P00592320 - 3 - CNCG Burner Sequences
P00592320 - 3 - CNCG Burner Sequences
P00592320 - 3 - CNCG Burner Sequences
PRELIMINARY
Rev. Created By Inspected By Released By Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA
8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Cust. Doc ID Page:
DRAWING LIST
3 5/29/2020/TREJARVEJO
5/29/2020/FTAMJNS 5/29/2020/FTAMSRE SEQ-28.01
Pos. 1
Doc ID: P00592320
0 1 2 3 4 5 6 7
IF THE SEQUENCE DON'T HAVE THE FOLLOWING OPERATIONS PROT ->A AON ->M MON INIT REL
THEN THEY ARE NOT SHOWNED AT THE DIAGRAM A
This document is the exclusive intellectual property of Valmet Corporation and/or its subsidiaries and is furnished solely for operating and maintaining the specific project. Re-use of the document for any other
&
MON SEQUENCE MANUAL (OPERATOR) START/STOP AND - GATE
SEQUENCE STARTS ALWAYS FROM BEGINNING
TO FIRST STEP
INIT SEQUENCE IS STOPPED AND RETURNED
1
project or purpose is prohibited. The document or the information shall not be reproduced, copied or disclosed to a third party without prior written consent of the company.
TO BEGINNING OR - GATE
FROM PREVIOUS STEP
AON SEQUENCE AUTOMATIC START (PULSE-WISE) B
IF ONLY AON, THEN OPERATOR CAN NOT MAKE OPERABLE WAITING TIME:
ANY CHANGES WHEN THE SEQUENCE IS RUNNING =1
- OPERABLE FROM DISPLAY XOR - GATE
- ELAPSED TIME DISPLAY,
PROT SEQUENCE IS FORCED TO MANUAL AND STARTED
IF TIME > 60 s
STEP NAME
REL SEQUENCE IS RELEASED TO START NEGATION
OPERABLE WAITING TIME MONITORING TIME ACTION
WAITING TIME 1 s OWT +5s
0...5s FAILURE
ON TIME DELAY, ON
C
STEP NUMBER
OFF TIME DELAY, OFF
JUMP CONDITIONS
TO NEXT STEP
WAITING TIME:
-THE NEXT STEP CAN NOT BE ACTIVATED
UNTIL THE WAITING TIME IS PASSED
-WAITING TIME DOESN'T APPLY TO JUMP CONDITIONS FROM PREVIOUS STEP PAGE MERGE INSIDE SAME DOC. GROUP
2
Into page: 1
Rev. Created By Inspected By Released By Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA
8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Cust. Doc ID Page:
LEGEND SHEET
3 5/29/2020/TREJARVEJO
5/29/2020/FTAMJNS 5/29/2020/FTAMSRE SEQ-28.02
Pos. 1
Doc ID: P00592320
0 1 2 3 4 5 6 7
VALID
.S1 BMS2
CNCG B LEAKAGE TEST A
This document is the exclusive intellectual property of Valmet Corporation and/or its subsidiaries and is furnished solely for operating and maintaining the specific project. Re-use of the document for any other
START COND. OK
.S1 BMS2
CNCG MAIN INTERLOCK CNCG B NG START SEQUENCE RUN
INT-28.11 CNCGB main common interlocks NC-CB3-KJ0051.S11
NG EQUIPMENT IN STOP POS. STATUS
.S1 BMS2 RUNNING
CNCG B EQ IN STOP POS .S11
project or purpose is prohibited. The document or the information shall not be reproduced, copied or disclosed to a third party without prior written consent of the company.
Rev. Created By Inspected By Released By Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA
8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Cust. Doc ID Page:
CNCGB NG START SEQUENCE
3 5/29/2020/TREJARVEJO
5/29/2020/FTAMJNS 5/29/2020/FTAMSRE SEQ-28.03
Pos. 1
Doc ID: P00592320
0 1 2 3 4 5 6 7
S2 STEP
252-HIC-817.S3 AUTO MODE ON
S3 STEP
IN AUTO-MODE WAITING TIME MONITORING TIME ACTION BMS2 DO DI DCS 252-HIC-817
252-HIC-817 DCS DO DI BMS2 1 1s s
CNCG B combustion air damper
CNCG B combustion air damper
252-HIC-817.S1 BMS2
CNCG Comb.air damper open B
INT-28.11 CNCGB main common interlocks
GAS LANCE IN
AUTO IN
WAITING TIME MONITORING TIME ACTION 252-HSV-812
2 1s s
CNCG B natural gas lance in-out
SEQ-28.16 CNCGB NG lance
SET MONITORING ON
252-HIC-817 BMS2
IN POSITION & NOT FAILURE CNCG B combustion air damper
252-HSV-812.S11 BMS2 SEQ-28.15 CNCGB combustion air monitoring
CNCG B natural gas lance in-out
SEQ-28.16 CNCGB NG lance C
IGNITER CYLINDER IN
AUTO IN
WAITING TIME MONITORING TIME ACTION 252-HSV-811
3 1s s
CNCG B igniter in-out
SEQ-28.08 CNCGB Igniter cylinder
IGNITER START
AUTO START
WAITING TIME MONITORING TIME ACTION 252-BX-804
4 1s s
CNCG B igniter
SEQ-28.09 CNCGB Igniter
PRELIMINARY
Rev. Created By Inspected By Released By Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA
8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Cust. Doc ID Page:
CNCGB NG START SEQUENCE
3 5/29/2020/TREJARVEJO
5/29/2020/FTAMJNS 5/29/2020/FTAMSRE SEQ-28.03
Pos. 2
Doc ID: P00592320
0 1 2 3 4 5 6 7
STEP 4
A
This document is the exclusive intellectual property of Valmet Corporation and/or its subsidiaries and is furnished solely for operating and maintaining the specific project. Re-use of the document for any other
S21 STEP
50 %
WAITING TIME MONITORING TIME ACTION BMS2 DO DI DCS 252-PIC-835.S21
5 1s s
CNCG B natural gas pressure
CNT-28.01 CNCG burner NG flow and pressure
252-PIC-835.S23
S23 STEP
CONTROLLER IN MANUAL MODE
252-FIC-805 DCS DO DI BMS2
CNCG B natural gas flow
project or purpose is prohibited. The document or the information shall not be reproduced, copied or disclosed to a third party without prior written consent of the company.
D
OPEN GAS VALVES
AUTO OPEN
WAITING TIME MONITORING TIME ACTION 252-HSV-814
8 1s s
CNCG B natural gas valve 1
OPEN LIMIT & NOT FAILURE SEQ-28.11 CNCGB NG valves
252-HSV-814.S11 BMS2
CNCG B natural gas valve 1
AUTO OPEN
SEQ-28.11 CNCGB NG valves
252-HSV-815
&
CNCG B natural gas valve 2
OPEN LIMIT & NOT FAILURE SEQ-28.11 CNCGB NG valves
252-HSV-815.S11 BMS2
CNCG B natural gas valve 2 E
SEQ-28.11 CNCGB NG valves
STEP 9
PRELIMINARY
Rev. Created By Inspected By Released By Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA
8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Cust. Doc ID Page:
CNCGB NG START SEQUENCE
3 5/29/2020/TREJARVEJO
5/29/2020/FTAMJNS 5/29/2020/FTAMSRE SEQ-28.03
Pos. 3
Doc ID: P00592320
0 1 2 3 4 5 6 7
STEP 8
S22 STEP
RESET
BMS2 DO DI DCS 252-PIC-835.S22
IGNITER FLAME ON CNCG B natural gas pressure
252-BX-804.S1 BMS2 CNT-28.01 CNCG burner NG flow and pressure
CNCG B igniter
INT-28.14 CNCGB igniter
IGNITER CYLINDER OUT
AUTO OUT D
WAITING TIME MONITORING TIME ACTION 252-HSV-811
12 20s s
CNCG B igniter in-out
SEQ-28.08 CNCGB Igniter cylinder
S1 STEP
AUTO MODE ON
WAITING TIME MONITORING TIME ACTION BMS2 DO DI DCS 252-FIC-805
E
13 1s s
CNCG B natural gas flow
CNT-28.01 CNCG burner NG flow and pressure
PRELIMINARY
STEP 14
Rev. Created By Inspected By Released By Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA
8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Cust. Doc ID Page:
CNCGB NG START SEQUENCE
3 5/29/2020/TREJARVEJO
5/29/2020/FTAMJNS 5/29/2020/FTAMSRE SEQ-28.03
Pos. 4
Doc ID: P00592320
0 1 2 3 4 5 6 7
STEP 13
READY
A
This document is the exclusive intellectual property of Valmet Corporation and/or its subsidiaries and is furnished solely for operating and maintaining the specific project. Re-use of the document for any other
PRELIMINARY
Rev. Created By Inspected By Released By Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA
8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Cust. Doc ID Page:
CNCGB NG START SEQUENCE
3 5/29/2020/TREJARVEJO
5/29/2020/FTAMJNS 5/29/2020/FTAMSRE SEQ-28.03
Pos. 5
Doc ID: P00592320
0 1 2 3 4 5 6 7
IGNITER/BLOWING OK
.S3 BMS2
CNCG MAIN INTERLOCK
A
This document is the exclusive intellectual property of Valmet Corporation and/or its subsidiaries and is furnished solely for operating and maintaining the specific project. Re-use of the document for any other
RUNNING
project or purpose is prohibited. The document or the information shall not be reproduced, copied or disclosed to a third party without prior written consent of the company.
