7SR45 Hardware Manual en-US

Download as pdf or txt
Download as pdf or txt
You are on page 1of 54

Preface

Open Source Software

Table of Contents

Reyrolle Introduction 1
7SR45 Hardware Device Modules and Terminal Details 2
V03.00 Working with the Device 3
Technical Data 4
Manual Appendix A
Index

C53000-T7040-C101-3
NOTE

i For your own safety, observe the warnings and safety instructions contained in this document, if available.

Disclaimer of Liability Copyright


Subject to changes and errors. The information given in Copyright © Siemens 2021. All rights reserved.
this document only contains general descriptions and/or The disclosure, duplication, distribution and editing of this
performance features which may not always specifically document, or utilization and communication of the content
reflect those described, or which may undergo modifica- are not permitted, unless authorized in writing. All rights,
tion in the course of further development of the products. including rights created by patent grant or registration of a
The requested performance features are binding only when utility model or a design, are reserved.
they are expressly agreed upon in the concluded contract.
Document version: C53000-T7040-C101-3.0
Edition: 11.2021
Version of the product described: V03.00
Preface

Purpose of the Manual


This manual describes the hardware of the Reyrolle 7SR5 device family and provides general information on
the product structure, the modules, and technical data.

Target Audience
This manual is mainly intended for protection system engineers, commissioning engineers, persons entrusted
with the setting, testing and maintenance of automation, selective protection and control equipment, and
operational crew in electrical installations and power plants.

Scope
This manual applies to the Reyrolle 7SR5 device family.

Further Documentation

[dw_7SR45_furtherdocumentation_hardwaremanual, 1, en_US]

• Device manual
The device manual describes the functions and applications of the Reyrolle 7SR45 device. The printed
manual for the device has the same informational structure.

• Hardware manual
The hardware manual describes the hardware building blocks and device combinations of the Reyrolle
7SR45 device family.

Reyrolle, 7SR45, Manual 3


C53000-T7040-C101-3, Edition 11.2021
Preface

• Operating manual
The operating manual describes the basic principles and procedures for operating and installing the
devices of the Reyrolle 7SR45 range.

• Communication protocol manual


The communication protocol manual contains a description of the protocols for communication within
the Reyrolle 7SR45 device family and to higher-level network control centers.

• Security manual
The security manual describes the security features of the Reyrolle 7SR45 devices and Reydisp Manager 2.

• Engineering Guide
The engineering guide describes the essential steps when engineering with Reydisp Evolution. In addi-
tion, the engineering guide shows you how to load a planned configuration to a Reyrolle Hardware
device and update the functionality of the Reyrolle Hardware device.

• Reyrolle 7SR45 catalog


The Reyrolle 7SR45 catalog describes the system features and the devices of Reyrolle 7SR45.

• Selection guide for Reyrolle and SIPROTEC


The selection guide offers an overview of the device series of the Siemens protection devices, and a
device selection table.

Indication of Conformity

This product complies with the directive of the Council of the European Communities
on the harmonization of the laws of the Member States relating to electromagnetic
compatibility (EMC Directive 2014/30/EU) and concerning electrical equipment for use
within specified voltage limits (Low Voltage Directive 2014/35/EU) as well as restriction
on usage of hazardous substances in electrical and electronic equipment (RoHS Direc-
tive 2011/65/EU).
This conformity has been proved by tests conducted by Siemens AG in accordance of
the Council Directive in accordance with the product standard IEC/EN 60255-26 for the
EMC directives, and with the standard IEC/EN 60255-27 for the low-voltage directive.
RoHS directive 2011/65/EU is met using the standard IEC/EN 63000.
The device has been designed and produced for industrial use.

Standards
IEEE Std C 37.90
The technical data of the product is approved in accordance with UL.
For more information about the UL database, see ul.com
You can find the product with the UL File Number E194016.

Additional Support
For questions about the system, contact your Siemens sales partner.

Customer Support Center


Our Customer Support Center provides a 24-hour service.
Siemens AG
Smart Infrastructure – Digital Grid Phone: +49 911 2155 4466
Customer Support Center E-mail: energy.automation@siemens.com

4 Reyrolle, 7SR45, Manual


C53000-T7040-C101-3, Edition 11.2021
Preface

Training Courses
Inquiries regarding individual training courses should be addressed to our Training Center:
Siemens AG
Siemens Power Academy TD Phone: +49 911 9582 7100
Humboldtstraße 59 E-mail: poweracademy@siemens.com
90459 Nuremberg Internet: www.siemens.com/poweracademy
Germany

Notes on Safety
This document is not a complete index of all safety measures required for operation of the equipment (module
or device). However, it comprises important information that must be followed for personal safety, as well as
to avoid material damage. Information is highlighted and illustrated as follows according to the degree of
danger:

! DANGER
DANGER means that death or severe injury will result if the measures specified are not taken.
² Comply with all instructions, in order to avoid death or severe injuries.

! WARNING
WARNING means that death or severe injury may result if the measures specified are not taken.
² Comply with all instructions, in order to avoid death or severe injuries.

! CAUTION
CAUTION means that medium-severe or slight injuries can occur if the specified measures are not taken.
² Comply with all instructions, in order to avoid moderate or minor injuries.

NOTICE
NOTICE means that property damage can result if the measures specified are not taken.
² Comply with all instructions, in order to avoid property damage.

NOTE

i Important information about the product, product handling or a certain section of the documentation
which must be given attention.

Qualified Electrical Engineering Personnel


Only qualified electrical engineering personnel may commission and operate the equipment (module, device)
described in this document. Qualified electrical engineering personnel in the sense of this document are
people who can demonstrate technical qualifications as electrical technicians. These persons may commission,
isolate, ground and label devices, systems and circuits according to the standards of safety engineering.

Reyrolle, 7SR45, Manual 5


C53000-T7040-C101-3, Edition 11.2021
Preface

Proper Use
The equipment (device, module) may be used only for such applications as set out in the catalogs and the
technical description, and only in combination with third-party equipment recommended and approved by
Siemens.
Problem-free and safe operation of the product depends on the following:

• Proper transport

• Proper storage, setup and installation

• Proper operation and maintenance


When electrical equipment is operated, hazardous voltages are inevitably present in certain parts. If proper
action is not taken, death, severe injury or property damage can result:

• The equipment must be grounded at the grounding terminal before any connections are made.

• All circuit components connected to the power supply may be subject to dangerous voltage.

• Hazardous voltages may be present in equipment even after the supply voltage has been disconnected
(capacitors can still be charged).

• Operation of equipment with exposed current-transformer circuits is prohibited. Before disconnecting the
equipment, ensure that the current-transformer circuits are short-circuited.

• The limiting values stated in the document must not be exceeded. This must also be considered during
testing and commissioning.

