10 125/5 1 1 RCT-T-D50-300/5 A VA 5 CL1 DIA 50 300/5 5 1 ---
SPCT 62/40 150/5 A VA 1.5 CL 1 40x10 150/5 1.5 1 RCT-T-D50-400/5 A VA 5 CL1 DIA 50 400/5 5 1 ---
SPCT 62/40 150/5 A VA 3 CL 1 40x10 150/5 3 1 RCT-T-D50-500/5 A VA 5 CL1 DIA 50 500/5 5 1 ---
SPCT 62/40 160/5 A VA 1.5 CL 1 40x10 160/5 1.5 1 RCT-T-D50-600/5 A VA 5 CL1 DIA 50 600/5 5 1 ---
SPCT 62/40 200/5 A VA 2.5 CL 0.5 40x10 200/5 2.5 0.5 RCT-W-D30-30/5 A VA 1.5 CL5 DIA 30 30/5 1.5 5 ---
SPCT 62/40 200/5 A VA 3 CL 1 40x10 200/5 3 1 RCT-W-D30-30/5 A VA 5 (2T) CL5 DIA 30 30/5 5 5 2
SPCT 62/40 250/5 A VA 2.5 CL 0.5 40x10 250/5 2.5 0.5 RCT-W-D30-50/5 A VA 5 CL5 DIA 30 50/5 5 5 ---
SPCT 62/40 250/5 A VA 3 CL 1 40x10 250/5 3 1 RCT-W-D30-75/5 A VA 5 CL5 DIA 30 75/5 5 5 ---
SPCT 62/40 300/5 A VA 3 CL 0.5 40x10 300/5 3 0.5 RCT-W-D30-100/5 A VA 5 CL1 DIA 30 100/5 5 1 ---
SPCT 62/40 400/5 A VA 3.75 CL 0.5 40x10 400/5 3.75 0.5 RCT-W-D30-150/5 A VA 5 CL1 DIA 30 150/5 5 1 ---
SPCT 62/40 400/5 A VA 5 CL 1 40x10 400/5 5 1 RCT-W-D50-200/5 A VA 5 CL1 DIA 50 200/5 5 1 ---
SPCT 100/60 500/5 A VA 5 CL 1 60x12 500/5 5 1 RCT-W-D50-250/5 A VA 5 CL1 DIA 50 250/5 5 1 ---
SPCT 100/60 600/5 A VA 5 CL 0.5 60x12 600/5 5 0.5 RCT-W-D50-300/5 A VA 5 CL1 DIA 50 300/5 5 1 ---
SPCT 100/60 600/5 A VA 7.5 CL 1 60x12 600/5 7.5 1 RCT-W-D50-400/5 A VA 5 CL1 DIA 50 400/5 5 1 ---
SPCT 100/60 800/5 A VA 10 CL 0.5 60x12 800/5 10 0.5 RCT-W-D50-500/5 A VA 5 CL1 DIA 50 500/5 5 1 ---
SPCT 100/60 1000/5 A VA 15 CL 0.5 60x12 1000/5 15 0.5 RCT-W-D50-600/5 A VA 5 CL1 DIA 50 600/5 5 1 ---
SPCT 100/60 1200/5 A VA 15 CL 0.5 60x12 1200/5 15 0.5
SPCT 140/100 800/5 A VA 15 CL 0.5 100x30 800/5 15 0.5 TWCT
SPCT 140/100 1000/5 A VA 15 CL 0.5 100x30 1000/5 15 0.5 WIRE APERTURE CURRENT BURDEN ACCURACY
PRODUCT
PRODUCT CODE
CODE
SPCT 140/100 1200/5 A VA 15 CL 0.5 100x30 1200/5 15 0.5 In mm RATIO IN VA CLASS
SPCT 140/100 1250/5 A VA 15 CL 0.5 100x30 1250/5 15 0.5 TWCT-T-D35 30/5 A VA 1.5 CL 5 DIA 35 30/5 1.5 5
m

SPCT 140/100 1500/5 A VA 15 CL 0.5 100x30 1500/5 15 0.5 TWCT-T-D35 50/5 A VA 5 CL 5 DIA 35 50/5 5 5
SPCT 140/100 1600/5 A VA 15 CL 0.5 100x30 1600/5 15 0.5 TWCT-T-D35 75/5 A VA 5 CL 5 DIA 35 75/5 5 5
.co

SPCT 140/100 2000/5 A VA 15 CL 0.5 100x30 2000/5 15 0.5 TWCT-T-D35 100/5 A VA 5 CL 1 DIA 35 100/5 5 1
SPCT 140/100 2500/5 A VA 15 CL 0.5 100x30 2500/5 15 0.5 TWCT-T-D35 150/5 A VA 5 CL 1 DIA 35 150/5 5 1
SPCT 140/100 3000/5 A VA 15 CL 0.5 100x30 3000/5 15 0.5 TWCT-T-D55 150/5 A VA 5 CL 1 DIA 55 150/5 5 1
u

SPCT 140/100 3500/5 A VA 15 CL 0.5 100x30 3500/5 15 0.5 TWCT-T-D55 200/5 A VA 5 CL 1 DIA 55 200/5 5 1
ia

SPCT 140/100 4000/5 A VA 15 CL 0.5 100x30 4000/5 15 0.5 TWCT-T-D55 250/5 A VA 5 CL 1 DIA55 250/5 5 1
TWCT-T-D55 300/5 A VA 5 CL 1 DIA 55 300/5 5 1
ha

TWCT-T-D55 400/5 A VA 5 CL 1 DIA 55 400/5 5 1


TWCT-T-D65 500/5 A VA 5 CL 1 DIA 65 500/5 5 1
en

TWCT-T-D65 600/5 A VA 5 CL 1 DIA 65 600/5 5 1


TWCT-T-D110 800/5 A VA 10 CL 0.5 DIA 110 800/5 10 0.5
di

TWCT-T-D110 1000/5 A VA 10 CL 0.5 DIA 110 1000/5 10 0.5


TWCT-T-D120 1000/5 A VA 10 CL 0.5 DIA 120 1000/5 10 0.5
Co

TWCT-T-D120 1200/5 A VA 10 CL 0.5 DIA 120 1200/5 10 0.5


TWCT-T-D120 1600/5 A VA 10 CL 0.5 DIA 120 1600/5 10 0.5

15 www.selec.com CURRENT TRANSFORMERS


New

APFC148 : With 3 CT sensing APFC147 : With 1 CT sensing APFC347 : With 1 CT sensing


Size : 144 x 144mm Size : 144 x 144mm Size : 96 x 96mm

! With Built In Multifunction Meter ! Auto Detection of Capacitor Bank Values ! Auto Detection of Capacitor Bank Values
! Dual Colour Backlight for Alarm Indication ! Configurable Alarm Settings ! Configurable Alarm Settings
! Auto Detection of Capacitor Bank Values ! Dual Password Protection ! Dual Password Protection
FEATURES ! Configurable Alarm Settings
! Dual Password Protection
! RS485 Communication MODBUS RTU Protocol
*(Only for 12 stage variant)
DISPLAY LCD with Dual Colour Backlight 7 segment LED
DIGITS 3 Rows, 4 Digits to show electrical parameters 1 Row, 4 Digits to show Power Factor
ELECTRICAL
3Ø - 4W, 3Ø - 3W, 2Ø - 2W, 1Ø - 2W 2Ø - 2W, 1Ø - 2W
CONNECTION
RATED INPUT VOLTAGE 11 to 300V AC (L-N), 50 to 520V AC (L-L) 40 to 300V AC (L-N), 50 to 530V AC (L-L)

RATED INPUT CURRENT Nominal 5A AC (min : 11mA ; max : 6A) Nominal 5A AC (min : 50mA ; max : 6A)

POWER CONSUMPTION 15VA max 7VA max.

FREQUENCY 45 to 65Hz

MEASUREMENT RANGE Power Factor : 0.8 Lag to 0.8 Lead


Over / Under Voltage, Over / Under Compensation, Over / Under Voltage, Over / Under Compensation,
ALARM SETTINGS CT Polarity Error, THDI error, CT Polarity Error, Current Absent Indication
Step Error, Over Temperature, Fan Setting, No voltage
PHASE COMPENSATION 0°, 90°, 120°, 210°, 240°, 330°
Power Factor : ± 0.01, Voltage (L-N/L-L),
Current : ±0.5% of full scale,
ACCURACY Frequency : For L-N >20V, For L-L >35V : ±0.1% of full scale, Power Factor : ±0.01
Power (kW, kVA, kVAr) : 1%, Energy (kWh, kVAh, kVArh) : Class 1
Temperature : ±3°C of full scale

CT PRIMARY 1 / 5A to 9999A (Programmable for any value)

CT SECONDARY 1 or 5 A (Programmable)

PT PRIMARY 100V to 500kV (Programmable for any value) --

PT SECONDARY 100 to 500V (Programmable for any value) --


1 to 8 / 12 / 14*
STEPS th th
*(FAN & ALARM output can be used as 13 & 14 step) 3 to 8/12 3 to 8

RELAY CONTACT 5A @ 250V AC


SWITCHING PROGRAM Automatic / Linear / Rotational
STEP TIME 1 to 999s

DISCHARGE TIME 1 to 9999s 1 to 999s


CONTROL MODE Automatic / Manual
CONTROL SENSITIVITY 55 to 100%
m

AUTO INITIALIZATION Yes / No


.co

RS485 Communication MODBUS RTU Protocol --


COMMUNICATION *(Only for 12 stage variant)
SUPPLY VOLTAGE 90 to 550V AC, 50/60Hz 85 to 270V AC, 50/60Hz
u

Ordering Information
ia

OUTPUT
PRODUCT CODE SUPPLY VOLTAGE CERTIFICATION
ha

STEPS COMMN. (RS485)


APFC148-312-90/550V-CE-RoHS 90 to 550V AC, 50 / 60Hz 12 RoHS
en

APFC148-308-90/550V-CE-RoHS 90 to 550V AC, 50 / 60Hz 8 --- RoHS

APFC147-112-90/550V-CE-RoHS 90 to 550V AC, 50 / 60Hz 12 --- RoHS in process

APFC147-108-90/550V-CE-RoHS 90 to 550V AC, 50 / 60Hz 8 ---


di

RoHS in process

APFC347-108-230V-CE-RoHS 85 to 270V AC, 50 / 60Hz 8 --- RoHS in process


Co

16 www.selec.com AUTOMATIC POWER FACTOR CONTROLLERS


Terminal Connections

APFC148 : With 3 CT sensing APFC147: With 1 CT sensing


Where n - 12 For 12 stage variant. Where n - 12 For 12 stage variant.
8 For 8 stage variant. 8 For 8 stage variant.
*Valid Only For 12 stage variant.

Aux. Supply
*
RS485

Aux. Supply
N L1 L2 L3
T2 T1

N L1 L2 L3
C C
V3 V3 1 R1
C1 C1 2 R2 Um1 1
1 R1 V2 V2 3 R3
2 R2 2
4 R4 Um2
3 R3 V1 V1
5 R5
4 R4 N N
6 R6 S1 1
5 R5
7 R7 S2 2
6 R6 S1 S1
I3 8 R8
7 R7 CBn CB1 S2 S2

8 R8 S1 S1
I2
9 R9 S2 S2
9 R9
S1 S1
I1 10 R10
S2 S2
11 R11 C C
10 R10
n Rn
11 R11 C
ALM Cn C1 NO
n Rn NO NO
50-250VAC

C
DI FAN
NO TO LOAD

TO LOAD

APFC347: With 1 CT sensing

Where n - 8 For 8 stage variant.

N L Um1 Um2 S1 S2

L L3
O L2
A L1
D N

CBn CB1
m

ALM
C2 NO Rn R7 R6 R5 R4 R3 R2 R1 C1
u .co
ia

Dimensions (All are in mm)


ha

APFC347 APFC148 & APFC147


en

90.5 91.5 136.5 138


99 144
di

138
Co

99 55 91.5 144 50
3 5
Front bezel Side view Panel cutout Front bezel Side view Panel cutout

17 www.selec.com AUTOMATIC POWER FACTOR CONTROLLERS


PROTECTION RELAYS

Types : Analog / Digital Protection Relays


Line Monitoring Relay Earth Leakage Relay
Phase Sequence Relay Earth Fault Relay
Voltage Protection Relay Motor Protection Relay
Current Protection Relay Water Level Controller

Applicable EMI / EMC Standards


Product Standard :
Products Electromagnetic Compatibility
Phase Sequence IEC60947-5-1
Voltage Protection IEC61326-1
Current Protection IEC60947-1
Earth Leakage Current IEC60947-2
Earth Fault Relay IEC60947-5-1
Water Level Controller IEC60947-5-1

Category Standards Compliance

ESD Immunity
m

IEC 61000-4-2 Level III


+/- 2 kV common mode,
Surge Immunity IEC 61000-4-5
.co

+/- 1 kV differential mode


Level III, 80 to 1000MHz
Radiated Susceptibility IEC 61000-4-3 Level II, 1.4GHz to 2GHz
u

Level I, 2GHz to 2.7GHz


ia

Conducted Susceptibility IEC 61000-4-6 Level III

Dips : 0% residual voltage / 1 cycle (Criteria B.),


ha

Voltage Dips and 40% residual voltage / 10 cycles 50 Hz / 12 cycles 60 Hz (Criteria C)


IEC 61000-4-11
Interruptions 70% residual voltage / 25 cycles 50 Hz / 30 cycles 60 Hz (Criteria C)
en

Interruptions : 0% residual voltage / 250 cycles 50 Hz / 300 cycles 60 Hz (Criteria C)

Conducted Emission CISPR-11


di

Radiated Emission CISPR-11


Co

Electrical Fast Transient IEC 61000-4-4 Level III

Note : Above standards are applicable only for CE certified Analog / Digital Protection Relays

18 www.selec.com
Phase Sequence Relays

600PSR 800PSR
Size : 17.5 x 90mm Size : 22.5 x 76.85mm

! Din Rail Mount ! Din Rail Mount


! Phase Failure ! Phase Failure
! Phase Sequence ! Phase Sequence
FEATURES
! Phase Asymmetry ! Phase Asymmetry
! Space Saving Design

Phase Asymmetry,
Phase Failure Trip :- <154V AC (L-L)
MODES Phase Asymmetry :- 30V Fixed
Reset : Auto Reset

TIME RANGES Power On Delay :- 200msec

ACCURACY Trip accuracy : ±10V


OUTPUT CONTACT 1 C/O SPDT

OUTPUT RATING NC : 3A @ 250V AC, NO : 5A @ 250V AC


ELECTRICAL
3Ø - 3W
CONNECTION
OPERATING VOLTAGE 154 to 500V AC (L-L)

Terminal Connections Dimensions (All are in mm)

600PSR 800PSR 600 SERIES


44

L1
L2 L1
L3 L2
45

67.5

35.3
90
L3
L1
L3 L2 L1
17.5
R L2 L3
60

800 SERIES

15 22.5
100.5
16 18 16
15 18
m

NC NO COM NO
76.85

35
.co

NC
COM
u

105.5
ia
ha

Ordering Information
en

PRODUCT CODE OPERATING RANGE CERTIFICATION


di

600PSR ---
154 to 500V AC
600PSR-CE RoHS
Co

600PSR-165/300-CU 165 to 300V AC RoHS C UL US


LISTED

800PSR 154 to 500V AC ---

19 www.selec.com LINE MONITORING RELAY


Voltage Protection Relays

New

600VPR-310/520V 600VPR-170/290V 600VPR-1-180/300V 800VPR-3


Size : 17.5 x 90mm Size : 17.5 x 90mm Size : 17.5 x 90mm Size : 22.5 x 76.85mm

! Din Rail Mount ! Din Rail Mount ! Din Rail Mount


! Under Voltage ! Under Voltage ! Under Voltage
! Over Voltage ! Over Voltage ! Over Voltage
FEATURES ! Phase Sequence ! Space Saving Design ! Phase Sequence
! Phase Failure ! Phase Failure
! Space Saving Design

Under Voltage trip : Under Voltage trip : Under Voltage trip : Under voltage trip :
310 to 405V AC (-25% to -2.5% of 415V AC) 170 to 224V AC (-25% to -2.5% of 230V AC) 180 to 234V AC (-25% to -2.5% of 240V AC) 310 to 405V AC (-25% to -2.5% of 415V AC)
Over Voltage trip : Over Voltage trip : Over Voltage trip : Over Voltage trip :
425 to 520V AC (+2.5% to +25% of 415V AC) 236 to 290V AC (+2.5% to +25% of 230V AC) 246 to 300V AC (+2.5% to +25% of 240V AC) 425 to 520V AC (+2.5% to +25% of 415V AC )
MODES
Phase Sequence : YES Phase Sequence : YES Reset : Auto Reset Phase Sequence : YES
Phase Failure : YES Phase Failure : YES Phase Failure : YES
Reset : Auto Reset Reset : Auto Reset Reset : Auto Reset

