7 December 2020 BLUE POWER HOUSE ELECTRICAL

ADIDAS @ LAGOONA MALL

OPERATIONAL & MAINTENANCE MANUAL


7 December 2020 BLUE POWER HOUSE ELECTRICAL

 PROJECT NAME: ADIDAS

 LOCATION: LAGOONA MALL

 FIT-OUT CONTRACTOR: INTELLIGENT DESIGN CONTRACTING

 CONSULTANT: MZ PARTNERS

 PROJECT COMMENCMENT DATE: 21ST OCTOBER 2020

 PROJECT HAND OVER DATE: 30TH NOVEMBER 2020


7 December 2020 BLUE POWER HOUSE ELECTRICAL

INDEX

 LIST OF MATERIALS AND SUPPLIERS

1. ELECTRICAL AND FIRE ALARM


2. HVAC AND FIRE FIGHTING

 MATERIAL SUBMITTALS WITH APPROVALS

1. ELECTRICAL AND FIRE ALARM


2. HVAC AND FIRE FIGHTING

 SHOP DRAWING APPROVED FROM CONSULTANT

1. ELECTRICAL AND FIRE ALARM


2. HVAC AND FIRE FIGHTING

 SITE INSPECTION REPORT

1. ELECTRICAL AND FIRE ALARM


2. HVAC AND FIRE FIGHTING

 GURANTEE AND WARRANTEE CERTIFICATE

 AS BUILT DRAWING WITH APPROVAL

 TESTING AND COMMSSIONING REPORTS

1. ELECTRICAL AND FIRE ALARM REPORTS


2. MECHANICAL REPORT
7 December 2020 BLUE POWER HOUSE ELECTRICAL

LIST OF MATERIALS AND SUPPLLIERS

1. CONTACT DETAILS

NAME DESIGNATION COMPANY TRADE CONTACT


Mr. Supreeth Dsouza Project Manager BPHE MEP +974-77035818
Mr. Wilson Simon Project Engineer BPHE MEP +974-30023822
Mr. Suraj Dsouza Project Coordinator BPHE MEP +974-70021138

2. ELECTRICAL AND FIRE ALARM SUPPLIERS

NAME DESIGNATION LOCAL SUPPLIER USED MATERIAL CONTACT NO.


Mr.Shanavas Sales Engineer Electrocoms G.I CONDUITS +974-7070 9529
Mr. Shebin Sales Engineer Falkland Cables +974-50118892
Mr. Kshithish Sales Engineer Mohammed Al Muftah Ceiling Rose +974-74475579
Mr. Shanavas Sales Engineer Electrocoms PVC Conduits +974-7070 9529
Mr. Satheesh Sales Engineer Safetech Trading Emergency Exit +974-55958204
Lights
Mr. Vipin Sales Engineer Thermal Arabia Sounder and +974-74797094
Chandran Smoke Detectors
Mr. Shebin Sales Engineer Falkland Fire Rated cables +974-50118892
Mr. Shabin Sales Engineer Falkland Switches and +974-50118892
Sockets

3. MECHANICAL AND FIRE FIGHTING SUPPLIERS

NAME DESIGNATION LOCAL SUPPLIER USED MATERIAL CONTACT NO.


Mr. Shadi Sales Engineer Taj Duct Fab factory Diffusers +974-55819757
Mr. Shamnaz Sales Engineer Tech Hans Insulation 974-33844094
Mr. Sunny Sales Engineer Pipeline trading GI Pipes +974-55061085
Mr. Satheesh Sales Engineer Vigilant Trading Sprinklers +97-70605152
Mr. Sunny Sales Engineer Pipeline Trading OS&Y Valve +974-55061085
Mr. Sunny Sales Engineer Pipeline Trading Supervisory +974-55061085
Mr. Shabin Sales Engineer Falkland Switches and +974-50118892
Sockets
Mr. Imtiaz Sales Engineer Inovec PICV +974-66252766
Hussain
Mr. Krishna Sales Engineer Firepink Trading Fire Hose Reel +974-33469965
7 December 2020 BLUE POWER HOUSE ELECTRICAL

 MATERIAL SUBMITTALS WITH APPROVALS


7 December 2020 BLUE POWER HOUSE ELECTRICAL

 ELECTRICAL AND FIRE ALARM SUBMITTALS

 CABLES

 EMERGENCY AND EXIT LIGHTS

 CEILING ROSE

 G.I CONDUITS

 FIRE RATED CABLES

 MANUAL PULL STATION

 SMOKE DETECTORS

 SOUNER WITH STROBE LIGHTS


CR-7006 LED Emergency Light

FEATURES
Injection-molded thermoplastic ABS housing
UL-94V-0 flame rating, fire-resistant
Input Voltage: 220-240V
Power consumption: 3W max.
Output: 4W max.
Input: 1.2W
3.6V Nickel Cadmium Battery
Charging time: 24 hours
Discharge time: 180 minutes
Operating temperature: 0°C~40°C
Dimension: 401.7*130.5*103.7mm

PHOTOMETRIC

ORDER INFORMATION
Model Voltage Emergency Duration Certificate
CR-7006 120/277V 90 minutes UL, CUL
CR-7006-220 220-240V 180 minutes UL, UAE-COC
CR-7006D 110-240V 180 minutes N/L
CR-7007GX-220 EXIT SIGN

Product Overview
CR-7007GX-220 comes with super bright LED, the total power rate is 2W. The lifespan of LED is more than
50,000 hours. With 3.6V 600mAh nickel-cadmium battery, it allows the light last more than 180 minutes after
power failure.

Features
*Injection-molded thermoplastic ABS housing

*UL-94V-0 flame rating, fire-retardant

*Wall, side and ceiling mounting

*Input Voltage: 220-240VAC 50Hz

*Super bright LED 2W

*Nickel Cadmium Battery

*Test button and charge indicator light

*Backup time: ≥180minutes

*Conversion time: <0.2second

*IP Class: IP20


Packing
*Insulation: II, Range: 80m²
39*31.8*38.5CM
*Operating Temperature: 0℃~40℃ 12PCS/CTN

*Overcharge & Over-discharge protection G.W.: 11.50KG

*Dimension: 299 x 184.5 x 44.6 MM N.W.: 10.00 KG


CR-7031-220 BULKHEAD EMERGENCY LIGHT

Product Overview
CR-7031 comes with 30PCS SMD LED, the total power rate is 3W. The lifespan of LED is more than 50,000 hours.
With 3.6V 1000mAh nickel-cadmium battery, it allows the lamps last more than 180 minutes after power failure.

Features
*Injection-molded thermoplastic ABS housing

*UL-94V-0 flame rating, fire-retardant

*Wall mounting

*Input Voltage: 220-240VAC 50Hz

*Super bright SMD LED 3W

*Nickel Cadmium Battery

* IP65 waterproof

*Backup time: ≥180minutes

*Conversion time: <0.2second

*Insulation: II, Range: 80m² Packing

*Operating Temperature: 0℃~40℃ 49*35*34CM

*Overcharge & Over-discharge protection 4PCS/CTN

G.W.: 9.80 KG

N.W.: 9.30 KG
‫‪2020-03-30‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻟﻄﺒﺎﻋﺔ ‪:‬‬ ‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴــــﺔ‬
‫‪AM 8:12‬‬ ‫ﻭﻗـﺖ ﺍﻟﻄﺒﺎﻋﺔ ‪:‬‬ ‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺓ ﻟﻟﺩﻓﺎﻉ ﺍﻟﻣﺩﻧﻲ‬
‫‪PAC20003249‬‬ ‫ﺭﻗــﻢ ﺍﻟﻄﻠـﺐ ‪:‬‬ ‫ﺍﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺷﻬــــــﺎﺩﺓ ﻋﺪﻡ ﻣﻤﺎﻧﻌﺔ‬

‫‪ :‬ﺍﻋﺘﻤﺎﺩ ﻣﻨﺘﺞ‬ ‫ﻧﻮﻉ ﺍﻟﺸﻬﺎﺩﺓ‬

‫ﺑﻴﺎﻧﺎﺕ ﺍﻟﻤﻨﺸﺄﺓ‬

‫‪ :‬ﺳﻴﻔﺘﻚ ﺍﻟﻜﺘﺮﻭﻣﻴﻜﺎﻧﻴﻚ ﻟﻠﺘﺠﺎﺭﺓ ﻭﺍﻟﻤﻘﺎﻭﻻﺕ‬ ‫ﺍﻹﺳﻢ ﺍﻟﺘﺠﺎﺭﻱ‬


‫‪67018 :‬‬ ‫ﺭﻗﻢ ﺍﻟﺮﺧﺼﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ‬ ‫‪39385 :‬‬ ‫ﺭﻗﻢ ﺍﻟﺴﺠﻞ ﺍﻟﺘﺠﺎﺭﻱ‬
‫‪:‬‬ ‫ﺭﻗﻢ ﺍﻟﻬﺎﺗﻒ‬ ‫‪12-8917-00 :‬‬ ‫ﺭﻗﻢ ﻗﻴﺪ ﺍﻟﻤﻨﺸﺄﺓ‬
‫‪:‬‬ ‫ﺍﻟﺒﺮﻳﺪ ﺍﻹﻟﻜﺘﺮﻭﻧﻲ‬
‫‪Fire alarm systems :‬‬ ‫ﺍﻟﺘﺼﻨﻴﻒ‬
‫‪Emergency Power Supply System, Units and Components :‬‬ ‫ﺇﺳﻢ ﺍﻟﻤﻨﺘﺞ‬

‫ﺗﻔﺎﺻﻴﻞ ﺍﻟﺸﻬﺎﺩﺓ‬

‫ﺗﻢ ﻣﺮﺍﺟﻌﺔ ﺍﻟﻄﻠﺐ ﺍﻟﻤﻘﺪﻡ ﻭﺍﺗﻀﺢ ﺑﺄﻧﻪ ﻻ ﻣﺎﻧﻊ ﻣﻦ ﺍﻋﺘﻤﺎﺩ ﺍﻟﻤﻨﺘﺞ ‪/‬ﺍﻟﻤﻨﺘﺠﺎﺕ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻰ ﺍﻟﻤﺮﻓﻖ ﺑﻨﺎﺀ ﻋﻠﻰ ﺍﻋﺘﻤﺎﺩﻩ ﻣﻦ ﻗﺒﻞ ﺍﻟﻬﻴﺌﻪ‬
‫ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﺭ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ‪.‬‬

‫ﻣﻼﺣﻈﺎﺕ‬

‫‪ .1‬ﻳﺠﺐ ﻋﻠﻰ ﺍﻟﺸﺮﻛﻪ ﺍﻻﻟﺘﺰﺍﻡ ﻭﺍﻟﻌﻤﻞ ﺑﻤﺎ ﺟﺎﺀ ﻓﻲ ﺍﺷﺘﺮﺍﻃﺎﺕ ﻗﺴﻢ ﺃﻧﻈﻤﺔ ﺍﻟﺴﻼﻣﻪ ﺍﻟﺘﻲ ﺗﻢ ﺍﻻﻃﻼﻉ ﻭﺍﻟﻤﻮﺍﻓﻘﺔ ﻋﻠﻴﻬﺎ ﻣﻦ ﺧﻼﻝ ﺍﻟﻤﻮﻗﻊ‪.‬‬
‫‪ .2‬ﻳﺠﺐ ﺍﻥ ﻳﻘﻮﻡ ﺑﺘﺮﻛﻴﺐ ﻫﺬﺍ ﺍﻟﻤﻨﺘﺞ ﻣﻦ ﻗﺒﻞ ﻣﻬﻨﺪﺳﻴﻦ ﻭﻓﻨﻴﻴﻦ ﻣﻌﺘﻤﺪﻳﻦ ﻣﻦ ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‪.‬‬
‫‪ .3‬ﻳﺠﺐ ﺍﻥ ﻳﺤﻤﻞ ﺍﻟﻤﻨﺘﺞ ﺍﻟﻌﻼﻣﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ ﻟﻠﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻌﺘﻤﺪﺓ ﻭﺍﻟﻤﻮﺿﺤﻪ ﻓﻲ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ ‪.‬‬

‫‪2022-03-30‬‬ ‫‪:‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻹﻧﺘﻬﺎﺀ‬ ‫‪2020-03-30‬‬ ‫‪:‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻻﻋﺘﻤﺎﺩ‬

‫ﻉ‪/‬‬

‫ﻣﺪﻳﺮ ﺍﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺓ ﻟﻟﺩﻓﺎﻉ ﺍﻟﻣﺩﻧﻲ‬

‫‪Page 1 of 2‬‬
‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
DATE : 2020-03-30 : ‫ﺍﻟﺘﺎﺭﻳـــــــﺦ‬
‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬
PERMIT # PAC20003249 : ‫ﺭﻗﻢ ﺍﻟﻄﻠﺐ‬
‫ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

TECHNICAL REPORT ‫ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ‬


PRODUCT Emergency Power Supply System, Units and Components ‫ﻣﻨﺘﺞ‬
PRODUCT APPLICATION Fire alarm systems ‫ﺗﺼﻨﻴﻒ ﺍﻟﻤﻌﺪﺓ‬
APPLICANT / P.O BOX ‫ﺳﻴﻔﺘﻚ ﺍﻟﻜﺘﺮﻭﻣﻴﻜﺎﻧﻴﻚ ﻟﻠﺘﺠﺎﺭﺓ ﻭﺍﻟﻤﻘﺎﻭﻻﺕ‬ ‫ﻣﻘﺪﻡ ﺍﻟﻄﻠﺐ‬
Ningbo Changrong Lighting and Electronics Technology Co.
MANUFACTURER / LOCATION ‫ ﺑﻠﺪ ﺍﻟﺼﻨﻊ‬/ ‫ﺍﻟﺸﺮﻛﺔ ﺍﻟﻤﺼﻨﻌﺔ‬
Ltd / CHINA
‫ﺍﻟﻮﺻﻒ‬ ‫ﺍﻟﻤﻮﺩﻳﻞ‬
Emergency Exit Sign; Wall / Ceiling Mounted "Green Letters"; Voltage Rating: 230Vac, 50Hz
CR-7007GX-220
Light Source: Super bright LED 2W; Duration: 3 hrs; Battery Type: 3.6V 350mAh NiCd
Emergency Exit Sign; Wall / Ceiling Mounted "Red Letters"; Voltage Rating: 230Vac, 50Hz
CR-7007RX-220
Light Source: Super bright LED 4W; Duration: 3 hrs; Battery Type: 3.6V 350mAh NiCd
Bulkhead LED Emergency Light; Wall Mounted; Voltage Rating: 230Vac, 50Hz;
CR-7031-220
Light Source: Super bright LED 3W; Duration: 3 hrs; Battery Type: 3.6V 1500mAh NiCd
Emergency Exit Sign; Wall / Ceiling Mounted "Green Letters"; Voltage Rating: 230Vac, 50Hz
CR-7007GX
Light Source: Super bright LED 2W; Duration: 1.5 hrs; Battery Type: 3.6V 350mAh NiCd
Emergency Exit Sign; Wall / Ceiling Mounted "Red Letters"; Voltage Rating: 230Vac, 50Hz
CR-7007RX
Light Source: Super bright LED 2W; Duration: 1.5 hrs; Battery Type: 3.6V 350mAh NiCd
LED Emergency Light; Wall Mounted "Dual Head"
CR-7006-220
Voltage Rating: 230Vac, 50Hz; Duration: 3 hrs; Battery Type: NiCd 3.6V 1500mah
3RD PARTY CERTIFICATE /
Underwriters Laboratories ‫ﺷﻬﺎﺩﺓ ﺍﻟﻤﺨﺘﺒﺮﺍﺕ ﺍﻟﻤﺴﺎﻧﺪﺓ‬
APPROVAL FTBR.E489087
(UL) ( ‫)ﻣﻦ ﻫﻴﺌﺎﺕ ﻣﻌﺘﻤﺪﺓ‬

RECOMMENDATIONS ‫ﺍﻟﺘﻮﺻﻴﺎﺕ‬
Notes:
1.This product approval shall comply with the Design, Inspection, Installation, Testing and Maintenance requirements of
NFPA 101 (and/or other related NFPA Codes / Standards), other acceptable International Codes / Standards, Local
Regulations, Listing Instructions and/or Manufacturer's Published Instructions subject to the technical review and approval
of the Authority Having Jurisdiction / Qatar Civil Defence.

2.The basic standard used to investigate products in this category is ANSI/UL 924, "Emergency Lighting and Power
Equipment."

/‫ﻉ‬

‫ﻣﺪﻳﺮ ﺍﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺓ ﻟﻟﺩﻓﺎﻉ ﺍﻟﻣﺩﻧﻲ‬

Page 2 of 2
‫‪2020-08-11‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻟﻄﺒﺎﻋﺔ ‪:‬‬ ‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴــــﺔ‬
‫ﺹ ‪6:53‬‬ ‫ﻭﻗـﺖ ﺍﻟﻄﺒﺎﻋﺔ ‪:‬‬ ‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺓ ﻟﻟﺩﻓﺎﻉ ﺍﻟﻣﺩﻧﻲ‬
‫‪PAC20007643‬‬ ‫ﺭﻗــﻢ ﺍﻟﻄﻠـﺐ ‪:‬‬ ‫ﺍﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺷﻬــــــﺎﺩﺓ ﻋﺪﻡ ﻣﻤﺎﻧﻌﺔ‬

‫‪ :‬ﺍﻋﺘﻤﺎﺩ ﻣﻨﺘﺞ‬ ‫ﻧﻮﻉ ﺍﻟﺸﻬﺎﺩﺓ‬

‫ﺑﻴﺎﻧﺎﺕ ﺍﻟﻤﻨﺸﺄﺓ‬

‫‪ :‬ﺷﺮﻛﻪ ﺍﺩﺍﺭﻩ ﻭﺗﻮﺭﻳﺪ ﺍﻟﻤﻮﺍﺩ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﻪ ﻗﻄﺮ‬ ‫ﺍﻹﺳﻢ ﺍﻟﺘﺠﺎﺭﻱ‬


‫‪25726 :‬‬ ‫ﺭﻗﻢ ﺍﻟﺮﺧﺼﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ‬ ‫‪35356 :‬‬ ‫ﺭﻗﻢ ﺍﻟﺴﺠﻞ ﺍﻟﺘﺠﺎﺭﻱ‬
‫‪:‬‬ ‫ﺭﻗﻢ ﺍﻟﻬﺎﺗﻒ‬ ‫‪12-4391-00 :‬‬ ‫ﺭﻗﻢ ﻗﻴﺪ ﺍﻟﻤﻨﺸﺄﺓ‬
‫‪:‬‬ ‫ﺍﻟﺒﺮﻳﺪ ﺍﻹﻟﻜﺘﺮﻭﻧﻲ‬
‫‪Fire alarm systems :‬‬ ‫ﺍﻟﺘﺼﻨﻴﻒ‬
‫‪Cables (Fire Rated, Electrical and Communication) and Wiring Accessories :‬‬ ‫ﺇﺳﻢ ﺍﻟﻤﻨﺘﺞ‬

‫ﺗﻔﺎﺻﻴﻞ ﺍﻟﺸﻬﺎﺩﺓ‬

‫ﺗﻢ ﻣﺮﺍﺟﻌﺔ ﺍﻟﻄﻠﺐ ﺍﻟﻤﻘﺪﻡ ﻭﺍﺗﻀﺢ ﺑﺄﻧﻪ ﻻ ﻣﺎﻧﻊ ﻣﻦ ﺍﻋﺘﻤﺎﺩ ﺍﻟﻤﻨﺘﺞ ‪/‬ﺍﻟﻤﻨﺘﺠﺎﺕ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻰ ﺍﻟﻤﺮﻓﻖ ﺑﻨﺎﺀ ﻋﻠﻰ ﺍﻋﺘﻤﺎﺩﻩ ﻣﻦ ﻗﺒﻞ ﺍﻟﻬﻴﺌﻪ‬
‫ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﺭ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ‪.‬‬

‫ﻣﻼﺣﻈﺎﺕ‬

‫‪ .1‬ﻳﺠﺐ ﻋﻠﻰ ﺍﻟﺸﺮﻛﻪ ﺍﻻﻟﺘﺰﺍﻡ ﻭﺍﻟﻌﻤﻞ ﺑﻤﺎ ﺟﺎﺀ ﻓﻲ ﺍﺷﺘﺮﺍﻃﺎﺕ ﻗﺴﻢ ﺃﻧﻈﻤﺔ ﺍﻟﺴﻼﻣﻪ ﺍﻟﺘﻲ ﺗﻢ ﺍﻻﻃﻼﻉ ﻭﺍﻟﻤﻮﺍﻓﻘﺔ ﻋﻠﻴﻬﺎ ﻣﻦ ﺧﻼﻝ ﺍﻟﻤﻮﻗﻊ‪.‬‬
‫‪ .2‬ﻳﺠﺐ ﺍﻥ ﻳﻘﻮﻡ ﺑﺘﺮﻛﻴﺐ ﻫﺬﺍ ﺍﻟﻤﻨﺘﺞ ﻣﻦ ﻗﺒﻞ ﻣﻬﻨﺪﺳﻴﻦ ﻭﻓﻨﻴﻴﻦ ﻣﻌﺘﻤﺪﻳﻦ ﻣﻦ ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‪.‬‬
‫‪ .3‬ﻳﺠﺐ ﺍﻥ ﻳﺤﻤﻞ ﺍﻟﻤﻨﺘﺞ ﺍﻟﻌﻼﻣﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ ﻟﻠﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻌﺘﻤﺪﺓ ﻭﺍﻟﻤﻮﺿﺤﻪ ﻓﻲ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ ‪.‬‬

‫‪2022-08-10‬‬ ‫‪:‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻹﻧﺘﻬﺎﺀ‬ ‫‪2020-08-10‬‬ ‫‪:‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻻﻋﺘﻤﺎﺩ‬

‫ﻉ‪/‬‬

‫ﻣﺪﻳﺮ ﺍﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺓ ﻟﻟﺩﻓﺎﻉ ﺍﻟﻣﺩﻧﻲ‬

‫‪Page 1 of 2‬‬
‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
DATE : 2020-08-11 : ‫ﺍﻟﺘﺎﺭﻳـــــــﺦ‬
‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬
PERMIT # PAC20007643 : ‫ﺭﻗﻢ ﺍﻟﻄﻠﺐ‬
‫ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

TECHNICAL REPORT ‫ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ‬


Cables (Fire Rated, Electrical and Communication) and
PRODUCT ‫ﻣﻨﺘﺞ‬
Wiring Accessories
PRODUCT APPLICATION Fire alarm systems ‫ﺗﺼﻨﻴﻒ ﺍﻟﻤﻌﺪﺓ‬
APPLICANT / P.O BOX ‫ ﻗﻄﺮ‬- ‫ﺷﺮﻛﻪ ﺍﺩﺍﺭﻩ ﻭﺗﻮﺭﻳﺪ ﺍﻟﻤﻮﺍﺩ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﻪ‬ ‫ﻣﻘﺪﻡ ﺍﻟﻄﻠﺐ‬
MANUFACTURER / LOCATION Prysmian Cables and Systems Limited / U K ‫ ﺑﻠﺪ ﺍﻟﺼﻨﻊ‬/ ‫ﺍﻟﺸﺮﻛﺔ ﺍﻟﻤﺼﻨﻌﺔ‬
‫ﺍﻟﻮﺻﻒ‬ ‫ﺍﻟﻤﻮﺩﻳﻞ‬
Fire Resistant Cables; Fire Rating: 950C for 3 hours; Solid / Stranded Conductor
FP200 Gold
Conductor Sizes (mm) 1.0, 1.5, 2.5 & 4.0; Number of Core: 2, 3 & 4; Voltage Rating: 300 / 500
3RD PARTY CERTIFICATE / ‫ﺷﻬﺎﺩﺓ ﺍﻟﻤﺨﺘﺒﺮﺍﺕ ﺍﻟﻤﺴﺎﻧﺪﺓ‬
APPROVAL 077f/01 LPCB-BRE
( ‫)ﻣﻦ ﻫﻴﺌﺎﺕ ﻣﻌﺘﻤﺪﺓ‬

RECOMMENDATIONS ‫ﺍﻟﺘﻮﺻﻴﺎﺕ‬
Notes:
1.This product approval shall comply with the Design, Inspection, Installation, Testing and Maintenance requirements of
NFPA 72 (and/or other related NFPA Codes / Standards), other acceptable International Codes / Standards, Local
Regulations, Listing Instructions and/or Manufacturer's Published Instructions subject to the technical review and approval
of the Authority Having Jurisdiction / Qatar Civil Defence.