DCS DI
.S11 BMS2 STEP S1
CNCG B NG LEAKAGE TEST SEQ B
BMS2 DO CNCG B NG STOP SEQUENCE RUN
SEQ-28.12 CNCGB NG leakage test sequence
NC-CB3-KJ5097.S11
BURNER NG FAILURE
.S4 BMS2 STATUS
CNCG B NG FAILURE CONTROL
SEQ-28.06 CNCGB NG burner failure
DCS DI
STEP S11
BMS2 DO
C
3s
OPERATOR STOP
.S2 BMS2
CNCG B NG OPERATOR CONTROL
SEQ-28.72 CNCGB Support fuel start release
1
3s
LOCAL STOP STOP COMMAND
252-LCP-150.PB09.S1 BMS2 .S10 BMS2
CNCG B NG burner stop CNCG B NG OPERATOR CONTROL
SEQ-28.05 CNCGB NG local controls SEQ-28.03 CNCGB NG start sequence
SEQUENCE STEP NUMBER
D
NC-CB3-KJ5097.I1
ALWAYS STATUS
A-MODE.
FAILURE RESET
PROT AON REL DCS DI
.S10 BMS2 1
STEP I1
CNCGB FAILURE RESET OPR
SEQ-28.70 CNCGB Common local controls INIT CNCG B NG STOP SEQUENCE BMS2 DO RUNNING
STEP .S12 BMS2
CNCG B NG STOP SEQUENCE
SEQ COMPLETED INT-28.27 Oil burner start conditions
57 SEQ-28.03 CNCGB NG start sequence
From page: 3 SEQ-28.05 CNCGB NG local controls
SEQ-28.06 CNCGB NG burner failure E
SEQ-28.12 CNCGB NG leakage test sequence
SEQ-28.15 CNCGB combustion air monitoring
SEQ-28.70 CNCGB Common local controls
STEP 51
PRELIMINARY
Rev. Created By Inspected By Released By Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA
8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Cust. Doc ID Page:
CNCGB NG STOP SEQUENCE
3 5/29/2020/TREJARVEJO
5/29/2020/FTAMJNS 5/29/2020/FTAMSRE SEQ-28.04
Pos. 1
Doc ID: P00592320
0 1 2 3 4 5 6 7
A
This document is the exclusive intellectual property of Valmet Corporation and/or its subsidiaries and is furnished solely for operating and maintaining the specific project. Re-use of the document for any other
STEP STOP
S2 STEP
CNCG B natural gas valve 2 CLOSE TO 0% AND TO M-MODE
SEQ-28.11 CNCGB NG valves BMS2 DO DI DCS 252-PIC-835.S2
CNCG B natural gas pressure
CNT-28.01 CNCG burner NG flow and pressure
OPEN VENT VALVE
AUTO OPEN
WAITING TIME MONITORING TIME ACTION 252-HSV-830
C
52 1s s
CNCG B natural gas vent valve
SEQ-28.11 CNCGB NG valves
IGNITER FLAME ON
252-BX-804.S1 BMS2
CNCG B igniter
INT-28.14 CNCGB igniter
STEP 54
PRELIMINARY
Rev. Created By Inspected By Released By Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA
8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Cust. Doc ID Page:
CNCGB NG STOP SEQUENCE
3 5/29/2020/TREJARVEJO
5/29/2020/FTAMJNS 5/29/2020/FTAMSRE SEQ-28.04
Pos. 2
Doc ID: P00592320
0 1 2 3 4 5 6 7
STEP 53
READY
SEQ COMPLETED
WAITING TIME MONITORING TIME ACTION 57
Into page: 1
57 s s
E
PRELIMINARY
Rev. Created By Inspected By Released By Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA
8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Cust. Doc ID Page:
CNCGB NG STOP SEQUENCE
3 5/29/2020/TREJARVEJO
5/29/2020/FTAMJNS 5/29/2020/FTAMSRE SEQ-28.04
Pos. 3
Doc ID: P00592320
0 1 2 3 4 5 6 7
This document is the exclusive intellectual property of Metso Power AB/Metso Power Oy/Metso Paper USA, Inc./Metso Paper Sulamericana Ltda and is furnished for the sole purpose of operating and maintaining of the specific project,
ON
ON
252-LCP-150.PB08.S1 BMS2 252-LCP-150.PB01.S1 BMS2
PUSH-BUTTON CNCG B NG burner start PUSH-BUTTON CNCG B lamp test
NO 252-43-150.PB08 NO 252-43-150.PB01
SEQ-28.03 CNCGB NG start sequence SEQ-28.43 CNCGB CNCG local controls
SEQ-28.70 CNCGB Common local controls
SEQ-30.13 CNCGB Local controls MeOH
CNCG B READY
READY TO START 1 FOR START NG
.S1 BMS2
CNCG B NG
NOT ON
CNCG B RUNNING NG
.S1 BMS2
CNCG B FLAME MONITORING &
INT-28.13 CNCGB NG flame monitoring
C
RUNNING
.S11 BMS2
CNCG B NG START SEQUENCE
SEQ-28.03 CNCGB NG start sequence
CNCG B NG BURNER
1
©Metso Power AB or ©Metso Power Oy or ©Metso Paper USA, Inc. or ©Metso Paper Sulamericana Ltda.
RUNNING 1 ON
.S12 BMS2
CNCG B NG STOP SEQUENCE
252-43-150.XL11
SEQ-28.04 CNCGB NG stop sequence
PILOT LAMP
&
2 Hz
PRELIMINARY
Rev. Designed by Checked by Approved by Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA 8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Page:
CNCGB NG LOCAL CONTROLS Cust. Doc. ID:
3 5/29/2020/TREJARVEJO 5/29/2020/FTAMJNS 5/29/2020/FTAMSRE
Pos.
SEQ-28.05
Doc. ID: P00592320
0 1 2 3 4 5 6 7
FAILURE
252-HSV-812.FLT BMS2
CNCG B natural gas lance in-out
SEQ-28.16 CNCGB NG lance
NG EQUIPMENT IN STOP POS.
.S1 BMS2
CNCG B EQ IN STOP POS
SEQ-28.07 CNCGB NG equipment in stop position
&
FAILURE RESET
.S10 BMS2
CNCGB FAILURE RESET OPR
SEQ-28.70 CNCGB Common local controls E
PRELIMINARY
Rev. Designed by Checked by Approved by Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA 8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Page:
CNCGB NG BURNER FAILURE Cust. Doc. ID:
3 5/29/2020/TREJARVEJO 5/29/2020/FTAMJNS 5/29/2020/FTAMSRE
Pos.
SEQ-28.06
Doc. ID: P00592320
0 1 2 3 4 5 6 7
This document is the exclusive intellectual property of Metso Power AB/Metso Power Oy/Metso Paper USA, Inc./Metso Paper Sulamericana Ltda and is furnished for the sole purpose of operating and maintaining of the specific project,
A
and re-use of the document for any other project or purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of the company.
PRELIMINARY
Rev. Designed by Checked by Approved by Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA 8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Page:
CNCGB NG EQUIPMENT IN STOP POSITION Cust. Doc. ID:
3 5/29/2020/TREJARVEJO 5/29/2020/FTAMJNS 5/29/2020/FTAMSRE
Pos.