Selection of Used Symbols on the Device

Nr. Symbol Description

1 Direct current, IEC 60417, 5031

2 Alternating current, IEC 60417, 5032

3 Direct and alternating current, IEC 60417, 5033

4 Earth (ground) terminal, IEC 60417, 5017

5 Protective conductor terminal, IEC 60417, 5019

6 Caution, risk of electric shock

7 Caution, risk of danger, ISO 7000, 0434

8 Protective Insulation, IEC 60417, 5172, Safety Class II devices

9 Guideline 2002/96/EC for electrical and electronic devices

10 Guideline for the Eurasian Market

11 Mandatory Conformity Mark for Electronics and Electrotechnical Products in Morocco

6 Reyrolle, 7SR45, Manual


C53000-T7040-C101-3, Edition 11.2021
Preface

Nr. Symbol Description

12 South Korea KC Certification for Electrical and Electronic Products

13 UL recognized for Canada and the United States

OpenSSL
This product includes software developed by the OpenSSL Project for use in OpenSSL Toolkit (http://
www.openssl.org/).
This product includes software written by Tim Hudson (tjh@cryptsoft.com).
This product includes cryptographic software written by Eric Young (eay@cryptsoft.com).

Reyrolle, 7SR45, Manual 7


C53000-T7040-C101-3, Edition 11.2021
8 Reyrolle, 7SR45, Manual
C53000-T7040-C101-3, Edition 11.2021
Open Source Software

The product contains, among other things, Open Source Software developed by third parties. The Open
Source Software used in the product and the license agreements concerning this software can be found in the
Readme_OSS. These Open Source Software files are protected by copyright. Your compliance with those
license conditions will entitle you to use the Open Source Software as foreseen in the relevant license. In the
event of conflicts between Siemens license conditions and the Open Source Software license conditions, the
Open Source Software conditions shall prevail with respect to the Open Source Software portions of the soft-
ware. The Open Source Software is licensed royalty-free. Insofar as the applicable Open Source Software
License Conditions provide for it you can order the source code of the Open Source Software from your
Siemens sales contact – against payment of the shipping and handling charges – for a period of at least
3 years after purchase of the product. We are liable for the product including the Open Source Software
contained in it pursuant to the license conditions applicable to the product. Any liability for the Open Source
Software beyond the program flow intended for the product is explicitly excluded. Furthermore, any liability
for defects resulting from modifications to the Open Source Software by you or third parties is excluded. We
do not provide any technical support for the product if it has been modified.
The ReadmeOSS documents for the product can be found here: www.siemens.com/reyrolle

Reyrolle, 7SR45, Manual 9


C53000-T7040-C101-3, Edition 11.2021
10 Reyrolle, 7SR45, Manual
C53000-T7040-C101-3, Edition 11.2021
Table of Contents

Preface.......................................................................................................................................................... 3

Open Source Software..................................................................................................................................9

1 Introduction................................................................................................................................................13
1.1 Design and Hardware Characteristics.................................................................................14

2 Device Modules and Terminal Details........................................................................................................ 17


2.1 Dimension Drawings......................................................................................................... 18
2.2 Connectors ...................................................................................................................... 20
2.3 Current Inputs ..................................................................................................................22
2.4 Auxiliary Voltage Inputs.................................................................................................... 23
2.5 Recommended Terminal Lugs Specifications .....................................................................24
2.6 Power Supply Unit (PSU) ...................................................................................................25
2.7 Battery ............................................................................................................................. 26
2.8 Standard Variants of 7SR45............................................................................................... 27

3 Working with the Device............................................................................................................................ 29


3.1 Safety Information............................................................................................................ 30

4 Technical Data............................................................................................................................................ 33
4.1 Analog Inputs................................................................................................................... 34
4.2 Supply Voltage..................................................................................................................35
4.3 Binary Inputs.....................................................................................................................36
4.4 Binary Outputs.................................................................................................................. 37
4.5 Light Emitting Diodes and Data Storage.............................................................................38
4.6 Communication Interfaces................................................................................................ 39
4.7 Mechanical Tests...............................................................................................................40
4.8 Electrical Tests.................................................................................................................. 41
4.9 Environmental Conditions................................................................................................. 43
4.10 Product Safety Test ...........................................................................................................44
4.11 Design Data...................................................................................................................... 45
4.12 Modular-Device Name Plate.............................................................................................. 46
4.13 Display Resolution.............................................................................................................48

A Appendix.................................................................................................................................................... 49
A.1 Revision History................................................................................................................ 50
A.2 Software and Hardware Versions Compatibility..................................................................51

Index...........................................................................................................................................................53

Reyrolle, 7SR45, Manual 11


C53000-T7040-C101-3, Edition 11.2021
12 Reyrolle, 7SR45, Manual
C53000-T7040-C101-3, Edition 11.2021
1 Introduction

1.1 Design and Hardware Characteristics 14

Reyrolle, 7SR45, Manual 13


C53000-T7040-C101-3, Edition 11.2021
Introduction
1.1 Design and Hardware Characteristics

1.1 Design and Hardware Characteristics


The 7SR45 Argus self powered/dual powered non-directional overcurrent and earth fault relay is developed
using the latest generation of hardware technology and is available in multiple variants depending on the
following:

• CT ratings (1 A or 5 A)

• Auxiliary power supply

• Communication configuration

• Binary inputs (2/4)

• Binary outputs (2/4)

• Pulse output

• Local/remote flag indicator


The 7SR45 Argus is a member of Siemens Reyrolle protection devices Argus product family.
The structure of the 7SR45 Argus relay is based on the compact hardware platform. The 7SR45 Argus relay is
supplied in a 4U high, size 4 non-draw-out case . The rear connection comprises user-friendly pluggable type
terminals for pulse and remote flag output, binary inputs, binary outputs, RS485 communication, and auxiliary
input. The CT terminals are suitable for ring-type lug connection to provide a secure and reliable termination.
The hardware design provides a commonality between the products and components across the range of
relays.

