7SR45 Hardware Manual en-US
7SR45 Hardware Manual en-US
7SR45 Hardware Manual en-US
Table of Contents
Reyrolle Introduction 1
7SR45 Hardware Device Modules and Terminal Details 2
V03.00 Working with the Device 3
Technical Data 4
Manual Appendix A
Index
C53000-T7040-C101-3
NOTE
i For your own safety, observe the warnings and safety instructions contained in this document, if available.
Target Audience
This manual is mainly intended for protection system engineers, commissioning engineers, persons entrusted
with the setting, testing and maintenance of automation, selective protection and control equipment, and
operational crew in electrical installations and power plants.
Scope
This manual applies to the Reyrolle 7SR5 device family.
Further Documentation
[dw_7SR45_furtherdocumentation_hardwaremanual, 1, en_US]
• Device manual
The device manual describes the functions and applications of the Reyrolle 7SR45 device. The printed
manual for the device has the same informational structure.
• Hardware manual
The hardware manual describes the hardware building blocks and device combinations of the Reyrolle
7SR45 device family.
• Operating manual
The operating manual describes the basic principles and procedures for operating and installing the
devices of the Reyrolle 7SR45 range.
• Security manual
The security manual describes the security features of the Reyrolle 7SR45 devices and Reydisp Manager 2.
• Engineering Guide
The engineering guide describes the essential steps when engineering with Reydisp Evolution. In addi-
tion, the engineering guide shows you how to load a planned configuration to a Reyrolle Hardware
device and update the functionality of the Reyrolle Hardware device.
Indication of Conformity
This product complies with the directive of the Council of the European Communities
on the harmonization of the laws of the Member States relating to electromagnetic
compatibility (EMC Directive 2014/30/EU) and concerning electrical equipment for use
within specified voltage limits (Low Voltage Directive 2014/35/EU) as well as restriction
on usage of hazardous substances in electrical and electronic equipment (RoHS Direc-
tive 2011/65/EU).
This conformity has been proved by tests conducted by Siemens AG in accordance of
the Council Directive in accordance with the product standard IEC/EN 60255-26 for the
EMC directives, and with the standard IEC/EN 60255-27 for the low-voltage directive.
RoHS directive 2011/65/EU is met using the standard IEC/EN 63000.
The device has been designed and produced for industrial use.
Standards
IEEE Std C 37.90
The technical data of the product is approved in accordance with UL.
For more information about the UL database, see ul.com
You can find the product with the UL File Number E194016.
Additional Support
For questions about the system, contact your Siemens sales partner.
Training Courses
Inquiries regarding individual training courses should be addressed to our Training Center:
Siemens AG
Siemens Power Academy TD Phone: +49 911 9582 7100
Humboldtstraße 59 E-mail: poweracademy@siemens.com
90459 Nuremberg Internet: www.siemens.com/poweracademy
Germany
Notes on Safety
This document is not a complete index of all safety measures required for operation of the equipment (module
or device). However, it comprises important information that must be followed for personal safety, as well as
to avoid material damage. Information is highlighted and illustrated as follows according to the degree of
danger:
! DANGER
DANGER means that death or severe injury will result if the measures specified are not taken.
² Comply with all instructions, in order to avoid death or severe injuries.
! WARNING
WARNING means that death or severe injury may result if the measures specified are not taken.
² Comply with all instructions, in order to avoid death or severe injuries.
! CAUTION
CAUTION means that medium-severe or slight injuries can occur if the specified measures are not taken.
² Comply with all instructions, in order to avoid moderate or minor injuries.
NOTICE
NOTICE means that property damage can result if the measures specified are not taken.
² Comply with all instructions, in order to avoid property damage.
NOTE
i Important information about the product, product handling or a certain section of the documentation
which must be given attention.
Proper Use
The equipment (device, module) may be used only for such applications as set out in the catalogs and the
technical description, and only in combination with third-party equipment recommended and approved by
Siemens.
Problem-free and safe operation of the product depends on the following:
• Proper transport
• The equipment must be grounded at the grounding terminal before any connections are made.
• All circuit components connected to the power supply may be subject to dangerous voltage.
• Hazardous voltages may be present in equipment even after the supply voltage has been disconnected
(capacitors can still be charged).
• Operation of equipment with exposed current-transformer circuits is prohibited. Before disconnecting the
equipment, ensure that the current-transformer circuits are short-circuited.
• The limiting values stated in the document must not be exceeded. This must also be considered during
testing and commissioning.
