Design Guidelines Wastewater Networks - Pumping Systems
Design Guidelines Wastewater Networks - Pumping Systems
Design Guidelines Wastewater Networks - Pumping Systems
Strictly Confidential
3. INTRODUCTION ....................................................................................................................................... 6
Department Actions
2. GLOSSARY OF TERMS
Glossary of Terms
Air valve Hydromechanical device designed to automatically release air and wastewater gases o
admit air during the filling, draining or operation of liquid piping systems for wastewater
services.
Allowable maximum Maximum hydrostatic pressure including surge that a component can withstand from tim
operating pressure to time in service.
(PMA)
Electromagnetic Flowmeter which creates a magnetic field perpendicular to the flow, so enabling t
flowmeter flowrate to be deduced from induced electromotive force (emfV) produced by the moti
of a conducting fluid in the magnetic field. The electromagnetic flowmeter consists of
sensor and a transmitter
Explosive atmosphere A mixture of dangerous substances with air, under atmospheric conditions, in the form
gases, vapours, mist or dust in which, after ignition has occurred, combustion spreads
the entire unburned mixture.
Layout Configuration of components of drain and sewer systems in both horizontal and vertic
planes.
Level controller Device used for monitoring and comparing the level of liquid with a set value.
Low voltage Voltage rating of between 50 V and 1 000 V for alternating current and between 75 V
and 1 500 V for direct current.
Pipeline Assembly of pipes, fittings and joints between manholes or other structures.
Pump Mechanical device for moving fluids, including inlet and outlet connections as well as,
general, a shaft end.
Pump unit Assemblage of mechanical devices, including pump and the driver, together w
transmission elements, baseplate and any auxiliary equipment.
Pumping System comprising a pump or pumps, rising mains, vacuum pipelines and
system associated equipment, which together provide the specified service.
Reflux valve Valve which allows fluid to flow in one direction only and which automatically closes wh
flow ceases or reverses.
Rising main A sewer through which foul sewage and/or surface water is pumped.
Transient (surge) eve Surge pressure created in a pipeline which is outside the range of pressures experienc
under steady state hydraulic conditions.
Ultrasonic flowmeter Flowmeter that operates by sending pulses of ultrasound into the water.
Washout valve Valve used for maintenance work of main like allowing flowing out of water during cleani
process.
Wastewater Water composed of any combination of water discharged from domestic, industrial
commercial premises, surface run-off and accidentally any sewer infiltration water
Wet well A chamber in a pumping station, including a submersible pump station, where wastewa
collects until it is pumped out.
3. INTRODUCTION
This asset design standard sets out the standards and guidelines required for design of NEOM pumping
systems.
For the design of wastewater vacuum systems refer to Design Guidelines – Vacuum systems – NEN-
WRC-GGD-208.
If the designer has good reason not to comply with this standard and identifies alternative standards or
guidelines, a change request shall be submitted to the NEOM Wastewater Engineer, with evidence for
change.
The Engineer will approve or reject the request and their decision is final.
4.2 Waivers
NEOM is committed to using new and innovative technologies where they, in NEOM’s opinion, represent
the best technical solution, provide low life cycle costs and value for money. All technologies will be
considered for use by NEOM providing they have been proven in terms of performance, quality, and cost.
NEOM will approve plans for new systems, extensions to new areas or replacement sewers only when
designed upon the separate system, and when they meet the requirements of these guidelines. NEOM
reserve the right not to adopt any system that fails to meet the minimum standards of these guidelines.
If the designer identifies alternative technical solutions to those stated in this standard or recently
developed or innovative products which properties and performance can be determined to align with their
intended duty and design life, a design waiver request shall be submitted to the NEOM Wastewater
Engineer, with evidence for change.
The Engineer will approve or reject the request and their decision is final.
Calculations shall clearly state which standard has been used with a full justification for its use. Further,
this shall be supported by the collection of data and site-specific evidence to validate the proposal. Design
consultants shall also need to refer to International industry guides and codes of practice such as British
Water Code of Practice for Flows & Loads for the guidance of flow rate calculations.
NEOM emphasise that all sewerage design shall be done in accordance with accepted international
Standards. Where deviation from Standards is required it shall be fully justified on a case-by-case basis.
The designer is responsible for ensuring that the design eliminates, reduces, or controls foreseeable risks
to the health and safety of all people during construction and at all other stages of the asset life including
during inspection, cleaning, repair, maintenance, and decommissioning.
Considerations in design to mitigate risks will include but not be limited to:
• The designer shall develop designs that preclude the need to enter confined spaces wherever
possible.
• Safe access shall be provided to all plant requiring maintenance.
• All above ground systems shall be fenced off and be inaccessible to the public.
• Craneage or mobile lifting facilities shall be provided for all heavy equipment.