2.Meets the requirements of BS 7629-1:2015 (Standard 30) BS 7629-1:2015 (Standard 60) BS 6387:2013 (CWZ) EN
50200:2015 (Class PH30 & PH120) EN 50200:2015 Annex E (30 mins) BS 5839-1:2013 (Clause 26.2d Standard)

/‫ﻉ‬

‫ﻣﺪﻳﺮ ﺍﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺓ ﻟﻟﺩﻓﺎﻉ ﺍﻟﻣﺩﻧﻲ‬

Page 2 of 2
Wiring BG-12LX
To Addressable Pull Station
Next Document 52141 I56-3655-003
Addressable
From Device
FACP
SLC
BG-12LX Addressable Pull Station
SLC

Document 52141 I56-3655-003


1 2 3 4

Description
STRIP GAUGE

The BG-12LX Addressable pull station is a non-coded, dual-action manual pull station with
a key-lock reset feature. It provides Fire•Lite intelligent control panels with one addressable
alarm initiating input. The addressable module is housed inside the pull station. The BG-
12LX is compatible with all Fire•Lite intelligent panels. The BG-12LX meets the ADAAG
controls and operating mechanisms guidelines (section 4.1.3[13]), and the ADA require-
ment for a 5 lb. maximum pull force to activate the pull station. Operating instructions are
molded into the pull station handle along with Braille text. Molded Terminal numbers are
also present. Conforms to ANSI/UL Standard 38 and ULC Standard S528.

P0194-01
P0267-00
Ratings
Normal Operating Voltage: 24 VDC.
Average Operating Current (LED Flash): 375 µA.
Maximum Operating Current (LED On): 5 mA.
Temperature Range: 32° F - 120° F (0° C - 49° C).
Relative Humidity Range: 10% - 93% non-condensing. NOTE: Closing the door automatically resets the switch to the ‘Normal’ position.
Opening the door will not activate or deactivate the alarm switch.
Installation CAUTION! Do not detach the door of the pull station during installation. The door of
The BG-12LX Addressable pull station can be surface mounted to an SB-10 or SB-I/O sur- the pull station cannot be reattached to the backplate after the backplate has already been
face backbox or semi-flush mounted on a standard single-gang, double-gang or 4″ (10.16 installed onto an electrical box.
cm) square electrical box. The optional BG-TR trim ring can be used if the BG-12LX is to
be semi-flush mounted. CAUTION!
Install the Fire•Lite BG-12LX addressable pull station in accordance with these instructions,
Operation applicable NFPA standards, national and local Fire and Electrical codes and the requirements
To activate the dual-action pull station, push in and pull down on the handle. The word of the AHJ (Authority Having Jurisdiction). Regular testing of the devices should be con-
‘ACTIVATED’ appears after the handle is pulled down. This will remain until the pull sta- ducted in accordance with the appropriate NFPA standards. Failure to follow these directions
tion is reset. may result in failure of the device to report an alarm condition. Fire•Lite is not responsible for
devices that have been improperly installed, tested or maintained.
The pull station includes one Single Pole, Single Throw (SPST) Normally Open (N/O)
switch which closes upon activation of the pull station. ADA Compliance
For ADA compliance, if the clear floor space only allows forward approach to an object, the
Resetting the Pull Station maximum forward reach height allowed is 48 inches (121.92 cm). If the clear floor space
1. Insert the key into the lock and rotate 1/4 turn counterclockwise. allows parallel approach by a person in a wheelchair, the maximum side reach allowed is
2. Open the door until the handle returns to normal. 54 inches (137.16 cm).
3. Close and lock the door.

(over for Programming information)


Setting the BG-12LX Address
The BG-12LX Addressable pull station is factory preset with address ‘00.’ Set the address for
the pull station by turning the rotary address switches on the addressable module mounted
inside the pull station. Only one device per address is allowed. Multiple modules may not
be set to the same address on the Signaling Line Circuit. Once the address is set, record it
in the space provided on the product ID label located inside the pull station.

LED OPERATION
Normal:
Flash RED
Alarm:
Steady RED

Note: LED is visible


through translucent
handle.

Note – Opening the


pull station door
will not activate or
deactivate the alarm
switch.

P0105-00
‫‪2020-11-03‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻟﻄﺒﺎﻋﺔ ‪:‬‬ ‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴــــﺔ‬
‫‪AM 9:32‬‬ ‫ﻭﻗـﺖ ﺍﻟﻄﺒﺎﻋﺔ ‪:‬‬ ‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺓ ﻟﻟﺩﻓﺎﻉ ﺍﻟﻣﺩﻧﻲ‬
‫‪PAC20011883‬‬ ‫ﺭﻗــﻢ ﺍﻟﻄﻠـﺐ ‪:‬‬ ‫ﺍﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺷﻬــــــﺎﺩﺓ ﻋﺪﻡ ﻣﻤﺎﻧﻌﺔ‬

‫‪ :‬ﺍﻋﺘﻤﺎﺩ ﻣﻨﺘﺞ‬ ‫ﻧﻮﻉ ﺍﻟﺸﻬﺎﺩﺓ‬

‫ﺑﻴﺎﻧﺎﺕ ﺍﻟﻤﻨﺸﺄﺓ‬

‫‪ :‬ﺍﺭﻣﻮﺭ ﻓﺎﻳﺮ ﻓﻠﻴﺘﻨﺞ ﺍﻧﺠﻨﻴﺮﻳﻨﺞ‬ ‫ﺍﻹﺳﻢ ﺍﻟﺘﺠﺎﺭﻱ‬


‫‪84548 :‬‬ ‫ﺭﻗﻢ ﺍﻟﺮﺧﺼﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ‬ ‫‪54310 :‬‬ ‫ﺭﻗﻢ ﺍﻟﺴﺠﻞ ﺍﻟﺘﺠﺎﺭﻱ‬
‫‪:‬‬ ‫ﺭﻗﻢ ﺍﻟﻬﺎﺗﻒ‬ ‫‪13-8288-00 :‬‬ ‫ﺭﻗﻢ ﻗﻴﺪ ﺍﻟﻤﻨﺸﺄﺓ‬
‫‪:‬‬ ‫ﺍﻟﺒﺮﻳﺪ ﺍﻹﻟﻜﺘﺮﻭﻧﻲ‬
‫‪Fire Detection and Alarm System :‬‬ ‫ﺍﻟﺘﺼﻨﻴﻒ‬
‫‪Initiating Devices and Accessories :‬‬ ‫ﺇﺳﻢ ﺍﻟﻤﻨﺘﺞ‬

‫ﺗﻔﺎﺻﻴﻞ ﺍﻟﺸﻬﺎﺩﺓ‬

‫ﺗﻢ ﻣﺮﺍﺟﻌﺔ ﺍﻟﻄﻠﺐ ﺍﻟﻤﻘﺪﻡ ﻭﺍﺗﻀﺢ ﺑﺄﻧﻪ ﻻ ﻣﺎﻧﻊ ﻣﻦ ﺍﻋﺘﻤﺎﺩ ﺍﻟﻤﻨﺘﺞ ‪/‬ﺍﻟﻤﻨﺘﺠﺎﺕ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻰ ﺍﻟﻤﺮﻓﻖ ﺑﻨﺎﺀ ﻋﻠﻰ ﺍﻋﺘﻤﺎﺩﻩ ﻣﻦ ﻗﺒﻞ ﺍﻟﻬﻴﺌﻪ‬
‫ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﺭ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ‪.‬‬

‫ﻣﻼﺣﻈﺎﺕ‬

‫‪ .1‬ﻳﺠﺐ ﻋﻠﻰ ﺍﻟﺸﺮﻛﻪ ﺍﻻﻟﺘﺰﺍﻡ ﻭﺍﻟﻌﻤﻞ ﺑﻤﺎ ﺟﺎﺀ ﻓﻲ ﺍﺷﺘﺮﺍﻃﺎﺕ ﻗﺴﻢ ﺃﻧﻈﻤﺔ ﺍﻟﺴﻼﻣﻪ ﺍﻟﺘﻲ ﺗﻢ ﺍﻻﻃﻼﻉ ﻭﺍﻟﻤﻮﺍﻓﻘﺔ ﻋﻠﻴﻬﺎ ﻣﻦ ﺧﻼﻝ ﺍﻟﻤﻮﻗﻊ‪.‬‬
‫‪ .2‬ﻳﺠﺐ ﺍﻥ ﻳﻘﻮﻡ ﺑﺘﺮﻛﻴﺐ ﻫﺬﺍ ﺍﻟﻤﻨﺘﺞ ﻣﻦ ﻗﺒﻞ ﻣﻬﻨﺪﺳﻴﻦ ﻭﻓﻨﻴﻴﻦ ﻣﻌﺘﻤﺪﻳﻦ ﻣﻦ ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‪.‬‬
‫‪ .3‬ﻳﺠﺐ ﺍﻥ ﻳﺤﻤﻞ ﺍﻟﻤﻨﺘﺞ ﺍﻟﻌﻼﻣﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ ﻟﻠﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻌﺘﻤﺪﺓ ﻭﺍﻟﻤﻮﺿﺤﻪ ﻓﻲ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ ‪.‬‬

‫‪2022-11-03‬‬ ‫‪:‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻹﻧﺘﻬﺎﺀ‬ ‫‪2020-11-03‬‬ ‫‪:‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻻﻋﺘﻤﺎﺩ‬

‫ﻉ‪/‬‬

‫ﻣﺪﻳﺮ ﺍﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺓ ﻟﻟﺩﻓﺎﻉ ﺍﻟﻣﺩﻧﻲ‬

‫‪Page 1 of 2‬‬
‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
DATE : 2020-11-03 : ‫ﺍﻟﺘﺎﺭﻳـــــــﺦ‬
‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬
PERMIT # PAC20011883 : ‫ﺭﻗﻢ ﺍﻟﻄﻠﺐ‬
‫ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

TECHNICAL REPORT ‫ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ‬


PRODUCT Initiating Devices and Accessories ‫ﻣﻨﺘﺞ‬
PRODUCT APPLICATION Fire Detection and Alarm System ‫ﺗﺼﻨﻴﻒ ﺍﻟﻤﻌﺪﺓ‬
APPLICANT / P.O BOX ‫ﺍﺭﻣﻮﺭ ﻓﺎﻳﺮ ﻓﻠﻴﺘﻨﺞ ﺍﻧﺠﻨﻴﺮﻳﻨﺞ‬ ‫ﻣﻘﺪﻡ ﺍﻟﻄﻠﺐ‬
MANUFACTURER / LOCATION FIRE-LITE ALARMS / USA ‫ ﺑﻠﺪ ﺍﻟﺼﻨﻊ‬/ ‫ﺍﻟﺸﺮﻛﺔ ﺍﻟﻤﺼﻨﻌﺔ‬
‫ﺍﻟﻮﺻﻒ‬ ‫ﺍﻟﻤﻮﺩﻳﻞ‬
Noncoded boxes, dual action, with LED status indicator, key reset, semi-flush mount, 24 VDC
BG-12LX
operating voltage range, 5 mA alarm current.
3RD PARTY CERTIFICATE /
Underwriters Laboratories ‫ﺷﻬﺎﺩﺓ ﺍﻟﻤﺨﺘﺒﺮﺍﺕ ﺍﻟﻤﺴﺎﻧﺪﺓ‬
APPROVAL UNIU.S711
(UL) ( ‫)ﻣﻦ ﻫﻴﺌﺎﺕ ﻣﻌﺘﻤﺪﺓ‬

RECOMMENDATIONS ‫ﺍﻟﺘﻮﺻﻴﺎﺕ‬
Boxes having electrical contacts actuated to change their normal position when a part is operated manually so as to
produce a non-coded signal.

INVESTIGATED TO STANDARD UL 38.

This product approval shall comply with the Design, Inspection, Installation, Testing and Maintenance requirements of
NFPA 38 (and/or other related NFPA Codes / Standards), other acceptable International Codes / Standards, Local
Regulations and/or Manufacturer's Published Instructions subject to the technical review and approval of the Authority
Having Jurisdiction (Qatar Civil Defence).

/‫ﻉ‬

‫ﻣﺪﻳﺮ ﺍﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺓ ﻟﻟﺩﻓﺎﻉ ﺍﻟﻣﺩﻧﻲ‬

Page 2 of 2
‫‪2020-11-03‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻟﻄﺒﺎﻋﺔ ‪:‬‬ ‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴــــﺔ‬
‫‪AM 9:32‬‬ ‫ﻭﻗـﺖ ﺍﻟﻄﺒﺎﻋﺔ ‪:‬‬ ‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺓ ﻟﻟﺩﻓﺎﻉ ﺍﻟﻣﺩﻧﻲ‬
‫‪PAC20011882‬‬ ‫ﺭﻗــﻢ ﺍﻟﻄﻠـﺐ ‪:‬‬ ‫ﺍﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺷﻬــــــﺎﺩﺓ ﻋﺪﻡ ﻣﻤﺎﻧﻌﺔ‬

‫‪ :‬ﺍﻋﺘﻤﺎﺩ ﻣﻨﺘﺞ‬ ‫ﻧﻮﻉ ﺍﻟﺸﻬﺎﺩﺓ‬

‫ﺑﻴﺎﻧﺎﺕ ﺍﻟﻤﻨﺸﺄﺓ‬

‫‪ :‬ﺍﺭﻣﻮﺭ ﻓﺎﻳﺮ ﻓﻠﻴﺘﻨﺞ ﺍﻧﺠﻨﻴﺮﻳﻨﺞ‬ ‫ﺍﻹﺳﻢ ﺍﻟﺘﺠﺎﺭﻱ‬


‫‪84548 :‬‬ ‫ﺭﻗﻢ ﺍﻟﺮﺧﺼﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ‬ ‫‪54310 :‬‬ ‫ﺭﻗﻢ ﺍﻟﺴﺠﻞ ﺍﻟﺘﺠﺎﺭﻱ‬
‫‪:‬‬ ‫ﺭﻗﻢ ﺍﻟﻬﺎﺗﻒ‬ ‫‪13-8288-00 :‬‬ ‫ﺭﻗﻢ ﻗﻴﺪ ﺍﻟﻤﻨﺸﺄﺓ‬
‫‪:‬‬ ‫ﺍﻟﺒﺮﻳﺪ ﺍﻹﻟﻜﺘﺮﻭﻧﻲ‬
‫‪Fire Detection and Alarm System :‬‬ ‫ﺍﻟﺘﺼﻨﻴﻒ‬
‫‪Initiating Devices and Accessories :‬‬ ‫ﺇﺳﻢ ﺍﻟﻤﻨﺘﺞ‬

‫ﺗﻔﺎﺻﻴﻞ ﺍﻟﺸﻬﺎﺩﺓ‬

‫ﺗﻢ ﻣﺮﺍﺟﻌﺔ ﺍﻟﻄﻠﺐ ﺍﻟﻤﻘﺪﻡ ﻭﺍﺗﻀﺢ ﺑﺄﻧﻪ ﻻ ﻣﺎﻧﻊ ﻣﻦ ﺍﻋﺘﻤﺎﺩ ﺍﻟﻤﻨﺘﺞ ‪/‬ﺍﻟﻤﻨﺘﺠﺎﺕ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻰ ﺍﻟﻤﺮﻓﻖ ﺑﻨﺎﺀ ﻋﻠﻰ ﺍﻋﺘﻤﺎﺩﻩ ﻣﻦ ﻗﺒﻞ ﺍﻟﻬﻴﺌﻪ‬
‫ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﺭ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ‪.‬‬

‫ﻣﻼﺣﻈﺎﺕ‬

‫‪ .1‬ﻳﺠﺐ ﻋﻠﻰ ﺍﻟﺸﺮﻛﻪ ﺍﻻﻟﺘﺰﺍﻡ ﻭﺍﻟﻌﻤﻞ ﺑﻤﺎ ﺟﺎﺀ ﻓﻲ ﺍﺷﺘﺮﺍﻃﺎﺕ ﻗﺴﻢ ﺃﻧﻈﻤﺔ ﺍﻟﺴﻼﻣﻪ ﺍﻟﺘﻲ ﺗﻢ ﺍﻻﻃﻼﻉ ﻭﺍﻟﻤﻮﺍﻓﻘﺔ ﻋﻠﻴﻬﺎ ﻣﻦ ﺧﻼﻝ ﺍﻟﻤﻮﻗﻊ‪.‬‬
‫‪ .2‬ﻳﺠﺐ ﺍﻥ ﻳﻘﻮﻡ ﺑﺘﺮﻛﻴﺐ ﻫﺬﺍ ﺍﻟﻤﻨﺘﺞ ﻣﻦ ﻗﺒﻞ ﻣﻬﻨﺪﺳﻴﻦ ﻭﻓﻨﻴﻴﻦ ﻣﻌﺘﻤﺪﻳﻦ ﻣﻦ ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‪.‬‬
‫‪ .3‬ﻳﺠﺐ ﺍﻥ ﻳﺤﻤﻞ ﺍﻟﻤﻨﺘﺞ ﺍﻟﻌﻼﻣﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ ﻟﻠﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻌﺘﻤﺪﺓ ﻭﺍﻟﻤﻮﺿﺤﻪ ﻓﻲ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ ‪.‬‬

‫‪2022-11-03‬‬ ‫‪:‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻹﻧﺘﻬﺎﺀ‬ ‫‪2020-11-03‬‬ ‫‪:‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻻﻋﺘﻤﺎﺩ‬

‫ﻉ‪/‬‬

‫ﻣﺪﻳﺮ ﺍﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺓ ﻟﻟﺩﻓﺎﻉ ﺍﻟﻣﺩﻧﻲ‬

‫‪Page 1 of 2‬‬
‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
DATE : 2020-11-03 : ‫ﺍﻟﺘﺎﺭﻳـــــــﺦ‬
‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬
PERMIT # PAC20011882 : ‫ﺭﻗﻢ ﺍﻟﻄﻠﺐ‬
‫ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

TECHNICAL REPORT ‫ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ‬


PRODUCT Initiating Devices and Accessories ‫ﻣﻨﺘﺞ‬
PRODUCT APPLICATION Fire Detection and Alarm System ‫ﺗﺼﻨﻴﻒ ﺍﻟﻤﻌﺪﺓ‬
APPLICANT / P.O BOX ‫ﺍﺭﻣﻮﺭ ﻓﺎﻳﺮ ﻓﻠﻴﺘﻨﺞ ﺍﻧﺠﻨﻴﺮﻳﻨﺞ‬ ‫ﻣﻘﺪﻡ ﺍﻟﻄﻠﺐ‬
MANUFACTURER / LOCATION FIRE-LITE ALARMS / USA ‫ ﺑﻠﺪ ﺍﻟﺼﻨﻊ‬/ ‫ﺍﻟﺸﺮﻛﺔ ﺍﻟﻤﺼﻨﻌﺔ‬
‫ﺍﻟﻮﺻﻒ‬ ‫ﺍﻟﻤﻮﺩﻳﻞ‬
Smoke Detectors for Fire Alarm Systems, open area protection, duct detector, installation inside
duct, photoelectric, 0 to 4000 FPM velocity range, with LED status indicator, 15 to 32 VDC SD355
operating voltage range.
3RD PARTY CERTIFICATE /
Underwriters Laboratories ‫ﺷﻬﺎﺩﺓ ﺍﻟﻤﺨﺘﺒﺮﺍﺕ ﺍﻟﻤﺴﺎﻧﺪﺓ‬
APPROVAL UROX.S1059
(UL) ( ‫)ﻣﻦ ﻫﻴﺌﺎﺕ ﻣﻌﺘﻤﺪﺓ‬

RECOMMENDATIONS ‫ﺍﻟﺘﻮﺻﻴﺎﺕ‬
INVESTIGATED TO STANDARD UL 268A.

