Yokogawa Eja 110a
Yokogawa Eja 110a
Yokogawa Eja 110a
GS 1C21B1-E
j STANDARD SPECIFICATIONS
Refer to GS 1C22T2-E for Fieldbus communication
type marked with “e.”
h PERFORMANCE SPECIFICATIONS
Zero-based calibrated span, linear output, wetted
parts material code ‘S’ and silicone oil.
Effect on Zero (can be corrected at line pres-
Reference Accuracy of Calibrated Span
(including the effects of zero-based linearity, hyster- sure)
esis, and repeatability) L capsule
6[0.02 % Span+0.052 % URL] per 3.4 MPa {500 psi}
60.075 % of Span
M, H and V capsules
For spans below X 60.028 % of URL per 6.9 MPa {1000 psi}
Overpressure Effects (M, H and V capsules)
6[0.025 + 0.05
X
] % of Span
60.03 % of URL per 14 MPa {2000 psi}
Span Stability (M, H and V capsules)
where X equals: 60.1 % of URL per 60 months
Capsule X kPa {inH2O} Power Supply Effects “e”
L 3 {12} 60.005 % per Volt (from 21.6 to 32 V DC, 350 V for
M 10 {40} Output signal code D and E.)
H 100 {400}
V 1.4 MPa {200 psi} h FUNCTIONAL SPECIFICATIONS
Square Root Output Accuracy
Span & Range Limits
The square root accuracy is a percent of flow span.
Measurement
Output Accuracy Span/Range kPa inH2O(/D1) mbar(/D3) mmH2O(/D4)
Span 0.5 to 10 2 to 40 5 to 100 50 to 1000
same as reference L
50 % or Greater Range -10 to 10 -40 to 40 -100 to 100 -1000 to 1000
accuracy Span 1 to 100 4 to 400 10 to 1000 100 to 10000
M
reference accuracy350 Range -100 to 100 -400 to 400 -1000 to 1000 -10000 to 10000
50 % to Dropout point Span 5 to 500 20 to 2000 50 to 5000 0.05 to 5 kgf/cm2
square root output (%) H
Range -500 to 500 -2000 to 2000 -5000 to 5000 -5 to 5 kgf/cm2
T00E.EPS
Span 0.14 to 14 MPa 20 to 2000 psi 1.4 to 140 bar 1.4 to 140 kgf/cm2
V*1 Range
Ambient Temperature Effects -0.5 to 14 MPa -71 to 2000 psi -5 to 140 bar -5 to 140 kgf/cm2
Total Effects per 28 ˚C (50 ˚F) Change T01E.EPS
*1: For Wetted parts material code other than S, the
Capsule Effect ranges are 0 to 14 MPa, 0 to 2000 psi, 0 to 140
bar, and 0 to 140 kgf/cm2.
L 6[0.08 % Span + 0.09 % URL]
M 6[0.07 % Span + 0.02 % URL] URL is defined as the Upper Range Limit from the table
H 6[0.07 % Span + 0.015 % URL] above.
V 6[0.07 % Span + 0.03 % URL]
Zero Adjustment Limits
Static Pressure Effects Zero can be fully elevated or suppressed, within the
Lower and Upper Range Limits of the capsule.
Total Effects per Change
L capsule External Zero Adjustment “e”
6[0.07 % Span+0.052 % URL] per 3.4 MPa {500 psi} External zero is continuously adjustable with 0.01 %
M, H and V capsules incremental resolution of span. Span may be
6[0.1% Span+0.028 % URL] per 6.9 MPa {1000 psi} adjusted locally using the digital indicator with range
switch.
250
Capsule (Silicone Oil) L M H and V
Time Constant (approx. sec) 0.8 0.6 0.3 R (V)
(approval codes may affect limits) Figure 2. Relationship Between Power Supply Voltage
-40 to 120 ˚C (-40 to 248 ˚F) and External Load Resistance
Ambient Humidity Limits
5 to 100 % RH @ 40 ˚C (104 ˚F)
Working Pressure Limits (Silicone Oil) Supply Voltage “e”
Maximum Pressure Limit 10.5 to 42 V DC for operation(10.5 to 30 V DC for
Intrinsically safe type)
Capsule Pressure 16.4 to 42 V DC for digital communications, BRAIN
and HART protocols(16.4 to 30 V DC for
L 3.5 MPa {500 psig} Intrinsically safe type)
M, H, and V 14 MPa {2000 psig}
Load(Output signal code D and E)
Minimum Pressure Limit 0 to 1335 V for operation
See graph below 250 to 600 V for digital communication
EMC Conformity Standards ,
100{14.5} Atmospheric For EMI (Emission): EN55011, AS/NZS 2064 1/2
pressure For EMS (Immunity): EN50082-2
Working
pressure
Communication Requirements “e”
kPa abs BRAIN
{psi abs}
Communication Distance
Applicable range Up to 2 km (1.25 miles) when using CEV polyethyl-
10{1.4} ene-insulated PVC-sheathed cables. Communication
distance varies depending on type of cable used.