SEQ-28.07
Doc. ID: P00592320
0 1 2 3 4 5 6 7
IGNITER &
IN COMMAND DCS DI
BMS2 DO
IN
IGNITER INTERLOCKING OK PROT
252-BX-804.S6 BMS2 REL
CNCG B igniter & IN POSITION & NOT FAILURE
CNCG B IGNITER IN 252-HSV-811.S11 BMS2
SEQ-28.09 CNCGB Igniter ->A IN-OUT CNCG B igniter in-out
OUT SEQ-28.03 CNCGB NG start sequence
BURNER NG FAILURE (PULSED) SEQ-28.09 CNCGB Igniter
.S6 BMS2 AUTO 252-HSV-811 SEQ-28.11 CNCGB NG valves
OUT
CNCG B NG FAILURE CONTROL & PROT SEQ-28.14 CNCGB igniter local control
SEQ-28.06 CNCGB NG burner failure REL SEQ-30.11 CNCGB Start sequence MeOH
RESET SEQ-30.12 CNCGB Stop sequence MeOH
SEQ-28.03 CNCGB NG start sequence
OIL&MEOH BURNER NOT RUNNING SEQ-28.04 CNCGB NG stop sequence SEQ-30.16 CNCGB MeoH valves
BMS2
Oil burner running/starting SEQ-30.11 CNCGB Start sequence MeOH
INT-28.27 Oil burner start conditions SEQ-30.12 CNCGB Stop sequence MeOH
IGNITER
OUT COMMAND
D
OUT POSITION LIMIT
252-HSV-811.ZSO BMS2
MeOH ADDITION OIL&NG BURNER NOT RUNNING CNCG B igniter in-out
BMS2 SEQ-28.04 CNCGB NG stop sequence
Oil burner running/starting
SEQ-28.14 CNCGB igniter local control
INT-28.27 Oil burner start conditions SEQ-30.14 CNCGB Burner failure MeOH
3
CNCG BURNER FAILURE MEOH &
S6 BMS
CNCG B Failure Control MeOH
SEQ-30.14 CNCGB Burner failure MeOH AUTO
OPEN
PROT
IGNITER/BLOWING OK
.S3 BMS2 REL
CNCG MAIN INTERLOCK CNCG B IGNITER
INT-28.11 CNCGB main common interlocks ->A INSTRUMENT
AIR VALVE
IGNITER FLAME ON
CLOSE
252-BX-804.S1 BMS2
AUTO 252-HSV-816 E
PROT
CNCG B igniter
REL
INT-28.14 CNCGB igniter
FAILURE RESET
.S10 BMS2
CNCGB FAILURE RESET OPR
SEQ-28.70 CNCGB Common local controls PRELIMINARY
Rev. Designed by Checked by Approved by Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA 8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Page:
CNCGB IGNITER CYLINDER Cust. Doc. ID:
3 5/29/2020/TREJARVEJO 5/29/2020/FTAMJNS 5/29/2020/FTAMSRE
Pos.
SEQ-28.08
Doc. ID: P00592320
0 1 2 3 4 5 6 7
A
IGNITER ON COMMAND 1
.S2 BMS2
CNCGB IGNITER TEST CONTROL
SEQ-28.14 CNCGB igniter local control
and re-use of the document for any other project or purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of the company.
TRIPPED &
N7:30/4
A3-C000533-252-00-002 A5
IGNITER FLAME ON B
252-BX-804.S1 BMS2
IGNITER OFF COMMAND CNCG B igniter
.S3 BMS2 INT-28.14 CNCGB igniter
CNCGB IGNITER TEST CONTROL
SEQ-28.14 CNCGB igniter local control
OIL SEQUENCE
STOP IGNITER TRANSFORM ON COMMAND
PAGE 1 A6
START
AUTO IGNITER ON COMMAND 252-BX-804.S10 BMS2
PROT FLAME ON CNCG B igniter
1 REL INT-28.14 CNCGB igniter
BURNER NG FAILURE (PULSED) CNCG B IGNITER ON
.S6 BMS2 ->A
CNCG B NG FAILURE CONTROL OFF
SEQ-28.06 CNCGB NG burner failure
& C
Monitoring time in BMS
AUTO 252-BX-804
STOP
PROT On = 10 s
OIL&MEOH BURNER NOT RUNNING
BMS2 REL Off = 20 s
Oil burner running/starting
INT-28.27 Oil burner start conditions
3 SEQ-28.03 CNCGB NG start sequence
SEQ-28.04 CNCGB NG stop sequence
©Metso Power AB or ©Metso Power Oy or ©Metso Paper USA, Inc. or ©Metso Paper Sulamericana Ltda.
IGNITER/BLOWING OK
.S3 BMS2
CNCG MAIN INTERLOCK
INT-28.11 CNCGB main common interlocks IGNITER INTERLOCKING OK
& 252-BX-804.S6 BMS2
180 s CNCG B igniter
IGNITER FLAME & CONTROL ON SEQ-28.08 CNCGB Igniter cylinder
252-BX-804.S3 BMS2 ON
SEQ-28.14 CNCGB igniter local control
CNCG B igniter
INT-28.14 CNCGB igniter T1
IGNITER ON FAILURE
252-BX-804.S4 BMS2
CNCG B igniter E
INT-28.14 CNCGB igniter
1
IGNITER OFF FAILURE IGNITER FAILURE
252-BX-804.S5 BMS2 252-BX-804.S7 BMS2
CNCG B igniter CNCG B igniter
INT-28.14 CNCGB igniter SEQ-28.07 CNCGB NG equipment in stop position
SEQ-30.15 CNCGB Equipment in stop position MeOH
PRELIMINARY
Rev. Designed by Checked by Approved by Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA 8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Page:
CNCGB IGNITER Cust. Doc. ID:
3 5/29/2020/TREJARVEJO 5/29/2020/FTAMJNS 5/29/2020/FTAMSRE
Pos.
SEQ-28.09
Doc. ID: P00592320
0 1 2 3 4 5 6 7
IN POSITION & NOT FAILURE NOTE: VALVE FAILURE
252-HSV-811.S11 BMS2 252-HSV-814 BMS2
CNCG B igniter in-out LOGIC SPLITTED IN TWO PAGES CNCG B natural gas valve 1
SEQ-28.08 CNCGB Igniter cylinder SEE INT-28.15 INT-28.16 CNCGB burner NG valves
&
OPEN LIMIT & OPEN LIMIT & NOT FAILURE
This document is the exclusive intellectual property of Metso Power AB/Metso Power Oy/Metso Paper USA, Inc./Metso Paper Sulamericana Ltda and is furnished for the sole purpose of operating and maintaining of the specific project,
IGNITER FLAME & CONTROL ON AUTO OPEN COMMAND ON 252-HSV-814.ZSO BMS2 252-HSV-814.S11 BMS2 A
OPEN
252-BX-804.S3 BMS2 PROT CNCG B natural gas valve 1 CNCG B natural gas valve 1
CNCG B igniter 1
REL INT-28.16 CNCGB burner NG valves SEQ-28.03 CNCGB NG start sequence
INT-28.14 CNCGB igniter SEQ-28.12 CNCGB NG leakage test sequence
CNCG B NATURAL OPEN
->A GAS VALVE 1
and re-use of the document for any other project or purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of the company.
CLOSE
CLOSE
AUTO 252-HSV-814 CLOSE LIMIT & CLOSED LIMIT & NOT FAILURE
PROT 252-HSV-814.ZSC BMS2 252-HSV-814.S12 BMS2
REL CNCG B natural gas valve 1 CNCG B natural gas valve 1
INT-28.16 CNCGB burner NG valves SEQ-28.04 CNCGB NG stop sequence
SEQ-28.03 CNCGB NG start sequence SEQ-28.07 CNCGB NG equipment in stop position
SEQ-28.04 CNCGB NG stop sequence OPEN COMMAND ON SEQ-28.12 CNCGB NG leakage test sequence
SEQ-28.12 CNCGB NG leakage test sequence 252-HSV-814.S10 BMS2 SEQ-28.13 CNCGB NG leakage test
CNCG B natural gas valve 1
SEQ-28.72 CNCGB Support fuel start release
INT-28.16 CNCGB burner NG valves
A
BURNER NG FAILURE B
.S4 BMS2
CNCG B NG FAILURE CONTROL & NG VALVES OPEN CMD
.S3 BMS2
SEQ-28.06 CNCGB NG burner failure CNCG B NG VALVES COMMON
&
SEQ-28.06 CNCGB NG burner failure
CNCG B NG VALVES INTERLOCK SEQ-28.15 CNCGB combustion air monitoring
.S1 BMS2
CNCG B NG INTERLOCK OPEN COMMAND ON
252-HSV-815.S10 BMS2
INT-28.12 CNCGB NG interlocks CNCG B natural gas valve 2
INT-28.16 CNCGB burner NG valves
VALVE FAILURE
252-HSV-815 BMS2
CNCG B natural gas valve 2
INT-28.16 CNCGB burner NG valves
OPEN
PROT CNCG B natural gas valve 2 CNCG B natural gas valve 2
REL INT-28.16 CNCGB burner NG valves SEQ-28.03 CNCGB NG start sequence
CNCG B NATURAL SEQ-28.12 CNCGB NG leakage test sequence
OPEN
->A GAS VALVE 2
©Metso Power AB or ©Metso Power Oy or ©Metso Paper USA, Inc. or ©Metso Paper Sulamericana Ltda.