This product approval shall comply with the Design, Inspection, Installation, Testing and Maintenance requirements of
NFPA 72 (and/or other related NFPA Codes / Standards), other acceptable International Codes / Standards, Local
Regulations and/or Manufacturer's Published Instructions subject to the technical review and approval of the Authority
Having Jurisdiction (Qatar Civil Defence).

/‫ﻉ‬

‫ﻣﺪﻳﺮ ﺍﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺓ ﻟﻟﺩﻓﺎﻉ ﺍﻟﻣﺩﻧﻲ‬

Page 2 of 2
INSTALLATION AND MAINTENANCE INSTRUCTIONS

I56-3660-002R
SD355, SD355T and AD355 One FireLite Place
Northford, CT 06472
Addressable Photoelectric Smoke Sensors Phone: 203.484.7161

SPECIFICATIONS
Operating Voltage Range: 15 to 32 VDC
Standby Current: 300µA @ 24 VDC (one communication every 5 seconds with LED blink enabled)
Maximum Alarm Current (LED on): 6.5 mA @ 24 VDC
Operating Humidity Range: 10% to 93% Relative Humidity, Non-condensing
Operating Temperature Range: 32°F to 120°F (0°C to 49°C); SD355
Operating Temperature Range: 32°F to 100°F (0°C to 38°C); SD355T and AD355
Height: 2.0˝ (51 mm) installed in B350LP Base
Diameter: 6.2˝ (155 mm) installed in B350LP Base
Weight: 5.2 oz. (147 g)

This sensor must be installed in compliance with the control panel system Figure 1. Wiring Diagram:
installation manual. The installation must meet the requirements of the Au- REMOTE ANNUNCIATOR CAUTION: DO NOT LOOP WIRE
UNDER TERMINAL 1 OR 2.
thority Having Jurisdiction (AHJ). Sensors offer maximum performance when + – BREAK WIRE RUN TO PROVIDE
installed in compliance with the National Fire Protection Association (NFPA); SUPERVISION OF CONNECTIONS.
see NFPA 72. +

UL LISTED COMPATIBLE
CONTROL PANEL
GENERAL DESCRIPTION
Model SD355, SD355T and AD355 are addressable sensors that combine a
3 2 3 2
state-of-the-art photoelectronic sensing chamber with communications. The
sensors transmit an analog representation of smoke density over a communi- 1 1
cation line to a control panel. Rotary decade switches are provided for setting
the sensor’s address.
Two LEDs on the sensor are controlled by the panel to indicate sensor status. –
An output is provided for connection to an optional remote LED annunciator
(P/N RA400Z). Models AD355 and SD355T combine a photoelectronic sens- – OPTIONAL RETURN LOOP
+
ing chamber and 135°F (57.2°C) fixed temperature heat detector.
SPACING C0100-01
Fire-Lite recommends spacing sensors in compliance with NFPA 72. In low
Figure 2. Rotary Address Switches:
air flow applications with smooth ceilings, space sensors 30 feet apart. For
specific information regarding sensor spacing, placement, and special appli- 6 7 89 6 7 8 9
cations, refer to NFPA 72 or the System Smoke Detector Application Guide 5 10 5
available from Fire-Lite. 4 11 4
3 12 3
WIRING INSTRUCTIONS 13
2 2
All wiring must be installed in compliance with the National Electrical Code, 1 0 1514 10
applicable local codes, and any special requirements of the Authority Having
TENS ONES
Jurisdiction. Proper wire gauges should be used. The installation wires should
be color-coded to limit wiring mistakes and ease system troubleshooting. Im- C0162-00
proper connections will prevent a system from responding properly in the TAMPER-RESISTANCE
event of a fire. Models SD355, SD355T and AD355 include a tamper-resistant capability that
Remove power from the communication line before installing sensors. prevents its removal from the bracket without the use of a tool. Refer to the
base manual for details on making use of this capability.
1. Wire the sensor base (supplied separately) per the wiring diagram, see
Figure 1. TESTING
Before testing, notify the proper authorities that the system is undergoing
2. Set the desired address on the sensor address switches, see Figure 2.
maintenance, and will temporarily be out of service. Disable the system to
3. Install the sensor into the sensor base. Push the sensor into the base prevent unwanted alarms.
while turning it clockwise to secure it in place.
All sensors must be tested after installation and periodically thereafter. Test-
4. After all sensors have been installed, apply power to the control unit and
ing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors
activate the communication line.
offer maximum performance when tested and maintained in compliance with
5. Test the sensor(s) as described in the TESTING section of this manual. NFPA 72. The sensor can be tested in the following ways:
CAUTION A. Functional: Magnet Test (P/N M02-04-01 or M02-09-00)
Dust covers provide limited protection against airborne dust particles during This sensor can be functionally tested with a test magnet. The test mag-
shipping. Dust covers must be removed before the sensors can sense smoke. net electronically simulates smoke in the sensing chamber, testing the
Remove sensors prior to heavy remodeling or construction. sensor electronics and connections to the control panel.
1. Hold the test magnet in the magnet test area as shown.
2. The sensor should alarm the panel.
Two LEDs on the sensor are controlled by the panel to indicate sensor
status. Coded signals, transmitted from the panel, can cause the LEDs
to blink, latch on, or latch off. Refer to the control panel technical docu-
mentation for sensor LED operation and expected delay to alarm.
FL-400-002 1 I56-3660-002R
B. Smoke Entry: Aerosol Generator (Gemini 501) CLEANING
The GEMINI model 501 aerosol generator can be used for smoke entry Before removing the detector, notify the proper authorities that the smoke
testing. Set the generator to represent 4%/ft to 5%/ft obscuration as de- detector system is undergoing maintenance and will be temporarily out of
scribed in the GEMINI 501 manual. Using the bowl shaped applicator, service. Disable the zone or system undergoing maintenance to prevent un-
apply aerosol until the panel alarms. Additionally, canned aerosol simu- wanted alarms.
lated smoke (canned smoke agent) may be used for smoke entry testing 1. Remove the sensor to be cleaned from the system.
of the smoke detector. Tested and approved aerosol smoke products are 2. Remove the sensor cover by pressing firmly on each of the four removal
the Smoke Detector Tester model 25S available from Home Safeguard In- tabs that hold the cover in place.
dustries and Chekkit Smoke Detector Tester models CHEK02 and CHEK06
3. Vacuum the screen carefully without removing it. If further cleaning is
available from SDi. When used properly, the canned smoke agent will
required continue with Step 4, otherwise skip to Step 7.
cause the smoke detector to go into alarm. Refer to the manufacturer’s
published instructions for proper use of the canned smoke agent. 4. Remove the chamber cover/screen assembly by pulling it straight out.
5. Use a vacuum cleaner or compressed air to remove dust and debris from
CAUTION
the sensing chamber.
Canned aerosol simulated smoke (canned smoke agent) formulas will vary by 6. Reinstall the chamber cover/screen assembly by sliding the edge over the
manufacturer. Misuse or overuse of these products may have long term adverse sensing chamber. Turn until it is firmly in place.
effects on the smoke detector. Consult the canned smoke agent manufacturer’s
7. Replace the cover using the LEDs to align the cover and then gently
published instructions for any further warnings or caution statements.
pushing it until it locks into place. Make sure that the thermistors do not
become bent under the cover on SD355T and AD355 models.
For AD355, smoke entry testing should be performed immediately fol-
lowing the magnet test. Magnet test initiates an approximately 10 minute 8. Reinstall the detector.
period when the detector’s signal processing software routines are not 9. Test the detector as described in TESTING.
active. Failure to first perform the magnet test will introduce a time delay 10. Reconnect disabled circuits.
before the detector alarms. 11. Notify the proper authorities that the system is back on line.
C. Direct Heat Method (Hair dryer of 1000-1500 watts). SD355T and SPECIAL NOTE REGARDING SMOKE DETECTOR GUARDS
AD355 only. Smoke detectors are not to be used with detector guards unless the combina-
A hair dryer of 1000-1500 watts should be used to test the thermistors. tion has been evaluated and found suitable for that purpose.
Direct the heat toward either of the two thermistors, holding the heat
source approximately 12 inches from the detector in order to avoid dam- Figure 4:
aging the plastic housing. The detector will reset only after it has suf-
SENSOR
ficient time to cool. Make sure both thermistors are tested individually. COVER
A sensor that fails any of these tests should be cleaned as described under
CLEANING, and retested. If the sensor fails after cleaning, it must be replaced
and returned for repair.
When testing is complete, restore the system to normal operation and notify
the proper authorities that the system is back in operation.
Figure 3:
MAGNET TEST TEST MAGNET
MARKER POSITION
SENSING
CHAMBER
COVER COVER AND
REMOVAL SCREEN
TABS

OPTIONAL THERMISTORS
(SD355T AND AD355)
LED STATUS
INDICATORS SENSING
CHAMBER
TEST MAGNET
POSITION
MAGNET TEST
MARKER

C0145-00 C0222-00

Please refer to insert for the Limitations of Fire Alarm Systems


FCC Statement
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used
in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installa-
tion. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try
to correct the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
FL-400-002 2 I56-3660-002R
©2008 Fire-Lite
‫‪2020-11-03‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻟﻄﺒﺎﻋﺔ ‪:‬‬ ‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴــــﺔ‬
‫‪AM 9:34‬‬ ‫ﻭﻗـﺖ ﺍﻟﻄﺒﺎﻋﺔ ‪:‬‬ ‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺓ ﻟﻟﺩﻓﺎﻉ ﺍﻟﻣﺩﻧﻲ‬
‫‪PAC20011884‬‬ ‫ﺭﻗــﻢ ﺍﻟﻄﻠـﺐ ‪:‬‬ ‫ﺍﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺷﻬــــــﺎﺩﺓ ﻋﺪﻡ ﻣﻤﺎﻧﻌﺔ‬

‫‪ :‬ﺍﻋﺘﻤﺎﺩ ﻣﻨﺘﺞ‬ ‫ﻧﻮﻉ ﺍﻟﺸﻬﺎﺩﺓ‬

‫ﺑﻴﺎﻧﺎﺕ ﺍﻟﻤﻨﺸﺄﺓ‬

‫‪ :‬ﺍﺭﻣﻮﺭ ﻓﺎﻳﺮ ﻓﻠﻴﺘﻨﺞ ﺍﻧﺠﻨﻴﺮﻳﻨﺞ‬ ‫ﺍﻹﺳﻢ ﺍﻟﺘﺠﺎﺭﻱ‬


‫‪84548 :‬‬ ‫ﺭﻗﻢ ﺍﻟﺮﺧﺼﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ‬ ‫‪54310 :‬‬ ‫ﺭﻗﻢ ﺍﻟﺴﺠﻞ ﺍﻟﺘﺠﺎﺭﻱ‬
‫‪:‬‬ ‫ﺭﻗﻢ ﺍﻟﻬﺎﺗﻒ‬ ‫‪13-8288-00 :‬‬ ‫ﺭﻗﻢ ﻗﻴﺪ ﺍﻟﻤﻨﺸﺄﺓ‬
‫‪:‬‬ ‫ﺍﻟﺒﺮﻳﺪ ﺍﻹﻟﻜﺘﺮﻭﻧﻲ‬
‫‪Fire Detection and Alarm System :‬‬ ‫ﺍﻟﺘﺼﻨﻴﻒ‬
‫‪Notification Devices and Accessories :‬‬ ‫ﺇﺳﻢ ﺍﻟﻤﻨﺘﺞ‬

‫ﺗﻔﺎﺻﻴﻞ ﺍﻟﺸﻬﺎﺩﺓ‬

‫ﺗﻢ ﻣﺮﺍﺟﻌﺔ ﺍﻟﻄﻠﺐ ﺍﻟﻤﻘﺪﻡ ﻭﺍﺗﻀﺢ ﺑﺄﻧﻪ ﻻ ﻣﺎﻧﻊ ﻣﻦ ﺍﻋﺘﻤﺎﺩ ﺍﻟﻤﻨﺘﺞ ‪/‬ﺍﻟﻤﻨﺘﺠﺎﺕ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻰ ﺍﻟﻤﺮﻓﻖ ﺑﻨﺎﺀ ﻋﻠﻰ ﺍﻋﺘﻤﺎﺩﻩ ﻣﻦ ﻗﺒﻞ ﺍﻟﻬﻴﺌﻪ‬
‫ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﺭ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ‪.‬‬

‫ﻣﻼﺣﻈﺎﺕ‬

‫‪ .1‬ﻳﺠﺐ ﻋﻠﻰ ﺍﻟﺸﺮﻛﻪ ﺍﻻﻟﺘﺰﺍﻡ ﻭﺍﻟﻌﻤﻞ ﺑﻤﺎ ﺟﺎﺀ ﻓﻲ ﺍﺷﺘﺮﺍﻃﺎﺕ ﻗﺴﻢ ﺃﻧﻈﻤﺔ ﺍﻟﺴﻼﻣﻪ ﺍﻟﺘﻲ ﺗﻢ ﺍﻻﻃﻼﻉ ﻭﺍﻟﻤﻮﺍﻓﻘﺔ ﻋﻠﻴﻬﺎ ﻣﻦ ﺧﻼﻝ ﺍﻟﻤﻮﻗﻊ‪.‬‬
‫‪ .2‬ﻳﺠﺐ ﺍﻥ ﻳﻘﻮﻡ ﺑﺘﺮﻛﻴﺐ ﻫﺬﺍ ﺍﻟﻤﻨﺘﺞ ﻣﻦ ﻗﺒﻞ ﻣﻬﻨﺪﺳﻴﻦ ﻭﻓﻨﻴﻴﻦ ﻣﻌﺘﻤﺪﻳﻦ ﻣﻦ ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‪.‬‬
‫‪ .3‬ﻳﺠﺐ ﺍﻥ ﻳﺤﻤﻞ ﺍﻟﻤﻨﺘﺞ ﺍﻟﻌﻼﻣﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ ﻟﻠﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻌﺘﻤﺪﺓ ﻭﺍﻟﻤﻮﺿﺤﻪ ﻓﻲ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ ‪.‬‬

‫‪2022-11-03‬‬ ‫‪:‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻹﻧﺘﻬﺎﺀ‬ ‫‪2020-11-03‬‬ ‫‪:‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻻﻋﺘﻤﺎﺩ‬

‫ﻉ‪/‬‬

‫ﻣﺪﻳﺮ ﺍﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺓ ﻟﻟﺩﻓﺎﻉ ﺍﻟﻣﺩﻧﻲ‬

‫‪Page 1 of 2‬‬
‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
DATE : 2020-11-03 : ‫ﺍﻟﺘﺎﺭﻳـــــــﺦ‬
‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬
PERMIT # PAC20011884 : ‫ﺭﻗﻢ ﺍﻟﻄﻠﺐ‬
‫ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

TECHNICAL REPORT ‫ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ‬


PRODUCT Notification Devices and Accessories ‫ﻣﻨﺘﺞ‬
PRODUCT APPLICATION Fire Detection and Alarm System ‫ﺗﺼﻨﻴﻒ ﺍﻟﻤﻌﺪﺓ‬
APPLICANT / P.O BOX ‫ﺍﺭﻣﻮﺭ ﻓﺎﻳﺮ ﻓﻠﻴﺘﻨﺞ ﺍﻧﺠﻨﻴﺮﻳﻨﺞ‬ ‫ﻣﻘﺪﻡ ﺍﻟﻄﻠﺐ‬
SYSTEM SENSOR UNINCORPORATED, DIV OF
MANUFACTURER / LOCATION ‫ ﺑﻠﺪ ﺍﻟﺼﻨﻊ‬/ ‫ﺍﻟﺸﺮﻛﺔ ﺍﻟﻤﺼﻨﻌﺔ‬
HONEYWELL INTERNATIONAL INC / USA
‫ﺍﻟﻮﺻﻒ‬ ‫ﺍﻟﻤﻮﺩﻳﻞ‬

Audible-signal appliance, Horn Strobes. P2RL

Audible-signal appliance, Horn, Intended for indoor use mounted on the wall or ceiling. HR

3RD PARTY CERTIFICATE /


Underwriters Laboratories ‫ﺷﻬﺎﺩﺓ ﺍﻟﻤﺨﺘﺒﺮﺍﺕ ﺍﻟﻤﺴﺎﻧﺪﺓ‬
APPROVAL ULSZ.S4011
(UL) ( ‫)ﻣﻦ ﻫﻴﺌﺎﺕ ﻣﻌﺘﻤﺪﺓ‬

RECOMMENDATIONS ‫ﺍﻟﺘﻮﺻﻴﺎﺕ‬

NOTES / STANDARDS

The strobes functionality is not included within the scope of this approval.

Investigated to standard ANSI/UL 464

This product approval shall comply with the NFPA 72 (and/or other related NFPA Codes / Standards), other acceptable
International Codes / Standards, Local Regulations, Listing Instructions and/or Manufacturer's Published Instructions
subject to the technical review and approval of the Authority Having Jurisdiction / Qatar Civil Defence.

/‫ﻉ‬

‫ﻣﺪﻳﺮ ﺍﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺓ ﻟﻟﺩﻓﺎﻉ ﺍﻟﻣﺩﻧﻲ‬

Page 2 of 2
Indoor Selectable-
Output Horns,
Strobes, and
Horn Strobes for
Wall Applications
System Sensor L-Series audible visible notification
products are rich with features guaranteed to cut
installation times and maximize profits with lower
current draw and modern aesthetics.

Features
• Updated Modern Aesthetics The System Sensor L-Series offers the most versatile and
• Small profile devices for Horns and Horn Strobes easy-to-use line of horns, strobes, and horn strobes in the industry
with lower current draws and modern aesthetics. With white and red
• Plug-in design with minimal intrusion into the back box
plastic housings, standard and compact devices, and plain, FIRE,
• Tamper-resistant construction
and FUEGO-printed devices, System Sensor L-Series can
• A
 utomatic selection of 12- or 24-volt operation at 15 and 30 meet virtually any application requirement.
candela
• F
 ield-selectable candela settings on wall units: The L-Series line of wall-mount horns, strobes, and horn strobes
15, 30, 75, 95, 110, 135, and 185 include a variety of features that increase their application versatility
• Horn rated at 88+ dBA at 16 volts while simplifying installation. All devices feature plug-in designs
with minimal intrusion into the back box, making installations fast
• Rotary switch for horn tone and two volume selections
and foolproof while virtually eliminating costly and time-consuming
• Mounting plate for all standard and all compact wall units ground faults.
• M
 ounting plate shorting spring checks wiring continuity before
device installation To further simplify installation and protect devices from construction
• Electrically compatible with legacy SpectrAlert and SpectrAlert damage, the L-Series utilizes a universal mounting plate for all
Advance devices models with an onboard shorting spring, so installers can test wiring
• Compatible with MDL3 sync module continuity before the device is installed.

• Strobes and Horn Strobes listed for wall mounting only


Installers can also easily adapt devices to a suit a wide range
• Horns listed for wall or ceiling use of application requirements using field-selectable candela settings,
automatic selection of 12- or 24-volt operation, and a rotary switch
for horn tones with two volume selections.
Agency Listings

S5512 FM approved except 7125-1653:0504


S4011 for ALERT models 7135-1653:0503
3057383, 3057072

AVDS865-05 • 2/22/2018 • Page 1


L-Series Specifications
Architect/Engineer Specifications
General
L-Series standard horns, strobes, and horn strobes shall mount to a standard 2 x 4 x 17/8-inch back box, 4 × 4 × 1½-inch back box, 4-inch
octagon back box, or double-gang back box. L-Series compact products shall mount to a single-gang 2 × 4 × 17 ⁄8 -inch back box. A universal
mounting plate shall be used for mounting ceiling and wall products for all standard models and a separate universal mounting plate shall be
used for mounting wall compact models. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series
products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output
and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs
shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor
L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply.
Strobes and horn strobes shall have field-selectable candela settings including 15, 30, 75, 95, 110, 135, and 185.

Strobe
The strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe
shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible
signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and
associated lens/reflector system.

Horn Strobe Combination


The horn strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective
service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act
requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist
of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a
temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe
models shall operate on a coded or non-coded power supply.