Trip time delay : 0.2 to 10 sec (For under voltage and over voltage) Trip time delay : 0.2 to 10 sec (For under Trip Delay : 0 to 10s (For under voltage and
: Instantaneous (For phase failure & phase sequence) voltage and over voltage) over voltage)
TIME RANGES : Instantaneous (For phase failure
Power On Delay : 400msec Power On Delay : 400msec
& phase sequence)
Trip Voltage : ±0.5% of F.S
ACCURACY Trip Time : ±5% of F.S
OUTPUT CONTACT 1 C/O SPDT
NC: 3A @ 250V AC NC: 5A @ 250V AC, (Resitive Load)
OUTPUT RATING NO: 5A @ 250V AC NO: 5A @ 250V AC
ELECTRICAL
3Ø - 3W 1Ø - 2W 3Ø - 3W
CONNECTION
OPERATING VOLTAGE 310 to 520V AC (L-L) 170 to 290V AC (L-L) 180 to 300V AC(L-N) 310 to 520V AC (L-L)

Terminal Connections Dimensions (All are in mm)


600VPR-310/520V, 600VPR-1-180/300V 800VPR-3 600 SERIES
600VPR-170/290V 44
45

67.5

35.3
90
N L
17.5

60

800 SERIES
m

22.5
100.5
.co
76.85

35
u

Ordering Information
ia

PRODUCT CODE OPERATING RANGE CERTIFICATION


ha

600VPR-310/520 -- 105.5
310 to 520V AC
600VPR-310/520-CE RoHS
en

UL US
600VPR-170/290-CU 170 to 290V AC RoHS C
LISTED

600VPR-1-180/300 --
di

180 to 300V AC
600VPR-1-180/300-CE RoHS
Co

800VPR-3 310 to 520V AC --

20 www.selec.com LINE MONITORING RELAY


Voltage Protection Relays

900VPR-2 900VPR-BL-U
Size : 35 x 90mm Size : 35 x 90mm

! Din Rail Mount ! Din Rail Mount


! Monitors Under Voltage, Over Voltage, Under Frequency, Over ! Monitors Under Voltage, Over Voltage, Under Frequency, Over Frequency,
Frequency, Phase Asymmetry, Phase Failure and Phase Sequence Phase Asymmetry, Phase Failure, Neutral Failure and Phase Sequence
FEATURES
! True RMS Measurement ! True RMS Measurement
! Adjustable Switching Hysteresis ! Adjustable Switching Hysteresis
! Two Separate Alarm Relays ! Two Alarm Relays With NO or NC Operation selectable
MEASUREMENTS Under / Over Voltage, Under / Over Frequency, Phase Asymmetry, Phase Failure, Phase Sequence, (Neutral Failure applicable only for 900VPR-BL-U)

DISPLAY 3 digit LCD 3 digit LCD with backlight

ALARM INDICATIONS Trip


ELECTRICAL
3Ø - 3W, 3Ø - 4W
CONNECTION
Under / Over Voltage : 280 to 520V AC L-L (for 3Ø - 3W system) Under / Over Voltage : 85 to 500V AC L-L (for 3Ø - 3W system)
TRIP SETTING 160 to 300V AC L-N (for 3Ø - 4W system) 50 to 288V AC L-N (for 3Ø - 4W system)
Under / Over Frequency : 45 to 65Hz, Voltage Asymmetry : 5.0 to 99.9% Under / Over Frequency : 45 to 65Hz, Phase Asymmetry : 5.0 to 30.0%
Power ON Delay : 2 to 99.9sec Power ON Delay : 0.5 to 300sec
Trip Time Delay : 0 to 99.9sec Trip Time Delay : 0 to 300sec
TRIP TIME SETTING Delay on Release : 0 to 99.9sec Recovery Time Delay : 0 to 300sec
Response Time : <200ms Response Time : <120ms

HYSTERESIS Voltage : 1.0 to 99.0V, Frequency : 0.2 to 2Hz, Asymmetry : 2 to 20% Voltage : 1.0 to 40V, Frequency : 0.1 to 2Hz, Asymmetry :2 to 20%

RESOLUTION Voltage : 1V, Frequency : 0.1Hz


Voltage : ±1% of set value, Frequency : ±0.3Hz, Voltage : ±1% of set value ±2 digits, Frequency : ±0.5% ± 1 digits,
ACCURACY Time (Recovery Time, Trip delay, Power on delay) : ±5% of setting +200ms Time (Recovery Time, Trip delay, Power on delay) : ±5% of Setting +120ms

OUTPUT CONTACT 2 x 1 C/O SPDT

RELAY RATING NO : 5A @ 250V AC ; NC : 3A @ 250V AC (Res.)

Self Powered, Operating Voltage : 280 to 520V AC (L-L)


SUPPLY VOLTAGE : 160 to 300V AC (L-N) 85 to 270V AC / DC

FREQUENCY 45 to 65Hz
POWER CONSUMPTION 30VA max. 4VA max.

Terminal Connections Dimensions (All are in mm)


900VPR-2 900VPR-BL-U 900 SERIES 35
RELAY 1
RELAY 1
15 18 16
15 18 16 COM1 NO1 NC1
COM1 NO1 NC1
67.50
90

45
90

RELAY 2
m

RELAY 2
28 25 26
.co

26 28 25 NO2 COM2 NC2


NC2 NO2 COM2
70.50
u
ia

L2 L3 N Ordering Information
L2 L3
ha

PRODUCT CODE OPERATING RANGE CERTIFICATION


900VPR-2-280/520V
L1 A2 A1
en

N L1 900VPR-2-280/520V-CE 280 to 520V AC RoHS


~- Aux ~
+
900VPR-2-280/520V-CU RoHS C UL US
LISTED
AC/DC
di

900VPR-BL-U-CE 85 to 270V AC / DC RoHS


Co

21 www.selec.com LINE MONITORING RELAY


Voltage Protection Relays

VPRA2M
Size : 35 x 90mm

! Din Rail Mount


! Monitors Under Voltage, Over Voltage
! Monitors Phase Asymmetry,Phase Failure,Phase Sequence
FEATURES ! True RMS Measurement
! Adjustable Over and Under Voltage Trip Level
! Adjustable Operate Time & Trip Time Delay
! Auto Reset
MEASUREMENT Under Voltage, Over Voltage, Phase Failure, Phase Sequence, Phase Asymmetry

LED indications for Power ON, Phase Failure, Under Voltage,


DISPLAY Over Voltage, Phase Sequence, Phase Asymmetry
ELECTRICAL
1Ø - 2W, 3Ø - 4W
CONNECTION
Under Voltage : 55 to 95% of Un [127 to 219V AC (L-N)]
TRIP SETTING Over Voltage : 105 to 125% of Un [242 to 288V AC (L-N)]
Phase Asymmetry : > 10%

Power ON Delay : 0 to 15sec, Trip Time Delay : 0 to 15sec


TRIP TIME SETTING Recovery Time Delay : 5sec ± 200ms, L1 / Neutral Failure trip delay <200msec,
Phase sequence trip delay <250msec

HYSTERESIS Voltage : 7V (±2V) of trip voltage


Trip Setting Accuracy : ±5% of F. S.
ACCURACY Time Setting Accuracy : ±10% of F. S.

OUTPUT CONTACT 2 C/O DPDT

RELAY RATING NO, NC : 5A @ 250V AC (Res.) / 28V DC

SUPPLY VOLTAGE Self powered, Nominal Input Voltage (Un) : 230V AC (L-N), Operating Voltage : 127 to 288V AC (L-N)

FREQUENCY 48 to 63Hz
POWER
5VA max
CONSUMPTION

Terminal Connections Dimensions (All are in mm)


VPRA2M VPRA2M

26 25 28 16 15 18 35

COM2 COM1
NC2 NC1
NO2 NO1
45
90

67.5

N L3 L2 P L1
.co

Note: Short L1 and P for 1Ø - 2 Wire connection

60
u
ia

Ordering Information
ha

PRODUCT CODE OPERATING RANGE CERTIFICATION


VPRA2M
en

127 to 288V AC
VPRA2M-CE RoHS
di
Co

22 www.selec.com LINE MONITORING RELAY


Current Protection Relays

900CPR-1 900CPR-3 900CPR-1-BL-U


Size : 35 x 90mm Size : 35 x 90mm Size : 35 x 90mm

! Din Rail Mount ! Din Rail Mount ! Din Rail Mount


! Under Current & Over Current Protection for 1Ø ! Under Current & Over Current Protection for ! Under Current & Over Current Protection for 1Ø
system 1Ø & 3Ø system system
FEATURES ! True RMS Measurement ! True RMS Measurement
! True RMS Measurement
! One Alarm Relay with NC or NO operation ! One Alarm Relay with NC or NO operation ! Two Alarm Relay with NC or NO operation

MEASUREMENTS Under Current, Over Current (Current Asymmetry applicable only for 900CPR-3)

DISPLAY 3 digit LCD 3 digit LCD with backlight

ALARM INDICATIONS Trip

ELECTRICAL
1Ø - 2W 1Ø - 2W, 3Ø - 3W, 3Ø - 4W 1Ø - 2W
CONNECTION
CT SETTING CT Primary : 1A/5A - 999A, CT Secondary : 1A / 5A (selectable)

TRIP SETTING Under Current : 0-999A, Over Current : 0.5 to 1.19kA, (Current Asymmetry : 5.0 to 99.9% applicable only for 900CPR-3)

Power ON Delay : 0.5 to 99.9sec


Trip Time Delay : 0 to 99.9sec
TRIP TIME SETTING Recovery Time Delay : 0 to 99.9sec
Response Time : < 200ms

HYSTERESIS Current : 0.1 to 99.9A


RESOLUTION Current : 0.01, 0.1, 1A, 0.01kA (Depends on CT setting)

Current : ±1% of Setting ± 2 digits,


ACCURACY Time (Recovery Time, Trip delay, Power on delay) : ±5% of setting +200ms

OUTPUT CONTACT 1C/O SPDT 2 x 1 C/O SPDT

RELAY RATING NO : 5A @ 250V AC; NC : 3A @ 250V AC

SUPPLY VOLTAGE 230V AC ±15% 85 to 270V AC/DC


FREQUENCY 45 to 65Hz
POWER CONSUMPTION 12VA max. 4VA max.

Terminal Connections Dimensions (All are in mm)


900CPR-1 900CPR-3 900CPR-1-BL-U 900 SERIES
35

S1 S2 1S1 1S2
45
90

67.5

RELAY RELAY RELAY 1


m

18 15 16 18 15 16 18 15 16
NO COM NC NO1 COM 1 NC1
NO COM NC
.co

RELAY 2

26 25 28 60
3S1 3S2
NC2 COM 2 NO2
u
ia

N L 2S1 2S2 N L S1 S2 N L
Ordering Information
-
ha

Aux.
+ PRODUCT CODE SUPPLY VOLTAGE CERTIFICATION
˜Supply AC/DC˜
900CPR-1-230V
230V AC
900CPR-3-230V
en

900CPR-1-BL-U-CE 85 to 270V AC / DC RoHS


di
Co

23 www.selec.com PROTECTION RELAY


Current Protection Relays

CPRD2M 900CPR-1-1-BL 900CPR-3-1-BL


Size : 35 x 90mm Size : 35 x 90mm Size : 35 x 90mm

! Din Rail Mount ! Din Rail Mount ! Din Rail Mount


! Under Current & Over Current Protection for 1Ø ! Under Current & Over Current Protection for 1Ø ! Under Current & Over Current Protection for
system system 1Ø & 3Ø system
FEATURES ! True RMS Measurement ! True RMS Measurement ! True RMS Measurement
! One Alarm Relay with NC or NO operation ! One Alarm Relay with NC or NO operation ! One Alarm Relay with NC or NO operation
Selectable Selectable

Under Current & Over Current monitoring,


MEASUREMENTS UnderCurrent & Over Current monitoring
Current Asymmetry
DISPLAY 3 digit LCD 3 digit LCD with backlight

ALARM INDICATIONS Trip


ELECTRICAL
1Ø - 2W 1Ø - 2W, 3Ø - 3W, 3Ø - 4W
CONNECTION
CT Primary : 5A / 10A to 999A (selectable),
CT SETTING CT Primary : 1A / 5A to 999A, CT Secondary : 1A / 5A (selectable)
CT Secondary : 5A / 10A (selectable)
TRIP SETTING Under Current : 0 to 999A, Over Current : 0.5 to 1.09kA Under Current : 0 to 999A, Over Current : 0.5 to 1.19kA, Current Asymmetry : 5.0 to 99.9%

Power ON Delay: 0.5 to 99.9sec Power ON Delay : 0.5 to 99.9sec


Trip Time Delay: 0 to 99.9sec Trip Time Delay : 0 to 99.9sec
TRIP TIME SETTING Recovery Time Delay: 0 to 99.9sec Recovery Time Delay : 0 to 99.9sec
Response Time: < 100ms Response Time : < 200ms

HYSTERESIS Current : 0.1 to 99.9A


RESOLUTION Current : 0.01, 0.1, 1A, 0.01kA (Depends on CT setting)
Current : ±1% of Setting ± 2 digits,
ACCURACY Time (Recovery Time, Trip delay, Power on delay) : ±5% of setting ±200ms
OUTPUT CONTACT 1C/O SPDT

RELAY RATING NO : 10A @ 250V AC ; NC : 10A @ 250V AC NO : 5A @ 250V AC ; NC : 3A @ 250V AC

SUPPLY VOLTAGE 230V AC ±15%

FREQUENCY 50 to 60Hz 50 to 60Hz


POWER CONSUMPTION 18VA max. 15VA max.

Terminal Connections Dimensions (All are in mm)


CPRD2M 900 SERIES
35
m
45
90

67.5

.co

900CPR-1-1-BL 900CPR-3-1-BL
3S1 3S2
u

RELAY 60
RELAY
ia

18 15 16 18 15 16
NO COM NC NO COM NC
ha

Ordering Information
en

N L N L PRODUCT CODE SUPPLY VOLTAGE CERTIFICATION


CPRD2M-1-1-230V-CE RoHS

900CPR-1-1-BL-230V-CE 230V AC RoHS


di

S1 S2
1S1 1S2 2S1 2S2 900CPR-3-1-BL-230V-CE RoHS
Co

24 www.selec.com PROTECTION RELAY


Earth Leakage Relays
New
16 15 18 Y2
New

900ELR-2 ELRA2M ELCTR35


Size : 35 x 90mm Size : 35 x 90mm Size : 74 x 105mm
! Din Rail Mount ! Din Rail Mount ! Din Rail Mount
! Leakage Current Monitoring in 3Ø & 1Ø systems ! Monitors True Rms Earth Leakage Current (upto 30A) ! Inbuilt CBCT
! RMS Value Measurement (AC) ! Sensitivity and Time Delay Adjustable ! Monitors True RMS Earth Leakage Current
FEATURES ! Test and Reset via Front / Remote ! Test and Reset Function ! Test and Reset Function
! Two Separate Alarms Relays with NO or NC ! CBCT Open Circuit Indication ! 1 SPDT Output Protection Relay
operation selectable

MEASUREMENT Earth Leakage Current (Via external CBCT) Earth Leakage Current (internal CBCT)
3 Digit LCD with backlight.
DISPLAY 2 LED for Trip indication 5 LED indication 2 LED indication
ELECTRICAL 1Ø - 2W, 3Ø - 4W, 3Ø - 3W 1Ø - 2W, 3Ø - 4W 1Ø - 2W, 3Ø - 3W, 3Ø - 4W
CONNECTION
TRIP SETTING 10mA to 30A 30mA to 30A 75% of 30mA or 300mA
Power ON Delay : 0.5 to 99.9 sec, Trip Time Delay : 0 to 9 sec
TIME RANGES Reset time : Instantaneous
Trip Time Delay : 0 to 99.9 sec, Delay On Release : 0 to 99.9 sec (NA when In=0.03A)
HYSTERSIS 5 to 40% -- 8% of input current
RESOLUTION 0.1mA, 1mA, 0.01A, 0.1A -- --
Current : ± 5% of setting, Recovery Time, Trip Delay, Power Trip : ± 5% of Set Trip Current Trip : ± 5% of Input Current
ACCURACY ON delay : ± 5% of setting + 100ms Time : ± 5% of set Time + Response Time Time : ± 5% of Response Time
OUTPUT CONTACT 2 C/O SPDT 1 C/O SPDT