Load Capacitance
2.7{0.38}
0.22 mF or less (see note)
Load Inductance
3.3 mH or less (see note)
1{0.14}
-40 0 40 80 120 Input Impedance of communicating device
(-40) (32) (104) (176) (248) 10 kV or more at 2.4 kHz.
Process temperature 8C (8F)
F01E.EPS Note : For general-use and Flameproof type.
For Intrinsically safe type, please refer to
Figure 1. Working Pressure and Process Temperature ‘OPTIONAL SPECIFICATIONS.’
All Rights Reserved. Copyright © 1997, Yokogawa Electric Corporation GS 1C21B1-E July 01, 1999-00
3
HART
Communication Distance
Up to 1.5 km (1 mile) when using multiple twisted pair
cables. Communication distance varies depending on
type of cable used.
h PHYSICAL SPECIFICATIONS
Wetted Parts Materials
Diaphragm, Cover flange, Process connector,
and Vent/Drain Plug
Refer to ‘MODEL AND SUFFIX CODE.’
Capsule Gasket
For wetted parts material code S, Teflon-coated
SUS316L.
For wetted parts material code other than S,
PTFE(Teflon).
Process Connector Gasket
PTFE Teflon
Non-wetted Parts Materials
Bolting
SCM435 or SUS630
Housing
Low copper cast-aluminum alloy with polyurethane
paint (Munsell 0.6GY3.1/2.0)
Enclosure Classification
JIS C0920 immersion proof
(equivalent to NEMA 4X and IEC IP67)
Cover O-rings
Buna-N
Name plate and tag
SUS304
Fill Fluid
Silicone, Fluorinated oil (option)
Weight
3.9 kg (8.6 lbs.) without integral indicator, mounting
bracket, and process connector.
Connections
Refer to the model code to specify the process and
electrical connection type.
All Rights Reserved. Copyright © 1997, Yokogawa Electric Corporation GS 1C21B1-E July 01, 1999-00
4
■ MODEL AND SUFFIX CODES
Model Suffix Codes Description
EJA110A ························· Differential pressure transmitter
Output Signal -D · · · · · · · · · · · · · · · · · · · · · · · 4 to 20 mA DC with digital communication (BRAIN protocol)
-E · · · · · · · · · · · · · · · · · · · · · · · 4 to 20 mA DC with digital communication (HART protocol, refer to GS 1C22T1-E)
-F · · · · · · · · · · · · · · · · · · · · · · · Digital communication (FOUNDATION Fieldbus protocol, refer to GS 1C22T2-E)
Measurement L ····················· 0.5 to 10 kPa {50 to 1000 mmH2O}
span(capsule) M····················· 1 to 100 kPa {100 to 10000 mmH2O}
H····················· 5 to 500 kPa { 0.05 to 5 kgf/cm2}
V····················· 0.14 to 14 MPa { 1.4 to 140 kgf/cm2}*1
Wetted parts [Body]*2 [Capsule] [Vent plug]
material S ··················· SCS14A SUS316L*5 SUS316
H ··················· SCS14A Hastelloy C-276*6 SUS316
M ··················· SCS14A Monel*6 SUS316
T ··················· SCS14A Tantalum*6 SUS316
A···················· Hastelloy C-276 equivalent*3 Hastelloy C-276*6 Hastelloy C-276
D ··················· Hastelloy C-276 equivalent*3 Tantalum*6 Hastelloy C-276
B ··················· Monel equivalent*4 Monel*6 Monel
Process connections 0·················· without process connector (Rc1/4 female on the cover flanges)
1·················· with Rc1/4 female process connector
2·················· with Rc1/2 female process connector
3· · · · · · · · · · · · · · · · · · with 1/4 NPT female process connector
4· · · · · · · · · · · · · · · · · · with 1/2 NPT female process connector
q 5· · · · · · · · · · · · · · · · · · without process connector (1/4 NPT female on the cover flanges)
[Maximum working pressure]
Bolts and nuts material
(L capsule) (M, H, and V capsule)
q A················ SCM435 3.5 MPa {35 kgf/cm2} 14 MPa {140 kgf/cm2}
B················ SUS630 3.5 MPa {35 kgf/cm2} 14 MPa {140 kgf/cm2}
Installation -2 · · · · · · · · · · · · · · Vertical impulse piping type, right side high pressure, process connector upside*7
-3 · · · · · · · · · · · · · · Vertical impulse piping type, right side high pressure, process connector downside*7
-6 · · · · · · · · · · · · · · Vertical impulse piping type, left side high pressure, process connector upside*7
-7 · · · · · · · · · · · · · · Vertical impulse piping type, left side high pressure, process connector downside*7
-8 · · · · · · · · · · · · · · Horizontal impulse piping type, right side high pressure*8
q -9 · · · · · · · · · · · · · · Horizontal impulse piping type, left side high pressure*8
The ‘q’ marks indicate the most typical selection for each specification. Example: EJA110A-DMS5A-92NA/h
*1: For Wetted parts material code H, M, T, A, and D, the range limits are 0 to 14 MPa{0 to 140 kgf/cm2}.