OpenSSL
This product includes software developed by the OpenSSL Project for use in OpenSSL Toolkit (http://
www.openssl.org/).
This product includes software written by Tim Hudson (tjh@cryptsoft.com).
This product includes cryptographic software written by Eric Young (eay@cryptsoft.com).
The product contains, among other things, Open Source Software developed by third parties. The Open
Source Software used in the product and the license agreements concerning this software can be found in the
Readme_OSS. These Open Source Software files are protected by copyright. Your compliance with those
license conditions will entitle you to use the Open Source Software as foreseen in the relevant license. In the
event of conflicts between Siemens license conditions and the Open Source Software license conditions, the
Open Source Software conditions shall prevail with respect to the Open Source Software portions of the soft-
ware. The Open Source Software is licensed royalty-free. Insofar as the applicable Open Source Software
License Conditions provide for it you can order the source code of the Open Source Software from your
Siemens sales contact – against payment of the shipping and handling charges – for a period of at least
3 years after purchase of the product. We are liable for the product including the Open Source Software
contained in it pursuant to the license conditions applicable to the product. Any liability for the Open Source
Software beyond the program flow intended for the product is explicitly excluded. Furthermore, any liability
for defects resulting from modifications to the Open Source Software by you or third parties is excluded. We
do not provide any technical support for the product if it has been modified.
The ReadmeOSS documents for the product can be found here: www.siemens.com/reyrolle
Preface.......................................................................................................................................................... 3
1 Introduction................................................................................................................................................13
1.1 Design and Hardware Characteristics.................................................................................14
4 Technical Data............................................................................................................................................ 33
4.1 Analog Inputs................................................................................................................... 34
4.2 Supply Voltage..................................................................................................................35
4.3 Binary Inputs.....................................................................................................................36
4.4 Binary Outputs.................................................................................................................. 37
4.5 Light Emitting Diodes and Data Storage.............................................................................38
4.6 Communication Interfaces................................................................................................ 39
4.7 Mechanical Tests...............................................................................................................40
4.8 Electrical Tests.................................................................................................................. 41
4.9 Environmental Conditions................................................................................................. 43
4.10 Product Safety Test ...........................................................................................................44
4.11 Design Data...................................................................................................................... 45
4.12 Modular-Device Name Plate.............................................................................................. 46
4.13 Display Resolution.............................................................................................................48
A Appendix.................................................................................................................................................... 49
A.1 Revision History................................................................................................................ 50
A.2 Software and Hardware Versions Compatibility..................................................................51
Index...........................................................................................................................................................53
• CT ratings (1 A or 5 A)
• Communication configuration
• Pulse output
[sc_7SR4504, 4, en_US]
Hardware Characteristics
Relay Current Inputs Auxiliary Voltage Binary Inputs Binary Outputs Pulse Output LEDs
7SR4503 4 Self powered 2 2 1 9
or
Dual powered
7SR4504 4 Dual powered 4 4 1 9
• Processor module
• Input module
• Output module
• Rear port communications module (available with 7SR45 dual powered relay)
2.2 Connectors
In the 7SR45 Argus Relay, all the connectors are pluggable except the CT connectors.
The relay consists of the following pluggable connectors and the connector terminals are designated appropri-
ately:
• Pulse output
• Binary inputs
• Binary outputs
• RS485 connector
[le_7SR45_case_dim_rear_view, 2, en_US]
[le_7SR45-case_dim_with_2BI-2BO, 1, --_--]
The earthing cable must be wired using a non-stranded cable with a cross section of 2.5 mm2 or 4 mm2 and
this must be terminated in the shortest possible path to the earthing terminal/busbar in the panel or cubicle.
NOTE
i The earthing point (E) of auxiliary supply is connected to the ground (GND) point of the relay. The earth
connection of the relay case must be solidly connected to the panel earth.
NOTE
i In the CT/VT CONFIG menu, the setting is a multiplication factor applied to the secondary values for
displaying the primary values. The appropriate setting which considers the CT ratio must be done for 5-A
relays.
NOTE
i The auxiliary voltage input is available for the 7SR45 dual power variants only.
The 7SR45 Argus Relay is powered primarily using auxiliary voltage when the relay is ordered with a auxiliary
power supply option even if all other power sources are available. In the absence of auxiliary voltage, the relay
is powered through phase currents.
In the absence of both auxiliary voltage and phase currents, the relay can be powered by USB or battery.
