Low Voltage Alternator - 4 Pole: Installation and Maintenance
Low Voltage Alternator - 4 Pole: Installation and Maintenance
Low Voltage Alternator - 4 Pole: Installation and Maintenance
LSA 40
Low Voltage Alternator - 4 pole
This manual concerns the alternator which you have just purchased.
We wish to draw your attention to the contents of this maintenance manual.
2
Electric Power Generation Installation and maintenance 4455 en - 2021.06 / p
LSA 40
Low Voltage Alternator - 4 pole
CONTENTS
1 - RECEIPT.............................................................................................................................4
1.1 - Standards and safety measures.................................................................................4
1.2 - Inspection................................................................................................................... 4
1.3 - Identification............................................................................................................... 4
1.4 - Storage....................................................................................................................... 4
1.5 - Applications................................................................................................................ 4
1.6 - Usage restrictions.......................................................................................................4
2 - TECHNICAL CHARACTERISTICS....................................................................................5
2.1 - Electrical characteristics.............................................................................................5
2.2 - Mechanical characteristics.........................................................................................5
3 - INSTALLATION..................................................................................................................7
3.1 - Assembly.................................................................................................................... 7
3.2 - Checks prior to first use..............................................................................................8
3.3 - Terminal connection diagrams....................................................................................8
3.4 - Commissioning......................................................................................................... 11
3.5 - Setting up................................................................................................................. 11
4 - SERVICING - MAINTENANCE.........................................................................................12
4.1 - Safety measures.......................................................................................................12
4.2 - Routine maintenance................................................................................................12
4.3 - Bearings................................................................................................................... 13
4.4 - Mechanical defects...................................................................................................13
4.5 - Electrical faults......................................................................................................... 14
4.6 - Dismantling, reassembly..........................................................................................16
4.7 - Table of characteristics.............................................................................................18
5 - SPARE PARTS.................................................................................................................20
5.1 - First maintenance parts............................................................................................20
5.2 - Technical support service.........................................................................................20
5.3 - Exploded views, parts list and tightening torque......................................................21
3
Electric Power Generation Installation and maintenance 4455 en - 2021.06 / p
LSA 40
Low Voltage Alternator - 4 pole
1 - RECEIPT 1.4 - Storage
1.1 - Standards and safety Prior to commissioning, machines should
measures be stored:
- away from humidity (< 90%); after a long
Our alternators comply with most
period of storage, check the machine
international standards. insulation. To prevent the bearings from
See the EC Declaration of Incorporation on becoming marked, do not store in an
the last page. environment with significant vibration.
1.2 - Inspection 1.5 - Application
On receipt of your alternator, check that it This alternator is mainly designed to
has not suffered any damage in transit. If produce electricity in the context of
there are obvious signs of knocks, contact applications involving the use of
the transporter (you may be able to claim generators.
on their insurance) and after a visual
check, turn the machine by hand to detect 1.6 - Usage restrictions
any malfunction.
Use of the machine is restricted to operating
1.3 - Identification conditions (environment, speed, voltage,
power, etc) compatible with the characteri-
The alternator is identified by means of a stics indicated on the nameplate.
nameplate fixed on the machine (see
drawing).
Make sure that the nameplate on the
machine conforms to your order.
So that you can identify your alternator
quickly and accurately, we suggest you fill in
its specifications on the nameplate below.
MOTEURS LEROY-SOMER
2 BD MARCELLIN LEROY - 16000 ANGOULÊME - FRANCE
www.leroy-somer.com Scan the code or go to
GEN.LS1.DO
Made in Europe by Leroy-Somer to check product data
4
Electric Power Generation Installation and maintenance 4455 en - 2021.06 / p
LSA 40
Low Voltage Alternator - 4 pole
2 - TECHNICAL 2.2 - Mechanical characteristics
CHARACTERISTICS - Steel frame
2.1 - Electrical characteristics - Aluminum end shields
- Protected ball bearings, greased for life
This alternator is a machine without - Mounting arrangement: single bearing
sliprings or revolving armature brushes, with standard feet and SAE flanges/
wound as “2/3 pitch”, 4 or 12-wire, with coupling discs, two-bearing with SAE flange
class H insulation and a field excitation and standard cylindrical shaft extension
system available in either SHUNT or AREP - Drip-proof machine, self-cooled
version (see diagrams and AVR manuals). - Degree of protection: IP 23
• Electrical options • Mechanical options
- Stator temperature detection sensors - Direct output power by cables (not
- Space heaters reconnectable), regulator fitted outside the
- R791 interference suppression alternator
- Protection against harsh environments
- Air inlet filter, air outlet filter
Alternators fitted with air inlet filters are
subject to a power derating of 5%.
