Csavarkompresszoros - SM GB0003 - r0 - 01-07-Service Manual RCUE AG2
Csavarkompresszoros - SM GB0003 - r0 - 01-07-Service Manual RCUE AG2
Csavarkompresszoros - SM GB0003 - r0 - 01-07-Service Manual RCUE AG2
Service Manual
RCUE40AG2-400AG2
Cooling capacity 112 kW - 1030 kW
RHUE40AG2-240AG2
Cooling capacity 106 kW - 585 kW
Heating capacity 110 kW - 556 kW
Specifications in this manual are subject to change without notice in order that HITACHI
may bring the latest innovations to their customers.
Whilst every effort is made to ensure that all specifications are correct, printing errors are
beyond Hitachi’s control; Hitachi cannot be held responsible for these errors.
Contents
0. C o n t e n t s
pag. 3
SMGB0003 rev.0 - 01/2007
Contents
Content
1. Product range and specifications ............................................................................ 11
1.1. General data for RCUE40~400AG2 ..................................................................................................... 12
2. Test run....................................................................................................................19
2.1. Check before test run ........................................................................................................................... 20
4.12. Installation of switch for snow measure (Fan manual operation) ......................................................... 68
4.15. Saving energy priority mode, silence priority mode (night shift), only cooling ...................................... 70
pag. 5
SMGB0003 rev.0 - 10/2006
Contents
Content (Cont.)
5. Troubleshooting .......................................................................................................83
5.1. Initial check ........................................................................................................................................... 84
6. Maintenance ..........................................................................................................149
6.1. Maintenance criteria ........................................................................................................................... 150
pag. 6
SMGB0003 rev.0 - 10/2006
Contents
NOTE:
MODELS Please check, according to the model name, which is your air conditioner type and how it is abbreviated and referred
CODIFICATION to in this service manual.
RCUE80AG2 8E081072
RCUE60AG2
Series
Refrigeration Capacity
Refrigerant: 407C
Unit Europe
Cooling
Air condensed
pag. 7
SMGB0003 rev.0 - 10/2006
Contents
RHUE80AG2 9E081072
RHUE60AG2
Series
Refrigeration Capacity
Refrigerant: 407C
Unit Europe
Heat pump Air condensed
pag. 8
SMGB0003 rev.0 - 10/2006
Contents
HARC70-CE1 60559055
Lonwork BMX Interface
HARC70-CE1 OP 60559056
CSNET WEB
CSNET WEB 7E891924
pag. 9
SMGB0003 rev.0 - 10/2006
Contents
Communication Set
PM001-GW (Power Meter Option 7E891933 NEW
Accessory for CSNET WEB)
pag. 10
SMGB0003 rev.0 - 10/2006
Product range and
specifications
1. P r o d u c t r a n g e a n d s p e c i f i c a t i o n s
This chapter provides you with a fast review of the most important general data of the Air cooled water chillers and Air to
water heat pump chillers of HITACHI.
1
Content
1. Product range and specifications ............................................................................ 11
1.1. General data for RCUE40~400AG2 ..................................................................................................... 12
page 11
SMGB0003 rev.0-01/2007
Product range and
specifications
Quantity - 1 1 1 1
NOTE:
The nominal cooling capacities are based on the European Standard EN12055.
− Chilled Water Inlet / Outlet Temperature : 12/7 °C
− Condenser Inlet Air Temperature : 35 °C
page 12
SMGB0003 rev.0-01/2007
Product range and
specifications
Cooling Capacity
kW
206
69.6
260
85.4
312
104.5
356
119.6
1
COP - 2.96 3.04 2.99 2.98
Height mm 2.430 2.430 2.430 2.430
Outer Dimension Width mm 1.900 1.900 1.900 1.900
Depth mm 2.750 4.050 4.050 5.250
Cabinet colour - Natural Grey
Net weight Kg 1.820 2.830 3.000 3.420
Compressor type - Semi-Hermetic screw type
Quantity - 1 2 2 2
NOTE:
The nominal cooling capacities are based on the European Standard EN12055.
− Chilled Water Inlet / Outlet Temperature : 12/7 °C
− Condenser Inlet Air Temperature : 35 °C
page 13
SMGB0003 rev.0-01/2007
Product range and
specifications
Quantity - 2 3 3 3
NOTE:
The nominal cooling capacities are based on the European Standard EN12055.
− Chilled Water Inlet / Outlet Temperature : 12/7 °C
− Condenser Inlet Air Temperature : 35 °C
page 14
SMGB0003 rev.0-01/2007
Product range and
specifications
COP
Height mm
- 3.0
2.430
3.0
2.430
3.0
2.430
3.0
2.430
1
Outer Dimension Width mm 1.900 1.900 1.900 1.900
Depth mm 10.250 10.250 12.750 12.750
Cabinet colour - Natural Grey
Net weight Kg 6.750 7.000 8.450 8.750
Compressor type - Semi-Hermetic screw type
Quantity - 4 4 5 5
NOTE:
The nominal cooling capacities are based on the European Standard EN12055.
− Chilled Water Inlet / Outlet Temperature : 12/7 °C
− Condenser Inlet Air Temperature : 35 °C
page 15
SMGB0003 rev.0-01/2007
Product range and
specifications
NOTES:
(1) The nominal cooling capacities are based on the European Standard EN12055.
− Chilled Water Inlet / Outlet Temperature : 12/7 ºC
− Condenser Inlet Air Temperature : 35 ºC
(2) The nominal heating capacities are based on the European Standard EN12055.
− Heated Water Inlet / Outlet Temperature : 40/45 ºC
page 16
SMGB0003 rev.0-01/2007
Product range and
specifications
1
Heating Capacity kW 185 254 305 371
Total Power input in cooling kW 69.6 85.4 104.5 119.6
Total Power input in heating kW 67.7 89.0 108.6 135.5
Height mm 2.430 2.430 2.430 2.430
Outer Dimension Width mm 1.900 1.900 1.900 1.900
Depth mm 2.500 3.800 3.800 5.500
Cabinet colour - Natural Grey
Net weight Kg 1.950 3.050 3.250 3.670
Compressor type - Semi-Hermetic screw type
Models - 60ASC-Z 40ASC-Z 50ASC-Z 60ASC-Z
Quantity - 1 2 2 2
Oil heater W 150 150x2
- Continuous Capacity Control
Capacity control
% 15~100
Water side heat exchanger - Brazing plate type
Air side heat exchanger - Multi-Pass cross finned tube
Fan Motor (pole) kW 0.38 (8)
Quantity - 6 8 8 12
Refrigerant type - R407C (Factory charged)
Flow control - Electronic expansion valve
Number of independent circuits - 1 2 2 2
Quantity of refrigerant - 64 92 82 96
Oil type - JAPAN ENERGY FREOL UX300 (Ester)
3” Victaulic (1xInlet/
Water pipe connection Inch 3” Victaulic (2xInlet/2xOutlet)
1xOutlet)
Control system - Micro-processor control
Chilled water outlet temperature ºC -10 (Option) 5~15
Heated water outlet temperature ºC 35~55
Condenser air inlet temperature ºC -15~46 for cooling operation
Evaporator air inlet temperature ºC DB: -9.5~21/ WB:-10~15.5 for heating operation
Permissible water pressure max. MPa 1.0
Reverse Phase Protection, Fuse and Thermal Relay for Compressor,
Internal Thermostat for Compressor, Compressor Oil Heater,
Fuse and Internal Thermostat for Fan Motor, Control Circuit Fuse,
Safety and protection devices - High Pressure Switch, Low Pressure Control,
High Pressure Relief Valve, Discharge Gas Temperature Control,
Suction Gas Temperature Control, Freeze Protection Control
and Compressor Operation Hour Meter
Power suply - 3~, N/380-415V/50Hz
NOTES:
(1) The nominal cooling capacities are based on the European Standard EN12055.
− Chilled Water Inlet / Outlet Temperature : 12/7 ºC
− Condenser Inlet Air Temperature : 35 ºC
(2) The nominal heating capacities are based on the European Standard EN12055.
− Heated Water Inlet / Outlet Temperature : 40/45 ºC
− Evaporator Inlet Air Temperature : 6 ºC (WB)
page 17
SMGB0003 rev.0-01/2007
Product range and
specifications
NOTES:
(1) The nominal cooling capacities are based on the European Standard EN12055.
− Chilled Water Inlet / Outlet Temperature : 12/7 ºC
− Condenser Inlet Air Temperature : 35 ºC
(2) The nominal heating capacities are based on the European Standard EN12055.
− Heated Water Inlet / Outlet Temperature : 40/45 ºC
− Evaporator Inlet Air Temperature : 6 ºC (WB)
page 18
SMGB0003 rev.0-01/2007
Test run
2. Te s t r u n
This chapter describes the procedure of test run of the Air cooled water chillers and the Air to water heat pump chillers.
Content
2.
2.1.
Test run....................................................................................................................19
Check before test run ........................................................................................................................... 20
2
2.1.1. Cabinet ......................................................................................................................................................... 20
2.1.2. Refrigerant System ...................................................................................................................................... 20
2.1.3. Electrical System.......................................................................................................................................... 21
2.1.4. Water System ............................................................................................................................................... 22
pag. 19
SMGB0003 rev.0-01/2007
Test run
Confirm there is no problem regarding chiller installation space and requirements. See
technical catalogue for more details.
Check the following items at the beginning of the season and before first test run.
2.1.1. Cabinet
Air side heat − Check visually if there is no dust between fins. In case of
exchanger dust, wash the part with fin cleaner.
CAUTION:
Do not use domestic 2.1.2. Refrigerant System
detergent as a
forming agent at System in − Confirm individually if screws are fixed well using
refrigerant leakage general screwdriver or wrench.
check. The followings
are recommended: − Confirm if there is no gas leakage using foaming agent or
− Snove (Nupro, leak tester especially in flanges, screws, and flare parts.
USA),
pag. 20
SMGB0003 rev.0-01/2007
Test run
2
carefully since devices might be damaged if screws in wire
connection part are not tightened well.
− Confirm if the insulation resistance is more than 1MΩ in
500 V DC 500V DC. In case of below 1MΩ, do not operate the unit
since insulation of electrical device has failure.
Fig.1 Compressor − Check if insulation works well. Do not operate the unit in
case of below 3MΩ in 500V DC (fig.1)
Fan motor − Check if insulation works well. Do not operate the unit in
case of below 3MΩ in 500V DC. (fig.1)
100 ºC
over Wire in the − Confirm touching directly with hands if the wiring is not
unit removed or loosed.
− Confirm the covered insulation part. Pay attention not to
Fig.2
touch it by wet hand or to touch directly the edge of metal
plate or high temperature part of electrical devices. (fig.2)
Local wiring − Confirm if earth wire is installed correctly and not broken.
− Confirm if R, S, and T phase are connected correctly.
− Confirm the local wiring size. If the volume is not sufficient,
it may cause extreme heating or fire.
pag. 21
SMGB0003 rev.0-01/2007
Test run
open
− Open the inlet/outlet valve of water and pass the
close
direction
liquid type water inside the water heat exchanger and pipes.
direction
− While operating the water pump, remove the air
water inside the water pipe from the plug or automatic air-
state of removing valve.
opening
− Continue operating the pump and confirm if there
Fig.3 is no water leakage, strange noise nor abnormal
vibration.
− Remove the air from the pump and pass the water inside
all the system.
− Check if water is not leaked in all the system.
− Confirm if the valve is open.
− Confirm if strainer (correspondent to 20 mesh) prepared
in local is installed in water inlet pipe near the unit. When
checking at the beginning of the season, check also if there
is any dust or foreign materials in strainer.
1. Need to apply electricity to oil heater. Power ON 12 hours before the first
start up.
2. Screw compressor start-up. Confirm if there is no strange noise or abnormal
vibration in 1~2 minutes after compressor operation.
3. Confirmation of standard operating pressures. Stop the operation once and
re-start the unit after more than 3 minutes. Confirm if pressure is correct after
15 minutes of compressor operation referring for “Fig.6 Standard operation
pressure” and “Fig.6 Water side heat exchanger washing area”.
4. Positive revolution of fan. Confirm if fan is spinning in counter clockwise
rotation observing the fan from the above.
5. Check of gas leakage.Confirm if gas is not leaked after stopping the
operation.
pag. 22
SMGB0003 rev.0-01/2007
Test run
Heating operation:
Fig.5
Saturated
curve
Fig.6 Saturated
curve
Area need to clean
Chilled water outlet temperature (ºC) Warm water outlet temperature (ºC)
(Cooling operation) (Heating operation)
CAUTION:
For installation and
test run under low
ambient temperature,
like at the beginning NOTE:
of summer, it is Fig.6 area need to be cleaned water side heat exchanger
possible to decrease
low pressure
abnormally.
