Optiview Control Center Non-York Centrifugal Liquid Chillers
Optiview Control Center Non-York Centrifugal Liquid Chillers
Optiview Control Center Non-York Centrifugal Liquid Chillers
Issue Date:
April 27, 2018
FORM 160.10-O1
ISSUE DATE: 4/27/2018
IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
This equipment is a relatively complicated apparatus. which it is situated, as well as severe personal injury or
During rigging, installation, operation, maintenance, death to themselves and people at the site.
or service, individuals may be exposed to certain com-
ponents or conditions including, but not limited to: This document is intended for use by owner-authorized
heavy objects, refrigerants, materials under pressure, rigging, installation, and operating/service personnel. It
rotating components, and both high and low voltage. is expected that these individuals possess independent
Each of these items has the potential, if misused or training that will enable them to perform their assigned
handled improperly, to cause bodily injury or death. It tasks properly and safely. It is essential that, prior to
is the obligation and responsibility of rigging, instal- performing any task on this equipment, this individual
lation, and operating/service personnel to identify and shall have read and understood the on-product labels,
recognize these inherent hazards, protect themselves, this document and any referenced materials. This in-
and proceed safely in completing their tasks. Failure dividual shall also be familiar with and comply with
to comply with any of these requirements could result all applicable industry and governmental standards and
in serious damage to the equipment and the property in regulations pertaining to the task in question.
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to specific situations:
External wiring, unless specified as an optional connection in the manufacturer’s product line, is not
to be connected inside the control cabinet. Devices such as relays, switches, transducers and controls
and any external wiring must not be installed inside the micro panel. All wiring must be in accor-
dance with Johnson Controls’ published specifications and must be performed only by a qualified
electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper
connections to the controls or application of improper control signals. Failure to follow this warn-
ing will void the manufacturer’s warranty and cause serious damage to property or personal injury.
2 JOHNSON CONTROLS
FORM 160.10-O1
ISSUE DATE: 4/27/2018
EMERGENCY SHUTDOWN The chiller must not be operated outside the design pa-
rameters specified in any of the manuals included with
In case an emergency of any type should arise while
the OptiView Retrofit Kit and the Trane unit.
the chiller is running, IMMEDIATELY switch the Op-
tiView compressor switch to the OFF position. Structural Support
RESPONSIBILITY FOR SAFETY Proper structural support of the OptiView Panel must
be provided as indicated in these instructions. Failure
Every effort has been made in the design and manufac- to provide proper support may result in injury to the
ture of this kit to ensure the safety of personnel work- operator or damage to the equipment and/or building.
ing on the chiller. However, the individual operating/
working on any equipment is ultimately responsible Mechanical Strength
for:
The OptiView Panel is not designed to withstand
• Personal safety, the safety of other personnel, and loads or stresses from adjacent equipment, pipework
the machinery or structures. No other components may be mounted
on or to the OptiView Control Panel. Any extraneous
• Correct utilization of the machinery in accordance
loads may cause failure and may result in injury to the
with the procedures detailed in the YORK and
operator, or damage to the equipment.
Trane manuals
• Proper chiller maintenance Pressure Systems
The chiller contains refrigerant vapor and liquid under
ABOUT THIS MANUAL pressure, which can be a hazardous and cause injury if
The contents of this manual include suggested best released. Care must be taken during installation, opera-
working practices and procedures related to the service tion and maintenance of this kit to avoid damage to the
and repair of this kit. These are issued for guidance pressure system. No attempt should be made to gain
only; they do not take precedence over the above stated access to the component parts of the pressure system
individual responsibility and local safety regulation. other than by suitably trained and qualified personnel.
JOHNSON CONTROLS 3
FORM 160.10-O1
ISSUE DATE: 4/27/2018
General Access
There are a number of areas and features which may
be a hazard and potentially cause injury when operat-
ing the Control Center and chiller unless suitable safety
precautions are taken. Access to the Control Center and
chiller should be restricted to suitably qualified persons
who are familiar with the potential hazards and precau-
tions necessary for safe operation and maintenance of
equipment containing high temperatures, pressures and
voltages.
In complying with Johnson Controls’ policy for con- regarding the applicability of these documents, rig-
tinuous product improvement, the information con- ging, lifting, and operating/service personnel should
tained in this document is subject to change without verify whether the equipment has been modified and
notice. Johnson Controls makes no commitment to if current literature is available from the owner of the
update or provide current information automatically equipment prior to performing any work on the equip-
to the manual or product owner. Updated manuals, if ment.
applicable, can be obtained by contacting the nearest
Johnson Controls Service office or accessing the John- CHANGE BARS
son Controls QuickLIT website at http://cgproducts. Revisions made to this document are indicated with a
johnsoncontrols.com. line along the left or right hand column in the area the
It is the responsibility of rigging, lifting, and operating/ revision was made. These revisions are to technical in-
service personnel to verify the applicability of these formation and any other changes in spelling, grammar
documents to the equipment. If there is any question or formatting are not included.
ASSOCIATED LITERATURE
4 JOHNSON CONTROLS
FORM 160.10-O1
ISSUE DATE: 4/27/2018
TABLE OF CONTENTS
JOHNSON CONTROLS 5
FORM 160.10-O1
ISSUE DATE: 4/27/2018
LIST OF FIGURES
6 JOHNSON CONTROLS
FORM 160.10-O1
ISSUE DATE: 4/27/2018
JOHNSON CONTROLS 7
FORM 160.10-O1
ISSUE DATE: 4/27/2018
LIST OF TABLES
TABLE 1 - Master Slot Numbers List (For Use With Trend Features)��������������������������������������������������������������������98
TABLE 2 - Status Line Messages and Colors�������������������������������������������������������������������������������������������������������101
TABLE 3 - Current Limit Thresholds���������������������������������������������������������������������������������������������������������������������102
TABLE 4 - Evaporator Pressure Thresholds���������������������������������������������������������������������������������������������������������103
TABLE 5 - Starter - Low Supply Line Voltage Limits���������������������������������������������������������������������������������������������105
TABLE 6 - Starter - High Supply Line Voltage Limits��������������������������������������������������������������������������������������������106
TABLE 7 - LCSSS Low Supply Line Voltage Thresholds��������������������������������������������������������������������������������������108
TABLE 8 - LCSSS High Supply Line Voltage Thresholds�������������������������������������������������������������������������������������108
TABLE 9 - Evaporator Pressure Thresholds��������������������������������������������������������������������������������������������������������� 113
TABLE 10 - Okidata 182, 182 Turbo, 184 Turbo Printer Connections������������������������������������������������������������������121
TABLE 11 - Weigh-Tronix Printer Connections�����������������������������������������������������������������������������������������������������121
TABLE 12 - Seiko Printer Connections�����������������������������������������������������������������������������������������������������������������121
TABLE 13 - Programmable Setpoint Values���������������������������������������������������������������������������������������������������������133
TABLE 14 - Analog Input Ranges (Low Pressure Chillers)�����������������������������������������������������������������������������������139
TABLE 15 - SI Metric Conversion�������������������������������������������������������������������������������������������������������������������������141
8 JOHNSON CONTROLS
FORM 160.10-O1
ISSUE DATE: 4/27/2018
LD10254
RETROFIT KIT DESCRIPTION served by pressing the keys as labeled on the Control
Center.
The OptiView Control Center Retrofit Kit for Trane
centrifugal chillers is a state of the art microprocessor- The OptiView Control Center is compatible with elec-
based control system that monitors and controls opera- tro-mechanical starters, YORK Solid State Starters, or
tion of Non-York chillers. YORK Variable Speed Drives.
For specific information on principles of The YORK Mod “B” Solid State Starter, the most re-
chiller operation, refer to the manuals cent version, contains a combination Logic/trigger
provided by the chiller manufacturer. Board that interfaces the Control Center with a serial
communications link. The Mod “A” Solid State Starter
is not compatible with this kit for Trane model chillers.
The panel comes configured with a full screen LCD
The OptiView control center can be configured to work Graphic Display mounted in the middle of a keypad
with Trane CVHA, CVHB, CVHE, and CVHF low- interface. The graphic display allows the presentation
pressure chillers that utilize R-11 or R-123 refrigerant. of several operating parameters at once. In addition,
The OptiView is programmed by the operator to suit the operator may view a graphical representation of the
job specifications. Automatic timed start-ups and shut- historical operation of the chiller as well as the present
downs are also programmable to suit nighttime, week- operation. For the novice user, the locations of various
ends, and holidays. The operating status, temperatures, chiller parameters are clearly and intuitively marked.
pressures, and other information pertinent to operation Instructions for specific operations are provided on
of the chiller are automatically monitored and dis- many of the display screens.
played on a graphic display. Other displays can be ob-
JOHNSON CONTROLS 9
FORM 160.10-O1
SECTION 1 - OPTIVIEW RETROFIT KIT CONTROL CENTER INTRODUCTION
ISSUE DATE: 4/27/2018
10 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 1 - OPTIVIEW RETROFIT KIT CONTROL CENTER INTRODUCTION
ISSUE DATE: 4/27/2018
JOHNSON CONTROLS 11
FORM 160.10-O1
ISSUE DATE: 4/27/2018
12 JOHNSON CONTROLS
FORM 160.10-O1
ISSUE DATE: 4/27/2018
2
R
1 2 3
SYSTEM STATUS DATE TIME CONTROL SOURCE
Motor
x
Leaving 44.7 F Leaving 00.0 F
Setpoints
Return 52.4 F Return 68.7 F
LD10322a
JOHNSON CONTROLS 13
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
When the switch is placed this position, the chiller is Access Level
able to operate. The switch spring-returns to the “RUN”
When power is applied to the chiller, the system begins
state after being turned to the “START” position. When
with an access level of “View”. This will allow the user
in this position, the chiller is allowed to function nor-
to navigate to most screens and observe the values dis-
mally and will also allow the chiller to automatically
played there. The user will not be allowed to change
restart following a cycling shutdown. The switch must
any values at the “View” level. To change any values,
be in this position to receive a valid remote start signal
the user must return to the “Home” screen (shown by
when operating under a remote control source.
default when power is applied to the system) and use
OPTIVIEW DISPLAY PANEL OVERVIEW the “Login” button, located in the series of five but-
tons below the display. The user may also utilize the
The graphical display on each control panel allows “Change Setpoints” key (described below) to login. At
a wide variety of information to be presented to the this point, the user will be prompted to enter a User ID
user. Each screen description in this document will and the corresponding password.
begin with a section entitled “Overview” which will
describe the graphical elements on the screen and give By default, the User ID is zero (0). In order to gain
a short summary of the functions available. Each ele- standard “Operator” level access, the password would
ment on the screen will then be categorized into three be entered as 9 6 7 5, using the numeric keypad and
distinct groups: “Display Only”, “Programmable”, then pressing the ‘ü’ (Enter) key. The “Operator” ac-
and “Navigation”. Below is a short description of what cess level will revert to the “View” level after 10 con-
types of information are included in these groups. tinuous minutes without a keypress.
The Programmable values and Naviga- If a custom user ID and password have been defined
tion commands are also subject to access (see “User Screen”), the user may enter that user ID
level restrictions. A minimum access level and the corresponding password value at login. If the
is noted for any value or command that correct password is entered, the user is authorized with
can be changed. the appropriate access level. If an incorrect password is
entered, the user is notified of the failure and prompted
again. At this point, the user may retry the password
entry or cancel the login attempt.
14 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
JOHNSON CONTROLS 15
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
16 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
HOME SCREEN
LD09991
JOHNSON CONTROLS 17
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
Access Level Required: VIEW This key, available only when the compressor is run-
ning, initiates a “Soft Shutdown”. A soft shutdown ful-
The OptiView panel restricts certain operations based ly closes the pre-rotation vanes prior to shutting down
on password entry by the operator. This key allows the the compressor, reducing bearing wear by eliminating
operator to login under a unique user name (as pro- compressor backspin at shutdown. While the vanes
grammed) and access level. Users logged in under are closing, the System Status line displays “VANES
higher access levels may perform any actions permit- CLOSING BEFORE SHUTDOWN”. When the Vane
ted by lower access levels. Motor Switch (VMS) closes, indicating the vanes have
fully closed (or 3.5 minutes have elapsed, whichever
Logout
occurs first), the run signal is removed from the com-
Access Level Required: OPERATOR pressor motor starter and a “System Coastdown” is
When logged in at any level other than “View”, this performed.
key appears on the OptiView display. Pressing this While the vanes are closing, if a “Local Stop” is initi-
key will return the access level to “View”. After any ated by the compressor switch or a fault occurs, the
setpoint changes are made, the operator should press chiller will immediately enter system coastdown.
the “Logout” key.
This chiller will not enter a system coastdown if one
Print of the following faults occur: “Leaving Chilled Liquid
Temp – Low Temperature”, “Remote Stop”, “Multi-
Access Level Required: VIEW
Unit Cycling – Contacts Open”, “System Cycling –
This key provides a printout of the user selected condi- Contacts Open” or “Control Panel – Schedule”
tions at the time the key is pressed. The “History” page
provides further reporting capability (See “History” To restart the chiller after an operator-initiated soft
below). This option will not be present if the chiller is shutdown, place the compressor switch in the “Stop/
presently configured to log any incoming adaptive ca- Reset” position (O) and then the “Start” position (◄).
pacity control map points (See the Adaptive Capacity
NAVIGATION
Control Details screen).
System
Message Clear
Advances to an additional chiller system operating
Access Level Required: SERVICE level parameter screen.
