Maguire Ultra-600-Ts-File Manual PDF
Maguire Ultra-600-Ts-File Manual PDF
Maguire Ultra-600-Ts-File Manual PDF
-6
• INSTALLATION
• OPERATION
• MAINTENACE
This document is the Original Instructions manual of the Maguire ULTRA-600 Dryer equipped
with the Touchscreen Controller.
The information contained within this manual including any translations thereof, is the property of
Maguire Products Inc. and may not be reproduced, or transmitted in any form or by any means
without the express written consent of Maguire Products Inc.
To every person concerned with use and maintenance of the Maguire ULTRA-600 it is
recommended to read thoroughly these operating instructions. Maguire Products Inc. accepts no
responsibility or liability for damage or malfunction of the equipment arising from non-observance
of these operating instructions.
To avoid errors and to ensure trouble-free operation, it is essential that these operating
instructions are read and understood by all personnel who are to use the equipment.
Should you have problems or difficulties with the equipment, please contact Maguire Products
Inc. or your local Maguire distributor.
These operating instructions only apply to the equipment described within this manual.
Phone: 610.459.4300
Fax: 610.459.2700
Website: http://www.maguire.com
Email: info@maguire.com
For additional information, or to download the latest copy of this manual or any
other Maguire manual, please visit our website or contact us directly.
Table of Contents
INSTALLATION 8
Dryer Assembly 11
Engaging the Load Cells 13
Dryer Connections 14
Compressed Air Connection 15
Electrical Connection 16
Temperature Sensor (RTD) Locations 17
Home Screen Overview 18
Setup Menu Map -Brief Explanation 26
Parameters Explained 29
Changing Parameters 52
Batch Mode 29
Communication Setup 53
Operation 19
Start Up and Operation Instructions 19
What is happening when the Dryer is Running 21
Shutdown-Options 22
Auto-Stop Setup 23
Advanced Information 24
Recommended Drying Temperatures 25
Maintenance 55
Drain and purge Air Filter / Regulator 55
Air Pressure Adjustments 55
Loadcell Calibration 56
Cleanout Procedure 59
Alarms - Cause and Solution 63
Logs and Print Outputs 69
Dryer Firmware Updates 75
General Information 76
Technical Specifications 72
Theory of Operation / Performance 79
Warranty 80
Recommended Spare Parts List 75
Wiring Diagrams 82
Declaration of Conformity 87
Technical Support / Contact Information 88
This warranty shall not apply to equipment repaired or altered outside MAGUIRE
PRODUCTS INC. factory, unless such repair or alteration was, in our judgment, not
responsible for the failure; nor which has been subject to misuse, negligence or
accident, incorrect wiring by others,
or installation or use not in accord with instructions furnished by
Maguire Products, Inc.
Our liability under this warranty will extend only to equipment that is returned to our
factory in Aston, Pennsylvania, PREPAID.
Please note that we always strive to satisfy our customers in whatever manner is
deemed most expedient to overcome any problems they may have in connection with
our equipment.
GETTING STARTED:
PROCEED TO: SAFETY WARNINGS NEXT PAGE
SAFETY WARNINGS
HOT SURFACES:
As with all dryers, there are HOT
SURFACES to avoid. Temperatures can
reach 350F, (180C).
USE GLOVES
DO NOT REACH into the dryer
enclosure.
RISK OF SHOCK:
Installation
Transport and Setup
Shipment
The ULTRA-600 Dryer is shipped as separate components that require re-assembly.
The ULTRA-600 platform is designed for ease of lifting and moving. The retention hopper
and vacuum chamber assembly frame was designed with two steel channels spanning
the depth of the machine to allow for a fork truck to safely and easily lift and position the
machine into place.
Dryer Assembly
Leveling Feet
Air Pressure
Electrical Connection
RISK OF INJURY!
Only qualified
technicians should
make electrical
connections.
The electrical cable located on the left side of the Dryer on the power
box supplies the power to the Dryer. Within the cable is four wires.
Three of the wires are black and labeled with a number: 1, 2, and 3.
The fourth wire is a green/yellow wire and is the ground wire.
Home Screen
Overview
Shown with enabled options: Auto
Shutdown, Batch Mode, and
Preheat, ULTRA-600 screen
T1 Actual - Actual Heating
Hopper inlet air temperature
Navigation Menu
Home Screen Pressing the Home Screen button from any other screen will return the
operator to the main Home Screen.
Alarm and Alarm and Event Log displays a history of alarms and other events with a
Event date and time stamps and description.
Presets Interactive screen for material presets (recipes) that enable users to
input, edit, and load material parameters to minimize testing setup time.
Print Center A menu screen of print related options including Totals, Parameters,
Alarm History, Events, Cycle History, Diagnostics. See page 69.
Setup Login Password protected access to advanced Dryer and System configuration
information. Also displays firmware/software, IP and MAC address info.
Important: Inspect the ULTRA dryer, verify that machine is clear of all material from all tanks,
heating hopper, Vacuum Chamber and Retention Hopper. To facilitate a Clean Out, use the
Clean Out function accessible from the home screen.