A CLOSE
&
CLOSE
1 AUTO 252-HSV-815 CLOSE LIMIT & CLOSED LIMIT & NOT FAILURE
B PROT 252-HSV-815.ZSC BMS2 252-HSV-815.S12 BMS2
REL CNCG B natural gas valve 2 CNCG B natural gas valve 2
INT-28.16 CNCGB burner NG valves SEQ-28.04 CNCGB NG stop sequence
SEQ-28.03 CNCGB NG start sequence SEQ-28.07 CNCGB NG equipment in stop position
SEQ-28.04 CNCGB NG stop sequence SEQ-28.12 CNCGB NG leakage test sequence
SEQ-28.12 CNCGB NG leakage test sequence SEQ-28.13 CNCGB NG leakage test
SEQ-28.72 CNCGB Support fuel start release
VALVE FAILURE D
252-HSV-830 BMS2
& 1 CNCG B natural gas vent valve
INT-28.16 CNCGB burner NG valves
AUTO 252-HSV-830
PROT
REL CLOSE COMMAND ON
CLOSE LIMIT & CLOSED LIMIT & NOT FAILURE
SEQ-28.03 CNCGB NG start sequence 252-HSV-830.ZSC BMS2 252-HSV-830.S12 BMS2 E
SEQ-28.04 CNCGB NG stop sequence CNCG B natural gas vent valve CNCG B natural gas vent valve
SEQ-28.12 CNCGB NG leakage test sequence INT-28.16 CNCGB burner NG valves SEQ-28.03 CNCGB NG start sequence
SEQ-28.12 CNCGB NG leakage test sequence
CLOSE COMMAND ON
252-HSV-830.S10 BMS2
CNCG B natural gas vent valve
INT-28.16 CNCGB burner NG valves
PRELIMINARY
Rev. Designed by Checked by Approved by Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA 8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Page:
CNCGB NG VALVES Cust. Doc. ID:
3 5/29/2020/TREJARVEJO 5/29/2020/FTAMJNS 5/29/2020/FTAMSRE
Pos.
SEQ-28.11
Doc. ID: P00592320
0 1 2 3 4 5 6 7
IN STOP POSITION
.S1
CNCG B EQUIPMENT/LEAK TEST A
This document is the exclusive intellectual property of Valmet Corporation and/or its subsidiaries and is furnished solely for operating and maintaining the specific project. Re-use of the document for any other
&
CNCG BURNER ES NOT ON
252-LCP-150.PB02.S1 BMS2 B
P> MIN1 CNCG B emergency stop
252-PI-834 BMS2 INT-28.11 CNCGB main common interlocks CNCG B LEAKAGE TEST READY CNCG B LEAKAGE TEST RUNNING
NC-CB3-KJ5093.S1 NC-CB3-KJ5093.S11
CNCG B natural gas pressure
INT-28.12 CNCGB NG interlocks STATUS STATUS
ES NOT PUSHED
BMS2 DCS DI DCS DI
Natural gas emergency stop
INT-28.12 CNCGB NG interlocks BMS2 DO BMS2 DO
C
3s
START LEAKAGE TEST
.S56
CNCG B NG STOP SEQUENCE
SEQ-28.04 CNCGB NG stop sequence NC-CB3-H10038.S1 3s 1 RUNNING
S1 STEP
.S11
CNCG B LEAKAGE START DCS DO NC-CB3-H10038.S2
DI BMS2 CNCG B NG LEAKAGE TEST SEQ
S2 STEP
D
3s
SEQUENCE STEP NUMBER
1
NC-CB3-KJ5093.I1
STATUS
ALWAYS
LOCAL STOP
TO STOP STEP A-MODE.
252-LCP-150.PB09.S1 BMS2 1
Into page: 5
CNCG B NG burner stop PROT AON REL DCS DI
SEQ-28.05 CNCGB NG local controls STEP I1INTEGER
Rev. Created By Inspected By Released By Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA
8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Cust. Doc ID Page:
CNCGB NG LEAKAGE TEST SEQUENCE
3 5/29/2020/TREJARVEJO
5/29/2020/FTAMJNS 5/29/2020/FTAMSRE SEQ-28.12
Pos. 1
Doc ID: P00592320
0 1 2 3 4 5 6 7
STEP START
P > MIN 2
252-PI-837.L2 BMS2
CNCG B natural gas Pressure (leak test)
SEQ-28.13 CNCGB NG leakage test TO FAILURE STEP
3
Into page: 4
STEP 5 PRELIMINARY
Rev. Created By Inspected By Released By Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA
8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Cust. Doc ID Page:
CNCGB NG LEAKAGE TEST SEQUENCE
3 5/29/2020/TREJARVEJO
5/29/2020/FTAMJNS 5/29/2020/FTAMSRE SEQ-28.12
Pos. 2
Doc ID: P00592320
0 1 2 3 4 5 6 7
STEP 4
TESTING VALVE 1
20s 25s
FAILURE .F5
CNCG B NG LEAKAGE TEST SEQ
SEQ-28.13 CNCGB NG leakage test
STEP 9 PRELIMINARY
Rev. Created By Inspected By Released By Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA
8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Cust. Doc ID Page:
CNCGB NG LEAKAGE TEST SEQUENCE
3 5/29/2020/TREJARVEJO
5/29/2020/FTAMJNS 5/29/2020/FTAMSRE SEQ-28.12
Pos. 3
Doc ID: P00592320
0 1 2 3 4 5 6 7
STEP 8
TO END STEP
10
Into page: 5
TO FAILURE STEP
3
From page: 2
TO FAILURE STEP
6
From page: 3
D
FAILURE STEP
LEAK TEST FAILURE
WAITING TIME MONITORING TIME ACTION .F11
11 s s
CNCG B NG LEAKAGE TEST SEQ
SEQ-28.13 CNCGB NG leakage test
E
STEP 12
PRELIMINARY
Rev. Created By Inspected By Released By Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA
8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Cust. Doc ID Page:
CNCGB NG LEAKAGE TEST SEQUENCE
3 5/29/2020/TREJARVEJO
5/29/2020/FTAMJNS 5/29/2020/FTAMSRE SEQ-28.12
Pos. 4
Doc ID: P00592320
0 1 2 3 4 5 6 7
STEP 11
TO STOP STEP
1 A
From page: 1
This document is the exclusive intellectual property of Valmet Corporation and/or its subsidiaries and is furnished solely for operating and maintaining the specific project. Re-use of the document for any other
TO STOP STEP
5
From page: 3
TO STOP STEP
8
From page: 3
project or purpose is prohibited. The document or the information shall not be reproduced, copied or disclosed to a third party without prior written consent of the company.
STOP STEP B
AUTO OPEN
WAITING TIME MONITORING TIME ACTION 252-HSV-830
12 1s s
CNCG B natural gas vent valve
OPEN LIMIT & NOT FAILURE SEQ-28.11 CNCGB NG valves
252-HSV-830.S11 BMS2
CNCG B natural gas vent valve
AUTO CLOSE
SEQ-28.11 CNCGB NG valves
252-HSV-814
CNCG B natural gas valve 1
CLOSED LIMIT & NOT FAILURE SEQ-28.11 CNCGB NG valves
252-HSV-814.S12 BMS2 &
CNCG B natural gas valve 1 C
AUTO CLOSE
SEQ-28.11 CNCGB NG valves
252-HSV-815
CNCG B natural gas valve 2
CLOSED LIMIT & NOT FAILURE SEQ-28.11 CNCGB NG valves
252-HSV-815.S12 BMS2
CNCG B natural gas valve 2 RESET
SEQ-28.11 CNCGB NG valves 252-PIC-835.S11
CNCG B natural gas pressure
CNT-28.01 CNCG burner NG flow and pressure
TO END STEP
10 D
From page: 4
READY
SEQ COMPLETED
WAITING TIME MONITORING TIME ACTION 13
Into page: 1
13 s s
PRELIMINARY
Rev. Created By Inspected By Released By Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA
8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Cust. Doc ID Page:
CNCGB NG LEAKAGE TEST SEQUENCE
3 5/29/2020/TREJARVEJO
5/29/2020/FTAMJNS 5/29/2020/FTAMSRE SEQ-28.12
Pos. 5
Doc ID: P00592320
0 1 2 3 4 5 6 7
VALVE FAILURE
252-HSV-814 BMS2
CNCG B natural gas valve 1
INT-28.16 CNCGB burner NG valves
This document is the exclusive intellectual property of Metso Power AB/Metso Power Oy/Metso Paper USA, Inc./Metso Paper Sulamericana Ltda and is furnished for the sole purpose of operating and maintaining of the specific project,
4s A
VALVE FAILURE LEAKAGE TEST OK VALID
252-HSV-815 BMS2 1 .S10 S .S1 BMS2
CNCG B natural gas valve 2 CNCG B NG LEAKAGE TEST SEQ .T2 CNCG B LEAKAGE TEST
INT-28.16 CNCGB burner NG valves SEQ-28.12 CNCGB NG leakage test sequence 2s R TIME RUNNING DOWN IN DCS DISPLAY SEQ-28.03 CNCGB NG start sequence
CNCG B LEAKAGE TEST TIME XX d ; XX h
and re-use of the document for any other project or purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of the company.