When the control center detects certain safety or cy-
cling conditions and the chiller shuts down, the main Evaporator
status display on the display will show a message in- Advances to a detailed view of all evaporator param-
dicating the cause of the shutdown. Pressing this key eters, including the programmable leaving chilled liq-
while logged in at the appropriate access level clears uid setpoint.
the message, provided the condition no longer exists.
Condenser
Warning Reset Advances to a detailed view of all condenser param-
Access Level Required: OPERATOR eters such condenser refrigerant temperature.
Use of this key acknowledges a warning condition and Compressor
resets the message display associated with the condi-
tion. Advances to a detailed view of all the compressor pa-
rameters. This includes pre-rotation vane control and
calibration.
18 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
Oil Sump
Advances to a detailed view of all the oil pump and oil
sump parameters such as oil temperature and pressure.
2
Motor
A detailed view of the motor controller parameters,
specific to the controller type presently utilized on the
chiller system. This allows programming of the current
limit and the pulldown demand limit values. For a VSD
system, the adaptive capacity control and harmonic fil-
ter information is controlled under this screen.
Setpoints
This screen provides a single location to program the
most common system setpoints. This screen is also the
gateway to many of the general system setup param-
eters such as: Date/Time, Display Units, Scheduling,
Printer Setup, etc.
History
This screen provides access to a “snapshot” of system
data at each of the last ten (10) shutdown conditions.
This is particularly useful when troubleshooting chiller
system problems.
JOHNSON CONTROLS 19
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
SYSTEM SCREEN
LD09992
20 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
Condenser Pressure
This display indicates the refrigerant pressure in the
condenser.
2
Condenser Saturation Temperature
This display indicates the saturation temperature in the
condenser.
Oil Pressure
This display indicates the pressure differential between
the high side oil pressure transducer (output of oil
filter) and the low side oil pressure transducer (com-
pressor housing). The displayed value includes offset
pressure derived from auto-zeroing during the system
prelube. If either of the transducers used to calculate
this differential are out of range, the display field will
show XX.X.
Current Limit
This display indicates the current limit value in use.
This value could come from a 0-20mA, 4-20mA,
0-10VDC or 2-10VDC input in analog remote mode,
PWM signal in digital remote mode, MicroGateway
interface in ISN (Integrated Systems Network) mode,
or a locally programmed value.
PROGRAMMABLE
None
NAVIGATION
Home
Access Level Required: VIEW
Returns the display to the Home screen.
JOHNSON CONTROLS 21
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
EVAPORATOR SCREEN
LD23594
22 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
ration temperature if the refrigerant temperature sensor liquid temperature is 45.0°F, then the remote de-
is disabled. vice is able to change and set the leaving chilled
liquid temperature setpoint over the range 45.0°
Leaving Chilled Liquid Temperature Setpoints - 55.0°F.
– Setpoint
2
A remote device that provides an analog signal (0-
This display indicates the present setpoint to which the 20mA, 4-20mA, 0-10VDC or 2-10VDC) in analog re-
chiller is operating, whether controlled locally or re- mote mode or a PWM signal in digital remote mode
motely. defines the setpoint change as an offset value.
Leaving Chilled Liquid Temperature Setpoints • For example, if the setpoint is 45.0°F and the de-
– Shutdown sired setpoint is 50.0°F, then 5.0°F would be the
This display indicates the leaving chilled liquid tem- input on the remote device.
perature at which the chiller will shut down to avoid A MicroGateway (in ISN Remote mode) can define the
over-cooling. The default value is 4.0°F below the setpoint through a serial data stream. In this case, the
leaving chilled liquid temperature setpoint. incoming setpoint is not an offset that is applied to the
leaving chilled liquid temperature setpoint value, but is
Leaving Chilled Liquid Temperature Setpoints
the programmed as the actual setpoint value.
– Restart
This display indicates the leaving chilled liquid tem- Leaving Chilled Liquid Temperature Cycling
perature at which the chiller will restart after the chiller Offset – Shutdown
has shut down due to over-cooling temperature. The
Access Level Required: OPERATOR
leaving chilled liquid temperature setpoint is the de-
fault value for this setting. This value specifies the number of degrees below the
leaving chilled liquid temperature setpoint the chilled
PROGRAMMABLE liquid can reach before the OptiView performs a
“LEAVING CHILLED LIQUID – LOW TEMPERA-
Local Leaving Chilled Liquid Temperature – TURE” cycling shutdown. This setpoint is program-
Setpoint mable over a range of 1°F to 64°F (dependant on
Access Level Required: OPERATOR setpoint temperature), to a minimum cutout of 36.0°F
(water), 34.0°F (water with Smart Freeze enabled) or
This value allows the user to define the leaving chilled
6.0°F (brine). This prevents over-cooling of the chilled
liquid temperature that is to be maintained by the chill-
liquid.
er. The temperature is programmable over the range of
38.0°F to 70.0°F (water) or 10.0°F to 70.0°F (brine). Anytime the leaving chilled liquid temperature setpoint
The range is 36.0°F to 70.0°F (water) if Smart Freeze is increased, the shutdown threshold is 36.0°F (water)
is enabled (see below). or 6.0°F (brine) for the next ten (10) minutes. If Smart
Freeze is enabled, the threshold is 34.0°F for the next
Local Leaving Chilled Liquid Temperature – ten minutes. After ten minutes have elapsed, the shut-
Range down threshold becomes the programmed setpoint
Access Level Required: OPERATOR value.
This is the range that a remote device is able to adjust Leaving Chilled Liquid Temperature Cycling
the leaving chilled liquid temperature setpoint above Offset – Restart
the temperature set locally at the OptiView. The range
setpoint is programmable to either 10°F or 20°F, with a Access Level Required: OPERATOR
default of 20°F. This setpoint value is added to the lo- This value specifies the number of degrees above the
cal leaving chilled liquid temperature (see above) val- leaving chilled liquid temperature setpoint the chilled
ue to create a range limit over which a remote device liquid is permitted to reach before the chiller will re-
can adjust the setpoint. start after a “LEAVING CHILLED LIQUID – LOW
TEMPERATURE” cycling shutdown. The value is
• For example, if the range is programmed for 10°F
programmable over a range of 0°F to 70°F (depen-
and the locally programmed value of the chilled
dant on setpoint temperature) above the chilled liq-
JOHNSON CONTROLS 23
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
uid setpoint, to a maximum restart value of 80°F. The Refrigerant (Enabled / Disabled)
chiller will automatically restart when this temperature
Access Level Required: SERVICE
is reached. This setpoint can be used to reduce chiller
cycling by delaying the chiller restart until the cooling Enables/Disables the display of the refrigerant temper-
load has increased. ature sensor reading. This sensor should be enabled for
Trane applications when the optional refrigerant sensor
Brine Low Evaporator Cutout kit is installed.
Access Level Required: SERVICE Change Setpoints
This value is only available when the chiller is in
Access Level Required: VIEW
“Brine” chilled liquid mode. This allows the user to
specify the evaporator pressure at which a safety Allows user to enter login password to change motor
shutdown is initiated. Service technicians refer to the settings. This button is only present at the “View” ac-
OptiView Control Center Retrofit Kit - Trane Service cess level.
Manual (Form 160.10-M1).
NAVIGATION
Smart Freeze (Off/On)
Home
Access Level Required: SERVICE
Access Level Required: VIEW
This setting is only available when the chiller is in
“Water” chilled liquid mode. This feature allows the Returns the display to the Home screen.
user to enable or disable the Smart Freeze operation,
Load Rate/Agitator Valves
which permits the chiller to run closer to the freeze
point without shutting down. Service technicians re- Access Level Required: SERVICE
fer to the OptiView Control Center Retrofit Kit - Trane Advances to a sub-screen which allows programming
Service Manual (Form 160.10-M1). of load rate. Agitator valves are not used in this ap-
plication.
24 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
LD23595
JOHNSON CONTROLS 25
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
26 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
CONDENSER SCREEN
LD23596
JOHNSON CONTROLS 27
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
PROGRAMMABLE
Purge Type
Access Level Required: SERVICE
Allows for selection of type of purge system. If a Trane
purge unit is utilized, “Skyguard Remote” must be se-
lected.
28 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
PURGE SCREEN
LD10008
JOHNSON CONTROLS 29
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
30 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
COMPRESSOR SCREEN
LD27085
JOHNSON CONTROLS 31
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
32 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
NAVIGATION
Home
Access Level Required: VIEW 2
Returns the display to the Home Screen.
Hot Gas
Access Level Required: SERVICE
If the chiller is equipped with a hot gas bypass, this key
accesses a sub-screen that allows programming of the
hot gas bypass control setpoints and manual control of
the hot gas bypass valve. This key is only displayed if
hot gas bypass feature has been enabled on the “Opera-
tions” screen. This feature is engineered according to
each specific application. Service technicians MUST
consult YORK Service Marketing if this option is in-
stalled.
SURGE
Access Level Required: SERVICE
Advances to the SURGE Protection Screen allowing
the setup of the surge protection for the unit. Service
technicians should refer to OptiView Control Center-
Retrofit Kit- Trane Service Manual (Form 160.10-M1)
JOHNSON CONTROLS 33
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
LD23597
34 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
JOHNSON CONTROLS 35
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
LD09998
Start Calibration
DISPLAY ONLY
This option is hidden after calibration has started. Ser-
Pre-Rotation Vanes Opening (LED) vice technicians refer to the OptiView Control Center
Indicates the vanes are opening. Retrofit Kit - Trane Service Manual (Form 160.10-M1)
for an explanation of this function.
Pre-Rotation Vanes Closing (LED)
Indicates the vanes are closing.
36 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
Cancel Calibration
This option only becomes available after calibration
has started. Service technicians refer to the OptiView
Control Center Retrofit Kit - Trane Service Manual 2
(Form 160.10-M1) for an explanation of this function.
NAVIGATION
Home
Access Level Required: VIEW
Returns the display to the Home screen.
Compressor
Access Level Required: VIEW
Returns the display to the Compressor screen.
JOHNSON CONTROLS 37
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
LD09999
38 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
Fixed
This key puts the VSD frequency control into fixed
speed mode and constantly sends the maximum fre-
quency to the VSD control.
Incr(ement) Amount
Defines the increment or amount by which the “In-
crease” and “Decrease” keys will modify the present
VSD command frequency.
Raise
This key puts the VSD frequency control into manual
mode and increases the present command frequency
by the defined increment amount. The value cannot be
raised above the maximum allowed frequency.
Lower
This key puts the VSD frequency control into manual
mode and decreases the present command frequency
by the defined increment amount. The value will not
decrease below one (1) Hz.
JOHNSON CONTROLS 39
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
LD10331
When the chiller is first started and begins to run, this Illuminates for 5 seconds each time a surge is detected
value counts up to the time programmed in the count by the surge protection feature. This LED does not il-
window setpoint (1 to 5 minutes). When this value luminate in response to surge events detected by the
reaches the number of minutes programmed in the compressor VSD adaptive capacity control (ACC)
board.
40 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
Total Surge Count • If the shutdown setpoint is disabled and the ex-
Displays the total number of surge events detected over tended run setpoint is enabled, the pre-rotation
the lifetime of the unit (up to a maximum of 65535). vanes are driven closed for ten (10) minutes and
These are the surge events detected by the surge pro- “WARNING – SURGE PROTECTION – EX- 2
tection feature. The surge events detected by the com- CESS SURGE LIMIT” is displayed. When the 10
pressor VSD adaptive capacity control board (ACC) minutes have elapsed, if the surge window count
are not included in this total. is less than or equal to the count limit, this mes-
sage and load inhibit are automatically cleared.
Extended Run Time Remaining Alternating with this message is “WARNING –
EXCESS SURGE DETECTED” that continues
Displays the time remaining in the ten minute “Extend-
after the 10 minute period has elapsed until manu-
ed Run” period. During this period, the pre-rotation
ally cleared with the Warning Reset key.
vanes are driven closed and “WARNING – SURGE
PROTECTION – EXCESS SURGE LIMIT” is dis- • If both the shutdown and extended run setpoint are
played. Refer to operation under “Count Limit”. Enabled, the ten (10) minute extended run mode
is invoked as described previously. However, if
PROGRAMMABLE the surge window count exceeds the count limit
at the completion of the ten (10) minute extended
Count Window
run period, a safety shutdown is performed and
Access Level Required: OPERATOR “SURGE PROTECTION – EXCESS SURGE” is
displayed.
Allows the user to define the period of time (1 to 5
minutes; 3 minutes is default) in which the number of If the chiller is equipped with a VSD and/or hot gas
surge events (Surge Window Count) are compared to bypass, there are several exceptions related to VSD
the maximum allowed (Count Limit). This is used for and/or hot gas bypass equipped chillers for the surge
the purpose of detecting an excess surge situation. correction/avoidance features to operate. These excep-
tions are as follows:
Count Limit
• If the hot gas bypass control is enabled, the valve
Access Level Required: OPERATOR position must be 100% before the shutdown or ex-
Allows the user to define the maximum number of tended run feature is implemented.
surge events (4 to 20; default is 15) that can occur
• If the chiller is equipped with a VSD, output fre-
within a defined period of time (count window) before
quency must be at full speed (50 Hz/60 Hz) before
an excess surge situation is triggered. If the number
the shutdown or extended run feature is imple-
of surges occurring within window time exceeds the
mented.
count limit, an excess surge situation is signaled.
• If equipped with a VSD and hot gas bypass, the
When an excess surge situation is detected, the action VSD output frequency must be at maximum and
resulting from the situation depends upon the follow- the hot gas valve must be at 100% before the shut-
ing: down or extended run feature is implemented.