Important Settings
Press the setpoint field to adjust the setting. Use the on-
screen keypad to enter the setpoint and press the green
check to complete the setting adjustment.
After pre-heat, approximately one third of the material in the heating hopper is dispensed
into vacuum chamber, and the first vacuum cycle begins. Each vacuum cycle has a
minimum vacuum time, set on the Pre-start screen, or the main run screen (VTs).
(default is 20 minutes).
The loader loads the Heating Hopper with new material as the Vacuum Chamber
receives the heated material and heating cycle begins concurrent to vacuum cycle (the
first vacuum cycle is timed). The new batch of material in the upper portion of the heating
hopper will take less time to heat. Minimum time in the heating is dictated vacuum time.
After first vacuum cycle, material is then dispensed into retention hopper ready for use.
Material in the retention hopper is blanketed with dry air.
The rate of consumption of dried material from the retention hopper ultimately dictates
the amount of time that the material will be preheated and under vacuum. Examples: If it
takes 30 minutes to deplete the retention hopper, the vacuum cycle will run past its 20-
minute setpoint (pre-start screen) to 30 minutes. This is normal operation. However, if
the retention hopper is depleted in 15 minutes and the vacuum time is set to 20 minutes,
there will be a 5-minute window where no material is available. This indicates that the
throughput of the dryer has been exceeded. If the Throughput Alarm is enabled (Alarm
Setup), a Throughput Alarm (Alarm Code 20) will be triggered.
Shutdown Options
At any point after the preheat cycle has ended (or forced to
end), pressing the red Shutdown button will bring up the
Shutdown Options screen with the following shutdown
options:
Auto-Stop Setup
Auto-Stop initiates a shutdown at a specified time on specific days if the week.
To enable and configure Auto-Stop follow the steps below.
Press Display will prompt for a password. (default: 22222) Then press:
Press Dryer Configuration Display will show the Dryer Configuration categories.
To Enable Auto-Stop:
Press Auto-Stop Enabled to enable Auto-Stop. Display will show Auto-Stop scheduling.
Press
the Home Button to return to the Home Screen.
Advanced Information
Pressing on the Home Screen will display additional information such as readings of all
RTD thermometers, vacuum time elapsed, absolute pressure in the Vacuum Chamber,
blower drive frequency.
This section outlines the Setup menu. For detailed info, see Setup Menu Full Explanation.
► Setup (password protected) – Settings and Options Menus
► Dryer Configuration - Dryer specific settings
► Alarm Setup – Enable or disable various alarms.
► Auto-Stop Setup - Scheduling Auto-Stop of the dryer.
► Dry Purge Setup - Configuration of dry purge.
► Preheat Setup - Configuration of Preheat.
► Auto-Start Setup - Scheduling Auto-Start of the dryer.
► Convey Setup - Configuration of material convey and loaders.
► Load-cell Setup - Loadcell calibration, zero and full calibration.
► Parameters - Operation Parameters
► Blower
► Heater
► System
► Dispensing
► Load-Cell
► Vacuum
► System Configuration System specific settings
► Print Options
► Print Parameters - Prints parameter report to USB Flash Drive
► Print Alarms and Events - Prints alarms and events to USB Flash Drive
► Copy Log File - Copies raw log file to USB drive.
► Print Alarm History - Prints Alarm History to USB Flash Drive
► Print All - Prints all above reports to USB Flash Drive
► Diagnostics
► System Information - Firmware, bootloader, I/O versions
► Load-Cell Diagnostics - Loadcell raw counts
► Alarm and Event Log - Alarms and Events displayed and printable
► Live Diagnostics - Live Cycle diagnostic report, printable history
► Communication Diagnostics - Information for communications
► Resets
► User Settings - Save / Restore User entered Settings
► Restore All - Restores factory default settings
► Firmware Updates - Reads USB drive for updates, selects and updates
firmware. Contact Maguire Products Inc. for updates.
► Factory Access - Factory Access Only
► Restore Parameters - Restores factory default parameters
► Preferences
► Change Passwords - Change Admin and Operator passwords
► Display Options – On-screen information display preferences
► Language - Language selection
► Screen Options - Screen saver, brightness, calibration, options
► Date and Time
► Weight Units - pounds, ounces, grams kilograms
► Menu Bar Options - menu button preferences
► Communications
► MLAN I.D. Number - Set Dryer identification number
► Modbus Server - enable/disable Modbus TCP
► TCP/IP Configuration - Sets IP address, Subnet mask, gateway
► MLAN Serial Baud Rate - Set baud rate of MLAN over serial
Modes of Operation
Three modes of operation (on Home Screen): Run Dryer, Manual Operations, Clean Out.
Manual Operations – Options that allow direct control over specific outputs.
Operate Outputs
Alarm Audio – OFF/ON – Operates audible alarm.
Alarm Strobe – OFF/ON – Operates strobe.