*2: Indicates material of cover flanges and process connectors.
*3: Indicated material is equivalent to ASTM CW-12MW.
*4: Indicated material is equivalent to ASTM M35-2.
*5: Diaphragm material is Hastelloy C-276. Indicated is other wetted parts materials.
*6: Indicates diaphragm and other wetted parts material.
*7: If necessary, specify Mounting bracket code C or D.
*8: If necessary, specify Mounting bracket code A or B.
All Rights Reserved. Copyright © 1997, Yokogawa Electric Corporation GS 1C21B1-E July 01, 1999-00
5
■ OPTIONAL SPECIFICATIONS (For Explosion Protected type “e”)
For FOUNDATION Fieldbus explosion protected type, see GS 1C22T2-E.
Item Description Code
FM Explosionproof Approval *3
Explosionproof for Class I, Division 1, Groups B, C and D
Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G
Hazardous (classified) locations, indoors and outdoors ( NEMA 4X ) FF1
Temperature class : T6
Amb. Temp. :–40 to 60 8C (–40 to 140 8F)
Electrical connection : 1/2 NPT female *1
FM Intrinsically safe Approval *3
Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1,
Groups E, F & G and Class III, Division 1 Hazardous Locations.
Factory Mutual (FM) Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division. 2,
Groups E, F & G, and Class III, Division 1 Hazardous Locations.
Enclosure : "NEMA 4X", Temp. Class : T4, Amb. Temp. : –40 to 60 8C (–40 to 140 8F) FS1
Intrinsically Safe Apparatus Parameters
[Groups A, B, C, D, E, F and G]
Vmax=30 V, Imax=165 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730 mH
[Groups C, D, E, F and G]
Vmax=30 V, Imax=225 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730 mH
Electrical connection : 1/2 NPT female *1
Combined FF1and FS1*3
FU1
Electrical connection : 1/2 NPT female *1
CENELEC (KEMA) Flameproof Approval *3
EExd IIC T4, T5, T6, Amb. Temp. : –40 to 80 8C (–40 to 176 8F)
KF1
Max. process Temp. : T4 ; 120 8C (248 8F), T5 ; 100 8C (212 8F), T6 ; 85 8C (185 8F)
Electrical connection : 1/2 NPT female, Pg 13.5 female and M20 female *2
CENELEC (KEMA) Intrinsically safe Approval *3
EEx ia IIC T4, Amb. Temp. : –40 to 60 8C(–40 to 140 8F)
CENELEC (KEMA) Ui=30 V, Ii=165 mA, Pi=0.9 W, Ci=22.5 nF, Li=730 mH KS1
Electrical connection : 1/2 NPT female, Pg 13.5 female and M20 female *2
Combined KF1, KS1 and Type N Approval *3
KEMA Type N Approval
Ex nA IIC T4, Amb. Temp. : –40 to 60 8C(–40 to 140 8F) KU1
U=30 V, I=165 mA
Electrical connection : 1/2 NPT female, Pg 13.5 female and M20 female *2
CSA Explosionproof Approval *3
Explosionproof for Class I, Division 1, Groups B, C and D
Dustignitionproof for Class II/III, Division 1, Groups E, F and G
Division2 'SEALS NOT REQUIRED' , Temp. Class : T4, T5, T6 Encl Type 4x CF1
Max. Process Temp. : T4 ; 120 8C (248 8F), T5 ; 100 8C (212 8F), T6 ; 85 8C (185 8F)
Amb. Temp. :–40 to 80 8C (–40 to 176 8F)
Canadian Standards Electrical connection : 1/2 NPT female *1
Association (CSA) CSA Intrinsically safe Approval *3
Class I, Groups A, B, C and D Class II and III, Groups E, F and G
Encl Type 4x, Temp. Class : T4, Amb. Temp. : –40 to 60 8C (–40 to 140 8F) CS1
Vmax=30 V, Imax=165 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730 mH
Electrical connection : 1/2 NPT female *1
Combined CF1 and CS1 *3
CU1
Electrical connection : 1/2 NPT female *1
SAA Flameproof, Intrinsically safe and Non-sparking Approval *3
Ex d IIC T4/T5/T6, IP67 class I, Zone 1, Amb. Temp. : –40 to 80 8C (–40 to 176 8F)
Standards Association of Max. Process Temp. : T4 ; 120 8C (248 8F), T5 ; 100 8C (212 8F), T6 ; 85 8C (185 8F)
Ex ia IIC T4, IP67 class I, Zone 0 SU1
Australia (SAA)
Ex n IIC T4, IP67 class I, Zone 2
Ui=30 V DC, Ii=165 mA DC, Wi=0.9 W, Amb. Temp. : –40 to 60 8C (–40 to 140 8F)
Electrical connection : 1/2 NPT female, Pg 13.5 female and M20 female *2
T05E.EPS
*1: Applicable for Electrical connection code 2 and 7.