To prevent excessive temperature rise
caused by clogged filters, it is advisable to fit
the stator winding with thermal sensors
(PTC).
T1 T3
EXCITER
Varistor
Armature
T2 T4
Field
5
Electric Power Generation Installation and maintenance 4455 en - 2021.06 / p
LSA 40
Low Voltage Alternator - 4 pole
• SHUNT three-phase 12-wire
MAIN FIELD STATOR: 12-wire (marking T1 to T12)
T1 T7 T2 T8 T3 T9
EXCITER
Varistor
Armature
5+ 6-
T4 T10 T5 T11 T6 T12
Field
Armature
5+ 6-
T4 T10 T5 T11 T6 T12
Field
6
Electric Power Generation Installation and maintenance 4455 en - 2021.06 / p
LSA 40
Low Voltage Alternator - 4 pole
3 - INSTALLATION
Personnel undertaking the various
operations indicated in this section must
wear personal protective equipment
appropriate for mechanical and electrical
hazards.
7
Electric Power Generation Installation and maintenance 4455 en - 2021.06 / p
LSA 40
Low Voltage Alternator - 4 pole
3.2 - Checks prior to first use - the standard direction of rotation is clock-
wise as seen from the drive end (phase
• Electrical checks rotation in order 1 - 2 - 3).
For anti-clockwise rotation, swap 2 and 3.
- the winding connection corresponds to the
site operating voltage (see section 3.3).
WARNING T1 T2 T3 T4
L
T3 T1
0V
NDE
are correct, 0V
8
Electric Power Generation Installation and maintenance 4455 en - 2021.06 / p
LSA 40
Low Voltage Alternator - 4 pole
• SHUNT or AREP three-phase 12-wire
Connection codes Voltage / Detection Factory connection
A 3PH L1(U)
Winding 50 Hz 60 Hz T11 T5 T6
D 3PH T1
L1(U) Winding 50 Hz 60 Hz T11
T3 T10
T8 T10 L2(V)
R220 :
L3(W) L2(V) T4 T2
T11 T8 T5 T2 0 => (T8) / 110 V => (T11) L
L L T7 T12 L1(U)
M D350 :
Voltage LM = 1/2 voltage LL U => T1 / V => T2 / W => T3 T1 NDE
Winding 50 Hz 60 Hz T4
FF 1PH T11
T7 M
6 220 - 240 220 - 240
T2 T6 T8 T12 T3
7 250 - 260 - T9 L
T3
T5 T11 T9 8 200 220 - 240 T10
T1 T4 T7 T8 T6
T10
L L R220 :
M T2
0 => (T1) / 110 V => (T4)
T12 T5 L
D350 :
Voltage LM = 1/2 voltage LL NDE
V => T1 / W => T10 T1
9
Electric Power Generation Installation and maintenance 4455 en - 2021.06 / p
LSA 40
Low Voltage Alternator - 4 pole
• SHUNT or AREP three-phase 12-wire
Connection codes Voltage / Detection Factory connection
T6 T1 M T4
T12
T7
7 250 - 260 -
T9 L
T4
T3 8 200 220 - 240 T3
T2
T10
T9 T5 T8 L
L
R220 :
L T12 T2
T11 T8 0 => (T8) / 110 V => (T11)
T7 T6
D350 :
Voltage LM = 1/2 voltage LL V => T2 / W => T3 T1 NDE
R221 : 0 => (T1) / 110 V => (T2) R221 : 0 => (T1) / 110 V => (T2)
ST
10
5
20 0
Voltage adjustment
40 30
90 80
0
5
60
70 via remote potentiometer
103 130 °C
Ph1 Blue wire
101 150 °C
Ph2 Black wire
102
180 °C
Ph3 Red/white wire
104
10
Electric Power Generation Installation and maintenance 4455 en - 2021.06 / p
LSA 40
Low Voltage Alternator - 4 pole
• Connection checks 3.4 - Commissioning
11
Electric Power Generation Installation and maintenance 4455 en - 2021.06 / p
LSA 40
Low Voltage Alternator - 4 pole
4 - SERVICING - MAINTENANCE WARNING
4.1 - Safety measures
Do not use: trichlorethylene, perchlo-
Servicing or troubleshooting must be
rethylene, trichloroethane or any alkaline
carried out strictly in accordance with
products.