In such case, heating
operation should be
run firstly and then
cooling operation.
(In case of air-cooled
heat pump)
pag. 23
SMGB0003 rev.0-01/2007
Test run
Fig.7
Fig.8
pag. 24
SMGB0003 rev.0-01/2007
Test run
After a series of items are confirmed from the beginning to the end of test run, restart the unit and check also the
following items.
− Momentary voltage at
compressor start-up is over
rated voltage ±15%
2
− Operation voltage is within Unbalance of voltage
Voltage makes current value
rated voltage: ±10% change significantly.
− Unbalance between voltage:
within 2%, in any case, within
3%.
If it needs to adjust
it with water volume,
Is there no trouble in discharge water adjust it in the
pressure nor in operation noise? discharge side of
Water system: pump.
Pump
− Re-check if there is no
Is there any clogging in strainer? dust nor foreign matters in
strainer.
pag. 25
SMGB0003 rev.0-01/2007
Test run
NOTE:
See “HIgh pressure
confirmation” in
chapter 4 “Control
functions” for the
details.
Fig.9
CAUTION:
It is recommended that
this confirmation test
3. After confirmation, alarm should be released by unit stop operation. When alarm
be performed at load-
up state, operation for is released, high pressure cut confirmation test is also released.
a few minutes after
start-up.
pag. 26
SMGB0003 rev.0-01/2007
Test run
2
2. If chiller unit is not used for a long time, drain the water out of pipes using water-drawing or air-drawing
plug.
3. Anti-freeze in winter
− To avoid freezing, which might damage devices or pipes, it is needed to be installed some insulation in pump
and water pipes.
− This chiller has a function to operate chilled (warm) water circulation pump automatically in case of
decreasing outside temperature during unit stop, therefore, do not turn off the power source during season.
In case of turning off, draw the water out of chiller unit.
4. In case of fire,
Turn all power OFF
5. The unit will not display failure in spite of the following cases.
− During operation and after unit stop, if there is water flowing noise. However, this is a refrigerant flowing
noise, and it is not a failure.
− Compressor is not operated (fuses are out) although operation switch is ON while temperature controller is
being activated. This is not a failure, but operation is started when temperature control (Thermostat) turns
ON.
− In screw type chiller unit, there is a noise in the compressor rotors when it is stopped. Refrigerant is flowed
back temporally, and this is not a failure.
6. The refrigerant used in this unit is incombustible, non-toxic and odourless safe. However, toxic gas is
produced when leaked refrigerant is exposed to fire and oxygen will be lacked due to that refrigerants
gravity is higher than air. Therefore, in case that refrigerant is leaked or eye or throat are irritated, stop the
use of fire, and ventilate well, then contact a distributor.
7. About operation method
Standard method of use is described in the operation manual attached with the product. Operation
method would be changed if special modification were realized by request of the customers. Give a
clear explanation to the customers that it is necessary to contact a distributor or Customer Service
Centre of manufactures in case that operation, not described in the manual, must be performed.
8. For customers’ continued safety
For customers’ safety, give plain and sufficient explanation and instruction to them about the contents
of “Please observe safety precautions fully” described in Installation Manual and “For safety use”
described the Operation Manual, and tell them to read them very carefully.
Cautions are divided into “Alarm” and “Caution”:
“Alarm” includes cases where it is possible to lead to a dangerous result like death or severe injury.
Cases described in “Caution” may also lead a grave result depending on the situations. Therefore,
please read them carefully and follow the instruction.
Operation Manual should be kept where any user can reach.
pag. 27
SMGB0003 rev.0-01/2007
Test run
Fig.14
pag. 28
SMGB0003 rev.0-01/2007
Test run
WARNING − Turn OFF all powers when checking electrical parts, otherwise, it may result in
electrical shock.
− Do not touch protection device. It may result in failure, electrical shock, fire
Fig.12
and explosion if these devices are touched, the setting value can be changed
or short-circuited.
− In case of troubles (smell something burning etc), stop the operation and
2
turn OFF main power immediately. Operation with abnormal state may cause
failure, electrical shock and fire. Contact a distributor of Customer Service
Centre of manufacturer in such case (fig.12)
− Consult to a distributor of Customer Service Centre of manufacturer in case of
repair and relocation. Inadequate installation may cause electrical shock
2.5.4. Other cautions
pag. 29
SMGB0003 rev.0-01/2007
Electrical Wiring
Diagrams
This chapter shows the electrical wiring diagrams for Chiller AG2 of Hitachi.
Content
3 Electrical Wiring Diagram ........................................................................................31
3.1. Power Wiring Diagram.......................................................................................................................... 32
3.1.1. Model: R(C/H)UE 40~80AG2 ....................................................................................................................... 32
3.1.2. Model: R(C/H)UE 100~160AG2 ................................................................................................................... 33
3
3.1.3. Model: R(C/H)UE 180~240AG2 ................................................................................................................... 34
3.1.4. Model: R(C/H)UE 280~320AG2 ................................................................................................................... 35
3.1.5. Model: R(C/H)UE 350~400AG2 ................................................................................................................... 36
pag. 31
SMGB0003 rev.0 - 01/2007
Electrical Wiring
Diagrams
Drawing Code:
XEKS1037_r1 NOTE:
All the field wiring equipment must comply with local codes.
For more information about DWS configuration, please refer to chapter 4 of this catalogue.
See the diagram abbreviations description at the end of this chapter.
pag. 32
SMGB0003 rev.0 - 01/2007
Electrical Wiring
Diagrams
Drawing Code:
XEKS1038_r1 NOTE:
All the field wiring equipment must comply with local codes.
For more information about DWS configuration, please refer to chapter 4 of this catalogue.
See the diagram abbreviations description at the end of this chapter.
pag. 33
SMGB0003 rev.0 - 01/2007
Electrical Wiring
Diagrams
Drawing Code:
XEKS1036_r1 NOTE:
All the field wiring equipment must comply with local codes.
For more information about DWS configuration, please refer to chapter 4 of this catalogue.
See the diagram abbreviations description at the end of this chapter.
pag. 34
SMGB0003 rev.0 - 01/2007
Electrical Wiring
Diagrams
Drawing Code:
XEKS1040_r1 NOTE:
All the field wiring equipment must comply with local codes.
For more information about DWS configuration, please refer to chapter 4 of this catalogue.
See the diagram abbreviations description at the end of this chapter.
pag. 35
SMGB0003 rev.0 - 01/2007
Electrical Wiring
Diagrams
Drawing Code:
XEKS1041_r1 NOTE:
All the field wiring equipment must comply with local codes.
For more information about DWS configuration, please refer to chapter 4 of this catalogue.
See the diagram abbreviations description at the end of this chapter.
pag. 36
SMGB0003 rev.0 - 01/2007
Electrical Wiring
Diagrams
Drawing Code:
XEKS1042_r0 NOTE:
All the field wiring equipment must comply with local codes.
For more information about DWS configuration, please refer to chapter 4 of this catalogue.
See the diagram abbreviations description at the end of this chapter.
pag. 37
SMGB0003 rev.0 - 01/2007
Electrical Wiring
Diagrams
Drawing Code:
XEKS1043_r1 NOTE:
All the field wiring equipment must comply with local codes.
For more information about DWS configuration, please refer to chapter 4 of this catalogue.
See the diagram abbreviations description at the end of this chapter.
pag. 38
SMGB0003 rev.0 - 01/2007
Electrical Wiring
Diagrams
Drawing Code:
XEKS1045_r1 NOTE:
All the field wiring equipment must comply with local codes.
For more information about DWS configuration, please refer to chapter 4 of this catalogue.
See the diagram abbreviations description at the end of this chapter.
pag. 39
SMGB0003 rev.0 - 01/2007
Electrical Wiring
Diagrams
Drawing Code:
XEKS1044_r1 NOTE:
All the field wiring equipment must comply with local codes.
For more information about DWS configuration, please refer to chapter 4 of this catalogue.
See the diagram abbreviations description at the end of this chapter.
pag. 40
SMGB0003 rev.0 - 01/2007
Electrical Wiring
Diagrams
Drawing Code:
XEKS1046_r1 NOTE:
All the field wiring equipment must comply with local codes.
For more information about DWS configuration, please refer to chapter 4 of this catalogue.
See the diagram abbreviations description at the end of this chapter.
pag. 41
SMGB0003 rev.0 - 01/2007
Electrical Wiring
Diagrams
Drawing Code:
XEKS1047_r1 NOTE:
All the field wiring equipment must comply with local codes.
For more information about DWS configuration, please refer to chapter 4 of this catalogue.
See the diagram abbreviations description at the end of this chapter.
pag. 42
SMGB0003 rev.0 - 01/2007
Electrical Wiring
Diagrams
Drawing Code:
XEKS1048_r1 NOTE:
All the field wiring equipment must comply with local codes.
For more information about DWS configuration, please refer to chapter 4 of this catalogue.
See the diagram abbreviations description at the end of this chapter.
pag. 43
SMGB0003 rev.0 - 01/2007
Electrical Wiring
Diagrams
Drawing Code:
XEKS1046_r1 NOTE:
All the field wiring equipment must comply with local codes.
For more information about DWS configuration, please refer to chapter 4 of this catalogue.
See the diagram abbreviations description at the end of this chapter.
pag. 44
SMGB0003 rev.0 - 01/2007
Electrical Wiring
Diagrams
Drawing Code:
XEKS1050_r1 NOTE:
All the field wiring equipment must comply with local codes.
For more information about DWS configuration, please refer to chapter 4 of this catalogue.
See the diagram abbreviations description at the end of this chapter.
pag. 45
SMGB0003 rev.0 - 01/2007
Electrical Wiring
Diagrams
Drawing Code:
XEKS1051_r1 NOTE:
All the field wiring equipment must comply with local codes.
For more information about DWS configuration, please refer to chapter 4 of this catalogue.
See the diagram abbreviations description at the end of this chapter.
pag. 46
SMGB0003 rev.0 - 01/2007
Electrical Wiring
Diagrams
Drawing Code:
XEKS1037_r1 NOTE:
All the field wiring equipment must comply with local codes.
For more information about DWS configuration, please refer to chapter 4 of this catalogue.
See the diagram abbreviations description at the end of this chapter.
pag. 47
SMGB0003 rev.0 - 01/2007
Electrical Wiring
Diagrams
pag. 48
SMGB0003 rev.0 - 01/2007
Control system
4.C o n t r o l s y s t e m
Content
4. Control system ........................................................................................................49
4.1. List of Main Control Function ................................................................................................................ 50
4
4.3.2. Rotation control ........................................................................................................................................... 53
4.12. Installation of switch for snow measure (Fan manual operation) ......................................................... 68
4.15. Saving energy priority mode, silence priority mode (night shift), only cooling ...................................... 70
pag. 49
SMGB0003 rev.0-01/2007
Control System
pag. 50
SMGB0003 rev.0-01/2007
Control system
Item Contents
− Full load operation is performed by external order (no-
voltage contact input).
Ice/Heat storage operation by external order − Chiller unit stops when the water temperature reaches
the setting value (no capacity control).
− Dip Switch setting is necessary.
− It is possible to operate only fans by an external order
as a countermeasure against snow while units are
Fan forced operation function stopped.
− Run or Stop operation is performed by a no-voltage
contact .
− While the actuation of high pressure interrupt device is
High pressure cut confirmation test (only cooling) confirmed, unit is operated with fan forcedly stopped.
4
− Push button is set on PCB for every cycle number.
− Operation order to pump is output automatically by
Pump automatic operation function in winter chiller in order to avoid freezing due to the decrease of
chilled water temperature during unit stop in winter.
− It is to keep high pressure at low values when ambient
temperature below 30 ºC.
“Saving energy” priority mode <option> (only cooling) − Since fan speed is increased, it is a saving energy
operation more than a silence operation.
− It is an optional setting by Dip Switch.
− It is focused on a silent operation of the unit reducing
the fan speed.
− Since the revolution number is reduced during night
or mid-term period, efficiency is changed hardly in all
“Silence priority” mode <option> (only cooling) around the year.
− Silence is given priority over saving energy.
− It is an optional setting by Dip Switch. It is possible to
switch from the remote controller by the external signal
(no-voltage contact ).
− When fan full speed operation is not needed, fan
revolution number is reduced, and low noise operation
is performed.
Night shift mode <option> (only cooling)
− Ambient temperature target: function is valid under 30
°C (noise value 1-~-2dB) (changeover by no-voltage a
contact input)
− There are two methods to judge Thermo OFF, possible
to select.
1. Immediate Thermo OFF by Thermo OFF
temperature
Thermo OFF selection function
2. No immediate Thermo OFF if Thermo OFF
temperature continues for 3 minutes. (however, if
outlet water temperature is out of the range, it will
be immediate Thermo OFF)
pag. 51
SMGB0003 rev.0-01/2007
Control System
− Outlet water temperature of Chiller Unit is detected by Thermistor, and based on this value, compressor ON/
OFF and the most suitable capacity is determined.