• If both the shutdown and extended run setpoints
Shutdown (Enabled/Disabled)
are disabled, the chiller will continue to run, dis-
playing the message “WARNING – EXCESS Access Level Required: OPERATOR
SURGE DETECTED”. This selectable feature allows the user to select wheth-
• If the shutdown setpoint is enabled and the ex- er the chiller will shutdown or continue to run when an
tended run setpoint is disabled, the chiller will excess surge situation has been detected.
perform a safety shutdown and display “SURGE
If this setpoint is enabled and the extended run setpoint
PROTECTION – EXCESS SURGE”.
is disabled, a safety shutdown is performed when the
surge window count exceeds the count limit setpoint.
JOHNSON CONTROLS 41
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
If this setpoint is enabled and the extended run setpoint Surge Sensitivity
is enabled, a safety shutdown is performed if the surge
Access Level Required: SERVICE
window count exceeds the count limit setpoint at the
completion of the ten (10) minute extended run period. Allows the user to define the sensitivity of the surge
“SURGE PROTECTION – EXCESS SURGE” is dis- detection. Selectable over the range of 0.3 to 1.3; de-
played with either shutdown. fault is 0.3. The smaller the number, the greater the
sensitivity.
If this setpoint is disabled, refer to operation under
“Count Limit”. Clear Surge Count
Access Level Required: ADMIN
Extended Run (Enabled/Disabled)
Allows user to set the “Total Surge Count” display to
Access Level Required: OPERATOR zero.
Allows the user to select the surge correction/avoid-
ance extended run mode. This will be implemented NAVIGATION
when an excess surge situation is detected as follows:
Home
Anytime the surge window count exceeds the count
limit, the pre-rotation vanes are driven closed for the Access Level Required: VIEW
next ten (10) minutes. While this load inhibit is in ef- Returns the display to the Home screen
fect, “WARNING – SURGE PROTECTION – EX-
CESS SURGE LIMIT’ is displayed. When ten (10) Compressor
minutes have elapsed, the warning message and load
inhibit are automatically cleared, provided the surge Access Level Required: VIEW
window count is less than or equal to the count limit. Returns the display to the Compressor screen.
If the shutdown setpoint is enabled and the surge win-
dow count exceeds the count limit after the ten minutes
elapse, a safety shutdown is performed and “SURGE
PROTECTION – EXCESS SURGE” is displayed.
There are several exceptions related to VSD and/or hot
gas bypass equipped chillers for extended run to oper-
ate. See the exceptions listed under “Shutdown”.
42 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
LD26953
JOHNSON CONTROLS 43
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
Access Level Required: Operator This key enables standby lubrication by setting how of-
ten you want the oil pump to come on when the chiller
This key allows the oil pump to be manually activated. has been offline. If the chiller runs before the time pe-
The oil pump will run for ten (10) minutes when man- riod elapses then the timer will be reset. The time is
ual pump is “Enabled”. After ten minutes, the display between 2 hours and 12 hours in 2 hour increments.
will revert to “Disabled”. If a longer run time is desired By selecting Disabled it will prevent the oil pump from
the manual pump must be enabled again when the time running when the chiller is off for an extended period
has elapsed. Manual oil pump control is only available of time.
when the chiller is stopped. The Manual Pump key is
not displayed during system prelube, system run and Change Setpoint
system coastdown.
Access Level Required: VIEW
Low Pressure Limit Allows the login password to be entered to change
Access Level Required: Service oil pump settings. This button is only present at the
“View” access level.
Allows the minimum oil pressure the system is permit-
ted to operated at to be adjusted. This setting can be NAVIGATION
adjusted from 10.0 PSID to 40.0 PSID, with 25.0 PSID
as the default setting. Home
Access Level Required: VIEW
Prelube Time
Returns the display to the Home screen.
Access Level Required: Service
Allows the system prelube time to be adjusted from 15
seconds to 60 seconds. The default setting is 30 sec-
onds.
Coastdown Time
Access Level Required: Service
Allows the system coastdown time to be adjusted from
150 seconds to 600 seconds. The default setting is 150
seconds.
44 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
LD26954
JOHNSON CONTROLS 45
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
Change Setpoint
Access Level Required: VIEW
Allows user to enter login password to change motor
settings. This button is only present at the “View” ac-
cess level.
46 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
LD10001
JOHNSON CONTROLS 47
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
Access Level Required: OPERATOR Defines the maximum allowed motor starting inrush amps.
The solid state starter will limit the motor starting current
Allows the maximum allowed motor current (as a to this value. The starting current can be adjusted from 310
percentage of FLA) to be adjusted. When the motor Amps to 3300 Amps; 310 Amps is the default value. Ser-
current reaches this value, the pre-rotation vanes will vice technicians refer to the Solid State Starter MOD “B”
not open further. If the motor current rises above this – Operation/Service Manual (Form 160.00-O2).
value, the pre-rotation vanes will close to reduce cur-
rent to this setpoint. This value is adjustable from 30 to Open SCR (Enabled/Disabled)
100%, with 100% as the default setting.
Access Level Required: SERVICE
Pulldown Demand Limit Allows the user to enable or disable the solid state starter
Access Level Required: OPERATOR Open SCR safety detection. This must never be disabled
unless under advisement of the YORK Factory. Service
This setpoint limits the motor current (programmed as technicians refer to the Solid State Starter MOD “B” –
a percentage of FLA) during the specified pulldown Operation/Service Manual (Form 160.00-O2).
demand time. This value will override the motor cur-
rent limit value during this time period. This function is Shorted SCR (Enabled/Disabled)
used to provide energy savings following chiller start-
up and is adjustable from 30 to 100%, with 100% as Access Level Required: SERVICE
the default setting. Allows the user to enable or disable the Solid State Starter
Shorted SCR safety detection. This setpoint must never
Pulldown Demand Time be disabled unless under advisement of the York Factory.
Access Level Required: OPERATOR Service technicians refer to the Solid State Starter MOD
“B” – Operation/Service Manual (Form 160.00-O2).
This setpoint programs the period of time the pulldown
demand limit will be in effect after the chiller starts. kWH Reset
The pulldown demand time is adjustable from 0 to 255
minutes, with 0 minutes as the default. Access Level Required: SERVICE
Allows the user to reset the cumulative kilowatt-hours
Full Load Amps to zero (0). Service technicians refer to the Solid State
Access Level Required: SERVICE Starter MOD “B” – Operation/Service Manual (Form
160.00-O2).
Defines the maximum amps at which the motor can
operate. This value is displayed when logged in at “Op- Change Setpoint
erator” or “View” access level. This value is adjust-
able from 35 Amps to 1050 Amps; 35 Amps is the de- Access Level Required: VIEW
fault value. Service technicians refer to the Solid State Allows user to enter login password to change motor
Starter MOD “B” – Operation/Service Manual (Form settings. This button is only present at the “View” ac-
160.00-O2). cess level.
48 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
LD10002
JOHNSON CONTROLS 49
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
Pre-Rotation Vane Position The pulldown demand time is adjustable from 0 to 255
Displays the pre-rotation vane position as a value be- minutes, with 0 minutes as the default.
tween 0 and 100%.
kWH Reset
Supply kVA Access Level Required: SERVICE
Displays the supply kilovolt-amps (kVA) measured by Allows the user to reset the cumulative kilowatt-hours
the filter (harmonic filter installed only). to zero (0). Service technicians refer to the OptiView
Control Center Retrofit Kit - Trane Service Manual
Total Power Factor (Form 160.10-M1).
Displays the relationship between the input power and
the supply kVA (harmonic filter installed only). Filter Inhibit (Harmonic Filter installed only)
Access Level Required: SERVICE
Voltage Total Harmonic Distortion –
(L1, L2, L3) Allows operator to enable or disable the filter logic
from activating, although the system will still commu-
Displays the Total Harmonic Distortion (THD) for
nicate with the device. Access to this setting is only
each of the voltage lines as calculated by the filter (har-
available when chiller is stopped.
monic filter installed only).
Change Setpoint
Supply Current Total Demand Distortion –
(L1, L2, L3) Access Level Required: VIEW
Displays the Total Dynamic Distortion (TDD) for each Allows user to enter login password to change motor
of the supply current lines as calculated by the filter settings. This button is only present at the “View” ac-
(harmonic filter installed only). cess level.
PROGRAMMABLE NAVIGATION
Local Motor Current Limit Home
Access Level Required: OPERATOR Access Level Required: VIEW
Allows the maximum allowed motor current (as a Returns the display to the Home screen.
percentage of FLA) to be adjusted. When the motor
current reaches this value, the pre-rotation vanes will VSD Details
not open further. If the motor current rises above this
Access Level Required: VIEW
value, the pre-rotation vanes will close to reduce cur-
rent to this setpoint. This value is adjustable from 30 to Advances to the sub-screen which provides more in-
100%, with 100% as the default setting. formation about the VSD.
50 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
LD09096
JOHNSON CONTROLS 51
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
52 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
00665VIP
JOHNSON CONTROLS 53
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
Home
VSD Model
Access Level Required: VIEW
Access Level Required: SERVICE
Returns the display to the Home Screen.
Displays the horsepower configuration of the VSD
control. The VSD transmits the model number to the VSD
OptiView panel.
Access Level Required: VIEW
Full Load Amps Returns the display to the VSD Screen.
Displays the Full Load Amps (FLA) value reported by
the VSD to the OptiView Control Center.
PROGRAMMABLE
54 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
LD23598
JOHNSON CONTROLS 55
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
56 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
00315VIP
JOHNSON CONTROLS 57
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
Displays the 3-phase peak voltages as measured by the Access Level Required: OPERATOR
harmonic filter (neutral to line). This setpoint programs the period of time the pulldown
demand limit will be in effect after the chiller starts.
RMS Voltage (L1-L2, L2-L3, L3-L1) The pulldown demand time is adjustable from 0 to 255
Displays the 3-phase RMS voltages across each line. minutes, with 0 minutes as the default.
58 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
00664VIP
JOHNSON CONTROLS 59
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
Displays the 3-phase RMS voltages across each line. This setpoint programs the period of time the pulldown
demand limit will be in effect after the chiller starts.
Voltage Total Harmonic Distortion (L1, L2, L3) The pulldown demand time is adjustable from 0 to 255
minutes, with 0 minutes as the default.
Displays the 3-phase voltage Total Harmonic Distor-
tion (THD) measurements. NAVIGATION
RMS Filter Current (L1, L2, L3) Home
Displays the 3-phase filter current values as measured Access Level Required: VIEW
by the harmonic filter.
Returns the display to the Home screen.
Supply Current Total Demand Distortion
(L1, L2, L3) VSD
Displays the 3-phase current Total Demand Distortion Access Level Required: VIEW
(TDD) measurements. Returns the display to the VSD screen.
RMS Supply Current (L1, L2, L3)
Displays the 3-phase RMS voltages across each line.
60 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
LD23599
JOHNSON CONTROLS 61
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
62 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
NAVIGATION
Home
Access Level Required: VIEW 2
Returns the display to the Home screen.
Motor
Access Level Required: VIEW
Returns the display to the Motor screen.
JOHNSON CONTROLS 63
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
SETPOINTS SCREEN
ID10004
64 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
due to over-cooling. This value is calculated by adding • For example, if the range is programmed for 10°F
the Leaving Chilled Liquid Temperature Cycling Off- and the locally programmed value of the chilled
set Restart to the Leaving Chilled Liquid Temperature liquid temperature is 45°F, then the remote device
Setpoint. is able to change and set the leaving chilled liquid 2
temperature setpoint over the range 45.0° - 55.0°F.
Leaving Chilled Liquid Temperature Cycling –
Restart Offset A remote device that provides an analog signal (0-
20mA, 4-20mA, 0-10VDC or 2-10VDC) in analog re-
Displays the programmed number of degrees the mote mode or a PWM signal in digital remote mode
chilled liquid is permitted to reach above the leaving defines the setpoint change as an offset value.
chilled liquid temperature setpoint before the chiller
will restart. • For example, if the setpoint is 45.0°F and the de-
sired setpoint is 50.0°F, then 5.0°F would be the
Current Limit Setpoint input on the remote device.
Displays the active current limit setpoint, as a percent- A MicroGateway (in ISN Remote mode) can define the
age of full load amps. In local mode, this is the local- setpoint through a serial data stream. In this case, the
ly programmed current limit setpoint. In ISN remote incoming setpoint is not an offset that is applied to the
mode, this is the setpoint received from the Micro- leaving chilled liquid temperature setpoint value, but is
Gateway interface. In analog remote mode, this is the the actual setpoint value.
setpoint received via 0-10VDC, 2-10VDC, 0-20mA or
4-20mA input. In digital remote mode, this is a Pulse Leaving Chilled Liquid Temperature Cycling
Width Modulation (PWM) signal input. Offset – Restart
JOHNSON CONTROLS 65
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
66 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
SETUP SCREEN
LD26950
JOHNSON CONTROLS 67
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
68 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
Printer
Access Level Required: VIEW
Advances to the sub-screen allowing configuration and
2
control of printer functions.
Sales Order
Access Level Required: VIEW
Advances to the sub-screen displaying the original
Sales Order information for the chiller system.
Operations
Access Level Required: VIEW
Advances to the sub-screen displaying operating pa-
rameters of the chiller system.
Diagnostics
Access Level Required: SERVICE
Advances to the diagnostic sub-screen, which allows
viewing of OptiView software versions. Also allows
for analog and digital input/output diagnostic capa-
bility while operating. Refer to the OptiView Control
Center Retrofit Kit - Trane Service Manual (Form
160.10-M1).