OUTPUT RATING NC : 3A @ 250V AC, NO : 5A @ 250V AC NC : 5A @ 250V AC, NO : 10A @ 277V AC / 28DC NC : 5A @ 250V AC, NO : 5A @ 30V AC

SUPPLY VOLTAGE 230V AC 230V AC (± 15%)


FREQUENCY 45 to 65Hz 50 / 60Hz
POWER CONSUMPTION 3VA max <5 VA max 15 VA max

Terminal Connections
900ELR-2 ELRA2M2-1-230V ELCTR35 Aux. Supply
230V AC
RELAY 2 S1 S2 N RELAY 1
25 28 26 CBCT 16 15 18 Y2 L N 15 16 18
Auxiliary Supply

COM2 NO2 NC2 L L1 NC COM NO


NC
O L2 TST / RST
A L3 COM NO
D N
E L1
R T C L N S1 S2 Y1
L2
CBCT L3
TEST RELAY 1
230V AC L L1 N
16 18 15 L O L2
A L3 E
RESET NC1 NO1 COM1 D N
E

Ordering Information
PRODUCT CODE SUPPLY VOLTAGE CERTIFICATION PRODUCT CODE SUPPLY VOLTAGE CERTIFICATION
900ELR-2-230V ELCTR35-1-30mA-230V RoHS in process
m

230V AC
900ELR-2-230V-CE 230V AC RoHS ELRA2M2-1-230V RoHS in process

ELCTR35-1-300mA-230V RoHS in process


.co

CBCT for Earth Leakage Relays


u

DESCRIPTION CBCT for ELRA2M CBCT for 900ELR-2


ia

CT RATIO 1000:1
SIZES (inner diameter) 35 mm, 70 mm, 120 mm, 210mm, 310mm
ha

Ordering Information
en

Order Code Inner Diameter (in mm) CERTIFICATION


CBCT-35-1 35 RoHS in process
di

CBCT-70-1 70 RoHS in process

CBCT-120-1 120 RoHS in process


Co

CBCT-210-1 210 RoHS in process

CBCT-310-1 310 RoHS in process

25 www.selec.com PROTECTION RELAY


Earth Fault Relays

New

900EFR-BL-U 900EFR-2
Size : 35 x 90mm Size :35 x 90mm

! Din Rail Mount ! Din Rail Mount


! Earth Fault Current Monitoring in 1Ø and 3Ø systems, ! Earth Fault Current Monitoring in 1Ø and 3Ø Systems
FEATURES ! RMS Value Measurements(AC) ! RMS Value Measurements(AC)
! Alarm Relays With NO and NC operation selectable ! Alarm Relays with NO and NC operation selectable

MEASUREMENT Earth fault Current (via external EFCT)

DISPLAY 3 Digit Liquid Crystal Display with backlight, 2 LED for Trip indication 3 Digit Liquid Crystal Display without backlight, 3 LED for Trip indication
ELECTRICAL 1Ø - 2W, 3Ø - 3W, 3Ø - 4W
CONNECTION
FRAME RATING (CT 160A, 250A, 630A
PRIMARY)
M.C.C.B RATING Depends on Frame Rating 16A to Frame Rating

TRIP SETTING 10% to 80% of selectable MCCB frame rating Upto 80% of MCCB rating
Response time : <100ms Trip time delay : 0 to 99.9sec
Trip time delay : 0 to 99.9sec Recovery time : 0 to 99.9sec
TIME RANGES Recovery time : 0 to 99.9sec Power ON delay : 0.5 to 99.9sec
Power ON delay : 0.5 to 99.9sec 1 to 10% of fault current settings
HYSTERSIS 1 to 10% of fault current settings
RESOLUTION 0.1A when fault current is less than or equal to 99.9A 1A when fault current is greater than 100A
Current : ±5% of the settings ±2digit
ACCURACY Time : ±5% of the settings ±100ms
OUTPUT CONTACT 2 C/O SPDT
NC : 3A @ 250V AC
OUTPUT RATING NO : 5A @ 250V AC

SUPPLY VOLTAGE Auxillary Supply : 85 to 270V AC/DC 415V AC

FREQUENCY 50 / 60Hz

POWER CONSUMPTION 4VA max 50VA max

Terminal Connections Dimensions (All are in mm) Ordering Information


900EFR-BL-U 900EFR-2 900 SERIES
R T C RELAY1
TEST
15 18 16
PRODUCT CODE SUPPLY VOLTAGE CERTIFICATION
RESET COM1 NO1 NC1
35 900EFR-BL-U
RELAY 1
A1 A2 85 to 270V AC/DC
NO1
18 15
COM2 NC1
16
900EFR-BL-U-CE RoHS
RELAY 2
RELAY 2 900EFR-2-415V-CE 415V AC RoHS
67.50

45
90

26 25 28
26 25 28
COM2 NO2
NC2 COM2 NO2 NC2

S1 S2 Y1 Y2
S1 S2 N L TST/RST
m

CBCT Auxilliary 70.50


Supply
L L1
L L1 O L2
O L2 A L3
A L3 D N
D N E
.co

CT for Earth Fault Relays


u

DESCRIPTION 900EFR
ia

CURRENT RATIO 160/1A, 250/A, 630/1A


LOAD RESISTANCE 1 VA
ha

Ordering Information
en

Part No. Window Size Current Rating


EFCT 100/25 160/1A VAL CL1 100/25 160/1A
di

EFCT 140/35 160/1A VAL CL1 140/35 160/1A


EFCT 140/35 250/1A VAL CL1 140/35 250/1A
Co

EFCT 180/35 250/1A VAL CL1 180/35 250/1A


EFCT 180/35 630/1A VAL CL1 180/35 630/1A
EFCT 220/50 630/1A VAL CL1 220/50 630/1A

26 www.selec.com PROTECTION RELAY


Motor Protection Relay Water Level Controller

New New

MPR-3M MPCT WLCA2M1


Size : 52.5 x 90mm Size : 35 x 90mm

! Din Rail Mount ! Din Rail Mount


! Single Phasing, Phase Asymmetry, Phase Sequence ! Used For Drain & Fill Control.
FEATURES
! Under Current, Overload Trip Current ! 3 No's Stainless Steel Prods.
! Test and Reset Buttons via Front / Remote ! 10A SPDT Output (Resistive)

DISPLAY 3 LED Indication 2 LED Indication

AUXILLARY SUPPLY 230 / 415V AC ±15% 85 - 270V AC/DC


FREQUENCY 45 to 65Hz 50 to 60Hz
ELECTRICAL 3Ø - 3W Auxiliary Supply
CONNECTION
POWER RATING 5 VA max 3 VA max
Phase Asymmetry : 50% of motor current (Fixed)
T(sec ) setting : To select 2 ,4 ,6 ,8 ,10 sec trip time curve in overload trip curve graph.
TRIP SETTING According to the levels of sensor placed in the water tank
Under Current : 50% of Motor Current
X Imax : To select motor current rating
SENSITIVITY NA 1 Kohms to 200Kohms

Single Phase trip : 5 sec, Phase Asymmetry : 5 sec, Phase Sequence : 5 sec 0.5 sec (approx)
TRIP TIME
Over load trip : As per graph 1, Under Current trip : 5 Sec
MODE Auto / Manual / Remote Automatic
Time : ± 5% of full scale ±100msec
ACCURACY NA
Current : ± 5% of full scale
OUTPUT CONTACT 2 C/O DPDT 1 C/O SPDT

OUTPUT RATING NC : 5A @ 240V AC NO : 5A @ 240V AC 10A @ 250V AC / 28V DC

Terminal Connections Dimensions (All are in mm)


MPR-3M 45
MPR-3M-2-230V

1 2 3 4 5 6 7 8 9
73

52.5 90

WLCA2M1

MPR-3M-2-415V
m
u .co
ia

Ordering Information
PRODUCT CODE SUPPLY VOLTAGE CERTIFICATION
ha

WLCA2M1 MPR-3M-2-230V 230V AC


MPR-3M-2-415V 415V AC
en

WLCA2M1 85 to 270V AC/DC RoHS in process

PRODUCT CODE INPUT CURRENT CERTIFICATION


di

MPCT D15 10 A 10 A
Co

MPCT D15 40 A 40 A
MPCT D15 80 A 80 A

27 www.selec.com PROTECTION RELAY


TIME SWITCHES

Time Switch - Din Rail Mount


Time Switch - Wall Mount

Applicable EMI / EMC standards


m

Product standard : IEC 61326-1


.co

Category Standards Compliance


Level II for Contact discharge
ESD Immunity IEC 61000-4-2
Level III for Air discharge
u

Surge Immunity IEC 61000-4-5 +/- 2 kV common mode,


ia

Level III, 80 to 1000MHz


ha

Radiated Susceptibility IEC 61000-4-3 Level II, 1.4GHz to 2GHz


Level I, 2GHz to 2.7GHz
Conducted Susceptibility
en

IEC 61000-4-6 Level II

Conducted Emission CISPR-11


di

Radiated Emission CISPR-11


Electrical Fast Transient Level II
Co

IEC 61000-4-4

28 www.selec.com
Weekly Astronomical

TS2M1-1-16A-230V TS1W1-1-20A-230V ATS2M1-1-16A-230V


Size : 35mm (Width) Size : 60 x 60 mm Size : 35mm (Width)

! Din Rail Mount ! Wall Mount ! Din Rail Mount


! 50 ON - OFF Steps per day ! 50 ON - OFF Steps per day ! Latitude / Longitude precise to a minute
! 1 C/O SPDT ! 1 NO & Neutral ! with the time zone.
FEATURES
! 10+ years battery life ! 10+ years battery life ! Sunrise / Sunset or Twilight rise / set trigger modes
! 1 C/O SPDT
! 10+ years battery life

DISPLAY Text LCD (Without Backlight)


RTC ACCURACY 15 Minutes a year @ 25ºC
OUTPUT CONTACT 1 C/O SPDT 1 NO & Neutral 1 C/O SPDT

CONTACT RATING 16A @ 250V AC 20A @ 250V AC 16A @ 250V AC

OPERATION PERIOD 1 Week


Total 50 ON Steps and 50 OFF Steps
2 Programs x 25 Steps
3 Programs x 16 Steps
WEEKLY PROGRAM 4 Programs x 12 Steps
5 Programs x 10 Steps
6 Programs x 08 Steps
7 Programs x 07 Steps
8 Programs x 06 Steps
MINIMUM SETTING UNIT 1 second
HOLIDAY SETTINGS 16 Dates
CLOCK 12-hr. (AM / PM) and 24-hr. selection
RELAY OPERATING MODE Auto / Temporary Override / Permanent Override ON / Permanent Override OFF

SUPPLY VOLTAGE
(AC : 50 / 60 Hz) 230V AC ±10% / 110V AC ±10%

Terminal Connections Dimensions (All are in mm)


TS2M1-1-16A-230V / ATS2M1-1-16A-230V TS2M1-1-16A-230V / ATS2M1-1-16A-230V

16 15 18 35

COM
NC
NO
67.5

45
90

N L
m

TS1W1-1-20A-230V
60
.co

TS1W1-1-20A-230V
u
ia

Ordering Information
ha

PRODUCT CODE SUPPLY VOLTAGE CERTIFICATION


TS2M1-1-16A-230V 230V AC ---
en

TS2M1-1-16A-230V-CE 230V AC
TS1W1-1-20A-230V 230V AC ---
di

TS1W1-1-20A-230V-CE 230V AC
TS2M1-1-16A-110V 110V AC ---
Co

TS2W1-1-20A-110V 110V AC ---

ATS2M1-1-16A-230V 230V AC ---

29 www.selec.com TIME SWITCHES


TIMERS

Analog Timers - 17.5mm DIN Rail Timers


Analog Timers - 22.5mm DIN Rail Timers
Analog Timers - Plug / Panel Mount
Digital Timers - Single Display Multifunction
Digital Timers - Dual Display Multifunction
Digital Timer - Sequential
Time Interval Meters
m

Applicable EMI / EMC standards


.co

Product standard : IEC 61326-1

Category Standards Compliance


u

Level II for Contact discharge


ESD Immunity IEC 61000-4-2
ia

Level III for Air discharge


Surge Immunity IEC 61000-4-5 +/- 2 kV common mode,
ha

Level III, 80 to 1000MHz


Radiated Susceptibility IEC 61000-4-3 Level II, 1.4GHz to 2GHz
en

Level I, 2GHz to 2.7GHz


Conducted Susceptibility IEC 61000-4-6 Level II
di

Radiated Emission CISPR-11


Co

Electrical Fast Transient IEC 61000-4-4 Level II

Note : Above standards are applicable only for CE certified Timers

30 www.selec.com
17.5mm Din Rail Timers

600DT 600ST 600XU 600SD 642SQ-A 642XA


Size : 17.5 x 90 x 60mm Size : 17.5 x 90 x 60mm Size : 17.5 x 90 x 60mm Size : 17.5 x 90 x 60mm Size : 17.5 x 90 x 60mm Size : 17.5 x 90 x 60mm

! Digital Timer ! Single Function ! 13 Functions ! Star Delta ! 2 Functions ! 2 Functions


! 15 Functions ! 10 Time Ranges ! 10 Time Ranges ! 1 C/O Relay each for ! 8 Time Ranges ! 8 Time Ranges
! 8 Time Ranges ! 1 C/O SPDT ! 1 C/O SPDT Star & Delta ! 1 C/O SPDT ! 1 C/O SPDT
FEATURES
! 1 C/O SPDT

A, B, C, D, E, F, H, J, K, L, P, A, B, C, Ci, D, E, F, H,
MODES A Star - Delta ON delay / Interval ON delay / Interval
Q, R, T, U I, J, K, Ai, Bi
0 - 3sec / min, 0 - 3sec / min,
99.9sec / min / hr, 0.1 - 1sec, 0.3 - 3sec, 1 - 10sec, 3 - 30sec, Runup time : 0 - 10sec / min, 0 - 10sec / min,
TIME RANGES 999sec / min / hr 0.1 - 1min, 0.3 - 3min, 1 - 10min, 3 - 30min, 3 - 30sec, 6 - 60sec 0 - 30sec / min, 0 - 30sec / min,
9:59min:sec, 9:59hr:min 0.1 - 1hr, 0.3 - 3hr Change over : 50/100ms 0 - 60sec / min 0 - 60sec / min
RESOLUTION 0.1sec 0.1sec 0.1sec --- 0.3sec 0.3sec
Setting : ± 0.1% of set time or Setting : ±5% of F.S
±50ms (whichever is greater)
ACCURACY Repeat : ±0.5% (F.S. = Full Scale)
For Y contact operation :
+100ms, Repeat : ± 0.1 % Pause time accuracy : ±5% ±5ms

1 C/O SPDT 1 C/O SPDT 1 C/O SPDT 1 C/O Relay each 1 C/O SPDT
OUTPUT CONTACT
for Star & Delta
CONTACT RATING 8 A @ 250V AC 5A @ 250V AC or 24V DC
SUPPLY VOLTAGE 20 to 240V AC 20 to 240V AC
20 to 240V AC / DC 240V AC, 110V AC, 24V DC 110V AC, 230V AC 230V AC, 24V AC/DC
(AC : 50 / 60 Hz) 12 to 240V DC 12 to 240V DC

A - On delay, B - Interval, C - Asymmetrical cyclic OFF first, D - Asymmetrical cyclic ON first, E - Repeat cycle equal OFF first, F - Repeat cycle equal ON first,
600DT H - Pulse output, J - Delay on break, K - Delay on make/Delay on break, L - Interval after break, P - Single shot,Q - Retriggerable Single shot, R - Latching relay,
T - Delay on make with Totalise, U - Interval with Totalise
Modes
A - On delay, B - Interval, C - Repeat cycle equal OFF first, Ci - Repeat cycle equal ON first, D - Pulse output 500ms fixed, E - Delay on break,
600ST & F - Delay on make/Delay on break, H - Interval after break, I - Single shot, J - Retriggerable Single shot, K - Latching relay,
600XU
Ai - Delay on make with Totalise, Bi - Interval with Totalise

Terminal Connections
600DT 600ST 600XU 600SD 642SQ-A 642XA

+ -
+ -

A1 A2
A1 A2 A1 A2 A1 A2 18 28
relay

26 28 NO NO
Y relay

R
Control NC NC
Control 20 to 240 V AC/
Contact Y1 12 to 240V DC
Contact
ON Y1
15 25 15 15 25
Y 15 25
16 18 16 18 16 18 COM COM
NC NO 15 25
NC NO NC NO 16 26
16 18
m