− Possible range of water temperature setting (°C):
Cooling –10(option)~15, Heating: 35~55 (outlet water temperature control)
− Capacity control : 100~15%, stop
− The minimum range of temperature adjustment (°C): 0,5
− Restarting of unit after thermo-OFF is done depending on inlet water temperature.
In case of standard setting: outlet setting temp 7°C, neutral zone (∆T3) 2°C (change of outlet water temp 7~9°C).
Range of stop temp (∆T1) 1°C (stop temp 6°C), range of restart temp 2°C.
1. Load-up I control at over 10°C (The capacity is changed a lot in order to approximate the target temp.
quickly)
2. Load-up II control at 9~10 °C (The capacity is changed moderately)
3. In neutral zone (9~7°C), load is balanced and performance is not changed.
4. Under neutral zone (below 7°C) load-down control is performed and performance is decreased.
5. Stop temp: Compressor is stopped at 6 °C. The inlet temp of that time is saved.
6. When inlet temp becomes 2°C higher than that of at stop, re-start signal is output and unit is re-started after
at least 3 min guard.
7. Control mode after re-start is the same as listed before.
pag. 52
SMGB0003 rev.0-01/2007
Control system
4
−
heating load is small (at minimum 3 minutes of stop time to avoid more than
6 ON/OFF in one hour)
− Sequential starting control which reduces the starting current of the unit.
(Cycles start sequentially with a 1 minute delay between each one. Finally all
work together for 30 seconds before capacity control starts.).
No. 1 ON
Compressor
OFF
No. 2 ON
Compressor
OFF
Stop the Operate the
compressor compressor
whose Operate first
operation
time is
longest
pag. 53
SMGB0003 rev.0-01/2007
Control System
Unit has a function to perform automatically forced unload when the power consumption
is over a certain set point.
4.4.1. Actuation of current limiter
When unit current detected by CT reaches to the setting value, forced unload
operation is performed for some minutes to reduce the power capacity load. (See
the figure below)
Load is down until actual current value is 95% of setting value, and then load
down signal is output for 12 seconds to keep the load.
Current value and forced unload operation time are set on PCBa (current limit
setting).
Actuation
Unit current
Current value
Set value
T min/hour (standard: 30 m)
Time
Forced unload
Segment indication
Cooling : [←→]
Heating : [←→]
[
40A 40 HP
1 X 50 HP
, X
RSW6 RSW5 60 HP
50A 70 HP
Adjust the calculated 80 HP
setting value
1 6 1 2
, X 50 = 80 A
, X 40 = 48 A
RSW6 RSW5 RSW6 RSW5
pag. 54
SMGB0003 rev.0-01/2007
Control system
Reverse phase
3 phase input status
Alarm
detection
UNIT STATUS
OFF
4
Open phase T phase:
open phase
R phase:
open phase Alarm
S phase:
open phase
Reverse phase
UNIT STATUS
ON
R phase:
UNIT GOES OFF
open phase
S phase:
open phase
pag. 55
SMGB0003 rev.0-01/2007
Control System
Restart control after power failure: 4.6. Restart control after power failure
3 min 3 min
NOTE:
In case that power failure occurs
during unit stop, the units shall
be stopped when power supply
returns.
pag. 56
SMGB0003 rev.0-01/2007
rev.0-11/2006
Control system
1. Operation error
− While the unit is stopped, there is a input (including external Thermo signal) from
the remote controller in spite of local operation mode.
− However, alarm is not indicated if there is a local input (operation switch of unit
body) while the unit is stopped in remote operation mode.
2. Local /Remote operation error
− To switch local remote or remote local while the unit is running, unit is
stopped and alarm is output. [40-40]
3. Cooling/Heating operation error
− To operate heating during cooling or to operation in cooling during heating, unit is
stopped and alarm is output. [40-40]
This control is individual In case that it is required to stop a compressor temporally, the order can be
for each compressor. given forcedly through the customer wiring terminals. After receiving this signal,
compressor shall be Thermo OFF forcedly. When this order is released, normal
operation is performed.
Unit
Running operation
External
signal
pag. 57
SMGB0003 rev.0-01/2007
Control System
Xa ON ON OFF OFF
Xb ON OFF ON OFF
According to the day run / night run or classification of load application, temperature
setting can be changed remotely.
Thanks to the two setting temperatures and the two control procedures for water
temperature (capacity control and full load or energy storage) these can be combined to
have the following possibilities.
1) Air-conditioning (capacity control ) + Air-conditioning (capacity control)
2) Air-conditioning (capacity control) + Heat storage operation (100-0%)
3) Heat storage operation (100-0%) + Heat storage operation (100-0%)
Air-conditioning temperature is set by rotary switch on operation PCB and heat storage
temperature is set by using “▲or▼” switch on indication PCB (7 segment).
Switch: Air-
Water temp Dip Switch Setting water
Operation mode conditioning/ Operation signal
control setting temp
heat storage
Air-conditioning Capacity control - Air-conditioning Rotary Switch Local / remote
1)
Air-conditioning Capacity control - heat storage Segment Local / remote
Air-conditioning Capacity control External Thermo Air-conditioning Rotary Switch Local / remote
2)
Heat storage 100-0% External Thermo heat storage Segment External Thermo
Heat storage 100-0% External Thermo Air-conditioning Rotary Switch External Thermo
3)
Heat storage 100-0% External Thermo heat storage Segment External Thermo
pag. 58
SMGB0003 rev.0-01/2007
Control system
4
c) Setting of air-conditioning temperature 2
Set chilled water outlet temperature as 10°C using “▲or▼” switch on indication PCB. (see item
(4) for the setting method)
Switch for
setting temp.
220-240V
Running operation:
− Run/Stop signal: Local or remote (cooling), external Thermo (heat storage)
− Water temperature is set by air-conditioning / heat storage switch. Air-conditioning / heat storage = Air-
conditioning setting water temperature / heat storage setting water temperature.
pag. 59
SMGB0003 rev.0-01/2007
Control System
− In case that operation signal is input in local at heat storage operation, capacity control operation is
performed.
a) Dip Switch Setting
In option A, 3 and 4 are ON.
External
thermo
NOTE:
contactor
AC: Air-conditioning
HS: Heat Storage
pag. 60
SMGB0003 rev.0-01/2007
Control system
pag. 61
SMGB0003 rev.0-01/2007
Control System
External
Thermo
Contactor
pag. 62
SMGB0003 rev.0-01/2007
Control system
pag. 63
SMGB0003 rev.0-01/2007
Control System
(normal)
Applied power
(heat storage) source AV200V
under 1A
(normal)
(*) In case of only heat storage operation, wiring of ( ) part is not necessary
pag. 64
SMGB0003 rev.0-01/2007
Control system
ATTENTION:
− Dip Switch for this control should be set before power ON.
− Local external Thermo does not run/stop by pulse signal order.
− Normal operation order and heat storage operation order shall be input to Chiller unit separately.
− Local external Thermo order shall have at minimum 5 minutes interval of continuous operation order (5 min in
case of stop).
− Additional wiring shall be put into a metal pipe independently, or shield line shall be used.
− During control by external Thermo, Chiller unit stops when water temperature reaches to the setting value of
Chiller unit, and automatically starts again. Therefore, set the temperature in external Thermo higher than that
of chiller unit.
− If Thermo setting value of body side is set “higher” at cooling and “lower” at heating, unit is stopped earlier than
the stop order from external Thermo.
− Switch normal / heat storage operation during unit stop.
4
4.11. Operation by DC24V input (Remote Control)
1. Outline
Operation control by DC24V is explained here.
− Operation signal pattern: 1. Level input, 2. 1 pulse input, 3. 2 pulse input.
− Set as follows and perform additional wiring in each 3 cases.
− This control is not compatible with other remote Run/Stop order.
2. Level input
a) Signal and basic sequence
Arrangement
in local
Terminal
Run/Stop switch
(prepared in local)
Switch
pag. 65
SMGB0003 rev.0-01/2007
Control System
b) Setting method
Dip Switch for optional function setting on PCBB is set as follows before power ON.
ON
ATTENTION:
− Additional wiring should not be connected to other operation circuit, especially wiring for 220-240V.
− Additional wiring shall be put into a metal pipe independently or shield line shall be used.
Arrangement
in local
Terminal
Run/Stop switch
(prepared in local)
Alarm output
(DC24V, under 0.8A) Switch
b) Setting method
Dip Switch for optional function setting on PCBB is set as follows before power ON.
ATTENTION:
− Additional wiring should not be connected to other operation circuit, especially wiring for 220-240V.
− Additional wiring shall be put into a metal pipe independently or shield line shall be used.
pag. 66
SMGB0003 rev.0-01/2007
Control system
Remove it
More than 200 m
4
Construction in local, parts prepared in local
b) Setting method
It is an application of remote control and it is unnecessary to modify the setting of PCB.
ATTENTION:
− Additional wiring should not be connected to other operation circuit, especially wiring for 220-240V.
− Additional wiring shall be put into a metal pipe independently or shield line shall be used.
pag. 67
SMGB0003 rev.0-01/2007
Control System
Installation of switch for snow If a switch for snow measure is installed, it is connected to terminal #31 and #32 in
measureHeat storage operation customer wiring terminals. When the switch is ON, fan is operated during unit stop or
by external order: Thermo OFF.
However, the fan is not operated in the following cases:
− When local is set
− During alarm occurrence
− When the switch has been ON before power ON (including power failure)
− Fan manual operation is stopped by the stop switch of unit body
Customer
Terminal
Switch
(prepared
in local)
ATTENTION:
− It is possible to insert a automatic contactor like a snow relay in this switch part.
− This switch can be used only at remote control. Pay attention to it at Unit check.
− Once the fan is started-up by this switch, fan continues running at least for
10 minutes if it is not stopped by the switch during this period. (In case of
emergency, stop the fan by the stop switch of unit)
− This switch is locally purchased.
pag. 68
SMGB0003 rev.0-01/2007
Control system
Operation method
4
makes high pressure cut device activated.
Perform unit stop operation to release
alarm stop and fan forced stop.
Cycle 1
Cycle 2
Cycle 3
PCBa2
PCBa2 SW9 SW10
Cycle 4
Cycle 5
It happens sometimes that chilled water temperature is decreased so much that heat
exchanger of water side or piping system are frozen during operation stop in winter.
This control prevents Chiller unit from freezing by operating chilled and warm water
circulation pump automatically after detecting ambient and chilled water temperature.
1. Ambient temperature is below 2°C
When ambient temperature is below 2°C, operation order is sent to pump and
continuos operation of chilled water circulation pump is started automatically.
When chilled water is over 15°C, intermittent operation (5 min of operation and
55 min of stop) is performed.
pag. 69
SMGB0003 rev.0-01/2007
Control System
Pump continuous
operation
Pump intermittent
operation (operation:
5min, stop: 55 min)
Pump stop
Change course
of chilled water
temperature
ATTENTION:
In case that ambient temperature of chilled/warm water circulation system is lower than that of
the Unit installation place, Thermostat for ambient temperature shall be introduced in the place
with the lowest temperature and shall be connected to pump operation order circuit in parallel.
4.15. Saving energy priority mode, silence priority mode (night shift),
only cooling
Saving energy priority
mode, silence priority
mode (night shift), only It is possible to select 3 types of fan control depending on the installation place or use
cooling.
applications PCBb
1. Standard mode
− Fan control (revolution number control)
suitable to ambient temperature.
− Good balance from the view of saving
energy and silence.
pag. 70
SMGB0003 rev.0-01/2007
Control system
Silence priority mode is valid by a no-voltage contactor input in Dip Switch setting of Standard mode or Saving
energy priority mode, therefore, such changeover as saving energy mode in daytime and silence priority mode at
night can be performed from remote controller.
Silence priority
ON/OFF
4
Silence priority mode (night shift) Saving energy priority mode
Standard mode
NOTE:
The above figure is an image, and the real effect differs from temperature condition.
pag. 71
SMGB0003 rev.0-01/2007
Control System
Manual defrost SW ON
Manual
AND
Not during defrost operation
− Defrosting is performed for 6 minutes at longest. (automatic stop when all frost is
taken out).
− In case that all frost is taken out very quickly, the period till next frost is extended
automatically in order to avoid too much defrost.
− Warm water outlet temperature is lower than inlet temperature due to the reverse
cycle defrost.
pag. 72
SMGB0003 rev.0-01/2007
Control system
Confirmation of defrost
conditions
10 sec count
Yes
Yes
Yes High pressure ≥2.4MPa ?
