Proline Promass 83
Coriolis Mass Flow Measuring System
KA00024D/06/EN/14.11
71141449
Proline Promass 83
Table of contents
1 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Installation, commissioning and operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.4 Safety conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1 Transporting to the measuring point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2 Installation conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.3 Post-installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.4 Post-installation check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3 Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1 Connecting the various housing types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.2 Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.3 Post-connection check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4 Hardware settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.1 Device address PROFIBUS DP/PA, MODBUS RS485 . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.2 Device address EtherNet/IP network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.3 Terminating resistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
5.1 Switching on the measuring device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
5.2 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.3 Navigating within the function matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.4 Calling the Commissioning Quick Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.5 Software settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.6 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
2 Endress+Hauser
Proline Promass 83 Safety instructions
1 Safety instructions
1.1 Designated use
• The measuring device should only be used to measure the mass flow rate of liquids and gases.
At the same time, the measuring device also measures the density and fluid temperature.
These parameters are then used to calculate other process variables such as volume flow.
• Any use other than that described here compromises the safety of persons and the entire
measuring system and is, therefore, not permitted.
• The manufacturer is not liable for damage caused by improper or non-designated use.
Endress+Hauser 3
Safety instructions Proline Promass 83
• The measuring device must be wired in accordance with the wiring diagrams and connection
labels. Interconnecting must be permitted.
• All parts of the measuring device must be integrated into the potential matching system of the
plant.
• The cables, tested cable glands and tested dummy plugs must suit the prevailing operating
conditions, e.g. the temperature range of the process. Housing openings that are not used
need to be sealed with dummy plugs.
• The measuring device can only be used in conjunction with fluids to which all the wetted
parts of the measuring device are adequately resistant. With regard to special fluids, including
fluids used for cleaning, Endress+Hauser will be happy to assist in clarifying the
corrosion-resistant properties of wetted materials. However, minor changes in temperature,
concentration or in the degree of contamination in the process may result in variations in
corrosion resistance. For this reason, Endress+Hauser does not accept any responsibility with
regard to the corrosion resistance of wetted materials in a specific application. The user is
responsible for the choice of suitable wetted materials in the process.
• When hot fluid passes through the measuring tube, the surface temperature of the housing
increases. In the case of the sensor, in particular, users should expect temperatures that can
be close to the fluid temperature. If the temperature of the fluid is high, implement sufficient
measures to prevent burning or scalding.
• Hazardous areas
Measuring devices for use in hazardous areas are labeled accordingly on the nameplate.
Relevant national regulations must be observed when operating the device in hazardous areas.
• Hygienic applications
Measuring devices for hygienic applications have their own special labeling. Relevant national
regulations must be observed when using these devices.
• Pressure instruments
Measuring devices for use in systems that need to be monitored are labeled accordingly on the
nameplate. Relevant national regulations must be observed when using these devices. The
documentation on the CD-ROM for pressure instruments in systems that need to be
monitored is an integral part of the entire device documentation. The installation regulations,
connection data and safety instructions provided in the Ex documentation must be observed.
• Endress+Hauser will be happy to assist in clarifying any questions on approvals, their
application and implementation.
4 Endress+Hauser
Proline Promass 83 Safety instructions
" Caution!
"Caution" indicates an action or procedure which, if not performed correctly, can result in
incorrect operation or destruction of the device. Comply strictly with the instructions.
! Note!
"Note" indicates an action or procedure which, if not performed correctly, can have an indirect
effect on operation or trigger an unexpected response on the part of the device.
Endress+Hauser 5
Installation Proline Promass 83
2 Installation
2.1 Transporting to the measuring point
• Transport the measuring device to the measuring point in the original packaging.
• The covers or caps fitted on the process connections prevent mechanical damage to the
sensors during transport and storage. For this reason, do not remove the covers or caps until
immediately before installation.
# Warning!
Risk of injury! The device can slip.
The center of gravity of the measuring device may be
higher than the holding points of the slings.
Always ensure that the device cannot slip or turn around
its axis.
A0007408
A0007409
A0007409
6 Endress+Hauser
Proline Promass 83 Installation
2.2.1 Dimensions
For the dimensions of the measuring device see associated Technical Information on the
CD-ROM.
Endress+Hauser 7
Installation Proline Promass 83
2.2.3 Orientation
• The direction of the arrow on the nameplate of the measuring device must match the flow
direction of the fluid.