[sc_7SR4504, 4, en_US]

Figure 1-1 7SR4503/7SR4504 Front View and Rear View

Hardware Characteristics

Table 1-1 Summary of 7SR45 Argus relay configurations

Relay Current Inputs Auxiliary Voltage Binary Inputs Binary Outputs Pulse Output LEDs
7SR4503 4 Self powered 2 2 1 9
or
Dual powered
7SR4504 4 Dual powered 4 4 1 9

The 7SR45 Argus Relay is assembled from the following modules:

14 Reyrolle, 7SR45, Manual


C53000-T7040-C101-3, Edition 11.2021
Introduction
1.1 Design and Hardware Characteristics

• Front fascia with 5 non-programmable LEDs and 4 user programmable LEDs

• Processor module

• Current analog input

• Input module

• Output module

• Power supply module

• Rear port communications module (available with 7SR45 dual powered relay)

Reyrolle, 7SR45, Manual 15


C53000-T7040-C101-3, Edition 11.2021
16 Reyrolle, 7SR45, Manual
C53000-T7040-C101-3, Edition 11.2021
2 Device Modules and Terminal Details

2.1 Dimension Drawings 18


2.2 Connectors 20
2.3 Current Inputs 22
2.4 Auxiliary Voltage Inputs 23
2.5 Recommended Terminal Lugs Specifications 24
2.6 Power Supply Unit (PSU) 25
2.7 Battery 26
2.8 Standard Variants of 7SR45 27

Reyrolle, 7SR45, Manual 17


C53000-T7040-C101-3, Edition 11.2021
Device Modules and Terminal Details
2.1 Dimension Drawings

2.1 Dimension Drawings

[dw_7SR45 case dimensions front view, 6, en_US]

Figure 2-1 Front View

[dw_7SR45 case dimensions side view, 7, en_US]

Figure 2-2 Side View

18 Reyrolle, 7SR45, Manual


C53000-T7040-C101-3, Edition 11.2021
Device Modules and Terminal Details
2.1 Dimension Drawings

[dw_7SR45 case dimensions panel cut out view, 5, en_US]

Figure 2-3 Panel Cut-out View

Reyrolle, 7SR45, Manual 19


C53000-T7040-C101-3, Edition 11.2021
Device Modules and Terminal Details
2.2 Connectors

2.2 Connectors
In the 7SR45 Argus Relay, all the connectors are pluggable except the CT connectors.
The relay consists of the following pluggable connectors and the connector terminals are designated appropri-
ately:

• Auxiliary power supply

• Remote flag output

• Pulse output

• Binary inputs

• Binary outputs

• RS485 connector

Connectors for Self and Dual Powered Relay Variant


The power supply module is equipped with 2 additional numbers of binary input and binary outputs. It also
consists of a RS485 communication port at the rear side.

[le_7SR45_case_dim_rear_view, 2, en_US]

Figure 2-4 7SR45 Argus Relay Connectors with 4 BI and 4 BO

(1) Current inputs


(2) Additional binary inputs
(3) Additional binary outputs
(4) Rear communication port
(5) Binary inputs/binary outputs/remote flag output/pulse output
(6) Auxiliary power supply
(7) IP20 Cover for current terminals

20 Reyrolle, 7SR45, Manual


C53000-T7040-C101-3, Edition 11.2021
Device Modules and Terminal Details
2.2 Connectors

[le_7SR45-case_dim_with_2BI-2BO, 1, --_--]

Figure 2-5 7SR45 Argus Relay Connectors with 2 BI and 2 BO

(1) Current inputs


(2) Binary inputs/binary outputs/remote flag output/pulse output

The earthing cable must be wired using a non-stranded cable with a cross section of 2.5 mm2 or 4 mm2 and
this must be terminated in the shortest possible path to the earthing terminal/busbar in the panel or cubicle.

NOTE

i The earthing point (E) of auxiliary supply is connected to the ground (GND) point of the relay. The earth
connection of the relay case must be solidly connected to the panel earth.

Reyrolle, 7SR45, Manual 21


C53000-T7040-C101-3, Edition 11.2021
Device Modules and Terminal Details
2.3 Current Inputs

2.3 Current Inputs


The 7SR45 Argus Relay provides 4 current inputs. 3 current inputs are provided for measuring the phase
currents and 1 current input is provided for measuring the earth current.
Based on the ordering option, current inputs are available for 1 A and 5 A variants.
The 7SR45 Argus relay consists of the following for each phase current input:

• 1 built-in power current transformer (PCT)

• 1 built-in measuring current transformer (MCT)


1 MCT is provided on the earth-current input.
The current is sampled at 800 Hz for both 50 Hz and 60 Hz system frequency. Protection and monitoring func-
tions of the relay use the fundamental frequency component.
The primary CT ratio used for the relay instruments and fault logs can be set in the CT/VT CONFIG menu.

NOTE

i In the CT/VT CONFIG menu, the setting is a multiplication factor applied to the secondary values for
displaying the primary values. The appropriate setting which considers the CT ratio must be done for 5-A
relays.

22 Reyrolle, 7SR45, Manual


C53000-T7040-C101-3, Edition 11.2021
Device Modules and Terminal Details
2.4 Auxiliary Voltage Inputs

2.4 Auxiliary Voltage Inputs

NOTE

i The auxiliary voltage input is available for the 7SR45 dual power variants only.

The 7SR45 Argus Relay is powered primarily using auxiliary voltage when the relay is ordered with a auxiliary
power supply option even if all other power sources are available. In the absence of auxiliary voltage, the relay
is powered through phase currents.
In the absence of both auxiliary voltage and phase currents, the relay can be powered by USB or battery.
All the protection and measurement algorithms and RS485 communication (Rear port) are active when the
7SR45 Argus Relay is powered by auxiliary voltage.
The following auxiliary voltage inputs are provided on the 7SR45 Argus relay:

• DC 24 V to 60 V

• DC 60 V to 240 V/AC 60 V to 240 V

Reyrolle, 7SR45, Manual 23


C53000-T7040-C101-3, Edition 11.2021
Device Modules and Terminal Details
2.5 Recommended Terminal Lugs Specifications

2.5 Recommended Terminal Lugs Specifications


Terminal Lugs Type/Cable Specifications
Current inputs TE connectivity PIDG series insulated tin plated crimp ring terminal
Stud size: M3.5
2.6 mm2 to 6.6 mm2
12 AWG
Required torque: 1.0 Nm
Auxiliary supply Insulated tin plated crimp pin connector
2.6 mm2 to 6.6 mm2
12 AWG to 10 AWG
Required torque: 0.5 Nm to 0.6 Nm
Rear communication port Pin type lug/1.5 mm2 control cable
Required torque: 0.5 Nm to 0.6 Nm
Front communication port USB, type B
Binary input/binary output/pulse Insulated tin plated crimp pin connector
output/flag output 2.6 mm2 to 6.6 mm2
12 AWG to 10 AWG
Required torque: 0.5 Nm to 0.6 Nm
Ground terminal Tin plated crimp ring terminal
Stud size: M3
4 mm2 to 6 mm2
12 AWG to 10 AWG
Yellow
Required torque: 0.5 Nm to 0.6 Nm

24 Reyrolle, 7SR45, Manual


C53000-T7040-C101-3, Edition 11.2021
Device Modules and Terminal Details
2.6 Power Supply Unit (PSU)

2.6 Power Supply Unit (PSU)


The relay is supplied with the following rated power supply ranges:

• AC 60 V to 240 V/DC 60 V to 240 V power supply (BI threshold - AC 88 V/DC 88 V)

• DC 24 V to 60 V power supply (BI threshold - DC 19 V)


The power supply module is equipped with 2 or 4 binary inputs and binary outputs based on the ordering
option. The device with a PSU (dual powered) also provides 1 RS485 communication interface (half duplex) for
communicating with RTUs and parameterization of relays via remote locations.
For AC connections, the auxiliary supply is made with the live connection to positive terminal and neutral
connection to negative for consistency and safety.
If the supply voltage levels are falling below the relay minimum operate level, the relay power automatically
switches over to CT power through CT phase currents.