Water side HE inlet
refrigerant temp ≤10ºC ?
if during fan operation, No
Yes
fan 0Hz order
6 min from defrost? start?
Fan operation control?
Yes No
Yes
pag. 73
SMGB0003 rev.0-01/2007
Control System
Yes
Is fan running?
No
Yes
High pressure ≥2.6MPa ?
No
No
10min since 6Hz order
output?
Yes
Yes
High pressure ≤1.5MPa ?
No
No
10min since running with
Max frequency?
Yes
Changeover of 4 way
valve
30 sec count
(Staring unload continued)
pag. 74
SMGB0003 rev.0-01/2007
Control system
PCBC
1. Standard setting
Standard setting
4
Immediate stop when reaching to Themo OFF temp
Setting to continue
Thermo OFF
temperature
NOTE:
However, it becomes Thermo OFF immediately once outlet water temperature is decreased
until protection values
pag. 75
SMGB0003 rev.0-01/2007
Control System
1. Cooling operation
In this series, fan speed is controlled by inverters and adjusts depending on discharge pressure. Target high
pressure is set based on the ambient temperature, and revolution number is increased / decreased by PID
control. The unit number is not changed.
Standard mode
Fan frequency
Start-up at 10 Hz
pag. 76
SMGB0003 rev.0-01/2007
Control system
2. Heating operation
Basically unit is operated with Max frequency, but under the following conditions revolution number control is
4
performed.
Fan speed control is activated if “suction pressure ≥ 0.6 MPa” and “ambient temperature ≥ 25ºC”
*Released at ambient temperature ≤ 20 °C
pag. 77
SMGB0003 rev.0-01/2007
Control System
Case 1 SUS305
Slider 1 SUS304
pag. 78
SMGB0003 rev.0-01/2007
Control system
In this series, electronic expansion valve is used. Electronic expansion valve is consisted in the body (figure), Coil,
and PCB for expansion valve running (PCBG (VD PCB)).
4
(less than 0 pulse) and both control pulse number recognized in micro computer and real pulse number are
adjusted to zero. During this adjustment, “Cn-Eo” is indicated in the segment. (n= Unit No.)
Zero point adjustment is also performed “ at the first compressor stop after 24 hours since the last zero point
adjustment”., to modify the error between control pulse number and real pulse number. If compressore has
not stopped for over 200 hours, compressor is to be stopped forcedly (forced Thermo OFF) and zero point
is adjusted. Then, unit is re-started after 3 minutes guards. It is possible to cancel this forced zero point
adjustment by Dip Switch selection on expansión valve PCB.
pag. 79
SMGB0003 rev.0-01/2007
Control System
a) Normal Control
Compressor
Operation start Thermo OFF or stop
During super
heat control
Power on
Time
Standby at 10 pulse Standby at 10 pulse
Re-start in 3min
Opening of expansion valve
Superheat control
Thermo OFF
Thermo ON
Time
Zero point adjustment during Thermo OFF Forced zero point adjustment
If 24 h has passed since the last adjustment
Re-activation of Td control
Release if Td is below 70°C
Time
Fix the opening if Td is over 100°C
(Td control)
pag. 80
SMGB0003 rev.0-01/2007
Control system
This series has a protection control to resolve abnormal status before reaching to the alarm status, occurrence.
4
discharge gas -Re-start in 3 min
temperature 1min
(alarm: 3 times in 90min)
-Compressor stop: retry code
Prevention of [Cn-P5]
Actuation of internal Thermo of
overheat of -Re-start at internal Thermo -
motor for compressor
compressor restart
(alarm: 3 times in 60min)
Prevention of Inlet refrigerant temperature -output of fan inverter frequency
decrease of of water side heat exchanger 6Hz 30 min or high pressure≧2.0MPa during
evaporating ≦–4.5°C -Fan inverter frequency is 20Hz at fan is fixed at 20Hz
temperature (1)
3 sec high pressure≧1.8MPa
<COOLING>
Prevention of Inlet refrigerant temperature
decrease of of water side heat exchanger Hold after output of load-up 10
evaporating 30 min
≦–5.5°C second
temperature (2)
10 sec
<COOLING>
Prevention of -Compressor stop: retry code
Inlet refrigerant temperature
decrease of [Cn-P6]
of water side heat exchanger
evaporating ≦–6.5°C -Re-start in 3 min
temperature (3)
3 sec (alarm: 3 times in 30min)
<COOLING>
-Compressor stop: retry code
Suction refrigerant gas [Cn-P6]
Anti-freezing (1) temperature ≦–2°C -
<COOLING> -Re-start in 3 min
10 sec
(alarm: 3 times in 30min)
Anti-freezing (2) Chilled water outlet temperature Hold after output of load-down 10 30 min
<COOLING> ≦2.5°C second
Protection of High pressure – low Hold after output of load-up 12 High pressure – low pressure > 0.3MPa
pressure difference pressure≦0.3MPa second 1min
pag. 81
SMGB0003 rev.0-01/2007
Troubleshooting
5. T r o u b l e s h o o t i n g
Content
5. Troubleshooting .......................................................................................................83
5.1. Initial check ........................................................................................................................................... 84
5.1.1. Check of power supply and connection ....................................................................................................... 84
5.1.2. Check on PCB.............................................................................................................................................. 85
5.1.3. Confirmation of activation value of protection device an Automatic operation device ................................. 96
5.1.4. Individual indication for activation of protection device ................................................................................ 97
5
5.2.2. Alarm indication.......................................................................................................................................... 109
5.2.3. Failure diagnosis method ............................................................................................................................ 111
pag. 83
SMGB0003 rev.0 - 01/2007
Troubleshooting
1 Is power supply or fuse broken? Measure secondary voltage of breaker and current carrying of fuse by tester.
Pull out the connection of secondary side in Transformer and measure the
voltage by tester. Confirm if the voltage corresponds to the indication in
Transformer.
Red
Blue
Rated
Circuit and voltage
Load
Blue
Orange
Red
Orange
White
Red
Red
Circuit and voltage
Blue
Rated
Load
Blue
Orange
Red
Orange
Green
Confirm if wiring is not loose nor wiring is wrong referring to the electricity
circuit.
− Insertion of connector of Thermistor or Compressor Sensor
Wiring loose?
3 − Insertion of connector of Flat Cable
Wrong wiring?
− Insertion of connector of Transformer Connector
pag. 84
SMGB0003 rev.0 - 01/2007
Troubleshooting
Configuration for standard version. Standard values are the ones shown on PCB drawing and table below.
RHUE50AG2
RHUE60AG2
RHUE70AG2
RHUE80AG2
RHUE100AG2
RHUE120AG2
RHUE140AG2
RHUE160AG2
RHUE180AG2
RHUE210AG2
RHUE240AG2
pag. 85
SMGB0003 rev.0 - 01/2007
Troubleshooting
RCUE40AG2
RCUE50AG2
RCUE60AG2
RCUE70AG2
RCUE80AG2
RCUE100AG2
RCUE120AG2
RCUE140AG2
RCUE160AG2
RCUE180AG2
RCUE210AG2
RCUE240AG2
RCUE280AG2
RCUE320AG2
RCUE350AG2
RCUE400AG2
pag. 86
SMGB0003 rev.0 - 01/2007
Troubleshooting
RCUE40AG2
5
RCUE50AG2
RCUE60AG2
RCUE70AG2
RCUE80AG2
RCUE100AG2
RCUE120AG2
RCUE140AG2
RCUE160AG2
RCUE180AG2
RCUE210AG2
RCUE240AG2
RCUE280AG2
RCUE320AG2
RCUE350AG2
RCUE400AG2
pag. 87
SMGB0003 rev.0 - 01/2007
Troubleshooting
DESCRIPTION:
NORMAL
MODE
(Now low voltage control)
MODE 1
(Hi/Lo)
MODE 2
(Pulse)
Figure 1 2 1 2 1 2
Location ON ON ON OFF OFF ON OFF OFF
pag. 88
SMGB0003 rev.0 - 01/2007
Troubleshooting
Figure 9 10 9 10 9 10 9 10
Location OFF ON ON OFF ON ON OFF OFF
Compressor 40 HP 40 HP 50 HP 60 HP
Figure 3 4 3 4 3 4 3 4
Location ON ON ON OFF OFF ON OFF OFF
Band (degree) 1.0 2.0 3.0 4.0
DSW5-5: Temperature band for LOAD UP2 This chart is based on a Temp. Setting of 7ºC
Figure 5 5 Water
Temperature
Location ON OFF
Load up 1 Mode
Band (degree) 1.0 3.0
Set by
DSW5 Load up 2 Mode
5 pin
Set by
DSW5,
3&4 pin
Water Oultet
Temperature
Set by Inlet Water Temp
RSW8 when system is
Neutral zone
stopped with Thermo
Setting
OFF MODE
Temperature
Thermo OFF
Standard setting
pag. 89
SMGB0003 rev.0 - 01/2007
Troubleshooting
− DSW5-6: Pulse width in Seconds for Load Up Slide Valve in compressor in LOAD UP1 Mode.
(SVn-UP: Coil energizing)
Figure 6 6
Location ON OFF
Time (minute) 12 24
− DSW5-7,8: Pulse width in Seconds for Load Up Slide Valve in compressor in LOAD UP2 Mode.
(SVn-UP: Coil energizing)
Figure 7 8 7 8 7 8 7 8
Location ON ON ON OFF OFF ON OFF OFF
Time (minute) 2 4 6 8
Frequency
Pulse width [DSW5-9,10]
Frequency
Pulse width [DSW5-9,10]
Figure 1 2 1 2 1 2
Location OFF OFF ON OFF OFF ON
DSW7-3: ON; Thermo OFF is delayed after Outlet Temperature is below Thermo OFF setting for 3 min.
DSW7-4: ON: Used only in case of remote control through H-LINK (e.g.:CSC-5S, HARC)
pag. 90
SMGB0003 rev.0 - 01/2007
Troubleshooting
− PCBB1 RSW1,2 (SW5): Setting Temperature in Cooling Mode with to digits and the sign indicated in
SW5
(PCBB2 RSW1,2 & SW5: No function)
In case of Brine 2 Option can be set negative temperatures.
− PCBB1 RSW3,4: Setting Temperature in Heating Mode with to digits (Only available in Heat Pump
Models- RHUEXXXAG2)
(PCBB2 RSW3,4: No function)
5
− PCBB1 RSW5,6,7: CT Sensor function (Supplied as standard)
5 60/120/180
Y
X 10 min.
6 70/140/210/280/350 RSW7
7 80/160/240/320/400
Compressor load is kept for period when CT sensor measures set current
e.g.:
RCUE40AG2: Compressor load is “down” and “hold” for 30min (Y=3; 3*10min) when compressor current is
higher than 48 A (X=2; 1.2*40A).
− PCBB1 RSW8: Temperature band for Neutral Zone (See also DSW5)
Figure 0 1 2 3 4 5 6 7 8 9
Band (degree) 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0
pag. 91
SMGB0003 rev.0 - 01/2007
Troubleshooting
− PCBB1 RSW9: Temperature setting for one Defrost condition [Evaporator. Temp.- Ambient Temp.:
2~20ºC]
pag. 92
SMGB0003 rev.0 - 01/2007
Troubleshooting
− PCBB1,B2 SW9, SW10: High Cut check (Fan Stop for Check)
SW9 (PCBB1): ON Checking Cycle 1
SW10 (PCBB1): ON Checking Cycle 2
SW9 + SW10 (PCBB1): ON Checking Cycle 3
SW9 (PCBB2): ON Checking Cycle 4
SW10 (PCBB2): ON Checking Cycle 5
5
DIP SWITCH SETTING PCBC1,C2 (MAIN CONTROL PCB; Master & Subsidiary)
DSW-1: H-LINK end resistance (ON only PCB C1)
DSW-2: Fuse protection
pag. 93
SMGB0003 rev.0 - 01/2007
Troubleshooting
pag. 94
SMGB0003 rev.0 - 01/2007
Troubleshooting
H-LINK:
DSW4-1~3
5
H-LINK end Resistence
All pins in OFF
pag. 95
SMGB0003 rev.0 - 01/2007
Troubleshooting
Protection device
Activation value of protection device is as follows:
Cooling Prevention control for low pressure decrease 0.314 MPa (Electron control)
40 HP 55 A
50 HP 60 A
Excess current in relay
for compressor
60 HP 70 A
70 HP 85 A
80 HP 90 A
NOTE:
Safety valve is installed in all models
pag. 96
SMGB0003 rev.0 - 01/2007
Troubleshooting
-Δ switch Sec 5
Relay for only Electron control
starting control
Staring unload Sec 30
Sequential Min 1
starting (Note 2)
NOTES:
1. It should be normally over 3 min.
2. In all chiller units there is a timer which prevents compressors starting at the same time.
5.1.4. Individual indication for activation of protection device
~ Power ON
No. of cycle
Wait for pump feed
back
State
Procedure of ex.