JOHNSON CONTROLS 69
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
SCHEDULE SCREEN
ID10011
70 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
JOHNSON CONTROLS 71
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
USER SCREEN
ID10006
72 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
NAVIGATION
Home
Access Level Required: VIEW 2
Returns the display to the Home screen.
Setup
Access Level Required: VIEW
Returns the display to the Setup screen.
JOHNSON CONTROLS 73
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
COMMS SCREEN
ID10007
74 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
munication.
NAVIGATION
Home
Access Level Required: VIEW
Returns the display to the Home screen.
Setup
Access Level Required: VIEW
Returns the display to the Setup screen.
JOHNSON CONTROLS 75
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
PRINTER SCREEN
ID10009
This setting allows the start time of scheduled print This feature is only available if the chiller system uti-
logs to be programmed lizes a Variable Speed Drive (VSD) motor controller.
The chiller monitors the ACC communications and
Output Interval when a surge point is mapped, a short report of system
parameters is printed.
Access Level Required: OPERATOR
This setting defines the amount of time between each
scheduled automatic print log.
76 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
When the ACC auto map print feature is Access Level Required: VIEW
enabled, all other printing capability is Returns the display to the Home screen.
disabled.
Setup
Access Level Required: VIEW
Returns the display to the Setup screen.
Print Report
Access Level Required: OPERATOR
Selects the report type to print when the “Print Report”
key is pressed. This parameter can be selected from the
following:
• Status report (present system parameters)
• Setpoints report (present value of the system
setpoints)
• Schedule report (present value of the system
schedule times)
• Sales Order Data report (information provided on
the Sales Order screen).
A print report is generated upon completion of selec-
tion.
JOHNSON CONTROLS 77
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
ID10010
PROGRAMMABLE
78
JOHNSON CONTROLS 78
JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
NAVIGATION
Home
Access Level Required: VIEW 2
Returns the display to the Home screen.
Setup
Access Level Required: VIEW
Returns the display to the Setup screen.
JOHNSON CONTROLS 79
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
DIAGNOSTICS SCREEN
LD26951
OVERVIEW GPIC
The Diagnostics screen identifies software version in- Displays the EPROM installed in the MicroGateway,
formation. This screen also serves as a gateway to view as equipped.
analog and digital input/output screens.
PROGRAMMABLE
Requires a login access level of SERVICE None
to view. Service technicians refer to Op-
tiView Control Center Retrofit Kit - Trane NAVIGATION
Service Manual (Form 160.10-M1) for
further explanation of displayed values. Home
Access Level Required: VIEW
Returns the display to the Home screen.
DISPLAY ONLY
Controls Setup
Displays version of flash software installed/loaded into Access Level Required: VIEW
the microboard. Returns the display to the Setup screen.
BIOS (Basic Input/Output Software) Analog I/O
Displays the version of the BIOS EPROM installed in
the microboard. Access Level Required: SERVICE
Advances to a sub-screen which details voltage levels
Kernal and counts for internal and external analog inputs.
Displays the operating system core components in-
stalled/loaded into the microboard.
80 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
Digital I/O
Access Level Required: SERVICE
Advances to a sub-screen which indicates activity for
2
digital inputs and outputs.
VSD Comms
Access Level Required: SERVICE
This key is only available if the chiller is equipped with
a VSD. This advances to a sub-screen which details
VSD and ACC error statistics.
JOHNSON CONTROLS 81
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
ID10022
OVERVIEW NAVIGATION
This screen displays voltage and counts for the analog Home
inputs and outputs connected to the OptiView Control
Center. This screen is useful for service technicians Access Level Required: VIEW
checking voltage of analog inputs and outputs. Returns the display to the Home screen.
DISPLAY ONLY This key toggles the analog screen from the internal
input/output view to the external (analog I/O board)
Voltage and counts for internal and external analog in- input view.
puts are displayed.
Internal
PROGRAMMABLE
Access Level Required: SERVICE
None
This key toggles the analog screen from the external
input/output view to the internal input view.
82 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
ID10023
OVERVIEW PROGRAMMABLE
This screen displays the activity for each of the digital None
inputs and outputs that are connected to the OptiView
Control Center. The digital screen is useful to service NAVIGATION
technicians checking operation of digital inputs and
Home
outputs as well as program jumper and switch posi-
tions. Access Level Required: VIEW
Requires a login access level of SERVICE Returns the display to the Home screen.
to view. Service technicians refer to Op-
tiView Control Center Retrofit Kit - Trane Diagnostics
Service Manual (Form 160.10-M1) for
Access Level Required: VIEW
further explanation of displayed values.
Returns the display to the Diagnostics screen.
External
DISPLAY ONLY
Access Level Required: SERVICE
This screen displays each of the internal and external
digital input/outputs connected to the OptiView Con- This key toggles the display from internal input/output
trol Center. An LED beside each input/output indicates view to the external I/O board view.
activity. The tag beside each LED indicates that the in-
put/output is a DIP switch, a jumper (JP), a relay (K), Internal
a Terminal (TB#) or the channel for the external digital Access Level Required: SERVICE
input/output view.
This key toggles the display from external input/output
channels to internal input/output view.
JOHNSON CONTROLS 83
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
ID10024
84 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
OPERATIONS SCREEN
LD26952
JOHNSON CONTROLS 85
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
Chiller Model
Access level required: SERVICE
The chiller model key allows the selection of the chill-
er model. The OptiView operating program controls
the chiller per the requirements of the entered model.
NAVIGATION
Home
Access Level Required: VIEW
Returns the display to the Home screen.
Setup
Access Level Required: VIEW
Returns the display to the Setup screen.
86 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
HISTORY SCREEN
ID10013
JOHNSON CONTROLS 87
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
Select Fault
Access Level Required: VIEW
Select Fault allows the user to choose the details or his-
tory that is viewed or printed when the “View Details”
or “Print History” key is selected.
NAVIGATION
Home
Access Level Required: VIEW
Returns the display to the Home screen.
View Details
Access Level Required: VIEW
Advances to a sub-screen containing the value of select
chiller parameters at the time of the associated shut-
down.
Trending
Access Level Required: VIEW
Advances to the Trending sub-screen, allowing the
user to view trending data per user-defined chiller pa-
rameters.
Custom View
Access Level required: VIEW
Advances the panel display to the Custom View screen.
88 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
00660VIP
OVERVIEW NAVIGATION
This screen allows the user to view all the system pa- Home
rameters at the time of the shutdown selected on the
history screen. Not all screens are shown above; the Access Level Required: VIEW
number of screens required to display all of the data Returns the display to the Home screen.
varies with differences in motor starters and options
applied. History
JOHNSON CONTROLS 89
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
00324VIP
OVERVIEW NAVIGATION
This screen displays up to ten (10) user-selected pa- Home
rameters to be displayed simultaneously. These param-
eters are selected at the custom view “Setup” screen. Access Level Required: VIEW
This feature is useful to display parameters pertinent Returns the display to the Home screen.
to a particular problem during service troubleshooting.
Once the problem has been resolved, the display can be History
cleared or the parameters can be left there for monitor-
Access Level Required: VIEW
ing by chiller operating personnel.
Returns the display to the History screen.
DISPLAY ONLY
Setup
None
Access Level Required: SERVICE
PROGRAMMABLE Advances to a sub-screen that allows selection of cus-
Print tom view display parameters.
90 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
00325VIP
JOHNSON CONTROLS 91
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
NAVIGATION
Home
Access Level Required: VIEW
Returns the display to the Home screen.
Custom View
Access Level Required: SERVICE
Returns the display to the Custom View screen.
92 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
TREND SCREEN
LD10015
JOHNSON CONTROLS 93
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
PROGRAMMABLE NAVIGATION
Start Home
Access Level Required: OPERATOR Access Level Required: VIEW
Pressing this key clears and starts a new graph, sets the Returns the display to the Home screen.
time of day to the present clock time and begins the
trending data collection. This key is only available if History
trending is stopped. Access Level Required: VIEW
Stop Returns the display to the History screen.
X-Axis
Access Level Required: VIEW
This key toggles the X-Axis labels of the graph. Each
key press alternates the scaling between time of day
and elapsed time. The “Time of Day” scaling is in 24-
hour format. The “Elapsed Time” scaling is the time
elapsed since the “Start” key was pressed, starting the
trending.
94 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
LD10020
JOHNSON CONTROLS 95
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
Select the desired data collection interval as follows: Data Point Maximum (1-6)
1. Determine the desired time interval (in seconds), Access Level Required: OPERATOR
between data samples. This is the maximum value displayed for the Y-Axis.
2. Calculate the full screen time display as follows: Selecting a parameter for a data point sets this to the
default value, which is the highest value allowed for
• 450 x Data Collection Interval = full screen that particular parameter. This can be changed to a val-
seconds ue that provides a more appropriate resolution for the
• full screen seconds / 60 = full screen minutes parameter being monitored. Data Point Maximum is
only displayed if the associated slot number is not zero.
• full screen minutes / 60 = full screen hours
To change this setting, use the “Select” key as described
• full screen hours / 24 = full screen days previously and enter the desired value. The value must
3. View the resulting sample interval and full screen always be set to a value greater than the data point
display to determine if the data display meets the minimum. Otherwise, a red graph is displayed on the
desired requirements. Trend screen with the words “TREND MAX MUST
BE > TREND MIN”. There are twenty (20) Y-Axis
Select divisions. If a MIN-MAX span is selected that is not
evenly divided by 20, the program will automatically
Access Level Required: OPERATOR
select the next higher MAX value that makes the span
The Select key is used to enter the slot numbers and evenly divided.
the minimum and maximum Y-Axis values of each pa-
rameter. Pressing this key places a yellow box around • For example: If 0.0 is selected as the MIN and
Data Point 1 Slot Number. Use the ▲ and ▼ cursor 69.0 is selected as the MAX, the program will in-
arrow keys to select the box for the Data Point(s) to be sert 70.0 as the MAX value. If the parameter se-
changed. Data Point Slots one through six may be pro- lected for this data point is a digital type (on/off),
grammed. With the desired value highlighted, press the this value must be set to one (1). One indicates the
‘ü’ (Enter) key. A dialog box is displayed permitting “ON” state.
entry of the slot number or data point min and max.
NAVIGATION
Press the ‘ü’ (Enter) once the desired slot number has
been entered. Setting the slot number to zero will dis- Home
able trending for that particular data point. Any or all
points can be disabled. Access Level Required: VIEW
Returns the display to the Home screen.
Data Point Minimum (1-6)
Trending
Access Level Required: OPERATOR
This is the minimum value displayed for the Y-Axis. Access Level Required: OPERATOR
Selecting a parameter for a data point sets this to the Returns the display to the Trending screen.
default value, which is the lowest value allowed for
that parameter. This can be changed to a value that pro- Slot #s (Numbers)
vides a more appropriate resolution for the parameter
Access Level Required: OPERATOR
being monitored. This key is not displayed when the
slot # for the data point is set to zero (0). Advances to the Trend Common Slots sub-screen. The
desired parameters to be plotted are selected from this
Use the “Select” key as described above to enter the screen.
desired value. The value must always be set to a value
less than the data point maximum. Otherwise, a red
graph is displayed on the Trend screen with the words
“TREND MAX MUST BE > TREND MIN”. If the pa-
rameter selected for this data point is a digital type (on/
off), this value must be set to zero (0). Zero indicates
the digital input/output is in the “OFF” state.
96 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
00328VIP
OVERVIEW NAVIGATION
This screen displays the slot numbers of the commonly Page Down
monitored parameters used for trending or custom view
and are listed on this screen by chiller component. The Access Level Required: OPERATOR
slot numbers for the remainder of the available param- Scroll down in the displayed data.
eters are listed on the “Master Slot Numbers List”.
Page Up
This screen requires a login access level Access Level Required: OPERATOR
of OPERATOR or higher to view.
Scroll up in the displayed data.
Home
Access Level Required: VIEW
Returns the display to the Home screen.
DISPLAY ONLY
Trend Setup
Slot Numbers
These are the slot numbers of the most commonly used Access Level Required: OPERATOR
parameters. Returns the display to the Trend Setup screen.
JOHNSON CONTROLS 97
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
Table 1 - MASTER SLOT NUMBERS LIST (FOR USE WITH TREND FEATURES)
98 JOHNSON CONTROLS
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
JOHNSON CONTROLS 99
FORM 160.10-O1
SECTION 2 - OPTIVIEW OPERATION
ISSUE DATE: 4/27/2018
ten to a location in the microboard battery backed Table 4 - EVAPORATOR PRESSURE THRESHOLDS
memory device (BRAM). This data is then read from
the BRAM and compared to the test data. If the read WARNING THRESHOLD RESET THRESHOLD
(PSIA) (PSIA)
data is not the same as what was written to the device,
Refrig. Water Brine Water Brine
the control center assumes the BRAM (and Real time
Clock operation) is defective and this message is dis- R11 5.5 0.1>Safety 5.6 0.3>Safety
Setpoint Setpoint
played. The BRAM should be replaced by a qualified 3
service technician. This message automatically clears R123 4.5 0.1>Safety 4.7 0.3>Safety
Setpoint Setpoint
when the BRAM problem has been solved.
