Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Air Circuit Breaker

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 8

Air Circuit Breaker (ACB) – Construction,

Operation, Types and Uses


Electrical Technology

Air Circuit Breaker Construction, Operation, Types, Advantages and


Applications
What is a Circuit Breaker?
A circuit breaker is a device, which can
 Make or break a circuit manually or by remote control under normal conditions.
 Break a circuit automatically under fault conditions (like over current, Short circuit,
etc.).
 Make a circuit manually or by remote control under the fault conditions.
A circuit breaker is used for switching mechanism and protection of the system. Other
associated devises and components are also used for this purpose associated with
circuit breakers like fuses, relays, switches etc. Circuit breakers are widely used in
industries as well as power system for controlling and protection of different parts of the
circuit like switch gears, Transformers, Motors, Generators/Alternator etc., which leads

the system stable and reliable.


There are different types of air circuit breakers available in the market and we will
discuss one by one in detail.
Air Circuit Breaker (ACB)
Air Circuit Breaker (ACB) is an electrical protection device used for short circuit and
overcurrent protection up to 15kV with amperes rating of 800A to 10kA. It operates in air
(where air-blast as an arc quenching medium) at atmospheric pressure to protect the
connected electric circuits. ACB has completely replaced by oil circuit breaker because
it is still a preferable choice to use an ACB because, there is no chance of oil fire like in
oil circuit breaker.

Construction of Air-Circuit Breaker


The following fig shows the main and external parts of an ACB. (ABB EMax Low
Voltage, Current Limiting and Selective (Non-Current Limiting) Air Circuit Breaker).

1. OFF button (O)


2. ON button (I)
3. Main contact position indicator
4. Energy storage mechanism status indicator
5. Reset Button
6. LED Indicators
7. Controller
8. “Connection”, “Test” and “isolated” position stopper (the three-position
latching/locking mechanism)
9. User-supplied padlock
10. Connection “,” Test “and” separation “of the position indication
11. Connection (CE) Separation, (CD) Test (CT) Position indication contacts
12. Rated Name Plate
13. Digital Displays
14. Mechanical energy storage handle
15. Shake (IN/OUT)
16. Rocker repository
17. Fault trip reset button
The following fig shows the Internal Construction of Air Circuit Breaker

     1.   Sheet Steel Supporting Structure


     2.   Current Transformer for Protection Trip Unit
     3.   Pole Group insulating box
     4.   Horizontal rare terminals
     5a. Plates for fixed main contacts
     5b. Plates for fixed arcing Contacts
     6a. Plates for Main moving contacts
     6b. Plates for Moving Arcing contacts
     7.   Arcing Chamber
     8.  Terminal box for fixed version – Sliding Contacts for withdrawable version
     9.   Protection Trip Unit
     10. Circuit breaker Closing and Opening Control
     11. Closing Springs

Principle of Operation of Air Circuit Breaker


The working principle of Air Circuit breaker is rather different from other types of circuit
breaker. The main aim of circuit breaker is to prevent reestablishment of arcing after
current zero where the contact gap will withstand the system recovery voltage. It does it
same work, but in a different manner. During interruption of arc, it creates an arc voltage
instead of supply voltage. Arc voltage is defined as the minimum voltage required for
maintaining arc. The circuit breaker increases the voltage in three different ways:
 Arc voltage can be increased by cooling arc plasma. As soon as the temperature of
arc plasma motion of particle in arc plasma is reduced, more voltage gradient will be
required to maintain the arc.
 By splitting the arc into a number of series will increases the arc voltage.
 Arc voltage can be increased by lengthening the arc path. As soon length of arc path
is increased the resistance path will increase more arc voltage is applied across the
arc path hence arc voltage is increased.
It is operated within voltage level up to 1 KV. It contains two pairs of contact. The main
pair carries the current and the contact made of copper. An additional pair of contact is
made of carbon. When the breaker is opened, the main contact opens first. During
opening of the main contact, the arc contact remains in touch with each other. The
arcing gets initiated when arc contacts are separated. The circuit breaker is obsolete for
medium voltage.      
Types of Air Circuit Breaker
There are four types of ACBs used in the control and protection to maintain and stable
operation of switch gears and indoor medium voltage.
 Plain Break Type Air Break Circuit Breaker or Cross-Blast ACB
 Magnetic Blowout Type Air Break Circuit Breaker
 Air Chute Air Break Circuit Breaker
 Air Blast Circuit Breaker