Dry Purge Supply – CLOSED/OPEN of dry purge supply air valve
Vac Gate Upper – OPEN/CLOSED – Material gate above vacuum chamber.
Vac Gate Lower – OPEN/CLOSED – visible disk-shaped gate below vacuum
chamber.
Vac Cham Fill – OPEN/CLOSED - Gate located at the base of the heating
hopper.
Vac Cham Dump – OPEN/CLOSED – Internal gate (not visible) located at the
base of the vacuum chamber.
Vac Gen Supply – OPEN/CLOSED – Vacuum generator supply. When
operating, the vacuum generator supply pulls a vacuum on the vacuum chamber.
Vac Gen Check – OPEN/CLOSED – Vacuum generator check valve located on
the vacuum generator. Holds the vacuum on the vacuum chamber.
Vac Cham Purge – OPEN/CLOSED – Located below the vacuum generator.
When open the vacuum on the vacuum chamber is released.
Heater Test – Operates heater and blower that supplies heat to the Heating Hopper.
T1s: Heating Hopper inlet temp setpoint.
T1a: Heating Hopper inlet temp actual.
Start: Starts the heater test. Blower will run during test.
Heater Output: Heater duty cycle expressed in percent
Blower: Status of blower
Control: PID or manual. Controller will modulate the heater as it would during
auto cycle. In manual mode the operator can select a heater duty cycle.
Edit Settings: Easy access to heater control parameters
Clean Out – Clean Out opens all valves and allows for material evacuation and cleanout.
Dump Heat Hopper – Opens the Vacuum Chamber Fill Valve, drains the Heating
Hopper.
Dump Vacuum Chamber – Opens Vacuum Chamber dump valve, draining Vacuum
Chamber
Dump All – Opens both the Vacuum Chamber Fill Valve and Vacuum Chamber dump
valve
Batch Mode
Batch Mode enables the dryer to dry a predetermined amount of material and then automatically stop and
display a message indicating the batch is complete. To turn on Batch Mode see: System Configuration /
System Preferences / Display Options / Batch Mode.
To enable and run the dryer in Batch Mode follow these steps from the Home Screen:
Press Start Batch Start Batch button is located on the Home Screen after Batch
Mode is enabled. Display will show: Batch Start Options.
Press Set Batch Target Keypad screen will display. Enter Batch Weight.
Press To save the batch weight or press the red X to cancel and exit.
Press Reset Totalizer to reset the totalized value back to zero (if applicable).
Press To save the entered batch weight and begin the batch and
start the Dryer. Press the red X to cancel.
Press Display will prompt for a password. (default: 22222) Then press:
Setup is divided into two categories: Dryer Configuration and System Configuration.
Dryer Configuration includes device specific settings such as: Alarm Setup, Auto-Stop
Setup, Dry Purge Setup, Preheat Setup, Auto-Start Setup, Convey Setup, Load-Cell
Setup, and Parameters.
System Configuration includes system wide general settings such as: print options,
diagnostics, resets, system preferences, and communications settings.
The following section describes the features within the Setup Menu.
Dryer Configuration
Setup Menu Option Description / Options
Alarm Setup Material Shortage Alarm
1st: Material Ready Alarm sounds after the first and only
the first batch of material is ready to drop from the
Vacuum Chamber.
ON: Material Ready Alarm sounds after every batch of
material is ready to drop from the Vacuum Chamber.
This mode can be useful in lab environments.
Print Alarm Log - Prints the Alarm Log. See page 69.
Clear Alarm Log - Clears the Alarm Log. See page 69.
Auto-Start Setup Auto-Starts the Dryer at a specified Time and Day(s). Can be set to
Auto-Start the Dryer at one time only or on a repeated schedule.
Must be turned ON in Display Setup (see below).
Auto-Stop Setup Auto-Stop the Dryer at a specified Time and Day(s). Can be set to
Auto-Stop the Dryer at one time only or on a repeated schedule.
Must be turned ON in Display Setup (see below).
Dry Purge Setup Purge Cham - OFF/CYC/ON – Controls when the vacuum chamber is
purged with membrane dried air.
Preheat Setup Preheat Mode - Auto or time - Preheat time for the material in the
Material Hopper. Default preheat time is 30 minutes.
Preheat Time - The Preheat Time is the duration of preheat time.
System Configuration
Print Options Print Setup - See page 69
• Print Parameters - Prints the parameter list to a USB.
• Print Alarm History - Prints the Alarm History to USB.
• Print Alarms and Event: Prints Alarm and Events to USB.
• Print All - Prints parameters, events, and alarms to USB.
• Copy Log File – Copies raw log file to USB.
System Preferences Change Passwords - Sets the Setup Menu Password. Default
password is 22222. Setting the password to 00000 disables
password protection.
Alarm and Event Log – Displays the Alarm and Event Log screen.