RUNNING STATUS
BMS2 DO DI DCS
.S11 BMS2 & ALARM
CNCG B NG LEAKAGE TEST SEQ
SEQ-28.12 CNCGB NG leakage test sequence
&
LEAK TEST FAILURE 1 FAILURE CNCG B NATURAL D
.F11 S .S3 GAS PRESSURE (LEAK
CNCG B NG LEAKAGE TEST SEQ CNCG B LEAK TEST FAILURE TEST)
SEQ-28.12 CNCGB NG leakage test sequence R SEQ-28.12 CNCGB NG leakage test sequence 252-PI-837 P < MAX 2
P< MAX2 bar(g) 252-PI-837.H2 BMS2
P> MIN2 bar(g) CNCG B natural gas Pressure (leak test)
CALCULATED LIMIT VALUES SEQ-28.12 CNCGB NG leakage test sequence
CLOSED LIMIT & NOT FAILURE
252-HSV-814.S12 BMS2 CNCG B EQUIPMENT/LEAK TEST P< MAX1 bar(g)
CNCG B natural gas valve 1 NC-CB3-X5094.S1 P > MIN 2
P> MIN1 bar(g)
SEQ-28.11 CNCGB NG valves 252-PI-837.L2 BMS2
STATUS CNT-28.01 CNCG burner NG flow and pressure CNCG B natural gas Pressure (leak test)
SEQ-28.12 CNCGB NG leakage test sequence
CLOSED LIMIT & NOT FAILURE
252-HSV-815.S12 BMS2 &
CNCG B natural gas valve 2 DCS DI
P < MAX 1 (CALC)
SEQ-28.11 CNCGB NG valves 252-PI-837.H1 BMS2
CNCG B natural gas Pressure (leak test)
BMS2 DO
SEQ-28.12 CNCGB NG leakage test sequence
OPEN LIMIT & NOT FAILURE IN STOP POSITION
252-HSV-830.S11 BMS2 .S1 E
CNCG B natural gas vent valve CNCG B EQUIPMENT/LEAK TEST P > MIN 1 (CALC)
SEQ-28.11 CNCGB NG valves SEQ-28.12 CNCGB NG leakage test sequence 252-PI-837.L1 BMS2
CNCG B natural gas Pressure (leak test)
SEQ-28.12 CNCGB NG leakage test sequence
FAILURE RESET &
.S10 BMS2
CNCGB FAILURE RESET OPR
SEQ-28.70 CNCGB Common local controls PRELIMINARY
Rev. Designed by Checked by Approved by Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA 8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Page:
CNCGB NG LEAKAGE TEST Cust. Doc. ID:
3 5/29/2020/TREJARVEJO 5/29/2020/FTAMJNS 5/29/2020/FTAMSRE
Pos.
SEQ-28.13
Doc. ID: P00592320
0 1 2 3 4 5 6 7
3s
This document is the exclusive intellectual property of Metso Power AB/Metso Power Oy/Metso Paper USA, Inc./Metso Paper Sulamericana Ltda and is furnished for the sole purpose of operating and maintaining of the specific project,
PUSHED
252-LCP-150.PB05.S1 BMS2 A
CNCG B igniter start
SEQ-28.70 CNCGB Common local controls
and re-use of the document for any other project or purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of the company.
1s
IGNITER IN COMMAND
S .S1 BMS2
CNCGB IGNITER TEST CONTROL
R SEQ-28.08 CNCGB Igniter cylinder
IGNITER INTERLOCKING OK 1s B
252-BX-804.S6 BMS2
CNCG B igniter IN POSITION & NOT FAILURE & IGNITER ON COMMAND
1 252-HSV-811.S11 BMS2 .S2 BMS2
SEQ-28.09 CNCGB Igniter CNCG B igniter in-out CNCGB IGNITER TEST CONTROL
SEQ-28.08 CNCGB Igniter cylinder SEQ-28.09 CNCGB Igniter
30 s
ON
C
1s
3s 1s
©Metso Power AB or ©Metso Power Oy or ©Metso Paper USA, Inc. or ©Metso Paper Sulamericana Ltda.
IGNITER FLAME ON
252-BX-804.S1 BMS2
CNCG B igniter
INT-28.14 CNCGB igniter
PRELIMINARY
Rev. Designed by Checked by Approved by Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA 8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Page:
CNCGB IGNITER LOCAL CONTROL Cust. Doc. ID:
3 5/29/2020/TREJARVEJO 5/29/2020/FTAMJNS 5/29/2020/FTAMSRE
Pos.
SEQ-28.14
Doc. ID: P00592320
0 1 2 3 4 5 6 7
NG VALVES OPEN CMD
.S3 BMS2
CNCG B NG VALVES COMMON
SEQ-28.11 CNCGB NG valves
1
This document is the exclusive intellectual property of Metso Power AB/Metso Power Oy/Metso Paper USA, Inc./Metso Paper Sulamericana Ltda and is furnished for the sole purpose of operating and maintaining of the specific project,
RUNNING
.S12 BMS2 A
CNCG B NG STOP SEQUENCE
SEQ-28.04 CNCGB NG stop sequence
3 MEOH ADDITION
AIR DAMPER NOT CLOSED
and re-use of the document for any other project or purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of the company.
252-HIC-817.S1 BMS2
CNCG Comb.air damper open CNCG B COMBUSTION AIR (NG)
INT-28.11 CNCGB main common interlocks FAILURE
& 252-HIC-817.S1
IN AUTO MODE & STATUS
252-HIC-817 BMS2 & ALARM
CNCG B combustion air damper
SEQ-28.03 CNCGB NG start sequence
DCS DI
B
BMS2 DO
20 s
SET MONITORING ON COMB. AIR FAILURE/NG
ON
252-HIC-817 BMS2 S S 252-HIC-817 BMS2
CNCG B combustion air damper CNCG B combustion air damper
2s
SEQ-28.03 CNCGB NG start sequence R R SEQ-28.06 CNCGB NG burner failure
2s
1
BURNER NG FAILURE
.S4 BMS2
CNCG B NG FAILURE CONTROL
SEQ-28.06 CNCGB NG burner failure
C
FAILURE RESET
.S10 BMS2
3
CNCGB FAILURE RESET OPR
SEQ-28.70 CNCGB Common local controls
CNCGB MEOH VALVES OPEN CMD
S3 BMS
©Metso Power AB or ©Metso Power Oy or ©Metso Paper USA, Inc. or ©Metso Paper Sulamericana Ltda.
DCS RB DI
BMS RB DO
20 s
SET MONITORING ON (MEOH) COMB. AIR FAILURE (MEOH)
ON
252-HIC-817S12 BMS S S 252-HIC-817.S4 BMS
CNCG B combustion air damper CNCG B combustion air damper
2s
SEQ-30.12 CNCGB Stop sequence MeOH R R SEQ-30.14 CNCGB Burner failure MeOH
SEQ-30.11 CNCGB Start sequence MeOH
2s E
1
Rev. Designed by Checked by Approved by Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA 8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Page:
CNCGB COMBUSTION AIR MONITORING Cust. Doc. ID:
3 5/29/2020/TREJARVEJO 5/29/2020/FTAMJNS 5/29/2020/FTAMSRE
Pos.
SEQ-28.15
Doc. ID: P00592320
0 1 2 3 4 5 6 7
This document is the exclusive intellectual property of Metso Power AB/Metso Power Oy/Metso Paper USA, Inc./Metso Paper Sulamericana Ltda and is furnished for the sole purpose of operating and maintaining of the specific project,
GAS LANCE IN A
252-ZS-808.ZSI BMS2
CNCG B natural gas lance in position
INT-28.12 CNCGB NG interlocks
and re-use of the document for any other project or purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of the company.
DCS DI
BMS2 DO
FAILURE
252-HSV-812.FLT BMS2
CNCG B natural gas lance in-out
SEQ-28.06 CNCGB NG burner failure
AUTO FAILURE
IN
PROT
REL IN POSITION & NOT FAILURE
&
->A
CNCG B NATURAL IN 252-HSV-812.S11 BMS2 C
CLOSE LIMIT GAS LANCE IN-OUT CNCG B natural gas lance in-out
252-HSV-814.ZSC BMS2 SEQ-28.03 CNCGB NG start sequence
CNCG B natural gas valve 1 OUT
INT-28.16 CNCGB burner NG valves 1 AUTO 252-HSV-812
OUT
CLOSE LIMIT PROT
252-HSV-815.ZSC BMS2 REL
©Metso Power AB or ©Metso Power Oy or ©Metso Paper USA, Inc. or ©Metso Paper Sulamericana Ltda.
FAILURE RESET
.S10 BMS2
CNCGB FAILURE RESET OPR
SEQ-28.70 CNCGB Common local controls
& OUT POSITION & NOT FAILURE
252-HSV-812.S12 BMS2 D
CNCG B natural gas lance in-out
SEQ-28.04 CNCGB NG stop sequence
SEQ-28.07 CNCGB NG equipment in stop position
PRELIMINARY
Rev. Designed by Checked by Approved by Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA 8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Page:
CNCGB NG LANCE Cust. Doc. ID:
3 5/29/2020/TREJARVEJO 5/29/2020/FTAMJNS 5/29/2020/FTAMSRE
Pos.
