Technical Data
Technical Data
Displacement (1450 RPM 50Hz) 41,33 m3/h
Displacement (1750 RPM 60Hz) 49,88 m3/h
No. of cylinder x bore x stroke 4 x 60 mm x 42 mm
Weight 134 kg
Max. pressure (LP/HP) 19 / 32 bar
Connection suction line 35 mm - 1 3/8''
Connection discharge line 28 mm - 1 1/8''
Oil type R134a/R407C/R404A/R507A/R407A/R407F BSE32(Standard) / R134a tc>70°C: BSE55 (Option)
Oil type R22 (R12/R502) B5.2(Option)
Motor data
Motor version 2
Motor voltage (more on request) 380-420V PW-3-50Hz
Max operating current 19.9 A
Winding ratio 50/50
Starting current (Rotor locked) 49.0 A Y / 81.0 A YY
Max. Power input 13,0 kW
Extent of delivery (Standard)
Motor protection SE-B1, CM-RC-01(Option)
Enclosure class IP66
Vibration dampers Standard
Oil charge 2,60 dm³
Available Options
Discharge gas temperature sensor Option
Start unloading Option
Capacity control 100-50% (Option)
Capacity Control - infinite 100-10% (Option)
Additional fan Option
Refrigerant Injection (RI) Option
Oil service valve Option
Crankcase heater 0..140 W PTC (Option)
Oil level monitoring OLC-K1 (Option)
Sound measurement
Sound power level (-10°C / 45°C) 74,3 dB(A) @50Hz
Sound power level (-35°C / 40°C) 78,9 dB(A) @50Hz
Sound pressure level @ 1m (-10°C / 45°C) 66,3 dB(A) @50Hz
Sound pressure level @ 1m (-35°C / 40°C) 70,9 dB(A) @50Hz
Sound power level (-10°C / 45°C) R134a 72,3 dB(A) @50Hz
Sound pressure level @ 1m (-10°C / 45°C) R134a 64,3 dB(A) @50Hz
MFM-REF
https://www.mfmref.com
info@mfmref.com
BITZER Software v6.9.1 rev2074 28.02.2019 / All data subject to change. 6 / 13
Semi-hermetic Reciprocating Compressors
Condensing capacity
The condensing capacity can be calculated with or without heat rejection. This option can be set in the menu
Program ⟹ Options. The heat rejection is constantly 5 % of the power consumption. The condensing capacity is to be found in
the line Condensing cap. (with HR) resp. Condensing capacity.
Operating Points
A
to [°C] -10
tc [°C] 45
Result
Compressor: 4TES-9Y
Recommendation: F252H
Selection F252H
Recommended operating point: A
Selected operating point: A
Receiver volume 25,0 dm³
max refrigerant charge 27,6 kg
receiver load 75,4 %
Receiver unit indivi. components
lower fixing rails 327301-05
upper fixing rails 327301-24
upper fixing plate 320366-02
#1: Receiver selection for compact systems without condensing pressure control. Precise calculation only via refrigerant charge (see notes).