• The following table lists the possible orientations of the measuring devices:
A0015445
A0004580
A0004576
A0004572
Promass H Recommended
Recommended Recommended Recommended
(p)
Promass I Recommended
Recommended Recommended Recommended
(p)
Promass P Recommended
Recommended Recommended Recommended
(p)
Promass S Recommended
Recommended Recommended Recommended
(p)
Promass X Recommended
Recommended Recommended Possible
(p)
*HT = high temperature version for medium temperatures (TM) > 200 °C (392 °F)
m Do not install the measuring device in such a way that is suspended without any support or securing unit.
n This orientation is not suitable for fluids with entrained solids.
o This orientation is not suitable for outgassing fluids.
p This orientation is not suitable for low fluid temperatures.
8 Endress+Hauser
Proline Promass 83 Installation
2.2.4 Heating
For information on the heating, please see the Operating Instructions on the CD-ROM.
2.2.7 Vibrations
No measures are necessary.
2.3 Post-installation
2.3.1 Turning the transmitter housing
b d
£ 180° £ 180°
c
a
f
A0007540
max. 360°
b a. Release the setscrew.
c b. Turn the transmitter housing
gently clockwise until the stop
Nic
ht unt
er Spannu
öffnen
ng
(end of the thread).
Nicht-eigensichere
Stromkreise durch
p cover tight wh
IP40-Abdeckung geschützt
p cover tight w
a
Non-intrinsically safe
Boucles de courant
c
ve
sous nsion
pas o te pparei
uvrir l’a
l Ne to the desired position.
d
d. Retighten the setscrew.
A0008036
Endress+Hauser 9
Installation Proline Promass 83
£ 180° c £ 180°
a b
e
A0007661
max. 360°
b a. Release the setscrew.
c b. Turn the transmitter housing
gently clockwise until the stop
Nic
ht unt
er Spannu
öffnen
ng
(end of the thread).
Nicht-eigensichere
Stromkreise durch
p cover tight wh
IP40-Abdeckung geschützt
p cover tight w
a
Non-intrinsically safe
Boucles de courant
c
ve
sous nsion
pas o te apparei
uvrir l’
l Ne to the desired position.
d
d. Retighten the setscrew.
A0008036
a
A0007541
10 Endress+Hauser
Proline Promass 83 Installation
" Caution!
• Make sure that the ambient temperature does not exceed the permitted range.
• Always install the wall-mount housing in such a way that the cable entries point downwards.
35 (1.38) mm (inch)
1. Connection compartment
2 2. Securing screws M6 (max. ø 6.5 mm (0.25");
3 3 screw head max. ø 10.5 mm (0.4"))
81.5 (3.2)
3. Housing bores for securing screws
Pipe mounting
mm (inch)
Ø 20…70
(Ø 0.79…2.75)
" Caution!
Danger of overheating! If the device is mounted on a
warm pipe, make sure that the housing temperature
~155 (~ 6.1) does not exceed +60 °C (+140 °F) which is the
maximum temperature permitted.
A0007543
Endress+Hauser 11
Installation Proline Promass 83
Panel mounting
+0.5 (+0.019)
–0.5 (–0.019)
210 (8.27)
+0.5 (+0.019)
–0.5 (–0.019)
245 (9.65)
mm (inch)
~110 (~4.33)
A0007544
12 Endress+Hauser
Proline Promass 83 Wiring
3 Wiring
# Warning!
Risk of electric shock! Components carry dangerous voltages.
• Never mount or wire the measuring device while it is connected to the power supply.
• Prior to connecting the power supply, connect the protective ground to the ground terminal
on the housing.
• Route the power supply and signal cables so they are securely seated.
• Seal the cable entries and covers so they are airtight.
" Caution!
Risk of damaging the electronic components!
• Connect the power supply in accordance with the connection data on the nameplate.
• Connect the signal cable in accordance with the connection data in the Operating Instructions
or the Ex documentation on the CD-ROM.
" Caution!
Risk of damaging the electronic components!
• Only connect sensors and transmitters with the same serial number
• Observe the cable specifications of the connecting cable Operating Instructions on the
CD-ROM.
! Note!
Install the connecting cable securely to prevent movement.
" Caution!
Risk of damaging the electronic components!
• Observe the cable specification of the fieldbus cable Operating Instructions on the
CD-ROM.
• Keep the stripped and twisted lengths of cable shield as short as possible.
• Screen and ground the signal lines Operating Instructions on the CD-ROM.
• When using in systems without potential matching Operating Instructions on the
CD-ROM.