~ valve zero reset
~ At cooling operation
~ At heating operation
At activation of
~ current limit
At Alarm
~ At thermo OFF
~ At stop operation
NOTES:
− C1~C5 means No of cycle. (C1: Cycle 1)
− Number of cycle whose manual set switch is ON is indicated alternately.
− It is a state from the output of pump operation signal to the confirmation of pump interlock. In case that
pump interlock is confirmed immediately, it is possible that the indication is not checked visually since the
indication time is too short.
pag. 97
SMGB0003 rev.0 - 01/2007
Troubleshooting
Segment Indication
Contents
abnormal code
Activation of High Pressure Block Devise(63H)
Activation of Prevention Control for Suction Pressure Block
Decrease
Flickering alternately
Outlet Chilled Water Thermistor Abnormality in some cycles
Activation of Water Overheating Protection Control Abnormality in
some cycles
Liquid Temperature Thermistor Abnormality
pag. 98
SMGB0003 rev.0 - 10/2006
Troubleshooting
Segment Indication
Contents
abnormal code
Inverter Speed Control Abnormality
Segment Indication
5
Contents
abnormal code
During retry control at simultaneous abnormal in some (majority) fans
(Fan single retry)
Abnormal code during retry control in Fn-4m, Fn-5m
NOTES:
“n”: Cycle Nº (n=1-5)
“m”: Fan Nº (m=1-4)
In case of fan abnormal operation, retry is performed in every case and in case that the same abnormal
operation occurs in specified times within specified period, unit is stopped by alarm.
Retry:
1. Retry in fan by itself (compressor keeps operating. Re-start in 10 seconds)
2. Retry in cycle by itself (compressor also stops. Re-start in 3 minutes).
In case of retry in cycle by itself, retry is indicated like above “list of state at inverter retry”. In case of retry in
fan by itself, it is possible to confirm which fan is being retried in check mode.
pag. 99
SMGB0003 rev.0 - 01/2007
Troubleshooting
Every Chiller is delivered with the correct priority configuration (Master PCB and slave PCB). In case of a
Control PCB delivered as a spare part, it will be necessary to set the correct priority configuration because it
is not known where it will be applied (Chiller model).
In case that this priority configuration is not correct, the Chiller cannot operate. See next point.
Problem detection
:
7 segments on PCBA shows the above message and no alarm message is shown.
Configuration
To establish the right priority configuration in each PCBC it is necessary to connect an operation
PCB (PCBA and PCBB) to the corresponding Control PCBC. It means that in case of a CHILLER Electric Box
with 5 cycles, it is necessary to connect an additional operation PCB (PCBA and PCBB) to establish the right
priority configuration in this subsidiary control PCB (PCB C2)
PCBA
SW4
SW3
pag. 100
SMGB0003 rev.0 - 01/2007
Troubleshooting
PCBB
5
Checking of current priority configuration
:x
(“X”: 0, 1 or 2)
pag. 101
SMGB0003 rev.0 - 01/2007
Troubleshooting
7 segments
: Setting for main control PCB (PCBC) in all CHILLERS up to 240 HP
: Setting for main control PCB (PCBC1) in Cooling Only CHILLERS with 4 or 5 cycles.
: Setting for subsidiary control PCB (PCBC2) in Cooling Only CHILLERS with 4 or 5 cycles
7 segments
:x “X” is the priority number of the PCB (0, 1 or 2), according to the above table
2. Priority number is changeable only in “U2” position, it means that first it is necessary to set U2 in 7
segments pushing the SW3 and SW4 at the same time in Operation PCB (PCBA) during 3 seconds.
7 segments
:x “X” is the priority number (0, 1 or 2) that you can select following the next point.
3. For modifying “X” value is necessary to push during 1 second SW3 or SW4 of Operation PCB (PCBA)
depending if you want to increase (DSW3) or decrease (DSW4) the priority number
4. Push at the same time DSW3 and DSW4 for 3 seconds for fixing at “U1” the corresponding priority
number established before in “U2”.
5. Switch OFF the power supply in the Electrical Box (M.I. switch OFF)
6. Switch ON the power supply in the Electrical Box (M.I. switch ON)
7. See on the Operation PCB, in the 7 segments, the right configuration number according to the table on
point 7. On the contrary repeat again all steps and select the right configuration number.
8. Restore the initial setting: DWS1, RSW8-3
Confirm the initial setting for these switches with the Technical Catalogue considering the options included
in the model. The standard setting values are the next:
DSW1 RSW8
NOTE:
In case of additional option DSW1 and RSW8 can be different
pag. 102
SMGB0003 rev.0 - 01/2007
Troubleshooting
Is
it judged
Could it that it is possible to NO
NO
be a temporal continue operation although fan
phenomenon due to an is stopped temporally
accidental factor?
YES
YES
- Stop the compressor of
- Stop the correspondent fan
- Stop the compressor of correspondent cycle
- Count retry times
correspondent cycle - Count retry times
- Count retry times
Retry
control by NO
Retry the same abnormal
control by
5
YES reason is performed specified
the same abnormal times within specified
reason is performed specified period?
times within specified (*) Fan restart by itself
period? YES - no indication of retry code
(fan under retry is indicated
1
NO in check mode)
abnormal
NO - correspondent fan is re-
fan per 1 cycle?
- Retry code is indicated started in 10 sec.
And are all fan manual set
- Compressor is re-started
SW ON?
in 3 min.
YES
(*) Cycle retry
- Correspondent fan is stopped - indication of retry code
REMOTE OUTPUT (ALARM)
- compressor is re-started
terminals (n54~n55)
in 3 min.
- No indication of alarm code (fan
under stop by abnormal function is
indicated in check mode)
(Alarm stop)
- compressor of correspondent
cycle is stopped
- indication of alarm code
Operation continues
Indication lamp of remote controller side distinguishes “Run”, “Alarm”, and ”Stop”:
pag. 103
SMGB0003 rev.0 - 01/2007
Troubleshooting
Check mode
By pressing [▲] (SW3) on PCB more than 3 seconds, control state of chilled water temperature, each
refrigerant cycle pressure/ temperature etc are indicated. (it is possible both during stopping and during
running), (*mode shall not be shifted in case of alarm).
Pressing again [▲] (SW3) on PCB more than 3 seconds enables you to see the different values but with
decimals
Normal indication State
Indication of check mode
- Nº 1 cycle (C1)
- During cooling (Co)
Press more than 3 sec.
-in case of outlet water temperature = 7ºC
(For units with more than one cycle, this is the average
value)
In 2 cycles, chilled water outlet temp every cycle is
indicated. (no indication in case of 1 cycle)
-in case of outlet water temp of No.1 = 7ºC
-in case of outlet water temp of No.2 = 7ºC
*Unit whose manual set SW is OFF is indicated.
pag. 104
SMGB0003 rev.0 - 01/2007
Troubleshooting
Setting state
indication 3. Chilled water second temperature setting indication
[ºC]
-in case of setting temperature = 5ºC
*only at alarm selection
Ambient
temperature Ambient temperature indication [ºC]
5
indication -In case of 35ºC
Capacity *Load-up [UP] / Neutral Zone [nU] / Load down [d0]
control state
indication
Thermo OFF [- - ].
*In case of 2 cycles, [C2-Ld]
activation) Starting
capacity control Silence mode
Operation mode Protection Pd control
control state Night Shift mode
Abnormal stop
Light the position correspondent to the fan
In case of 2 cycles, [C2-FC]
Control
software ROM
Nº indication . Indication of ROM NO. (ex: 239)
The following operation makes change from check mode back to normal mode.
1. Press [▲] (SW3) more than 3 sec.
2. In case that un-input state continues 1 hour.
pag. 105
SMGB0003 rev.0 - 01/2007
Troubleshooting
Flicker alternately
.
Normal indication State
The latest alarm code
- Nº 1 cycle (C1)
- Under cooling (Co) Press them simultaneously more than 3 sec.
5th oldest
.
Activation of
protection
device
The 5th oldest alarm [pump interlock abnormality].
(alarm code)
The following operation makes change from alarm occurrence indication mode back to normal mode.
1. Press [▲] (SW3) [▼] (SW4) more than 3 sec.
2. In case that un-input state continues 30 seconds.
3 Alarm Data Indication Function (The Last Saved Data before Alarm Occurrence)
Regarding the latest alarm, the last sensor data before stop can be indicated, while alarm occurrence is
indicated. (Data is indicated by the following operation during the latest alarm occurrence indication)
-Alarm data of the latest alarm occurrence is only saved.
-Alarm data is cleared by Power OFF
-In case that data is not saved, alarm occurrence data mode after flickering [- - -] twice.
4 To switch indication items, Press [▲] (SW3) [▼] (SW4).
5 Indication data is the same as the one of check mode. However, the next items are indicated as an additional.
pag. 106
SMGB0003 rev.0 - 01/2007
Troubleshooting
Refrigerant liquid
Outlet water temp (backside of heat exchanger of
Outlet water temp
(backside of heat
water side) [ºC]
The following operation makes change from alarm data indication mode to normal mode.
5
1. Press [▲] (SW3) [▼] (SW4) more than 3 sec.
2. In case that un-input state continues 30 seconds.
The following operation makes change from alarm data indication mode to alarm occurrence data mode.
1. Press [▼] (SW4) more than 3 sec.
Electron expansion valve opening indication
By pressing [Ο] (PSW1) on PCB for electron expansion valve more than 3 seconds, actual expansion valve
order opening (pulse) is indicated on the segment. (it is possible during stop / operation)
Once pulses are displayed, pushing again PSW1 enables you to check each cycles expansion valve
position.
PWBG (VD PCB)
Flicker
alternately
Press it more
than 3 sec.
Check switch
PULSES OPENING %
10 (Thermo OFF) 1,5 %
112 (Min. running value) 17%
* Light off by pressing [Ο] more than 3 seconds. 656 (Max. running value) 100%
pag. 107
SMGB0003 rev.0 - 01/2007
Troubleshooting
5.2. Troubleshooting
Alarm occur
Stop Operation
Yes
Is abnormality code
in segment indication
confirmed?
No
NOTES:
− After the stop operation, alarm indication is turned off and initial status 88 is displayed.
Abnormality code, which was activated before can be seen by entering “Indication Mode of
Alarm Occurrence Data”.
− When the power turns off and turns on, the indication on the display is initial status. Abnormal
code, which was activated before can be seen by entering “Indication Mode of Alarm
Occurrence Data”
− When the power turns off (Main switch), “The Last Saved Data before Alarm Occurrence” is
cleared.
− "The Last Saved Data before Alarm Occurrence” has only the last data before last alarm. In case
of before that, only alarm code is saved.
pag. 108
SMGB0003 rev.0 - 01/2007
Troubleshooting
With indication
Alarm Code
Description of abnormality
No.1~6 cycles
[]~[] Activation of High Pressure Switch
[]~[] Activation of Fan Motor Internal Thermostat (Only for 70,80,140,160,210,240,280,320,350 and 400HP)
[]~[]
5
Activation of Thermal Relay for Compressor or Chattering alarm or Malfunction of Auxiliary Relay Arn
[]~[] Failure of Water Outlet Thremistor at Rear Side of Water Cooler (Open / Short)
[]~[] Error Communication between Inverter PCB and Control or Fan Control PCB *1
[] Failure of Water Outlet Thermistor (Open / Short) (Only for 1 cycle unit)
pag. 109
SMGB0003 rev.0 - 01/2007
Troubleshooting
Alarm Code
Description of abnormality
No.1~5 cycles
[] Incorrect Operation
[] Error communication between Expansion Valve PCB and Cntrol PCB
[ ]
Error communication between Fan Contol PCB and Cntrol PCB
[] Error communication between Chiller and Remote Controller (If CSC-5S is connected.)
[]~[] Retry Operation (More Than 3 Fans Retry at The Same Time)
“ - " : Flickering
pag. 110
SMGB0003 rev.0 - 01/2007
Troubleshooting
No
Is 380-415V supplied Check the power
to the unit?: source switch
Yes
No Yes
Is 220-240V supplied to Is fuse broken? Replace fuse
transformer primary side?
No
Yes
Is R phase or S Yes
Wiring check
phase failure? and repair
5
No
Wiring check
Is 30V in PIN1~PIN2, No Yes
16.3V in PIN3~PIN4,
Check the power
19.6V in PIN5~PIN6 of the Replace
source switch
printed circuit board for transformer
CPU (PCBc) connector
CN2A?
No Wiring check
Yes
Connector check
Yes
Yes
Check Printed Circuit
Board for Display and
Operation (PCBA,
PCBB)
Check Printed Circuit
Board for CPU (PCBC)
pag. 111
SMGB0003 rev.0 - 01/2007
Troubleshooting
Yes
(activated
immediately) No
Is alarm activated just Is high pressure switch Reset the switch
after running? (63H) reset?
