Product data sheet

Specifications

Circuit breaker, ComPact NSX630N,


50kA/415VAC, MicroLogic 2.3 trip
unit 630A, 4 poles 4d
LV432894

To be discontinued on: 30 June 2023

To be discontinued Important message : This product has been switched to new


ComPacT range and is no longer commercialized. It will continue

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
to be available in H1 2023 only limited to specific projects.

Main
Range ComPact

Product name ComPact NSX

Range of product ComPact NSX400...630

Device short name NSX630N

Product or component type Circuit breaker

Device application Distribution

Number of poles 4P

Protected poles description 4t


3t
3t + N/2

Neutral position Left

[In] rated current 630 A at 40 °C

[Ue] rated operational voltage 690 V AC 50/60 Hz

Network type AC

Network frequency 50/60 Hz

Suitability for isolation Yes conforming to EN/IEC 60947-2

Utilisation category Category A

[Icu] rated ultimate short-circuit 85 kA at 240 V AC 50/60 Hz conforming to UL 508


breaking capacity 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
20 kA at 600 V AC 50/60 Hz conforming to UL 508
50 kA at 480 V AC 50/60 Hz conforming to UL 508
50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2

Performance level N 50 kA 415 V AC

Trip unit name Micrologic 2.3

Trip unit technology Electronic

Trip unit protection functions LSoI

Control type Toggle

Circuit breaker mounting mode Fixed

Mar 28, 2023 1


Complementary
[Ui] rated insulation voltage 800 V AC 50/60 Hz

[Uimp] rated impulse withstand 8 kV


voltage

[Ics] rated service short-circuit 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2

Mechanical durability 15000 cycles

Electrical durability 2000 cycles at 690 V In


6000 cycles at 690 V In/2
4000 cycles at 440 V In
8000 cycles at 440 V In/2

Mounting support Backplate

Upside connection Front

Downside connection Front

Connection pitch 45 mm

Protection type L : for overload protection (long time)


So : for short time short-circuit protection with fixed delay
I : for instantaneous short-circuit protection

Trip unit rating 630 A at 40 °C

Long-time pick-up adjustment Adjustable 9 settings


type Ir (thermal protection)

[Ir] long-time protection pick-up 250...630 A


adjustment range

Long-time protection delay Fixed


adjustment type tr

[Tr] long-time protection delay 16 s at 6 x Ir


adjustment range

Thermal memory 20 minutes before and after tripping

Short-time protection pick-up Adjustable 9 settings


adjustment type Isd

[Isd] Short-time protection pick- 1.5...10 x Ir


up adjustment range

Short-time protection delay Fixed


adjustment type tsd

Instantaneous protection pick- Fixed


up adjustment type Ii

[Ii] instantaneous protection 6900 A


pick-up adjustment range

Earth-leakage protection Without

Neutral protection settings 0.5 x Ir (3t + N/2)


1 x Ir (4t)
No protection (3t)

Zone selective interlocking ZSI Without

Number of slots for electrical 6 slot(s)


auxiliaries

Local signalling Flashing LED (green) for ready to operate


LED 105 % Ir (red) for overload
LED 90 % Ir (orange) for overload

Width (W) 185 mm

Height (H) 255 mm

Depth (D) 110 mm

2
Mar 28, 2023
Net weight 8.13 kg

Environment
Standards EN/IEC 60947

Product certifications CCC


EAC
Marine

Overvoltage category Class II

Electrical shock protection Class II


class

Pollution degree 3 conforming to IEC 60664-1

IP degree of protection IP40 conforming to IEC 60529

IK degree of protection IK07 conforming to IEC 62262

Ambient air temperature for -25…70 °C


operation

Ambient air temperature for -50…85 °C


storage

Relative humidity 0…95 %

Operating altitude 0...2000 m without derating


2000 m...5000 m with derating

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 14.7 cm

Package 1 Width 20.0 cm

Package 1 Length 28.9 cm

Package 1 Weight 7.43 kg

Unit Type of Package 2 S04

Number of Units in Package 2 3

Package 2 Height 30.0 cm

Package 2 Width 40.0 cm

Package 2 Length 60.0 cm

Package 2 Weight 23.158 kg

Offer Sustainability
Sustainable offer status Green Premium product

REACh Regulation REACh Declaration

EU RoHS Directive Compliant


EU RoHS Declaration

Mercury free Yes

China RoHS Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

RoHS exemption information Yes

Environmental Disclosure Product Environmental Profile

Circularity Profile End of Life Information

WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins

Mar 28, 2023 3


Contractual warranty
Warranty 18 months

Recommended replacement(s)
LV432894 is replaced by:

Circuit breaker, ComPacT NSX630N, 50kA/415VAC, 4 poles, MicroLogic 2.3 trip unit
1x 630A
C63N42D630