Product Specification

03259

505LST
for Large Steam
Turbines
• Full-arc-partial-arc
transfers
• Automated valve
testing
APPLICATIONS control’s front service panel via a user-
friendly menu-driven software program. • Controls up to 4
The 505LST digital control is designed to modulating valves
control large power-generation-based An Operator Control Panel is provided on
reheat steam turbines with up to 4 the 505LST’s front panel. Easy to follow (more with
modulating valves (up to 6 valves with the instructions are presented in English external drivers)
use of external drivers). through the OCP’s two-line display, and
operators can view actual and setpoint • User-friendly
This control performs turbine speed values from the same screen. menu
control off-line, and throttle pressure or programming
valve position control on-line. Full-arc
partial-arc transfers are accomplished on-
PROTECTION format
or off-line depending on the unit’s • Integral operator
Emergency trip commands can be
configuration. Valve testing can be done
automatically or manually from the
performed from the control’s front panel, control panel
hardwired discrete commands, or through
control’s front service panel, or remotely • Throttle pressure
serial communications.
via discrete commands.
Standard control features include
control
Depending on the programmed
overspeed frequency regulation through • Valve position
configuration, overspeed valve regulation
intercept valves, overspeed trip condition,
is achieved via throttle and or intercept
and high acceleration protection.
control
valves.
• Modbus®
The 505LST can be configured to operate
as a stand-alone unit or in conjunction
FUNCTIONALITY communications
with a plant’s Distributed Control System. • Certified for Class
The 505LST’s functionality includes:
• Speed Control I, Division 2,
DESCRIPTION • Throttle Pressure Control Groups A, B, C, D
• Valve Position Control Locations
The 505LST is a field-programmable • Full-arc-Partial-arc Transfers
digital control that has an application • Valve Testing
software program designed to control
• First-Out Shutdown Indication
multi-valve reheat steam turbines driving
• Valve Limiters
utility-paralleled generators.
• Security—Program is password
This control’s hardware package consists protected
of printed circuit boards in an enclosure • Remote Analog Setpoints for Speed
designed to be mounted within a system and Valve Position Setpoints
control panel. Removable terminal blocks • Critical Speed Avoidance
allow for easy wiring and installation. • Modbus® Communications
The 505LST is programmed through the • Automatic Start
• Coordinated Control with Plant DCS
FUNCTIONAL BLOCK DIAGRAMS
Turbine Type 1: 2 Throttle Valves (modulating control)
2 Governor Valves (modulating control)
2 Intercept Valves (relay output control)

Turbine Type 2: 1 Stop Valve (modulating control), (second valve possible with External Driver)
1 Governor Valve (modulating control), (second valve possible with External Driver)
2 Intercept Valves (modulating control)
2 Intercept Valves (relay output control)
Turbine Type 3: 2 Stop Valves (relay output control)
2 Governor Valves (modulating control), (3 or 4 valves possible with External Drivers)
2 Intercept Valves (modulating control)
2 Reheat Stop Valves (relay output control)

505LST Outline Drawing


(Do not use for construction)
CONTROL SPECIFICATIONS
PO Box 1519
Fort Collins CO, USA INPUTS
80522-1519 Power: 18–32 Vdc, 90–150 Vdc, 88–132 Vac (47–63 Hz), 180–264 Vac (47–63 Hz)
1000 East Drake Road Speed: 2 MPUs (1–30 Vrms) or Proximity Probes (24 Vdc provided), 0.5 to 15 kHz
Fort Collins CO 80525 Discrete Inputs: 16 Dedicated Contact Inputs (24 Vdc wetting voltage)
Ph: +1 (970) 482-5811 Analog Inputs: 6 Dedicated 4–20 mA Current Inputs
Fax: +1 (970) 498-3058
OUTPUTS
Valve/Actuator Drivers: 4 Actuator Outputs (4–20 mA)
Distributors & Service Discrete Outputs: 8 Dedicated Relay Outputs (Form-C relay contacts)
Woodward has an Analog Outputs: 4 Dedicated Readouts (4–20 mA)
international network of
distributors and service
COMMUNICATIONS
facilities. For your nearest Serial: 2 Modbus (ASCII or RTU) Comm Ports (RS-232, RS-422, or RS-485
representative, call the compatible)
Fort Collins plant or see PC Port: 1 RS-232 PC port for uploading/downloading program configurations
the Worldwide Directory
on our website.
ENVIRONMENTAL
Operating Temperature
Range: –25 to +65 °C
Corporate Headquarters Electromagnetic Immunity—IEC 61000-4-2
Rockford IL, USA Compatibility: Emissions—EN55011, Class A, Gr 1
Ph: +1 (815) 877-7441 Radiated RF Immunity—IEC 61000-4-3
Fast Transient Immunity—IEC 61000-4-4
www.woodward.com Conducted RF Immunity—IEC 61000-4-6
Shock: US MIL-STD-810C Procedure 516.2, Procedure 1B
Vibration: Lloyd's Register ENV2 Vibration Test 1 (0.7G, 5 to 100 Hz)
Humidity: Lloyd's Register ENV2 Test #1
Salt Fog: US MIL-STD-810 Method 509.2 Procedure 1
Size: 14”L X 11”H X 4”D (356 x 279 x 102 mm)
Mounting: Bulkhead mounted
Location Rating: NEMA 4
Agency Approvals: UL/cUL Listed—Class I, Division 2, Groups A, B, C, D
CE (18–32 Vdc version only)
Technical Manual 26173

This document is distributed Basic Program Architecture


for informational purposes
only. It is not to be construed
as creating or becoming part
of any Woodward Governor
Company contractual or
warranty obligation unless
expressly stated in a written
sales contract.

© Woodward 2002