All the protection and measurement algorithms and RS485 communication (Rear port) are active when the
7SR45 Argus Relay is powered by auxiliary voltage.
The following auxiliary voltage inputs are provided on the 7SR45 Argus relay:
• DC 24 V to 60 V
2.7 Battery
The 7SR45 Argus relay has 2 batteries: a main battery CR123A and a coin cell RTC battery CR1632. This section
is applicable to the main battery CR123A, 3 V 1400 mAh Li non-rechargeable battery . The battery is used to
energize the device when auxiliary voltage or phase current or USB are not available. You can perform actions
such as viewing the fault records, setting change, and resetting the flags with battery power.
The relay can be powered on by the battery only if all other power sources are not available.
In the battery mode, the relay can be energized by pressing the BAT ON/OFF key or if any binary input status is
changed.
The battery is used to operate the 7SR45 Argus Relay only when other power sources are not available.
In the battery mode:
• You can edit all the settings even if the protection functions are inactive.
• The pulse output and remote flag output cannot be operated with battery.
• If no keys are pressed for 60 s, then the relay goes in to sleep mode automatically.
By default in the battery mode, if the LCD backlight is off, then the LCD backlight can be turned on by pressing
the backlight key.
Figure 2-6 Terminal Diagram of Self Powered Non-Directional Overcurrent and Earth Fault Relay with Flag
(7SR4503-xGx10-1Ax0)
[dw_7SR450x-xH-J-A20-1AA0_termDia_dual-powered_non-dir_OCP_and_GndFlt_without_Flag, 4, en_US]
Figure 2-7 Terminal Diagram of Dual Powered Non-Directional Overcurrent and Earth Fault Relay without
Flag (7SR4503-x[H/J]A20-1Ax0)
[dw_7SR450x-xHB10-1AA0_termDia_dual-powered_non-dir_OCP_and_GndFlt_with_Flag, 4, en_US]
Figure 2-8 Terminal Diagram of Dual Powered Non-Directional Overcurrent and Earth Fault Relay with
Flag (7SR4504-x[H/J]B20-1Ax0)
! DANGER
DANGER means that death or severe injury will result if the measures specified are not taken.
² Comply with all instructions, in order to avoid death or severe injuries.
! WARNING
WARNING means that death or severe injury may result if the measures specified are not taken.
² Comply with all instructions, in order to avoid death or severe injuries.
! CAUTION
CAUTION means that medium-severe or slight injuries can occur if the specified measures are not taken.
² Comply with all instructions, in order to avoid moderate or minor injuries.
NOTICE
NOTICE means that property damage can result if the measures specified are not taken.
² Comply with all instructions, in order to avoid property damage.
NOTE
i Important information about the product, product handling or a certain section of the documentation
which must be given attention.
Qualified Personnel
Only qualified electrical engineering personnel may commission and operate the equipment (module, device)
described in this document. Qualified electrical engineering personnel in the sense of this manual are people
who can demonstrate technical qualifications as electrical technicians. These persons may commission,
isolate, ground and label devices, systems and circuits according to the standards of safety engineering.
Proper Use
The equipment (device, module) may be used only for such applications as set out in the catalogs and the
technical description, and only in combination with third-party equipment recommended and approved by
Siemens.
Problem-free and safe operation of the product depends on the following:
• Proper transport
When electrical equipment is operated, hazardous voltages are inevitably present in certain parts. If proper
action is not taken, death, severe injury or property damage can result:
• The equipment must be grounded at the grounding terminal before any connections are made.
• All circuit components connected to the power supply may be subject to dangerous voltage.
• Hazardous voltages may be present in equipment even after the supply voltage has been disconnected
(capacitors can still be charged).
• Operation of equipment with exposed current-transformer circuits is prohibited. Before disconnecting the
equipment, ensure that the current-transformer circuits are short-circuited.
• The limiting values stated in the document must not be exceeded. This must also be considered during
testing and commissioning.
RMS
± 5 % (relative) or ± 2 % Irated (absolute)(≥ 0.10 ⋅ Irated to 10
⋅ Irated) – whichever is greater
Frequency 50 Hz (Range: 45 Hz to 55 Hz)
60 Hz (Range: 54 Hz to 66 Hz)
Rated CT burden ≤ 2.5 VA per phase and ≤ 0.2 VA earth for 1 A CT input
(measured at rated currents (1 A and 5 A)) ≤ 2.5 VA per phase and ≤ 0.2 VA earth for 5 A CT input
NOTE
i Refer to Device Manual > Applications > Current Transformer Requirements for the practical CT burden
selection.