Parameters
All Maguire ULTRA controllers operate according to certain internal PARAMETERS. Because customer
requirements vary widely, we have made parameters accessible for change through the keypad. In most cases,
these parameters will never need to be changed. Some parameters that are routinely adjusted values are
adjustable from the main display. To access and edit the parameters, see Changing Parameters in this section:
Parameter Units
TIMES Are expressed as full seconds or full minutes.
PERCENTAGES are expressed as percentages.
TEMPERATURES are expressed in full degrees (Fahrenheit or Celsius).
TERM used to calculate a value.
3-letter Parameter title (units) – default parameter value
Acronym Parameter description
Blower
BDT - Blower Delay Time
format: xxxyy (seconds / seconds)
function(s): xxx: The amount of time between the blower powering-up and the heater
powering-up.
yy: The amount of time between the blower powering-down and the heater
powering-down.
BLF - Blower Low Frequency
format: xxxxx (Hz)
function(s): Minimum allowable user-enterable blower drive frequency. Note: this parameter is only
visible on units equipped with a VFD.
Dispensing
VCH - Vacuum Chamber High Level
format: xxxxx (lbs. or kgs.)
function(s): Vacuum chamber fill dispense target. Also known as “fill weight”.
Heater
PTS - Preheat Temperature Setpoint
format: xxxxx (°F or °C)
function(s): Target heating hopper air inlet temperature during preheat (when the Preheat Setpoint is
set to “Temperature”).
NH2 - Heating Hopper Heater No Heat Alarm [ULTRA-600 and ULTRA-1000 only]
format: xxxxx (seconds)
function(s): Maximum amount of time after the purge heat cycle begins during which one of the
following two conditions must be detected:
1. the purge air temperature must climb 20 degrees
2. the purge air temperature must move at least 20 percent toward the target
If neither condition is met, a “NO HEAT” alarm will be triggered.
Load Cell
KDF -Load Cell Stable Weight
format: xxxxx (counts)
function(s): Maximum allowable load cell fluctuations during a weight reading during filling
operations. A lower number will equate to a more accurate reading but could slow the
system down.
Vacuum
VTS -Vacuum Time Setting
format: xxyyy (minutes / minutes)
function(s): xx: Minimum user-enterable vacuum cycle time.
yyy: Vacuum cycle time.
System
ELT - Event Logging Time
format: xxxxx (seconds)
function(s): The amount of time between event log data line entries.
Changing Parameters
Press Display will prompt for a password. (default: 22222) Then press:
Press Dryer Configuration Display will show the Dryer Configuration categories.
Press The category that would Categories will have several parameters indicated by a 3-letter
contain the parameter you acronym on the left of the screen.
want to adjust.
Some categories have multiple pages. Navigate pages using
the arrow buttons at the lower-left of the screen.
Communications Setup
ULTRA-600 communications enabled software communication over Ethernet using the MLAN Protocol.
For more information about the MLAN Protocol and the ULTRA-600 Dryer see the MLAN Protocol
manual, available on the Maguire Products Inc website.
Press Display will prompt for a password. (default: 22222) Then press:
Press MLAN I.D. Number Display will show the MLAN I.D. Number screen.
Press Display will prompt for a password. (default: 22222) Then press:
Press TCP/IP Display will show the TCP/IP Configuration screen. On this
Configuration screen, enter the IP Address, Subnet Mask and Default
Gateway. Use the keypad to enter the number into the field
highlighted in green. To advance to the next field, touch
the field you want to edit and type the desired value.
Enabling Modbus
Press Display will prompt for a password. (default: 22222) Then press:
Press Modbus Server Display will show the Modbus Server screen. On this
screen, press the checkbox Enable to enable Modbus.
Maintenance
Drain and purge Air Filter / Regulator
The purpose of the air filter is to remove moisture and contaminants from the compressed
air supply and protect the pneumatic components of the Dryer. The air filter must be
periodically purged of moisture.
*Dryers received prior to 2019 will show moist as PINK and MOIST DRY
dry as BLUE
Air Pressure
Loadcell Calibration
Zero Weight Calibration
Press Display will prompt for a password. (default: 22222) Then press:
Press Vacuum Chamber Display will show the ZERO / FULL Calibration screen.
Zero/Full Calibration
Press ZERO Display will say: Confirm Vacuum Chamber is empty then
press ZERO. Gram weight of 0 follows successful
calibration.
Press
To return to the Load-Cell Setup screen.
Press Retention Hopper Display will show the ZERO / FULL Calibration screen.
Zero/Full Calibration
Press ZERO Display will say: Confirm Retention Hopper is empty then
press ZERO. Gram weight of 0 follows successful
calibration.
The ZERO point of the load cells is now set properly. FULL weight calibration may also be
done at this time; however, it probably is NOT NECESSARY. When load cell readings shift
due to rough handling, the entire range of readings from ZERO to FULL shift together. The
ZERO weight calibration routine resets the full range of the cells and, therefore, corrects FULL
weight readings as well.
Enter the EXACT weight that you have placed in the chamber. Weigh units are in tenths of a
pound or tenths of a kilogram depending on the weigh units set in LOAD Cell Setup menu. The
weight should be close to 35.0 lbs. or 16.0 kilograms.