Reyrolle, 7SR45, Manual 25


C53000-T7040-C101-3, Edition 11.2021
Device Modules and Terminal Details
2.7 Battery

2.7 Battery
The 7SR45 Argus relay has 2 batteries: a main battery CR123A and a coin cell RTC battery CR1632. This section
is applicable to the main battery CR123A, 3 V 1400 mAh Li non-rechargeable battery . The battery is used to
energize the device when auxiliary voltage or phase current or USB are not available. You can perform actions
such as viewing the fault records, setting change, and resetting the flags with battery power.
The relay can be powered on by the battery only if all other power sources are not available.
In the battery mode, the relay can be energized by pressing the BAT ON/OFF key or if any binary input status is
changed.
The battery is used to operate the 7SR45 Argus Relay only when other power sources are not available.
In the battery mode:

• You can edit all the settings even if the protection functions are inactive.

• The binary inputs and binary outputs are operational.

• The local flag indicator reset is possible.

• LED test/reset is possible.

• The pulse output and remote flag output cannot be operated with battery.

• If no keys are pressed for 60 s, then the relay goes in to sleep mode automatically.
By default in the battery mode, if the LCD backlight is off, then the LCD backlight can be turned on by pressing
the backlight key.

26 Reyrolle, 7SR45, Manual


C53000-T7040-C101-3, Edition 11.2021
Device Modules and Terminal Details
2.8 Standard Variants of 7SR45

2.8 Standard Variants of 7SR45


The 7SR45 Argus Relay is housed in a non draw-out 4U size 4 case.
The rear connection comprises user-friendly pluggable type terminals:

• Binary input (BI)

• Binary output (BO)

• Pulse output (PO)

• Fixed terminal current transformer (CT) (non-pluggable)

• Remote flag indicator

• RS485 communication port

• Auxiliary power supply


The CT terminals are suitable for ring-type lug connections and to provide a secure and reliable termination.

7SR4503 Terminal/Wiring Diagram

[lo_7SR4501(03)-xGB10 terminal label/wiring diagram, 6, en_US]

Figure 2-6 Terminal Diagram of Self Powered Non-Directional Overcurrent and Earth Fault Relay with Flag
(7SR4503-xGx10-1Ax0)

Reyrolle, 7SR45, Manual 27


C53000-T7040-C101-3, Edition 11.2021
Device Modules and Terminal Details
2.8 Standard Variants of 7SR45

[dw_7SR450x-xH-J-A20-1AA0_termDia_dual-powered_non-dir_OCP_and_GndFlt_without_Flag, 4, en_US]

Figure 2-7 Terminal Diagram of Dual Powered Non-Directional Overcurrent and Earth Fault Relay without
Flag (7SR4503-x[H/J]A20-1Ax0)

7SR4504 Terminal/Wiring Diagram

[dw_7SR450x-xHB10-1AA0_termDia_dual-powered_non-dir_OCP_and_GndFlt_with_Flag, 4, en_US]

Figure 2-8 Terminal Diagram of Dual Powered Non-Directional Overcurrent and Earth Fault Relay with
Flag (7SR4504-x[H/J]B20-1Ax0)

28 Reyrolle, 7SR45, Manual


C53000-T7040-C101-3, Edition 11.2021
3 Working with the Device

3.1 Safety Information 30

Reyrolle, 7SR45, Manual 29


C53000-T7040-C101-3, Edition 11.2021
Working with the Device
3.1 Safety Information

3.1 Safety Information


This document is not a complete index of all safety measures required for operation of the equipment (module
or device). However, it comprises important information that must be followed for personal safety, as well as
to avoid material damage. Information is highlighted and illustrated as follows according to the degree of
danger:

! DANGER
DANGER means that death or severe injury will result if the measures specified are not taken.
² Comply with all instructions, in order to avoid death or severe injuries.

! WARNING
WARNING means that death or severe injury may result if the measures specified are not taken.
² Comply with all instructions, in order to avoid death or severe injuries.

! CAUTION
CAUTION means that medium-severe or slight injuries can occur if the specified measures are not taken.
² Comply with all instructions, in order to avoid moderate or minor injuries.

NOTICE
NOTICE means that property damage can result if the measures specified are not taken.
² Comply with all instructions, in order to avoid property damage.

NOTE

i Important information about the product, product handling or a certain section of the documentation
which must be given attention.

Qualified Personnel
Only qualified electrical engineering personnel may commission and operate the equipment (module, device)
described in this document. Qualified electrical engineering personnel in the sense of this manual are people
who can demonstrate technical qualifications as electrical technicians. These persons may commission,
isolate, ground and label devices, systems and circuits according to the standards of safety engineering.
Proper Use
The equipment (device, module) may be used only for such applications as set out in the catalogs and the
technical description, and only in combination with third-party equipment recommended and approved by
Siemens.
Problem-free and safe operation of the product depends on the following:

• Proper transport

• Proper storage, setup and installation

• Proper operation and maintenance

30 Reyrolle, 7SR45, Manual


C53000-T7040-C101-3, Edition 11.2021
Working with the Device
3.1 Safety Information

When electrical equipment is operated, hazardous voltages are inevitably present in certain parts. If proper
action is not taken, death, severe injury or property damage can result:

• The equipment must be grounded at the grounding terminal before any connections are made.

• All circuit components connected to the power supply may be subject to dangerous voltage.

• Hazardous voltages may be present in equipment even after the supply voltage has been disconnected
(capacitors can still be charged).

• Operation of equipment with exposed current-transformer circuits is prohibited. Before disconnecting the
equipment, ensure that the current-transformer circuits are short-circuited.

• The limiting values stated in the document must not be exceeded. This must also be considered during
testing and commissioning.