instructions so as to avoid the risk of
accidents and to maintain the machine in
its original state.
These operations must be performed at a
cleaning station, equipped with a
vacuum system that collects and flushes
All such operations performed on the
out the products used.
alternator should be undertaken by
The insulating components and the
personnel trained in the commissioning,
servicing and maintenance of electrical impregnation system are not at risk of
and mechanical components, who must damage from solvents. Avoid letting the
wear personal protective equipment cleaning product run into the slots.
appropriate for mechanical and electrical Apply the product with a brush, sponging
hazards. frequently to avoid accumulation in the
Before any intervention on the machine, housing. Dry the winding with a dry cloth. Let
ensure that it cannot be started by a manual any traces evaporate before reassembling
or automatic system and that you have the machine.
understood the operating principles of the
system. • Mechanical servicing
WARNING
Cleaning the machine using water or a
Warning : During and after running, the highpressure washer is strictly prohi-
alternator will reach temperatures hot bited. Any problems arising from such
enough to cause injury, such as burns. treatment are not covered by our
warranty.
Degreasing: Use a brush and detergent
4.2 - Routine maintenance (suitable for paintwork).
Dusting: Use an air gun.
• Checks after start-up If the machine is fitted with air inlet and outlet
After approximately 20 hours of operation, filters, the maintenance personnel should
check that all fixing bolts on the machine are clean them routinely at regular intervals. In
still tight, plus the general state of the the case of dry dust, the filter can be cleaned
machine and the various electrical using compressed air and/or replaced if it is
connections in the installation. clogged.
After cleaning the alternator, it is essential to
• Electrical servicing
Commercially-available volatile degreasing check the winding insulation (see sections
agents can be used. 3.2 and 4.5).
12
Electric Power Generation Installation and maintenance 4455 en - 2021.06 / p
LSA 40
Low Voltage Alternator - 4 pole
4.3 - Bearings
The bearings are permanently greased Approximate life of the grease (depending on use) =
20,000 hours or 3 years.
- System short-circuit
- Misparalleling
Alternator damaged by a Possible consequences
Abnormal - Broken or damaged coupling
significant impact, followed by
noise - Broken or bent shaft end
humming and vibration
- Shifting and short-circuit of main field
- Fan fractured or coming loose on shaft
- Irreparable damage to rotating diodes/AVR, surge suppressor
13
Electric Power Generation Installation and maintenance 4455 en - 2021.06 / p
LSA 40
Low Voltage Alternator - 4 pole
4.5 - Electrical faults
Fault Action Effect Check/Cause
The alternator builds up and
its voltage is still correct - Lack of residual magnetism
when the battery is removed
Connect a new
battery of 4 to 12 The alternator builds up but - Check the connection of the voltage reference
No voltage volts to terminals its voltage does not reach to the AVR
at no load on E- and E+, the rated value when the - Faulty diodes
start-up respecting the battery is removed - Armature short-circuit
polarity, for 2 to 3
The alternator builds up but -- Faulty
seconds AVR
its voltage disappears when - Field windings open circuit (check winding)
Revolving field coil open circuit (check the
the battery is removed resistance)
Check the AVR connections (AVR may be
faulty)
- Field windings short-circuited
Correct speed - Rotating diodes burnt out
Voltage too Check the drive - Revolving field coil short-circuited (check the
low speed resistance)
Increase the drive speed (do not touch the AVR
Speed too low voltage pot. (P2) before running at the correct
speed)
Voltage too Adjust AVR voltage Adjustment ineffective - Faulty AVR
high potentiometer
- Check the speed: possibility of cyclic
irregularity
Adjust the
Voltage If no effect : try normal / fast - Loose connections
AVR stability
oscillations recovery modes (ST2) - Faulty AVR
potentiometer - Speed too low when on load (or AVR LAM set
too high)
14
Electric Power Generation Installation and maintenance 4455 en - 2021.06 / p
LSA 40
Low Voltage Alternator - 4 pole
• Checking the winding Assembly A: Connect a 12 V battery in
You can check the winding insulation by series with a rheostat of approximately
performing a high voltage test. In this case, 50 ohms - 300 W and a diode on both exciter
you must disconnect all AVR wires. field wires (5+) and (6-).