After FULL weight calibration, if the display says (BAD CELL), the weight you are using does
not match the weight you entered, the chamber is not free to move, OR the load cells are bad.
Full Weight Calibrations - Full weight calibration will be done on both the Vacuum Chamber
and Retention Hopper. It is recommended to use a known weight of material for the Full
Calibration. Place approximately 35 lb. of material into the Heating Hopper. Using Manual
Operations, Operation Outputs, Vac Cham Fill, dispense the material from the Heating Hopper
to the Vacuum Chamber prior to entering the Full Calibration Routine.
If material totals are being observed loadcell full weigh calibration is recommended periodically
(approximately every six months).
The ZERO point of the load cells is now set properly. FULL weight calibration may also be
done at this time, however, it probably is NOT NECESSARY. When load cell readings shift
due to rough handling, the entire range of readings from ZERO to FULL shift together. The
ZERO weight calibration routine resets the full range of the cells and, therefore, corrects FULL
weight readings as well.
Press Display will prompt for a password. (default: 22222) Then press:
Press Dryer Configuration Display will show the Dryer Configuration categories.
Press Load-Cell Setup Display will show the Load-Cell Setup screen.
Press Vacuum Chamber Display will show the ZERO / FULL Calibration screen.
Zero/Full
Calibration
Press ZERO Display will say: Confirm Vacuum Chamber is empty then
press ZERO. Gram weight of 0 follows successful calibration.
Press FULL Display will show a keypad and the message: Enter the known
weight and then press ENTER. Enter your known weight in
GRAMS and then press ENTER.
Place the known weight in the Vacuum Chamber and then properly re-install the Vacuum Chamber into
the Dryer. Press CONTINUE to proceed.
Wait while calibrating load cells. Do not touch weigh bin during calibration. After Full calibration has
proceeded successfully, you will be prompted.
Do Not Perform a Clean Out Unless ULTRA-600 Dryer is First Properly Shut
Down.
For proper shutdown proceedure, see Startup and Operation on page 22.
During the Clean Out, keep hands and tools clear of all valves. DO NOT reach
into machine during Clean Out.
Note: use of the Heating Hopper Manual Dump Valve is optional. Material can be dumped into
the vacuum chamber, then into the retention hopper and conveyed away from the VTA at the
base of the dryer.
Both the Dump Heating Hopper screen button and the Heating
Hopper Drain Valve button (located near the upper rear of the
Vacuum Chamber area) can be used to empty the Heating
Hopper.
The Vacuum Chamber is non-removable. The Vacuum Chamber has a front facing cleanout
hatch. Prior to opening the front access hatch, removal of all material is recommended.
IMPORTANT: During the Clean Out, keep hands and tools clear of all valves. DO NOT reach
into machine during Clean Out.
Both the Dump Heating Hopper button and the Heating Hopper
Drain Valve button (located near the upper rear of the Vacuum
Chamber area) can be used to empty the Heating Hopper.
Clean Out / Dump All – Dump All opens all valves allowing material to flow freely through the
dryer. Material in the Heating Hopper will pass into the Vacuum Chamber and then pass into
the Retention Hopper. In this mode, it is possible to empty the entire dryer using a conveying
system pulling from the material outlet at the base of the dryer.
IMPORTANT: During the Clean Out, keep hands and tools clear of all valves. DO NOT reach
into machine during Clean Out.
Both the Dump Heating Hopper button and the Heating Hopper
Drain Valve button (located near the upper rear of the Vacuum
Chamber area) can be used to empty the Heating Hopper.
The Retention Hopper will slide out for easy access. Prior to sliding out the Retention Hopper
remove all material. Sliding out the Retention Hopper will open the bottom drain of the hopper.
Solution: Check for airflow from the blower. Check blower inlet
obstruction, check that 2” air duct from blower to heater is not
detached, obstructed or perforated. Check 2” air duct from top of
heater to heating hopper inlet for detachment, obstruction or
perforation. Check resistance across heater. Disconnecting heater
from circuit is not necessary to measure resistance. Measurement
should read 80 ohms. See wiring diagram on page 82. If the dryer’s
heater shorted, the result would be a trip of the breaker or fuse
supplying power to the ULTRA-600 dryer.
Solution: Allow the dryer to cool. Open the left side panel of the
dryer and locate the Heater Tube Safety Switch on the upper side of
the stainless-steel heater tube. Press the red safety switch button to
reset the Temperature Safety Switch. If problem occurs repeatedly,
contact Maguire Technical Support.
Solution: Allow the dryer to cool. Open the left side panel of the
dryer and locate the purge heater thermal safety switch on the side of
the stainless-steel purge heater tube. Press the red reset button to
reset the thermal safety switch. If problem occurs repeatedly, contact
Maguire Technical Support.
Solution:
Check material supply feeding the heating hopper. Check heating
hopper material flow (sticking material, melted material, hard to flow
regrind). Check Vacuum Chamber Fill Valve (butterfly valve below
heating hopper). Check air pressure (80 psi).