Reyrolle, 7SR45, Manual 31


C53000-T7040-C101-3, Edition 11.2021
32 Reyrolle, 7SR45, Manual
C53000-T7040-C101-3, Edition 11.2021
4 Technical Data

4.1 Analog Inputs 34


4.2 Supply Voltage 35
4.3 Binary Inputs 36
4.4 Binary Outputs 37
4.5 Light Emitting Diodes and Data Storage 38
4.6 Communication Interfaces 39
4.7 Mechanical Tests 40
4.8 Electrical Tests 41
4.9 Environmental Conditions 43
4.10 Product Safety Test 44
4.11 Design Data 45
4.12 Modular-Device Name Plate 46
4.13 Display Resolution 48

Reyrolle, 7SR45, Manual 33


C53000-T7040-C101-3, Edition 11.2021
Technical Data
4.1 Analog Inputs

4.1 Analog Inputs


Current Inputs

Quantity 3 x phase and 1 x earth


Rated current Irated 1 1 A or 5 A
Measuring range Phase current: 0.1 ⋅ Irated to 20 ⋅ Irated
Earth current: 0.06 ⋅ Irated to 20 ⋅ Irated
Instrumentation Fundamental
± 5 % (relative) or ± 2 % Irated (absolute)(≥ 0.10 ⋅ Irated to 2 ⋅
Irated) – whichever is greater
± 3 % (> 2 ⋅ Irated to 20 ⋅ Irated)

RMS
± 5 % (relative) or ± 2 % Irated (absolute)(≥ 0.10 ⋅ Irated to 10
⋅ Irated) – whichever is greater
Frequency 50 Hz (Range: 45 Hz to 55 Hz)
60 Hz (Range: 54 Hz to 66 Hz)
Rated CT burden ≤ 2.5 VA per phase and ≤ 0.2 VA earth for 1 A CT input
(measured at rated currents (1 A and 5 A)) ≤ 2.5 VA per phase and ≤ 0.2 VA earth for 5 A CT input

NOTE

i Refer to Device Manual > Applications > Current Transformer Requirements for the practical CT burden
selection.

1 Depending on the ordering option

34 Reyrolle, 7SR45, Manual


C53000-T7040-C101-3, Edition 11.2021
Technical Data
4.2 Supply Voltage

4.2 Supply Voltage


Auxiliary Supply

Rated voltage2 AC 60 V to 240 V/DC 60 V to 240 V


Tolerance: -20 % to +10 %
DC 24 V to DC 60 V
Tolerance: -20 % to +10 %
Frequency 50 Hz (Range: 45 Hz to 55 Hz)
60 Hz (Range: 54 Hz to 66 Hz)
Allowable alternating component in DC (Ripple) 15 % of DC voltage
Typical power consumption (DC) <7W
Typical power consumption (AC) < 13 VA
Max interruption time (collapse to 0) ≤ 20 ms (DC 19.2 V)
≤ 20 ms (DC 48 V)
≤ 500 ms (AC 230 V)

Auxiliary Supply Variation (AC/DC 60 V to 240 V Variant)

Type Test Reference Parameters Declared Operation


AC voltage dips IEC 60255-26 0 % RV for 25 cycles @ 50 Hz Normal operation3
RV = AC 230 V 0 % RV for 25 cycles @ 60 Hz
40 % RV for 10 cycles @ 50 Hz Normal operation3
40 % RV for 12 cycles @ 60 Hz
70 % RV for 25 cycles @ 50 Hz Normal operation3
70 % RV for 30 cycles @ 60 Hz
DC voltage dips IEC 60255-26 0 % RV for 0.02 s Normal operation3
RV = DC 110 V 40 % RV for 0.2 s Normal operation4
70 % RV for 0.5 s Normal operation4
DC voltage dips IEC 60255-26 0 % RV for 0.02 s Normal operation3
RV = DC 48 V 40 % RV for 0.2 s Normal operation4
70 % RV for 0.5 s Normal operation4
Gradual shutdown/Start- IEC 60255-26 Shutdown ramp 60 s Normal operation4
up test Power off 5 min
Startup ramp 60 s
Voltage interruption IEC 60255-26 0 % RV at 5 s Normal operation4
(AC/DC auxiliary supply)
RV = DC 48 V/220 V
RV = AC 230 V
Alternating component in IEC 60255-26 15 % of DC voltage Normal operation3
DC (Ripple)
DC power supply

2 Depending on the ordering option


3 No effect on relay performance.
4 Restart with no mal-operation, loss of data or relay damage. RV = Residual Voltage.

Reyrolle, 7SR45, Manual 35


C53000-T7040-C101-3, Edition 11.2021
Technical Data
4.3 Binary Inputs

4.3 Binary Inputs

Number5 2 or 4
BI threshold/operating range BI voltage rating BI operating range
DC 19 V DC 18 V to 66 V
DC 88 V DC 86 V to 252 V
AC 88 V AC 71 V to 252 V
Maximum AC/DC current for operation 3.5 mA
Pick up delay User-selectable 0 s to 600 s (up to 10 min)
Drop off delay User-selectable 0 s to 600 s (up to 10 min)
Maximum cable length < 10 m
For larger cable length, always use a multi-core screened or twisted-
pair (screened or unscreened) cables

5 Depending on the ordering option

36 Reyrolle, 7SR45, Manual


C53000-T7040-C101-3, Edition 11.2021
Technical Data
4.4 Binary Outputs

4.4 Binary Outputs

Number6 2 (1 make contact and 1 changeover contact) or


4 (2 make contact and 2 changeover contact)
Operating voltage Potential-free
Operating mode User selectable
BO 1 and BO 2 self or hand/electrical reset
BO 3 and BO 4 self reset (operated only when auxiliary input is
present)
Operating time from energizing binary < 20 ms
input
Disengaging time < 20 ms
BO 1 and BO 2 Output Contact Details
Switching voltage AC 250 V and DC 125 V
Contact current rating:
Continuous AC 5 A/DC 5 A
Short time AC 20 A/DC 20 A for 0.5 s
AC 30 A/DC 30 A for 0.2 s
Limiting making capacity: 1000 W
(L/R ≤ 40 ms)
Limiting Breaking Capacity:
AC resistive 1250 VA V/I = 250/5
AC inductive 250 VA V/I = 250/1 @ PF ≤ 0.4
DC resistive 75 W V/I = 48/1.5; 110/0.7
DC inductive (L/R ≤ 40 ms) 30 W V/I = 48/0.7; 110/0.3
Mechanical/electrical endurance 10 000 operations
BO 3 and BO 4 Output Contact Details
Switching voltage AC 250 V/DC 250 V
Contact current rating:
Continuous AC 5 A/DC 5 A
Short time AC 20 A/DC 20 A for 0.5 s
AC 30 A/DC 30 A for 0.2 s
Limiting making capacity: 1000 W
(L/R ≤ 40 ms)
Limiting Breaking Capacity:
AC resistive 1250 VA V/I = 250/5
AC inductive 250 VA V/I = 250/1@ PF≤ 0.4
DC resistive 75 W V/I = 48/1.5; 110/0.7; 220/0.3
DC inductive (L/R ≤ 40 ms) 30 W V/I = 48/0.7; 110/0.3; 220/0.14
Mechanical/electrical endurance 10 000 operations