ASSEMBLY A
6 - Field 5+
WARNING
1A diode Rh. 50 -300W
Damage caused to the AVR in such
conditions is not covered by our
warranty. +
-
• Checking the diode bridge
A diode in good working order should allow
12V battery
the current to flow only in the anode-to-
cathode direction.
Assembly B: Connect a “Variac” variable
+ - power supply and a diode bridge on both
Anode Cathode exciter field wires (5+) and (6-).
Both these systems should have
+R IN +R characteristics which are compatible with
IN IN
the field excitation power of the machine
(see the nameplate).
-W 3) Run the unit at its rated speed.
IN -W 4) Gradually increase the exciter field
current by adjusting the rheostat or the
variac and measure the output voltages on
• Checking the windings and rotating L1 - L2 - L3, checking the excitation voltage
diodes using separate excitation and current at no load (see the machine
nameplate or ask for the factory test report).
When the output voltage is at its rated value
and balanced within 1% for the rated
excitation level, the machine is in good
During this procedure, make sure that working order. The fault therefore comes
the alternator is disconnected from any from the AVR or its associated wiring (ie.
external load and inspect the terminal sensing, auxiliary windings).
box to check that the connections are
ASSEMBLY B
fully tightened. 6 - Field 5+
1) Stop the unit, disconnect and isolate the 40
50 60 +
AVR wires.
30
70
1A diode
2) There are two ways of creating an
20
80
90
0 100
- DC
Variac AC 12V
220V
15
Electric Power Generation Installation and maintenance 4455 en - 2021.06 / p
LSA 40
Low Voltage Alternator - 4 pole
4.6 - Dismantling, reassembly • Access to connections and the
regulation system
WARNING The terminals are accessed directly by
During the warranty period, this removing the terminal box panel (41).
operation should only be carried out in
an approved workshop or in our factory, • Accessing, checking and replacing the
otherwise the warranty may be diode bridge
invalidated. Dismantling
Whilst being handled, the machine - Remove the terminal box panel (41).
should remain horizontal (rotor not - Cut the fixing clamps of the exciter cables,
locked in position). Check how much the disconnect E+, E- from the exciter.
machine weighs before choosing the - Remove the nuts on the tie rods.
lifting method. - Remove the NDE shield (36) using a puller:
eg. U.32 - 350 (Facom).
- Unsolder the connections.
- Check the bridge using an ohmmeter or a
battery lamp.
Reassembly
- Replace the bridges, respecting the
polarity.
- Resolder the connections.
- Refit the NDE shield and pass the bundle
of wires between the top bars of the shield.
- Replace the fixing clamps on the cables.
- Replace the terminal box panel (41).
NDE shield
• Tools required Rotor
To fully dismantle the machine, we Threaded rod M8
recommend using the tools listed below:
- 1 ratchet spanner + extension
- 1 torque wrench
- 1 set of flat spanners: 8 mm, 10 mm, 12 mm
- 1 socket set: 8, 10, 13 mm
- 1 socket TORX bit T20 and T30
- 1 puller (eg. Facom: U35, U32/350)
• Screw tightening torque
See section 5.3.