SEQ-28.16
Doc. ID: P00592320
0 1 2 3 4 5 6 7
A
This document is the exclusive intellectual property of Valmet Corporation and/or its subsidiaries and is furnished solely for operating and maintaining the specific project. Re-use of the document for any other
A
This document is the exclusive intellectual property of Valmet Corporation and/or its subsidiaries and is furnished solely for operating and maintaining the specific project. Re-use of the document for any other
STEP START
FLUSHING ON
SET FLUSH POSITION
WAITING TIME MONITORING TIME ACTION 252-PIC-846B.S1 BMS2
1 1s s
LP Steam to CNCG RB2 burner
project or purpose is prohibited. The document or the information shall not be reproduced, copied or disclosed to a third party without prior written consent of the company.
252-PIC-846B.S8
S8 STEP
S7 STEP
CNCG pressure to CNCG burner AUTO MODE ON
BMS2 DO DI DCS 252-PIC-846B
& LP Steam to CNCG RB2 burner
CNT-28.12 CNCG pressure to CNCG burner
OK 252-PIC-846.S5 INT-28.23 CNCG pressure to burner
S5 STEP
252-PIC-846.S10 BMS2 AUTO MODE ON
CNCG pressure to CNCG burner BMS2 DO DI DCS 252-PIC-846
INT-28.23 CNCG pressure to burner CNCG pressure to CNCG burner
CNT-28.12 CNCG pressure to CNCG burner
INT-28.23 CNCG pressure to burner
SET MONITORING ON
252-PIC-846B.S5 BMS2
LP Steam to CNCG RB2 burner E
SEQ-28.48 CNCGB CNCG lance pressure monitoring
STEP 4
PRELIMINARY
Rev. Created By Inspected By Released By Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA
8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Cust. Doc ID Page:
CNCGB CNCG START SEQUENCE
3 5/29/2020/TREJARVEJO
5/29/2020/FTAMJNS 5/29/2020/FTAMSRE SEQ-28.41
Pos. 2
Doc ID: P00592320
0 1 2 3 4 5 6 7
STEP 3 A
This document is the exclusive intellectual property of Valmet Corporation and/or its subsidiaries and is furnished solely for operating and maintaining the specific project. Re-use of the document for any other
AUTO CLOSE
CLOSE CNCG VENT VALVE 252-HSV-879
CNCG RB2 vent valve 1
WAITING TIME MONITORING TIME ACTION SEQ-28.46 CNCGB CNCG valves
4 3s s
SET FLUSHING BIT ON
.S5 BMS2
CNCG B CNCG START SEQUENCE
SEQ-28.42 CNCGB CNCG stop sequence
project or purpose is prohibited. The document or the information shall not be reproduced, copied or disclosed to a third party without prior written consent of the company.
S3 STEP
RAMP UPWARDS
WAITING TIME MONITORING TIME ACTION BMS2 DO DI DCS 252-HIC-878.S3
5 3s s
CNCG valve 2 to CNCG RB2 burner
CNT-28.12 CNCG pressure to CNCG burner
AUTO OPEN C
252-HSV-880
CNCG valve 3 to CNCG RB2 burner
SEQ-28.46 CNCGB CNCG valves
READY
SEQ COMPLETED
WAITING TIME MONITORING TIME ACTION 6
Into page: 1
6 s s
E
PRELIMINARY
Rev. Created By Inspected By Released By Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA
8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Cust. Doc ID Page:
CNCGB CNCG START SEQUENCE
3 5/29/2020/TREJARVEJO
5/29/2020/FTAMJNS 5/29/2020/FTAMSRE SEQ-28.41
Pos. 3
Doc ID: P00592320
0 1 2 3 4 5 6 7
IGNITER/BLOWING OK
.S3 BMS2
CNCG MAIN INTERLOCK
INT-28.11 CNCGB main common interlocks
A
This document is the exclusive intellectual property of Valmet Corporation and/or its subsidiaries and is furnished solely for operating and maintaining the specific project. Re-use of the document for any other
DCS DI
252-ZS-810 BMS2 STEP S4
CNCG burner lance limit switch B
BMS2 DO
INT-28.21 CNCGB CNCG interlocks
3s
OPERATOR STOP
.S1 BMS2
CNCG B CNCG OPR CONTROL
SEQ-28.41 CNCGB CNCG start sequence 3s 1
OPERATION FAILURE
.S1 BMS2
CNCG B CNCG BURNER FAILURE C
SEQ-28.44 CNCGB CNCG burner failure & CNCG B CNCG GAS IN PIPE
SET FLUSHING BIT ON NC-CB3-KJ10006.S1
.S5 BMS2 S
STATUS
CNCG B CNCG START SEQUENCE
SEQ-28.41 CNCGB CNCG start sequence R SEQUENCE STEP NUMBER
DCS DI
NC-CB3-KJ10007.I1
STEP S1
STATUS CNCG B CNCG STOP SEQUENCE RUN
BMS2 DO NC-CB3-KJ10007.S12
FAILURE RESET
.S10 BMS2 STATUS
CNCGB FAILURE RESET OPR DCS DI
SEQ-28.70 CNCGB Common local controls STEP INTEGER
I1 D
3s PROT ->M MON REL
ALWAYS
STOPPING FAILURE BMS2 DO
.S3 BMS2 ON 1
M-MODE DCS DI
CNCG B CNCG STOP SEQUENCE STEP S12
CNCG B CNCG BURNER FAILURE
SEQ-28.44 CNCGB CNCG burner failure INIT STEP BMS2 DO
3s SHUT-DOWN PROGRAM RUN
SEQ COMPLETED .S12
57
From page: 3 CNCG B CNCG STOP SEQUENCE
SEQ-28.41 CNCGB CNCG start sequence
SEQ-28.43 CNCGB CNCG local controls
SEQ-28.44 CNCGB CNCG burner failure
INT-28.27 Oil burner start conditions
VALVE FAILURE 1 &
JUMP TO STEP 56 E
.S5 BMS2 50
Into page: 3
CNCG B CNCG BURNER FAILURE
SEQ-28.44 CNCGB CNCG burner failure
STEP 51 PRELIMINARY
Rev. Created By Inspected By Released By Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA
8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Cust. Doc ID Page:
CNCGB CNCG STOP SEQUENCE
3 5/29/2020/TREJARVEJO
5/29/2020/FTAMJNS 5/29/2020/FTAMSRE SEQ-28.42
Pos. 1
Doc ID: P00592320
0 1 2 3 4 5 6 7
A
This document is the exclusive intellectual property of Valmet Corporation and/or its subsidiaries and is furnished solely for operating and maintaining the specific project. Re-use of the document for any other
STEP START
S4 STEP
RAMP DOWNWADS
WAITING TIME MONITORING TIME ACTION BMS2 DO DI DCS 252-HIC-878.S4
51 1s s
CNCG valve 2 to CNCG RB2 burner
CNT-28.12 CNCG pressure to CNCG burner
project or purpose is prohibited. The document or the information shall not be reproduced, copied or disclosed to a third party without prior written consent of the company.
FLUSHING TIME
STEP 56
PRELIMINARY
Rev. Created By Inspected By Released By Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA
8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Cust. Doc ID Page:
CNCGB CNCG STOP SEQUENCE
3 5/29/2020/TREJARVEJO
5/29/2020/FTAMJNS 5/29/2020/FTAMSRE SEQ-28.42
Pos. 2
Doc ID: P00592320
0 1 2 3 4 5 6 7
A
This document is the exclusive intellectual property of Valmet Corporation and/or its subsidiaries and is furnished solely for operating and maintaining the specific project. Re-use of the document for any other
STEP 55
JUMP TO STEP 56
50
From page: 1
project or purpose is prohibited. The document or the information shall not be reproduced, copied or disclosed to a third party without prior written consent of the company.
FLUSHING OFF B
RESET FLUSH POSITION
WAITING TIME MONITORING TIME ACTION 252-PIC-846B.S4 BMS2
56 1s s
LP Steam to CNCG RB2 burner
CNT-28.12 CNCG pressure to CNCG burner
S7 STEP
MAN MODE ON
BMS2 DO DI DCS 252-PIC-846B
LP Steam to CNCG RB2 burner
CNT-28.12 CNCG pressure to CNCG burner
INT-28.23 CNCG pressure to burner
HEATING POSITION
252-PIC-846B.S6 BMS2
LP Steam to CNCG RB2 burner C
CNT-28.12 CNCG pressure to CNCG burner
S8 STEP
MAN MODE ON
BMS2 DO DI DCS 252-PIC-846
CNCG pressure to CNCG burner
CNT-28.12 CNCG pressure to CNCG burner
252-PIC-846.S3 INT-28.23 CNCG pressure to burner
S3 STEP
S6 STEP
OPEN TO 100%
BMS2 DO DI DCS 252-PIC-846.S3 DCS
CNCG pressure to CNCG burner
INT-28.23 CNCG pressure to burner
D
READY
SEQ COMPLETED
WAITING TIME MONITORING TIME ACTION 57
Into page: 1
57 s s
PRELIMINARY
Rev. Created By Inspected By Released By Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA
8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Cust. Doc ID Page:
CNCGB CNCG STOP SEQUENCE
3 5/29/2020/TREJARVEJO
5/29/2020/FTAMJNS 5/29/2020/FTAMSRE SEQ-28.42
Pos. 3
Doc ID: P00592320
0 1 2 3 4 5 6 7
This document is the exclusive intellectual property of Metso Power AB/Metso Power Oy/Metso Paper USA, Inc./Metso Paper Sulamericana Ltda and is furnished for the sole purpose of operating and maintaining of the specific project,
LAMP TEST ON
and re-use of the document for any other project or purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of the company.