Yes
Yes
Yes
Is 220-240V the voltage
between connector Check Printed Circuit
PCN203 PIN1 and Board for Relay
connector PCN203 PIN3 (PCBD)
on the Printed Circuit
Board for Relay (PCBD)?
Wiring check
No (disconnecting, wiring
error)
Yes (PCB is
Is alarm activated in 3 normal) <COOLING>
minutes after running Is high pressure switch
(63H) activated? Clogging of air side heat exchanger
operation?
Check of high pressure
Yes No
Cycle check
<HEATING>
Shortage of Water
Air mixed
Yes
pag. 112
SMGB0003 rev.0 - 01/2007
Troubleshooting
Alarm code Excessively low suction pressure
Shortage of Water
5
Pump reverse rotation
Air mixed
pag. 113
SMGB0003 rev.0 - 01/2007
Troubleshooting
[Retry Code]
No. 1 Cycle: C1-P6
No. 2 Cycle: C2-P6
No. 3 Cycle: C3-P6
No. 4 Cycle: C4-P6
No. 5 Cycle: C5-P6
Shortage of Water
Air mixed
pag. 114
SMGB0003 rev.0 - 01/2007
Troubleshooting
Yes
(activated
immediately) Is 220-240V the voltage
Yes
Is alarm activated just after between connectorPCN207
Check Printed Circuit
PIN1 and connector PCN 207
5
running operation? Board for input/output
PIN3 on the Printed Circuit
(PWBD)
Board for Relay (PCBD)?
No (Activate
after a while)
No
Wiring Check
(breaking of wire,
wrong wiring)
pag. 115
SMGB0003 rev.0 - 01/2007
Troubleshooting
[Retry Code]
No. 1 Cycle: C1-P5
No. 2 Cycle: C2-P5
No. 3 Cycle: C3-P5
No. 4 Cycle: C4-P5
No. 5 Cycle: C5-P5
Is connector CN24Td on No
the Printed Circuit Board Plug correctly and
for Relay (PCBD) correctly repair wiring
connected?
Yes
No
Pull out connector and
measure thermistor Replace thermistor
resistance. Is resistance
correct?
Yes Yes
Shortage of refrigerant/ gas leakage
pag. 116
SMGB0003 rev.0 - 01/2007
Troubleshooting
[Retry Code]
No. 1 Cycle: C1-P5
No. 2 Cycle: C2-P5
No. 3 Cycle: C3-P5
No. 4 Cycle: C4-P5
5
No. 5 Cycle: C5-P5
No (Printed
Is 220-240V the voltage Circuit Board is Excessive or short power source voltage
between connector normal)
PCN204 PIN1 and
connector PCN 204 PIN3 Interphase of power source voltage is imbalanced.
on the Printed board for
Relay (PCBD)? Compressor motor is locked
Wiring Check
pag. 117
SMGB0003 rev.0 - 01/2007
Troubleshooting
Alarm code Excess Low Temperature of Cooler Inlet Refrigerant (Tr)
No
Is the wiring of connector
Plug correctly and
in the Printed Circuit Board
repair wiring
for Relay (PCBD) correct?
Yes
No
Pull out connector and
measure thermistor Replace thermistor
resistance. Is resistance
correct?
Yes Yes
Check the water flow rate.(Check
temperature of inlet and outlet.)
pag. 118
SMGB0003 rev.0 - 01/2007
Troubleshooting
Alarm code Low Pressure Protection by Suction Gas Thermistor (Ts)
Yes
No
Pull out connector and
measure thermistor Replace thermistor
resistance. Is resistance
correct?
Yes Yes
Check the water flow rate.(Check
temperature of inlet and outlet.)
pag. 119
SMGB0003 rev.0 - 01/2007
Troubleshooting
No (Printed
Circuit Board
Is 220-240V the voltage is normal) Yes
between connector PCN4 Is thermal relay for pump Check pump lock
PIN1 and connector PCN4 (TRP) activated?
PIN3 on the Printed Circuit
Board for CPU (PCBc)?
No
Yes
pag. 120
SMGB0003 rev.0 - 01/2007
Troubleshooting
Alarm code Phase Abnormality (Reverse Phase / Phase Failure)
5
Is 3 phase power source Reverse Phase) Power Supply,
phase failure or reverse Wiring Check
phase?
No
Yes
No (Correct Phase)
Check printed
circuit board for
relay (PCBD)
pag. 121
SMGB0003 rev.0 - 01/2007
Troubleshooting
Alarm code Activation of Freeze Protection Control
No
Is connectors on the Plug correctly and
Printed Circuit Board repair wiring
correctly connected?
Yes
No
Pull out connector and
measure thermistor Replace Thermistor
resistance
Is resistance correct?
Check water flow rate (Check the
Yes Yes temperature of Inlet and Outlet)
NOTE:
− One inlet temperature Themistor is installed in each unit.
− Two outlet temperature Thermistors are installed in every heat exchanger in water side.
− The below table shows the relation between Thermistor and alarm indication as well as
connecting Printed Circuit Board (PCB).
pag. 122
SMGB0003 rev.0 - 01/2007
Troubleshooting
Abnormal
Product Model Thermistor PCB Connector
Code
5
Chilled water outlet temperature Thermistor 2
(backside cooler) PCBD3 CN23
pag. 123
SMGB0003 rev.0 - 01/2007
Troubleshooting
Alarm code Activation of Water Overheating Protection Control
No
Pull out connector and
measure thermistor Replace Thermistor
resistance
Is resistance correct?
Check water flow rate (Check the
Yes Yes temperature of Inlet and Outlet)
NOTE:
The below table shows the relation between Thermistor and alarm indication as well as
connecting Printed Circuit Board (PCB).
Abnormal
Product Model Thermistor PCB Connector
Code
RCUE 40 ~ 80 AG2
Outlet water outlet temperature Thermistor 1 PCBC1 CN4
RHUE 40 ~ 80AG2
pag. 124
SMGB0003 rev.0 - 01/2007
Troubleshooting
No
Yes
Is alarm reset by stop Is setting of Dip Switch Check Printed Circuit
switch? correct? Board for Operation
(PCBB)
Yes No
Set Dip Switch correctly
and turn the power source
Yes (Normal ON again.
No (Remote) Running)
Is local operation? Is changeover to local side It is incorrect that
during remote operation? operation changeover to
local side during remote
Yes (Local) No operation.
5
Do not perform it.
Is 220-240V between No
PIN1-PIN3 of connector Wiring Check between
PCN16 on the printed remote control switch and
circuit board for CPU printed circuit board.
(PCBC)?
Yes
Check Printed Circuit
Board for Relay (PCBD)
Yes
(Normal
Is optional wiring Yes Running)
Is the signal transmitted It is incorrect that remote
connected? operation signal is
from option device?
transmitted from option
device during local
operation.
Do not perform it.
No
No Wiring Check between
external device and
Yes printing board
(Normal
Is it changed over to Running)
remote side during local It is incorrect operation
operation? that changeover to
Remote Side during
Local Operation.
No
Do not perform it.
pag. 125
SMGB0003 rev.0 - 01/2007
Troubleshooting
No
Is Printed Circuit Board for
Plug, Wiring Repair
Control (PCBC) connector
CN3 correctly connected?
Yes
Alarm code Outlet Chilled Water Thermistor Abnormality
No
Is Printed Circuit Board for
Plug, Wiring Repair
Control (PCBC) connector
CN3 correctly connected?
Yes [] Stop by abnormality of chilled water outlet Themistor for No.1 cycle
[] Stop by abnormality of chilled water outlet Themistor for No. 2 cycle
NOTE:
The connector position differs from product model.
pag. 126
SMGB0003 rev.0 - 01/2007
Troubleshooting
Abnormal
Product Model Thermistor PCB Connector
Code
RCUE 40 ~ 80 AG2
Outlet water temperature Thermistor 1 PCBC1 CN4
RHUE 40 ~ 80AG2
Alarm code
Evaporating Temperature Thermistor Abnormality
5
No
Is Printed Circuit Board for
Plug, Wiring Repair
Relay (PCBD) connector
CN27correctly connected?
Yes
pag. 127
SMGB0003 rev.0 - 01/2007
Troubleshooting
Alarm code Discharge Gas Temperature Thermistor Abnormality
Alarm code Liquid Temperature Thermistor Abnormality
pag. 128
SMGB0003 rev.0 - 01/2007
Troubleshooting
Yes
NOTE:
The connector position differs from product model.
Abnormal
Product Model Thermistor PCB Connector
Code
RCUE 40 ~ 80 AG2 Outlet water temperature Thermistor
PCBD1
RHUE 40 ~ 80AG2 (backside of cooler)
pag. 129
SMGB0003 rev.0 - 01/2007
Troubleshooting
pag. 130
SMGB0003 rev.0 - 01/2007
Troubleshooting
Is connector CN28Pd on No
the printed circuit board Connect correctly
for relay (PCBD) correctly
connected?
Yes
Is DC24V between
connector CN28Pd PIN1
and PIN3 on the printed
No
Replace printed circuit
5
circuit board for relay board for Relay (PCBD)
(PCBD)?
Yes
Yes
Yes
Is discharge gas pressure Removing the clogging
sensor connecting pipe in the pipe.
Yes
clogging?
Discharge pressure
sensor abnormality
pag. 131
SMGB0003 rev.0 - 01/2007
Troubleshooting
Is connector CN29Ps on No
the printed circuit board Connect correctly
for relay (PCBD) correctly
connected?
Yes
Is DC5V between
connector CN29Ps PIN1 No
and PIN3 on the printed Replace printed circuit
circuit board for relay board for Relay (PCBD)
(PCBD)?
Yes
Yes
Yes
Is discharge gas pressure Removing the clogging
sensor connecting pipe in the pipe.
Yes
clogging?
Discharge pressure
sensor abnormality
pag. 132
SMGB0003 rev.0 - 01/2007
Troubleshooting
Yes
5
Replace Printed Circuit
Board for CPU (PCBC)
Alarm code Error Communication between Ctrl. PCB and Ex. Valve PCB
Is connector VCN13 No
on the Printed Circuit Plug correctly and
Board for Ex. valve repair wiring
control (PCBG) correctly
connected?
Yes
pag. 133
SMGB0003 rev.0 - 01/2007
Troubleshooting
Is connector CN 8 on
the Printed Circuit Board No Replace printed circuit
for Fan Speed Control board for Relay (PCBD)
(PCBH, PCBJ) correctly
connected?
Yes
Yes
pag. 134
SMGB0003 rev.0 - 01/2007
Troubleshooting
Is connector on the No
Printed Circuit Board Plug correctly and
correctly connected? repair wiring
Yes
Yes No
No problem as a
product.
Ask users to check the
Replace Printed Circuit installation.
Board for CPU (PCBC)
No
Is setting of Dip Switch
Set Dip Switch correctly
correct?
Yes
No
Check Printed Circuit Replace printed circuit
Board for Operation board for Relay (PCBD)
(PCBB) and Printed
Circuit Board forYes
Fan
Speed Control (PCBH
and PCBJ )
pag. 135
SMGB0003 rev.0 - 01/2007
Troubleshooting
Alarm code Water flow Protection Switch Activation (at 63W use;
Option)
No
Is chilled water flowing? Check the pump
Yes
Is water shortage
protection switch ON No
during pump running? Check water flow in the
pump
Clogging of water
Yes strainer
Yes
No
Is setting of Dip Switch Set Dip Switch correctly
correct?
Yes
pag. 136
SMGB0003 rev.0 - 01/2007
Troubleshooting
[Retry Code]
No code indication (indicated within the
check mode)
NOTE:
See "Inverter position detection abnormality" in the next page for flowchart
[Retry Code]
No code indication (indicated within the
check mode)
NOTE:
See "Inverter position detection abnormality" in the next page for flowchart
pag. 137
SMGB0003 rev.0 - 01/2007
Troubleshooting
Re-operate
Yes
Is motor operating? Possible alarm cause is to detect excess current by
head wind.
Use as it is since the product has no failure
No
No
Check if connector on the fan module, relay connector and PIN are OFF.
*Connector is different from models. Confirm it with operation circuit drawing
Yes
Is connector abnormal? Repair it
No
Re-operate
Yes
Is motor operating? Repaired
No
Re-operate
Yes
Is motor operating? Repaired
No (No indication)
pag. 138
SMGB0003 rev.0 - 01/2007
Troubleshooting
No
Is fan module No. set Set Dip Switch correctly
correctly?
Yes
Yes Yes
Check fuse
Is connector CN201, No
202 on the fan module Plug correctly and
correctly connected? repair wiring
Yes
pag. 139
SMGB0003 rev.0 - 01/2007
Troubleshooting
Yes
Yes
Yes
Is voltage down by
operating some operating
devices?