16
Electric Power Generation Installation and maintenance 4455 en - 2021.06 / p
LSA 40
Low Voltage Alternator - 4 pole
• Replacing the NDE bearing on single • Accessing the main field and stator
bearing machines
Dismantling
Dismantling Follow the procedure for dismantling
- Remove the NDE shield (36). bearings.
- Remove the ball bearing (70) using a screw - Remove the coupling discs (single-bearing
puller. alternator) or the DE shield (two-bearing
alternator) and insert a tube of the
corresponding diameter on the shaft end or
a support made according the following
bellow.
Reassembly
- Heat the inner slipring of a new bearing by
induction or in a drying oven at 80 °C (do not
use an oil bath) and fit it to the alternator.
- Place the preloading wavy washer (79) in
the shield.
- Replace the NDE shield (36).
17
Electric Power Generation Installation and maintenance 4455 en - 2021.06 / p
LSA 40
Low Voltage Alternator - 4 pole
Field excitation current i exc (A)
400V - 50 Hz
“i exc”: excitation current of the exciter field
Type No load At rated load
VS1 0.77 1.94
VS2 0.78 1.97
S3 0.76 2.05
S4 0.75 2.06
Follow the procedure for reassembling the M5 0.72 1.95
bearings.
18
Electric Power Generation Installation and maintenance 4455 en - 2021.06 / p
LSA 40
Low Voltage Alternator - 4 pole
Field excitation current i exc (A) • Table of weights
400V - 50 Hz (values given for information only)
“i exc”: excitation current of the exciter field
Type Total weight (kg) Rotor (kg)
Type No load At rated load
VS1 82 27
VS1 1.06 2.65
VS2 89 29
VS2 1.06 2.69
S3 96 32
S3 1.03 2.79
S4 101 34
S4 1.03 2.80
M5 109 37
M5 0.98 2.66
19
Electric Power Generation Installation and maintenance 4455 en - 2021.06 / p
LSA 40
Low Voltage Alternator - 4 pole
5 - SPARE PARTS 5.2 - Technical support service
5.1 - First maintenance parts Our technical support service will be
pleased to provide any additional
Emergency repair kits are available as an information you may require.
option.
They contain the following items: For all spare parts orders or technical
support requests, send your request to
Emergency kit SHUNT ALT 040 KS 001
service.epg@leroy-somer.com or your
AVR R220 - nearest contact, whom you will find at
Diode bridge assembly - www.lrsm.co/support indicating the comp-
Surge suppressor - lete type of machine, its number and the
information indicated on the nameplate.
Emergency kit AREP 5155832
AVR D350 - Part numbers should be identified from the
Diode bridge assembly - exploded views and their description from
Surge suppressor - the parts list.
Single-bearing kit ALT 422 KB 002 To ensure that our products operate correctly
Non drive end bearing - and safely, we recommend the use of
«O» ring - original manufacturer spare parts.
Preloading (wavy) washer - In the event of failure to comply with this
advice, the manufacturer cannot be held
Double-bearing kit ALT 422 KB 001 responsible for any damage.
Non drive end bearing -
Drive end bearing -
«O» ring -
Preloading (wavy) washer -
After operational testing, it is essential to
replace all access panels or covers.
20
Electric Power Generation Installation and maintenance 4455 en - 2021.06 / p
LSA 40
Low Voltage Alternator - 4 pole
5.3 - Exploded views, parts list and tightening torque
• Single bearing
21
Electric Power Generation Installation and maintenance 4455 en - 2021.06 / p
LSA 40
Low Voltage Alternator - 4 pole
• Two-bearing
22
Electric Power Generation Installation and maintenance 4455 en - 2021.06 / p
LSA 40
Low Voltage Alternator - 4 pole
Screw Torque Screw Torque
Ref. Qty Description Ref. Qty Description
Ø N.m Ø N.m
1 1 Stator assembly - - 90 1 Exciter field (stator) M6 10
Exciter armature
4 1 Rotor assembly - - 100 1 - -
(rotor)
15 1 Fan M5 4 120 1 Terminal block support - -
23
Electric Power Generation Installation and maintenance 4455 en - 2021.06 / p
LSA 40
Low Voltage Alternator - 4 pole
Disposal and recycling All materials listed above need special
instructions treatment to separate waste from
reclaimable materials and should be
We are committed to limiting the
entrusted to specialist recycling companies.
environmental impact of our activity. We
continuously monitor our production
The oil and grease from the lubrication
processes, material sourcing and product
system should be treated as hazardous
design to improve recyclability and minimise
waste and must be treated in accordance
our environmental footprint.
with local legislation.