4.4 Confidentiality
Only employees and contractors of NEOM have a right to see this document and reproduction of the
whole or part shall not be made without permission of NEOM.
BS EN 14654 – Drain and sewer systems outside buildings. Management and control of activities.
BS EN 16932-1:2018 – Drain and sewer systems outside buildings. Pumping systems. General
requirements.
BS EN 16932-2:2018 – Drain and sewer systems outside buildings. Pumping systems. Positive pressure
systems.
BS EN 16933-2 – Drain and sewer systems outside buildings. Design. Hydraulic design
BS EN 752:2017 – Drain and sewer systems outside buildings. Sewer system management
BS EN 12255-9:2002 – Wastewater treatment plants. Odour control and ventilation.
EN 61439-2:2011 Low-voltage switchgear and controlgear assemblies. Power switchgear and
controlgear assemblies
ISO 14122-3:2016 – Safety of machinery — Permanent means of access to machinery — Part 3: Stairs,
stepladders, and guard-rails
ISO 16143-1:2014 – Stainless steels for general purposes — Part 1: Corrosion-resistant flat products
SASO-IEC-61439-2 – Low-voltage switchgear and controlgear assemblies – Part 2: Power switchgear
and controlgear assemblies
SASO-ISO-16143-1 – Stainless steels for general purposes -- Part 1: Corrosion-resistant flat products
WIMES specification 1.02 – Submersible pump units.
WIMES specification 3.02 – Low voltage electrical installations.
6. DESIGN GUIDELINES
6.1 General
Pumping stations and rising mains and lift stations shall be designed in accordance with BS EN 16932-
1 [1] & BS EN 16932-2 [2]. Pumping stations shall be submersible pump type installations. Pumps shall
Document. No. NEOM-NWA-TGD-2021-022 General Guideline Document
Page 8 of 17
be located in position on guide rails and connected with auto-couplers to allow for the removal and
replacement of the pumps with lifting chains without entry into the wet well. Safety grill shall be provided
to protect operator personnel from falling into the wet well.
The design shall take into account the expected changes to the foul flow rate over the design life of the
pumping station and rising main. The designer shall submit a plan specifying how the pumping system
will be adapted over its design life to take into account these changes.
The designer shall carry out a surge analysis. Pressure during a transient (surge) event should not
exceed the maximum allowable operating pressure for the specific class of rising main and pipe material,
having regard to any de-rating required due to the properties of the pipe material.
Pumping stations have been classified by flow rate and power rating as follows:
• Type 1 - Having an incoming peak design flow rate of ≤ 0.25 litres per second;
• Type 2 - Having an incoming peak design flow rate of > 0.25 litres per second but less than 1
litres per second;
• Type 3 - Having an incoming peak design flow rate of ≥ 1 litre per second but with pumps rated
no more than 30 kW; and
• Type 4 - Having at least one pump rated more than 30 kW.
6.2.1 Hydraulic design
Hydraulic design of positive pressure pumping systems shall be in accordance with BS EN 16932-2:2018
[2], Clause 7 and EN 16933-2 [19].
Flow rates for foul wastewater pumping stations shall be determined in accordance with EN 16933-2 [19]
and the minimum, average, and peak design flows shall be established.
See Section 6.2.1 of Design Guidelines – Gravity Foul Sewer Systems – NEOM-NWA-TGD-2021-021
for design flow details.
The diameter of the rising main shall be such that the velocity of the discharge is in the range of 0.75 –
1.8 m/s when the pump unit is operating.
In foul sewers, a biofilm is created at the inner surface of the pipe which largely determine roughness
conditions, therefore, for all sewer material type, the Colebrook-White hydraulic roughness value, ks,
shall have a default value of:
• 0.30 mm – for mean velocities up to 1.1 m/s; and
• 0.15 mm – for mean velocities between 1.1 and 1.8 m/s.
If the designer wishes to use a different hydraulic roughness value in the design, evidence for change
shall be submitted to NEOM for approval. The NEOM wastewater engineer will approve or reject the
request and their decision is final.
6.3 Valves chambers
All valve chambers shall be designed with provision for removal and replacement of valves or other
provision for access to the rising main for cleaning and inspection.
Odour treatment shall be provided at pumping stations and valve chambers in accordance with BS
EN 12255-9 [4].
6.6 Buildings
Electrical switchgear and control gear shall be contained in a building constructed over the pumping
station. It shall be contained in a compartment that is isolated from any hazardous atmosphere. The
building shall be designed in accordance with Design Guidelines – Sewerage structures – NEOM-NWA-
TGD-2021-019. The atmosphere in the building shall be regulated by an HVAC system. IECC 2015 [11]
and ANSI/ASHRAE/IES 90.1 Standards [12] provide useful advice on HVAC systems requirements.
Adequate provision shall be made to effectively protect maintenance personnel from hazards.