Synchronization Module
The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The
module shall synchronize Strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns
on horn strobe models over a single pair of wires. The module shall mount to a 411/16 × 411/16 × 21/8-inch back box. The module shall also
control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more
synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.

Physical/Electrical Specifications
Standard Operating Temperature 32°F to 120°F (0°C to 49°C)
Humidity Range 10 to 93% non-condensing
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 DC or regulated 24 DC/FWR1
Operating Voltage Range 2
8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal)
Input Terminal Wire Gauge 12 to 18 AWG
Wall-Mount Dimensions (including lens) 5.6˝ L × 4.7˝ W × 1.91˝ D (143 mm L × 119 mm W × 49 mm D)
Compact Wall-Mount Dimensions (including lens) 5.26” L x 3.46” W x 1.91” D (133 mm L x 88 mm W x 49 mm D)
Horn Dimensions 5.6˝ L × 4.7˝ W × 1.25˝ D (143 mm L × 119 mm W × 32 mm D)
Compact Horn Dimensions 5.25” L x 3.45” W x 1.25” D (133 mm L x 88 mm W x 32 mm D)
1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs.
2. Strobe products will operate at 12 V nominal only for 15 cd and 30 cd.

AVDS865-05 • 2/22/2018 • Page 2


UL Current Draw Data
UL Max. Strobe Current Draw (mA RMS) UL Max. Horn Current Draw (mA RMS)
8–17.5 Volts 16–33 Volts 8–17.5 Volts 16–33 Volts
Candela DC DC FWR Sound Pattern dB DC DC FWR
Candela 15 88 43 60 Temporal High 39 44 54
Range 30 143 63 83 Temporal Low 28 32 54
75 N/A 107 136 Non-Temporal High 43 47 54
95 N/A 121 155 Non-Temporal Low 29 32 54
110 N/A 148 179 3.1 KHz Temporal High 39 41 54
135 N/A 172 209 3.1 KHz Temporal Low 29 32 54
185 N/A 222 257 3.1 KHz Non-Temporal High 42 43 54
3.1 KHz Non-Temporal Low 28 29 54
Coded High 43 47 54
3.1 KHz Coded High 42 43 54

UL Max. Current Draw (mA RMS), Wall Horn Strobe, Candela Range (15–185 cd)
8–17.5 Volts 16–33 Volts
DC Input 15cd 30cd 15cd 30cd 75cd 95cd 110cd 135cd 185cd
Temporal High 98 158 54 74 121 142 162 196 245
Temporal Low 93 154 44 65 111 133 157 184 235
Non-Temporal High 106 166 73 94 139 160 182 211 262
Non-Temportal Low 93 156 51 71 119 139 162 190 239
3.1K Temporal High 93 156 53 73 119 140 164 190 242
3.1K Temporal Low 91 154 45 66 112 133 160 185 235
3.1K Non-Temporal High 99 162 69 90 135 157 175 208 261
3.1K Non-Temporal Low 93 156 52 72 119 138 162 192 242
16–33 Volts
FWR Input 15cd 30cd 75cd 95cd 110cd 135cd 185cd
Temporal High 83 107 156 177 198 234 287
Temporal Low 68 91 145 165 185 223 271
Non-Temporal High 111 135 185 207 230 264 316
Non-Temportal Low 79 104 157 175 197 235 283
3.1K Temporal High 81 105 155 177 196 234 284
3.1K Temporal Low 68 90 145 166 186 222 276
3.1K Non-Temporal High 104 131 177 204 230 264 326
3.1K Non-Temporal Low 77 102 156 177 199 234 291

Horn Tones and Sound Output Data


Horn and Horn Strobe Output (dBA)
8–17.5 16–33
Switch Volts Volts
Position Sound Pattern dB DC DC FWR
1 Temporal High 84 89 89
2 Temporal Low 75 83 83
3 Non-Temporal High 85 90 90
4 Non-Temporal Low 76 84 84
5 3.1 KHz Temporal High 83 88 88
6 3.1 KHz Temporal Low 76 82 82
7 3.1 KHz Non-Temporal High 84 89 89
8 3.1 KHz Non-Temporal Low 77 83 83
9* Coded High 85 90 90
10* 3.1 KHz Coded High 84 89 89
* Settings 9 and 10 are not available on 2-wire horn strobes. Temporal coding must
be provided by the NAC. If the NAC voltage is held constant, the horn output remains
constantly on.

AVDS865-05 • 2/22/2018 • Page 3


L-Series Dimensions

1.91" 3.46"
3.46" 48.5 mm 88 mm 1.25" 3.57" 1.55"
88 mm 1.25" 32 mm (9.1 cm) (3.9 cm)
32 mm

5.27" 5.38"
133.9 mm 5.27" (13.7 cm)
133.9 mm

A0548-00 A0547-00 A0557-00

Compact Strobe, Horn Strobe Compact Horn Compact Wall Surface Mount Back Box
SBBGRL, SBBGWL

4.70"
(11.94 cm) 1.91"
4.7" 1.25"
(4.85 cm) 4.82"
119 mm 32 mm 1.85"
(12.24 cm)
1.25" (4.69 cm)
(3.18 mm)

5.78"
5.67" 5.67"
(14.68 cm)
(14.4 cm) 144 mm

A0554-01
A0550-00 A0549-00
Strobe, Horn Strobe Horn Wall Surface Mount Back Box
SBBRL/SBBWL

L-Series Ordering Information addressable system


Model Description Model Description
Wall Horn Strobes Horns*
P2RL 2-Wire, Horn Strobe, Red HRL* Horn, Red
P2WL 2-Wire, Horn Strobe, White HWL* Horn, White
P2GRL 2-Wire, Compact Horn Strobe, Red HGRL* Compact Horn, Red
P2GWL 2-Wire, Comp 2 fils act Horn Strobe, White HGWL* Compact Horn, White
P2RL-P 2-Wire, Horn Strobe, Red, Plain Accessories
P2WL-P 2-Wire, Horn Strobe, White, Plain TR-2 Universal Wall Trim Ring Red
P2RL-SP 2-Wire, Horn Strobe, Red, FUEGO TR-2W Universal Wall Trim Ring White
P2WL-SP 2-Wire, Horn Strobe, White, FUEGO SBBRL Wall Surface Mount Back Box, Red
P4RL 4-Wire, Horn Strobe, Red SBBWL Wall Surface Mount Back Box, White
P4WL 4-Wire, Horn Strobe, White SBBGRL Compact Wall Surface Mount Back Box, Red
Wall Strobes SBBGWL Compact Wall Surface Mount Back Box, White
SRL Strobe, Red
SWL Strobe, White
SGRL Compact Strobe, Red
SGWL Compact Strobe, White
SRL-P Strobe, Red, Plain
SWL-P Strobe, White, Plain
SRL-SP Strobe, Red, FUEGO
SWL-CLR-ALERT Strobe, White, ALERT Notes:
All -P models have a plain housing (no “FIRE” marking on cover).
All -SP models have “FUEGO” marking on cover.
All -ALERT models have “ALERT” marking on cover.
*Horn-only models are listed for wall or ceiling use.

3825 Ohio Avenue • St. Charles, IL 60174 ©2018 System Sensor.


Phone: 800-SENSOR2 • Fax: 630-377-6495 Product specifications subject to change without notice. Visit systemsensor.com
for current product information, including the latest version of this data sheet.
www.systemsensor.com AVDS865-05 • 2/22/2018
7 December 2020 BLUE POWER HOUSE ELECTRICAL

 HVAC AND FIRE FIGHTING SUBMITTALS

 PENDANT SPRINKLER

 STEEL PIPES

 BUTTERFLY VALVE WITH SUPERVISORY SWITCH

 G.I SPIRAL DUCT

 PICV

 BIS FITTINGS

 FIRE HOSE REEL


x

1. Installation shall be done as per NFPA 13 and QCDD requirements.


2. Submittal for upright sprinklers shall be provided.

Fadi Kaakour 20/10/2020


x

1. Proposed GI piping made by Al Jazeera is acceptable to use for fire fighting application.
2. Installation shall be done as NFPA and QCDD requirements.
3. Contractor to provide updated QCDD certificate upon material delivery.

Fadi Kaakour 20/10/2020


x

1. Installation shall be done as recommended by NFPA and QCDD.


2. Valve shall be easily accessible.

Fadi Kaakour 27.10.2020


x

1. Third party certificate relevant to QCDD certificate shall be provided.


2. QCDD certificate is expired, contractor/supplier to amen.
3. Authorization letter for the supplier by the manufacturer shall be provided.
4. Country of origin certificate shal be provided, the same shall be mentioned on the transmittal
cover.

Fadi Kaakour 24.10.2020


OSYSU-1, -2
OUTSIDE SCREW AND YOKE VALVE
SUPERVISORY SWITCH
UL, ULC, and CSFM Listed, FM Approved, NYMEA Accepted,
CE Marked
Dimensions: 6.19"L X 2.25"W X 5.88"H
15,7cm L X 5,7cm W X 14,6cm H
Weight: 2 lbs. (0,9 kg.)
Enclosure: Cover - Die-Cast
Finish - Red Spatter Enamel
Base - Die Cast Zinc
  All parts have corrosion resistant fi nishes.
Cover Tamper: Tamper resistant screws,
Optional cover tamper kit available.
Contact Ratings:
OSYSU-1: One set of SPDT (Form C)
OSYSU-2: Two sets of SPDT (Form C)
15.00 Amps at 125/250VAC
2.50 Amps at 30VDC resistive
Environmental Limitations:
•  NEMA 4 and NEMA 6P Enclosure (IP67) when used with
appropriate watertight conduit fi ttings.
•  Indoor or Outdoor use (Not for use in hazardous    
locations. See bulletin no. 5400705 OSYS-U-EX
for hazardous locations.)
•  Temperature Range: ­40°F to 140°F (­40°C to 60°C)
Conduit Entrances:
2 knockouts for 1/2" conduit provided
Service Use:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72

General Information Ordering Information


The OSYSU is used to monitor the open position of an OS&Y (outside Model Description Stock No.
screw and yoke) type gate valve. This device is available in two models; 
OSYSU-1 Outside Screw & Yoke-Supervisory Switch 1010106
the OSYSU-1, containing one set of SPDT (Form C) contacts and the
OSYSU-2, containing two sets of SPDT (Form C) contacts. These (Single switch)
switches mount conveniently to most OS&Y valves ranging in size from OSYSU-2 Outside Screw & Yoke-Supervisory Switch 1010206
2" to 12" (50mm to 300mm). They will mount on some valves as small (Double switch)
as ½" (12,5mm). -- Cover Screw 5490424
The cover is held in place by two tamper resistant screws that require a -- Hex Key for Cover Screws and Installation 5250062
special tool to remove. The tool is furnished with each device and should be Adjustments
left with the building owner or responsible party. Replacement or additional -- Optional Cover Tamper Switch Kit 0090131
cover screws and hex keys are available. See Ordering Information.
For pressure reducer type valve installation kits (if required)
Optional Cover Tamper Switch contact valve manufacturer.
A fi eld installable cover tamper switch is available as an option which may 
be used to indicate removal of the cover. See Ordering Information.
Testing
The OSYSU and its associated protective monitoring system should
be inspected and tested in accordance with applicable NFPA codes
and standards and/or the authority having jurisdiction (manufacturer
recommends quarterly or more frequently).

Potter Electric Signal Company, LLC • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com

PRINTED IN USA MKT. #8820004 - REV R PAGE 1 OF 3


MFG# 5400979 - 2/08
OSYSU-1, -2
OUTSIDE SCREW AND YOKE VALVE
SUPERVISORY SWITCH
Fig. 1 Small Valve Installation ½" thru 2½" Fig. 2 Large Valve Installation 3" thru 12"
(12,5mm thru 63,5mm) Sizes (76mm thru 300mm) Sizes

These switches mount conveniently to most 2" to 12" OS&Y valves.


They will mount on some valves as small as ½" (12,5mm). J-hooks
may be required on valves with limited clearance.

Small Valve Installation Large Valve Installation


1. Remove and discard "C" washer and roller from the trip rod. 1. With the valve in the FULL OPEN position, locate the OSYSU
2. With the valve in the FULL OPEN position, locate the OSYSU across the valve yoke as far as possible from the valve gland, so that
across the valve yoke as far as possible from the valve gland, so that the trip rod lays against the non-threaded portion of the valve stem.
the trip rod lays against the non-threaded portion of the valve stem. 2. Mount the OSYSU loosely with the carriage bolts and clamp bar supplied.
3. Loosen the locking screw that holds the trip rod in place and 3. Loosen the locking screw that holds the trip rod in place and
adjust the rod length (see Fig. 4). When adjusted properly, the adjust the rod length (see Fig. 4). When adjusted properly, the
rod should extend past the valve screw, but not so far that it rod should extend past the valve screw, but not so far that it
contacts the clamp bar. Tighten the locking screw to hold the trip contacts the clamp bar. Tighten the locking screw to hold the trip
rod in place. rod in place.
Note: If trip rod length is excessive, loosen the locking screw Note: If trip rod length is excessive, loosen the locking screw
and remove the trip rod from the trip lever. Using pliers, break and remove the trip rod from the trip lever. Using pliers, break
off the 1" (25mm) long notched section (see Fig. 5). Reinstall off the one 1" (25mm) long notched section (see Fig. 5). Reinstall
trip rod and repeat Step 3 procedure. trip rod and repeat Step 3 procedure.
4. Mount the OSYSU loosely with the carriage bolts and clamp bar 4. Mark the valve stem at the center of the trip rod.
supplied. On valves with limited clearance use J-hooks supplied 5. Remove the OSYSU. File a 1/8" (3,2mm) deep groove centered
instead of the carriage bolts and clamp bar to mount the OSYSU. on the mark of the valve stem utilizing a 3/8" (9,5mm) round,
5. Mark the valve stem at the center of the trip rod. non­tapered fi le.  Round and smooth the edges of the groove to 
6. Remove the OSYSU. File a 1/8" (3,2mm) deep groove centered prevent damage to the valve packing and to allow the trip rod to
on the mark on the valve stem utilizing a 3/16" (4,8mm) round, move easily in and out of the groove as the valve is operated.
non­tapered fi le.  Round and smooth the edges of the groove to  6. Mount the OSYSU loosely with the trip rod centered in groove.
prevent damage to the valve packing and to allow the trip rod to 7. Final adjustment is made by loosening 2 screws (see Fig. 2) and
move easily in and out of the groove as the valve is operated. sliding the OSYSU on the bracket. Adjustment is correct when
7. Mount the OSYSU with the trip rod centered in groove. switches are not activated with the trip rod seated in the valve
8. Final adjustment is made by loosening 2 screws (see Fig. 1) and stem groove and that the switches activate within one turn when
sliding the OSYSU on the bracket. Adjustment is correct when the valve is operated from the FULL OPEN towards the CLOSED
switches are not activated with the trip rod seated in the valve position.
stem groove and that the switches activate when the trip rod 8. Tighten the adjustment screws and mounting hardware. Check
moves out of the groove. to insure that the rod moves out of the groove easily and that the
9. Tighten the adjustment screws and all mounting hardware. switches activate within one turn when the valve is operated from
Check to insure that the rod moves out of the groove easily the FULL OPEN towards the CLOSED position.
and that the switches activate within one turn when the valve is Note: close the valve fully to determine that the stem threads
operated from the FULL OPEN towards the CLOSED position. do not activate the switch. The switch being activated by the stem
Note: Close the valve fully to determine that the stem threads threads could result in a false valve open indication.
do not activate the switch. The switch being activated by the stem
threads could result in a false valve open indication.

PRINTED IN USA MKT. #8820004 - REV R PAGE 2 OF 3


MFG# 5400979 - 2/08
OSYSU-1, -2
OUTSIDE SCREW AND YOKE VALVE
SUPERVISORY SWITCH
Fig. 3 Dimensions Fig. 4 Parts

Fig. 5 Breaking Excessive Rod Length Typical Electrical Connections

Switch Terminal Connections Clamping Plate Terminal

Contacts shown in normal (valve open) condition.

Typical Switch Action

An uninsulated section of a single conductor should not be looped


around the terminal and serve as two separate connections. The
wire must be severed, thereby providing supervision of the
connection in the event that the wire becomes dislodged from
under the terminal.

PRINTED IN USA MKT. #8820004 - REV R PAGE 3 OF 3


MFG# 5400979 - 2/08
FIRE WALL VALVE
FOR FIRE PROTECTION VALVES WWW.FIREWALLLLC.COM

Model F-507-W Resilient Wedge Gate Valve

Technical Features
300 PSI/20.7 bar non-shock water working pressure
Outside screw and yoke
Bolted bonnet
Resilient Wedge
Epoxy coated body inside and out per AWWA C-550
Flanged end connections
Conforms to AWWA C509
Listed by UL
FM Approved
Size range 2½” to 10”
Size range 12” to 16” 250 PSI /17.2 Bar non-shock water working pressure
MATERIAL LIST
PART SPECIFICATION
1.Valve Body Ductile Iron ASTM A 536
2.Resilent Wedge Ductile Iron ASTM A 536/EDPM ASTM D 2000
3.Wedge Nut Bronze ASTM B 584 UNS C83600 F-507-W
4.Dowel Pin Stainless Steel ASTM A 276 UNS S42000
4"-16" ASTM B584 UNS C92200 2"-3"
5.Stem Back Seat O-Ring EDPM ASTM D 2000
6.Bonnet Gasket EDPM ASTM D 2000
7.Bonnet Ductile Iron ASTM A 536
8.Stem Packing EDPM ASTM D 2000
9.Threaded Rod Carbon Steel Zinc Plated
10.Gland Bushing Bronze ASTM B 584
11.Gland Cast Iron ASTM A 126-B
12.Gland Nut Stainless Steel 18-8
13.Yoke Screw Alloy Steel ASTM A 574M Zinc Plated
14.Yoke Cast Iron ASTM A 126-B
15.Yoke Bushing Bronze ASTM B 584
16.Flat Point Set Screw Alloy Steel ASTM F912M Black Oxide
17.Yoke Bushing Retainer Cast Iron ASTM A 126-B
18.Handwheel Ductile Iron ASTM A 536
19.Handwheel Nut Carbon Steel Zinc Plated
20.Flat Head Screw Carbon Steel Zinc Plated
21.Stem Bronze ASTM B150 UNS C61400
22.Bonnet Screw Alloy Steel ASTM A 574M Zinc Plated
23.NPT Pipe Plug Malleable Iron ANSI B16.3(Epoxy Coated)
24.UL/FM Label Aluminum

DIMENSIONS---WEIGHTS---QUANTITIES
Dimensions
Size A B Open B Closed C D E F G Bolt Circle Flange Turns to Weight
In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm Holes Open L Lbs Kg
b
21/2 65 7.5 190 17.8 453 14.9 378 0.69 17.5 7.0 178 7.9 200 1.50 38 1.6 40 5.50 140 4 8.8 45 20
3 80 8 203 19.7 500 15.9 405 0.75 19.0 7.5 191 7.9 200 1.73 44 2.1 54 6.00 152 4 10.5 53 24
4 100 9 229 21 534 16.6 422 0.94 24.0 9.0 229 10.2 260 2.13 54 2.1 54 7.50 191 8 10.4 94 43
6 150 10.5 267 29.3 744 22.9 581 1.00 25.4 11.0 279 12.4 315 2.24 57 2.5 64 9.50 241 8 15.7 154 70
8 200 11.5 292 37 939 28.5 724 1.13 28.6 13.5 343 14.8 375 2.48 63 2.8 70 11.75 298 8 17.2 247 112
10 250 13 330 44.8 1139 34.5 877 1.19 30.2 16.0 406 16.4 416 2.56 65 2.8 70 14.25 362 12 21.4 349 159
12 300 14 356 52.2 1326 39.9 1014 1.25 31.8 19.0 483 17.5 445 2.91 74 3.4 86 17.00 432 12 25.5 484 220
14 350 15 381 62.51 1595 46.1 1171 1.38 35.0 21.0 533 18.7 475 2.95 75 3.1 80 18.75 476 12 44.0 682 310
16 400 16 406 74.64 1900 53.3 1354 1.46 37.0 23.5 597 20.5 520 3.00 77 3.1 80 21.25 540 16 50.0 860 391

7045 Mechanicsville TurnPike Mechanicsville VA 23111 USA


Phone: 804-9778777 Fax: 804-9778778 WWW.FIREWALLLLC.COM
‫ﺗﺎﺭﻳﺦ ﺍﻟﻄﺒﺎﻋﺔ ‪2018-10-08 :‬‬ ‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴــــﺔ‬
‫ﻭﻗـﺖ ﺍﻟﻄﺒﺎﻋﺔ ‪AM 8:46 :‬‬ ‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﻪ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬
‫ﺭﻗــﻢ ﺍﻟﻄﻠـﺐ ‪PAC18012014 :‬‬ ‫ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺷﻬــــــﺎﺩﺓ ﻋﺪﻡ ﻣﻤﺎﻧﻌﺔ‬