COM COM COM

Dimensions (All are in mm) Ordering Information


.co

PRODUCT CODE SUPPLY VOLTAGE CERTIFICATION


600, 642 SERIES
44 600DT
20 to 240V AC/DC
600DT-CU RoHS
u

600XU
ia

20 to 240V AC, 12 to 240V DC


600XU-A-1-CU RoHS
600SD-2-230
ha

230V AC
600SD-2-230-CU-RoHS RoHS
67.5

35.3

600SD-2-110V
45

90

en

110V AC
600SD-2-110-CU
600ST
240V AC
di

600ST-CU RoHS

600ST-110V 110V AC ---


Co

17.5 600ST-24V 24V DC ---


60 642SQ-A 230VAC, 24 AC/DC ---
642XA 20 to 240V AC, 12 to 240VDC ---

31 www.selec.com ANALOG TIMERS


22.5mm Din Rail Timers

800XU 800XA 800SQ-A 800S


Size : 22.5 x 75 x 101mm Size : 22.5 x 75 x 101mm Size : 22.5 x 75 x 101mm Size : 22.5 x 75 x 101mm

! 2 Functions ! 2 Functions ! 2 Functions ! Single Function


! 12 Time Ranges ! 8 Time Ranges ! 8 Time Ranges ! 2 Time Ranges
! 2 C/O DPDT ! 2 C/O DPDT ! 1 C/O SPDT ! 1 C/O SPDT
FEATURES

MODES ON delay / Interval ON delay

TIME RANGES 1 / 3 / 10 / 30sec / min / hr 3 / 10 / 30 / 60sec / min 3 / 10 / 30 / 60sec / min 30sec, 60sec (factory set)

RESOLUTION 0.1sec 0.3sec 0.3sec ---


Setting : ±5% of Full Scale
ACCURACY Repeat : ±0.5% or 50ms (Whichever is greater)
OUTPUT CONTACT 2 C/O DPDT 2 C/O DPDT 1 C/O SPDT 1 C/O SPDT
CONTACT RATING 5A @ 250V AC or 24V DC
SUPPLY VOLTAGE 20 to 240V AC, 20 to 240V AC, 230V AC,415V AC,
12 to 240V DC 12 to 240V DC 230V AC & 24V AC/DC
(AC : 50 / 60 Hz) 12V DC

Terminal Connections Dimensions (All are in mm)


800XU 800XA 800 SERIES
22.5 100.5
76.85

35
105.5
800S 800SQ-A
A1 25
15 26

S
COM
Ordering Information
U NO NC
P PRODUCT CODE SUPPLY VOLTAGE CERTIFICATION
P
L
Y 800XU
16 28 20 to 240VAC, 12 to 240V DC
800XU-CU
®

C US
18 A2
800XA
m

20 to 240V AC, 12 to 240V DC


800XA-CE
800SQ-A
.co

230V AC, 24V AC/DC


800SQ-A-230-CU
®

C US

800S-1-ON-30S-230
230V AC
800S-1-ON-60S-230
u

800S-1-ON-30S-415
ia

415V AC
800S-1-ON-60S-415
ha
en
di
Co

32 www.selec.com ANALOG TIMERS


22.5mm Din Rail Timers

800SD-2 800XC 800XMR 800POD


Size : 22.5 x 75 x 101mm Size : 22.5 x 75 x 101mm Size : 22.5 x 75 x 101mm Size : 22.5 x 75 x 101mm

! Star Delta ! 2 Functions ! Forward Pause Reverse ! True Power OFF delay
! 2 Time Ranges ! 6 Time Ranges ! 1 C/O Relay each for Forward & ! Fixed Time Ranges
! 1 C/O relay each for Star & Delta ! 2 C/O DPDT Reverse ! 2 C/O DPDT
FEATURES

MODES Star - Delta Asymmetrical Cyclic ON first or OFF first Forward - Pause - Reverse True Power OFF delay
Run up time range : 30 / 60sec 1 / 10sec / min / hr ON time : 1 / 2 / 4 / 8min
TIME RANGES 60sec, 180sec
Change over : 50 / 100msec for both ON & OFF time Pause time : 10 / 20 / 40 / 80s
RESOLUTION --- 0.1sec --- ---
Setting : ±0.5% or 50ms (Whichever is greater) Setting : ±10% of full scale,
ACCURACY Repeat : ±5% of full scale Repeat : ±2% or 100ms
1 C/O Relay each 2 C/O DPDT 1 C/O each for 2 C/O DPDT
OUTPUT CONTACT for Star & Delta Forward & Reverse
CONTACT RATING 5A @ 250V AC or 24V DC
SUPPLY VOLTAGE 110V AC, 230V AC 20 to 240V AC, 20 to 240V AC,
(AC : 50 / 60 Hz) 110 to 240V AC/DC
230 to 450V AC 12 to 240V DC 12 to 240V DC

Terminal Connections Dimensions (All are in mm)


800SD-2 800XC 800 SERIES

A1 25 22.5 100.5
15 26
relay

COM
S NC
U
76.85
Y relay

NO
P COM

35
NO
P NC
L
Y
16 28
18 A2
105.5

800XMR 800POD Ordering Information


PRODUCT CODE SUPPLY VOLTAGE CERTIFICATION
800SD-2-230
230V AC
800SD-2-230-CU
®

Rly 1 C US

800SD-2-110
110V AC
m

800SD-2-110-CU
®

C US

Rly 2 800SD-2-415 230 to 450V AC


.co

800XC
20 to 240V AC, 12 to 240V DC
800XC-CU
®

C US

800XMR 20 to 240V AC, 12 to 240V DC


u

800POD-180S
®

C US

110 to 240V AC/DC


ia

800POD-60S
®

C US
ha
en
di
Co

33 www.selec.com ANALOG TIMERS


Plug / Panel Mounting Timers

55XU 55XC 55ES


Size : 48 x 48mm Size : 48 x 48mm Size : 48 x 48mm

! 2 Functions ! 2 Functions ! 2 Functions


! 12 Time Ranges ! 6 Time Ranges ! 8 Time Ranges
! 2 C/O DPDT ! 2 C/O DPDT ! 1 C/O SPDT
FEATURES

BASE TYPE P8 - 8 pin plug, T8 - Screw terminal


MODES ON delay / Interval Asymmetrical Cyclic ON first or OFF first ON delay / Interval
1 / 10sec / min / hr for
TIME RANGE 1 / 3 / 10 / 30sec min / hr 3 / 10 / 30 / 60sec / min
both ON & OFF time
RESOLUTION 0.1sec 0.1sec 0.3sec
ACCURACY Setting : ± 5% of full scale, Repeat : ± 0.5% or 50 ms (whichever is greater)

OUTPUT CONTACT 2 C/O DPDT 2 C/O DPDT 1 C/O SPDT


CONTACT RATING 5A @ 250V AC or 24V DC
SUPPLY VOLTAGE 20 to 240V AC, 230V AC & 24V AC/DC,
20 to 240V AC, 12 to 240V DC
(AC : 50 / 60 Hz) 12 to 240V DC 110V AC & 24V AC/DC

Terminal Connections Dimensions (All are in mm)


55XU / 55XC 55 SERIES 7

48 45 46
Panel Mount Type 8 Pin Socket

1 2 3 4 5 NC1 NC2 46
4 5 48 100
NC1 NO1 NO2 Front bezel Side view Panel cutout
COM1 NC2 COM2 3 6
NO1 NO2
11 12
2 7
Ordering Information
1 8
6 7 8 9 10 COM1 COM2 PRODUCT CODE SUPPLY VOLTAGE CERTIFICATION
L
-N +
+

L N 55XC-P8
®

55XC-P8-CU RoHS C US
20 to 240V AC, 12 to 240V DC
55XC-T8
®

55XC-T8-CU RoHS C US

55XU-P8
®

55ES 55XU-P8-CU RoHS C US


20 to 240V AC, 12 to 240V DC
55XU-T8
m

55XU-T8-CU RoHS C US

Panel Mount Type 8 Pin Socket 55ES-P8-230


.co

55ES-P8-230-CU
®

230V AC & 24V AC/DC C US

1 2 3 4 5 NC 55ES-T-230
4 5
55ES-T-230-CU
®

NC1 NO1
3 6
C US

COM1 24V
u

11 12 NO 55ES-P8-110
55ES-P8-110-CU
®

2 7
ia

C US
110V AC & 24V AC/DC
55ES-T-110
6 7 8 9 10 1 8
- COM 55ES-T-110-CU
®
ha

C US
L N
24V
L N
en
di
Co

34 www.selec.com ANALOG TIMERS


Single Display, Multifunction Timers

XT532 XT543 XT56 XT264 XT364


Size : 48 x 48mm Size : 48 x 48mm Size : 48 x 48mm Size : 72 x 72mm Size : 96 x 96mm

! Single set point ! Single set point ! Single set point


! 4 Functions ! 4 Functions ! 2 Functions
! 6 Time Ranges ! 9 Time Ranges ! 6 Time Ranges
FEATURES ! 2 C/O DPDT ! 2 C/O DPDT ! 2 C/O DPDT

DISPLAY 2 digits 3 digits

SET POINT Single set point

DELAY MODES ON delay / Interval / Cyclic ON first / Cyclic OFF first ON delay / Interval

TIME RANGE 9.9 / 99sec, 9.9 / 99min, 9.9 / 99hr


9.99 / 99.9 / 999sec, 9 : 59min : sec, 99.9 / 999min,
9.99 / 99.9 / 999sec, 99.9 / 999min, 99.9hr
9 : 59hr : min, 99.9 / 999hr

RESOLUTION 0.1sec 0.01sec

TIME SETTING --- Pushwheel

Start : Pulse start Start : Gate / Pulse start (Programmable) Start : Pulse start
RESET / START INPUT
Reset : Front panel, Remote reset, On power interruption

ACCURACY ±0.5% of F.S. or 50 ms

OUTPUT CONTACT 2 C/O DPDT

CONTACT RATING 5A @ 250V AC or 24V DC

MEMORY RETENTION 10 Years No memory retention


SUPPLY VOLTAGE
(AC : 50 / 60 Hz) 90 to 270V AC/DC 90 to 270V AC/DC, 24V DC (optional)

Terminal Connections Dimensions (All are in mm)


XT56-N XT264 XT532, XT543

48 45 46

48 7 100 46
Front bezel Side view Panel cutout
XT56

48 45 46

48 94 46
7
Front bezel Side view Panel cutout
XT364 XT532 XT364
m

96 90.5 92
.co

96 10 73 92
Front bezel Side view Panel cutout
XT264
u

72 68 69
ia

72 115 69
Front bezel 10 Side view Panel cutout
ha

XT543
Ordering Information
PRODUCT CODE SUPPLY VOLTAGE CERTIFICATION
en

XT532 90 to 270V AC/DC


XT543 90 to 270V AC/DC
di

XT56-N 90 to 270V AC/DC


XT56-N-CE 90 to 270V AC/DC
Co

XT56-N-24 24V DC
XT264 90 to 270V AC/DC
XT364 90 to 270V AC/DC

35 www.selec.com DIGITAL TIMERS


Dual Display, Multifunction Timers Sequential Timer

XT546 XT246 XT346 XT5042 PT380


Size : 48 x 48mm Size : 72 x 72mm Size : 96 x 96mm Size : 48 x 48mm Size : 96 x 96mm

! Single set point ! Dual set point ! Sequential timer


! 4 Functions ! 7 Functions ! 4 Functions
! 9 Time Ranges ! 9 Time Ranges ! 6 Time Ranges
FEATURES
! 2 C/O SPDT ! 2 C/O SPST ! 8 Channels

DISPLAY 3 digit 7 Segment LED, Dual display 4 + 4 digits 2 + 4 digits


SET POINT Single set point Dual set point Single set point

ON delay / Interval / Cyclic ON first / Cyclic ON delay / Interval / Cyclic ON first /


ON delay / Interval / Cyclic ON first / Cyclic OFF first OFF first / Forward-Pause-Reverse / Cyclic OFF first (Start up delay & no.
MODES of cycles programmable
Instantaneous + Delayed / Timer / Batch for cyclic mode)

9.99 / 99.9 / 999sec, 9.59min : sec, 99.99 / 999.9 / 9999sec, 99.59min : sec, 99.99sec, 999.9sec, 99.59min : sec,
TIME RANGES 99.9 / 999min, 9.59hr : min, 99.9 / 999hr 999.9 / 9999min, 99.59hr : min 99.59hr : min, 999.9hr
999.9 / 9999hr
RESOLUTION 0.01sec
TIME SETTING Front keypad
NO. OF CHANNELS -- 8 Channels
Start : Gate / Pulse start (Programmable)
RESET/START INPUT Start, Hold
Reset : Front panel, Remote reset, On power interruption

ACCURACY ±0.05% of F.S. or 50ms (whichever is greater) ±0.05% of F.S. or 50ms ±0.5% of F.S. or 50ms (whichever is greater)

OUTPUT CONTACTS 2 C/O SPDT 2 C/O SPST --

CONTACT RATING 5A @ 250V AC or 24V DC


MEMORY RETENTION 10 Years 10 Years 10 Years (User selectable)
SUPPLY VOLTAGE 85 to 270V AC, 24V AC/DC (optional)
(AC : 50 / 60 Hz) 90 to 270V AC/DC 85 to 270V AC/DC

Terminal Connections Dimensions (All are in mm)


XT5042
XT5042 XT546
48 45 46
L
1 11 6 COM
+ 100 46
48 7
START Front bezel Side view Panel cutout
- 2 7
N RST
XT546
NO1 NO2
3 8 48 45 46

COM1 COM2
4 9 48 94 46
7
Front bezel Side view Panel cutout

5 12 10 XT346
NC1 NC2

96 90.5 92
m

XT246 L
XT346 L
START START
+ 1 8 + 1 10 96 10 73 92
.co

-
Front bezel Side view Panel cutout
- 2 11 COM
COM N
2 9 XT246
N 3 12
RST
3 10 RST 4 13 72 68 69
u

4 11 5 14
72 115 69
10
ia

NO1 NO2 6 15 Front bezel Side view Panel cutout


5 12 NO1 NO2
7 16
COM1 6 13
COM2
Ordering Information
ha

COM1 8 17 COM2

NC1 7 14 NC1 9
PRODUCT CODE SUPPLY VOLTAGE CERTIFICATION
NC2 18
NC2
XT5042 90 to 270V AC/DC
en

PT380 XT5042-CU 90 to 270V AC/DC C US

To GND & STRT


of timer2 XT546 85 to 270V AC/DC
di

XT546-24V 24V AC/DC


1 2 3 4 5 6 7 8 9
STRT HOLD RST CONFIG +24V GND CAS NO1 NO2
XT246 85 to 270V AC/DC
Co

N L
XT246-24V 24V AC/DC
10 11 12 13 14 15 16 17 18 XT346 85 to 270V AC/DC
NO3 NO4 NO5 NO6 NO7 NO8 COM
- + PT380 85 to 270V AC/DC

36 www.selec.com DIGITAL TIMERS


TIME INTERVAL METERS

TT412 TI103 LT920A LT945A


Size : 36 x 72mm Size : 48 x 96mm Size : 24 x 48mm Size : 24 x 48mm

! 6 Digits Time Totaliser ! 4 Digits Time Interval Meter ! 8 Digits LCD TIme Totaliser ! 8 Digits LCD TIme Totaliser
! Selectable Least Count ! Range : Auto Ranging, Fixed Ranges ! Self Powered ! Self Powered
! Remote Reset ! Long Battery Life ! Long Battery Life
FEATURES
! Contact / Voltage Input ! Contact / Voltage Input
! Front Reset Button

DISPLAY 6 digits 4 digits 8 digits

a) Auto ranging : .0001 to 9999sec


a) 9999.59.59hr:min:sec
TIME RANGES 99999.9 / 999999sec / min / hr b) Fixed ranges : .9999, 9.999, 99.99, 999999.99hr
b) 999999.99hr
999.9,9999sec

ACCURACY ±0.05% + 1 count


Mains, Potential free contact, Potential free & 3 to 30V DC a) 24 to 260V AC a) 24 to 260V AC
INPUT PNP sensor from solid state devices b) Contact input b) Contact input
RESET Remote (Reset time : 20ms) Front, Remote (Reset time : 20ms), Auto Front, Remote Remote
MEMORY 10 Years 5 years
SUPPLY VOLTAGE 90 to 270V AC/DC Battery Powered
(AC : 50 / 60 Hz)

Terminal Connections Dimensions (All are in mm)