Components required for safe entry in confined space shall be provided in accordance with OSHA and
regulatory agency requirements shall be met for all sewage pumping stations.
Mechanical and electrical rooms shall be completely separated from area exposed to wastewater.
Common walls shall be gas tight and there shall be no internal doors linking the two areas.
6.8.2.1 General
The pumping station shall be provided with a Remote Telemetry Unit (RTU) which shall be compatible
with the NEOM Smart network SCADA system.
Digital inputs (i.e., providing a signal to the telemetry outstation), shall be volt-free contacts configured
with the closed contact for the healthy state. If the contact is provided by a relay, then the relay shall be
energised when the equipment is healthy.
Any analogue inputs (i.e., providing a signal to the telemetry outstation) shall be a 4-20 mA current loop
with a maximum loop impedance from the telemetry outstation of 250 Ohms. They shall be calibrated
such that 4 mA represents a zero measurement and 20 mA represents a full-scale measurement. A
current of less than 4 mA represents a fault condition.
Pulsed inputs (i.e., providing a signal to the telemetry outstation) shall be via normally open volt-free
contacts, providing a closed contact each time the total is incremented by one unit. The duration and
frequency of the pulse shall be compatible with the particular telemetry outstation used; the instrument
generating the pulses shall be configured to achieve this. If the instrument does not have volt-free outputs,
then an interposing relay shall be used.
For digital outputs, the control system shall respond to a pair of volt-free contacts in the telemetry
outstation rated at no less than 24 volts and 1 amp. Pulsed digital output contacts shall be closed for at
least ten seconds.
State
Function Signal Type Type 1 Type 2 Type 3 Type 4
Description
Site mains (DNO)
Normal/Failed Digital input
power health
High wet well alarm Normal/High Digital input
High high wet well
Normal/High Digital input
alarm
Back-up control Normal/
Digital input
system activated Activated
Maintenance in
Off/On Digital input
progress
Level controller health Normal/Failed Digital input
Flowmeter health Normal/Failed Digital input X X
Wet well effluent level Digital input X
Pumping station
overload (Pump unit
Digital input X X
running, and high high
level reached)
Rising main delivery
Pulsed input X X Note 1
flow (totalised)
State
Function Signal Type Type 1 Type 2 Type 3 Type 4
Description
Remote common fault Pulsed digital
Pulse to reset
reset (Note 1) output
Digital output
(on when
Remote control select On/off X
contacts
closed)
Remote pumping
Digital output
station start/stop
Enable/ (on when
(when remote X X X
disable contacts
operation selected)
open)
(Notes 1 and 2)
Digital output
(duty/standby
Remote pump duty Duty standby/
when X
select (Note 1) duty assist
contacts
open)
Note 1: Enabled when remote control selected to On.
Note 2: In Type 3 pumping stations, remote pumping station start/stop is not required as remote
pump units will be provided for each pump.
Table 6.3 Telemetry Requirements for the Monitoring of each Pump Unit
State
Function Signal Type Type 1 Type 2 Type 3 Type 4
Description
Running/
Pump unit running Digital input
stopped
Normal/
Pump unit tripped Digital input
tripped
Pump unit Available/
Digital input
available/not available unavailable
Motor stator
Normal/high Digital input
temperature
Pump unit vibration Normal/
Digital input X X Note 2
caution (Note 1) caution
Table 6.4 Telemetry Requirements for the Control of each Pump Unit
State
Function Signal Type Type 1 Type 2 Type 3 Type 4
Description
Digital output
(pump unit
Remote pump unit
Start/stop on when X X
control
contacts
open)
Note 1: Enabled when remote control selected to On.
7.1.3.1 Layout
Where practicable, the rising main should be installed in a straight line (from the pumping station to the
discharge point) and at constant gradient. Where bends are used, they should be preformed and of long
radius type.
Horizontal alignment (layout) and vertical alignment (profile) of the main need to be considered together
during the design process due to the implication one can have for the other.
Rising mains should be a minimum of 3 m from any building/structure.
The minimum burial depth to the top of pipe shall be:
• 1.5 m – under roads and parking areas; and
• 0.9 m – under other locations not specified above.
Where the minimum burial depth requirements cannot be met, then additional protection (such as full
concrete encasement for rigid pipes or the use of concrete protection slabs spanning the pipe trench for
flexible pipes) shall be provided. In special areas with heavy loading and highways specific protection
may be required based on structural evaluations and a design check shall be carried out.
In all cases, the pipe minimum and maximum depth should conform to the pipe manufacturers’
recommendations. However, designs shall be carried out to ensure that pipes are no deeper than 6
meters, unless specific written approval is provided by NEOM.
7.2 Valves
7.2.1 General
Metal components of valves should be coated with an appropriate corrosion protection or made from a
stainless-steel grade 4404-316-03-I to ISO 16143 [14].