No Fan is operated
normally and fan
frequency is increased.
Is LED201 of fan computer How is the running Fan is operated but Fan computer has
lightning ? status of fan at re- stopped immediately. failure.
operation?
Replace it.
Yes
Replace fuse
pag. 140
SMGB0003 rev.0 - 01/2007
Troubleshooting
Power Failure Measure voltage by tester. Wait the recovery of power source
5
Earth Fault in Operation
Measure insulation resistance. Eliminate earth fault and replace fuse
Circuit
Crankcase Heater Failure Measure resistance. Replace oil heater and fuse.
pag. 141
SMGB0003 rev.0 - 01/2007
Troubleshooting
Pump and
compressor Measure the interphase
Fan Motor Failure Replace fan motor
run, but fan resistance
does not run
Wiring Connection
Failure Repair the wiring
Check circuit by tester
Printed Circuit Board connection.
Printed Circuit
Board Failure Failure
Air temperature through Air Short Circuits in Chiller Unit Remove short-circuits
air side heat exchanger Another heat source around
is excessively high Remove heat source
chiller unit
pag. 142
SMGB0003 rev.0 - 01/2007
Troubleshooting
Check valve
Suction gas
(Air heat exchanger side) Replace check valve
temperature
Discharge gas Malfunction
is excessively
control is activated high (excessive Expansion Valve Clogging Remove Clogging
(- alarm)~ superheat)
(- alarm) Strainer Clogging Replace or clean the strainer
Single Phase
Check magnetic contactor Replace magnetic switch
Running
5
activated
(- alarm)~ Power Fuse melted Replace power fuse
(- alarm) Loose Power Terminal
Retighten the screw
Single Phase Screw
Fan internal Running
Contact point of compressor
Unit stops thermostat is Motor magnetic Contactor Replace contact points
during activated Roughness
cooling (- alarm)~
operation (- alarm) Compressor Bearing
Lock Status
Failure
Replace compressor
Compressor Motor Measure insulation
insulation Failure resistance
Compressor Motor
Measure current of
Over-current relay Replace over-current Relay
compressor motor
Failure
Pump reverse
Freeze protection Check rotative direction Repair to correct direction
rotated
control is activated
( alarm) Air mixed Open Air Vent Valve Evacuate Air
Thermistor Failure
( alarm) Check inlet temperature of
( alarm) Replace Thermistor
chilled water
( alarm)
( alarm)
pag. 143
SMGB0003 rev.0 - 01/2007
Troubleshooting
The heat load is bigger than cooling capacity Calculate heat load Replace to larger unit
Expansion Valve
Check clogging Remove clogging
Clogging
Pump Reverse Rotation Check the rotation direction Repair to the correct direction
Air Mixed Open the air vent valve Evacuate the air
Installation error or
Check each bolt if loosen Tighten up.
loose bolt
Beats of magnetic contactor Check the roughness of contact Replace contact points
pag. 144
SMGB0003 rev.0 - 01/2007
Troubleshooting
The thermistor is installed in this product to detect the cycle temperature such as water temperature (inlet-outlet of
water side heat exchanger). Ambient temperature and outlet liquid refrigerant temperature air side heat exchanger.
The temperature characteristics are shown in the below figures:
pag. 145
SMGB0003 rev.0 - 01/2007
Troubleshooting
pag. 146
SMGB0003 rev.0 - 01/2007
Troubleshooting
pag. 147
SMGB0003 rev.0 - 01/2007
Maintenance
6. M a i n t e n a n c e
This chapter describe the procedure of the maintenance of the Air cooled water chillers.
Content
6. Maintenance ......................................................................................149
6.1. Maintenance criteria ...................................................................................................150
6
6.6.2. Refrigerant oil ..................................................................................................................161
6.6.3. Refrigeration cycle complete parts .................................................................................162
6.6.4. Reference materials ........................................................................................................162
pag. 149
SMGB0003 rev.0 - 11/2006
Maintenance
Check
Check Item Criteria (procedure) Remarks
Frequency
1. General
Judge from aprox. 1m
Noise A/N Confirm if there is no abnormal noise. from the control panel
surface.
Vibration A/N Confirm visually if there is no abnormal vibration
2. Cabinet
Dirt A/N Clean with cloths
Outside board Rust A/N Perform repair painting with Anticorrosion paint
and inner
Vibration A/N Re-tighten screws
3. Refrigerant Circuit
Confirm if there is no refrigerant leakage by
using detecting device in each component
and pipe connection parts. As for checking
Refrigerant leakage once/ season for leakage in water cooler and condenser,
General confirm it with the air discharged to water inlet
and outlet, and in this, case water should be
drained.
once/ Perform visual check if there is no contact or
Capillary pipes
season resonance.
Confirm if there is no abnormal noise at starting,
Noise A/N operating and stop.
Confirm if there is no oil leakage or bleed from
Oil leakage bleed A/N the compressor.
Oil level A/N Perform visual check by sight glass.
once/
Insulation Resistance More than 3MΩ at 500V DC
season
once/
Oil Heater Apply current during compressor stop.
season
Compressor Ageing of Vibration once/
Touch and confirm if they have rubber elasticity.
Insulation rubber season
Pay special attention to noise, vibration and oil
Intermediate check (1) once/ 3,000 hr leakage etc.
Confirm if safety device and protection device See following
Intermediate check (2) once/ 6,000 hr function well. ”maintenance criteria
once/ 24,000 hr of Screw compressor”
(water-cooled) Overhaul the compressor and check it according for details
Overhauling 40,000 hr to the specialist’ advice.
(Air-cooled)
Condenser Fin clogging once / season Clean it spraying warm water (less than 40ºC).
(air-cooled)
See technical
Water flow, water temp. A/N Confirm if they are within the criteria catalogue for details.
once/ See technical
Water quality Confirm if it is within the criteria.
month catalogue for details.
Condenser Frequency of cleaning
(water-cooled) Cleaning Confirm if high pressure is within the criteria. differs depending on
A/N Perform the predetermined cleaning. result of water quality
or operation time.
If condenser is not used for intermediate or long
Drain water once/ season period, drain water. At this time, open also plug
for draining water and for removing air.
pag. 150
SMGB0003 rev.0 - 11/2006
Maintenance
Check
Check Item Criteria (procedure) Remarks
Frequency
3. Refrigerant Circuit (Cont.)
Frequency of cleaning
differs depending on
Cleaning once/ season Perform the predetermined cleaning. result of water quality
or operation time.
Adjust them so that standard operation pressure See technical
Water flow, water temp. A/N
Water Cooler is kept. catalogue for details.
once/ If the water cooler is not used for intermediate or Drain also water in
Drain water long period, drain water in the heat exchanger of pipes.
season water side.
See technical
Water quality once/ month Confirm if it is within the criteria. catalogue for details.
once/ Confirm if switching coolingheating is performed Only for air-cooled
4 way valve Operation
season smoothly. heat pump type
Expansion Confirm if low-pressure changes smoothly by See technical
valve Operation once/ month turning adjustable screw. catalogue for details.
(Mechanical)
Expansion once/ Touch it to confirm if it functions correctly when
valve Operation zero reset is performed automatically just after
(Electronic) season power ON.
Confirm if there is no pressure difference inlet
Strainer Clogging once/ month and outlet of strainer
Solenoid valve Operation once/ month Confirm if valve opens or closes smoothly.
Stop valve Operation once/ month Confirm if valve functions smoothly.
Confirm if it is activated correctly with the value Pay attention to
High pressure Operation Once / month of safety and control device setting in technical fluttering of contact
6
switch catalogue. parts at operation.
4. Electrical system
Supply voltage is as follows:
±10% rated voltage ±10% rated voltage
pag. 151
SMGB0003 rev.0 - 11/2006
Maintenance
2 Refrigerant oil
Decomposition of compressor
4 Bearing
5 Rotor
6 thrust liner
NOTE:
− : part change : part change if abnormality is detected in the check
− This table is applied in case that operation condition is good and operation record is fully equipped.
− Perform compressor check according to the compressor service manual and technical notice.
pag. 152
SMGB0003 rev.0 - 11/2006
Maintenance
This air-conditioning device uses water as a heat source (for cooling) or as a media (chilled water, heat water) for use of
heat. Therefore, it is necessary to select suitable water and control it to maintain the quality and performance and avoid
possible problems.
Serious failure of plate heat exchanger may stop the units function and cause high expenses for its repair. Therefore, it is
indispensable to promote the maintenance and selection of water for the chiller installation.
Read the below criteria of water quality very carefully to avoid any troubles.
In case of using some chemical products for water treatment, it is recommended to consult with manufacturers
specialised in water treatment, since characteristics of chemical agents may differ with product specifiactions.
− pH (hydrogen-ion concentration)
pH is used as a measure to judge acidity, neutral and alkalinity of water. It is a big factor in taste, corrosion,
6
purification effect in water treatment, disinfection effect in chloride treatment, water stain formation, and other
fields like analytic chemistry, biochemistry etc. The below figure shows an example of relation between pH
value and corrosion.
Penetration (mm/year)
− Electrical conductivity
To know the outline of water quality, it is effective to measure electrical conductivity. This value is determined
by quality and quantity of dissolved chlorine, and generally water with a greater value of electrical
conductivity is not suitable since it has a lot of substance causing corrosion and lime.
− Chloride ion
Chloride ion has a important property regarding corrosion and corrosion is higher in water with big amount
of chloride ion although pH value is free of corrosion. Chloride ion does not have oxidise property, however
precious metal is penetrated if chloride ion combines with oxidant or dissolved oxygen.
− Sulfate ion
Sulfate ion is a cause of corrosion, but it gives an indication for line formation. If running water has a great
amount of sulfate ion, it will become rusty water.
pag. 153
SMGB0003 rev.0 - 11/2006
Maintenance
pag. 154
SMGB0003 rev.0 - 11/2006
Maintenance
− Dissolved oxygen
It is an oxygen gas dissolved in water and is a great factor to promote the corrosion. Regarding copper
corrosion, possibility of corrosion is increased in dissolved oxygen volume of 5~15 (ml/l), and is decreased in
greater or less value than that.
Remarks: Oxygen consumption, all hardness and calcium hardness
If these values are greater, line is likely to be produced, and if they are fewer, corrosion is likely to be
caused. In the guideline presented in the table, only the upper value is limited, which is based on an idea of
prevention of line trouble and of that the corrosion can be judged by other method. Therefore, if there is no
worry about line trouble, it is better to keep these values high to prevent the possibility of corrosion.
Concretely, in chilled and warm water, if RSI is 6~7.5 (there is no worry about line problem), it is convenient
to maintain the below value to prevent the corrosion.
- Oxygen consumption (pH4.8) (mgCaCO3/l) =50~100
- All hardness (mgCaCO3/l) =50~200
- Calcium hardness (mgCaCO3/l) =below 150
1. Before test run, all criteria items in the table should be checked.
2. The first week after test run pH and electrical conductivity should be measured. In case of any
trouble, all items should be checked. 6
3. One month after test run, all items should be checked.
4. After that, water quality tendency should be captured in these 3 tests and afterward schedule should
be decided by these results. Even in the case of no trouble, pH and electrical conductivity should be
checked every month and all criteria items of water quality should be checked every half year.
When the result of periodical inspection recognises some troubles in water quality, those actions as similar to
the following should be taken according to the situation.
1. Replace old water to new one or perform forced blow. (once a week ~ once a month)
2. Water should be treated with anti-corrosion agent or line inhibitor.
pag. 155
SMGB0003 rev.0 - 11/2006
Maintenance
To maintain good water quality, it is necessary to consider the installation place. See the below for your
reference.
− Before installation
1. Installation place
− Analysis of water quality should be asked to a specialised
a). Study if installation place is suitable. company in water treatment. If it is a negative result,
water source should be changed or treatment system
(*). Abnormal wastewater from boiler or refrigerating should be changed after consulting with the company.
machine is not mixed with the chilled water.
2. System
a). Study if materials of heat exchanger, pipe, tank, valve
− Corrosion may concentrate to only one part due to the
etc are suitable.
difference of material in chilled and heating water system.
b). Prohibition of open the pipe connected with tank to
− Open the pipe to ambient air may promote the corrosion.
ambient air.
Pipe should be put inside the water.
c). Study of temperature, flow, pressure and minimum
− Control that these values be within the usage range.
holding water volume of chilled and heating water.
− After working
2. Study of temperature, flow, pressure and minimum − Control that these values be within the usage
holding water volume of chilled and heating water range. (once a day)
pag. 156
SMGB0003 rev.0 - 11/2006
Maintenance
Plate heat exchanger is used in water side heat exchanger in this series .