Plain air circuit breaker or Cross-Blast Air Circuit Breaker:


The circuit breaker is fitted with a chamber surrounding the contact. The chamber is
known as “arc chute”. The arc is made to drive in it. The arc chute will help in achieving
cooling. Arc chute is made from some refractory material. The inner walls of arc chute
are shaped in such a way that arc is not only forced into close proximity, but will drive
into the serpentine channel projected on arc chute wall.
The arc chute is divided into a number of small compartments by using metallic
separation plates. Metallic separation plates are arc splitters and each of small
compartments behave as a mini arc chute. Initial arc will split into a series of arcs this
will make all arc voltages higher than system voltage. They are preferable choice in low

voltage application.
Air Chute Air Break Circuit Breaker
In air chute air circuit breaker, there are two types of contacts namely “main contact”
and “auxiliary or arcing contacts”. The main contacts are made of copper and the silver
plates having low resistance and conducts the current in closed position. Auxiliary or
arcing contacts are made of copper alloy as they are heat resistance and used to
prevent from damaging the main contacts due to arcing and can be easily replaced
when needed in case of wear and tear. During the circuit breaker operation, the arcing
or auxiliary contacts are closed before and open after the main contacts of the circuit
breaker.

Magnetic Blowout Type Air Break Circuit Breaker


Magnetic blowout air circuit breakers provide magnetic control over the arc moment to
make arc extinction within the devices. The arc extinction is controlled using magnetic
field provided by the current in blowout coils connected in series with the circuit being
interrupted. These coils are known as “blow out the coil”. Magnetic field does not control
and extinguish the arc made in the breaker, but it moves the arc into chutes where the
arc is lengthened, cooled and extinguished accordingly. These kind of circuit breakers
are used up to 11kV.
Air Blast Circuit Breaker:
This type of circuit breaker is used for system voltage of 245 KV, 420 KV and even
more.
Air blast circuit breaker has further divided into three categories:
 Axial blast breaker
 Axial blast with sliding moving contact.

 Axial blast breaker


The moving contact is in contact. There is a nozzle orifice in fixed contact at normal
closed condition of breaker. When a fault occur high pressure is introduced into the
chamber. High-pressure air will flow through nozzle orifice voltage is sufficient to

sustain.
Axial blast with sliding moving contact
 The moving contact is fitted over a piston supported by a spring. The blast transfers arc

to arcing electrode.
Advantages & Disadvantages of Air Blast Circuit Breaker
Advantages
 Air blast circuit breaker is a suitable option to use where frequent operation is
required because of lesser arc energy
 The risk of fire is eliminated in the operation of Air blast circuit breaker.
 Air blast circuit breaker is small in size, because of the growth of dielectric strength is
so rapid (which final contact gap needed for arc extinction is very small).
 Speed of circuit breaker is much higher during operation of the air blast.
 Arc quenching is much faster
 The duration of the arc is same for all values of current.
 Stability of operation can be maintained and depends on speed operation of circuit
breakers.
 It requires less maintenance.

Disadvantages
 The air supplier plant requires additional maintenance.
 It contains high capacity air compressor.
 There is a chance of air pressure leakage from the air pipes junction.
 There is chance of a high rate rise of re-striking voltage and current chopping.
 The air has relatively lower arc extinguishing properties.
Application and Uses of Air Circuit Breaker

 It is used for protection of plants.


 It is used for common protection of electrical machines.
 It used for protection of transformers, capacitors and generators.
 ACB is also used in electricity sharing system and NGD about 15kV.
 Also used in Low as well as High voltage and Currents applications .

You might also like