‫ﺍﻋﺘﻤﺎﺩ ﻣﻨﺘﺞ‬ ‫ﻧﻮﻉ ﺍﻟﺸﻬﺎﺩﺓ ‪:‬‬

‫ﺑﻴﺎﻧﺎﺕ ﺍﻟﻤﻨﺸﺄﺓ‬

‫ﺷﺮﻛﻪ ﺑﺎﻳﺐ ﻻﻳﻦ ﻟﻠﺨﺪﻣﺎﺕ ﻭﺍﻟﺘﻮﺯﻳﻊ‬ ‫ﺍﻻﺳﻢ ﺍﻟﺘﺠﺎﺭﻱ‪:‬‬


‫‪58537‬‬ ‫ﺭﻗﻢ ﺍﻟﺮﺧﺼﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ‪:‬‬ ‫‪34101‬‬ ‫ﺭﻗﻢ ﺍﻟﺴﺠﻞ ﺍﻟﺘﺠﺎﺭﻱ‪:‬‬
‫ﺭﻗﻢ ﺍﻟﻬﺎﺗﻒ‪:‬‬ ‫‪12-5623-00‬‬ ‫ﺭﻗﻢ ﻗﻴﺪ ﺍﻟﻤﻨﺸﺄﺓ‪:‬‬
‫ﺍﻟﺒﺮﻳﺪ ﺍﻹﻟﻜﺘﺮﻭﻧﻲ‪:‬‬
‫‪Fire Fighting systems‬‬ ‫ﺍﻟﺘﺼﻨﻴﻒ ‪:‬‬
‫‪Flow Switches, Supervisory, Tamper & Pressure Switches / Flow detector, Gauges,‬‬ ‫ﺇﺳﻢ ﺍﻟﻤﻨﺘﺞ ‪:‬‬
‫‪Testers‬‬
‫ﺗﻔﺎﺻﻴﻞ ﺍﻟﺸﻬﺎﺩﺓ‬

‫ﺗﻢ ﻣﺮﺍﺟﻌﺔ ﺍﻟﻄﻠﺐ ﺍﻟﻤﻘﺪﻡ ﻭﺍﺗﻀﺢ ﺑﺄﻧﻪ ﻻ ﻣﺎﻧﻊ ﻣﻦ ﺍﻋﺘﻤﺎﺩ ﺍﻟﻤﻨﺘﺞ ‪/‬ﺍﻟﻤﻨﺘﺠﺎﺕ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻰ ﺍﻟﻤﺮﻓﻖ ﺑﻨﺎﺀ ﻋﻠﻰ ﺍﻋﺘﻤﺎﺩﻩ ﻣﻦ‬
‫ﻗﺒﻞ ﺍﻟﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﺭ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ‪.‬‬

‫ﻣﻼﺣﻈﺎﺕ ‪:‬‬

‫‪ .1‬ﻳﺠﺐ ﻋﻠﻰ ﺍﻟﺸﺮﻛﻪ ﺍﻻﻟﺘﺰﺍﻡ ﻭﺍﻟﻌﻤﻞ ﺑﻤﺎ ﺟﺎﺀ ﻓﻲ ﺍﺷﺘﺮﺍﻃﺎﺕ ﻗﺴﻢ ﺃﻧﻈﻤﺔ ﺍﻟﺴﻼﻣﻪ ﺍﻟﺘﻲ ﺗﻢ ﺍﻻﻃﻼﻉ ﻭﺍﻟﻤﻮﺍﻓﻘﺔ ﻋﻠﻴﻬﺎ ﻣﻦ ﺧﻼﻝ ﺍﻟﻤﻮﻗﻊ ‪.‬‬
‫‪ .2‬ﻳﺠﺐ ﺍﻥ ﻳﻘﻮﻡ ﺑﺘﺮﻛﻴﺐ ﻫﺬﺍ ﺍﻟﻤﻨﺘﺞ ﻣﻦ ﻗﺒﻞ ﻣﻬﻨﺪﺳﻴﻦ ﻭﻓﻨﻴﻴﻦ ﻣﻌﺘﻤﺪﻳﻦ ﻣﻦ ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‪.‬‬
‫‪ .3‬ﻳﺠﺐ ﺍﻥ ﻳﺤﻤﻞ ﺍﻟﻤﻨﺘﺞ ﺍﻟﻌﻼﻣﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ ﻟﻠﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻌﺘﻤﺪﺓ ﻭﺍﻟﻤﻮﺿﺤﻪ ﻓﻲ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ ‪.‬‬

‫‪07/10/2020‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻹﻧﺘﻬﺎﺀ ‪:‬‬ ‫‪08/10/2018‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻻﻋﺘﻤﺎﺩ ‪:‬‬

‫ﻉ‪/‬‬

‫ﻣﺪﻳﺮ ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗـﺎﻳـــــﺔ‬


‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬

‫‪Page 1 of 2‬‬
‫ﺑﺴﻢ ﺍﻟﻠﻪ ﺍﻟﺮﺣﻤﻦ ﺍﻟﺮﺣﻴﻢ‬

DATE : 2018-10-08 : ‫ﺍﻟﺘﺎﺭﻳـــــــﺦ‬ ‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬


PERMIT PAC18012014 : ‫ﺭﻗﻢ ﺍﻟﻄﻠﺐ‬ ‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬
‫ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

TECHNICAL REPORT ‫ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ‬

PRODUCT : Flow Switches, Supervisory, Tamper & Pressure : ‫ﺍﻟﻤﻨﺘﺞ‬


Switches / Flow detector, Gauges, Testers
PRODUCT APPLICATION : Fire Fighting systems : ‫ﺗﺼﻨﻴﻒ ﺍﻟﻤﻌﺪﺓ‬
APPLICANT / P.O .Box ‫ﺷﺮﻛﻪ ﺑﺎﻳﺐ ﻻﻳﻦ ﻟﻠﺨﺪﻣﺎﺕ ﻭﺍﻟﺘﻮﺯﻳﻊ‬ : ‫ﻣﻘﺪﻡ ﺍﻟﻄﻠﺐ‬
MANUFACTURER /
POTTER ELECTRIC SIGNAL CO. LLC. / USA :‫ ﺑﻠﺪ ﺍﻟﺼﻨﻊ‬/ ‫ﺍﻟﺸﺮﻛﺔ ﺍﻟﻤﺼﻨﻌﺔ‬
LOCATION :

‫ﺍﻟﻮﺻﻒ‬ ‫ﺍﻟﻤﻮﺩﻳﻞ‬
Outside screw and yoke valve supervisory switch, one set of SPDT form C contact, 10 Amps
OSYSU-1
at 250VAC.
Outside screw and yoke valve supervisory switch, two sets of SPDT form C contact, 10 amps
OSYSU-2
@ 250VAC, partnumber 1010202.
Pressure switch, dry and wet-pipe, 4 to 15psig operating pressure, 300psig max system
PS10-1
pressure, one set form C SPDT contacts, 10.1 amps at 240VAC.
Pressure switch, dry and wet-pipe, 4 to 15psig operating pressure, 300psig max system
PS10-2
pressure, two sets for C SPDT contacts.
Sprinkler system alarm initiating device, wet pipe paddle type, 2, 2-1/2, 3, 3-1/2, 4, 5, 6, 8, 10
VSR
inch size, 450 psig max system pressure.
Sprinkler system alarm initiating device, wet pipe paddle type, 1, 1-1/4, 1-1/2, 2 inch size, 300
VSR-S
psig max system pressure.
Sprinkler system alarm initiating device, wet pipe paddle type, 1, 1-1/4, 1-1/2, 2 inch size, 250
VS-SP
psig max system pressure.

3RD PARTY ‫ﺷﻬﺎﺩﺓ ﺍﻟﻤﺨﺘﺒﺮﺍﺕ ﺍﻟﻤﺴﺎﻧﺪﺓ‬


CERTIFICATE / - USQT.S309 - Underwriters
APPROVAL : Laboratories : ( ‫)ﻣﻦ ﻫﻴﺌﺎﺕ ﻣﻌﺘﻤﺪﺓ‬
(UL)

RECOMMENDATIONS ‫ﺍﻟﺘﻮﺻﻴﺎﺕ‬
NOTES/STANDARD:

Devices having electrical signaling contacts and designed for attachment to extinguishing system equipment.
INVESTIGATED TO STANDARD UL 346.

/‫ﻉ‬

‫ﻣﺪﻳﺮ ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗـﺎﻳـــــﺔ‬


‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬

Page 2 of 2
‫ﺗﺎﺭﻳﺦ ﺍﻟﻄﺒﺎﻋﺔ ‪2019-01-31 :‬‬ ‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴــــﺔ‬
‫ﻭﻗـﺖ ﺍﻟﻄﺒﺎﻋﺔ ‪ :‬ص ‪9:29‬‬ ‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﻪ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬
‫ﺭﻗــﻢ ﺍﻟﻄﻠـﺐ ‪PAC19001306 :‬‬ ‫ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺷﻬــــــﺎﺩﺓ ﻋﺪﻡ ﻣﻤﺎﻧﻌﺔ‬


‫ﺍﻋﺘﻤﺎﺩ ﻣﻨﺘﺞ‬ ‫ﻧﻮﻉ ﺍﻟﺸﻬﺎﺩﺓ ‪:‬‬

‫ﺑﻴﺎﻧﺎﺕ ﺍﻟﻤﻨﺸﺄﺓ‬

‫ﺷﺮﻛﻪ ﺑﺎﻳﺐ ﻻﻳﻦ ﻟﻠﺨﺪﻣﺎﺕ ﻭﺍﻟﺘﻮﺯﻳﻊ‬ ‫ﺍﻻﺳﻢ ﺍﻟﺘﺠﺎﺭﻱ‪:‬‬


‫‪58537‬‬ ‫ﺭﻗﻢ ﺍﻟﺮﺧﺼﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ‪:‬‬ ‫‪34101‬‬ ‫ﺭﻗﻢ ﺍﻟﺴﺠﻞ ﺍﻟﺘﺠﺎﺭﻱ‪:‬‬
‫ﺭﻗﻢ ﺍﻟﻬﺎﺗﻒ‪:‬‬ ‫‪12-5623-00‬‬ ‫ﺭﻗﻢ ﻗﻴﺪ ﺍﻟﻤﻨﺸﺄﺓ‪:‬‬
‫ﺍﻟﺒﺮﻳﺪ ﺍﻹﻟﻜﺘﺮﻭﻧﻲ‪:‬‬
‫‪Fire Fighting systems‬‬ ‫ﺍﻟﺘﺼﻨﻴﻒ ‪:‬‬
‫)‪Valves (OS&Y,Butterfly,Globe,Check,Gate Relief Valves etc‬‬ ‫ﺇﺳﻢ ﺍﻟﻤﻨﺘﺞ ‪:‬‬

‫ﺗﻔﺎﺻﻴﻞ ﺍﻟﺸﻬﺎﺩﺓ‬

‫ﺗﻢ ﻣﺮﺍﺟﻌﺔ ﺍﻟﻄﻠﺐ ﺍﻟﻤﻘﺪﻡ ﻭﺍﺗﻀﺢ ﺑﺄﻧﻪ ﻻ ﻣﺎﻧﻊ ﻣﻦ ﺍﻋﺘﻤﺎﺩ ﺍﻟﻤﻨﺘﺞ ‪/‬ﺍﻟﻤﻨﺘﺠﺎﺕ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻰ ﺍﻟﻤﺮﻓﻖ ﺑﻨﺎﺀ ﻋﻠﻰ ﺍﻋﺘﻤﺎﺩﻩ ﻣﻦ‬
‫ﻗﺒﻞ ﺍﻟﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﺭ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ‪.‬‬

‫ﻣﻼﺣﻈﺎﺕ ‪:‬‬

‫‪ .1‬ﻳﺠﺐ ﻋﻠﻰ ﺍﻟﺸﺮﻛﻪ ﺍﻻﻟﺘﺰﺍﻡ ﻭﺍﻟﻌﻤﻞ ﺑﻤﺎ ﺟﺎﺀ ﻓﻲ ﺍﺷﺘﺮﺍﻃﺎﺕ ﻗﺴﻢ ﺃﻧﻈﻤﺔ ﺍﻟﺴﻼﻣﻪ ﺍﻟﺘﻲ ﺗﻢ ﺍﻻﻃﻼﻉ ﻭﺍﻟﻤﻮﺍﻓﻘﺔ ﻋﻠﻴﻬﺎ ﻣﻦ ﺧﻼﻝ ﺍﻟﻤﻮﻗﻊ ‪.‬‬
‫‪ .2‬ﻳﺠﺐ ﺍﻥ ﻳﻘﻮﻡ ﺑﺘﺮﻛﻴﺐ ﻫﺬﺍ ﺍﻟﻤﻨﺘﺞ ﻣﻦ ﻗﺒﻞ ﻣﻬﻨﺪﺳﻴﻦ ﻭﻓﻨﻴﻴﻦ ﻣﻌﺘﻤﺪﻳﻦ ﻣﻦ ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‪.‬‬
‫‪ .3‬ﻳﺠﺐ ﺍﻥ ﻳﺤﻤﻞ ﺍﻟﻤﻨﺘﺞ ﺍﻟﻌﻼﻣﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ ﻟﻠﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻌﺘﻤﺪﺓ ﻭﺍﻟﻤﻮﺿﺤﻪ ﻓﻲ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ ‪.‬‬

‫‪30/01/2021‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻹﻧﺘﻬﺎﺀ ‪:‬‬ ‫‪31/01/2019‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻻﻋﺘﻤﺎﺩ ‪:‬‬

‫ﻉ‪/‬‬

‫ﻣﺪﻳﺮ ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗـﺎﻳـــــﺔ‬


‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬

‫‪Page 1 of 2‬‬
‫ﺑﺴﻢ ﺍﻟﻠﻪ ﺍﻟﺮﺣﻤﻦ ﺍﻟﺮﺣﻴﻢ‬

DATE : 2019-01-31 : ‫ﺍﻟﺘﺎﺭﻳـــــــﺦ‬ ‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬


PERMIT PAC19001306 : ‫ﺭﻗﻢ ﺍﻟﻄﻠﺐ‬ ‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬
‫ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

TECHNICAL REPORT ‫ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ‬

PRODUCT : Valves (OS&Y,Butterfly,Globe,Check,Gate Relief : ‫ﺍﻟﻤﻨﺘﺞ‬


Valves etc)
PRODUCT APPLICATION : Fire Fighting systems : ‫ﺗﺼﻨﻴﻒ ﺍﻟﻤﻌﺪﺓ‬
APPLICANT / P.O .Box ‫ﺷﺮﻛﻪ ﺑﺎﻳﺐ ﻻﻳﻦ ﻟﻠﺨﺪﻣﺎﺕ ﻭﺍﻟﺘﻮﺯﻳﻊ‬ : ‫ﻣﻘﺪﻡ ﺍﻟﻄﻠﺐ‬
MANUFACTURER /
FIREWALL L L C / USA :‫ ﺑﻠﺪ ﺍﻟﺼﻨﻊ‬/ ‫ﺍﻟﺸﺮﻛﺔ ﺍﻟﻤﺼﻨﻌﺔ‬
LOCATION :

‫ﺍﻟﻮﺻﻒ‬ ‫ﺍﻟﻤﻮﺩﻳﻞ‬
Gate valve, OS&Y pattern, Flange by flange end configutration, Rated pressure(psig) 300 &
F-507-W
250 and Size (in.) 2.5,3,4,6,8,10 & 12, 14, 16 respectively.

3RD PARTY ‫ﺷﻬﺎﺩﺓ ﺍﻟﻤﺨﺘﺒﺮﺍﺕ ﺍﻟﻤﺴﺎﻧﺪﺓ‬


CERTIFICATE / - HMRZ. - Underwriters
APPROVAL : EX16297 Laboratories : ( ‫)ﻣﻦ ﻫﻴﺌﺎﺕ ﻣﻌﺘﻤﺪﺓ‬
(UL)

RECOMMENDATIONS ‫ﺍﻟﺘﻮﺻﻴﺎﺕ‬
NOTES / STANDARS

Insvestigated to standard UL 262, "Gate Valves for Fire-Protection Service."

/‫ﻉ‬

‫ﻣﺪﻳﺮ ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗـﺎﻳـــــﺔ‬


‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬

Page 2 of 2
x

1. Installations shall be done as per SMACNA and ASHRAE recommendations.


2. All ducting shall be properly insulated.
3. This conditional approval is given to this specific project only & shall not be used as reference.

Fadi Kaakour 27.10.2020


 
 
 
 

INDEX 
 
1.   Company Profile 

2.  Company Strength 

3.  Key Business Attributes 

4.  Key performance Indicators 

5.  Working Principles 

6.  CAT Duct Planning & Production Cycle 

7.  Organization Chart 

8.  List of Products 

9.  List of Machineries 

10.  Project Reference List 

11.  ISO Certificate 

 
COMPANY PROFILE

Based in Qatar, the Al Malki Group is professionally managed engineering organization with
extensive interests in electro-mechanical contracting, trading, maintenance, facilities
management, manufacturing of HVAC ducts, dampers, Electrical Power & Control panels
besides a whole range of services for its diverse clientele.

The CAT DUCT Factory will be the most modern and


largest of its kind in Qatar using state-of-the-art computer
controlled machinery from the USA, the UK and Europe.
This facility will manufacture ducts complying with
international standards such as SMACNA, DW etc.

Manufacture from raw materials such as galvanized steel,


aluminium, stainless steel and mild steel, the products will
include Standard Rectangular HVAC Ducts and Fittings,
Special Traverse Joint TDF Ductwork for airtight
requirements, Fire-rated Ducts to BS:476: Part 24: 1987,
Volume Control Dampers, Fire Dampers, VAV Units, Air
Filters, Access Doors, Plenum Boxes and Sand Trap
Louvers.

Other salient features of CAT Duct Factory are quality assurance and control at every stage of
manufacture conforming to international processes and standards, highly experienced
engineers working with skilled technicians and fabricators-and strict compliance with health,
safety and environment norms.
COMPANY STRENGTH

1. Member of reputed Al Malki Group of Companies a well-diversified Qatar-based organization


with over 3,500 skilled employees and offers a broad spectrum of products and services: Civil
Contracting, MEP Contracting, Manufacturing, trading in Engineered Products and Systems,
Building Materials, Maintenance of Building Services, Facility Management, Duct
Manufacturing, Assembly of LV Electrical Panels, Real Estate, Food Logistics and other growth
areas.

2. Financial & Resource Support from the Al Malki Group

3. State-of-Art Duct Fabrication Machinery from USA, UK and Germany

4. Over one decade of successfully operation in Qatar

5. One of the largest Duct Fabrication factory in Qatar

6. CAT-Duct products are well known for Quality and on-time delivery

7. Highly skilled & well experience skilled Duct Technicians ( 100 plus )

8. Large Fleet of Vehicles and Trucks for delivery.

9. Annual Production Capacity

SN. Product Planned Achieved last year 2019 Usage


1 Ducting 220,000 sq. meter Approx. 241,000 sq. meter 109%
2 Accessories 28,000 pcs. Approx. 24,000 pcs. 85%

10. GI Coils are directly imported from Steel Factory and we hold stock for approx. six months
production.
 
KEY BUSINESS ATTRIBUTES

1. To consistently meet our customers’ expectations by


understanding their needs and delivering projects which
they and we can be proud of.

2. To achieve this by nurturing the experience and skills of


our people to ensure the highest standards of
workmanship and professionalism in everything we do.
KEY PERFORMANCE INDICATORS (KPIs)

Our performance, at an individual project and overall corporate level,


will be assessed through KPI measures of the following:

1. Health and Safety

2. Program

3. Quality

4. Supplier Performance

5. Relationships

6. Specialist Subcontractor Performance


WORKING PRINCIPLES

1. Endeavour to understand and respond to our customers’


needs, and deliver on our commitments.

2. Pre-plan our projects in detail, make comprehensive


provisions for logistics, provide a safe working
environment, respect our neighbor and the environment,
whilst ensuring on-time delivery for our customer.

3. Recognize the value of our people by investing in their


skills, promoting open communications and creating a
team working environment at all levels within
organization.