6 Depending on the ordering option

Reyrolle, 7SR45, Manual 37


C53000-T7040-C101-3, Edition 11.2021
Technical Data
4.5 Light Emitting Diodes and Data Storage

4.5 Light Emitting Diodes and Data Storage


Base Module

Status Color Quantity


Protection Healthy Green 1
Trip Red 1
Pickup Amber 1
Programmable LEDs: Protection function Red 4
and miscellaneous function
Trip Ready Green 1
Low Battery Amber 1

Data Storage

Fault record (trip log) 10 records


Events (event log) 100 events (1 ms resolution)

38 Reyrolle, 7SR45, Manual


C53000-T7040-C101-3, Edition 11.2021
Technical Data
4.6 Communication Interfaces

4.6 Communication Interfaces


Rear Communication Port

Quantity7 1
Electrical connection RS485, 2 wire electrical, twisted pair
Protocol support Modbus RTU, IEC 60870-5-103
Rate Data transfer rate: 1200 Bit/s to 57 600 Bit/s

Front Communication Port

Quantity 1
Electrical connection USB, type B
Protocol support7 Modbus RTU, IEC 60870-5-103

7 Depending on the ordering option

Reyrolle, 7SR45, Manual 39


C53000-T7040-C101-3, Edition 11.2021
Technical Data
4.7 Mechanical Tests

4.7 Mechanical Tests


Type Test Reference Requirement
Degree of protection IEC 60529 IP 52 front
IP 54 front with cover
IP 10 (rear side without cover for current terminal)
IP 20 (rear side with cover for current terminal)
Vibration IEC 60255-21-1 • Vibration endurance, class I, peak acceleration
1 gn X-axis, Y-axis, Z-axis (20 sweeps/axis)

• Vibration response, class I, peak acceleration


0.5 gn X-axis, Y-axis, Z-axis (1 sweeps/axis)
Frequency range: 10 Hz to 150 Hz
Sweep rate: 1 octave/min
Shock and bump IEC 60255-21-2 • Shock response, class I, peak acceleration 5 gn
X-axis, Y-axis, Z-axis (3 per direction)
Total number of shocks: 18
• Shock withstand, class I, peak acceleration
15 gn X-axis, Y-axis, Z-axis (3 per direction)
Total number of shocks: 18
• Bump, class I, peak acceleration 10 gn X-axis,
Y-axis, Z-axis (1000 per direction)
Total number of bumps: 6000
Seismic IEC 60255-21-3 • In single axis sine sweep in X-axis, class I, peak
acceleration 1 gn
• In single axis sine sweep in Y-axis, class I, peak
acceleration 0.5 gn
Frequency range: 1 Hz to 35 Hz
Sweep rate: 1 octave/min
Contact performance IEC 60255-1 Making capacity
(Ref: Std IEC 61810-1) Carry continuously
Make and carry
Breaking capacity
Electrical endurance: 10 000 operations

40 Reyrolle, 7SR45, Manual


C53000-T7040-C101-3, Edition 11.2021
Technical Data
4.8 Electrical Tests

4.8 Electrical Tests


Type Test Reference Requirement
Insulation resistance IEC 60255-278, Insulation resistance >100 MΩ at DC 500 V
Edition 2.0 Test duration: > 5 s
(Between any terminal and earth, independent
circuits)9
Impulse voltage withstand IEC 60255-27 8, 5 kV, 1.2/50 µs, 0.5 J
Edition 2.0 5 positive, negative pulses
(Between all terminals and case earth and any 2 inde-
pendent circuits)9
AC dielectric voltage IEC 60255-27 8 All case terminals connected together AC 2 kV RMS, 1
Edition 2.0 min
(Between terminals of independent circuits) 9
AC 1 kV RMS, 1 min
(across normally open contacts)
Slow damped oscillatory IEC 60255-26 Common mode:
wave 10
Test voltage: 2.5 kV peak voltage

Differential mode:
Test voltage: 1.0 kV peak voltage
Test duration: 2 s
Source impedance: 200 Ω
Voltage oscillation frequency: 1 MHz
Repetition frequency: 400 Hz
Electrostatic discharge IEC 60255-26 8 kV air discharge
6 kV contact discharge
Electrical fast transient or IEC 60255-26 Zone B
burst 10 Test severity amplitude: ± 2 kV
Repetition frequency: 5 kHz
Surge immunity11 10 IEC 60255-26 Test level: Zone A
Phase-to-phase: 0.5, 1, 2 kV
Phase-to-earth: 0.5, 1, 2, 4 kV
Front time/time to half-value: 1.2/50 µs
Source impedance: 2 Ω
Radiated immunity IEC 60255-26 Test field strength, frequency band
80 MHz to 1.0 GHz and 1.4 GHz to 2.7 GHz
Field strength: 10 V/m (RMS)
Test using AM: 1 kHz/80 %
Conducted radio frequency IEC 60255-26 150 kHz to 80 MHz
interference 10 10 VRMS, dwell time: 0.5 s
Power frequency magnetic IEC 60255-26 30 A/m applied for 1 min,
field 300 A/m applied for 3 s
Damped oscillatory IEC 61000-4-10 0.1 MHz and 1.0 MHz, 100 A/m
magnetic field value

8 All aspects of IEC 60255-5 are covered under IEC 60255-27.


9 Flag output and pulse output are excluded between any terminals and ground.
10 Not applicable for flag output and pulse output.
11 Additional 50 ms DTL pickup delay applied to binary inputs

Reyrolle, 7SR45, Manual 41


C53000-T7040-C101-3, Edition 11.2021
Technical Data
4.8 Electrical Tests

Type Test Reference Requirement


Radiated emissions IEC 60255-26 30 MHz to 230 MHz, 40 dB µ V/m (quasi peak)
230 MHz to 1 GHz, 47 dB µ V/m (quasi peak)
Limits are measured at 10 m distance
Conducted emissions IEC 60255-26 0.15 MHz to 0.5 66 dB (µV) (average)
MHz 79 dB (µV) (quasi peak)
0.5 MHz to 30 60 dB (µV) (average)
MHz 73 dB (µV) (quasi peak)
Thermal withstand IEC 60255-27 8 Continuous withstand: 2 ⋅ In
Edition 2.0 Short-time withstand:
Test duration 1 s
50 A (1 A current input)
150 A (5 A current input)
Functional performance IEC 60255-1 and For both 1 A relay and 5 A relay
IEC 60255-151
Maximum allowable IEC 60255-6 Max. temperature limit +100 °C
temperature
Gradual shutdown/Start-up IEC 60255-26 Shut down/start up ramp 60 s
test Power off 5 min
Power frequency immunity IEC 60255-26 Common-mode test parameters:
test 12
Test voltage: 300 V
Coupling resistor: 220 Ω
Coupling resistor: 0.47 μF
Fast transient burst IEEE Std C37.90.1 Peak voltage level: 2 kV
(Common mode and differ- Rise time: 5 ns
ential mode test) Impulse duration: 50 ns
Repetition rate during the burst: 5 kHz
Burst duration: 15 ms
Burst period: 300 ms
Output impedance: 50 Ω
Test duration: 1 min on each polarity
Oscillatory waves IEEE Std C37.90.1 Peak voltage level: 2.5 kV
(Common mode and differ- Rise time on the first peak: 75 ns
ential mode test) Repetition rate: 6 to 10 bursts
Oscillation frequency: 1 MHz
Output impedance: 200 Ω
Test duration: 2 s
Waveform envelope decay: between pk5-pk10