252-LCP-150.PB01.S1 BMS2
CNCG B lamp test
SEQ-28.05 CNCGB NG local controls
CNCG B READY
READY TO START CNCG 1 FOR START CNCG
.S4 BMS2
CNCG B CNCG START SEQUENCE
252-43-150.XL14
SEQ-28.41 CNCGB CNCG start sequence
PILOT LAMP
B
1 CNCG B CNCG
©Metso Power AB or ©Metso Power Oy or ©Metso Paper USA, Inc. or ©Metso Paper Sulamericana Ltda.
2 Hz
PRELIMINARY
Rev. Designed by Checked by Approved by Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA 8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Page:
CNCGB CNCG LOCAL CONTROLS Cust. Doc. ID:
3 5/29/2020/TREJARVEJO 5/29/2020/FTAMJNS 5/29/2020/FTAMSRE
Pos.
SEQ-28.43
Doc. ID: P00592320
0 1 2 3 4 5 6 7
NC-CB3-X10017.S1 A
STATUS CNCG B CNCG STARTING
NC-CB3-X10017.S2
STATUS CNCG B CNCG STOPPING
NC-CB3-X10017.S3
and re-use of the document for any other project or purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of the company.
FAILURE RESET
.S10 BMS2
CNCGB FAILURE RESET OPR STOPPING FAILURE D
SEQ-28.70 CNCGB Common local controls .S3 BMS2
& CNCG B CNCG BURNER FAILURE
SEQ-28.42 CNCGB CNCG stop sequence
CNCG EQUIP. IN STOP POS.
.S1 BMS2 STARTING FAILURE
CNCG B CNCG EQ IN STOP POS .S2 BMS2
SEQ-28.45 CNCGB CNCG equipment in stop pos CNCG B CNCG BURNER FAILURE
SEQ-28.41 CNCGB CNCG start sequence
OPERATION FAILURE
VALVE FAILURE .S1 BMS2
.S5 CNCG B CNCG BURNER FAILURE
CNCG B CNCG BURNER FAILURE
SEQ-28.42 CNCGB CNCG stop sequence
INT-28.23 CNCG pressure to burner
DCS DI
NC-CB3-X10017.S5
BMS2 DO
1 VALVE FAILURE E
.S5 BMS2
CNCG B CNCG BURNER FAILURE
CNT-28.12 CNCG pressure to CNCG burner
SEQ-28.42 CNCGB CNCG stop sequence
PRELIMINARY
Rev. Designed by Checked by Approved by Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA 8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Page:
CNCGB CNCG BURNER FAILURE Cust. Doc. ID:
3 5/29/2020/TREJARVEJO 5/29/2020/FTAMJNS 5/29/2020/FTAMSRE
Pos.
SEQ-28.44
Doc. ID: P00592320
0 1 2 3 4 5 6 7
This document is the exclusive intellectual property of Metso Power AB/Metso Power Oy/Metso Paper USA, Inc./Metso Paper Sulamericana Ltda and is furnished for the sole purpose of operating and maintaining of the specific project,
A
and re-use of the document for any other project or purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of the company.
IN POSITION
252-ZS-810 BMS2
CNCG burner lance limit switch
INT-28.21 CNCGB CNCG interlocks
NOTE!
CLOSED LIMIT & NOT FAILURE POP-UP INTERLOCK
252-HIC-878.S12 BMS2 WINDOW IS NEEDED
CNCG valve 2 to CNCG RB2 burner
SEQ-28.46 CNCGB CNCG valves
252-HSV-879.S11 BMS2
CNCG RB2 vent valve 1
SEQ-28.46 CNCGB CNCG valves
BMS2 DO
PRELIMINARY
Rev. Designed by Checked by Approved by Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA 8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Page:
CNCGB CNCG EQUIPMENT IN STOP POS Cust. Doc. ID:
3 5/29/2020/TREJARVEJO 5/29/2020/FTAMJNS 5/29/2020/FTAMSRE
Pos.
SEQ-28.45
Doc. ID: P00592320
0 1 2 3 4 5 6 7
NOTE:
LOGIC SPLITTED IN TWO PAGES
SEE INT-28.24 VALVE FAILURE
252-HIC-878 BMS2
CNCG valve 2 to CNCG RB2 burner
This document is the exclusive intellectual property of Metso Power AB/Metso Power Oy/Metso Paper USA, Inc./Metso Paper Sulamericana Ltda and is furnished for the sole purpose of operating and maintaining of the specific project,
C
VALVE FAILURE
252-HSV-880 BMS2
CNCG valve 3 to CNCG RB2 burner
INT-28.24 CNCGB CNCG valves
©Metso Power AB or ©Metso Power Oy or ©Metso Paper USA, Inc. or ©Metso Paper Sulamericana Ltda.
OPEN
PROT CNCG valve 3 to CNCG RB2 burner CNCG valve 3 to CNCG RB2 burner
REL INT-28.24 CNCGB CNCG valves SEQ-28.41 CNCGB CNCG start sequence
CNCG VALVE 3 OPEN
->A TO CNCG RB2 BURNER
CLOSE
CLOSE
AUTO 252-HSV-880 OPEN LIMIT & CLOSED LIMIT & NOT FAILURE
PROT 252-HSV-880.ZSO BMS2 252-HSV-880.S12 BMS2
REL CNCG valve 3 to CNCG RB2 burner CNCG valve 3 to CNCG RB2 burner D
INT-28.24 CNCGB CNCG valves SEQ-28.42 CNCGB CNCG stop sequence
SEQ-28.41 CNCGB CNCG start sequence SEQ-28.45 CNCGB CNCG equipment in stop pos
SEQ-28.42 CNCGB CNCG stop sequence
VALVE FAILURE
252-HSV-879 BMS2
CNCG RB2 vent valve 1
INT-28.24 CNCGB CNCG valves
OFF
PROT CNCG RB2 vent valve 1 CNCG RB2 vent valve 1
REL INT-28.24 CNCGB CNCG valves SEQ-28.42 CNCGB CNCG stop sequence
SEQ-28.45 CNCGB CNCG equipment in stop pos
CNCG RB2 VENT OPEN
->A VALVE 1
CLOSE
CLOSE
AUTO 252-HSV-879 CLOSE LIMIT & CLOSED LIMIT & NOT FAILURE E
PROT 252-HSV-879.ZSC BMS2 252-HSV-879.S12 BMS2
REL CLOSE COMMAND ON CNCG RB2 vent valve 1 CNCG RB2 vent valve 1
SEQ-28.41 CNCGB CNCG start sequence INT-28.24 CNCGB CNCG valves SEQ-28.41 CNCGB CNCG start sequence
SEQ-28.42 CNCGB CNCG stop sequence CLOSE COMMAND ON
252-HSV-879.S10 BMS2
CNCG RB2 vent valve 1
INT-28.24 CNCGB CNCG valves PRELIMINARY
Rev. Designed by Checked by Approved by Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA 8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Page:
CNCGB CNCG VALVES Cust. Doc. ID:
3 5/29/2020/TREJARVEJO 5/29/2020/FTAMJNS 5/29/2020/FTAMSRE
Pos.
SEQ-28.46
Doc. ID: P00592320
0 1 2 3 4 5 6 7
This document is the exclusive intellectual property of Metso Power AB/Metso Power Oy/Metso Paper USA, Inc./Metso Paper Sulamericana Ltda and is furnished for the sole purpose of operating and maintaining of the specific project,
A
and re-use of the document for any other project or purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of the company.
OK
252-PIC-846.S10 BMS2
CNCG pressure to CNCG burner B
INT-28.23 CNCG pressure to burner
CNCG B CNCG LANCE PRESS.
FAILURE
CONTROLLER IN AUTO MODE NC-CB3-X10017.S6
252-PIC-846B.S8 BMS2 & &
LP Steam to CNCG RB2 burner STATUS
SEQ-28.41 CNCGB CNCG start sequence & ALARM
BMS2 DO
1s 20 s
SET MONITORING ON PRESSURE FAILURE
ON
252-PIC-846B.S5 BMS2 S S .S6 BMS2 C
LP Steam to CNCG RB2 burner CNCG B CNCG BURNER FAILURE
SEQ-28.41 CNCGB CNCG start sequence R R SEQ-28.44 CNCGB CNCG burner failure
3s 2s
START-UP PROGRAM RUN
©Metso Power AB or ©Metso Power Oy or ©Metso Paper USA, Inc. or ©Metso Paper Sulamericana Ltda.