4. Take personal pride in our workmanship, plan quality and


learn from our success and failures.
MANAGEMENT SYSTEM PROCEDURE
Ref : CAT 01
PLANNING & PRODUCTION Issue : 01
Effective : 02-01-07
Page : 2 of 2

5. Process
Input Process Output
Job Order
Customer
Job Order Sales Manager

Production
Material Stock Status
Production Manager

Production Plan & Requirement


Production Plan
- Raw Materials
- Human Resources Production Manager
-Drawing Design

No
Material Purchase Purchasing
Available? Request Department

Yes

Production
- Control Production
Records
Production Supervisor

Inspection
- Customer Quality Inspection
Requirement
Quality In-charge
- Quality Plan

Yes
No
Conform? Corrective Measures

Delivery Point
-Customer Order No. Finished Ducts
-Labeling Production Supervisor & Fitting List

Customer Stores
Job Order
Warehouse Incharge

Feed back by Email


Delivery Process
LIST OF PRODUCTS

01. Rectangular Duct


Ductw
work

ork
02. Circular / Spiral Du
Ductwork

ctwork
03. Fire Rated Ductwo
Ductwork

rk
04. Pre-Insulated Duc
Ductt

05. Volume Control D


Daamper

mper
06. Motorized Damper
Dampers
s
07. Back Draft Dampe
Dampers

rs
06. Fire Damper

07. Access Doors

08. Air Filters

09. Sound Attenuator


Attenuatorss

10. Sand Trap Louvers


Louvers

11. Fresh Air Louvers

12. Variable Air Volu


Volum
mee ( VAV Box)

Box)
13. Aluminum Claddin
Cladding
g for Pipes & Ducts

Ducts
14. Fresh Air Intake A
As
ssembly

sembly

15. S.S Kitchen Hood

16. Kitchen Stainless Steel Equipments

Equipments
                 

                     Make:- Engel –USA

Make:- Vicon–USA

Make:- Spiro–Switzerland

Make:- Spiro–Switzerland

Make:- Engel –USA

Make:- Engel –USA

Make:- Engel –USA

Make:- Maximart–Taiwan

Make:- Fintek–Taiwan

Make:- ACL–China

Make:- Ador-India

Make:- Engel –USA

Make:- Fintek–Taiwan

Make:- Spiro–Switzerland

Make:- Spiro–Switzerland
 

Sl.No  Client / Contractor  Project Name 


1  Arabian MEP Contracting  Pearl Qatar Parcel – 1C 
2  Arabian MEP Contracting  Pearl Qatar Parcel – 2A 
3  Arabian MEP Contracting  Pearl Qatar Parcel – 7A 
4  Arabian MEP Contracting  Nakilat Ship Yard 
5  Arabian MEP Contracting  Qatar Airways 4*Hotel 
6  Arabian MEP Contracting  New Arrival Terminal 
7  Arabian MEP Contracting  Ezdan Mall 
8  Arabian MEP Contracting  Lusail Under Ground Car Park 
9  Arabian MEP Contracting  Kharamaa Substations Phase‐6,7,8,9,10 
10  Arabian MEP Contracting  Viva Bhariya ‐29 
11  Arabian MEP Contracting  Qatar Pharma 
12  Arabian MEP Contracting  Centro Hotel 
13  Arabian MEP Contracting  Tawar Mall 
14  Arabian MEP Contracting  Wakara Mall 
15  Arabian MEP Contracting  Katara Fitness Center 
16  Arabian MEP Contracting  Omar Al Fardan Palace 
17  Arabian MEP Contracting  Ali Al Fardan Palace 
18  Arabian MEP Contracting  Shemoukh Twin Tower 
19  Arabian MEP Contracting  QP‐TDOC 
20  Arabian MEP Contracting  Souq Car Park 
21  Arabian MEP Contracting  Abraj Quartier (AQ‐01) 
22  Al Malki Trading  Al Dakira Sports Club 
23  Al Malki Trading  TS‐3 Pumping Stations 
24  Al Malki Trading  Villa Complex 
25  Al Arab Trading & Contracting  Kharamaa Substations Phase‐8,9,10 
26  Anel MEK  NDIA (CP‐99,110 & 111) 
27  Al Jaber Electro Mechanical  Educational City – Tunnel 
28  AGA‐MEP  DSWMC Project 

 
 

29  Artic Cooling  Al Khass Studio 


30  Afrina Trading  Pearl Qatar Parcel‐16B 
31  Afrina Trading  Under Ground Project 
32  Butec  Kharamaa Substations Phase‐8 
33  Boom Construction  Al Khore Park 
34  Consolidated Construction Co  NDIA (CP‐76) 
35  Conspel Qatar  Al Wakara Hospital 
36  Conspel Qatar  Qanat Quartier 
Male & Female Accommodation‐Qatar 
37  Conspel Qatar 
Foundation 
38  Continental Cooling  Islamic Center 
39  Commodore Qatar  Qatar Steel Sub Station 
40  ETA  Barwa Commercial Avenue 
41  ESI Qatar  Multi Story Car Park 
42  Green Top International  Kharamaa Substations Phase‐8,9 
43  Gulf Integrated  KG School 
44  Gulf Contracting Co  Barzan On Shore camp (Ras gas) 
45  Harinsa Qatar  ABM Military College 
46  HKH  Sheik Villa 
47  HKH  Al Habara Breeding Station ‐Phase‐2 
48  HKH  Jordan Embassy 
49  HKH  Mosque 
50  Hyupjin Qatar  Msheireb Downtown Doha Project ‐ Phase 1A 
51  Hyundai  Msheireb Downtown Doha Project ‐ Phase 1A 
52  Megatech  Al Shamriya Tower 
53  Megatech  Abraj Quartier (AQ‐02) 
54  Radiant Engineering Enterprises  Island Palace Villa 
55  Radiant Engineering Enterprises  Fire House Project 
56  Radiant Engineering Enterprises  Souq Hotel 

 
 

57  Radiant Engineering Enterprises  Ramez Villa 


58  Radiant Engineering Enterprises  Wakara Terminal 
59  Siemens Limited  GTC‐282 
60  SECCO  New Doha Int’l Air port – CP 76 
61  Shelter Qatar  BV‐56 Villa 
62  SECCO  WCMC‐Qatar Foundation 
63  Transfield Mannai  Qatar Steel Project 
64  Transfield Mannai  QP‐Dukhan 
65  Ultimate Trading  Barwa Commercial Avenue 
66  Voltas  Sidra medical‐Qatar Foundation 
67  Voltas  Barwa Residential Complex 
68  Voltas  Msheireb Down Town Project (Heart of Doha) 
 

 
x x

1. GI sheet origin shall be provided, data sheet for the same shall be provided.
2. Manufacturer official documents shall be provided.
3. Required mill certificate shall be submitted for reference.

Fadi Kaakour 20/10/2020


x

1. Only diaphragm type PICV shall be installed.


2. PICV shall be of equal percentage type.
3. Country of origin certificate shall be provided upon material delivery.
4. Installation shall be done as recommended by the manufacturer.
5. This conditional approval is given to this project only and shall not be used for future reference.

Fadi Kaakour 23.11.2020


4 855

VPP46.. VPI46..

VPP46..Q, with pressure test points P/T VPI46..Q, with pressure test points P/T

ACVATIX™

Combi valves, PN 25 VPP46..


VPP46..Q
VPI46..
VPI46..Q
for rooms, zones, ventilation and air-conditioning systems

· With integrated differential pressure controller


· DN 10…DN 32: Valve body made of dezincification resistant hot-pressed
brass (DZR)
· DN 40…DN 50: Housing made of spheroidal graphite iron
· Volumetric flow 30... 11500 l/h,
· Differential pressure range 15…600 kPa
· Internally threaded Rp conforming to ISO 7-1
· Externally threaded G conforming to ISO 228-1
· Version with pressure test points for Δp measurement (optional)
· Can be equipped with electro thermal or electromotive actuators
- SSA.. (3-position or DC 0…10 V)
- STA..3../STP..3.. (2-position or PDM)
- SUA21/3, SUA21/3P, SUE21P (2-position SPST)
- STA63../STP63.. (DC 0…10 V)
- SAY..1P03 (3-position or DC 0…10 V)
Use

· In ventilation and air conditioning plants for control on the water side and auto-
matic hydraulic balancing of terminal units, such as fan coils, induction units, and
in heat exchangers for heating or cooling
· In heating zones like self-contained heating systems, apartments, individual
rooms, etc.
· For closed circuits

CE1N4855en
2020-05-29 Smart Infrastructure
Type summary

Product no. Stock DN H100 Connections Test v̇min v̇100 SUA21/32) SUE21P STA..3.. / SSA..
points SUA21/3P STP..3..3)
∆pmax1) ∆pmax1) ∆pmax1) ∆pmax1)
[mm] [inch] [l/h] [l/h] [kPa] [kPa] [kPa] [kPa]
VPP46.10L0.2 S55264-V101 2.5 30 200 600 - 600
600
10 4.5 G½ 333 - -
VPP46.10L0.4 S55264-V131 65 -
5 370 600 -
VPP46.15L0.2 S55264-V102 30 200 600
15 2.5 G¾ 600 -
VPP46.15L0.6 S55264-V103 100 575 600
4.5 200 1190 - -
VPP46.20F1.4 S55264-V104 20 G1 -
5 - 220 1330 600 - 600
4.5 238 1530 - 600 -
VPP46.25F1.8 S55264-V121 25 5 G 1¼ 260 1670 - 600 - -
5.5 280 1800 - - 600
4.5 468 3400 - 600 -
VPP46.32F4 S55264-V122 32 5 G 1½ 510 3700 - 600 - -
5.5 externally 550 4001 - -
600
VPP46.10L0.2Q S55264-V105 2.5 threaded 30 200 600 -
600
10 4.5 G½ 333 - -
VPP46.10L0.4Q S55264-V132 65 -
5 370 600 -
VPP46.15L0.2Q S55264-V106 30 200 600
15 2.5 G¾ 600 -
VPP46.15L0.6Q S55264-V107 100 575 600
4.5 with pres- 200 1190 - -
VPP46.20F1.4Q S55264-V108 20 G1 -
5 sure test 220 1330 600 - 600
4.5 points P/T 238 1530 - 600 -
VPP46.25F1.8Q S55264-V123 25 5 G 1¼ 260 1670 - 600 - -
5.5 280 1800 - - 600
4.5 468 3400 - 600 -
VPP46.32F4Q S55264-V124 32 5 G 1½ 510 3700 - 600 - -
5.5 550 4001 - - 600

VPI46.15L0.2 S55264-V109 30 200


15 2.5 Rp ½ 600 - 600
VPI46.15L0.6 S55264-V110 100 575 600
4.5 200 1190 - -
VPI46.20F1.4 S55264-V111 20 Rp ¾ -
5 220 1330 600 - 600
4.5 238 1530 - 600 -
-
VPI46.25F1.8 S55264-V125 25 5 Rp 1 260 1670 - 600 - -
5.5 280 1800 - - 600
4.5 468 3400 - 600 -
VPI46.32F4 S55264-V126 32 5 Rp 1¼ 510 3700 - 600 - -
5.5 internally 550 4001 - -
VPI46.15L0.2Q S55264-V112 threaded 30 200 600
15 2.5 Rp ½ 600 -
VPI46.15L0.6Q S55264-V113 100 575 600
4.5 200 1190 - -
VPI46.20F1.4Q S55264-V114 20 Rp ¾ -
5 220 1330 600 - 600
4.5 with pres- 238 1530 - 600 -
sure test
VPI46.25F1.8Q S55264-V127 25 5 Rp 1 points P/T 260 1670 - 600 - -
5.5 280 1800 - - 600
4.5 468 3400 - 600 -
VPI46.32F4Q S55264-V128 32 5 Rp 1¼ 510 3700 - 600 - -
5.5 550 4001 - - 600

1)
∆pmin value refer to page 9
2)
Only with mounting AL60 accessory, the SUA21/3 can drive the VPI46.. or VPP46..valve
3)
STP..3.. may only be used together with
- VPP46.10L0.2 - VPP46.10L0.2Q - VPI46.15L0.2 - VPI46.15L0.2Q
- VPP46.15L0.2 - VPP46.15L0.2Q - VPI46.15L0.6 - VPI46.15L0.6Q
- VPP46.15L0.6 - VPP46.15L0.6Q

2 / 18
Siemens Combi valves, PN 25 CE1N4855en
Smart Infrastructure 2020-05-29
Product no. Stock no. DN H100 Connections Test points v̇min v̇100 SAY..P
∆pmin ∆pmax
[mm] [Inch] [l/h] [l/h] [kPa] [kPa]

VPI46.40F9.5Q S55264-V129 40 Rp 1½ 1370 9500 25


with pres-
internally
15 sure test 600
threaded
VPI46.50F12Q S55264-V130 50 Rp 2 points P/T 1400 11500 36

DN = nominal size
H100 = nominal stroke
v̇100 = volumetric flow through fully open valve (H100)
v̇min = smallest pre-settable volumetric flow through fully open valve (H100)
∆pmax = maximum permissible differential pressure across the valves control path, valid for the entire
actuating range of the motorized valve
∆pmin = minimum differential pressure required across the valve’s control path, so that the difference
pressure regulator works reliably

Fittings Product no. Stock no. Description


ALG..2 ALG..2 Set of 2 fittings with threaded connections for 2-port valves, consisting of 2
union nuts, 2 discs and 2 flat seals
ALG..2B S55846-Z1.. Brass fittings, for media temperatures up to 100 °C

Ordering

Example Product no. Stock no. Designation


VPP46.15L0.2 S55264-V102 Combi valve, PN 25, externally threaded
SSA61 SSA61 Actuator

Delivery PICV valves, actuators and accessories are packed and supplied separately.

Revision numbers See page 18

Equipment combinations DN 15…32

Actuators Mounting Operating Positioning Actuators Spring Stroke Connecting Data sheet
set voltage signal force (no power)1) return cable

SSA31 AC 230 V
3-position
SSA81 AC 24 V 2.5 mm
- 1.5 m N4893
SSA61 5 mm
AC/DC 24 V DC 0...10 V
SSA61EP
STA23.. AC 230 V 2- position
- 100 N NC
STA73.. AC/DC 24V 2-position, PDM
STA63.. AC 24 V DC 0…10 V 2.5 mm
see data
ü max. 4.5 N4884
STP23.. 2)
AC 230 V 2-position sheet
mm
STP73.. 2) AC/DC 24V 2-position, PDM NO
STP63.. 2) AC 24 V DC 0...10 V
SUA21/3 AL60 AC230V 170N A6V10446174
3-wire on/off 2.5 mm
SUA21/3P AC230V 1) - 0.8 m A6V11780780
- (SPST ) 100N
SUE21P AC230V 5mm A6V11780777

1)
NC = Normal Closed = VPP46../VPI46.. powerless closed
NO = Normal Open = VPP46../VPI46.. powerless open
The valve is fully opened without an actuator
2)
STP..3.. may only be used together with
- VPP46.10L0.2 - VPI46.15L0.2
- VPP46.15L0.2 - VPI46.15L0.6
- VPP46.15L0.6 - VPI46.15L0.2Q
- VPP46.10L0.2Q - VPI46.15L0.6Q
- VPP46.15L0.2Q
- VPP46.15L0.6Q

3 / 18

Siemens Combi valves, PN 25 CE1N4855en


Smart Infrastructure 2020-05-29
Equipment combinations DN 40…50

Manual
Pos. Operating Positioning Spring Spring return di- Pos. Auxiliary
Type Article no. Stroke LED adjust-
force voltage signal return rection time functions
ment
1)
SAY31P03 S55150-A132 AC 230 V 3-position -
DC 0…10 V
Press and 2) 3)
SAY61P03 S55150-A133 15 mm 200 N DC 4…20 mA - - 30 s P ,
AC/DC 24 V 0…1000 Ω fix in place
1)
SAY81P03 S55150-A134 3-position -

1)
Optional accessories: Auxiliary switch ASC10.51
2)
Positioning feedback, forced control, characteristic curve changeover
3)
Optional accessories: Auxiliary switch ASC10.51, sequence control, control action changeover AZX61.1

Fittings
Combi valves Set of fittings
Externally threaded Malleable cast iron Brass
Product no. Stock no. Type / Stock no. Product no. Stock no.
VPP46.10L0.2 S55264-V101 - ALG132 1) BPZ:ALG132
VPP46.10L0.4 S55264-V131 - ALG132 1) BPZ:ALG132
VPP46.15L0.2 S55264-V102 - ALG142 1) BPZ:ALG142
VPP46.15L0.6 S55264-V103 - ALG142 1) BPZ:ALG142
VPP46.20F1.4 S55264-V104 ALG152 ALG152B 2) S55846-Z100
VPP46.25F1.8 S55264-V121 ALG202 ALG202B 2)
S55846-Z102
VPP46.32F4 S55264-V122 ALG252 ALG252B2) S55846-Z104
VPP46.10L0.2Q S55264-V105 - ALG132 1) BPZ:ALG132
VPP46.10L0.4Q S55264-V132 - ALG132 1) BPZ:ALG132
VPP46.15L0.2Q S55264-V106 - ALG142 1) BPZ:ALG142
VPP46.15L0.6Q S55264-V107 - ALG142 1)
BPZ:ALG142
VPP46.20F1.4Q S55264-V108 ALG152 ALG152B 2) S55846-Z100
VPP46.25F1.8Q S55264-V123 ALG202 ALG202B2) S55846-Z102
VPP46.32F4Q S55264-V124 ALG252 ALG252B2) S55846-Z104
1)
Connecting thread pipe side: Internally threaded
2)
Usable up to maximum medium temperature of 100 °C

Technical / mechanical design

1 Manual control knob


2 Ring with dial for presetting
3 Aperture for differential pressure controller is
linked with outlet port B
4 Differential pressure controller
5 Plug for presetting opening
6 Flow control valve
7 Pressure test point, blue ribbon, P-
8 Pressure test point, red ribbon, P+
A Inlet port A
B Outlet port B

Combi valves VP..46..Q (shown here) are additionally


equipped with pressure test points P/T.

4 / 18
Siemens Combi valves, PN 25 CE1N4855en
Smart Infrastructure 2020-05-29
Functional principle The medium entering the valve (inlet port A) passes
through the variable presetting opening (5) which is
connected to the ring with the dial (2) for presetting
the desired maximum volumetric flow. Then, the me-
dium flows through the flow control valve (6) with a
linear characteristic and a stroke of 2.5 mm
(DN 10…15) respectively 5 mm (DN 20).
Ring with dial for presetting (2)
The actuator (not shown here) opens and accurately positions the control valve
(6). Before leaving the Combi valve, the medium passes through a built-in me-
chanical differential pressure controller (4). This differential pressure controller is
the heart of the Combi valve and ensures that the selected volumetric flow is
maintained across the whole working range and independent of the inlet pressure
p1.
The Combi valves VP..46..Q are additionally equipped with two pressure test
points (P+, P-), which allow measurement of the differential pressure across the
Combi valve. For that purpose, the electronic manometer ALE10 can be used.

A Inlet medium (inlet port)


B Outlet medium (outlet port)
2 Ring with dial for presetting
4 Differential pressure controller
maintains the pressure p1 – p2
constant across the flow control
valve (6) and the presetting (2)
6 Control valve with mounted ac-
tuator

P- = P/T port, pressure test point with blue ribbon (7)


P+ = P/T port, pressure test point with red ribbon (8)
p1 = pressure at inlet of Combi valve
p2 = pressure at outlet of flow control valve
p3 = pressure at outlet of Combi valve

Manual control The manual control knob (1) is ready fitted to protect valve
DN 10…32 stem and pre-set mechanism and facilitates manual control
of the Combi valve during commissioning.

Factory setting:
The valve is open. To close the valve, turn the manual knob
clockwise.
The valve must be open to purge the system.

5 / 18

Siemens Combi valves, PN 25 CE1N4855en


Smart Infrastructure 2020-05-29
Accessories

Product
Stock no. Description
no.

Electronic manometer excluding measuring lines and measuring


tips. Measuring range 0-700 kPa. A differential pressure of more
than 1000 kPa will destroy the pressure sensor.
For measuring the differential pressure between P+ and P- of the
Combi valves (refer to diagram under "Functional principle" on page
3).
ALE10 ALE10
Functions of the manometer:
· Start/stop
· Automatic zero position
· Backlit display
· Display: Out à outside the measuring range
· Holding function

Measuring lines and straight measuring tips for use with Siemens
ALE11 ALE11 Combi valves.
Equipped with G ⅛” connection with 2 x 40 mm needles.

