Sup Ptu100 Turbidity Meter User Manual
Sup Ptu100 Turbidity Meter User Manual
Sup Ptu100 Turbidity Meter User Manual
Turbidity/TSS/MLSS
Controller
Headquarters
5th floor,Building 4,Singapore Hangzhou Science Technology Park,No. 6 street,
Hangzhou Economic Development Area,Hangzhou 310018,China
Singapore
2 Venture Drive #11-30 Vision Exchange Singapore
Philippines
Majestic Subdivision, Lot 1, 1800 Rainbow St, Marikina, 1811 Metro Manila, Philippines
info@supmea.com
www.supmea.com
Supmea Automation Co.,Ltd. U-TU1-MYEN2
Preface
Thank you for purchasing Turbidity/TSS/MLSS controller. Please read this manual
carefully before operating and using it correctly to avoid unnecessary losses
caused by false operation.
Note
Version
U-TU1-MYEN2
I
Safety Precautions
In order to use this product safely, be sure to follow the safety precautions
described.
To ensure safe use of this product and the systems it controls, Please read
carefully the operation manual and understand the correct application
methods before putting into operation, to avoid unnecessary losses due to
operation mistakes. If the instrument is operated in other ways not
described in the manual, the protections that the instrument give may be
destroyed, and the failures and accidents incurred due to violation of
precautions shall not be borne by our company.
When installing lightning protection devices for this product and its control
system, or designing and installing separate safety protection circuits for
this product and its control system, it needs to be implemented by other
devices.
If you need to replace parts of the product, please use the model
specifications specified by the company.
This product is not intended for use in systems that are directly related to
personal safety.Such as nuclear power equipment, equipment using
radioactivity, railway systems, aviation equipment, marine equipment,
aviation equipment and medical equipment.If applied, it is the responsibility
of the user to use additional equipment or systems to ensure personal
safety.
II
Do not modify this product.
The following safety signs are used in this manual:
III
immediately, otherwise there will be leakage, electric shock or even a
fire accident.
Please check the grounding protection status regularly. Do not operate if
you think that the protection measures such as grounding protection
and fuses are not perfect.
Ventilation holes on the product housing must be kept clear to avoid
malfunctions due to high temperatures, abnormal operation, shortened
life and fire.
Please strictly follow the instructions in this manual, otherwise the
product's protective device may be damaged.
Disclaimer
IV
The company does not make any guarantees for the terms outside the
scope of this product warranty.
This company is not responsible for damage to the instrument or loss of
parts or unpredictable damage caused directly or indirectly by improper
operation of the user.
No. Name Quantity Note
1 Turbidity/TSS/MLSS Sensor 1
2 Turbidity/TSS/MLSS controller 1
3 Manual 1
4 Certificate 1
After opening the box, please confirm the package contents before starting the
operation.If you find that the model and quantity are incorrect or there is physical
damage in appearance, please contact us.
V
Contents
Chapter 1 Introduction........................................................................................................1
1.1. Turbidity/TSS/MLSS sensor................................................................................1
1.2. Turbidity/TSS/MLSS controller........................................................................... 2
Chapter 2 Installation..........................................................................................................4
2.1. Instrument installation..........................................................................................4
2.2 Electrode installation.............................................................................................6
2.3. Instrument wiring.................................................................................................. 8
Chapter 3 Navigation keys.............................................................................................. 10
3.1 Button display...................................................................................................... 10
Chapter 4 Configuration................................................................................................... 11
4.1 Monitoring page................................................................................................... 11
4.2 Password verification page................................................................................12
4.3 Main menu screen...............................................................................................12
4.4 System Setting.....................................................................................................13
4.5 Signal Setting.......................................................................................................13
4.6 Online Calibration................................................................................................14
4.7 Remote Setting.................................................................................................... 14
4.8 Alarm Setting........................................................................................................14
4.9 Version Query...................................................................................................... 15
Chapter 5 Communication...............................................................................................16
Chapter 6 Calibration of MLSS/TSS.............................................................................. 18
Chapter 7 Maintenance....................................................................................................19
Chapter 8 Troubleshooting.............................................................................................. 20
VI
Chapter 1 IntroductionChapter 1 Introduction
Chapter 1 Introduction
1.1. Turbidity/TSS/MLSS sensor
The sensor is based on the combined infrared absorption and scattering light
method, and the ISO7027 method can be used to accurately determine the
turbidity, TSS and MLSS. The main parameters of the sensor showed as table 2:
Weight 1.65KG
Cable: PVC
whichever is larger
Accuracy
MLSS/TSS: less than ±5% of the measured value (depending on
Operating
0 ~ 45℃
temperature
Temperature(-15 ~ 65℃)
Altitude: <2000m
www.supmea.com -1-
Chapter 1 IntroductionChapter 1 Introduction
Sensor dimension
Weight 0.65Kg
Turbidity:0.00 ~ 4000NTU
120000 mg/L
-2- www.supmea.com
Chapter 1 IntroductionChapter 1 Introduction
homogeneity)
Temperature(-15 ~ 65℃)
Altitude:<2000m
www.supmea.com -3-
Chapter 2 Installation
Chapter 2 Installation
2.1. Instrument installation
Specify the installation site and installation method of this instrument. Please be
-4- www.supmea.com
Chapter 2 Installation
Install a 92.5 * 92.5 mounting hole on the instrument cabinet or mounting panel
the thickness of the mounting panel is 1.5mm~13mm
www.supmea.com -5-
Chapter 2 Installation
The instrument into the mounting hole and then buckle on the butterfly, as
shown below:
Install steps
Specific install steps showed as figure 4:
1. Use 1 (M8U buckle) to fix 8 (installation panel) on the pipe near
the pool where the sensor is installed.