TT412 TI103C TT412
NC/ NO/ COM+12V RST COM 36 31 32
STRT/ C1 C2
+12V HLD +12V RST COM CONFIG N L
1 2 3 4 5 6 7 8 9 10 72 73 69
1 2 3 4 5 6 7 8 9 10 11 12 22 24 4.5
Front bezel Side view Panel cutout
21 23
TI103C
11 12 13 14 15 16 17 18 N L
48 45 46
- +
96 88 92
Front bezel 10 Side view Panel cutout

LT920A-C LT920A-V LT920A , LT945A


21.9
24

FR 22.5
FR
INPUT RST COM RNG PWR ENBL RST COM RNG
INPUT PWR ENBL 48
48 45.5
OFF OFF Front bezel 4 Side view Panel cutout
1 2 3 4 5 1 2 3 4 5
ON ON

CONTACT 24-260V AC
Ordering Information
INPUT
PRODUCT CODE SUPPLY VOLTAGE CERTIFICATION
TI103C 90 to 270V AC/DC
LT945A-C LT945A-V
TT412 90 to 270V AC/DC
INPUT TYPE
INPUT RST COM RNG PWR INPUT RST COM RNG PWR PRODUCT CODE CERTIFICATION
CONTACT VOLTAGE
OFF OFF
1 2 3 4 5
m

ON 1 2 3 4 5 LT920A-C
ON
LT920A-V
CONTACT 24-260V AC
LT945A-C
.co

INPUT
LT945A-V
LT920A-C-CE
LT920A-V-CE
u

LT945A-C-CE
ia

LT945A-V-CE

Accessories (Common For All Products)


ha

ADAPTER PLATES - Material: ABS plastic 48 x 48mm COLLAR CLAMP SNUBBER CIRCUIT
To fit smaller products into 92 x 92mm size or 69 x 69mm size cut outs Model : ACL4802 R - C network to reduce electrical
en

noise
Model : APRC01
di

TRANSPARENT FULL COVER 8 PIN SOCKET


Material : Poly carbonate Mounting : a) DIN rail mounting
Co

Model : AP9672 Model : AP9648 Model : AP7248 Model : AP6050 Model : AP4848 Size : to fit for 48 x 48mm b) Surface mounting
To fit 72 x 72mm To fit 48 x 48mm To fit 48 x 48mm products Model : AS08
product in to product in to product in to Model : ACF4801
92 x 92mm cutout 92 x 92mm cutout 69 x 69mm cutout

37 www.selec.com TIME INTERVAL METERS


COUNTERS & RATE INDICATORS

Count Totalisers
Counters - Programmable / Preset
Rate Indicators

Applicable EMI / EMC standards


Product standard : IEC 61326-1

Category Standards Compliance

ESD Immunity IEC 61000-4-2 Level III


m

+/- 2kV common mode,


Surge Immunity IEC 61000-4-5
.co

+/- 1kV differential mode


Level III, 80 to 1000MHz
Radiated Susceptibility IEC 61000-4-3 Level II, 1.4GHz to 2GHz
Level I, 2GHz to 2.7GHz
u
ia

Conducted Susceptibility IEC 61000-4-6 Level II

Dips : 0% residual voltage /1 cycle (Criteria B.),


ha

Voltage Dips and 40% residual voltage /10 cycles 50Hz / 12 cycles 60Hz (Criteria C)
IEC 61000-4-11
Interruptions 70% residual voltage / 25 cycles 50Hz / 30 cycles 60Hz (Criteria C)
en

Interruptions : 0% residual voltage / 250 cycles 50Hz / 300 cycles 60Hz (Criteria C)

Conducted Emission CISPR-11


di

Radiated Emission CISPR-11


Co

Electrical Fast Transient IEC 61000-4-4 Level III

Note : Above standards are applicable only for CE certified Counters

38 www.selec.com
Count Totalisers Programmable / Preset Counters

XC410A XC10D XC22B XC1200


Size : 36 x 72mm Size : 48 x 96mm Size : 72 x 72mm Size : 48 x 96mm

! 6 Digits, 7 segment LED Totaliser ! Preset Counter ! 6 Digits Counter ; 5 Digits RPM Indicator
! Compact Size ! Thumbwheel Setting ! LED Status Indicator : Relay 1, Relay 2
! Inbuilt Sensor Supply ! Auto Reset ! Dual Set point
FEATURES
! Battery Backup ! Programmable Input Scaling
! Up, Down, Quadrature & Bi-directional

OPERATING MODES On delay / Interval / Auto reset On delay / Interval / Auto reset / Time pulse repeat

Selectable least count : 0.0001, 0.001, 0.01, 0.1 & 1


TIME RANGES 999999 counts 9999 counts Rate : 4.00 to 99999 RPM/RPH
RESET Front, Remote Front, Remote, Auto (Optional) Front (user selectable), Remote

MEMORY Yes Yes (Optional) Yes

DIRECTION Up Up Up, Down, Bidirectional, Quadrature

SET POINT Single set point Dual set point

a) 0 to 20Hz, a) 3Hz, 30Hz, a) 0 to 30Hz, a) 0 to 30Hz,


INPUT SPEED b) 0 to 1kHz b) 1kHz b) 0 to 5kHz b) 0 to 2.5kHz, c) 0 to 5kHz
0.00001 to 9.99999 x 10"
SCALE FACTOR n = -5, -4, -3, -2, -1, 0, 1, 2

OUTPUT CONTACT 2 C/O DPDT

OUTPUT RATING 5A @ 250V AC or 24V DC

SENSOR TYPE NPN, PNP, Potential free contacts NPN, PNP, Potential free contacts NPN, PNP, Potential free contacts, Encoder

SUPPLY VOLTAGE 230V AC (only for XC410A), 90 to 270V AC/DC,


230V AC 90 to 270V AC/DC
(AC : 50 / 60 Hz) 24V AC/DC (only for XC410)

Terminal Connections
XC410A XC10D XC22B XC1200
PNP NPN
COM RST N (-) L (+) SENSOR
SELECTION VERY RESET
NPN PNP +12V RST COM SLOW SLOW COM ENABLE

1 2 3 4 5 6 7 8 9 10
Front RST Slow CNT SPEED
Speed 22 24
Enable SELECTION

21 23

XC410 11 12 13 14 15 16 17 18 N L

N (-) L (+) - +

Ordering Information
PRODUCT CODE SUPPLY VOLTAGE CERTIFICATION
XC22B-4-230
m

Dimensions (All are in mm) XC22B-4-AR-M1-230


230V AC
.co

XC410 / XC410A XC1200


90 to 270V AC/DC ®

XC1200-CU RoHS C US
33

28

29

XC410
u

75 74.5 71 90 to 270V AC/DC ®

XC410-CU RoHS C
Front bezel 3.5 Side view Panel cutout
US
ia

XC410-24
XC10D, XC1200 24V AC/DC
XC410-24-CU
®
ha

C US

48 45 46 XC410A-1-230 230V AC in process

92 XC10D 90 to 270V AC/DC


96 88
en

Front bezel 10 Side view Panel cutout

XC22B
di

72 68 69
Co

72 10 115 69
Front bezel Side view Panel cutout

39 www.selec.com COUNTERS
Count Totaliser Programmable / Preset Counters

LXC900A XTC5400 XC3200 XC2200


Size : 24 x 48mm Size : 48 x 48mm Size : 96 x 96mm Size : 72 x 72mm

! 8 Digits LCD Counter ! Dual Display, 4 Digits, 7 segment LED ! 6 Digits Counter, 4 Digits RPM Indicator
! Self Powered ! LED Status Indicator : Relay 1, Relay 2, ! LED Status Indicator : Relay 1, Relay 2, Rate, Batch
! Long Battery Life Seconds, Minutes, Hours ! Dual Set point
FEATURES ! Contact / Voltage input ! Dual Set point ! Programmable Input Scaling, RS485 Communication (against order)
! Programmable Input Scaling ! User Configurable Relay 2 Operation Mode, Rate / Batch
! Batch Counting ! Unidirectional, Bi-directional & Quadrature with up / down selection
Timer : ON delay / Interval / Cyclic ON first
/ Cyclic OFF first / Batch.
OPERATING MODES ON delay / Interval / Auto reset / Time pulse repeat
Counter : ON delay / Interval / Auto reset, Time
pulse repeat, Batch
Timer : 99.99 / 999.9 / 9999sec,
99:59min:sec, 999.9 / 9999min,
TIME RANGES 99999999 counts
99:59hr:min, 999.9 / 9999hr
Counter : -999 to 9999 counts
RESET Front, Remote Front, Remote, Power Interruption Front (user selectable), Remote
MEMORY Yes Yes Yes
DIRECTION Up Timer : Down Counter : Up / Down Up / Down
SET POINT 2 2
INPUT SPEED a) 14Hz, b) 100Hz a) 3Hz, b) 30Hz, c) 5kHz a) 0 to 30Hz, b) 0 to 5kHz
n
SCALE FACTOR 0.001 to 9.999 x 10" n = -3, -2, -1, 0, 1, 2 0.00001 to 9.99999 x 10 n= -5, -4, -3, -2, -1, 0, 1, 2
OUTPUT CONTACTS 2 Relays each 1 NO 2 C/O DPDT
OUTPUT RATING 5A @ 250V AC or 24V DC
SENSOR TYPE NPN / PNP sensor
SUPPLY VOLTAGE Battery powered 90 to 270V AC / DC
(AC : 50 / 60 Hz)

Terminal Connections Ordering Information


LXC900A-C XTC5400 XC2200 XC2200-C INPUT TYPE
FR PRODUCT CODE CERTIFICATION
INPUT RST COM SPD PWR ENBL Contact Voltage
OFF NO1 1 30 29 28 27 26 25 24 12V NO1 1 30 29 28 27 26 25 24 12V
1 2 3 4 5
ON
NO1 COM1 2
PNP NPN
23 CNT1 COM1 2
PNP NPN
23 CNT1 LXC900A-C
CONTACT NC1 3 22 CNT2 NC1 3 22 CNT2
INPUT
NO2 4 21 GND NO2 4 21 GND LXC900A-V
COM2 5 20 FILTER COM2 5 20 FILTER
LXC900A-V
NC2 6 19 GND NC2 6 19 GND LXC900A-C-CE
FR L (+) 7 18 RST L (+) 7 18 RST
INPUT COM RST PWR ENBL 8 17 8
RS485
+ 17 LXC900A-V-CE
CON- CON-
OFF N 9 10 11 12 13 14 15 16 FIG N 9 10 11 12 13 14 15 16 FIG
1 2 3 4 5
ON PRODUCT CODE SUPPLY VOLTAGE CERTIFICATION
24-260V AC
XTC5400
90 to 270V AC/DC
XC3200-C XTC5400-CU RoHS C
®

XC3200
US
m

XC3200-C
11

12
10

15
13

14

11
1

12
10

13

15
14
1
2

9
4

9
4

8
CNT 1

CNT 2

CNT 1

CNT 2
GND

GND

GND

GND
+12V

+12V

XC3200
NPN

PNP

NPN

PNP
CONFIG

CONFIG

.co
RS485

90 to 270V AC/DC
FILTER

FILTER
RST

RST

XC2200-C
XC2200
u
COM1

COM2

COM1

COM2
NO1

NO2
NC1

NC2

L (+)

NO1

NO2
NC1

NC2

L (+)
N

ia
21

21
22
16

17

18

19

20

25

29
23

24

26

27

28

30

22
19
16

17

18

20

25

29
23

24

26

27

28

30

Dimensions (All are in mm)


ha

LXC900A XC2200 / XC2200-C 3


en
21.9
24

22.5

72 91 61 67
48 48 45.5
Front bezel 4 Side view Panel cutout 72 67
di

3 74
XTC5400 XC3200 / XC3200-C 13
Co

48 45 46 90.5
96 55 90.5

48 100 46
7 Side view Panel cutout 96 45.5 90.5
Front bezel 13

40 www.selec.com COUNTERS
RATE INDICATORS

RC5100 RC2100 RC100 RC102C


Size : 48 x 48mm Size : 72 x 72mm Size : 48 x 96mm Size : 48 x 96mm

! Measures upto 9999 RPM ! 6 Digits Counter


! Inbuilt Sensor Supply ! 4 Digits Rate Indicator
! Programmable Input Scaling
FEATURES ! Inbuilt Senor Supply

DISPLAY 4 digits Count : 6 digits, Rate : 4 digits


Count : 0.01 to 999999
RANGE 4.00 to 9999 RPM Rate : 4.00 to 9999 RPM
RESET --- Front, Remote

SET POINT ---

RELAY RATING ---

INPUT SPEED 4 to 9999 pulses per minute a) 0 to 30Hz, b) 0 to 2.5kHz

--- 0.00001 to 9.99999 X 10n.


SCALE FACTOR n = -3, -2, -1, 0, 1, 2
SENSOR TYPE PNP PNP / NPN PNP PNP / NPN
SENSOR SUPPLY Inbuilt, 12V DC, ±10%, 30mA.

COUNTING DIRECTION Unidirectional (Up)


INPUT TYPE Voltage Pulse : a) 3 to 30V DC from proximity switches, encoder solid state devices, b) Potential free contacts.

SUPPLY VOLTAGE 90 to 270V AC/DC


(AC : 50 / 60 Hz)

Terminal Connections Dimensions (All are in mm)


RC5100A RC102C RC100C, RC102C
SENSOR
+12V GND CNT SELECTION
NPN PNP COM FILTER CONFIG 48 45 46
+12V RST
1 2 3 4 5
96 88 92
1 2 3 4 5 6 7 8 9 10
Front bezel 10 Side view Panel cutout
CNT
11 12 22 24
21 23 RC2100
6 7 8 9 10 11 12 13 14 15 16 17 18 N L
L N 72 68 69
- - +
+

72 115 69
RC2100 RC100C Front bezel 10 Side view Panel cutout
CNT +12V GND
1 2 3 4 5 6 RC5100A
+12V CNT GND
1 2 3 4 5 6 7 8 9 10
48 45 46
m

22 24
13 L 15
21 23 48 100 46
.co

14 N 16 Front bezel 7 Side view Panel cutout


11 12 13 14 15 16 17 18 N L
- +
7 8 9 10 11 12
Ordering Information
u

PRODUCT CODE SUPPLY VOLTAGE CERTIFICATION


ia

RC100C 90 to 270V AC/DC


RC102C-CE
ha

90 to 270V AC/DC
RC102C-CU
®

RoHS C US

RC5100A 90 to 270V AC/DC


en

RC2100 90 to 270V AC/DC


di
Co

41 www.selec.com RATE INDICATORS


TEMPERATURE CONTROLLERS

Temperature Controllers - PID


Temperature Controller - Profile
Temperature Controllers
Temperature Controller - Analog
Cooling Controller
Process Indicators

Applicable EMI / EMC standards


Product standard : IEC 61326-1

Category Standards Compliance


m

ESD Immunity IEC 61000-4-2 Level III


+/- 2 kV common mode,
.co

Surge Immunity IEC 61000-4-5


+/- 1 kV differential mode
Level III, 80 to 1000MHz
Radiated Susceptibility IEC 61000-4-3 Level II, 1.4GHz to 2GHz
u

Level I, 2GHz to 2.7GHz


ia

Conducted Susceptibility IEC 61000-4-6 Level II


ha

Dips : 0% residual voltage /1 cycle (Criteria B.),


Voltage Dips and 40% residual voltage /10 cycles 50 Hz / 12 cycles 60 Hz (Criteria C)
IEC 61000-4-11
Interruptions 70% residual voltage / 25 cycles 50 Hz / 30 cycles 60 Hz (Criteria C)
en

Interruptions : 0% residual voltage / 250 cycles 50 Hz / 300 cycles 60 Hz (Criteria C)


di

Conducted Emission CISPR-11

Radiated Emission CISPR-11


Co

Electrical Fast Transient IEC 61000-4-4 Level II

Note : Above standards are applicable only for CE certified Temperature Controllers
42 www.selec.com
PID Profile

PID500 PID110 PID330 PR502


Size : 48 x 48mm Size : 96 x 48mm Size : 96 x 96mm Size : 48 x 48mm

! Universal Inputs ! Ramp / Soak Control


! Ramp Soak ! 10 Programs, 16 Steps Each
FEATURES ! Max 3 Output ! Alarm at Each Stage
! Retransmission (Optional) ! Memory Retention
! RS485 Communication MODBUS RTU Protocol (Optional)

DISPLAY 4 + 4 digits, 7 segment LED Dual display


Thermocouple: J, K, T, R, S, C, E, B, N, L, U, W, Platinel II RTD: Pt100
INPUT TYPE Signal Inputs (DC): -5 to 56 mV, 0 to 10 V DC, 0 to 20 mA DC
0
RESOLUTION TC / RTD : 1 / 0.1 ; Analog input :1 / 0.1 / 0.01 / 0.001
0 0