Warning – Setpoint Override The compressor motor variable speed drive (VSD) is
operating in FIXED SPEED (full speed) mode because
A blank BRAM battery-backed memory device or a the pre-rotation vanes position potentiometer calibra-
failure of this device was detected during the initial- tion has not been performed.
ization process that occurs when power is applied to
the control center. Because of this failure, any or all of Warning – Harmonic Filter –
the programmed setpoints may be corrupted. For safety Operation Inhibited
purposes, all setpoints are automatically changed to de-
The compressor motor VSD harmonic filter has been
fault values. All setpoints will have to be programmed
inhibited. Refer to the Variable Speed Drive – Service
to their desired values. This message will clear when
Manual (Form 160.00-M1). Harmonic filter operation
the WARNING RESET key is pressed (Operator or
should not be altered by anyone other than a qualified
higher access mode).
service technician.
Warning – Evaporator –
Warning – Harmonic Filter – Data Loss
Low Pressure Limit
Communication between the harmonic filter logic
The evaporator pressure has decreased to the warning
board and the VSD logic board or the ACC board can-
threshold. This threshold is fixed in water cooling ap-
not be detected. While this condition exists, all filter
plications. In brine cooling applications, the threshold
related parameters are displayed as X’s. This message
is a fixed amount above the programmable safety shut-
automatically clears when communications are re-
down threshold. The safety threshold in brine applica-
stored.
tions is dependent upon the brine solution concentra-
tion and is determined by the YORK Factory. While Warning – Vanes Uncalibrated
this condition is in effect, the pre-rotation vanes are in-
hibited from opening further. This message automati- The hot gas bypass feature is enabled, but the pre-
cally clears and the vanes are permitted to open when rotation vanes calibration procedure has not yet been
the evaporator pressure increases to the reset value. performed.
or 49 to 51 Hz (50 Hz). While this condition exists, Warning – Purge – Float Switch
all harmonic filter related parameters are displayed as Error (Turboguard II Units Only)
X’s. This message automatically clears when the line This message is displayed while the chiller is running
frequency is within range. and the purge float switches are in invalid states. Typi-
cally, this is caused by the bottom float switch being in
Warning – Surge Protection –
the closed position and the top float switch in the open
Excess Surge Limit
position, indicating the oil level is simultaneously be-
(Applies only if surge protection EXTENDED RUN low the bottom switch and above the top switch. This
feature is enabled) message will be displayed until the float switches are
If the optional hot gas bypass feature is indicating valid positions (or the chiller is not running)
enabled, the valve position must be at and the WARNING RESET key is pressed on the Home
100% before “Extended Run” is imple- screen. While this message is displayed, the purge oil
mented. If the chiller is equipped with a solenoid valve is de-energized, draining the purge tank.
VSD, the output frequency must be at full
speed (50 Hz/60 Hz) before this control Warning – Excess Purge
can be implemented. (Turboguard II Units Only)
The purge EXHAUST COUNT has equaled the pro-
Displayed during the surge protection ten (10) min- grammed MAXIMUM PURGES PER HOUR set-
ute extended run period. This period begins when the point. Purge operation continues while this message
SURGE WINDOW COUNT exceeds the COUNT is displayed, but the exhaust count is not incremented.
LIMIT. During this period, the pre-rotation vanes are Clearing this message resets the exhaust count and
driven closed. When the ten minutes elapse, this mes- exhaust window. If the chiller is running, the exhaust
sage and the pre-rotation vanes load inhibit are auto- window will then increment from 0 to 60 minutes and
matically cleared. The warning message and load in- the exhaust count will increment as exhausts occur.
hibit are also cleared when the chiller is shutdown. This message will be displayed until the WARNING
RESET key is pressed on the Home screen.
Warning – Purge – High Pressure
(Turboguard Ii Units Only) Warning – External I/O – Serial
With the chiller running, the purge pressure increased Communications
above the high pressure limit (95.0 PSIA, high effi- This message indicates serial data communications be-
ciency TGII purge units) continuously for four (4) min- tween the microboard and analog I/O board have been
utes. This message is displayed until purge pressure de- interrupted for longer than twenty (20) seconds.
creases below the high pressure limit or the chiller is
stopped and the WARNING RESET key is pressed on ROUTINE SHUTDOWN MESSAGES
the Home screen. This warning will not be displayed
if the PURGE FLOAT SWITCH ERROR warning Remote Stop
is triggered. This message indicates that a STOP command has
been received from a remote device. Remote stop
Warning – Purge – Canister #1 Full commands can be received in digital remote mode via
This message is triggered when the purge canister I/O Board TB4-7/8 or in ISN (Integrated Systems Net-
alarm output increases to 2.20V or above, indicating work) remote mode via the MicroGateway serial com-
the canister has reached full capacity. The canister munications. If the chiller is running when this occurs,
must be replaced following instructions on label inside the pre-rotation vanes are driven fully closed prior to
purge panel door. This message will be displayed until shutdown.
the alarm signal is 0.90 VDC or below and the WARN-
ING RESET key is pressed on the Home screen. Local Stop
A local STOP command has been received, indicating
the compressor switch in the STOP/RESET (O) posi-
tion.
Place Compressor Switch In Run down the chiller, if running. The chiller will automati-
Position cally restart when the liquid temperature increases to
The control center is in either digital or ISN (Integrated the programmed restart temperature setpoint.
Systems Network) remote mode. The operator is re-
Leaving Chilled Liquid – Flow Switch Open
quested to place the compressor switch in the RUN
position. The control center will not accept a remote The chilled liquid flow switch has remained open for 2
start/stop command unless the switch is in the RUN continuous seconds while the chiller was running or failed 3
position. to close during the system prelube period. The chiller will
automatically restart when the flow switch closes.
CYCLING SHUTDOWN MESSAGES
Condenser – Flow Switch Open
Multiunit Cycling – Contacts Open
The condenser water flow switch has remained open
The multiunit cycling contacts connected to I/O board for 2 continuous seconds while the chiller was running.
TB4-9, have opened to initiate a cycling shutdown. This check is bypassed for the first thirty (30) seconds
The pre-rotation vanes are driven fully closed prior to of SYSTEM RUN. The chiller will automatically re-
shutting down the chiller. The chiller will automati- start when the flow switch closes.
cally restart when the contacts close.
Motor Controller – Contacts Open
System Cycling – Contacts Open
This indicates the CM-2 current module (E-M starter
The system cycling contacts connected to I/O board applications) has shutdown the chiller. If a condition
TB4-13, have opened to initiate a cycling shutdown. that places the starter or motor at risk is detected, the
The pre-rotation vanes are driven fully closed prior to CM-2 module opens the motor controller contacts CM
shutting down the chiller. The chiller will automati- to initiate a shutdown. The CM-2 board LED’s will il-
cally restart when the contacts close. luminate to identify the specific fault that has occurred.
The chiller will automatically restart when the motor
Oil – Low Temperature controller contacts close. Refer to the OptiView Con-
This message indicates the oil temperature has de- trol Center Retrofit Kit - Trane Service Manual (Form
creased below 55.0°F. The chiller will automatically 160.10-M1) for more information.
restart when the temperature increases above 71.0°F.
Starter – Low Supply Line Voltage
Control Panel – Power Failure This message indicates that a voltage for a phase is low-
A power failure to the OptiView Control Center has er than the allowable limit for more than twenty (20)
occurred. If the power failure occurred while the chill- seconds. This fault can occur at chiller startup or after
er was running, the control center will automatically the chiller has been running for one minute. The fault is
restart (auto-restart enabled) when power is restored. released when the voltage for the phase increases above
However, if the duration of the power failure was less the limit starting. Refer to Table 5.
than the applicable SYSTEM COASTDOWN period
when power is restored, the remainder of the coastdown Table 5 - STARTER - LOW SUPPLY LINE
will be performed. This message indicates a cycling VOLTAGE LIMITS
shutdown when displayed in orange characters and a SUPPLY LIMIT LIMIT
safety shutdown when displayed in red characters. The VOLTAGE STARTING RUNNING
control center is configured for chiller auto-restart or 200 - 208 Volts 174 V 160 V
manual restart after power failure by a qualified service
220 - 240 Volts 200 V 185 V
technician following instructions in the OptiView Con-
380 Volts 331 V 305 V
trol Center Retrofit Kit - Trane Service Manual (Form
160.10-M1). 400 Volts 349 V 320 V
415 Volts 362 V 335 V
Leaving Chilled Liquid – Low Temperature 440 - 480 Volts 400 V 370 V
The leaving chilled liquid temperature has reached the 550 - 600 Volts 502 V 460 V
programmed shutdown temperature setpoint. The pre-
rotation vanes are driven fully closed prior to shutting
Starter – High Supply Line Voltage MOD B SOLID STATE STARTER CYCLING
This message indicates that a voltage for a phase is SHUTDOWN MESSAGES
greater than the allowable limit for more than twenty LCSSS Initialization Failed
(20) seconds. This fault can occur at chiller startup or
after the chiller has been running for one minute. The When power is restored to the system after a power
fault is released when the voltage for the phase falls failure, an initialization process occurs wherein the
below the limit when starting. Refer to Table 6. control center attempts to establish a link with the Liq-
uid Cooled Solid State Starter (LCSSS) through serial
Table 6 - STARTER - HIGH SUPPLY LINE communications If communications are not established
VOLTAGE LIMITS within 10 consecutive attempts, a Cycling Shutdown is
performed and this message is displayed. The control
SUPPLY LIMIT LIMIT
VOLTAGE STARTING RUNNING
center attempts to establish communications until suc-
cessful.
200 - 208 Volts 226 V 227 V
220 - 240 Volts 261 V 262 V LCSSS – Serial Communications
380 Volts 414 V 415 V
After communications have been successfully estab-
400 Volts 435 V 436 V
lished in the INITIALIZATION process, the OptiView
415 Volts 453 V 454 V Control Center transmits to the solid state starter on the
440 - 480 Volts 523 V 524 V serial communications link every two (2) seconds. Af-
550 - 600 Volts 654 V 655 V ter these communications have been established, if the
control center does not receive a reply within ten (10)
consecutive attempts, a cycling shutdown is performed
Motor Controller – Loss Of Current and this message is displayed. This same cycling shut-
This message indicates that compressor motor current down is performed, along with the same message, if
decreased to 10% Full Load Amps (FLA) for 25 con- the solid state starter does not receive a response from
tinuous seconds while the chiller was running. This the control center after ten (10) consecutive attempts
may be caused by the starter de-energizing during run to communicate with the control center. The control
or a defect in the motor current feedback circuitry to center will attempt to establish communications until
the control center. The chiller will automatically restart successful.
at the completion of SYSTEM COASTDOWN.
LCSSS SHUTDOWN – REQUESTING FAULT
Power Fault DATA...
This message indicates the CM-2 current module (Electro- The liquid cooled state starter logic/trigger board has
mechanical starter applications) has shutdown the chiller shut down the chiller but the OptiView Control Center
because a fault condition that places the chiller motor at has not yet received the cause of the fault from the LC-
risk has been detected. This device opens and closes the SSS, via the serial communications link. The LCSSS
motor controller CM contacts (located on the CM-2 board shuts down the chiller by opening the motor control-
and connected between TB6-16 and TB6-53 in the Con- ler lcsss stop contacts (K1 relay located on the starter
trol Center) in less than three (3) seconds to initiate the logic/trigger board and connected between TB6-16 and
shutdown and produce this message. One of three LEDs TB6-53 in the control center). The control center mi-
on the device will illuminate to identify the specific fault croboard then sends a request for the cause of the fault
that has occurred. Refer to the OptiView Control Center to the logic/trigger board over the serial communica-
Retrofit Kit - Trane Service Manual (Form 160.10-M1) tions link. Since serial communications are initiated
for CM-2 initiated shutdown details. The chiller will au- every two (2) seconds, this message is typically dis-
tomatically restart when the contacts close. played for a few seconds and then replaced with one of
the following fault messages.
Control Panel – Schedule
LCSSS – STOP CONTACTS OPEN
The programmed daily schedule setpoint has shutdown
the chiller. Prior to shutdown, the pre-rotation vanes Refer to LCSSS SHUTDOWN – REQUESTING
are driven fully closed. The chiller will automatically FAULT DATA ... described previously. If the Con-
restart at the next scheduled start time. trol Center’s Microboard does not receive the cause
of a starter initiated shutdown with twenty (20) sec- 33L-215 to 1050A. The chiller will be permitted to
onds of the shutdown, the microboard assumes the start when the jumpers are configured correctly. Re-
cause is not forthcoming and that message is re- fer to the Solid State Starter MOD “B” – Operation/
placed with this message. The chiller can be started Service Manual (Form 160.00-O2) for valid jumper
when the motor controller LCSSS stop contacts close. configurations.
A missing interlock jumper between starter logic/
trigger board J1-1 and J1-12 will also produce this LCSSS – PHASE LOCKED LOOP 3
message. The liquid cooled solid state starter logic/trigger board
phase locked loop circuit was not able to maintain lock
LCSSS – POWER FAULT with phase A of the power line. This could be caused
The liquid cooled solid state starter logic/trigger board by a power line anomaly such as sag or jitter. A power
has detected that the compressor motor current in one line frequency jitter of up to 3 Hz/second can be toler-
or more phases has decreased to less than 10% of the ated. The chiller will automatically restart when lock
FLA for a minimum of one (1) line cycle. This check is has resumed.
inhibited during the first four (4) seconds of chiller op-
eration and until the motor current is above 25% of the LCSSS – LOGIC BOARD PROCESSOR
Job FLA. The chiller will automatically restart upon Communication between the V25 Microprocessor and
completion of SYSTEM COASTDOWN. Digital Signal Processor (DSP) on the liquid cooled
solid state starter logic/trigger board has been inter-
LCSSS – LOW PHASE (X) TEMPERATURE rupted. The chiller will automatically restart when
SENSOR communications are restored.