These instructions are for information
purposes only. It is the user’s responsibility
Our alternators have a specified lifetime of
to comply with local legislation regarding
20 years. After this period, the operation of
product disposal and recycling.
the product should be stopped, regardless
of its condition. Any further operation after
Recyclable materials
this period will be under the sole responsi-
Our alternators are mainly constructed from bility of the user.
iron, steel and copper materials, which can
be reclaimed for recycling purposes.
These materials can be reclaimed through a
combination of manual dismantling,
mechanical separation and melting
processes. Our technical support depart-
ment can provide detailed directions on how
to dismantle products on request.
24
Electric Power Generation Installation and maintenance 4455 en - 2021.06 / p
LSA 40
Low Voltage Alternator - 4 pole
LSA 40 – LSA 42.3 – LSA 44.3 – LSA 46.3 – LSA 47.2 – LSA 47.3 – LSA 49.1 – LSA 49.3 – LSA 50.1 – LSA
50.2 – LSA 51.2 – LSA 52.2 – LSA 52.3 – LSA 53 – LSA 53.1 – LSA 53.2 – LSA 54 – LSA 54.2 – TAL 040 –
TAL 042 – TAL 044 – TAL 046 – TAL 047 – TAL 0473 – TAL 049 – LSAH 42.3 – LSAH 44.3 as well as their
derivatives, manufactured by Leroy-Somer or on Leroy-Somer's behalf, comply with the following International
Standards and Directive:
- EN and IEC 60034-1, 60034-5 and 60034-22.
- ISO 8528-3 “Reciprocating internal combustion engine driven alternating current generating sets. Part
3. Alternating current generators for generating sets”.
- Low Voltage Directive Nr 2014/35/EU dated 26 February 2014.
Furthermore, these generators, designed in compliance with the Machine Directive Nr 2006/42, are therefore
able to be incorporated into Electrical Gen-Sets complying with the following International Directives:
WARNING:
The here mentioned generators should not be commissioned until the corresponding Gen-Sets have been
declared in compliance with the Directives Nr 2006/42/EC, 2014/30/EU, 2011/65/EU and 2015/863, as well as
with other relevant Directives.
Leroy-Somer undertakes to transmit, in response to a reasoned request by the national authorities, relevant
information on the generator.
Technical Managers
J.P. CHARPENTIER Y. MESSIN
Moteurs Leroy-Somer
Siege social : Boulevard Marcellin Leroy CS 10015 - 16915 Angoulême cedex 9 - France
4152 en - 2021.03 / t
SAS au capital de 38 679 664 € - RCS Angoulême 338 567 258
The contractual EC Declaration of compliance and incorporation can be obtained from your contact on
request.
25
Electric Power Generation Installation and maintenance 4455 en - 2021.06 / p
LSA 40
Low Voltage Alternator - 4 pole
26
Service & Support
Life Extension
•Reconditioning Start-up
•System upgrade
•Commissioning
•Training
Optimisation
•Monitoring Operation
•System audit •Genuine spare parts
•Repair services
Contact us:
Americas: +1 (507) 625 4011
Europe & rest of the world: +33 238 609 908
Asia Pacific: +65 6250 8488
China: +86 591 88373036
India: +91 806 726 4867
Scan the code or go to:
service.epg@leroy-somer.com www.lrsm.co/support
www.emersonindustrial.com
www.leroy-somer.com/epg
Linkedin.com/company/leroy-somer
Twitter.com/Leroy_Somer_en
Facebook.com/LeroySomer.Nidec.en
YouTube.com/LeroySomerOfficiel
4455 en - 2021.06 / p