RESIDENCE ALARM Problem: Material has been in the retention hopper too
ALARM:23 long.
This alarm is triggered by the RAL parameter. When the Residence
Alarm has been enabled, this alarm will sound if not enough material
has been removed from the retention hopper in the time specified in
the RAL parameter. For more information, see the RAL parameter on
page 29.
Solution:
To prevent this alarm: decrease fill weight, or turn on Fill Weight
Adjust (Material Setup menu).
BATCH COMPLETE Batch is complete
ALARM:24 This alarm triggers at the end of a batch run, the end being defined as
the time at which the retention hopper is depleted to the HHL
parameter level after the final vacuum chamber dump of said batch
run.
1. To alert the operator that dry material is ready for the process.
Files will be created on the flash drive in the root of the drive.
Print Parameters Prints the full parameter and parameter values as well as other
information list to the USB flash drive.
Print Event and A combination of machine status lines at defined intervals as well as
Alarms mechanical events as they occur.
Print Alarm History Prints to USB any alarms recorded since the alarm log was last
cleared.
Copy Log File Copies raw log file to USB stick for analysis by a Maguire
technician.
Alarm Log - Display of the most recent log outputs. Toggle Select button to Alarm Log.
Event Log - The Event log is written to a file on a USB drive. To write the log file, toggle to wrench
mode, Print Setup, Print Event Log. Each log entry is a single line of information that was
recorded about the Dryer at the moment the line in the log was written.
The following is a description of the columns of information in a log. Note: line wrap in the manual due to
page space constraints. Actual log file continues as a single line with a carriage return after “ABS:”
08-20-2014 12:25:17
08-20-2014 10:10:08 | MODE: PHT | T1s: 180F | T1a: 90F | H1: 0.0 | T2s: 180F | T2a: 77F | H2: 7.5 | T3: 84F | T4: 78F | BLW: 0.00ma | LS: 98% | VTIME: 00:00/20:00 | ABS:
753mmHg | VT LC: 7 | RH LC: 6 | THROUGHPUT: 0
08-20-2014 10:10:23 | MODE: PHT | T1s: 180F | T1a: 90F | H1: 10.8 | T2s: 180F | T2a: 78F | H2: 7.5 | T3: 85F | T4: 78F | BLW: 0.00ma | LS: 98% | VTIME: 00:00/20:00 | ABS:
753mmHg | VT LC: 6 | RH LC: 6 | THROUGHPUT: 0
08-20-2014 10:10:39 | MODE: PHT | T1s: 180F | T1a: 112F | H1: 20.3 | T2s: 180F | T2a: 80F | H2: 14.3 | T3: 87F | T4: 78F | BLW: 0.00ma | LS: 98% | VTIME: 00:00/20:00 | ABS:
753mmHg | VT LC: 6 | RH LC: 6 | THROUGHPUT: 0
08-20-2014 10:10:54 | MODE: PHT | T1s: 180F | T1a: 145F | H1: 23.0 | T2s: 180F | T2a: 82F | H2: 14.3 | T3: 88F | T4: 78F | BLW: 0.00ma | LS: 98% | VTIME: 00:00/20:00 | ABS:
753mmHg | VT LC: 6 | RH LC: 6 | THROUGHPUT: 0
08-20-2014 10:11:09 | MODE: PHT | T1s: 180F | T1a: 165F | H1: 22.0 | T2s: 180F | T2a: 85F | H2: 20.3 | T3: 89F | T4: 79F | BLW: 0.00ma | LS: 98% | VTIME: 00:00/20:00 | ABS:
753mmHg | VT LC: 6 | RH LC: 6 | THROUGHPUT: 0
08-20-2014 10:11:24 | MODE: PHT | T1s: 180F | T1a: 172F | H1: 21.2 | T2s: 180F | T2a: 88F | H2: 20.3 | T3: 89F | T4: 79F | BLW: 0.00ma | LS: 98% | VTIME: 00:00/20:00 | ABS:
753mmHg | VT LC: 6 | RH LC: 10 | THROUGHPUT: 0
08-20-2014 10:11:39 | MODE: PHT | T1s: 180F | T1a: 174F | H1: 21.2 | T2s: 180F | T2a: 91F | H2: 25.5 | T3: 89F | T4: 80F | BLW: 0.00ma | LS: 98% | VTIME: 00:00/20:00 | ABS:
755mmHg | VT LC: 6 | RH LC: 10 | THROUGHPUT: 0
Blower:
Dispensing:
Heater:
Load Cell:
Vacuum:
System:
Alarm Flags:
Display Flags:
Heat Settings:
Misc. Settings:
Admin. Settings:
Blower VFD
T4 On
T5 Off
LOADCELL CALIBRATION
RH LC: 3303829 1588575 15422 Fri 06/17/2016 11:01 Thu 01/01/1970 00:00
VT LC: 3364083 1408275 16147 Fri 06/17/2016 11:01 Thu 01/01/1970 00:00
Press Display will prompt for a password. (default: 22222) Then press:
Press System Configuration Display will show the System Configuration categories.