The liquid cooled solid state starter logic/trigger board
has detected that the temperature of the starter phase LCSSS – LOGIC BOARD POWER SUPPLY
A, B or C (designated as X above) Silicon Controlled This message is displayed after a loss of power. Fol-
Rectifier (SCR) Module has decreased below 37°F. lowing application of power, this message is displayed
This would generally be indicative of a disconnected and a snapshot of the LCSSS parameters and time of
or defective sensor. If all three SCR modules are indi- power failure are sent to the control center.
cating a temperature of less than 37°F, the SCR module
cooling pump turns on. This is accomplished by dis- LCSSS – PHASE LOSS
connecting all three sensors. This feature allows ser- The liquid cooled solid state starter logic/trigger board
vice technicians to run the cooling pump while filling has detected the line-to-line RMS voltage in any phase
the cooling system by disconnecting plugs P2, P3 and has decreased to 30% or below the lowest value of the
P4 in the LCSSS. programed voltage range. If the programmed voltage
range is DISABLED, a value of 60VAC is used as the
LCSSS – RUN SIGNAL
threshold. The chiller will automatically restart when
The liquid cooled solid state starter receives two start the line voltage is higher than the shutdown threshold.
signals from the OptiView Control Center simultane- Service technicians program the voltage range follow-
ously; one via the serial communications link and one ing instructions in the Solid State Starter MOD “B” –
via the start relay TB6-24 in the control center. If the Operation/Service Manual (Form 160.00-O2).
signals are not received within 5 seconds of one anoth-
er, a cycling shutdown is performed and this message LCSSS – LOW SUPPLY LINE VOLTAGE
is displayed. This is generally indicative of defective The liquid cooled solid state starter logic/trigger board
wiring. has detected that the compressor motor AC power line
voltage, in any phase, decreased below the low line
LCSSS – INVALID CURRENT SCALE
voltage threshold continuously for twenty (20) sec-
SELECTION
onds. The chiller will automatically restart when the
There is an invalid compressor motor current scale voltage in all phases reaches the restart level. Refer to
jumper combination installed in the liquid cooled solid Table 7 for Voltage Thresholds.
starter logic/trigger board, J1. Jumper combination de-
termines allowable 100% FLA setpoint range; 7L - 35
to 260A, 14 L- 65 to 510A, 26L - 125 to 850A and
Table 7 - LCSSS LOW SUPPLY LINE VOLTAGE VSD Shutdown – Requesting Fault Data
THRESHOLDS
This message indicates the VSD has shutdown the
SUPPLY chiller on fault and the OptiView Control Center has
SHUTDOWN RESTART
VOLTAGE not received the cause of the fault from the VSD, via
(VOLTS) (VOLTS)
RANGE (VOLTS) the serial communications link. The VSD shuts down
Disabled None N/A the chiller by opening the motor controller VSD stop
200-208 160 174 contacts (located on the VSD logic board and connect-
220-240 185 200 ed between TB6-16 and TB6-53 in the control center).
380 305 331 The control center microboard then sends a request for
400 320 349 the cause of the fault to the VSD logic board via the
415 335 362 Adaptive Capacity Control board (ACC), over the se-
440-480 370 400
rial communications link. Since serial communications
are initiated every two (2) seconds, this message is typ-
550-600 460 502
ically displayed for a few seconds and then replaced
with one of the following fault messages.
LCSSS – High Supply Line Voltage
VSD – Stop Contacts Open
The liquid cooled solid state starter logic/trigger
board has detected that the compressor motor AC pow- Refer to VSD SHUTDOWN – REQUESTING
er line voltage, in any phase, exceeded the high line FAULT DATA message above. When the OptiView
voltage threshold continuously for twenty (20) seconds. microboard does not receive the cause of the fault over
The chiller will automatically restart when the voltage the serial link within twenty (20) seconds, the OptiV-
in all phases reaches the restart level. The thresholds are iew Control Center assumes the cause is not forthcom-
as follows: ing and this message is displayed.
Table 8 - LCSSS HIGH SUPPLY LINE VOLTAGE VSD – Logic Board Power Supply
THRESHOLDS This shutdown is generated by the VSD logic board,
SUPPLY indicating that the low voltage power supplies for the
SHUTDOWN RESTART logic boards have dropped below their allowable op-
VOLTAGE
(VOLTS) (VOLTS)
RANGE (VOLTS) erating limits. The logic board is supplied with power
Disabled None N/A from the 120 to 24 VAC secondary transformer, which
200-208 227 226 is supplied with power from the 480 to 120 VAC con-
220-240 262 261 trol power transformer. This message typically indi-
380 415 414
cates power to the VSD has been lost.
400 436 435
VSD – Single Phase Input Power
415 454 453
This fault is generated by the SCR trigger control and
440-480 524 523
relayed to the VSD logic board to initiate a system
550-600 655 654
shutdown. The SCR trigger control uses circuitry to
detect the loss of any one of the three input phases.
VSD CYCLING SHUTDOWN MESSAGES The trigger will detect the loss of a phase within one
half line cycle of the phase loss. This message is also
The following cycling shutdown messages are dis- displayed when power to the VSD is removed or if the
played on compressor motor Variable Speed Drive input power dips to an extremely low level.
(VSD) applications only. These messages are gener-
ated by events that occur within the VSD. The chiller VSD – Phase (X) Gate Driver
will automatically restart when the cycling condition
clears. Service and troubleshooting information is con- A second level of current protection exists for each
tained in the Variable Speed Drive – Service Manual current phase A, B, or C (designated as X above), on
(Form 160.00-M1). the VSD driver boards. The collector-to-emitter satura-
tion voltage of each Insulated Gate Bipolar Transitor
(IGBT) is checked continuously while the device is
gated on. If the voltage across the IGBT is greater than
a set threshold, the IGBT is gated off and a shutdown VSD – Low DC Bus Voltage
pulse is sent to the VSD logic board shutting down the If the DC link drops below 500 VDC (or 414 VDC
entire VSD system. A gate driver fault can be initiated for 50 Hz applications), the VSD will initiate a system
when the VSD is not running. shutdown. A common cause for this shutdown is a se-
vere sag in the incoming power to the drive. Monitor
VSD Initialization Failed
the incoming three-phase AC line and DC link for se-
Upon application of power, all VSD boards go through vere sags with a voltmeter. 3
the INITIALIZATION PROCESS. During this pro-
cess, memory locations are cleared, program jumper VSD – High DC Bus Voltage
positions are checked and serial communication links The VSD’s DC link voltage is continuously monitored
are established. There are several causes for unsuccess- and if the level exceeds 745 VDC, a bus over-voltage
ful initialization as follows: shutdown is initiated. If this shutdown occurs, the level
• The OptiView Control Center and the VSD must of the 460 VAC applied to the drive must be checked.
be energized at the same time. Pulling the fuse in The specified voltage range is 414 to 508 VAC. If the
the OptiView Control Center to remove power incoming voltage is in excess of 508 VAC, steps should
from the OptiView will create this fault. Power-up be taken to reduce the voltage to within the specified
must be accomplished by closing the main discon- limits.
nect on the VSD cabinet with all fuses in place. A
VSD – High Phase (X) Instantaneous Current
power interruption to the VSD Logic board will
also generate this message. This shutdown is generated by the VSD if the motor
current in phase A, B, or C (denoted as X above) ex-
• The Eproms must be of the correct version for ceeds a given limit. The motor current is sensed by the
each VSD board and they must be installed cor- current transformers on the VSD output pole assem-
rectly. The eproms are created as a set, and can- blies and the signals are sent to the VSD logic board
not be interchanged between earlier and later ver- for processing. Maximum instantaneous permissible
sions. currents are:
• Serial data communication must be established.
• 351/292 HP: 771 Amps
Refer to VSD – SERIAL COMMUNICATIONS
fault. If communication between the VSD logic • 503/419 HP: 1200 Amps
board, harmonic filter logic board, ACC board and
• 790/658 HP: 1890 Amps
OptiView Control Center microboard does not
take place during initialization, this message will If an overcurrent trip occurs, but the chiller restarts and
be generated. Proper serial communications can runs without a problem, the cause may be attributed
be verified by selecting the VSD DETAILS screen to a voltage sag on the utility power feeding the VSD
from the MOTOR screen and observing the FLA that is in excess of the specified voltage range. This is
value. A zero displayed for this and other VSD pa- especially true if the chiller was running at or near full
rameters, indicates a serial communications link load. If there is a sudden dip in line voltage, the cur-
problem. rent to the motor will increase, since the motor wants
to draw constant horsepower. The chiller pre-rotation
• If the harmonic filter option is included, make
vanes cannot close quickly enough to correct for this
sure the filter logic board is not in continuous re-
sudden increase in current, and the chiller will trip on
set. This condition is evidenced by the filter logic
an overcurrent fault.
board’s LED’s alternately blinking. The filter can
be eliminated as a cause of initialization failure by If the chiller will not restart, but keeps tripping on this
disconnecting the filter. Place switch SW1 on the same fault, an output pole problem is the most likely
filter logic board in the OFF position and remov- cause and the VSD would require service.
ing the ribbon cable between the filter logic board
and the VSD logic boards to check.
• VSD and harmonic filter horsepower ratings do
not agree.
VSD – Precharge – DC Bus Voltage Imbalance This message indicates a heatsink temperature sensor
This message indicates the same fault as the VSD-DC for Phase A, B, or C (denoted as X above) is showing
BUS VOLTAGE IMBALANCE, except the condi- a temperature less than 37°F and will cause the chiller
tion occurred during the chiller prelube period. to shut down. Typically, the problem will be an open
thermistor or broken wiring to the thermistor. The nor-
VSD – High Internal Ambient mal thermistor resistance is 10K ohms at 77°F.
Temperature
VSD – Low Converter Heatsink
The internal ambient temperature is monitored by a Temperature
component mounted on the VSD logic board with a
trip threshold set for 140°F. Some potential causes for If VSD part number is 371-02767-XXX (60 Hz) or
this shutdown are: internal VSD fan failure, VSD water 371-03700-XXX (50 Hz), a heatsink temperature sen-
pump failure or an entering condenser water tempera- sor indicating a temperature of less than 37°F will
ture that exceeds the allowable limit for the job. Ad- cause the chiller to shutdown and display this message.
ditional causes for the shutdown are: Typically, the problem will be an open thermistor or
broken wiring to the thermistor. The normal thermistor
• Plugged Strainer – The standard 1.5 Y-strainer resistance is 10K ohms at 77°F.
contains a woven mesh element with 20 stainless
steel wires per inch; adequate for most applica- VSD – Low Phase (X) Inverter Baseplate
tions. If condenser water is abnormally contami- Temperature
nated, the strainer may become plugged. Loca- [Applicable to VSD part number 371-03789-xxx (503
tions with special conditions may consider a dual HP 60 Hz; 419 HP 50 Hz)]
strainer arrangement with valves to permit clean-
ing of one strainer with the unit still online. The chiller has shutdown because the baseplate tem-
perature for the indicated current phase A, B, or C (de-
• Plugged Heat Exchanger – In cases where the noted as X above), has decreased below 37 ºF.
strainer plugs frequently, the heat-exchanger may
eventually plug or become restricted to the point VSD – Low Inverter Baseplate
of reduced flow. Back-flush the heat-exchanger by Temperature
reversing the two rubber hoses which supply con-
[Applicable to VSD with part number 371-02767-
denser water to-from the heat-exchanger. If the
XXX (60 Hz) or 371-03700-XXX (50 Hz)]
rust cannot be back-flushed, the heat-exchanger
must be replaced. A baseplate temperature sensor indicating a temper-
ature of less than 37°F will cause the chiller to shut
• Low Condenser Flow – The VSD system requires
down and display this message. Typically, the prob-
eight (8) feet of pressure drop across the heat ex-
lem will be an open thermistor or broken wiring to
changer to maintain adequate liquid flow. If the
the thermistor. The normal thermistor resistance is 5K
pressure drop is less than eight feet, the flow prob-
ohms at 77°F.
lem must be corrected or a booster pump must be
added.
The harmonic filter logic board generates a filter DC Harmonic Filter – Logic Board
link voltage by switching the filter IGBT’s. This DC Power Supply
level is higher than the level that could obtained by The low voltage power supplies on the filter logic
only rectifying the input line voltage. By generating board have decreased below the allowable operating
the DC link voltage, the harmonic filter performs a range. The filter logic board receives power from the
voltage BOOST function. This is necessary in order to VSD logic board via a ribbon cable that connects the
permit current to flow into the power line from the fil- two boards.
ter when the input line is at peak level. This varies with
the input line-to-line voltage. If this shutdown occurs, Harmonic Filter – Run Signal
the likely cause is a severe sag in the input line voltage.