ACCURACY For TC input : 0.25% of F.S. ±1 ; For R & S inputs : 0.5% of F.S. ±2 (20 min of warm up time) ;
For RTD input : 0.1% of F.S. ±10; Cold junction accuracy ± 50C ; Signal input : ±0.5%, ± 1 digit

SET POINT Maximum 3

CONTROL MODE Autotune PID or ON - OFF

CONTROL OUTPUT Relay : 5A @ 230V AC / 30V DC or SSR : 18V DC, 20mA or Current : 0/4 to 20 mA DC (max load 500E) or Voltage : 0 to 5/10V DC (min load 10K) (Depends on product code selection)

AUXILIARY OUTPUT (Maximum 2) Relay or SSR (Mode: Set point or Alarm mode) Relay : 5A @ 230V AC / 30V DC ; SSR : 12V DC,20mA
No. of Profiles : 10 (16 steps each), Ramp / Soak
Extra alarm output (relay3), RS485 Communication MODBUS RTU protocol Time Range : 0.01 to 99.59 Hrs,
Retransmission analog output Other Profile Parameters : Link profiles,
OPTIONAL FEATURES Programmable repeat cycle, Power down resume, Reset option,
Deviation hold, Alarm at each step with settable alarm duration,
Retransmission analog output
SUPPLY VOLTAGE 85 to 270V AC / DC
(AC : 50 / 60 Hz)

Terminal Connections
PID500 PR502 PID110 / 330 RTD3
TC +/RTD1

+ 11
TC /RTD2

L (+) 6 (-) N
-

1
mV +

V RS485
-
mV

+
RS485 TC +/RTD1
NO2 Ana IP + 1 2 3 4 5 7 8 9 10
2 7 6
+ - 12
SSR2

+
- SSR1/ MI / CT / R-SP
3 13 8 - ANA OP SSR2 SSR3
COM2 TC /RTD2 N L
+

Ana IP
-
NO3
0 -10 V/4 -20mA

NO1 + 14 11 12 13 14 15 16 17 18 19 20
SSR1/ 0-5 V/

+ 4 9
RTD3
SSR3

-
+
- 5 - 15 10 NO1 COM1 NO2 COM2 NO3 COM3
COM1 COM3

Dimensions ( All are in mm )


PID500 / PR502 PID330 PID110

48 45 45 96 90 92 96 92
90

48 7 100 45 96 10 74.5 92 48 10 74.5 45


Front bezel Side view Panel cutout Front bezel Side view Panel cutout Front bezel Side view Panel cutout
m

PID500 / PID110 / PID330


.co

OUTPUT 3
PRODUCT CODE OUTPUT 1 OUTPUT 2 SUPPLY VOLTAGE CERTIFICATION
RELAY / SSR COMMUNICATION (RS485)
PID500-0-0-00 V2 RELAY RELAY -- -- 85-270V AC / DC
PID500-0-0-01 V2 RELAY RELAY RELAY -- 85-270V AC / DC
u

PID500-0-0-04 V2 RELAY RELAY RELAY YES 85-270V AC / DC


ia

PID500-1-0-00 V2 SSR RELAY -- -- 85-270V AC / DC


PID500-2-0-00 V2 4-20mA RELAY -- -- 85-270V AC / DC
ha

PID500-2-0-01 V2 4-20mA RELAY RELAY -- 85-270V AC / DC


PID500-2-0-04 V2 4-20mA RELAY RELAY YES 85-270V AC / DC
PID500-3-0-00 V2 0 - 10V RELAY -- -- 85-270V AC / DC
en

PID330-0-0-01 V2 RELAY RELAY RELAY -- 85-270V AC / DC --


PID330-2-0-01 V2 4-20mA RELAY RELAY -- 85-270V AC / DC --
-- --
di

PID110-0-0-01 V2 RELAY RELAY RELAY 85-270V AC / DC

PR502
Co

PRODUCT CODE OUTPUT 1 OUTPUT 2 SUPPLY VOLTAGE CERTIFICATION


PR502-0-0-0 RELAY RELAY 85-270V AC / DC
PR502-2-0-0 4-20mA RELAY 85-270V AC / DC

43 www.selec.com TEMPERATURE CONTROLLERS


Temperature Controllers

TC544A TC244AX TC344AX TC513AX TC203AX TC303AX TC533AX


Size : 48 x 48mm Size : 72 x 72mm Size : 96 x 96mm Size : 48 x 48mm Size : 72 x 72mm Size : 96 x 96mm Size : 48 x 48mm

! Dual Display, Dual Setpoint ! Single Display, Single Setpoint ! Dual Display, Single Setpoint
! TC / RTD inputs ! TC / RTD inputs ! TC / RTD inputs
FEATURES
! Control Output : Relay or SSR ! Control Output : Relay or SSR ! Control Output : Relay or SSR
! Auxiliary Output : Relay
! Dwell Timer , Heat Cool PID

DISPLAY 4 + 4 digits, 7 segment LED Dual display 3 digits, 7 segment LED Single display 3 + 3 digits, 7 segment LED Dual display

INPUT TYPE Thermocouple (J,K,T,R,S) / RTD (Pt100)


0
0.1 / 1 for TC / RTD
RESOLUTION (fixed 10 for R & S TC) Fixed 10 resolution

0 0
For TC inputs : 0.25% of F.S. ±1 ; For R & S inputs : 0.5% of F.S. ±2
ACCURACY (20 min of warm up time); For RTD input : 0.1% of F.S. ±10

SETPOINT 2 1

CONTROL MODE Autotune PID or ON - OFF


Relay : 5A resistive @ 230V AC / 30V DC or
CONTROL OUTPUT SSR (Field Selectable) : 12V DC,50mA Relay : 10A resistive @ 230V AC / 30V DC or SSR : 12V DC,50mA

AUXILIARY OUTPUT Relay : 5A resistive @ 230V AC / 30V DC --

SPECIAL FUNCTIONS Heat cool PID


Dwell timer --

SUPPLY VOLTAGE 85 to 270V AC / DC,


(AC : 50 / 60 Hz) 24V AC / DC (optional) 85 to 270V AC / DC

Terminal Connections
TC544A TC244AX TC344AX TC513AX / TC533AX TC203AX / TC221A TC303AX / TC303A
TC+/RTD1 TC+/RTD1 TC+/RTD1
TC+/RTD1 TC+/RTD1 L (+) 1 10
TC+/RTD1 L (+) 1 8 L (+) 1 10
L (+) 1 11 6 L (+) 1 8 L (+) 1 11 6
N (-) 2 11 N (-) 2 11
N (-) TC-/RTD2 N (-) 2 9 TC-/RTD2
SSR1+ 2 9 TC-/RTD2
N( ) 2 7 TC-/RTD2 3 12 N( ) 3 12
NO2 RTD3 2 7 3 10 RTD3
-
TC /RTD2 + NO2 -
3 10 4 + 13 TC /RTD2 RTD3 4 13
NO2 RTD3
3 + 8 NC 4 11
COM2 4 11 COM2 5 3 8 5 14
-

14
RTD3
-

RTD3 NC +
NC2
5 12 6 15
NC2 + 6 15
SSR

5 12 NO NO NC
4 9
-

4 9
SSR

NO1 +
COM2 SSR1- NO1 6 13 7 16

SSR
7 16 +
-

NO
6 13
SSR1

NO1 8
-

17

-
5 12 10 COM1 COM1 8 17 7 14
-

7 14 5 12 10 COM 9 18
COM1 NC1 NC1 COM COM
9 18
SSR *NC valid for TC203AX *NC valid for TC303AX
+

Dimensions ( All are in mm )


TC544A / TC513AX / TC533AX TC244AX / TC203AX / TC221A TC303AX / TC303A / TC344AX

52 45 46 72 67 69 96 90.5 92
m

52 4 94 46 72 4.5 83.7 69 96 5 73 92
Front bezel Side view Panel cutout Front bezel Side view Panel cutout Front bezel Side view Panel cutout
.co

Ordering Information
PRODUCT CODE OUTPUT 1 OUTPUT 2 SUPPLY VOLTAGE CERTIFICATION PRODUCT CODE OUTPUT SUPPLY VOLTAGE CERTIFICATION
u

TC544A RELAY SSR RELAY 85-270V AC / DC TC513AX RELAY SSR 85-270V AC / DC


ia

TC544A-24V RELAY SSR RELAY 24V AC / DC TC533AX RELAY SSR 85-270V AC / DC


TC244AX RELAY SSR RELAY 85-270V AC / DC TC203AX RELAY SSR 85-270V AC / DC
ha

TC244AX-24V RELAY SSR RELAY 24V AC / DC TC303AX RELAY SSR 85-270V AC / DC


TC344AX RELAY SSR RELAY 85-270V AC / DC TC303A RELAY SSR 85-270V AC / DC
TC344AX-24V
en

RELAY SSR RELAY 24V AC / DC


di
Co

44 www.selec.com TEMPERATURE CONTROLLERS


Temperature Controllers

TC518 PID528 DTC204A-2 DTC324A-2


Size : 48 x 48mm Size : 48 x 48mm Size : 72 x 72mm Size :96 x 96mm

! Dual Display, Single Setpoint ! Dual Display, Dual Setpoint ! Single Display, Dual Setpoint
! TC / RTD inputs ! TC / RTD inputs ! TC / RTD inputs
! Control Output : Relay or SSR ! Control Output : Relay or SSR ! Control Output : Relay or SSR
FEATURES
! Auxiliary Output : Relay ! Auxiliary Output : Relay

DISPLAY 4 + 4 digits, 7 segment LED display 4 digits, 7 segment LED display


INPUT TYPE Thermocouple (J,K,T,R,S) / RTD (PT 100)

RESOLUTION 0.1/10 for TC/ RTD inputs (fixed 10 for R & S type TC input)
For TC inputs : 0.25% of F.S. ±10 ; For R & S inputs : 0.5% of F.S. ±20
ACCURACY (20 min of warm up time); For RTD input : 0.1% of F.S. ±1
0

SETPOINT
CONTROL MODE Autotune PID or ON - OFF

Relay : 10A resistive @ 230V AC / 30V DC Relay : 5A resistive @ 230V AC / 30V DC Relay : 10A resistive @ 230V AC / 30V DC
CONTROL OUTPUT Optional SSR : 18V DC, 20mA Optional SSR : 18V DC,30mA or SSR : 12V DC,30mA
AUXILIARY OUTPUT Relay : 5A resistive @ 230V AC / 30V DC
SUPPLY VOLTAGE 85 to 270V AC / DC
(AC : 50 / 60 Hz)

Terminal Connections
TC518 PID528 DTC204A-2 DTC324A-2

TC+/RTD1
L (+) 1 6 TC+/RTD1 L (+) 1 10
L (+) 1 8
(+) (-) N (-) 2 11
TC +/RTD1 N (-) 2 9 TC-/RTD2
N (-) 2 7 TC-/RTD2 3 12
NO2 RTD3
3 10 NO2
RTD3 4
SSR2

NO 13
3 8 TC /RTD2
- COM2 4 11 COM2 5 14
SSR

NC2 5 12 +
COM NC2 6 15
4 9
SSR

RTD3 NO1 NO1


6 13 7 16 +
SSR1

SSR
5 10 7 14 COM1 8 17

-
NC COM1 NC1
NC1 9 18

Dimensions ( All are in mm )


TC518 / PID528 DTC204A-2 DTC324A-2

48 45 46 72 67 69 96 90.5 92
m

48 11.5 100 46 72 4.5 83.7 69


96 5 73 92
Front bezel Side view Panel cutout Front bezel Side view Panel cutout Front bezel Side view Panel cutout
.co

Ordering Information
u

PRODUCT CODE OUTPUT 1 OUTPUT 2 SUPPLY VOLTAGE CERTIFICATION


ia

TC518 V2 RELAY -- -- 85-270V AC / DC in process

TC518-SSR V2 -- SSR -- 85-270V AC / DC in process


ha

PID528-1 V2 RELAY -- RELAY 85-270V AC / DC in process

PID528-2 V2 -- SSR RELAY 85-270V AC / DC in process


en

DTC204A-2 RELAY SSR RELAY 85-270V AC / DC --


DTC324A-2 RELAY SSR RELAY 85-270V AC / DC --
di
Co

45 www.selec.com TEMPERATURE CONTROLLERS


Temperature Controllers

New

New New New

TC544B TC513BX TC533BX DTC331


Size : 48 x 48mm Size : 48 x 48mm Size : 48 x 48mm Size : 96 x 96mm

! Dual Display, Dual Set Point ! Single Display, Single Set Point ! Dual Display, Single Set Point ! 3 Digit Single Display
! Short Depth TC ! Short Depth TC ! Short Depth TC ! J, K TC input
! TC / RTD input ! TC / RTD input ! TC / RTD input ! ON-OFF Control
FEATURES ! Control Output : Relay or SSR ! Control Output : Relay or SSR ! Control Output : Relay or SSR ! Economical TC
! Dwell Timer, Heat Cool PID

DISPLAY 4 + 4 digits, 7 segment LED dual display 3 digits, 7 segment LED single display 3 + 3 digits, 7 segment LED dual display 3 digits, 7 segment single display

INPUT TYPE Thermocouple (J,K,T,R,S) / RTD (PT 100) Thermocouple (J,K)


0
0.1 / 1 for TC / RTD inputs
RESOLUTION Fixed 10 resolution Fixed 10 resolution
(fixed 10 for R & S type TC input)
0
For J,K & T TC inputs : 0.25% of F.S ±1 ;
ACCURACY 0
For R & S inputs : 0.5% of F.S. ±2 (20 min of warm up time for TC inputs); 0.25% of F.S. ±10 (20 min warm up time)
0
For RTD input : 0.1% of F.S ±1

SETPOINT

CONTROL MODE Auto tune / self tune PID or ON-OFF ON-OFF

Relay : 5A resistive @ 230V AC / 30V DC Relay : 10A resistive @ 230V AC / 30V DC or Relay : 10A resistive @ 230V AC / 30V DC
CONTROL OUTPUT or SSR : 12V DC,30mA SSR : 12V DC,50mA

AUXILIARY OUTPUT Relay : 5A resistive @ 230V AC / 30V DC

SPECIAL FUNCTIONS Heat Cool PID, Dwell timer

SUPPLY VOLTAGE 85 to 270V AC / DC


(AC : 50 / 60 Hz)

Terminal Connections
TC544B TC513BX TC533BX DTC331

TC+/RTD1 TC+/RTD1
L (+) 1 11 6 L (+) 1 11 6

N( ) 2 7 N( ) 2 7
TC /RTD2
-
TC /RTD2
-

NC NC
3 8 3 8
RTD3 RTD3
NO NO
4 9 4 9

5 12 10 5 12 10
COM COM
SSR - SSR
+
+

Dimensions ( All are in mm )


m

TC544B / TC513BX / TC533BX DTC331


.co

52 45 46 99 90.5 90.5

52 46 38.8
4 76 99 3 90.5
u

Front bezel Side view Panel cutout Front bezel Side view Panel cutout
ia

Ordering Information
ha

PRODUCT CODE OUTPUT 1 OUTPUT 2 SUPPLY VOLTAGE CERTIFICATION


TC544B RELAY SSR RELAY 85-270V AC / DC
en

TC533BX RELAY SSR -- 85-270V AC / DC in process


TC513BX RELAY SSR -- 85-270V AC / DC in process
di

DTC331 RELAY -- -- 85-270V AC / DC --


DTC231 RELAY -- -- 85-270V AC / DC --
Co

46 www.selec.com TEMPERATURE CONTROLLERS


Analog

TC52
Size : 48 x 48mm / Panel Cutout : 46 x 46

! Features:
! Dial setting
! TC Inputs
FEATURES ! Single relay output
! Easy to use

DISPLAY Dial Setting


INPUT TYPE Thermocouple (J,K)
o
RESOLUTION Fixed 1 resolution

ACCURACY
Setting ± 3% of full scale
±0.5% of full scale
SETPOINT 1
CONTROL MODE Time Proportional & ON-OFF
CONTROL OUTPUT 7A resistive @ 230V AC
SUPPLY VOLTAGE 230V AC
(AC : 50 / 60 Hz)

Terminal Connections Dimensions ( All are in mm )


