ENGLISH MANUAL
After-sales hotline:0512-82079650、82079651、82079654
CATALOGUE:
ONE:YS-K32 introduction…………………………………………..1
3:Electrical debugging………………………………………………3
⑴:Motor tuning…………………………………………………3
Appendix 2、Troubleshooting……………………………………...10
First using YS-K32, please refer to the debugging part strictly (FOUR: YS-K32
1
THREE:YS-K32 terminal introduction
In the field replacement process, in order to avoid line error, please remove the line of
View original TD3200 output signal set (F107 = 3 normally closed, F107 = 0 normally
open).
2:Wiring of YS-K32
Power off, remove the lines of TD3200 one by one and access to the corresponding
2
interface of YS-K32.
YS-P02/YS-P03)
⑴ Motor tuning
First, remove the motor belt, make sure no-load state before motor tuning.
Set P0.01=3 to restore default parameters, check motor parameters and set the motor
parameters P1.02 ~ P1.04 (P1.02 Motor nominal current, P1.03 Motor nominal frequency,
P1.04 motor rated speed) according to motor nameplate. Set P0.06=0 by keyboard
control, and set P1.06=1 (Motor tune activate), press OD key, do motor parameter
identification. Do not install the motor belt until motor tuning finish.
Power on again after power off, 4-digit display default shows encoder pulses.
Pull the door if 4-digit display the panel increase when door open and reduce when
door close. It means the direction of the encoder is all right. If opposite, negated P2.01
( Encoder direction).
Set P2.05=1(door width auto-learning activated), press OD key, the door will
Notice: If first close and then open the door, means motor lines reversed, just change
Press OD key, the door will open, press CD key, the door will close, check the door
curve. Set the rational door curve and door torque according to function parameters
3
(Appendix 1、Parameter list).
In general, you just need to change the door speed parameters (P3.03 opening
speed, P4.03 closing speed) and deceleration point parameters (P3.04 open deceleration
position, P4.04 close deceleration position). For heavy-duty doors, avoid stuck situation,
increase the low-speed parameters (P3.01 Open start speed, P3.06 Open creeping speed,
P4.01 Close start speed, P4.06 Close creeping speed1, P4.08 Close creeping speed2),
T: torque
In open process, torques response as follows, first switch to P5.00 (open start
torque), then turn to P5.01 ( Open holding T1), until the door fully opened, and after the
waiting time P5.03 (T Dec time ) the torque turns to P5.02(Open holding T2).
In general , P5.00>P5.01>P5.02.
T: torque
4
In close process, torques response as follows, first switch to P5.04 (close start
torque),then turn to P5.05( Close holding T1), until the door fully close,and after the
waiting time P5.07 (T Dec time ) the torque turns to P5.06(Close holding T2).
In general , P5.04>P5.05>P5.06.
Set P0.06=1 terminal mode, and let the elevator control the door.
5
Appendix 1、Parameter list
“○”: can be set on running status and stop status.
“×”: can be set on stop status.
“* ” : register value, can’t be set.
Parameter name Setting rage MS setting
code Asyn motor
P0.00 User password 0:no password 0 ○
1~9999:user password;
5:reserved
0~1,confirm
P0.06 Controller mode 0: panel mode (OD: door open, CD: door 1 ×
2: Demo mode
P0.08 Two level code Input the two level code to see the protected 9888 ×
unset)
6
Parameter name Setting rage MS setting
code Asyn motor
P1.06 Motor tune 0:no function 0 ×
0→1:confirm
1:direction change
setting
0 →1:confirm
7
Parameter name Setting rage MS setting
code Asyn motor
P5.05 Close holding torque1 30.0%~150.0%(motor rating torque) 45.0% ○
P5.10 End torque under slow speed 30.0%~150.0%(motor rating torque) 50.0% ○
running
P6.00 relay output logical selection 0:signal open represent that door arrived 0 ×
closed contact)
open contact)
PA/PB/PC
P8.00~ reserved ○
P8.13
8
Parameter name Setting rage MS setting
code Asyn motor
P9.00 fault 3 0:no record
3:E003
4:E004
5:reserved
6:E006
7:E007
8:E008
9~13:reserved
14:E014
15:reserved
16:E016
17:E017
18:E018
19~22:reserved
23:E023
24:reserved
25:E025
26:E026
-Lu-:low voltage
9
Appendix 2、Troubleshooting
sequence Fault name Fault Fault reason countermeasure
number code
0 Ready / / /
6 Motor parameter tuning E006 1)incorrect motor rating parameter 1)setting correct motor rating parameter
9 Reserved E009
10 Reserved E010
11 Reserved E011
12 Reserved E012
13 Reserved E013
read/write error
15 Reserved E015
fault
19 Reserved E019
20 Reserved E020
21 Reserved E021
10
2)encoder wiring error 2)check encoder wiring
3)encoder pulse number setting error 3)setting correct encoder pulse number
24 Reserved E024
read/write error
1: Panel &display
11
STOP Stop Stop operation; reset fault.
M Multi-function
Stop status display parameter: door position pulse, door arrived signal, speed
command, input terminals status, DC bus voltage. Press key to achieve every status
selection.
Run status display parameter: door position pulse, door arrived signal, speed
command, output speed, output voltage, output current, output torque, DC bus voltage,
STEP 1, press PRG key, panel display –P0-. The first menu;
STEP 2, press key, panel display –P1-. The internal parameter group;
12
STEP 5, press key, panel display 24V and into the function code;
STEP 7, press key, the parameter P1.01 has been changed to 25V and panel
display P1.02.
STEP 8, press PRG key, panel display –P1-. Return to the first menu;
STEP 9, press PRG key, panel display. Back to operation stop and monitoring status;
Panel display fault code when controller fault occurs. Reset fault by pressing STOP
YS-K03 door controller design has control curve parameter storage and batch upload
and download function to meet the requirement of high-efficient elevator debugging and
maintenance.
For the same door width and type door machine can use the same curve parameter
to achieve door control. Upload the experience curve parameter from the controller of
debugging good results to the panel. Then download from the panel to the same door
Example: door 1 and door 2 have the same door width and door mechanical
configuration type. After debugging door 1 operation curve, upload the curve parameter
from controller A to the panel corresponding position and compile group number. Then
download the curve parameter from the panel corresponding group number position to the
controller B to achieve good door 2 control. It can batch copy to the same controller (3~n)
in the same way. If the operation test is normal it can be packed from factory. Parameter
batch upload and download function can improve the efficiency of producing and
maintaining.
13
The panel has 12 parameter macro spaces. You can upload parameter from the
from 12 macro spaces to the target controller to simple the parameter setting at
debugging.
Upload and download parameter range: P0.05~P8.15 (except P1.09 and P2.01);
Example: upload the controller parameter to 8 group space; when uploading, set
P0.01 to 2 and P0.02 to 8, then set P0.04 to 1 and confirm, panel displays , finally
Example: download the panel 7 group space parameter to the controller; when
downloading, set P0.01 to 2 and P0.03 to 7, then set P0.04 to 1 and confirm, panel
Special note: all parameters are the controller default parameter until upload the
14