Vorläufiges Datenblatt
IR125Y-4_D00114_01_D_XXEN/04.2017
ISOMETER® IR125Y-4 Insulation monitoring device for
unearthed AC and DC systems (IT systems)
Product description
The ISOMETER®s of the IR125Y-4 series monitor the insulation resistance of unearthed AC
and DC control circuits (IT systems). The supply voltage is taken from the system to be
monitored.
In contrast to insulation monitoring devices which use the passive voltage asymmetry
principle for insulation fault detection, this series uses the active AMP measuring principle.
This creates the possibility to detect and indicate both symmetrical and asymmetrical
insulation faults.
Application
• AC and DC control and auxiliary circuits in accordance with DIN EN 60204-1,
ISOMETER® IR125Y-4 “Electrical equipment of machines”, IEC 60204-1, EN 60204-1
• DC auxiliary circuits in accordance with DIN VDE 0100-725
Device features • Simple battery systems
• Insulation monitoring for AC and DC
systems (IT systems) Function
• Response values, adjustable 10…200 kΩ When the insulation resistance between the system conductors and earth falls below the
set response value, the alarm relay switches and the alarm LED lights up. The fault mes-
• LEDs: Power On LED, alarm LED to signal sage can be stored. The fault memory can be reset by pressing the reset button. The de-
insulation faults vice function can be tested using the test button.
• Internal combined test and reset button
• Connection external reset button Measurement method
• Alarm relay with one potential-free The IR125Y series uses a variant of the AMP measurement method.
changeover contact
• N/C operation
Standards
• Fault memory behaviour, selectable
The ISOMETER® of the IR125Y-4 series complies with the requirements of the standards:
Aapprovals DIN EN 61557-8 (VDE 0413- 8):1998-05, EN 61557-8:1997-03, IEC 61557-8:1997-02,
ASTM F 1669M-96(2002).
2 IR125Y-4_D00114_01_D_XXEN/04.2017
ISOMETER® IR125Y-4
interference. In this case, the user may be required to take corrective actions.
IR125Y-4_D00114_01_D_XXEN/04.2017 3