TC52
TC52

48 45 46

48 7 100 46
Front bezel Side view Panel cutout

Ordering Information

PRODUCT CODE OUTPUT SUPPLY VOLTAGE

TC52-400-J-230 RELAY 230V AC


m
u .co
ia
ha
en
di
Co

47 www.selec.com TEMPERATURE CONTROLLERS


Cooling Controller

CH403A CH403
Size : 36 x 72mm Size : 36 x 72mm

! 2½ Digit ! 3 Digit
! Defrost Management ! Defrost Management
! High / Low Temperature Alarms ! High / Low Temperature Alarms
FEATURES ! Control Output : Relay ! Control Output : Relay
! Auxiliary Output : Relay & SSR ! Auxiliary Output : Relay & SSR

DISPLAY 2½ digits, 7 segment display 3 digit, 7 segment display

INPUT TYPE NTC type sensor

RESOLUTION 1 / 0.10
ACCURACY 0.25% of full scale ±10 ±1% of F.S.
SETPOINT 1

CONTROL MODE ON - OFF

CONTROL OUTPUT 10A @ 230V AC / 30V DC or 20A @ 230V AC / 30V DC (Depends on product code selection)
AUXLIARY OUTPUT 12V DC, 10mA or 5A @ 230V AC / 30V DC (Depends on product code selection)
0
HYSTERESIS 0.1 to 9.9
0 0
DISPLAY OFFSET -19.9 to 19.9 -19.90 to 20.00

RESTART TIME DELAY Adjustable from 0 to 19.9 min

RELAY ACTION Heat & Cool Mode


DEFROST TIME Programmable from 0 to 99 min

DEFROST FREQUENCY Programmable from 0 to 99 (hr / min /sec)


SUPPLY VOLTAGE 230V AC, 85 to 270 V AC / DC 85 to 270V AC / DC, 24V AC / DC
(AC : 50 / 60 Hz)

Terminal Connections Ordering Information


CH403A-1-NTC CH403A-2-NTC OUTPUT
PRODUCT CODE SUPPLY CERTIFICATION
CONTROL ALARM VOLTAGE
1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12 OUTPUT OUTPUT
CH403A-1-NTC RELAY SSR 230V AC --
DI
L N SENSOR DI L N
NO NC COM SSR SSR SENSOR COM NO -- 85 to 270V AC --
+ - CH403A-2-NTC RELAY
/ DC
(ALARM)
CH403A-3-NTC RELAY RELAY 230V AC --

CH403A-3-NTC CH403-1-NTC CH403A-1-NTC-CE RELAY SSR 230V AC


85 to 270V AC
CH403A-2-NTC-CE RELAY --
/ DC
1 2 3 4 5 6 7 8 9 10 11 12 CH403A-3-NTC-CE RELAY RELAY 230V AC
85 to 270V AC
CH403-1-NTC RELAY
m

DI SSR / DC
L N
NO NC COM NO COM SENSOR 85 to 270V AC
CH403-2-NTC RELAY --
/ DC
(ALARM)
.co

85 to 270V AC
CH403-3-NTC RELAY RELAY
/ DC
CH403-2-NTC CH403-3-NTC SSR
CH403-1-24 RELAY 24V AC / DC
u
ia
ha

Dimensions ( All are in mm )


en

CH403A CH403
Panel Cutout
di

28.6
Co

Front bezel Side view

48 www.selec.com TEMPERATURE CONTROLLERS


Process Indicators

PIC152A-VI PIC101N PIC101A-T-230 PIC501A-VI-230 PIC101A-VI-230


Size : 48 x 96mm Size : 48 x 96mm Size : 48 x 96mm Size : 48 x 48mm Size : 48 x 96mm

! TC / RTD / Analog input ! TC / RTD / Analog input ! Simple Temperature Indicator ! Scalable Analog input
! 2 Alarm Output ! Basic Scalable Indicator ! TC / RTD input type ! Voltage / Current input type
FEATURES ! Retransmission
! RS485 Communication
MODBUS RTU Protocol (optional)

DISPLAY 4 digits, 7 segment LED

Thermocouple : J, K, T, R, S Thermocouple : J, K, T, R, S
RTD : Pt100 RTD : Pt100 Thermocouple : J, K, T, R, S Signal Inputs (DC) :
INPUT TYPE Signal Inputs (DC) : -5 to 56mV, Signal Inputs (DC) : RTD : Pt100 0 to 10V, 0/4 to 20mA
0 to 10V, 0/4 to 20mA 0 to 56mV, 0 to 10V, 0/4 to 20mA

TC / RTD : 1 / 0.1, Analog input : 1 / 0.1 / 0.01 / 0.001 0 0 Decimal Point position
RESOLUTION 1 / 0.1 (Fix 1 resolution for R & Stype TC)
selectable : 1/0.1/0.01/0.001

For TC inputs : 0.25% of F.S. ±10; For TC inputs : 0.25% of F.S. ±1 ;


0

For R & S inputs : 0.5% of F.S. ±20 (20 min of warm up time) ; For R& S input : 0.5% of F.S. ±20 Signal input : ±0.5%
ACCURACY 0
For RTD input : 0.1% of F.S. ±1 ; (20 min of warm up time); of F.S. ± 1 digit
Cold junction accuracy ± 50C ; Signal input : ±0.5% of F.S, ± 1 digit RTD input : 0.1% of F.S. ±10
2 Alarms : 5A @ 230V AC / 24V DC
OUTPUT Alarm modes : High, Low, Band, --
Fail output & fault diagnosis.
Hysteresis, Annunciator : Programmable,
Reset action : Automatic or latched
Retransmission output : 0/4 to 20mA DC,
OPTIONAL 0 to 5V DC, 0 to 10V DC,
FEATURES RS485 Communication --
MODBUS RTU Protocol (optional)
SENSOR SUPPLY 24V DC output to power the sensor, 30mA --
SUPPLY VOLTAGE
85 to 270V AC / DC, 24V DC (optional) 230V AC, ±20%
(AC : 50 / 60 Hz)

Terminal Connections
PIC152A-VI PIC152A-VI PIC101N mV/TC/RTD
+ -
( ( 4 V mA CONFIG
A B B’ + - + -
I

I
I

1 2 3 4 5 6 7 8 9 10
22 24
21 23
11 12 13 14 15 16 17 18 N L
+24V GND
~ sensor supply - +

PIC101A-T-230 PIC101A-VI-230 PIC501A-VI-230


TC / RTD
- + N L
+ V mA
N L
+

A
+
B’ B
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
m

Short Short 21 22
21 for TC for RTD 22
11 12 13 14 15 16 18 19 20
.co

17
11 12 13 14 15 16 17 18 19 20

Dimensions ( All are in mm )


PIC101N PIC152A-VI / PIC101A-VI-230 / PIC101A-T-230 PIC501A-VI-230
u
ia

50 45 46 50 45 46 52 45 46

52
ha

97.5 88 92 98 76 92 4 76 46
10 3
Front bezel Side view Panel cutout Front bezel Side view Panel cutout Front bezel Side view Panel cutout

Ordering Information
en

COMMUNICATION PRODUCT CODE SUPPLY VOLTAGE


PRODUCT CODE RETRANSMISSION (RS485) SUPPLY VOLTAGE CERTIFICATION
PIC101A-T-230 230V AC
di

PIC101N -- -- 85-270V AC / DC PIC101A-VI-230 230V AC


PIC101N-24V -- -- 24V AC / DC PIC501A-VI-230 230V AC
PIC152A-VI Universal -- 85-270V AC / DC in process
Co

PIC152A-VI-24V Universal -- 24V AC / DC in process


PIC152A-VI-C Universal YES 85-270V AC / DC in process
PIC152A-VI-C-24V Universal YES 24V AC / DC in process

49 www.selec.com TEMPERATURE CONTROLLERS


PLCs & HMI

Flexible IO Solution
Compact Series
Fixed I/O Solution
HMI

Applicable EMI / EMC standards


Product standard : IEC61131-2
Category Standards Compliance
m

ESD Immunity IEC 61000-6-2 Level III


+/- 2kV common mode,
Surge Immunity
.co

IEC 61000-6-2
+/- 1kV differential mode
Level III, 80 to 1000MHz
Radiated Susceptibility IEC 61000-6-2 Level II, 1GHz to 2GHz
u

Level I, 2GHz to 2.7GHz


ia

Conducted Susceptibility IEC 61000-6-2 Level II


ha

Voltage Dips and IEC 61000-6-2 0%, 0.5 Periods (Criteria A)


Interruptions 0%, 250/300 Periods (Criteria C)
40%, 10/12 Periods (Criteria C)
en

70%, 25/30 Periods (Criteria C)


80%, 250/300 Periods (Criteria C)
CISPR 16-2-1
di

Conducted Emission Criteria B


CISPR 16-1-2
Radiated Emission CISPR 16-2-3 Criteria A
Co

Electrical Fast Transient IEC61000-6-2 Level III

Note : Above standards are applicable only for CE certified PLCs & HMI

50 www.selec.com
Flexible IO Solution

FLEXYS GT35 FLEXYS PANEL TX4 FLEXYS RAIL


Size : 99 x 95.6 x 90.5mm Size : 99 x 95.6 x 90.5mm Size : 140 x 93.4 x 72mm
! 3.5" LCD with Touch Screen ! PLC with built in HMI ! PLC with Flexible I/O Card Selection
! Flexible I/O Card selection ! Flexible I/O Card selection ! Real Time Clock
! Real Time Clock ! Real Time Clock ! Expandable
FEATURES
! Expandable ! Expandable

TFT 3.5" diagonal Touch screen, Resolution 320x240 LCD with Backlight, 4x16 Character display, 7 segment display for slot number & card status.
DISPLAY
Font size 5x7mm Multipurpose LED Bank
NO. OF KEYS 5 function keys +1 System Key 18 keys (14 user configurable) One key to scroll through different slots

I/Os 3 I/O slots (Please refer I/O card for Flexys series) 4 I/O slots (Please refer I/O card for Flexys series)
DIGITAL INPUTS 4 / 10 /14 per card, PNP (6 to 30V DC)
MAXIMUM COUNTING
FC0 (I0 & I1) & FC1 (I2 & I3) - 5KHz (on power supply card only), Normal Digital Inputs - 30Hz
FREQUENCY
ANALOG INPUTS 3 / 4 / 6 Channels per card (TC, RTD, 0-10V, 0 to 20mA)
RESOLUTION 12 Bit
RELAY OUTPUTS 4 / 8 per card, NO type 5A @ 230V AC / 30V DC (Resistive)
TRANSISTOR OUTPUTS 8 per card, Source type 100mA @ 24V DC
ANALOG OUTPUTS 2 / 4 Channels per card (0 - 10V, 0 - 20mA)
RESOLUTION 14 Bit (0.0 to 100.0% = 0 to 10.000V, 0.0 to 100.0% = 0 to 20.000mA)
PROGRAM MEMORY 221K 351K
EXPANSION Yes
COMMUNICATION
RS485 MODBUS RTU Protocol RS485 MODBUS RTU, Proprietary Protocol
INTERFACE
RTC Yes
SUPPLY VOLTAGE 24V DC, 230V AC 50 / 60Hz

Terminal Diagram
Flexys panel TX4 with DI10, RO08, AI06-I, TO08 & 230V Terminal Diagram Flexys Rail with DI10, RO08, AI06-I, TO08 & 24V Terminal Diagram

m
.co

Dimensions (All are in mm) Ordering Information


PRODUCT CODE CERTIFICATION
u

FL–GT35–DI04-PS-230V ---
ia

---
90.5

FL–GT35–DI04-PS-24V
99

Front bezel Side view


92

FL–GT35–DSP ---
ha

FL-GT35-LG-1-0-1 ---
99 95.55 92
9 FL–TX4–DI04–PS–230V-CE RoHS
en

Flexys Rail I O Plate IO Plate IO Plate Common


FL–TX4–DI04–PS–24V-CE RoHS
9.4 9.4
140 72
FL-TX4-LG-1-1-1-CE RoHS
di

FL–RL–DI04–PS-24V-CE RoHS
93.6

93.6
76

FL-RL-BS-6-CE RoHS
Co
17.6

27.17 21.85 21.85 FL-RL-LG-1-1-1-CE RoHS


PS LG
FL-RL-PS-230V ---

51 www.selec.com PROGRAMMABLE LOGIC CONTROLLER


Add ons - PLC IO's

ORDER CODE DESCRIPTION TERMINAL CONNECTION CERTIFICATION

I9

I8

I7

I6

I5

I4

I3

I2

I1

I0
10DI (10 Digital Inputs) RoHS
FL-SC-DI10-CE

I12
I13

I11
I10

I0
I1
I6
I9

I5
I8

I4
I7

I3
I2
14DI (14 Digital Inputs) RoHS
in process
FL-SC-DI14

R3

R2

R1

RO

I3

I2

I1

I0
C
4 Digital Inputs & 4 Relay Outputs RoHS
in process
FL-SC-DI04-RO04

V5

V4

V3

V2

V1

V0
+
+

+
+
+

+
6 Analog Inputs (0-10V) RoHS
FL-SC-AI06-V-CE

I5

I4

I3

I2

I1

I0
+
+

+
+
+

+
6 Analog Inputs (0-20mA) RoHS
FL-SC-AI06-I-CE

NTC

TC3

TC2

TC1

TC0
+

+
-

-
4 Channel Thermocouple Analog
Inputs Differential type RoHS
FL-SC-AIDF04-TC
C1

R7

R6

R5

R4

C0

R3

R2

R1

R0
8 Relay Outputs RoHS
FL-SC-RO08-CE
+24
GND
T0
T7

T4
T6

T5

T3

T2

T1

8 Transistor Outputs RoHS


FL-SC-TO08-CE
V0
V3
+

+
V2

V1
-

-
O

4 Analog Outputs (0-10V) RoHS


FL-SC-AO04-V-CE
I3
+

I2
+

I1
+

I0
+
-

-
O

4 Analog Outputs (0-20mA) RoHS


FL-SC-AO04-I-CE
SO

SO+

E+
S3

S3+

S2

S2+

S1

S1+

4 Channel Load Cell Card RoHS


in process
.co

FL-SC-LC04
NTC
I2
I2+

I1

I0
I1+

I0+
O1+

O0+
R32

R31

R30
O

3 Universal Analog Inputs, RoHS


2 Universal Analog Outputs in process
ia

FL-SC-AI03-U-AO02-U
O

ha
I3
I3+

I2
I2+

I1

I0
I1+

I0+
NTC

R33

R32

R31

R30

RoHS
4 Universal Analog Inputs in process
en
di
Co

52 www.selec.com PROGRAMMABLE LOGIC CONTROLLER


Compact Series

New New

DIGIX-1 DIGIX-1-1-1-230V DIGIX-2-1-0-24VDC DIGIX-4-1-1-24VDC


Size : 70 x 90mm Size : 70 x 90mm Size : 70 x 90mm Size : 70 x 90mm
! Compact PLC with built in HMI
! 2 Line 8 Character LCD
! Real Time Clock
FEATURES
! RS485 Communication MODBUS RTU Protocol

DISPLAY 2 X 8 Character LCD


NO. OF KEYS 5 keys (4 - User configurable)
DIGITAL INPUTS 8 10 + 2* 10
INPUT TYPE PNP (6 - 30V DC)
MAXIMUM COUNTING FC0 (I0 & I1) - 5KHz, Normal Digital Input: 30Hz
FREQUENCY

2 Channels
ANALOG INPUTS (0 to 10V)
NA Through Expansion Through Expansion
RESOLUTION 12 Bit

DIGITAL OUTPUTS 5 Relay 8 Relay 6 Transistor

TYPE & RATING 5A NO type @ 230V AC / 30V DC (Resistive) Source 100mA @ 24V DC

ANALOG OUTPUTS Through Expansion


NA
RESOLUTION As per expansion model

RTC NO YES NO YES

EXPANSION NO YES

PROGRAM MEMORY 112K 240K

COMMUNICATION
RS485 Modbus RTU Protocol
INTERFACE
18 to 30V DC**, 100 to 270V AC / DC
SUPPLY VOLTAGE 100 to 270V AC / DC 18 to 30V DC
50 / 60Hz. 50 / 60Hz.