2. Connect 9 (converter) and 2 (DN40) PVC pipe with glue, and put
the sensor cable through PVC pipe, screw the sensor into 9 (converter), and
make sure that water resistance has been done.
3. Fix 2 (DN40 pipe) through 4 (DN42 u-shape clip) onto 8
(installation panel)
-6- www.supmea.com
Chapter 2 Installation
9、Thread converter
www.supmea.com -7-
Chapter 2 Installation
Wiring Diagram
Terminal definition
+12VDC: Turbidity / TSS/ MLSS electrode power supply +
AGND: Turbidity / TSS/ MLSS electrode power supply -
RS485-A: Turbidity / TSS/ MLSS electrode communication +
RS485-B: Turbidity / TSS/ MLSS electrode communication -
NC: Unidentified
NC: Unidentified
485A+: RS485 communication interface A﹢
485B-: RS485 communication interface B﹣
I+: 4-20mA output +
I-: 4-20mA output -
HO: High alarm normally open
HC: High alarm normally closed
COM: Common terminal
LO: Low alarm normally open relay
LC: Low alarm normally close relay
COM: Common terminal
-8- www.supmea.com
Chapter 2 Installation
www.supmea.com -9-
Chapter 3 Navigation keys
- 10 - www.supmea.com
Chapter 4 Configuration
Chapter 4 Configuration
4.1 Monitoring page
www.supmea.com - 11 -
Chapter 4 Configuration
The initial password is 0000, which can be modified by using the change
password function.
- 12 - www.supmea.com
Chapter 4 Configuration
www.supmea.com - 13 -
Chapter 4 Configuration
RS485 Setting: Set the address and baud rate of the 485 communication.
Current Transmission: Set the corresponding value of 4mA and the
corresponding value of 20mA for the 4 ~ 20mA output.
TUR High Alarm: When the measured value is larger than the high alarm
pick-up value, the high alarm relay is picked up and when the measured
value is less than the high alarm breaking value, the high alarm relay is
disconnected.
- 14 - www.supmea.com
Chapter 4 Configuration
TUR Low Alarm: When the measured value is less than the low alarm
pick-up value, the low alarm relay is picked up and when the measured
value is larger than the low alarm breaking value, the low alarm relay is
disconnected.
MLSS High Alarm: When the measured value is larger than the high alarm
pick-up value, the high alarm relay is picked up and when the measured
value is less than the high alarm breaking value, the high alarm relay is
disconnected.
MLSS Low Alarm: When the measured value is less than the low alarm
pick-up value, the low alarm relay is picked up and when the measured
value is larger than the low alarm breaking value, the low alarm relay is
disconnected.
www.supmea.com - 15 -
Chapter 5 Communication
Chapter 5 Communication
The instrument provides a standard RS485 serial communication interface, and
uses the general international standard MODBUS - RTU communication protocol.
Command format:
Function Register Data CRC
Definition Address
code address number check
Data ADDR 0x03 M N CRC 16
Number of
1 1 2 2 2
bytes
Return format:
Function CRC
Definition Address Data size Data
code check
Number of
1 1 1 2*N 2
bytes
- 16 - www.supmea.com
Chapter 5 Communication
MLSS/TSS value
(in mg/L, the
0x0002 long 4 bytes 0x03 obtained value Read-only
needs to be
divided by 10)
www.supmea.com - 17 -
Chapter 6 Calibration of MLSS/TSS
- 18 - www.supmea.com
Chapter 7 Maintenance
Chapter 7 Maintenance
Cleaning of sensors
Two lenses on the sensor need to be cleaned. Please regularly carry out cleaning
and maintenance in accordance with actual use to ensure the accuracy of the
measurement. Rinse it with clean water first and then wipe it with cleaners and rag
to remove stubborn stains.
www.supmea.com - 19 -
Chapter 8 Troubleshooting
Chapter 8 Troubleshooting
No display of the controller?
A: Check whether the power line is connected correctly and whether the
power supply is connected.
Displaying figures jumping up and down?
A: Check whether there is any interference equipment such as the
frequency converter. Be careful to keep it away from these interference
devices or take shielding measures.
Transmitter displaying horizontal bar?
A: The sensor is connected abnormally or water gets into the sensor; if
water gets into the sensor, please send the probe to the After-sale
Maintenance Department in time for checking and repair.
- 20 - www.supmea.com