Water passes through the clearance between plates in the plate heat exchanger,
therefore, dust or foreign materials should not exist there. (See the below structure
figure for your reference)
Strainer (correspondent to 20 mesh) should be installed in the inlet pipe of chilled water
(Strainer should be prepared in each case).
Line is produced based on the water quality, and it is possible to decrease the
performance or to break the plate due to the partial freezing caused by local clogging,
which leads to the refrigerant leakage. Cleaning of strainer as well as water side heat
exchanger should be performed periodically.
See the below cautions and normal cleaning method for your reference. Contact the
below detergent companies to the details.
Showa HQ (Gifu): +81-58-232-1131
Tokyo branch: +81-3-3580-6121
Osaka sales office: +81-6-6391-2051
Futuro +81-3-92-434-4143
Water (brine)
Water (brine)
CAUTION
1. Suitable cleaning agent for line should be selected. (According to the dirty, cleaning
agent differs)
2. Plate heat exchanger is made by stainless. (Copper material is used in the
connection of plate). Therefore, do not use a cleaning agent with “chlorine and
fluoride”. If it were used, heat exchanger should be damaged, which may cause the
refrigerant leakage.
3. After water discharge, wash the inside with water and then water treatment should
be performed in order to prevent the corrosion, rusty water or re-production of line.
4. Density of cleaning agent, cleaning time or temperature should be adjusted
according to the line.
5. After oxygen cleaning, neutralization treatment should be performed. Disposal of
waste water in neutralization treatment should be asked to the specialised company.
6. Cleaning agent or neutralization agent is corrosive or irritating to the body (skin,
eye etc). Therefore, when cleaning, put the protection materials (protection glasses,
protection grove, protection boots etc) on.
pag. 157
SMGB0003 rev.0 - 11/2006
Maintenance
Nº Name
Chiller unit
Water inlet
acid-proof pump
hose
Cleaning solution
Water outlet
Circulation tank
(tank for cleaning)
Tank for waste
water collection
Step 3: Cleaning
− Drain off the water in cleaning circuit.
− Adequate quantity of cleaning agent is put in the tank for cleaning and while diluting it,
operate the acid-proof pump so that the diluted cleaning liquid circulates in the circuit.
− Perform the circulation cleaning during prescribed time (it is determined in each
cleaning agent, although it differs from liquid type or density). It is necessary to
change the cleaning time according to the dirtiness.
pag. 158
SMGB0003 rev.0 - 11/2006
Maintenance
pag. 159
SMGB0003 rev.0 - 11/2006
Maintenance
4 Check of screws and bolts etc Re-tighten those which are loosed Tightened / No tightened
7 Dirtiness of air side heat exchanger Clean it by pouring hot (40°C) water. Done / No done
10 Compressor Good / NG
17 Strainer Good / NG
22 Vibration and noise Check compressor, fan, pipe etc. Abnormal / Normal
Operation adjustment and automatic operation Check the activation of ON, OFF,
23 Good / NG
mechanism temperature adjustment
Check the activation value and setting
24 High pressure block switch Good / NG
value.
25 Indication light Good / NG
35 Operation voltage V
36 Operation current A
6.6.1. Refrigerant
The refrigerant is HFC type refrigerant whose ozone destruction coefficient is ZERO. If other refrigerant is
mixed, the property of refrigerant is changed and may cause a problem. The following points should be taken
into account on its handling.
− Refrigerant should be added in liquid state not in gas state. R407C is nonazeotropic refrigerant mixture,
and compositions of boiling point are different. Therefore, if it is added in gas state, refrigerant, easy to
evaporate, is added and refrigerant, hard to evaporate, remains in a refrigerant tank.
− Confirm if the tanks specialised for R407C.
− The tank should be set so that refrigerant can be added in gas state.
− The valves or hose for charge should be specialised for R407C.
pag. 160
SMGB0003 rev.0 - 11/2006
Maintenance
pag. 161
SMGB0003 rev.0 - 11/2006
Maintenance
The refrigerant (R407C) used in this unit is HFC refrigerant and does not cause the destruction of ozone layer in
contrast with CFC or HCFC refrigerant.
However, its global heating coefficient is the same level as HCFC refrigerant, therefore it is important to control the
discharge. Also, it is necessary to collect refrigerant at disposal of device or at arrangement of devices.
Collection of refrigerant, vacuuming and additional insertion of refrigerant at compressor overall check and parts
check are shown in the following.
Handling of R407C alternative refrigerant is described in “Implantation / Service Technical of Devices used HFC
Refrigerant”.
pag. 162
SMGB0003 rev.0 - 11/2006
Maintenance
Structure of Compressor
The structure of compressor used in this series is shown below figures:
1. A screw of half-sealed compressor is composed with male rotors and female rotors which have 5~6
dies.
2. Capacity is controlled by bypassing the refrigerant moving the slide valve(#7), a part of casing, to a
shaft direction by a hydraulic piston(#9).
The standard specification of motor(#4), built-in the casing, is 200W and start-up.
Structure drawing of
40ASP-H, 40ASP-Z:
Nº Name Material
Roller bearing
Motor
Motor casing
Ball bearing
FC250
6
Slide valve
Rod
Piston
D casing FC250
Suction
E cover SM400B
Terminal
Gas strainer
C cover SM400B
pag. 163
SMGB0003 rev.0 - 11/2006
Maintenance
Roller bearing
Motor
Ball bearing
Slide valve
Rod
Piston
D casing FC250
Suction
E cover SM400B
Terminal
Gas strainer
C cover SM400B
Structure drawing of
60ASP-H, 60ASP-Z:
Nº Name Material
Roller bearing
Motor
Ball bearing
Slide valve
Rod
Piston
E cover SM400B
Terminal
Gas strainer
C cover SM400B
pag. 164
SMGB0003 rev.0 - 11/2006
Maintenance
Start-up method
Normally more than 22kW compressor has start-up, partly waiting start-up as well as normal start-up
due to its high start-up current.
All Hitachi self-sealed screw compressors of rated output more than 22kW adapt - start-up system
due to its high performance from the view of start-up current.
Like shown in the figure 9/18, at start-up, coil of the stator is connected as a star ( ), and 1/root3 of power
voltage is added to each phase. When motor is accelerated and compressor starts to run normally, the
connection is changed to a delta ( ) to add the power voltage to all phase fully.
Start-up method:
Line voltage=1
6
At start-up ( connection) At operation ( connection)
1. The connection of U~X, V~Y and W~Z is a motor, which is inside of screw compressor.
2. At start ( ) connection 52C, 6C:ON 42C:OFF
3. At operation ( ) connection 52C, 42C:ON 6C:OFF
Real Wiring:
Wiring
pag. 165
SMGB0003 rev.0 - 11/2006
Maintenance
Option
Gauge
manifold
Charging Evacuation
Chilled Water Outlet
Unit side
Flange Connection
Flare Connection
Solder Connection
Refrigerant Cycle
NOTE:
R407C shall be charged by LIQUID.
pag. 166
SMGB0003 rev.0 - 11/2006
Maintenance
Option
Gauge
manifold
6
Option
Option Option
Charging Evacuation
Chilled Water Outlet
NOTE:
R407C shall be charged by LIQUID.
pag. 167
SMGB0003 rev.0 - 11/2006
Maintenance
Gauge
manifold
Option
Option
Option Option
Charging Evacuation
Chilled Water Outlet Flange Connection
Flare Connection
Solder Connection
Unit side
Refrigerant Cycle
NOTE:
R407C shall be charged by LIQUID
pag. 168
SMGB0003 rev.0 - 11/2006
Maintenance
Gauge
manifold
Option
Option
Option
6
Chilled Water Inlet
Charging Evacuation
Chilled Water Outlet
Flange Connection
Unit side Flare Connection
Solder Connection
Refrigerant Cycle
NOTE:
R407C shall be charged by LIQUID
pag. 169
SMGB0003 rev.0 - 11/2006
Maintenance
6.10.Vacuuming Procedure
Although refrigerant is collected to airside heat exchanger by the above collection operation,
it is necessary to be vacuumed due to that refrigerant cycle of low pressure side pipe and of
water side heat exchanger are open.
Vacuum should be performed in the following 2 positions.
− Stop valve for refrigerant insertion ((D) part)
− Check joint of compressor suction side ((E) part)
*Capillary for compound gauge in low pressure side is installed in check joint. This
capillary should be removed from check joint.
Vacuuming procedure is shown in the following.
6.10.1. Vacuuming
− Manifold valve, vacuuming pump and vacuuming gauge for R407C are connected.
− Operate vacuuming pump for at least 1~2 hours until vacuum grade be below
–755mmHg (5Torr).
CAUTION
If vacuum grade
is not decreased
to –755mmHg in
Connect to (D)
1 hour, confirm (E) parts
if there is no
leakage or if water
(Refrigerant
is not in the pipes,
tank for R407C)
and then keep
vacuuming other
1 hour. Vacuuming pump
(prevention of adverse
current)
Vacuum Leave
− Confirmation of vacuum
Vacuum gauge should be used to measure a target vacuum, however, it is
impossible to read the vacuum gauge installed in the manifold very accurately.
It is recommended to use a digital vacuum measure device, available in the
market.
pag. 170
SMGB0003 rev.0 - 11/2006
Maintenance
− Water evaporation>
In atmosphere pressure, water boils at 100°C, however, each time a pressure in
pipes reaches to a vacuum state, water boils at lower temperature than 100°C.
The lower this temperature is, the more water evaporates and vacuum drying is
kept.
6.10.2. Leave
CAUTION
1. This process should be performed since air can be leaked due to the
negative pressure although air leakage is not confirmed in air tight test.
2. In case of increasing pressure, it is possible that there is a slight
leakage in some positions. Perform air tight test again, and perform
vacuum drying again after repaired.
pag. 171
SMGB0003 rev.0 - 11/2006
Maintenance
According to the refrigerant characteristics, the followings should be taken into account.
Painting color:
R407C: Brown
2. The refrigerant tank has two specifications as shown in the below. In any case,
liquid refrigerant should be added.
Siphon pipe
Do not add refrigerant while being stand It is possible to add refrigerant while being stand
pag. 172
SMGB0003 rev.0 - 11/2006
Maintenance
Measurement device for R407C is not compatible with that for R22 due to the following reasons, therefore,
do not divert them. These devices should be controlled separately to avoid being mixed.
Manifold valve
6
−
NOTE:
The specification of connection screw is different from measurement device for R410A.
− R407C, R404A UNF7/16
− R410A UNF1/2
Refrigerant tank
(with siphon pipe)
Specialized for R407C
Connect
to (C) (D)
parts
Brown
pag. 173
SMGB0003 rev.0 - 11/2006
Maintenance
1. After vacuuming, additional refrigerant should be inserted in liquid state with stop
valve of liquid side and gas side close. (Confirm the volume by the balance)
In principal, collected refrigerant from water side heat exchanger to outside of
CAUTION refrigeration cycle by collection device is measured to determine the volume. If
Do NOT add
it is impossible to measure it, use the following figure to determine the volume,
refrigerant in gas confirming the balance pressure after collection operation.
state from suction
side of compressor 2. If it is impossible to add regulated volume due to the lower ambient temperature,
(gas side stop valve). compressor is operated in cooling mode and liquid refrigerant should be added from
stop valve for refrigerant insertion (C). Then, regulated volume is added with the
liquid side stop valve (high pressure side) open a little bit.
Alarm:
Check for refrigerant leakage should be performed steadily. The refrigerant used
in this unit is incombustible, non-toxic and odourless safe one. However, toxic gas
is produced when leaked refrigerant is exposed to fire. And oxygen will be lacked
due to that refrigerant, its gravity is higher than air, is spread in the floor.
CAUTION
Refrigerant should
be added in a
suitable volume
since excess or
less insertion cause
Additional refrigerant insertion volume per 1 cycle (kg)
alarm or accident of
compressor.
pag. 174
SMGB0003 rev.0 - 11/2006
Maintenance
Electrical expansion valve is used in this product, and its opening is almost
closed (10 pulse) at compressor stop. Therefore, when removing the welding of
expansion valve, it is important not to remain the refrigerant between liquid outlet
valve of air side heat exchange (A) and expansion valve.
To compressor
CAUTION
Ex. Valve
There will be a clearance
between control value
and actual value of
expansion valve opening,
therefore, zero point
adjustment (re-input of
power source) should be
realized.
This operation makes expansion valve open in spite of compressor stop by low pressure
setting.
Compressor is started up
Operate chiller unit and when starting unload is Close outlet valve of air side
Remove the coil of ex. valve
finished heat exchanger
pag. 175
SMGB0003 rev.0 - 11/2006
HITACHI participa en el programa de certificación EUROVENT.
Los productos cumplen con las especificaciones del directorio
de productos certificados por EUROVENT.