.S11
CNCG B CNCG START SEQUENCE
SEQ-28.41 CNCGB CNCG start sequence 1
CNCG B CNCG FAILURE
.S4 BMS2
CNCG B CNCG BURNER FAILURE
SEQ-28.44 CNCGB CNCG burner failure
D
FAILURE RESET
.S10 BMS2
CNCGB FAILURE RESET OPR
SEQ-28.70 CNCGB Common local controls
PRELIMINARY
Rev. Designed by Checked by Approved by Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA 8/31/2018/FTAMJNS 8/31/2018/FTAMSRE CNCGB CNCG LANCE PRESSURE Page:
Cust. Doc. ID:
3 5/29/2020/TREJARVEJO 5/29/2020/FTAMJNS 5/29/2020/FTAMSRE MONITORING
Pos.
SEQ-28.48
Doc. ID: P00592320
0 1 2 3 4 5 6 7
CNCG B IGNITER
START
ON
This document is the exclusive intellectual property of Metso Power AB/Metso Power Oy/Metso Paper USA, Inc./Metso Paper Sulamericana Ltda and is furnished for the sole purpose of operating and maintaining of the specific project,
IGNITER FLAME ON ON
252-BX-804.S1 BMS2
CNCG B igniter
252-43-150.XL07
INT-28.14 CNCGB igniter
START-UP PROGRAM RUN PILOT LAMP
S1
CNCG B MeOH Start Sequence
SEQ-30.11 CNCGB Start sequence MeOH
STOP RESET
ON
©Metso Power AB or ©Metso Power Oy or ©Metso Paper USA, Inc. or ©Metso Paper Sulamericana Ltda.
PUSH-BUTTON PUSH-BUTTON
NC 252-43-150.PB06 NO 252-43-150.PB04 1 FAILURE RESET
.S10 BMS2
CNCGB FAILURE RESET OPR
INT-28.12 CNCGB NG interlocks
SEQ-28.04 CNCGB NG stop sequence
CNCGB FAILURE SEQ-28.06 CNCGB NG burner failure
RESET OPR 5s SEQ-28.08 CNCGB Igniter cylinder
NC-CB3-H10026.S1
SEQ-28.12 CNCGB NG leakage test sequence
RESET DCS DO DI BMS2 SEQ-28.13 CNCGB NG leakage test
SEQ-28.15 CNCGB combustion air monitoring D
SEQ-28.16 CNCGB NG lance
SEQ-28.42 CNCGB CNCG stop sequence
CNCG B RODDER SEQ-28.44 CNCGB CNCG burner failure
START PUSHED SEQ-28.48 CNCGB CNCG lance pressure monitoring
ON
PRELIMINARY
Rev. Designed by Checked by Approved by Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA 8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Page:
CNCGB COMMON LOCAL CONTROLS Cust. Doc. ID:
3 5/29/2020/TREJARVEJO 5/29/2020/FTAMJNS 5/29/2020/FTAMSRE
Pos.
SEQ-28.70
Doc. ID: P00592320
0 1 2 3 4 5 6 7
This document is the exclusive intellectual property of Metso Power AB/Metso Power Oy/Metso Paper USA, Inc./Metso Paper Sulamericana Ltda and is furnished for the sole purpose of operating and maintaining of the specific project,
TIME SETTING
NC-CB3-H5018.I1
RESET T1 DCS AO AI BMS2
INTEGER
DCS DI
NC-CB3-H5018.S1
BMS2 DO
1s
PUSHED
252-LCP-150.PB17.S1 BMS2
CNCG B rodder start
SEQ-28.70 CNCGB Common local controls
1s
& C
1s
1 MAN
ON IN AUTO-MODE
1 AUTO
OPEN
PROT
1s REL IN COMMAND ON
CNCG RODDER OPEN
©Metso Power AB or ©Metso Power Oy or ©Metso Paper USA, Inc. or ©Metso Paper Sulamericana Ltda.
->A MOVEMENT
->M
CLOSE
ON
CLOSE
AUTO 252-HSV-828
SSO VALVES OPEN PROT
.S8 BMS2 5s REL
CNCG B CNCG valves common
INT-28.26 CNCGB CNCG burner status 10 s
MeOH ADDITION
CNCGB RUNNING MEOH ON
S1 BMS 1
3 CNCG B Flame Monit MeOH
INT-30.12 CNCGB Flame monitoring MeOH
D
1s
CNCG B RUNNING NG
.S1 BMS2
CNCG B FLAME MONITORING
INT-28.13 CNCGB NG flame monitoring
PRELIMINARY
Rev. Designed by Checked by Approved by Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA 8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Page:
CNCGB RODDER Cust. Doc. ID:
3 5/29/2020/TREJARVEJO 5/29/2020/FTAMJNS 5/29/2020/FTAMSRE
Pos.
SEQ-28.71
Doc. ID: P00592320
0 1 2 3 4 5 6 7
10 min
ON (60S)
.S2 BMS2 OFF
CNCG SUPPORT BURNING ON
INT-28.25 CNCGB support fuel status
This document is the exclusive intellectual property of Metso Power AB/Metso Power Oy/Metso Paper USA, Inc./Metso Paper Sulamericana Ltda and is furnished for the sole purpose of operating and maintaining of the specific project,
252-HSV-814.S12 BMS2
CNCG B natural gas valve 1
SEQ-28.11 CNCGB NG valves
RUNNING
.S11 BMS2 B
CNCG B NG START SEQUENCE
3 SEQ-28.03 CNCGB NG start sequence
CNCG B IGNITION ATTEMPTS
NC-CB3-X10029.I1
CLOSED & NO FAILURE IGNITION ATTEMPTS CNCG B SUPP. FUEL START REL
252-HSV-1820S2 BMS STATUS
CNCG B methanol valve 1 GONE ON
NC-CB3-X10029.S1 NC-CB3-X10029.S2
SEQ-30.16 CNCGB MeoH valves
1 STATUS STATUS
DCS AI
CLOSED & NO FAILURE
252-HSV-1821S2 BMS & INTEGER
CNCG B methanol valve 2 BMS2 AO DCS DI DCS DI
SEQ-30.16 CNCGB MeoH valves
2s
START-UP PROGRAM RUN BMS2 DO BMS2 DO
S1 COUNTER
MEOH ADDITION CNCG B MeOH Start Sequence MAX 2 C
ATTEMPTS &
SEQ-30.11 CNCGB Start sequence MeOH
10 s 2s
CNCGB SPRT BURN NG START
ON NOTE: LOCAL START WITHOUT NC-CB3-X10029.S4
RESET
IGNITION ATTEMPTS LIMITATION STATUS
©Metso Power AB or ©Metso Power Oy or ©Metso Paper USA, Inc. or ©Metso Paper Sulamericana Ltda.
DCS DI
BMS2 DO
NC-CB3-H10028.S1 NG START
CNCG B &
START DCS DO DI BMS2 .S4 BMS2
NG OPERATOR CNCG B SUPRT BURN OPR STRT
CONTROL NC-CB3-H10028.S2 OPERATOR STOP D
SEQ-28.03 CNCGB NG start sequence
STOP DCS DO DI BMS2 .S2 BMS2
CNCG B NG OPERATOR CONTROL
SEQ-28.04 CNCGB NG stop sequence
CNCGB SPRT BURN NG START
NC-CB3-X10029.S5
3
MEOH ADDITION STATUS
DCS DI
BMS2 DO
PRELIMINARY
Rev. Designed by Checked by Approved by Project: 110374 Planta Arauco CNCG Drawn 6/27/2018/ATVAKI2 Design TREVESSAPA Rev.
1 8/3/2018/FTAMSLAP 8/3/2018/FTAMJNS 8/3/2018/FTAMSRE Name: CNCG burner Chkcd FTAMJNS Appr. FTAMSRE 3
2 8/31/2018/TREVESSAPA 8/31/2018/FTAMJNS 8/31/2018/FTAMSRE Page:
CNCGB SUPPORT FUEL START RELEASE Cust. Doc. ID:
3 5/29/2020/TREJARVEJO 5/29/2020/FTAMJNS 5/29/2020/FTAMSRE
Pos.
SEQ-28.72
Doc. ID: P00592320
This document is the exclusive intellectual property of Metso Power AB/Metso Power Oy/Metso Paper USA, Inc./Metso Paper Sulamericana Ltda and is furnished for the sole purpose of operating and maintaining of the specific project,
and re-use of the document for any other project or purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of the company.
3
2
©Metso Power AB or ©Metso Power Oy or ©Metso Paper USA, Inc. or ©Metso Paper Sulamericana Ltda.
Rev.
0
Designed by
Checked by
1
Approved by
INT-28.27
3
LOGIC MOVED TO
Name:
Project:
Doc. ID:
4
INTERLOCKING DIAGRAMS
P00592320
CNCG burner
110374 Planta Arauco CNCG
5
FTAMJNS
8/3/2018/ATILJO
Appr.
Design
FTAMSRE
FTAMSLAP
7
Rev.
Page:
3
PRELIMINARY
SEQ-28.73
E
B
A
D
C