*2: Applicable for Electrical connection code 2, 3, 4, 7, 8, and 9.
*3: Applicable for Output signal code D and E.
For intrinsically safe approval, use the safety barrier certified by the testing laboratories (BARD-400 is not applicable).
All Rights Reserved. Copyright © 1997, Yokogawa Electric Corporation GS 1C21B1-E Sep. 01, 1999-00
6
■ OPTIONAL SPECIFICATION
Item Description Code
Color change Amplifier cover only Ph
Painting
Coating change Epoxy resin-baked coating X1
Transmitter power supply voltage: 10.5 to 32 V DC (10.5 to 30 V DC for intrinsically
Lightning protector safe type, 9 to 32 V DC for Fieldbus communication type.) A
Allowable current: Max. 6000 A (1340 ms), Repeating 1000 A (1340 ms) 100 times
Degrease cleansing treatment K1
Oil-prohibited use*11 Degrease cleansing treatment and with fluorinated oilfilled capsule.
Operating temperature -20 to 80 8C K2
All Rights Reserved. Copyright © 1997, Yokogawa Electric Corporation GS 1C21B1-E July 01, 1999-00
7
■ DIMENSIONS
● Model EJA110A
Vertical Impulse Piping Type
Process connector upside (INSTALLATION CODE '6') (For CODE '2','3' or '7', refer to the notes below.)
Process connector External indicator Unit : mm (approx.inch)
(Optional) conduit connection
259(10.20) (Optional)
197 (7.76) 110 (4.33)
97 146 (5.75) High 54 Low
(3.82) pressure pressure
Process side
(2.13) side (Note)
connections
(2.83)
72
(1.81)
46
(5.83)
(3.07)
148
ø78
234(9.21)
Terminal
(4.02)
side
102
Internal
indicator
(Optional)
Ground
terminal Conduit Vent/Drain plugs
( 2.09)
connection 9(note 3)
53
(0.35)
Zero 2-inch pipe
Mounting bracket adjustment (O.D. 60.5 mm)
(L-type, Optional)
F03E.EPS
Horizontal Impulse Piping Type (INSTALLATION CODE '9') (For CODE '8', refer to the notes below.)
110 (4.33)
94 72 Conduit
connection 9(note3) Zero
(3.70) (2.83) (0.35) adjustment
Internal
indicator
(Optional)
(3.07)
(Optional)
(5.75)
(6.38)
146
162
Ground
terminal
High Low
pressure pressure
side side (Note)
46 connections
124
(Optional)
Mounting bracket
2-inch pipe (O.D. 60.5mm) (Flat-type, Optional)
F04E.EPS
* 1: When Installation code 2, 3, or 8 is selected, high and low pressure side on above figure are reversed.
(i.e. High pressure side is on the right side.)
* 2: When Installation code 3 or 7 is selected, process connection mounting bracket on above figure are reversed.