Number5 2 or 4
BI threshold/operating range BI voltage rating BI operating range
DC 19 V DC 18 V to 66 V
DC 88 V DC 86 V to 252 V
AC 88 V AC 71 V to 252 V
Maximum AC/DC current for operation 3.5 mA
Pick up delay User-selectable 0 s to 600 s (up to 10 min)
Drop off delay User-selectable 0 s to 600 s (up to 10 min)
Maximum cable length < 10 m
For larger cable length, always use a multi-core screened or twisted-
pair (screened or unscreened) cables
Data Storage
Quantity7 1
Electrical connection RS485, 2 wire electrical, twisted pair
Protocol support Modbus RTU, IEC 60870-5-103
Rate Data transfer rate: 1200 Bit/s to 57 600 Bit/s
Quantity 1
Electrical connection USB, type B
Protocol support7 Modbus RTU, IEC 60870-5-103
Differential mode:
Test voltage: 1.0 kV peak voltage
Test duration: 2 s
Source impedance: 200 Ω
Voltage oscillation frequency: 1 MHz
Repetition frequency: 400 Hz
Electrostatic discharge IEC 60255-26 8 kV air discharge
6 kV contact discharge
Electrical fast transient or IEC 60255-26 Zone B
burst 10 Test severity amplitude: ± 2 kV
Repetition frequency: 5 kHz
Surge immunity11 10 IEC 60255-26 Test level: Zone A
Phase-to-phase: 0.5, 1, 2 kV
Phase-to-earth: 0.5, 1, 2, 4 kV
Front time/time to half-value: 1.2/50 µs
Source impedance: 2 Ω
Radiated immunity IEC 60255-26 Test field strength, frequency band
80 MHz to 1.0 GHz and 1.4 GHz to 2.7 GHz
Field strength: 10 V/m (RMS)
Test using AM: 1 kHz/80 %
Conducted radio frequency IEC 60255-26 150 kHz to 80 MHz
interference 10 10 VRMS, dwell time: 0.5 s
Power frequency magnetic IEC 60255-26 30 A/m applied for 1 min,
field 300 A/m applied for 3 s
Damped oscillatory IEC 61000-4-10 0.1 MHz and 1.0 MHz, 100 A/m
magnetic field value
12 DC binary input ports interfacing with cables whose total length is more than 10 m, must have a multi-core twisted screened cable
for providing immunity against high level of power-frequency interferences.
13 Applicable for the following: 1) Self powered relay with the rated current. 2) Dual powered relay with the rated auxiliary voltage of
DC 110 V and above
14 Permissible temporary operating temperature is not applicabe for UL.
15 To retain the battery life during the transport and storage, Siemens recommends maintaining the permissible temperature range
from -20 °C to +45 °C
Mechanical Specifications
European CE marking
Hardware Version
2438H80001R1a-1a ■
2438H80001R1b-1a ■ ■ ■ ■
2438H80001R1c-1a ■ ■ ■ ■
2438H80001R1d-1a ■ ■ ■ ■
2438H80001R1e-1a ■ ■ ■ ■
2438H80001R1f-1a ■ ■ ■ ■
Hardware Version
2438H80001R2a-1a ■
2438H80001R2b-1b ■ ■
2438H80001R2c-1a ■ ■
2438H80001R2c-1b ■ ■
2438H80001R2e-1a ■ ■
2438H80001R2e-1b ■ ■
2438H80001R2f-1a ■ ■
2438H80001R2f-1b ■ ■ ■ ■
NOTE
i The firmware for the MLFB 7SR450[1/3]-[1/2]GA10-1AA0 is migrated from the R1x series to R2x series from
the HH hardware. The firmware series are not interchangeable and Siemens recommends to follow the
guidelines mentioned in the Table A-1 and Table A-2.
1,2,3 ... N
4U high size 4 non-draw-out case 14 Non-rechargeable battery 26
7SR45 relay configurations 14
P
A
Power supply unit 25
Auxiliary supply 35 Product safety test 44
Auxiliary supply variation 35
Auxiliary voltage inputs 23
R
B Rear port communications 15
Recommended terminal lugs specifications 24
Battery 26
Binary inputs 36
Binary outputs 37
S
Supply voltage 35
C
Connectors 20
Current inputs 22, 34 T
Terminal diagram 27
D
Data storage 38
E
Electrical tests 41
M
Mechanical specifications 45
Mechanical tests 40