When a digital run command is received at the filter
Harmonic Filter – Precharge – Low DC Bus logic board from the VSD logic board (via the 16 posi-
Voltage tion ribbon cable), a 1/10 second timer is started. If a
redundant RUN command does not occur on the serial
During precharge, the filter’s DC link must be equal data link from the VSD logic board before the timer
to or greater than 50 VDC (41 VDC for 50 Hz) within expires, a shutdown is performed and this message is
1/10 second after the precharge relay is energized. If generated.
this condition is not met, a shutdown is performed and
this message is generated. Harmonic Filter – DC Current
Transformer X (1 or 2)
Harmonic Filter – DC Bus Voltage
Imbalance During initialization, with no current flowing through
each DC Current Transformer (DCCT), the DCCT out-
This shutdown occurs when the shared voltage be- put voltages are measured and compared with a preset
tween the DC link capacitors is not within specifica- limit via the filter logic board. If the measured values
tions. The electrolytic capacitors, rated for 450 VDC, exceed the preset limits, the DCCT’s are presumed to
are wired in series to achieve a 900 VDC capability for be defective and a message indicating which DCCT is
the DC link. The voltage must be shared equally from affected (1 or 2) and a chiller shutdown will occur.
the junction of the center or series capacitor connec-
tion, to the negative bus and to the positive bus. This SAFETY SHUTDOWN MESSAGES
center point should be approximately half of the total
DC link voltage. Condenser – High Pressure
The condenser pressure, as sensed by the condenser
Harmonic Filter – Input Current Overload transducer, has increased above 29.7 PSIA. The chiller
The three phases of RMS filter current are monitored can be started after the pressure decreases below 23.7
and if any one of the three phases continuously exceeds PSIA and the compressor switch is placed in the STOP/
a given threshold for seven (7) seconds, a chiller shut- RESET (O) position.
down is performed and this message is displayed. The
maximum permissible continuous RMS current ratings Condenser – Pressure Transducer Out of
for the harmonic filter are as follows: Range
Condenser – High Pressure Contacts Open The total count is incremented for every second the
This safety fault is set whenever the High Pressure evaporator refrigerant temperature is below the freeze
Cutout (HPCO) switch contacts are open. the fault is threshold (but is never decremented below zero). The
released when the switch contacts close, and the com- amount of seconds until the chilled liquid will freeze is
pressor switch is placed in the STOP/RESET (O) po- based on how far the evaporator refrigerant tempera-
sition. ture is below the freeze threshold as follows:
# seconds to freezing = (4053.7) / (freeze 3
Evaporator – Low Pressure threshold – evap. refrigerant temp.)
The evaporator pressure has decreased to the safety Smart Freeze is activated only if the feature has been
shutdown threshold. For water cooling applications, enabled by a service technician and the leaving chilled
the safety shutdown threshold is a fixed value for the liquid temperature setpoint is less than 38.0°F.
respective refrigerant. For brine cooling applications,
the safety shutdown threshold varies according to the Evaporator – Transducer or Leaving Liquid
concentration of the brine solution and is programmed Probe
at the YORK Factory. This should not be changed by
The control center has detected a possible defective
anyone other than a qualified service technician fol-
evaporator pressure transducer or leaving chilled liq-
lowing instructions in the OptiView Control Center
uid temperature thermistor. The OptiView Control
Retrofit Kit - Trane Service Manual (Form 160.10-M1).
Center converts the evaporator pressure to a saturated
The chiller can be started after the evaporator pressure
temperature value and compares this value to the leav-
increases to the restart threshold and the compressor
ing chilled liquid temperature (difference = chilled liq-
switch is placed in the STOP/RESET (O) position.
uid temp – evaporator saturated temp). The difference
Refer to Table 9 for shutdown and restart thresholds:
should not be outside the range of –2.5°F to +25.0°F. If
Table 9 - EVAPORATOR PRESSURE THRESHOLDS the transducer and thermistor are accurate, the evapo-
rator saturated temperature should not be more than
SHUTDOWN THRESHOLD RESTART THRESHOLD 2.5°F warmer, or more than 25.0°F colder than the
(PSIA) (PSIA) leaving chilled liquid temperature. In order to initiate
Refrig. Water Brine Water Brine a shutdown, the difference must be outside the accept-
0.0 to 12.5 able range continuously for ten minutes.
> Shutdown
R11 < 5.4 as > 5.4
threshold
programmed Evaporator – Transducer or
0.0 to 12.5 Temperature Sensor
> Shutdown
R123 < 4.4 as > 4.4 The control center has detected a possible defective
threshold
programmed
evaporator pressure transducer or refrigerant tempera-
ture sensor. The control center converts the evaporator
Evaporator – Low Pressure – Smart Freeze pressure to a saturated temperature value and compares
this value to the evaporator refrigerant temperature
Smart Freeze protection is activated and has shutdown
sensor (RT7, if enabled). If the difference between
the chiller because the evaporator temperature has been
these temperatures is greater than 3.0°F continuously
below the Smart Freeze threshold for greater than the
for one minute, this shutdown is performed. This check
allowable number of seconds. If the refrigerant tem-
is only performed under the following conditions:
perature sensor (RT7) is ENABLED, this parameter
is used as the evaporator refrigerant temperature and • RT7 is enabled.
the freeze threshold is 32.8°F. If RT7 is not enabled,
the refrigerant temperature displayed is the evapora- • Chiller has been running for ten minutes.
tor saturation temperature, derived from the evaporator • Not in Brine chilled liquid mode.
pressure transducer. The freeze threshold is 34.0°F.
• Smart Freeze is enabled.
• Evaporator temperature sensor (RT7) or evapora-
tor saturation temperature is indicating a tempera-
ture less than 32.0°F ).
The chiller can be started after the temperatures are Auxiliary Safety – Contacts Closed
within 3.0°F of one another and the compressor switch The auxiliary safety shutdown contacts, connected to
is placed in the STOP/RESET (O) position. I/O board TB4-31 have closed, initiating a safety shut-
down. This input is connected to the electromechanical
Discharge – High Temperature
low differential oil pressure switch (LOPCO) installed
This message indicates the discharge temperature has on chillers retrofitted with the OptiView panel. The
increased above 220.0°F. The chiller can be re-started chiller can be started after the safety contacts open and
after the temperature decreases below 220.0°F and the the compressor switch is placed in the STOP/RESET
compressor switch is placed in the STOP/RESET (O) (O) position.
position.
Control Panel – Power Failure
Discharge – Low Temperature
A control panel power failure has occurred. If the power
This message indicates the discharge temperature has failure duration was less than the duration of the pro-
decreased below 30.0°F. The chiller can be re-started grammed SYSTEM COASTDOWN period, the re-
after the temperature increases above 30.0°F and the mainder of the coastdown is performed upon restoration
compressor switch is placed in the STOP/RESET (O) of power. The chiller can be started after the compres-
position. sor switch is placed in the STOP/RESET (O) position.
The control center indicates a cycling shutdown when
Oil – High Temperature this message is displayed in orange characters; a safety
The oil temperature, as sensed by the oil temperature shutdown when displayed in red characters. The control
thermistor, is above 180.0°F. The chiller can be started center can be configured for auto-restart or manual re-
after the temperature decreases below 180.0°F and the start after power failure by a qualified Service technician
compressor switch is placed in the STOP/RESET (O) following instructions in the OptiView Control Center
position. Retrofit Kit - Trane Service Manual (Form 160.10-M1).
down. The chiller can be restarted after the winding LCSSS – High Phase X Heatsink
temperature has decreased below the winding cutout Temperature – Running
setpoint. The solid state starter logic/trigger board has detected
the temperature of current phase A, B or C (designated
Motor – High Bearing Temperature
as X above) Silicon Controlled Rectifier (SCR) mod-
This message indicates that a motor bearing has ex- ules exceeded 212°F while the chiller was running. The
ceeded the programmed bearing cutout temperature, fault can be cleared after all SCR temperatures are low- 3
initiating a chiller shutdown. The chiller can be restart- er than 210°F and the compressor switch is placed in
ed after the bearing temperature has decreased below the STOP/RESET (O) position. However, the chiller
the bearing cutout setpoint. cannot be started until all SCR temperatures are lower
than 109°F. During the shutdown, the starter cooling
MOD “B” SOLID STATE STARTER pump runs until the temperature is below 109°F.
SAFETY SHUTDOWN MESSAGES
The following safety shutdown messages are displayed LCSSS – Phase (X) Shorted SCR
for liquid cooled solid state starter (LCSSS) applica- A shorted Silicon Controlled Rectifier (SCR) in phase
tions only. These messages are generated by events A, B or C (designated as X in the message) has been
that occur within the LCSSS. The chiller can be started detected by the solid state starter logic/trigger board.
after the problem has been corrected and a manual re- The voltage across each SCR in monitored to detect
set of the compressor motor switch occurs. Service and the shorted condition. The shorted condition must exist
troubleshooting information is contained in the Solid continuously for five (5) seconds in order for the Op-
State Starter MOD “B” – Operation/Service Manual tiView Control Center to trigger and display the fault.
(Form 160.00-O2). This check is disabled while the chiller is running.
VSD Shutdown – Requesting Fault Data VSD – High Phase (X) Inverter Heatsink
The VSD has shut down the chiller and the control Temperature
center has not yet received the cause of the fault from (Style D VSD)
the VSD, via the serial communications link. The VSD
shuts down the chiller by opening the motor controller This shutdown will occur if the heatsink temperature
VSD STOP CONTACTS (located on the VSD Logic for current phase A, B, or C (denoted by X above) ex-
Board and connected between TB6-16 and TB6-53 in ceeds 158°F on any of the output pole assemblies. This
the control center). The control center microboard then shutdown will seldom occur. In most cases where the
sends a request for the cause of the fault to the VSD coolant temperature has risen abnormally, the VSD
logic board via the adaptive capacity control (ACC) will shut down on AMBIENT TEMPERATURE @
board. Since serial communications are initiated every 140.0°F before the heatsinks can reach 158°F. If this
two seconds, this message is typically displayed for a message is displayed, make sure there is adequate
few seconds and then replaced with one of the follow- coolant level, ascertain the pump is operating when the
ing fault messages. chiller is running, and check the strainer of the heat
exchanger primary for clogs and silt.
VSD – 105% Motor Current Overload
VSD – High Converter Heatsink
This shutdown is generated by the VSD logic board Temperature
and indicating that a motor overload has occurred.
The shutdown is generated when the VSD logic board (Style D VSD)
has detected that at least one of the three output phase This shutdown will occur if the heatsink temperature
currents has exceeded 105% of the chiller Full Load exceeds 158°F on any of the output pole assemblies.
Amps (FLA) value for longer than seven (7) seconds. This shutdown will seldom occur. In most cases where
The chiller FLA value is set by adjustment of the FLA the coolant temperature has risen abnormally, the VSD
potentiometer on the VSD Logic Board. will shut down on AMBIENT TEMPERATURE @
140.0°F before the heatsinks can reach 158°F. If this
VSD – High Converter Heatsink message is displayed, make sure there is adequate
Temperature coolant level, check that the coolant pump is operating
(Applicable to VSD with Part Number 371-02767- when the chiller is running, and check the strainer of
XXX (60 Hz) and 371-03700-XXX (50 Hz)) the heat exchanger primary for clogs and silt.
This shutdown will occur if the heatsink temperature VSD – High Phase (X) Inverter
exceeds 170°F. The chiller can be started after the fault Baseplate Temperature
condition clears. If this message is displayed, make
sure there is adequate coolant level, check that the (VSD part number 371-03789-xxx (503HP 60 Hz;
coolant pump is operating when the chiller is running, 419HP 50 Hz)
and check the strainer of the heat exchanger primary The chiller has shutdown because the baseplate temper-
for clogs and silt. ature for current phase A, B, or C (denoted by X above)
has exceeded 158ºF. If this message is displayed, make
VSD – High Inverter Baseplate sure there is adequate coolant level, check that the
Temperature coolant pump is operating when the chiller is running,
(Applicable to VSD with Part Number 371-02767- and check the strainer of the heat exchanger primary
XXX (60 Hz) and 371-03700-XXX (50 Hz)) for clogs and silt.
This shutdown will occur if the baseplate temperature VSD – Precharge Lockout
exceeds 175°F. If this message is displayed, make sure
there is adequate coolant level, check that the cool- If the VSD fails to make precharge, the precharge relay
ant pump is operating when the chiller is running, and will cut out for ten (10) seconds during which time the
check the strainer of the heat exchanger primary for VSD fans and coolant pumps will remain energized in
clogs and silt. order to permit the precharge resistors to cool. Follow-
ing this ten second cool down period, precharge will
again be initiated. If the VSD fails to make precharge
after three consecutive tries, the unit will shut down,
lockout, and display this message.
SECTION 4 - PRINTERS
4
23887A
23889A
WEIGH-TRONIX
00085VIP
SEIKO DPU-414
Figure 43 - PRINTERS
• Setpoints - Figure 52 on page 129 Exercise care and use the following guidelines if an un-
listed printer is to be connected to the OptiView panel:
PRINTERS
1. The printer must be capable of RS‑232 Serial
The following printers can be connected to the OptiV- communications.
iew Control Center to provide print reports. Printers
must be equipped with an RS‑232 Serial interface for 2. Primary differences between printers involve the
to communicate properly with the OptiView panel. formatting control codes required by the printer.
These codes are sent from the control center to
Okidata the printer. For example, Weigh-Tronix printers
require a control code to select 40 column width.
Model: 184 turbo This same code is interpreted by the Okidata
• Dimensions: 14 in. wide x 10.5 in. deep printer as an instruction to print wide characters.
In some instances, a printer will ignore a code that
• Paper: 8.5 in. wide
cannot be interpreted.
• Type: Dot matrix impact
3. The control center requires a busy signal from the
• Purchase: 800‑OKIDATA or www.okidata.com printer when the printer receive buffer is full. This
causes the control center to suspend data trans-
Weigh‑Tronix mission until the printer can accept more data.
Models: 2600, 1220 The busy signal polarity must be logic low when
busy for proper printer operation.