* 3: 15 mm(0.59 inch) for right side high pressure.(for code 2, 3 or 8)
+
CHECK – External indicator(ammeter) terminal*1
All Rights Reserved. Copyright © 1997, Yokogawa Electric Corporation GS 1C21B1-E July 01, 1999-00
8
■ SELECTION GUIDE
Measurement Span Maximum Working Pressure
Application Type Model Capsule
kPa inH2O MPa psi
L 0.5 to 10 2 to 40 3.5 500
Differential M 1 to 100 4 to 400 14 2000
Pressure Traditional-Mounting*1 EJA110A
H 5 to 500 20 to 2000 14 2000
V 0.14 to 14MPa 20 to 2000 psi 14 2000
L 1 to 10 4 to 40 3.5 500
Flow Integral Orifice EJA115 M 2 to 100 8 to 400 14 2000
H 20 to 210 80 to 830 14 2000
Differential Pressure Extended EJA118N M 2.5 to 100 10 to 400
& Liquid Level Flush EJA118W 25 to 500 Based on Flange Rating
H 100 to 2000
with Remote Seals Combination EJA118Y
Draft Range Traditional-Mounting*1 EJA120A E 0.1 to 1 0.4 to 4 50 kPa 7.25
Differential Pressure Traditional-Mounting*1 M 1 to 100 4 to 400 32 4500
& Liquid Level EJA130A
H 5 to 500 20 to 2000 32 4500
Liquid Level, Closed Flush EJA210A M 1 to 100 4 to 400
20 to 2000 Based on Flange Rating
or Open Tank Extended EJA220A H 5 to 500
L 0.67 to 10*2 2.67 to 40*2 10 kPa*2 40 in H2O*2
Absolute (vacuum) 130 kPa*2
Pressure Traditional-Mounting*1 EJA310A M 1.3 to 130*2 0.38 to 38 inHg*2 18.65*2
A 0.03 to 3 MPa*2 4.3 to 430 psi*2 3000 kPa*2 430*2
A 0.03 to 3 MPa 4.3 to 430 psi 3 430
Gauge Pressure Traditional-Mounting*1 EJA430A 0.14 to 14 20 to 2000 psi 14
B 2000
Gauge Pressure Extended EJA438N A 0.06 to 3 MPa 9 to 430 psi Based on Flange Rating
with Remote Seal B 0.46 to 7 66 to 1000 psi
Gauge Pressure A 0.06 to 3 MPa 8 to 430 psi
Flush EJA438W 66 to 2000 psi Based on Flange Rating
with Remote Seal B 0.46 to 7
C 5 to 32 MPa 720 to 4500 psi 32 4500
High Gauge Traditional-Mounting*1 EJA440A 5 to 50 MPa 720 to 7200 psi
D 50 7200
A 10 to 200 1.45 to 29 psi 200 kPa 29
Absolute & Gauge EJA510A B 0.1 to 2 MPa 14.5 to 290 psi 2 290
Direct-Mounting
Pressure*3 EJA530A C 0.5 to 10 MPa 72.5 to 1450 psi 10 1450
D 5 to 50 MPa 720 to 7200 psi 50 7200
T08E.EPS
*1: Traditional-mounting is 1/4 - 18 NPTF process connections ( 1/2 - 14 NPTF with process adapters ) on 2-1/8" centers.
*2: Measurement values in absolute.
*3: Measurement values in absolute for EJA510A.
< Ordering Information > “e” < Related Instruments > “e”
Specify the following when ordering Power Distributor: Refer to GS 1B4T1-E, 1B4T2-E.
1. Model, suffix codes, and optional codes 3-Value Manifold: Refer to GS 22B1C1-E
2. Calibration range and units: BRAIN TERMINAL: Refer to GS 1C0A11-E
1) Calibration range can be specified with range
value specifications up to 5 digits < Reference >
(excluding any decimal point) for low or high range 1. Teflon; Trademark of E.I. DuPont de Nemours & Co.
limits within the range of -32000 to 32000. 2. Hastelloy; Trademark of Haynes International Inc.
2) Specify only one unit from the table, ‘Settings 3. Monel; Trademark of Inco Alloys International, Inc.
when shipped.’ 4. HART; Trademark of the HART Communication
3. Select linear or square root for output mode and Foundation.
display mode. 5. FOUNDATION; Trademark of Fieledbus Foundation.
Note: If not specified, the instrument is shipped set for Material Cross Reference Table
linear mode.
4. Select normal or reverse for operation mode SUS316L AISI 316L
Note: If not specified, the instrument is shipped in SUS316 AISI 316
normal operation mode. SUS304 AISI 304
5. Display scale and units (for transmitters equipped S25C AISI 1025
with integral indicator only)
SCM435 AISI 4137
Specify either 0 to 100 % or engineering unit scale
SUS630 ASTM630
and ‘Range and Unit’ for engineering units scale:
Scale range can be specified with range limit SCS14A ASTM CF-8M
specifications up to 5 digits (excluding any decimal T09E.EPS
All Rights Reserved. Copyright © 1997, Yokogawa Electric Corporation GS 1C21B1-E July 01, 1999-00