ISOMETER® IR125Y-4

Insulation monitoring device for unearthed AC and DC systems


(IT systems)

Vorläufiges Datenblatt

IR125Y-4_D00114_01_D_XXEN/04.2017
ISOMETER® IR125Y-4 Insulation monitoring device for
unearthed AC and DC systems (IT systems)

Product description
The ISOMETER®s of the IR125Y-4 series monitor the insulation resistance of unearthed AC
and DC control circuits (IT systems). The supply voltage is taken from the system to be
monitored.
In contrast to insulation monitoring devices which use the passive voltage asymmetry
principle for insulation fault detection, this series uses the active AMP measuring principle.
This creates the possibility to detect and indicate both symmetrical and asymmetrical
insulation faults.

Application
• AC and DC control and auxiliary circuits in accordance with DIN EN 60204-1,
ISOMETER® IR125Y-4 “Electrical equipment of machines”, IEC 60204-1, EN 60204-1
• DC auxiliary circuits in accordance with DIN VDE 0100-725
Device features • Simple battery systems
• Insulation monitoring for AC and DC
systems (IT systems) Function
• Response values, adjustable 10…200 kΩ When the insulation resistance between the system conductors and earth falls below the
set response value, the alarm relay switches and the alarm LED lights up. The fault mes-
• LEDs: Power On LED, alarm LED to signal sage can be stored. The fault memory can be reset by pressing the reset button. The de-
insulation faults vice function can be tested using the test button.
• Internal combined test and reset button
• Connection external reset button Measurement method
• Alarm relay with one potential-free The IR125Y series uses a variant of the AMP measurement method.
changeover contact
• N/C operation
Standards
• Fault memory behaviour, selectable
The ISOMETER® of the IR125Y-4 series complies with the requirements of the standards:
Aapprovals DIN EN 61557-8 (VDE 0413- 8):1998-05, EN 61557-8:1997-03, IEC 61557-8:1997-02,
ASTM F 1669M-96(2002).

Ordering information Accessories

Nominal system voltage 1) Un


Type Art. No. Type designation Art. No.
AC DC
19.2…265 V 19.2…308 V IR125Y-4 B 9102 3005 Mounting plate B 990 056
1)
Absolute values

Response values/measuring circuits Dimension diagram XM22


Dimensions in mm
System leakage
Type Response value Ran Response time tan
capacitance Ce
IR125Y-4… 10…200 kΩ ≤6s ≤ 10 µF

Measuring current Internal DC resist-


Type Measuring voltage Um
Im ance Ri
IR125Y-4… 13 V ≤ 0.12 mA 112 kΩ

2 IR125Y-4_D00114_01_D_XXEN/04.2017
ISOMETER® IR125Y-4

Wiring diagram – Operating elements Technical Data

L1 Insulation coordination acc. to IEC 60664-1

L2 Rated voltage AC 250 V


Rated impulse voltage/Pollution degree 4 kV/3
Voltage ranges
1 Nominal system voltage Un  DC 19.2 … 308 V, protected against polarity reversal
 AC 19.2 … 265 V
Nominal frequency fn  DC 42…460 Hz
Supply voltage  = Un
Max. power consumption  ≤ 3 VA
Response values
Response value contact  10… 200 kΩ
6 Response time tan at RF = 0,5 x Ran and Ce = 1 μF  ≤6s
Response uncertainty (acc. to IEC 61557-8) +30/- 0 %, at least ±1.5 kΩ
2
Measuring circuit
3 Measuring voltage Um 13 V
7 Measuring current Im max. (RF = 0 Ω) ≤ 120 μA
Internal d.c. resistance Ri  112 kΩ
4 System leakage capacitance  ≤ 10 μF
Switching elements
5 Switching components  1 change-over contact
Operating principle N/C operation
Electrical endurance  12000 cycles
Contact class  IIB (IEC60255-0-20)
8 Rated contact voltage AC 250 V/DC 300 V
Limited making capacity UC 5A
9 Limited breaking capacity 2 A, AC 230 V, cos φ = 0,4
 0.2 A, DC 220 V, L/R = 0.04 s
1 - Supply voltage US (see ordering details) via fuse
Environment/EMC
2 - Power On LED “ON”
EMC immunity acc. to IEC 61326-2-41)
3 - LED “ALARM” EMC emission  acc. to IEC 61326-2-41)
4 - Combined test and reset button “TEST/RESET”, Shock resistance acc.to IEC 60068-2-27 (device in operation)  15 g/11 ms
short-time pressing (< 1 s) = RESET; Bumping acc.to IEC 60068-2-29 (during transport) 40 g/6 ms
long-time pressing(> 1 s) = TEST Vibration resistance acc.to IEC60068-2-6 (device in operation) 1 g/10…150 Hz
Vibration resistance acc.to IEC60068-2-6 (during transport)  2 g/10…150 Hz
5 - Adjustable response value 10…200 kΩ
Ambient temperature (device in operation)  - 10…+55 ºC
6 - “R1/R2” bridged: Fault memory active Ambient temperature (during storage) - 40…+70 ºC
7 - Alarm relay in N/C operation Climatic class according to IEC 60721-3-3 3K5
8 - Alarm Operating mode  Continuous
Mounting any position
9 - No alarm
Connection
Connection screw terminals
rigid/flexible  0.2…4/0.2…2.5 mm2
flexible with ferrules without/with plastic collar  0.25…2.5 mm2
Conductor sizes AWG 24…12
Tightening torque, terminal screws 0.5…0.6 Nm (4.3…5.3 lb-in)
Degree of protection internal components  IP30
Degree of protection terminals  IP20
Enclosure/dimension diagram XM22
Screw fixing with mounting plate  2 x M4
DIN rail mounting acc. to  IEC 60715
Flammability class UL94 V-0
Documentation number D00114
Weight  approx. 130 g
This is a class A product. In a domestic environment, this product may cause radio
1)

interference. In this case, the user may be required to take corrective actions.

IR125Y-4_D00114_01_D_XXEN/04.2017 3
IR125Y-4_D00114_01_D_XXEN / 04.2017 / pdf / © Bender GmbH & Co. KG, Germany – Subject to change! The specified standards take into account the version that was valid at the time of printing.