Press User Settings Display will show Restore User Settings / Save User Settings.
Press Save User Settings Display will prompt for confirmation to save user settings.
Press Display will prompt for a password. (default: 22222) Then press:
Press System Configuration Display will show the System Configuration categories.
Press User Settings Display will show Restore User Settings / Save User Settings.
Press Restore User Settings Display will prompt for confirmation to Restore user settings.
Do not turn off controller or remove the flash drive while firmware
is updating! Doing so may corrupt the controller’s firmware.
Copy the new firmware update into a USB flash drive. (do not put in a directory)
Insert the USB Flash drive into the USB port on the ULTRA.
Press Display will prompt for a password. (default: 22222) Then press:
Press System Configuration Display will show the System Configuration categories.
Press Firmware Update The controller will search the USB drive for a firmware update
file with the XUF extension.
Select the file from the white display area on the left. If more than one firmware version is stored
on the flash drive, multiple version will be displayed in the white display area. If the
display is blank check USB for the file and that the file is location directly on the drive (not
in a sub-folder). Exit out of this screen and enter again to refresh the display window.
Highlight the version in the white panel on the left and press PROGRAM.
Press To proceed with the firmware update or press
the red X to cancel and exit.
The display will show progress in transferring to the internal SD card, then it will show
progress in verifying the update file. Then the controller will prompt: “Please toggle power.”
At this time, remove the flash drive, power off the controller then on. When the controller
restarts the display will show progress updating to the new firmware. When complete, the
display will show: UPDATES COMPLETE Toggle power. At this time turn off power, then
turn back on.
Software updates can be supplied electronically, via email or by download. Software updates are named according to their
date of release. For instance, VTQ0620A.XUF can be interpreted as VT=Vacuum Touchscreen, Q=2017 (R=2018), 06=June,
20=June 20th, A=the first revision for that day. During the update process detailed above, new software found on the USB
flash drive is first copied to an internally mounted SD card. From the SD card, the software is then loaded into the ULTRA. If
there is ever a problem with the ULTRA and the USB port cannot be used or the ULTRA software is corrupted and cannot load
new software through the menu, new software can be acquired from Maguire and renamed VTUPDATE.XUF. This renamed
software can be copied onto the Flash Drive and inserted into the USB port of the ULTRA. When the ULTRA is turned on, this
VTUPDATE.XUF file will be automatically loaded into the dryer, restoring the software.
General Information
ULTRA-600 Technical Specifications
SCOPE
- Provide up to 600 pounds per hour (272 kg/hr) of dry material to an injection molding or
extrusion platform utilizing energy efficient vacuum drying technology. Drying temperature
up to 350º F (185º C).
POWDER REQUIREMENTS
- Voltage: 480 Vac, 3 Phase, 60 Hz or 400 Vac, 3 Phase, 50 Hz
- FLA: 49 / 54
- Disconnect: 60 amp
- Air: 85 psi / 6 bar
- Heating Element: Primary: 20 Kw, Secondary: 1.25 kW (purge circuit)
- Blower: 8.5 HP, 350 SCFM @ 40” water
HEATING HOPPER
- Capacity: 420 lbs. (191 kg)
- Insulated construction, 4” of R-15 insulation
- Large Access Door
- Diffuser cone
- 304 Stainless steel internal wall construction, material contact
VACUUM CHAMBER
- Capacity: 195 lb. (88 kg)
- Rail mounted for ease of removal
- Insulated construction, 4” of R-7.5 insulation
- Access Hatch, insulated glass with captive air gap insulation
- 304 Stainless steel internal wall construction, material contact
- Unions on most air connections for ease of maintenance
- Load cell based continuous level control
RETENTION HOPPER
- Capacity: 215 lb. (98 kg)
- Insulated construction, 4” of R-7.5 insulation
- 304 Stainless steel internal wall construction, material contact
- Load cell based continuous level control
CONTROLLER
- Microprocessor based control (Motorola 6812)
- 4 x 20 character Blue back lit display
- 4 Digit 1” high Red LED for display of Actual or Set Temperature
- Icon representation of function
- Flash Memory, SD card with micro capability
- Ethernet & USB ports
- Optional CANbus communications for remote / repeater control
ELECTRICS
- Main Disconnect, 60 Amp, class J fuses
- Altec Euro style disconnects
- Step down transformer with regulated DC power supply
- 70 cfm cooling fan, bottom vented
- 8.5 HP regenerative blower, 350 SCFM w/ VFD
- RTD Inputs, 3: Heating hopper inlet, Heating hopper exit, Dry Purge inlet
VACUUM CIRCUIT
- 6 Element, 3 Stage PIAB configuration for maximum effectiveness
- 1” Electro-pneumatic check valve
Standard atmospheric pressure can support a column of Mercury 29.92 inches (760mm) high. If
we pull a perfect vacuum above a column of Mercury, the mercury will rise in that column 29.92
inches and, for that reason, the number we can expect to read on the vacuum gauge, at full
vacuum, is 29.92 inches. Lesser vacuums read lower numbers. No vacuum reads zero.