Spare nipples P/T port (set of 2)


Set contains 1 piece each with a red and blue ribbon.
ALP45 ALP45 Port: External threads G ⅛“ to ISO 228
Connection to valve body: G ¼“ to ISO 228, inclusive O-ring
Length: 40 mm

Blanking plug for P/T ports


ALP46 S55264-V115
Connection to valve body: G ¼“ to ISO 228, inclusive O-ring

Drain ball valve inclusive O-ring


Port: External threads G ½“ to ISO 228
ALP47 S55264-V116
Connection to valve body: G ¼“ to ISO 228, inclusive O-ring
Length: 48 mm

Combined P/T port and drain ball valve with red ribbon
Port: External threads G ⅛“ to ISO 228
ALP48 S55264-V117
Connection to valve body: G ¼” to ISO 228, inclusive O-ring
Length: 80 mm

Long P/T ports (set of 2 pieces)


Set contains 1 piece each with a red and blue ribbon.
ALP49 S55264-V118 Port: External threads G ⅛“ to ISO 228
Connection to valve body: G ¼“ to ISO 228, inclusive O-ring
Length: 120 mm

ALP50 S55264-V119 Spare black valve protection cap

6 / 18
Siemens Combi valves, PN 25 CE1N4855en
Smart Infrastructure 2020-05-29
Sizing

Engineering example Basis of calculation


1. Determine energy demand Q [kW]
2. Determine temperature differential ΔT [K]
3. Calculate volumetric flow
Q[kW] ∙ 1000 l
v̇=
1,163 ∙ ∆T[K] h
4. Select suitable Combi valve
- pipe connections (internally or externally threaded)
- with or without P/T ports
5. Determine dial setting using volumetric flow/dial presetting table, see the follow-
ing page

Example 1. Given is a heat exchanger with Q = 1.9 kW


2. Temperature differential (supply - return) ∆T = 6 K
3. Volumetric flow
1,9kW ∙ 1000
v̇ = = 272,28 ⁄h
1,163 ∙ 6 K
Hint: You can also determine the volumetric flow using the valve slide rule.
4. The valve shall have connections with external threads to ISO 228-1 and size
DN 15.
5. Combi valve selection:
Ideally, Combi valves should be selected such that they operate at about 80%
of their maximum flow, enabling them to deliver spare capacity, if required.
VPP46.15L0.6 (externally threaded connections, no pressure test points P/T,
nominal volumetric flow 600 l/h)
6. Determine dial setting using volumetric flow/dial presetting table below:
Volumetric flow 270 l/h
Dial setting 1.8

7 / 18

Siemens Combi valves, PN 25 CE1N4855en


Smart Infrastructure 2020-05-29
Volumetric flow/dial Tables to determine the dial setting for a desired volumetric flow.
presetting
Dp min [kPa] based on volumetric flow; interpolate missing values.
Presetting range linear to VDI/VDE 2173
Presetting range linear
Presetting range not permitted

VPP46.10L0.2, VPP46.10L0.2Q, VPP46.15L0.2, VPP46.15L0.2Q, VPI46.15L0.2, VPI46.15L0.2Q 200 l/h nominal


v̇ [l/h] 30 35 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
Dial Min. 0.2 0.4 0.5 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 Max.
Δpmin [kPa] 14.3 14.3 14.3 14.5 14.6 14.6 14.7 14.8 14.9 15 15.1 15.2 15.3 15.4 15.5 15.5 15.6 15.7 15.8

VPP46.10L0.4, VPP46.10L0.4Q with STA.. 330 l/h nominal


v̇ [l/h] 59 75 91 107 123 140 161 172 188 203 220 236 252 268 284 301 317 333
Dial Min. 0.2 0.4 0.5 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 Max.
Δpmin [kPa] 14.6 14.7 14.8 15 15.1 15.3 15.5 15.6 15.7 15.8 16 16.1 16.2 16.4 16.5 16.6 16.8 16.9

VPP46.10L0.4, VPP46.10L0.4Q 370 l/h nominal


v̇ [l/h] 65 83 101 119 137 155 179 191 209 226 244 262 280 298 316 334 352 370
Dial Min. 0.2 0.4 0.5 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 Max.
Δpmin [kPa] 14.6 14.8 14.9 15.1 15.3 15.4 15.6 15.7 15.9 16 16.2 16.3 16.5 16.6 16.7 16.9 17 17.2

VPP46.15L0.6, VPP46.15L0.6Q, VPI46.15L0.6, VPI46.15L0.6Q 600 l/h nominal


v̇ [l/h] 100 115 130 160 180 210 240 270 300 320 350 380 410 440 460 490 520 550 575
Dial Min. 0,2 0,4 0,5 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 Max.
Δpmin [kPa] 14.9 15.2 15.5 15.6 15.9 16.1 16.4 16.6 16.8 17 17.2 17.5 17.6 17.8 18 18.2 18.4 18.6 18.9

VPP46.20F1.4, VPP46.20F1.4 Q with STA.., VPI46.20F1.4, VPI46.20F1.4Q with STA.. 1200 l/h nominal
v̇ [ l/h] 200 260 310 380 430 490 550 610 660 730 780 840 900 960 1010 1070 1130 1190
Dial Min. 0.2 0.4 0.5 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 Max.
Δpmin [kPa] 16 16.5 17 17.5 17.9 18.4 18.8 19.2 19.5 19.9 20.2 20.4 20.7 20.9 21.1 21.3 21.4 21.6

VPP46.20F1.4, VPP46.20F1.4Q, VPI46.20F1.4, VPI46.20F1.4Q 1400 l/h nominal


v̇ [ l/h] 220 290 350 420 480 550 610 680 740 810 870 940 1000 1070 1130 1200 1260 1330
Dial Min. 0.2 0.4 0.5 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 Max.
Δpmin [kPa] 16 16.5 17 17.5 17.9 18.4 18.8 19.2 19.5 19.9 20.2 20.4 20.7 20.9 21.1 21.3 21.4 21.6

VPP46.25F1.8, VPP46.25F1.8Q, VPI46.25F1.8, VPI46.25F1.8Q with STA.. 1530 l/h nominal


v̇ [ l/h] 238 303 366 427 488 550 614 680 749 822 898 978 1063 1150 1241 1335 1432 1530
Dial Min. 0.2 0.4 0.5 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 Max.
Δpmin [kPa] 15.3 15.8 16.1 16.4 16.7 17 17.5 18 18.7 19.7 20.9 22.3 24.2 26.4 28.9 32.0 35.4 39.4

VPP46.25F1.8, VPP46.25F1.8Q, VPI46.25F1.8, VPI46.25F1.8Q 1800 l/h nominal


v̇ [ l/h] 280 356 430 502 574 647 722 800 881 967 1057 1151 1250 1353 1460 1571 1685 1800
Dial Min. 0.2 0.4 0.5 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 Max.
Δpmin [kPa] 15.3 15.8 16.1 16.4 16.7 17 17.5 18 18.7 19.7 20.9 22.3 24.2 26.4 28.9 32.0 35.4 39.4

VPP46.32F4, VPP46.32F4Q, VPI46.32F4, VPI46.32F4Q with STA.. 3400 l/h nominal


v̇ [ l/h] 468 680 770 940 1120 1290 1460 1640 1810 1980 2150 2330 2500 2670 2850 3020 3190 3400
Dial Min. 0.2 0.4 0.5 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 Max.
Δpmin [kPa] 17.9 18 18.1 18.2 18.3 18.5 18.7 18.9 19.2 19.6 20.1 20.7 21.4 22.3 23.4 24.6 26 28

VPP46.32F4, VPP46.32F4Q, VPI46.32F4, VPI46.32F4Q 4000 l/h nominal


v̇ [ l/h] 550 800 910 1110 1320 1520 1720 1930 2130 2330 2530 2740 2940 3140 3350 3550 3750 4001
Dial Min. 0.2 0.4 0.5 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 Max.
Δpmin [kPa] 17.9 18 18.1 18.2 18.3 18.5 18.7 18.9 19.2 19.6 20.1 20.7 21.4 22.3 23.4 24.6 26 28

VPI46.40F9.5Q 9500 l/h nominal


v̇ [ l/h] 1370 1600 1950 2250 2650 3000 3400 3800 4250 4750 5250 5800 6350 6950 7550 8200 8800 9500
Dial Min. 0.2 0.4 0.5 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 Max.
Δpmin [kPa] 10 10 10 10 10 10 10 11 11 12 13 15 16 18 20 22 24 25

VPI46.50F12Q 11500 l/h nominal


v̇ [ l/h] 1400 1650 2000 2350 2700 3150 3550 4050 4600 5150 5800 6500 7300 8150 9000 9800 10600 11500
Dial Min. 0.2 0.4 0.5 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 Max.
Δpmin [kPa] 10 10 11 11 11 12 12 13 14 15 17 19 21 24 27 30 33 36

8 / 18
Siemens Combi valves, PN 25 CE1N4855en
Smart Infrastructure 2020-05-29
Engineering notes

Valve Symbols / Direction of flow Flow in control mode Valve stem


VP..46.. VP..46..Q retracts extends

Combi valve VPP46.. variable closes opens

Combi valve VPI46.. variable closes opens

The direction of flow indicated (arrow on the valve body) is mandatory!


The valves should preferably be mounted in the return pipe where temperatures
are lower and where the sealing gland is less affected by strain.
Symbols Symbol used in catalogs and application descriptions Symbol used in diagrams

There are no standard symbols


for Combi valves in diagrams.

Recommendation A strainer or dirt trap should be fitted upstream of the valve to enhance reliability.
Remove dirt, welding beads etc. from valves and pipes.
Do not insulate the actuator bracket, as air circulation must be ensured!

Mounting notes Combi valve and actuator can be straightforwardly assembled on site. Special tools
or adjustments are not required.
Prior to mounting the actuator, the required volumetric flow must be set.
The valve is supplied complete with Mounting Instructions (74 319 0649 0 b).

Mounting positions

Thermal actuators STA.., STP.. may be installed in any position.


Actuators SSA.., SAY.. must be installed horizontally up to 90° and not hanging.

AL60 supporting ring The AL60 supporting ring must be put into position before mounting the actuator
SUA21/3 onto the valve.

9 / 18

Siemens Combi valves, PN 25 CE1N4855en


Smart Infrastructure 2020-05-29
Installation notes

Prior to mounting the actuator, the presetting is to be made as follows:


Presetting DN 10…32:
1. Remove control knob from 2. Loosen knurled nut. 3. Adjust the desired dial set- 4. Retighten knurled nut by
Combi valve. ting with the white knob. hand.

Presetting DN 40…50:
1. Loosen spindle head 2. Adjust the desired dial set- 3. Retighten spindle head -
ting with the white knob. by hand only

Valve characteristic
Volumetric flow V / V100

VP..46.., VP..46..Q

stroke H / H100

Commissioning notes

The valves must be commissioned with the manual control knob or actuator
correctly fitted. Strong pressure impacts can damage closed Combi valves.

The Combi valves have to be open when flushing or pressure testing the sys-
tem. Flush only in correct flow direction. Strong pressure impacts can dam-
age closed Combi valves.

Differential pressure Δpmax across the valve’s control path is not allowed to
exceed 600 kPa.

10 / 18
Siemens Combi valves, PN 25 CE1N4855en
Smart Infrastructure 2020-05-29
Manual control When turning the manual control knob in counter-clockwise direction or manually
operating the actuator, the valve opens. The actuator closes the valve. The valves
are supplied fully open. The manual knob is not designed for permanent manual
operation.

Maintenance notes

The V..P46.. PICV valves are maintenance-free without cartridge.


Valve plug, stem, presetting, diaphragm etc. may not be disassembled
When performing service work on the valve and / or actuator:
· Switch off the pump and disconnect power supply.
· Close the shut-off valves in the piping network.
· Fully reduce pressure in the piping network and allow the pipes to cool down
completely.

Remove the electrical connections only if necessary.

Sealing gland The stem sealing gland cannot be exchanged. Should leakage occur, the whole
valve must be replaced.

Disposal Do not dispose of the device as household waste.


Warning
Due to the tensioned spring return, valve disassembly may result in flying parts
causing possible injury.

Only authorized staff may disassemble valves with tensioned spring return!

Disposal
· Special handling of individual components may be mandated by law or
make ecological sense.
· Observe all local and currently applicable laws and regulations.

Warranty

Application-related technical data are guaranteed only when the valves are used in
connection with the Siemens actuators listed under "Equipment combinations" on
page 3. When used with actuators of other manufacture, any warranty by Siemens
becomes void.

Technical data

Functional data PN class PN 25 as per EN 1333


Permissible operating pressure 2.500 kPa (25 bar) as per ISO 7628 / EN 1333
Max. differential pressure 600 kPa
Min. differential pressure See tables volumetric flow/dial presetting

Valve characteristic Linear as per VDI/VDE 2173


Leakage rate in general Class IV (0…0.01% of volumetric flow V100) to
EN 1349
DN 25…32 with STA..3.. Class III (0…0,1% of volumetric flow V100) per
EN 1349
Average flow accuracy +/-10% from ΔPmin - to 2.5 x ΔPmin
+/- 5% from 2.5 x ΔPmin – to 600kPa

11 / 18

Siemens Combi valves, PN 25 CE1N4855en


Smart Infrastructure 2020-05-29
Permissible media Low-temperature hot water, chilled water, water
with antifreeze
Recommendation: Water treatment to VDI 2035
Medium temperature:
Valve with actuator 1...120 °C
1…110°C with SUA21/33), SUA21/3P, SUE21P
Permissible ambient temperature 1…50 °C
Nominal stroke DN 10L0.2
DN 15L0.2 2.5 mm
DN 15L0.6
DN 10L0.4 / DN 20 5 mm
DN 25…32 5.5 mm
DN 40…50 15 mm
Materials Valve body, port, seat, sealing gland Dezincification resistant hot-pressed brass
and test points (DZR), CW602N
Valve body DN 40…50 Nodular cast iron
Stem, spring Stainless steel
Presetting element PTFE, PPO, POM C and ABS
Regulator PPS
Seals EPDM 281 (O-ring)
Dimensions / weight Dimensions Refer to "Dimensions" on page 14
Threaded connections VPP46.. G to ISO 228-1 (externally threaded)
VPI46.. Rp to ISO 7-1 (internally threaded)
Actuator connection DN 10…32 M30 x 1.5 mm
DN 40…50 Siemens large stroke connector
Pressure test points (P/T-ports) G ¼” (connection valve body)
2 mm x 40 mm (needles)
Weight Refer to "Dimensions" on page 14
Standards, directives and ap- Pressure Equipment Directive PED 2014/68/EU
provals Pressure-carrying accessories Scope: Article 1, section 1
Definitions: Article 2, section 5
Fluid group 2 Without CE-marking as per article 4, section 3
DN 10…40
(sound engineering practice) 1)
Category I, Modul A, with CE-marking
DN 50
as per article 14, section 2
EU conformity (CE) DN 50 A5W00022837, CE1T4855xx 2)
EAC conformity Eurasia conformity
Environmental compatibility The product environmental declaration CE1E4855en 2) contains data on environmen-
tally compatible product design and assessments (RoHS compliance, materials com-
position, packaging, environmental benefit, disposal).

1) Valves where PS x DN < 1000, do not require special testing and cannot carry the CE label.
2) Documents are available at http://www.siemens.com/bt/download
3)
Only with mounting AL60 accessory, the SUA21/3 can drive the VPI46.. or VPP46..valve

12 / 18
Siemens Combi valves, PN 25 CE1N4855en
Smart Infrastructure 2020-05-29
Application examples

Combi valves in HVAC systems combined with variable speed pumps provide even
higher energy efficiency. When sizing the pump, it must be made certain that the
most critical branch or consumer in the system – usually the remotest from the
pump – gets enough pressure (pump head). Thus, it is recommended to use a vari-
able speed pump in constant-pressure mode with end-point feedback, to maintain
a minimum differential pressure across the critical valve.

Residential buildings Residential buildings with for example self-contained flat heating systems:

E = Floor
G = Group or zone

Non-residential Commercial buildings with for example Fan Coil Units or heat exchangers for heat-
buildings ing or cooling:

13 / 18

Siemens Combi valves, PN 25 CE1N4855en


Smart Infrastructure 2020-05-29
Dimensions

VPP46.. VPP46..Q

Valves DN G L1 L3 L4 H2 H3 H 1) Weight
SSA.. STA..3..
STP..3..
[inch] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [kg]
VPP46.10L0.2
10 ½ 10.5 68.5 83.5 0.314
VPP46.10L0.4
65
VPP46.15L0.2
15 ¾ 13.2 38 67.3 82.2 170 160 0.333
VPP46.15L0.6
VPP46.20F1.4 20 1 70 13.6 67.5 82.5 0.371
VPP46.25F1.8 25 1¼ 78 22 70 85 0.497
VPP46.32F4 32 1½ 104 26 63 85 100 185 175 1.22
VPP46.10L0.2Q 0.402
10 ½ 54.8 68.5 83.5
VPP46.10L0.4Q 0.302
65
VPP46.15L0.2Q
15 ¾ 55.5 38 67.3 82.2 170 160 0.422
VPP46.15L0.6Q
VPP46.20F1.4Q 20 1 70 57.3 67.5 82.5 0.459
VPP46.25F1.8Q 25 1¼ 78 59 70 85 0.59
VPP46.32F4Q 32 1½ 104 68 63 85 100 185 175 1.317
1)
Total height including actuator

Sets of threaded fittings with flat


4847Z09

seal
G

ALG132
R

ALG…2: set of 2 threaded fittings ALG142 pipe side with external R threads

T
L
4847Z10

ALG152
ALG152B
Rp

ALG202
ALG202B pipe side with internal Rp threads
ALG252
ALG252B T
L

14 / 18
Siemens Combi valves, PN 25 CE1N4855en
Smart Infrastructure 2020-05-29
Type ALG.. for valve type DN G R Rp L T

Malleable cast iron Brass 1) [Inch] [Inch] [Inch] [mm] [mm]

ALG132 VPP46.10.. 10 G½ R⅜ » 24 »9

ALG142 VPP46.15.. 15 G¾ R½ » 29.5 » 12

ALG152 ALG152B VPP46.20.. 20 G1 Rp ½ » 23 » 13

ALG202 ALG202B VPP46.25.. 25 G 1¼ Rp ¾

ALG252 ALG252B VPP46.32.. 32 G 1½ Rp 1


1)
Maximum medium temperature 100 °C
· On valve side: cylindrical thread to ISO 228-1, on pipe side: with cylindrical thread to ISO 7-1

VPI46.. VPI46..Q

Valves DN Rp S L1 L3 L4 H2 H3 H 1) Weight
SSA.. STA..3.. SAY..
STP..3..
[inch] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [kg]
VPI46.15L0.2
15 ½ 27 75 15.2 67.3 82.4 0.377
VPI46.15L0.6
38 170 160
VPI46.20F1.4 20 ¾ 32 79 17.9 67.5 82.5 0.418
VPI46.25F1.8 25 1 39 83 22 70 85 0.533
VPI46.32F4 32 1¼ 46 104 26 63 85 100 185 175 1.219
-
VPI46.15L0.2Q
15 ½ 27 75 60.2 67.3 82.4 0.477
VPI46.15L0.6Q
38 170 160
VPI46.20F1.4Q 20 ¾ 32 79 62.9 67.5 82.5 0.506
VPI46.25F1.8Q 25 1 39 83 59 70 85 0.625
VPI46.32F4Q 32 1¼ 46 104 68 63 85 100 185 175 1.316
VPI46.40F9.5Q 40 1½ 56 71 3.253
138 90 161 - - - 500
VPI46.50F12Q 50 2 70 77 3.683
1)
Total height including actuator

15 / 18

Siemens Combi valves, PN 25 CE1N4855en


Smart Infrastructure 2020-05-29
Revision Numbers

Product number Valid from rev. no. Product number Valid from rev. no.
VPP46.10L0.2 ..A VPP46.10L0.2Q ..A
VPP46.10L0.4 ..B VPP46.10L0.4Q ..B
VPP46.15L0.2 ..A VPP46.15L0.2Q ..A
VPP46.15L0.6 ..A VPP46.15L0.6Q ..A
VPP46.20F1.4 ..A VPP46.20F1.4Q ..A
VPP46.25F1.8 ..A VPP46.25F1.8Q ..A
VPP46.32F4 ..A VPP46.32F4Q ..A
VPI46.15L0.2 ..A VPI46.15L0.2Q ..A
VPI46.15L0.6 ..A VPI46.15L0.6Q ..A
VPI46.20F1.4 ..A VPI46.20F1.4Q ..A
VPI46.25F1.8 ..A VPI46.25F1.8Q ..A
VPI46.32F4 ..A VPI46.32F4Q ..A
VPI46.40F9.5Q ..A
VPI46.50F12Q ..A

16 / 18
Siemens Combi valves, PN 25 CE1N4855en
Smart Infrastructure 2020-05-29
Documentation form

Installed loca- Valve type Actuator Type Valve Size Planned Pre- Required Verified ∆p Flow1 (l/h)
tion setting ∆pmin (kPa) (kPa)

1)
Flow = if Verified ∆pmin > Required ∆pmin, then Flow is as per presetting in datasheet, otherwise check.

17 / 18

Siemens Combi valves, PN 25 CE1N4855en


Smart Infrastructure 2020-05-29
Issued by
Siemens Switzerland Ltd
Smart Infrastructure
International Headquarters
Theilerstrasse 1a
6300 Zug
Switzerland
Tel. +41 58-724 24 24 © Siemens Switzerland Ltd, 2019
www.siemens.com/buildingtechnologies Technical specifications and availability subject to change without notice.

18 / 18
Siemens Combi valves, PN 25 CE1N4855en
Smart Infrastructure 2020-05-29
x

1. Installation shall be done as per NFPA and QCDD requirements.


2. Third party certificates shall be provided upon material delivery.
3. Only GI fittings shall be used for fire fighting application.

Fadi Kaakour 24.11.2020


x

1. Steel Pipe fittings made by BIS, Thailand are approved subject to compliance to the below.
2. Contractor shall clearly state the area of application.
3. In case, pipe fittings will be used for fire fighting, the same shall be made of galvanized
steel.

Fadi Kaakour 20/10/2020


Material Transmittal
Project Name: Adidas Showroom Renovation Work Project No: IDJ-034
Owner: Adidas Qatar Submittal No.: ID-AD-LM-MS-MECH-002

Date: 25/11/2020

Submitted by: Eng. Damathi New Submittal:

Contractor's Representative Signature Resubmittal: Rev. 01

Description: Fire Hose Reel Drawing Ref.:


Specification Ref.:
Bill of Quantities Ref.:
Other Ref.:
Attachment:
Literature/Catalogue Test Certificates Samples

Discipline Involved: Architectural Structural Mechanical Electrical Interior Design Others:

Manufacturer/Supplier
From Approved Vendor List Equivalent or Approved

Name of Manufacturer/Supplier: SRI - Malaysia

Address: Local Agent: Fire-link

Agent Tel. No.: Fax No.:

Delivery Country of Origin: Malaysia

Availability Mode of Transportation


Locally Manufactured: Overland:
Overseas: Air Freight:
Sea Freight:
Manufacturer Programme
Production Period: Latest Date of Orders:
Delivery Ex Works: Date Material Required:
Total Delivery Time: Expected Date on Site:

Approved: Revise & Resubmit: Additional Info. Required:


Approved as noted: x Rejected: Others:

Comments:

1. Hose reel shall be mounted on a swinging arm with internal waterway capable of swinging 180
deg.
2. Contractor must verify the need of installation of a pressure regulating angle valve.
3. Installation shall be done as per NFPA & QCDD requirements.