12 DC binary input ports interfacing with cables whose total length is more than 10 m, must have a multi-core twisted screened cable
for providing immunity against high level of power-frequency interferences.

42 Reyrolle, 7SR45, Manual


C53000-T7040-C101-3, Edition 11.2021
Technical Data
4.9 Environmental Conditions

4.9 Environmental Conditions


Temperature and Humidity

Type Test Reference Requirement


Ambient operating temperature IEC 60068-2-1, -10 °C to +60 °C
IEC 60068-2-2,
IEC 60255-1
Permissible temporary operating IEC 60068-2-1, -40 °C to +70 °C
temperature IEC 60068-2-2, LCD display operating range: -20 °C to +70 °C
(Tested for 16 h)13 14 IEC 60255-1
Permissible temporary operating IEC 60068-2-1, -20 °C to +70 °C
temperature IEC 60068-2-2,
(Tested for 96 h) IEC 60255-1
Storage temperature IEC 60068-2-1, -25 °C to +70 °C
(Non-operational)15 IEC 60068-2-2,
IEC 60255-1
Dry Cold test operational IEC 60068-2-1, -10 °C, 96 h
(Energized condition) IEC 60255-1
Dry Cold test storage -25 °C, 16 h
(Unenergized condition)
Dry heat test operational IEC 60068-2-2, +60 °C, 96 h
(Energized condition) IEC 60255-1
Dry heat test storage +70 °C, 16 h
(Unenergized condition)
Damp heat test, steady state IEC 60068-2-78, 10 days at 93 ± 3 % RH, +40 °C
IEC 60255-1
Damp heat test, cyclic IEC 60068-2-30, +25 °C to +55 °C, R.H. > 93 % RH (6 cycles)
IEC 60255-1 At lower temperature, 97 %, -2 % to +3 % RH
At upper temperature, 93 %, ± 3 % RH

13 Applicable for the following: 1) Self powered relay with the rated current. 2) Dual powered relay with the rated auxiliary voltage of
DC 110 V and above
14 Permissible temporary operating temperature is not applicabe for UL.
15 To retain the battery life during the transport and storage, Siemens recommends maintaining the permissible temperature range
from -20 °C to +45 °C

Reyrolle, 7SR45, Manual 43


C53000-T7040-C101-3, Edition 11.2021
Technical Data
4.10 Product Safety Test

4.10 Product Safety Test


Type Test Reference Parameters Values
Clearances and IEC/EN 60255-27: Clearances and creepage ≥ 4 mm
creepage distances Edition 2: 2013-10 distances between external
circuits mutual and to the
enclosure
IP rating IEC/EN 60255-27: For unit front side IP 52 (without cover)
Edition 2: 2013-10 IP 54 (with cover)
For unit rear side IP 10
IP 20 (with cover)
Impulse voltage IEC/EN 60255-27: 5 kV, 5 +ve, 5 -ve pulses –
Edition 2: 2013-10
AC dielectric IEC/EN 60255-27: Test voltage (AC): 2 kV After test, the relay must be
voltage Edition 2: 2013-10 Test frequency: 50 Hz operative (Reinforced insula-
tion with communication
Test duration: 1 min
network).
Insulation resis- IEC/EN 60255-27: Test voltage: DC 500 V > 100 MΩ
tance Edition 2: 2013-10 Test duration: > 5 s
Protective bonding IEC/EN 60255-27: Test voltage: AC/DC < 12 V
resistance Edition 2: 2013-10 Test duration: 1 min < 0.1 Ω
Bonding resistance
Protective bonding IEC/EN 60255-27: Accessible conductive parts Low-current continuity test
continuity Edition 2: 2013-10 must be bonded with the
protective conductor terminal
Flammability of IEC/EN 60255-27: Structure part Standard for insulating
insulating mate- Edition 2: 2013-10 material of flammability
rials, components class
and fire enclosures Terminals Class UL 94 V-0
Terminal mounting Class UL 94 V-0
Wiring (CT) (N)2GFAF (VDE)
Components mounting Class UL 94 V-0
Enclosure Class UL 94 V-0
PCB Class UL 94 V-0
LCD Class UL 94 V-0
Single fault condi- IEC/EN 60255-27: Assessment of: The equipment does not
tion Edition 2: 2013-10 present any risk of electric
• Insulation between
shock or fire after a single-
circuits and parts
fault test.
• Compliance with require-
ments for protection
against the spread of fire
• Overloads
• Intermittently rated resis-
tors
• Compliance with require-
ments for mechanical
protection

44 Reyrolle, 7SR45, Manual


C53000-T7040-C101-3, Edition 11.2021
Technical Data
4.11 Design Data

4.11 Design Data


Dimensions and Weights
See appropriate case outline and panel drilling drawing as specified in diagrams and parameters document,
for complete dimensional specifications.
Mounting is front of panel/flush mounting.
Parameter Value
Width Size 4 108 mm
Height 159 mm (7SR4503/7SR4504)
Depth behind panel (including clearance for wiring) 233 mm
Weight Size 4 ~1.97 kg (without front cover)
~2.08 kg (with front cover)

Mechanical Specifications

Design Panel mounting, non draw-out polycarbonate


moulded case
Enclosure IP 52 (front side without cover)
IP 54 (front side with cover)16
IP 40 (enclosure sides)
IP 10 (rear side without cover for current terminal)
IP 20 (rear side with cover for current terminal)

16 Available for 7SR4503/7SR4504 variant only.

Reyrolle, 7SR45, Manual 45


C53000-T7040-C101-3, Edition 11.2021
Technical Data
4.12 Modular-Device Name Plate

4.12 Modular-Device Name Plate


In the following table, the name plate of a modular device is explained as an example. The name plate is
located on the device.

