Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

7KM10200BA011DA0 Datasheet en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Data sheet 7KM1020-0BA01-1DA0

SENTRON PAC1020 96X96 mm Power Monitoring Device Panel mount


type for measurement of electr. values Protocol: Modbus RTU With
graphical display Un max: 400/230V 45-65Hz Input current 5A AC Power
Supply 85V - 276V AC Terminal blocks

Model
product brand name SENTRON
product designation multimeter
design of the product basic
product type designation 7KM PAC1020
Measurements
measuring procedure
● for voltage measurement TRMS
● for current measurement TRMS
type of measured value detection complete
voltage curve Sinusoidal or distorted
measurable line frequency
● initial value 45 Hz
● full-scale value 65 Hz
operating mode for measured value detection automatic Yes
line frequency detection
operating mode for measured value detection
● set at 50 Hz No
● set to 60 Hz No
Supply voltage
design of the power supply Wide-range power supply
type of voltage of the supply voltage AC/DC
supply voltage at AC 100 ... 250 V
supply voltage at DC 100 ... 250 V
Degree of protection protection class
protection class IP on the front IP40
operating resource protection class when installed II
Suitability
suitability for operation Installation in stationary panels in closed rooms
Product Functions
product function
● voltage measurement Yes
● current measurement Yes
● active power measurement Yes
● reactive power measurement Yes
● frequency measurement Yes
Display and operation
design of the display LCD
height of the display 56 mm
width of the display 74 mm

7KM10200BA011DA0 Subject to change without notice


4/3/2023
Page 1/6 © Copyright Siemens
color of the background of the display white
illuminance of display backlight adjustable Yes
display contrast adjustable Yes
national language on the display screen is supported sp, en, cn, pt
number of keys 4
Communication
number of interfaces according to Fast Ethernet 1
Fault limits
reference condition for metering accuracy according to IEC62053-21
formula for relative total measurement inaccuracy
● for measured variable voltage 0.50%
● for measured variable current +/- 0,5 %
● for measured variable active power 1%
● for measured variable reactive power 2%
● for measured variable output factor 0.50%
● for measured variable active energy class 1 according to IEC62053-21
● for measured variable reactive energy 2%
Inputs Outputs
number of digital inputs 1
design of the switching input electronic, passive
type of electrical connection at the digital inputs screw-type terminals
operating conditions for digital inputs external voltage Yes
supply
input voltage at digital input at DC maximum 30 V
number of digital outputs 1
type of switching output electronic, passive
digital output version switching or pulse output function
operating voltage as output voltage at DC maximum 30 V
permissible
type of electrical connection at the digital outputs screw-type terminals
output current
● at the digital outputs at DC limited to 100 ms 130 mA
maximum
internal resistance at the digital outputs 55 Ω
standard for pulse emitter according to IEC62053-31
pulse duration
● initial value 500 ms
● full-scale value 30 ms
adjustable time period minimum 10 ms
switching frequency at digital output maximum 17 Hz
property of the output short-circuit proof Yes
Measuring inputs
measurable supply voltage between (PE)N and L at AC 230 V
maximum rated value
measurable supply voltage between (PE)N and L at AC
● minimum 11.5 V
● maximum 280 V
measurable supply voltage between the line conductors at 400 V
AC maximum rated value
voltage measuring range extension with external voltage yes
transformers
line conductors and neutral conductors internal resistance 1.5 MΩ
for voltage measurement
measuring category for voltage measurement CATIII
measurable current
● 1 at AC rated value 1A
● 2 at AC rated value 5A
relative measurable current at AC
● minimum 10 %
● maximum 120 %
current measuring range extension with external current Yes
transformers
zero point suppression for current measurement 0 ... 10 %
measuring category for current measurement CATIII

7KM10200BA011DA0 Subject to change without notice


4/3/2023
Page 2/6 © Copyright Siemens
Connections
type of electrical connection
● at the measurement inputs for voltage screw-type terminals
● at the measurement inputs for current screw-type terminals
Mechanical Design
fastening method standard rail mounting No
size of Power Monitoring Device size 96
height 96 mm
width 96 mm
depth 42 mm
installation depth 42 mm
net weight 240 g
mounting position vertical
Environmental conditions
ambient temperature during operation
● minimum -10 °C
● maximum 55 °C
ambient temperature during storage
● minimum -25 °C
● maximum 70 °C
relative humidity at 25 °C without condensation during 75 %
operation maximum
installation altitude at height above sea level maximum 2 000 m
degree of pollution 2
Certificates
certificate of suitability as EC Declaration of Conformity yes
General Product Approval Declaration of Conformity other

Confirmation Confirmation Miscellaneous

Environment

Environmental Con-
firmations

Further information
Siemens has decided to exit the Russian market (see here).
https://press.siemens.com/global/en/pressrelease/siemens-wind-down-russian-business
Siemens is working on the renewal of the current EAC certificates.
Please contact your local Siemens office on the status of validity of the EAC certification if you intend to import or offer to supply these
products to an EAC relevant market (other than the sanctioned EAEU member states Russia or Belarus).
Information on the packaging
https://support.industry.siemens.com/cs/ww/en/view/109813875
Information- and Downloadcenter (catalogues, leaflets,...)
http://www.siemens.com/energy-automation
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=7KM1020-0BA01-1DA0
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/7KM1020-0BA01-1DA0
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=7KM1020-0BA01-1DA0
CAx-Online-Generator
http://www.siemens.com/cax
Tender specifications
http://www.siemens.com/specifications

7KM10200BA011DA0 Subject to change without notice


4/3/2023
Page 3/6 © Copyright Siemens
95,6 45,4
95,6

DIC

DI0
VN
V1

V2

V3

N
L

-P
+

SIEMENS
k

RS 485
l

DOC
IL1k

IL1l

DO0

Com
IL2k

IL3k
IL2l

IL3l

B
A

7KM10200BA011DA0 Subject to change without notice


4/3/2023
Page 4/6 © Copyright Siemens
-P
Com

RS 485
B

DO0 DI0

DOC DIC

IL3l l - N

IL3k k + L

IL2l l VN

IL2k k V3
SIEMENS
IL1l l V2

IL1k k V1

last modified: 2/8/2023

7KM10200BA011DA0 Subject to change without notice


4/3/2023
Page 5/6 © Copyright Siemens
7KM10200BA011DA0 Subject to change without notice
4/3/2023
Page 6/6 © Copyright Siemens