• Dimensions: 2.3 in. wide x 2.8 in. deep
• Paper: 2.25 in. wide
• Type: Dot matrix impact
• Purchase:
• USA 800‑982‑6622
• International 707‑527‑5555
• www.wtxweb.com
Table 10 - OKIDATA 182, 182 TURBO, 184 TURBO OKIDATA 182, 182 turbo, 184 turbo Printer
PRINTER CONNECTIONS
CONTROL BOARD Switch settings:
MICROBOARD PRINTER FUNCTION 1 on Unslashed 0
J2-4 pin 3 Tx (data to printer) 4
2 off Unslashed 0
DSR (busy signal from
J2-2 pin 11
printer) 3 off Unslashed 0
J2-9 pin 7 Gnd
4 off Form Length 11 in.
Cabinet Shield
5 on Form Length 11 in.
Table 11 - WEIGH-TRONIX PRINTER
6 off Auto Line Feed off
CONNECTIONS
7 on 8 bit data
MICROBOARD PRINTER FUNCTION
J2-4 pin 2 Tx (data to printer) 8 off Enable front panel
DSR (busy signal from If equipped with a SUPER SPEED serial Board:
J2-2 pin 5
printer)
J2-9 pin 7 Gnd 1‑1 on Odd or even parity
7 off
Pin 20 & pin 11 act as busy 2‑1 on Printing Columns - 40
line
2‑2 on User Font Back‑up ‑ on
WEIGH‑TRONIX Printer 2‑3 on Character Select ‑ normal
IMP‑24 Model 2600 2‑4 off Zero ‑ slash
1 off 1200 Baud*
2‑5 on International character set ‑
2 on 1200 Baud* American
values must be entered. [All warnings presently active will be listed here]
Controls C.MLM.08.01
• Baud Rate ‑ Set as desired. Value selected must Run Time 0 Days 2 Hr 59 Min
Operating Hours = 25 Hr
agree with the installed printer’s configuration. Number Of Starts = 6 4
Control Source = Local
• Data Bits ‑ 8
Evaporator
• Parity ‑ None -----------------------------------------------------
Leaving Chilled Active Setpoint = 45.0 ºF
• Stop Bits ‑ 1 Chilled Liquid Pump = Run
Chilled Liquid Flow Switch = Closed
Automatic Data Logging Leaving Chilled Liquid Temperature = 45.0 ºF
Return Chilled Liquid Temperature = 55.0 ºF
Access Level Required: OPERATOR Evaporator Pressure = 75.0 Psig
Evaporator Saturation Temperature = 44.4 ºF
If automatic data logging is desired, a Status report can Evaporator Refrigerant Temperature = 44.5 ºF
be automatically printed at a specified interval begin- Small Temperature Difference = 0.5 ºF
[Skip the following section if Liquid Level is not enabled] [Skip the following section if Motor Type is not VSD or Filter is
Refrigerant Level Control not present]
----------------------------------------------------- Harmonic Filter Data
Refrigerant Level Position = 35 % ----------------------------------------------------
Precharge Contactor = Off
Purge Control Supply Contactor = On
----------------------------------------------------- Operating Mode = Running
Pressure = 30.1 PSIA Phase Rotation = ABC
Exhaust Count = 0 Total Supply kVA = 148 kVA
Exhaust Window = 0 Min Total Power Factor = 0.97
DC Bus Voltage = 608 V
Heatsink Temperature [If TMIII VSD] = 102 ºF
[Skip the following section if Motor Type is not EM]
Baseplate Temperature [If VyperDrive VSD] = 102 ºF
Electro-Mechanical Starter
Voltage Peak N-L1 = 200 V
-----------------------------------------------------
Voltage Peak N-L2 = 200 V
Motor Run = On
Voltage Peak N-L3 = 200 V
% Full Load Amps = 94 %
L1-L2 RMS Voltage = 215 V
L2-L3 RMS Voltage = 215 V
[Skip the following section if Motor Type is not Mod B SSS]
L3-L1 RMS Voltage = 215 V
Liquid-Cooled Solid State Starter
L1 RMS Filter Current = 150 A
-----------------------------------------------------
L2 RMS Filter Current = 150 A
Starter Model = 26L
L3 RMS Filter Current = 150 A
Motor Run = On
L1 RMS Supply Current = 152 A
% Full Load Amps = 95 %
L2 RMS Supply Current = 152 A
kW Hours = 20723 kWH
L3 RMS Supply Current = 152 A
Input Power = 8225 kW
L1 Voltage Total Harmonic Distortion = 1.5 %
Phase A Voltage = 422 V
L2 Voltage Total Harmonic Distortion = 1.2 %
Phase B Voltage = 449 V
L3 Voltage Total Harmonic Distortion = 1.1 %
Phase C Voltage = 449 V
L1 Supply Current Total Demand Distortion = 2.6 %
Phase A Current = 253 A
L2 Supply Current Total Demand Distortion = 2.3 %
Phase B Current = 257 A
L3 Supply Current Total Demand Distortion = 2.8 %
Phase C Current = 262 A
Phase A Temperature = 109 ºF
Phase B Temperature = 109 ºF
Phase C Temperature = 110 ºF
FIGURE 44 - SAMPLE PRINTOUT (STATUS) (CONT’D)
[Skip the following section if Motor Type is not VSD]
Variable Speed Drive
-----------------------------------------------------
Motor Run = On Motor Winding Temperature
% Full Load Amps = 94 % -----------------------------------------------------
Pre-Rotation Vanes Position = 75 % A1 = 193.3 ºF
Full Load Amps = 402 A B1 = 192.5 ºF
Precharge Relay Output = Off B2 = 193.1 ºF
Trigger SCR Output = On
Water Pump Output = On Bearing Temperature
kW Hours = 14528 kWH -----------------------------------------------------
Input Power = 150 kW Sensor 1 = 128.3 ºF
Output Frequency = 60 Hz Sensor 2 = 129.5 ºF
Output Voltage = 800 V
DC Bus Voltage = 600 V
DC Inverter Link Current = 300 A
Phase A Output Current = 195 A FIGURE 44 - SAMPLE PRINTOUT (STATUS) (CONT’D)
Phase B Output Current = 198 A
Phase C Output Current = 193 A
Internal Ambient Temperature = 88 ºF
Converter Heatsink Temperature = 102 ºF
Phase A Heatsink Temperature [If TMIII VSD] = 93 ºF
Phase B Heatsink Temperature [If TMIII VSD] = 99 ºF
Phase C Heatsink Temperature [If TMIII VSD] = 97 ºF
Baseplate Temperature [If VyperDrive VSD] = 106 ºF
CHILLER ID 3 CHILLER ID 3
© 1997 - 2004 YORK INTERNATIONAL CORPORATION © 1997 ‑ 1999 YORK INTERNATIONAL CORPORATION
--------------------------------------------------
---------------------------------------------------
NOZZLE ARRANGEMENT IN =
RETURN TEMPERATURE =
GPM =
TUBES =
--------------------------------------------------
PASSES =
FOULING FACTOR =
PRESSURE DROP =
NOZZLE ARRANGEMENT IN =
LEAVING TEMPERATURE =
RETURN TEMPERATURE =
GPM =
TUBES =
POWER (VOLTS) =
SYSTEM READY TO START
PHASES = LCSSS – LOGIC BOARD POWER SUPPLY
Condenser
-----------------------------------------------------
FIGURE 46 -SAMPLE PRINTOUT (SALES ORDER) Condenser Liquid Pump = Stop
Condenser Liquid Flow Switch = Open
(CONT’D)
Leaving Condenser Liquid Temperature = 95.0 ºF
Return Condenser Liquid Temperature = 85.0 ºF
Condenser Pressure = 200.0 Psig
Condenser Saturation Temperature = 101.4 ºF
Small Temperature Difference = 6.4 ºF
Drop Leg Refrigerant Temperature = 83.0 ºF
[If Drop Leg Sensor enabled]
Sub Cooling Temperature = 18.4 ºF
[If Drop Leg Sensor enabled]
Compressor
-----------------------------------------------------
Discharge Temperature = 120.0 ºF
Vent Line Solenoid = Off
Oil Sump
-----------------------------------------------------
Oil Pump Run Output = Off
Sump Oil Pressure (LOP) = 75.8 Psig
Pump Oil Pressure (HOP) = 76.6 Psig
Oil Pressure = 0.0 Psid
Oil Sump Temperature = 150.0 ºF
Jumper Settings
[Following section not displayed if Hot Gas Bypass is not enabled]
-----------------------------------------------------
Hot Gas
Oil Pump Type = Standard
-----------------------------------------------------
Coastdown = Standard
Chilled Liquid Pump Operation = Standard Hot Gas = Enabled
Refrigerant Selection = R123 Hold Period = 30 Min
Anti-Recycle = Enabled Close Percentage = 5 %
Power Failure Restart = Auto
Liquid Type = Water [Following section not displayed if Level Control is not enabled]
Motor Type = Fixed Speed Refrigerant Level Control
-----------------------------------------------------
Printer Setup Level Control = On
----------------------------------------------------- Setpoint = 50 %
Automatic Printer Logging = Disabled Period = 3.5 Sec
Log Start Time = 12:00 am
Proportion Limit Open = 15 %
Output Interval = 60 Min
Proportion Limit Close = 45 %
Printer Type = Okidata
Rate Limit Open = 10 %
Baud = 9600 Baud
Rate Limit Close = 10 %
Data Bits = 8 Bits
Parity = None
Stop Bits = 1 Bit [Not displayed if Motor Type is not EM]
Electro-Mechanical Starter
COM 2 Setup -----------------------------------------------------
----------------------------------------------------- Local Motor Current Limit = 100 %
Baud = 19200 Baud Remote ISN Current Limit = 100 %
Data Bits = 8 Bits Remote Analog Current Limit = 100 %
Parity = Odd Remote Digital Current Limit = 100 %
Stop Bits = 1 Bit Remote Modem Current Limit = 100 %
Pulldown Demand Limit = 100 %
Evaporator Pulldown Demand Time = 0 Min
-----------------------------------------------------
Leaving Chilled Local Setpoint = 45.0 ºF
Leaving Chilled ISN Setpoint = 45.0 ºF
Leaving Chilled Modem Setpoint = 45.0 ºF
Leaving Chilled Analog Setpoint = 45.0 ºF
FIGURE 52 - SAMPLE PRINTOUT (SETPOINTS)
Leaving Chilled Digital Setpoint = 45.0 ºF (CONT’D)
Remote Range = 10.0 ºF
Sensitivity = 100%
ID10291
ID10292
ID10290
ID10293
EVAPORATOR SCREEN
ACCESS MINIMUM MAXIMUM
SETPOINT DEFAULT
LEVEL VALUE VALUE
38.0 °F - Water
Local Leaving Chilled Liquid Temperature - Setpoint Operator 36.0 °F - Sm Frz 70.0 °F 45.0 °F
10.0 °F - Brine
Local Leaving Chilled Liquid Temperature - Range Operator 10.0 °F 20.0 °F 10.0 °F
Varies with 4.0 °F or highest
LCHLT setpoint allowed value,
LCHLT Cycling Offset - Shutdown Operator 1.0°F
and chilled liquid whichever is B
type. lower.
Varies with
LCHLT setpoint
LCHLT Cycling Offset - Restart Operator 0.0 °F 0.0 °F
and chilled liquid
type.
Brine Low Evaporator Cutout Service 0.0 PSIA 12.5 PSIA 12.5 PSIA
Sensitivity Service 10 % 200 % 100 %
Smart Freeze Service Off On Off
Refrigerant (Sensor) Service Disabled Enabled Disabled
CONDENSER SCREEN
ACCESS MINIMUM MAXIMUM
SETPOINT DEFAULT
LEVEL VALUE VALUE
High Pressure Warning Threshold Service 14.0 PSIA 28.8 PSIA 28.8 PSIA
Drop Leg (Sensor) Service Disabled Enabled Disabled
Refrigerant (Sensor) Service Disabled Enabled Disabled
TurboGuard, SkyGuard Local, SkyGuard
Purge Type Service
SkyGuard Remote Remote
SETPOINTS SCREEN
ACCESS MINIMUM MAXIMUM
SETPOINT DEFAULT
LEVEL VALUE VALUE
38.0 °F - Water
Local Leaving Chilled Liquid Temperature - Setpoint Operator 36.0 °F - Sm Frz 70.0 °F 45.0 °F
10.0 °F - Brine
Local Leaving Chilled Liquid Temperature - Range Operator 10.0 °F 20.0 °F 20.0 °F
4.0 °F or high-
est allowed
LCHLT Cycling Offset - Shutdown Operator 1.0°F 64.0 °F
value, which-
ever is lower.
LCHLT Cycling Offset - Restart Operator 0.0 °F 70.0 °F 0.0 °F
Remote Analog Input Range Operator 0 - 10 VDC 2 - 10 VDC 0 - 10 VDC
Motor Current Limit Operator 30 % 100 % 100 %
Pulldown Demand Limit Operator 30 % 100 % 100 %
Pulldown Demand Time Operator 0 Min 255 Min 0 Min
HISTORY SCREEN
ACCESS MINIMUM MAXIMUM
SETPOINT DEFAULT
LEVEL VALUE VALUE
Select Fault View Normal, Running, Fault # Normal
TEMPERATURE
To convert degrees Fahrenheit (°F) to degrees Celsius
(°C), subtract 32° and multiply by 5/9 or 0.5556.
Example: (45.0°F - 32°) x 0.5556 = 7.22°C
To convert a temperature range (i.e., a range of 10°F)
from Fahrenheit to Celsius, multiply by 5/9 or 0.5556.
Example: 10.0°F range x 0.5556 = 5.6 °C range