When water is subjected to a vacuum level of 25 inches (635mm) of mercury, it will boil at 133F
(56C) degrees. When plastic pellets are heated to 160F (71C) degrees, or greater, and subjected
to a vacuum of 25 inches (635mm), the water vapor within wants very much to boil. This
increased molecular activity within the pellet and the greatly reduced pressure surrounding the
pellet drives the moisture from the pellet in a remarkably short time. This then is the reason for
the remarkable short drying time of an ULTRA vacuum dryer.
PERFORMANCE
The true measure of a dryer's performance is determined by the moisture content of the resin
after the dryer has done its job. Resin moisture content, however, is not easily measured, so
dryer manufactures use other criteria to assure performance.
For example, for a particular resin, experience may tell us that 180f (82c) degree air dried to
minus 40 dew point, and passed over the material for 4 hours, is sufficient to reduce the moisture
content of that resin to the required level of dryness.
Since our ULTRA Dryer does NOT use dry air, we have no "dew point" to measure.
In our case, for the same resin, experience tells us that a vacuum of 25 inches (635mm) applied
for 20 minutes to material that has been heated to 180f (82c) degrees, is sufficient to reduce the
moisture content of that same resin to the correct level of dryness.
Therefore, just as desiccant driers assure dry material by measuring temperature and DEW
POINT over time, we assure dry material by measuring temperature and VACUUM over time.
When we assure that a certain temperature has been reached and a certain vacuum level
achieved for a correct length of time, we can then be assured the material is dry.
You may visually assess performance by monitoring temperature and vacuum levels yourself. Of
course, the final test is in the quality of the product you manufacture. We welcome your
comments and observations.
Warranty
MAGUIRE PRODUCTS offers THE MOST COMPREHENSIVE
WARRANTY in the plastics auxiliary equipment industry. We
warrant each MAGUIRE ULTRA DRYER manufactured by us to be
free from defects in material and workmanship under normal use
and service; our obligation under this warranty being limited to
making good at our factory any Dryer which shall, within FIVE (5)
YEARS after delivery to the original purchaser, be RETURNED
intact to us, transportation charges PREPAID, and which our
examination shall disclose to our satisfaction to have been thus
defective; this warranty being expressly in lieu of all other
warranties expressed or implied and of all other obligations or
liabilities on our part, and MAGUIRE PRODUCTS neither assumes
nor authorizes any other persons to assume for it any other liability in connection with the sale of its
Dryers.
This warranty shall not apply to equipment repaired or altered outside MAGUIRE PRODUCTS INC.
factory, unless such repair or alteration was, in our judgment, not responsible for the failure; nor which
has been subject to misuse, negligence or accident, incorrect wiring by others,
or installation or use not in accord with instructions furnished by
Maguire Products, Inc.
Our liability under this warranty will extend only to equipment that is returned to our factory in Aston,
Pennsylvania, PREPAID.
Please note that we always strive to satisfy our customers in whatever manner is deemed most expedient
to overcome any problems they may have in connection with our equipment.
This dryer is of a new design. We have had excellent results in all tests performed to date, but we HAVE
NOT tested every material available to the plastics industry. We have not anticipated all possible
materials, processing conditions, and requirements. We are not certain that our equipment will perform
properly in all instances. You must observe and verify the performance level of this equipment in your
plant as part of your overall manufacturing process. You must verify to your own satisfaction that this
level of performance meets your requirements. We CAN NOT be responsible for losses due to product
not dried correctly, even when due to equipment malfunction or design incorrect for your requirements;
and/or any consequential losses due to our equipment not drying material to your requirements.
We will only be responsible to correct, repair, replace, or accept return for full refund, our equipment if it
fails to perform as designed, or we have inadvertently misrepresented our equipment for your application.
If for any reason this disclaimer is not acceptable, we will accept return of the equipment for full refund,
including freight costs both ways.
line
MPI p/n Description General Location
item
1 hf23-E replacement filter element, blower intake upper rear panel
2 8324-11 silicone seal, vacuum chamber dump valve vacuum chamber
3 go-365V o-ring, size 365, Viton upper vacuum gate
4 go-359V o-ring, size 359, Viton lower vacuum gate
5 8324-03 vac. seal plate assy.,vac. cham. dump valve lower vacuum gate
6 nv88 solenoid valve segment, 4-way, 24 VDC main cabinet
7 nf-AW40f filter element, for "AW30" series regulator pneumatics cabinet
8 nf-AFM40f filter element, for oil separator pneumatics cabinet
Wiring Diagrams
ULTRA-600 I/O Board Wiring Diagram
Maguire Europe
Tame Park
Tamworth
Staffordshire
B775DY
UK
Tel: + 44 1827 265 850
Fax: + 44 1827 265 855
Email: info@maguire-europe.com