*Voltage Analog Inputs can be configured as Digital Inputs **Please refer Datasheet for exact Order code

Terminal Diagram
DIGIX-1 & DIGIX-1-1-1-230V DIGIX-2-1-0-24VDC DIGIX-4-1-1-24VDC
+
DI11/AI1
+

DI10/AI0
+

DI9
m

DI8
DI7
DI6
.co

DI5
DI4
24V Model DI3
0V
DI2
u

+24V FC0
DI0
Master RS485 is available only in DIGIX-1-1-1-230V
ia

Dimensions (All are in mm) Ordering Information


ha

PRODUCT CODE --
CERTIFICATION
DIGIX-1-230V --
en

DIGIX-1-0-0-24V --
DIGIX-1-1-1-230V --
di

DIGIX-2-1-0-24VDC --
DIGIX-4-1-1-24VDC --
Co

53 www.selec.com PROGRAMMABLE LOGIC CONTROLLER


Compact Series

New

TWIX-1 TWIX-2 TWIX-3 MM1015


Size : 48 x 96mm Size : 48 x 96mm Size : 48 x 96mm Size : 48 x 96mm

! Compact PLC with built in HMI ! Compact PLC with built in HMI
! Configurable LED display ! RS485 Communication
! RS485 Communication MODBUS RTU Protocol MODBUS RTU Protocol
FEATURES

DISPLAY 4 + 4 digits Red & 6 Green digits 7 Segment LED 3 + 4 digits Red & 4 Green digits 7 Segment LED
NO. OF KEYS 5 keys (4 - User configurable)
DIGITAL INPUTS 6 6 + 2* 8 10
INPUT TYPE PNP (6 to 30V DC) PNP (11 - 30V DC)
MAXIMUM COUNTING FC0 (I0 & I1) - 5KHz, Normal Digital Input: 30Hz Normal Digital Input: 30Hz
FREQUENCY
6 Channels 1 Channel
1 Channel 2 (TC / RTD ),
ANALOG INPUTS (TC / RTD) (TC / RTD)
2 (0 to 10V), 2 (0 to 20mA) NA

RESOLUTION 12 Bit

DIGITAL OUTPUTS 4 Relay 5 Relay 6 Transistor 6 Relay

TYPE & RATING 5A NO type @ 230V AC / 30V DC (Resistive) Source 100mA @ 24V DC 5A NO type @ 230V AC / 30V DC (Resistive)
1 Channel
ANALOG OUTPUTS (0 to 10V / 0 to 20mA)
NA NA NA
RESOLUTION 12 Bit

RTC NO

EXPANSION NO

PROGRAM MEMORY 112K 240K 112K 224KB

COMMUNICATION
RS485 Modbus RTU Protocol
INTERFACE
18 to 30VDC**, 100 to 270V AC / DC 100 to 270V AC 50 / 60Hz without retention
SUPPLY VOLTAGE 100 to 270V AC / DC 18 to 30V DC
180 to 270V AC, 50 / 60Hz with retention
50 / 60Hz. 50 / 60Hz.

*Voltage Analog Inputs can be configured as Digital Inputs **Please refer Datasheet for exact Order code
Dimensions (All are in mm)
TWIX-2 TWIX-1
TC+ / RTD1

TC- /RTD2

SENSOR

Panel Cutout
NTC

I5 I4 I3 I2 I1 I0 GND
m

1 2 3 4 5 6 7 8 9 10
Sensor
Supply

FC0
FC0 21 RTD3 +10V 22
.co

11 12 13 14 15 16 17 18 19 20

NO0 NO1 NO2 NO3 COM L N


u
ia

TWIX-3 MM1015 Ordering Information


ha

PRODUCT CODE --
CERTIFICATION
RTD1/TC+

RTD/ TC-
NTC-

NTC+ DI7 DI6 DI5 DI4 DI3 DI2 DI1 TWIX-1-230V --


en

TWIX-1-24V --
TWIX-2-230V --
di

TWIX-3-24VDC --
MM1015-230V --
Co

54 www.selec.com PROGRAMMABLE LOGIC CONTROLLER


Fixed IO Solution

New

MM3030-1 MM3030-2 MM3030-4 MM3030-3 MM3032-2-0-0-24V MM3032-2-0-0-230V


Size : 96 X 96 mm Size : 96 X 96 mm Size : 96 X 96 mm Size : 96 X 96 mm Size : 96 X 96 mm Size : 96 X 96 mm
! Low Cost ! Compact PLC with built-in HMI
! Panel / Din Rail Mounting ! 2 line x 16 characters LCD Display
FEATURES
! Fast Inputs / Outputs ! Panel / Din Rail Mounting
! Windows based User Friendly Software for Ladder Programming and HMI Configuration ! Windows based User Friendly Software for
Ladder Programming and HMI Configuration

DISPLAY 4x16 Character LCD 2x16 Character LCD

NO. OF KEYS 15 Keys (12 User Configurable) 8 Keys (6 User Configurable)

DIGITAL INPUTS 10 PNP (11 to 30V DC) 8 PNP (6 to 30V DC)


FC0 (I0 & I1), FC1 (I2 & I3) &
MAXIMUM COUNTING FC0 (I0 & I1) – 12Khz, FC1 (I2 & I3) & FC2 (I4 & I5) – 7.5KHz FC2 (I4 & I5) – 7.5KHz FC0 (I0 & I1) – 5Khz, Normal Input – 30Hz.
FREQUENCY Normal Input – 30Hz. Normal Input – 30Hz.
ANALOG INPUTS 2 Channel (0 to 10V or 0 to 20mA) selectable via jumpers 2 Channels (NTC & 0 to 20mA) 2 Channels (0 to 20mA)
RESOLUTION 10 Bit 12 Bit
DIGITAL OUTPUTS 8 Transistor 6 Relay
O0 - O1 - Sink 50mA @ 24V DC (Fast Outputs 50KHz) 3A NO type @ 230V AC / 30V DC
TYPE AND RATING 5A NO type @ 230V AC / 30V DC (Resistive)
O2 - O7 - Source 100mA @ 24V DC (Resistive)

Through Expansion 1 Channel


ANALOG OUTPUTS (0 to 10V)
NA

As per expansion modules 14 Bits (0.0% to 100.0% =


RESOLUTION
0 – 10.000V
RTC YES NO

EXPANSION YES NO

PROGRAM MEMORY 351K 240K

COMMUNICATION RS232 MODBUS RTU RS232 MODBUS RTU


RS485 MODBUS RTU Protocol RS485 MODBUS RTU Protocol
INTERFACE SLAVE Protocol Protocol
Proprietary Protocol &
COMMUNICATION Proprietary Protocol RS485 MODBUS Proprietary Protocol
RS485 MODBUS RTU NA
INTERFACE MASTER RTU Protocol
Protocol
100 to 270V AC 50 / 60Hz 100 to 270V AC 50 / 60Hz
without retention without retention
SUPPLY VOLTAGE 18 – 30V DC 18 – 30V DC
180 to 270V AC, 50 / 60Hz 180 to 270V AC, 50 / 60Hz
with Retention with Retention

Terminal Diagram Dimensions (All are in mm)


MM3030-1, MM3030-2, MM3032-2-0-0-24V Panel Cutout
MM3030-4
AI AI
AI0 NTC
I I I I I I I I I I
I I I I I I I I
m
u .co
ia

Ordering Information
MM3030-3 MM3032-2-0-0-230V
ha

PRODUCT CODE CERTIFICATION


AI AI

I I I I I I I I
A AI AI MM3030-1 --
en

DI DI DI DI DI DI DI DI

MM3030-2 --

MM3030-3-P1 --
di

MM3030-4 --

MM3032-2-0-0-230V --
Co

MM3032-2-0-0-24V --

55 www.selec.com PROGRAMMABLE LOGIC CONTROLLER


Human Machine Interface

SP11-GT70 SP3-GT35
Size : 214 x160mm Size : 96 x 96mm
! 7" LCD with Resistive Touchscreen ! 3.5" LCD with Resistive Touchscreen
! 10 Password Levels ! 10 Password Levels
! Serial Printing ! Serial Printing
FEATURES
! Data Logging ! Data Logging
! Built in Buzzer ! Built in Buzzer
! Recipe Management ! Recipe Management
DISPLAY 7" Diagonal 3.5" Diagonal

TOUCHSCREEN Yes (Resistive)


RESOLUTION 800 x 480 pixels 320 x 240 pixels
BACKLIGHT LED Backlight
USER MEMORY 16 MB

DATA LOGGING 2 GB (External SD Card)


COMMUNICATION Master Port - RS485 MODBUS RTU Protocol
Master Port - RS485 MODBUS RTU Protocol
PORT 1
COMMUNICATION Slave Port - RS232 MODBUS RTU Protocol
Slave Port – RS485 / RS232 MODBUS RTU Protocol (selectable vai jumper)
PORT 2
COMMUNICATION
Serial Printer ESC/P Protocol
PORT 3
USB SLAVE USB 2.0 NA

KEYS 7 Function keys + 1 System Key 5 Function keys + 1 System Key

RTC Yes
BACKUP BATTERY 3V CR2032
OPERATING
TEMPERATURE 0° to 55° C
STORAGE
-30° to 80° C
TEMPERATURE
SUPPLY VOLTAGE 18 to 30V DC

SP11-GT70 Terminal Diagram SP3-GT35


BACK VIEW
m
u .co
ia
ha

TOP VIEW
Dimensions (All are in mm)
en

SP11-GT70 Panel Cutout SP3-GT35 Ordering Information


Panel Cutout
PRODUCT CODE CERTIFICATION
di

--
160

Front bezel 142 142.9 92


SP11-GT70-V2
99 Front bezel Side view 91
SP3-GT35 --
Co

196.9
92
214 45.8 99 53
9
5.8

56 www.selec.com HMI
Add on - PLC IO's

EXP FLEX 2M IO610 IO630


Size : 35 x 90mm Size : 53 x 90mm Size : 53 x 90mm
! Any Flexys card can be Configured ! Can be used as independent I/O modules ! High Speed Communication between PLC
! Selectable baudrate and Slave ID through RS485 Modbus RTU and Expansion through Proprietary Protocol

FEATURES

DISPLAY LED indication for Power ON and Communication Status LED indication for Power On and Digital I/O status

DIGITAL INPUTS 4 / 10 / 14 per card PNP (6 to 30V DC) 8 per module (11 to 30V DC)

ANALOG INPUTS 3/4/6 Channels per card (TC, RTD, 0 to 10V, 0 to 20mA) 2 Channels per module (TC, RTD, 0 to 10V, 0 to 20mA)

RESOLUTION 12 Bit

RELAY OUTPUTS 4 / 8 per card. NO type 5A @ 230VA C / 30V DC (Resistive) 4 per module, NO type 5A @ 230V AC / 30V DC (Resistive)

TRANSISTOR OUTPUTS 8 per card. Source type 100mA @ 24V DC 4 per module, Source type 100mA @ 24V DC

ANALOG OUTPUTS 2 / 4 Channels per card (0 to 10V, 0 to 20mA) 2 Channels per module (0 to 10V, 0 to 20mA)
14 Bit
RESOLUTION (0.0 – 100.0% = 0 – 10.000V, 0.0 – 100.0% = 0 – 20.000mA) 12 Bit (0.0-100.00% = 0 - 10.00V, 0.0-200.00% = 0 -20.00mA)

RESPONSE TIME 100 mSec to 2 Sec + IO card Response 35 mSec 200 μSec

BAUDRATE 19200 / 115200 bps (Selectable) 19200 bps 500 Kbps


COMMUNICATION
RS485 Proprietary Protocol RS485 MODBUS RTU Protocol Proprietary Protocol
INTERFACE
SUPPLY VOLTAGE 24V DC

Terminal Diagram
IO610 / IO630-2AI-TCR
{

ON
Item Description
1 24V DC power supply
2 Expansion port - IO to PLC
3 DIP switch - slave ID (1 to 31)
4 LED - Power
{
{
{

Ordering Information
.co

PRODUCT CODE CERTIFICATION


IO610 / IO630-4RO IO610 / IO630-8DI
EXP-FLEX 2M --
u

IO610-8DI --
--
ia
{

{
{

IO610-4RO
IO610-4TO --
ha

Item Description IO610-2AI-TCR --


1 24V DC power supply IO610-2AI-VI --
2 Expansion port - IO to PLC IO610-2AO --
en

ON ON
3 DIP switch - slave ID (1 to 31) IO630-8DI --
4 LED - Power IO630-4RO --
di

5 LED - Output Status IO630-4TO --


IO630-2AI-TCR --
Co

IO630-2AI-VI --
I I I I I I I I
IO630-2AO --

57 www.selec.com EXPANSION MODULES


Data Converters

AC-USB-RS232-01 AC-USB-RS485-03 AC-USB-RS485-02 AC-USB-RS485-02-3M AC-S2E-01

! Port Powered ! Web Configuration Telnet Protocol


! Communication status available as LED Indication ! TCP / IP Protocol
FEATURES

LED indication for Power ON, Tx and Rx,


DISPLAY LED indication for Tx & Rx
& Ethernet Communication

SERIAL INTERFACE RS232 RS485 MODBUS RTU Protocol


MODBUS RTU Protocol
CONNECTOR DB9 RJ25 (6Pin) 2 open wires DB9

USB INTERFACE USB 2.0 Compliance


NA
CONNECTOR USB Type A

ETHERNET INTERFACE NA TCP / IP, Telnet Protocol

CONNECTOR NA RJ45 (8 Pin)


RS485 : 300 to 115000 bps
TRANSMISSION SPEED 2400 to 115000 bps Ethernet :10 / 100 Mbps
CABLE LENGTH 1 Meter 3 Meter NA
POWER CONSUMPTION 75mA @ 5V 0.5 W
SUPPLY VOLTAGE Port powered 12 to 30V DC

ACCESSORIES

Connecting
Links

AC-IOEXP-03 AC-IOEXP-01 ACH-002 ACH-004 ACH-003

DESCRIPTION Adapter for directing


RJ25 to open terminal Expansion adaptor for Both Side RJ25 type Both Side RJ45 Type
DB9 to RJ25 cable
and also for network looping MM303X PLCs Connector Connector
m

Ordering Information
.co

PRODUCT CODE CERTIFICATION


AC-USB-RS232-01 --
--
u

AC-USB-RS485-02
AC-USB-RS485-02-3M --
ia

AC-USB-RS485-03 --
ha

AC-S2E-01 --

AC-IOEXP-03 --
en

AC-IOEXP-01 --

ACH-004 --

ACH-002 --
di

ACH-003 --
Co

58 www.selec.com INTERFACE
Relay Modules

New

RLYMD-1-S4-1C0-24VDC RLYMD-2-S8-1C0-24VDC RLYMD-1-S4-2C0-24VDC RLYMD-2-S8-2C0-24VDC ERLYMD-2-1-S8-1C0-24V

! LED and Freewheeling Diode Across Coils ! Selectable Baudrate and Slave ID
! Reverse Polarity Protection ! Pluggable Relays
! Jumpers for Coil Looping
FEATURES
! Pluggable Relays

CONTACTS 1 C/O 2 C/O 1 C/O


NO. OF CHANNELS 4 8 4 8 8
CONTACT RATING 10A @ 277V AC / 30V DC (Resistive)
NOMINAL VOLTAGE 24V DC
MUST VOLTAGE 18V DC
MAX VOLTAGE 33V DC
OPERATE TIME 15mSec
RESET SETTIME 5mSec
COIL TO CONTACT
5000V AC for 1min
DIELECTRIC STRENGTH
OPEN CONTACT
1000V AC for 1min
DIELECTRIC STRENGTH
COMMUNICATION
NA RS485 MODBUS RTU
PROTOCOL
LED indication for Relay ON Status LED Indication for Relay ON Status,
STATUS DISPLAY
Power ON & Communication Status
SUPPLY VOLTAGE NA 24V DC

Terminal Diagram

RLYMD-2-S8-2CO-24VDC ERLYMD-2-1-S4-1C0-24V

DC Supply BAUD OPTIONAL


SID
}

RATE CONNECTION
+24V GND
}

(RS485)
}

2 2

+ - + - 6 PIN
JACK
ON
PWR LED_TX LED_RX LED_STAT
24V 1 2 3 4 5 RS485

LED1
6 PIN
JACK
m

Master RS485

PLC
.co

RLYMD-1-S4-2CO-24VDC

04 01 02 14 11 12 24 21 22 34 31 32 44 41 42 54 51 52 64 61 62 74 71 72
u
ia
ha

Ordering Information
2 2
PRODUCT CODE CERTIFICATION
en

RLYMD-1-S4-1CO-24VDC --

RLYMD-1-S4-2CO-24VDC --
di

RLYMD-2-S8-1CO-24VDC --

RLYMD-2-S8-2CO-24VDC --
Co

ERLYMD-2-1-S8-1CO-24V --

59 www.selec.com ACCESSORIES
Company Overview...

Delhi Office

Our facilities at Navi Mumbai, India...

Manufacturing:

SMT Manufacturing Plant (5 lines) m &


u .co

Other Facilities :
ia

Government Approved Design Center, Laboratory For Certification and EMC, Tool Room
ha
en

Subsidiaries : Selec GmbH | Selec USA


di

SELEC/ DOMESTIC - EXPORT/120417


Co