Consultant: Fadi Kaakour 26.11.2020


Printed Name Signature Date

Owner - Engineering Department Comments (if applicable):

Signed by:
Printed Name Signature Date
Received by Contractor:

Printed
Form Ref. No.: PRJ/F5/V3 Date of Issue: March 2014 Version: V3Name Signature Date Page 1 of 1
LEADING THE FIGHT
HOSE REEL CABINET AGAINST FIRE

Model A - Double Compartment Hose Reel Cabinet

TECHNICAL SPECIFICATION

♦ Overall Dimension : 740 mm f:N) x 1540 mm (H) x A (D)


♦ Material : Mild Steel
♦ Thickness : 1.2mm
♦ Installation : Surface/Wall Mounted, Recessed
♦ Capacity : Manual or Automatic Swing Hose Reel ¾" or 1", & 2 pcs
Fire Extinguisher
♦ Paint Finish : Epoxy Powder Red/White, minimum 70 micron

Code No. Dimension A (Depth) Type

HRS007-MS-400-RD 400mm Surface/Wall Mounted

HRS007-MS-320-RD 320mm Surface/Wall Mounted

HRS007-MS-250-RD 250mm Surface/Wall Mounted

HRS00B-MS-400-RD 400mm Recessed

HRS00B-MS-320-RD 320mm Recessed

HRS00B-MS-250-RD 250mm Recessed

HRS00B-MS-400-SS* 400mm Recessed

HRS00B-MS-320-SS* 320mm Recessed

HRS00B-MS-250-SS* 250mm Recessed

* Door and architrave in Stainless Steel

Model B - Double Compartment Pivot Type Hose Reel Cabinet

TECHNICAL SPECIFICATION

♦ Overall Dimension : 740 mm f:N) x 1540 mm (H) x A (D)


♦ Material : Mild Steel
♦ Thickness : 1.5 mm (Door), 1.2 mm (Body)
♦ Installation : Surface/Wall Mounted, Recessed
♦ Capacity : Manual or Automatic Fixed Type Hose Reel ¾" or 1", &
2 pcs Fire Extinguisher
♦ Paint Finish : Epoxy Powder Red/White, minimum 70 micron

Code No. Dimension A (Depth) Type

Surface/Wall Mounted
HRS002-MS-420-WH 420mm
(19" Drum)
Surface/Wall Mounted
HRS002-MS-450-WH 450mm
(22" Drum)

HRS005-MS-420-WH 420mm Recessed (19" Drum)

HRS005-MS-450-WH 450mm Recessed (22" Drum)


‫ﺗﺎﺭﻳﺦ ﺍﻟﻄﺒﺎﻋﺔ ‪2019-05-13 :‬‬ ‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴــــﺔ‬
‫ﻭﻗـﺖ ﺍﻟﻄﺒﺎﻋﺔ ‪ :‬ص ‪10:21‬‬ ‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﻪ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬
‫ﺭﻗــﻢ ﺍﻟﻄﻠـﺐ ‪PAC19004545 :‬‬ ‫ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺷﻬــــــﺎﺩﺓ ﻋﺪﻡ ﻣﻤﺎﻧﻌﺔ‬


‫ﺍﻋﺘﻤﺎﺩ ﻣﻨﺘﺞ‬ ‫ﻧﻮﻉ ﺍﻟﺸﻬﺎﺩﺓ ‪:‬‬

‫ﺑﻴﺎﻧﺎﺕ ﺍﻟﻤﻨﺸﺄﺓ‬

‫ﺷﺮﻛﻪ ﻓﺎﻳﺮ ﻟﻨﻚ‬ ‫ﺍﻻﺳﻢ ﺍﻟﺘﺠﺎﺭﻱ‪:‬‬


‫‪5571‬‬ ‫ﺭﻗﻢ ﺍﻟﺮﺧﺼﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ‪:‬‬ ‫‪97909‬‬ ‫ﺭﻗﻢ ﺍﻟﺴﺠﻞ ﺍﻟﺘﺠﺎﺭﻱ‪:‬‬
‫ﺭﻗﻢ ﺍﻟﻬﺎﺗﻒ‪:‬‬ ‫‪10-6614-03‬‬ ‫ﺭﻗﻢ ﻗﻴﺪ ﺍﻟﻤﻨﺸﺄﺓ‪:‬‬
‫ﺍﻟﺒﺮﻳﺪ ﺍﻹﻟﻜﺘﺮﻭﻧﻲ‪:‬‬
‫‪Fire Fighting systems‬‬ ‫ﺍﻟﺘﺼﻨﻴﻒ ‪:‬‬
‫‪(Reels/, Cabinets & Nozzles) Fire Hose‬‬ ‫ﺇﺳﻢ ﺍﻟﻤﻨﺘﺞ ‪:‬‬

‫ﺗﻔﺎﺻﻴﻞ ﺍﻟﺸﻬﺎﺩﺓ‬

‫‪.‬ﺗﻢ ﻣﺮﺍﺟﻌﺔ ﺍﻟﻄﻠﺐ ﺍﻟﻤﻘﺪﻡ ﻭﺍﺗﻀﺢ ﺑﺄﻧﻪ ﻻ ﻣﺎﻧﻊ ﻣﻦ ﺍﻋﺘﻤﺎﺩ ﺍﻟﻤﻨﺘﺞ ‪/‬ﺍﻟﻤﻨﺘﺠﺎﺕ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻰ ﺍﻟﻤﺮﻓﻖ ﺑﻨﺎﺀ ﻋﻠﻰ ﺍﻋﺘﻤﺎﺩﻩ ﻣﻦ‬
‫ﻗﺒﻞ ﺍﻟﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﺭ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ‬

‫ﻣﻼﺣﻈﺎﺕ ‪:‬‬

‫‪ .1‬ﻳﺠﺐ ﻋﻠﻰ ﺍﻟﺸﺮﻛﻪ ﺍﻻﻟﺘﺰﺍﻡ ﻭﺍﻟﻌﻤﻞ ﺑﻤﺎ ﺟﺎﺀ ﻓﻲ ﺍﺷﺘﺮﺍﻃﺎﺕ ﻗﺴﻢ ﺃﻧﻈﻤﺔ ﺍﻟﺴﻼﻣﻪ ﺍﻟﺘﻲ ﺗﻢ ﺍﻻﻃﻼﻉ ﻭﺍﻟﻤﻮﺍﻓﻘﺔ ﻋﻠﻴﻬﺎ ﻣﻦ ﺧﻼﻝ ﺍﻟﻤﻮﻗﻊ ‪.‬‬
‫‪ .2‬ﻳﺠﺐ ﺍﻥ ﻳﻘﻮﻡ ﺑﺘﺮﻛﻴﺐ ﻫﺬﺍ ﺍﻟﻤﻨﺘﺞ ﻣﻦ ﻗﺒﻞ ﻣﻬﻨﺪﺳﻴﻦ ﻭﻓﻨﻴﻴﻦ ﻣﻌﺘﻤﺪﻳﻦ ﻣﻦ ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‪.‬‬
‫‪ .3‬ﻳﺠﺐ ﺍﻥ ﻳﺤﻤﻞ ﺍﻟﻤﻨﺘﺞ ﺍﻟﻌﻼﻣﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ ﻟﻠﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻌﺘﻤﺪﺓ ﻭﺍﻟﻤﻮﺿﺤﻪ ﻓﻲ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ ‪.‬‬

‫‪12/05/2021‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻹﻧﺘﻬﺎﺀ ‪:‬‬ ‫‪13/05/2019‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻻﻋﺘﻤﺎﺩ ‪:‬‬

‫ﻉ‪/‬‬

‫ﻣﺪﻳﺮ ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗـﺎﻳـــــﺔ‬


‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬

‫‪Page 1 of 2‬‬
‫ﺑﺴﻢ ﺍﻟﻠﻪ ﺍﻟﺮﺣﻤﻦ ﺍﻟﺮﺣﻴﻢ‬

DATE : 2019-05-13 : ‫ﺍﻟﺘﺎﺭﻳـــــــﺦ‬ ‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬


PERMIT PAC19004545 : ‫ﺭﻗﻢ ﺍﻟﻄﻠﺐ‬ ‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬
‫ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

TECHNICAL REPORT ‫ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ‬

PRODUCT : (Reels/, Cabinets & Nozzles) Fire Hose : ‫ﺍﻟﻤﻨﺘﺞ‬


PRODUCT APPLICATION : Fire Fighting systems : ‫ﺗﺼﻨﻴﻒ ﺍﻟﻤﻌﺪﺓ‬
APPLICANT / P.O .Box ‫ﺷﺮﻛﻪ ﻓﺎﻳﺮ ﻟﻨﻚ‬ : ‫ﻣﻘﺪﻡ ﺍﻟﻄﻠﺐ‬
MANUFACTURER /
STEEL RECON INDUSTRIES SDN BHD / MALAYSIA :‫ ﺑﻠﺪ ﺍﻟﺼﻨﻊ‬/ ‫ﺍﻟﺸﺮﻛﺔ ﺍﻟﻤﺼﻨﻌﺔ‬
LOCATION :

‫ﺍﻟﻮﺻﻒ‬ ‫ﺍﻟﻤﻮﺩﻳﻞ‬
.
Fire Hose Reel; 25 mm Manually Operated Fixed Type HRS031-SS-022-RD
.
.
Fire Hose Reel; 25 mm Automatically Operated Fixed Type HRS027-SS-022-RD
.
.
Fire Hose Reel; 25 mm Manually Operated Swinging Type HRS033-SS-022-RD
.
.
Fire Hose Reel; 25 mm Automatically Operated Swinging Type HRS029-SS-022-RD
.

3RD PARTY ‫ﺷﻬﺎﺩﺓ ﺍﻟﻤﺨﺘﺒﺮﺍﺕ ﺍﻟﻤﺴﺎﻧﺪﺓ‬


CERTIFICATE / - KM 51857 - BSI/KITEMAR
APPROVAL : K : ( ‫)ﻣﻦ ﻫﻴﺌﺎﺕ ﻣﻌﺘﻤﺪﺓ‬

RECOMMENDATIONS ‫ﺍﻟﺘﻮﺻﻴﺎﺕ‬

STANDARD: BS EN 671

/‫ﻉ‬

‫ﻣﺪﻳﺮ ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗـﺎﻳـــــﺔ‬


‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬

Page 2 of 2
x

1. Fire hose reels shall be UL/FM approved.


2. The proposed material is not in MZP vendor list, contractor to submit an alternative.
3. Hose reel shall be mounted on a swinging arm with internal waterway capable of swinging 180
deg.
4. All third party certificates shall be provided.
5. Contractor must verify the need of installation of a pressure regulating angle valve.

Fadi Kaakour 18.11.2020


Q/JT 350 KX06-172-118-00D系列 Rev:A0

Fire Hose Reel Cabinets


Wall-mounted Type

Type H(mm) W(mm) D(mm)


SPECIFICATION
Single 720 720 280
1mm cold rolled steel DC01(RAL3000
Double 1500 720 280
polyester epoxy Powder coating Magic plus
Automatic coating line)
Manufacture by CNC punching machine
Fire hose reel EN 671-1 approved
The doors is opened ≥170°
6kg or 9kg Dry powder fire extinguisher
5kg Co2 fire extinguisher EN 3 approved
Option fire hose rack 2.5” x 30 M & Landing valve

Ningbo Kaixuan Fire Control Equipment Co.,Ltd.

Add: NO.999 Zhonghe Road,Huangjiabu Town,Yuyao City,Zhejiang Province,China.315466


Tel: 0086-574-62025710 Fax: 0086-574-62025711
E-mail: info@kaixuanfire.com
Q/JT 350 KX06-173-00-2017 Rev:A0

Fire Hose Reels

Size Type H(mm) W(mm) D(mm) Inlet Outlet


19mm×30M Fixed & Manual 710 220 580 1”BSP D6
25mm×30M Fixed & Manual 710 240 580 1”BSP D8
19mm×30M Swivelling & Manual 625 220 580 1”BSP D6
25mm×30M Swivelling & Manual 625 240 580 1”BSP D8
19mm×30M Swivelling & Automatic 625 220 580 1”BSP D6
25mm×30M Swivelling & Automatic 625 240 580 1”BSP D8

SPECIFICATION
Hose reel test and certificate complying with EN671-1
Certificate No: C1153a (approve by LPCB)
0832-CPR-S0032 (approve by BRE Global)
The wheels & drum 1mm cold rolled steel or stainless steel
RAL3000 polyester epoxy Powder coating,Thickness ≥80µm
Unwind the hose without hose guide force≤70N
Brass gooseneck and connection
30m Red or black fire hose to EN694 approve
Rotary operated nozzle shut / conical spray / jet
Brass nozzle and plastic cover,Spray angle≥45°
Effective throw range jet≥10m,conical spray≥3m
Max working pressure 12bar,Test pressure 18bar

Ningbo Jintian Fire Fighting Industrial Co.,Ltd


Add: Wucheyan,Yuyao city,Zhejiang province,CHINA
Tel: 0086-574-62025710 Fax: 0086-574-62025711
E-mail: info@kaixuanfire.com Http://www.jintianfire.com
‫ﺗﺎﺭﻳﺦ ﺍﻟﻄﺒﺎﻋﺔ ‪2019-07-16 :‬‬ ‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴــــﺔ‬
‫ﻭﻗـﺖ ﺍﻟﻄﺒﺎﻋﺔ ‪ :‬ص ‪8:05‬‬ ‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﻪ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬
‫ﺭﻗــﻢ ﺍﻟﻄﻠـﺐ ‪PAC19008156 :‬‬ ‫ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺷﻬــــــﺎﺩﺓ ﻋﺪﻡ ﻣﻤﺎﻧﻌﺔ‬


‫ﺍﻋﺘﻤﺎﺩ ﻣﻨﺘﺞ‬ ‫ﻧﻮﻉ ﺍﻟﺸﻬﺎﺩﺓ ‪:‬‬

‫ﺑﻴﺎﻧﺎﺕ ﺍﻟﻤﻨﺸﺄﺓ‬

‫ﻓﻴﺠﻴﻼﻧﺖ ﺗﺮﻳﺪﻳﻨﻎ ﺍﻧﺪ ﻛﻮﻧﺘﺮﺍﻛﺘﻴﻨﻎ‬ ‫ﺍﻻﺳﻢ ﺍﻟﺘﺠﺎﺭﻱ‪:‬‬


‫‪97759‬‬ ‫ﺭﻗﻢ ﺍﻟﺮﺧﺼﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ‪:‬‬ ‫‪63209‬‬ ‫ﺭﻗﻢ ﺍﻟﺴﺠﻞ ﺍﻟﺘﺠﺎﺭﻱ‪:‬‬
‫ﺭﻗﻢ ﺍﻟﻬﺎﺗﻒ‪:‬‬ ‫‪14-5378-00‬‬ ‫ﺭﻗﻢ ﻗﻴﺪ ﺍﻟﻤﻨﺸﺄﺓ‪:‬‬
‫ﺍﻟﺒﺮﻳﺪ ﺍﻹﻟﻜﺘﺮﻭﻧﻲ‪:‬‬
‫‪Fire Fighting systems‬‬ ‫ﺍﻟﺘﺼﻨﻴﻒ ‪:‬‬
‫‪Fire Department Connection and Stanpipe System / Hose, Coupling and Nozzles /‬‬ ‫ﺇﺳﻢ ﺍﻟﻤﻨﺘﺞ ‪:‬‬
‫‪Cabinet‬‬
‫ﺗﻔﺎﺻﻴﻞ ﺍﻟﺸﻬﺎﺩﺓ‬

‫‪.‬ﺗﻢ ﻣﺮﺍﺟﻌﺔ ﺍﻟﻄﻠﺐ ﺍﻟﻤﻘﺪﻡ ﻭﺍﺗﻀﺢ ﺑﺄﻧﻪ ﻻ ﻣﺎﻧﻊ ﻣﻦ ﺍﻋﺘﻤﺎﺩ ﺍﻟﻤﻨﺘﺞ ‪/‬ﺍﻟﻤﻨﺘﺠﺎﺕ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻰ ﺍﻟﻤﺮﻓﻖ ﺑﻨﺎﺀ ﻋﻠﻰ ﺍﻋﺘﻤﺎﺩﻩ ﻣﻦ‬
‫ﻗﺒﻞ ﺍﻟﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﺭ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ‬

‫ﻣﻼﺣﻈﺎﺕ ‪:‬‬

‫‪ .1‬ﻳﺠﺐ ﻋﻠﻰ ﺍﻟﺸﺮﻛﻪ ﺍﻻﻟﺘﺰﺍﻡ ﻭﺍﻟﻌﻤﻞ ﺑﻤﺎ ﺟﺎﺀ ﻓﻲ ﺍﺷﺘﺮﺍﻃﺎﺕ ﻗﺴﻢ ﺃﻧﻈﻤﺔ ﺍﻟﺴﻼﻣﻪ ﺍﻟﺘﻲ ﺗﻢ ﺍﻻﻃﻼﻉ ﻭﺍﻟﻤﻮﺍﻓﻘﺔ ﻋﻠﻴﻬﺎ ﻣﻦ ﺧﻼﻝ ﺍﻟﻤﻮﻗﻊ ‪.‬‬
‫‪ .2‬ﻳﺠﺐ ﺍﻥ ﻳﻘﻮﻡ ﺑﺘﺮﻛﻴﺐ ﻫﺬﺍ ﺍﻟﻤﻨﺘﺞ ﻣﻦ ﻗﺒﻞ ﻣﻬﻨﺪﺳﻴﻦ ﻭﻓﻨﻴﻴﻦ ﻣﻌﺘﻤﺪﻳﻦ ﻣﻦ ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‪.‬‬
‫‪ .3‬ﻳﺠﺐ ﺍﻥ ﻳﺤﻤﻞ ﺍﻟﻤﻨﺘﺞ ﺍﻟﻌﻼﻣﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ ﻟﻠﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻌﺘﻤﺪﺓ ﻭﺍﻟﻤﻮﺿﺤﻪ ﻓﻲ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ ‪.‬‬

‫‪15/07/2021‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻹﻧﺘﻬﺎﺀ ‪:‬‬ ‫‪16/07/2019‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻻﻋﺘﻤﺎﺩ ‪:‬‬

‫ﻉ‪/‬‬

‫ﻣﺪﻳﺮ ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗـﺎﻳـــــﺔ‬


‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬

‫‪Page 1 of 2‬‬
‫ﺑﺴﻢ ﺍﻟﻠﻪ ﺍﻟﺮﺣﻤﻦ ﺍﻟﺮﺣﻴﻢ‬

DATE : 2019-07-16 : ‫ﺍﻟﺘﺎﺭﻳـــــــﺦ‬ ‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬


PERMIT PAC19008156 : ‫ﺭﻗﻢ ﺍﻟﻄﻠﺐ‬ ‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬
‫ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

TECHNICAL REPORT ‫ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ‬

PRODUCT : Fire Department Connection and Stanpipe System / : ‫ﺍﻟﻤﻨﺘﺞ‬


Hose, Coupling and Nozzles / Cabinet
PRODUCT APPLICATION : Fire Fighting systems : ‫ﺗﺼﻨﻴﻒ ﺍﻟﻤﻌﺪﺓ‬
APPLICANT / P.O .Box ‫ﻓﻴﺠﻴﻼﻧﺖ ﺗﺮﻳﺪﻳﻨﻎ ﺍﻧﺪ ﻛﻮﻧﺘﺮﺍﻛﺘﻴﻨﻎ‬ : ‫ﻣﻘﺪﻡ ﺍﻟﻄﻠﺐ‬
MANUFACTURER /
:‫ ﺑﻠﺪ ﺍﻟﺼﻨﻊ‬/ ‫ﺍﻟﺸﺮﻛﺔ ﺍﻟﻤﺼﻨﻌﺔ‬
NINGBO JINTIAN FIRE FIGHTING INDUSTRIAL CO.
LOCATION : LTD. / CHINA

‫ﺍﻟﻮﺻﻒ‬ ‫ﺍﻟﻤﻮﺩﻳﻞ‬
JINTIAN FIRE Cabinet or Wall Mounted Fire Hose Reels, Automatic, swinging arm, 25 mm
KX06-172-00
hose nominal bore, 30 m hose maximum lenght.
JINTIAN FIRE Cabinet or Wall Mounted Fire Hose Reels, Manual, swinging arm, 25 mm hose
KX06-173B-00
nominal bore, 30 m hose maximum lenght.

3RD PARTY ‫ﺷﻬﺎﺩﺓ ﺍﻟﻤﺨﺘﺒﺮﺍﺕ ﺍﻟﻤﺴﺎﻧﺪﺓ‬


CERTIFICATE / - 1153a - LPCB-BRE
APPROVAL : : ( ‫)ﻣﻦ ﻫﻴﺌﺎﺕ ﻣﻌﺘﻤﺪﺓ‬

RECOMMENDATIONS ‫ﺍﻟﺘﻮﺻﻴﺎﺕ‬
NOTES/STANDARD:

Certificate No 1153Ac to EN 15182-1:2007+A1:2009 and EN 15182-3:2007+A1:2009

This product approval shall comply with the Design, Inspection, Installation, Testing and Maintenance
requirements of NFPA 14 (and/or other related NFPA Codes / Standards), other acceptable International Codes
/ Standards, Local Regulations and/or Manufacturer's Published Instructions subject to the technical review and
approval of the Authority Having Jurisdiction (Qatar Civil Defence).

/‫ﻉ‬

‫ﻣﺪﻳﺮ ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗـﺎﻳـــــﺔ‬


‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬

Page 2 of 2
7 December 2020 BLUE POWER HOUSE ELECTRICAL

 SHOP DRAWING WITH APPROVAL COVER SHEET


FROM CONSULTANT
7 December 2020 BLUE POWER HOUSE ELECTRICAL

 ELECTRICAL & FIRE ALARM SHOP DRAWING


APPROVED FROM CONSULTANT