7SR45 Device type


Argus Product group
Irated Rated current
frated Rated frequency
Vaux Auxiliary voltage range
VBI Binary input supply rating
7SR45XXXXXXXX Technical Numbering System (TNS), maximum 18 digits
Serial no: GFYYMMXXXXXX Serial number
GF - Goa Factory
YY - Year of Manufacturing (for example, YY will be 19 for a
device produced in 2019)
MM - Month of Manucaturing (for example, MM will be 08
for a device produced in August)
Insulation test of the voltage inputs, current inputs, and
binary outputs with AC 2.5 kV

5 kV impulse voltage test [type test] in compliance with


Class III

European CE marking

Guidelines for Eurasian Markets

“WEEE" Symbol instructions.


The product should not be disposed with other wastes at the
end of its working life. Please separate the product from
other types of wastes and recycle it responsibly to promote
the sustainable reuse of material resources. This will help
prevent harm to the environment or human health from
uncontrolled waste disposal.

46 Reyrolle, 7SR45, Manual


C53000-T7040-C101-3, Edition 11.2021
Technical Data
4.12 Modular-Device Name Plate

Mandatory Conformity Mark for Electronics and Electrotech-


nical Products in Morocco

South Korea KC Certification for Electrical and Electronic


Products

UL recognized component marks for Canada and United


States

Reyrolle, 7SR45, Manual 47


C53000-T7040-C101-3, Edition 11.2021
Technical Data
4.13 Display Resolution

4.13 Display Resolution


LCD graphic display (Liquid crystal display) small 2 line x 16 character

48 Reyrolle, 7SR45, Manual


C53000-T7040-C101-3, Edition 11.2021
A Appendix

A.1 Revision History 50


A.2 Software and Hardware Versions Compatibility 51

Reyrolle, 7SR45, Manual 49


C53000-T7040-C101-3, Edition 11.2021
Appendix
A.1 Revision History

A.1 Revision History


Software Revision History

2020/09 2438H80001R2f-1b Software maintenance


2020/08 2438H80001R2f-1a • Protection function 51-1 setting range change to 0.1 ⋅ Irated to
2.0 ⋅ Irated

• User-Programmable LED feature added


2020/05 2438H80001R2e-1b Software maintenance
2019/12 2438H80001R2e-1a Thermal overload protection function (49) added
2019/05 2438H80001R2c-1b Software maintenance to suit customer requirements
2018/11 2438H80001R2c-1a Supervision function (81HBL2) added
2018/06 2438H80001R1f-1a Third Release
2018/06 2438H80001R2b-1b Third Release
2018/04 2438H80001R2a-1a Second Release
2017/08 2438H80001R1e-1a Software maintenance to suit customer requirements
2017/01 2438H80001R1d-1a • Protection function 50, 50N, 50G setting range change to
0.2 ⋅ Irated to 20 ⋅ Irated in step of 0.1 ⋅ Irated

• Protection function 50, 50N, 50G reset ratio changed to 90 %


for setting below 1 ⋅ Irated and 94 % for setting above 1 ⋅ Irated
2016/10 2438H80001R1c-1a Software maintenance to suit customer requirements
2016/09 2438H80001R1b-1a • Faster response times on 1 phase (t + 100 ms max) in 0.2 to
0.3 ranges.
• IRF functionality.
2015/08 2438H80001R1a-1a First Release

Hardware Revision History

2021/11 7SR450/HH V1 obsolete and UL certified


2020/09 7SR450/GG Fourth Release (with conformal coating PCBA)
2018/06 7SR450/FF Third Release (with reduced front cover and housing height)
2018/04 7SR450/EE Second Release (with Aux. Power supply, remote flag and local
flag, RS 485, additional AC/DC BIs and BOs)
2017/02 7SR450/DD Hardware maintenance
2016/09 7SR450/CC Circuit changes to improve signal conditioning
2015/08 7SR450/BB First Release

50 Reyrolle, 7SR45, Manual


C53000-T7040-C101-3, Edition 11.2021
Appendix
A.2 Software and Hardware Versions Compatibility

A.2 Software and Hardware Versions Compatibility


Table A-1 Software Compatibility for MLFB Variants 7SR450[1/3]-[1/2]GA10-1AA0

Hardware Version

Software Version 7SR4501/BB 7SR4501/CC 7SR4501/DD 7SR4501/EE 7SR450[1/3]/FF 7SR450[1/3]/GG

2438H80001R1a-1a ■
2438H80001R1b-1a ■ ■ ■ ■
2438H80001R1c-1a ■ ■ ■ ■
2438H80001R1d-1a ■ ■ ■ ■
2438H80001R1e-1a ■ ■ ■ ■
2438H80001R1f-1a ■ ■ ■ ■

Table A-2 Software Compatibility for MLFB Variants: 7SR450[1/2/3/4]-[1/2][H/J][A/B]20-1A[A/B]0,


7SR450[1/2/3/4]-[1/2][H/J][A/B]20-1A[A/B]0

Hardware Version

Software Version 7SR450[1/2]/EE 7SR450[1/2/3/4]/FF 7SR450[1/2/3/4]/GG 7SR450[1/2/3/4]/HH

2438H80001R2a-1a ■
2438H80001R2b-1b ■ ■
2438H80001R2c-1a ■ ■
2438H80001R2c-1b ■ ■
2438H80001R2e-1a ■ ■
2438H80001R2e-1b ■ ■
2438H80001R2f-1a ■ ■
2438H80001R2f-1b ■ ■ ■ ■

NOTE

i The firmware for the MLFB 7SR450[1/3]-[1/2]GA10-1AA0 is migrated from the R1x series to R2x series from
the HH hardware. The firmware series are not interchangeable and Siemens recommends to follow the
guidelines mentioned in the Table A-1 and Table A-2.

Reyrolle, 7SR45, Manual 51


C53000-T7040-C101-3, Edition 11.2021
52 Reyrolle, 7SR45, Manual
C53000-T7040-C101-3, Edition 11.2021
Index

1,2,3 ... N
4U high size 4 non-draw-out case 14 Non-rechargeable battery 26
7SR45 relay configurations 14

P
A
Power supply unit 25
Auxiliary supply 35 Product safety test 44
Auxiliary supply variation 35
Auxiliary voltage inputs 23

R
B Rear port communications 15
Recommended terminal lugs specifications 24
Battery 26
Binary inputs 36
Binary outputs 37
S
Supply voltage 35
C
Connectors 20
Current inputs 22, 34 T
Terminal diagram 27

D
Data storage 38

E
Electrical tests 41

M
Mechanical specifications 45
Mechanical tests 40

Reyrolle, 7SR45, Manual 53


C53000-T7040-C101-3, Edition 11.2021
54 Reyrolle, 7SR45, Manual
C53000-T7040-C101-3, Edition 11.2021