# Warning!
When wiring Ex-certified measuring devices, all the safety instructions, wiring diagrams,
technical information, etc. of the related Ex documentation must be observed
Ex documentation on the CD-ROM.
Endress+Hauser 13
Wiring Proline Promass 83
Transmitter connection:
1 Connection diagram inside the
3 connection compartment cover
4 2 Power supply cable
2 3 Signal cable or fieldbus cable
4 Optional
1
A0007545
Transmitter connection:
1 Connection diagram inside the
connection compartment cover
2 Power supply cable
3 Signal cable
4 Fieldbus cable
Transmitter connection:
ht unter Spannun
Nic öffnen g
3
over tight whi
4
ve
c
Transmitter connection:
1 Connection diagram inside the connection compartment cover
5 1
Connecting cable connection:
5 Sensor/transmitter connecting cable
A0008037
14 Endress+Hauser
Proline Promass 83 Wiring
A0007549
The cables must loop down before they enter the cable
entries ("water trap").
A0007550
Endress+Hauser 15
Hardware settings Proline Promass 83
4 Hardware settings
This section only deals with the hardware settings needed for commissioning. All other settings
(e.g. output configuration, write protection, etc.) are described in the associated Operating
Instructions on the CD-ROM.
! Note!
No hardware settings are needed for measuring devices with HART or FOUNDATION
Fieldbus-type communication.
# Warning!
Risk of electric shock! Risk of damaging the electronic components!
• All the safety instructions for the measuring device must be observed and all the warnings
heeded ä 13.
• Use a workspace, working environment and tools purposely designed for electrostatically
sensitive devices.
# Warnung!
Switch off the power supply before opening the device.
a. Loosen the cheese head screw of the securing
1
2
O
N
E
W
clamp with an Allen key (3 mm / 0.12 in)
3
4
O
N
1 E
2 W
3
4
a
1 E
2 W
3
4 O
N
Installation is the reverse of the removal procedure.
d
1 E
b
2 W
3
4
A0007551
16 Endress+Hauser
Proline Promass 83 Hardware settings
PROFIBUS DP/PA
DP PA
OFF ON OFF ON
Device address range: 0 to 126
1 1 1
Factory setting: 126
2 2 2
c
3 4 3
a. Miniature switches for device address
4 8 a 4 Example shown:
1+16+32 = device address 49
1 16 1 1
2 32 2 2 b. Miniature switches for the address mode (method
of addressing):
3 64 3 4
– OFF (factory setting) = software addressing via
4 b 4 8 a local operation/operating program
– ON = hardware addressing via miniature
1 1 16
switches
2 2 32
c c. Miniature switch not assigned.
3 3 64
4 4 b
OFF ON OFF ON
A0007552
MODBUS RS485
OFF ON
1 1
2 2
Device address range: 1 to 247
Factory setting: 247
3 4
4 8
a a. Miniature switches for device address
1 16 Example shown:
1+16+32 = device address 49
2 32
3 64 b. Miniature switches for the address mode (method
of addressing):
4 128
– OFF (factory setting) = software addressing via
1 b local operation/operating program
– ON = hardware addressing via miniature
2
switches
3 c
c. Miniature switch not assigned.
4
OFF ON
A0007554
Endress+Hauser 17
Hardware settings Proline Promass 83
# Warning!
Risk of electric shock! Risk of damaging the electronic components!
• All the safety instructions for the measuring device must be observed and all the warnings
heeded ä 13.
• Use a workspace, working environment and tools purposely designed for electrostatically
sensitive devices.
2
A0015112
ON ! Note!
Deactivation hardware addressing and activation software
OFF addressing ( ä 25):
8 7 6 5 4 3 2 1
Switch all the DIP switches for hardware addressing to
A0015114
OFF.
18 Endress+Hauser
Proline Promass 83 Hardware settings
# Warning!
Risk of electric shock! Risk of damaging the electronic components!
• All the safety instructions for the measuring device must be observed and all the warnings
heeded ä 13.
• Use a workspace, working environment and tools purposely designed for electrostatically
sensitive devices.
O
N
1 E
2 W
3
4
O
N
1 E
2 W
3
4
O
N
1 E
2 W
3
4
1
2 W
3
4
2
1
2
3
4
O
N
E
W
220 W
3
O
N
1 E
2 W
3
4 O
N
1 E
2 W
3
4
4
390 W
OFF ON
A0007556
Endress+Hauser 19
Commissioning Proline Promass 83
5 Commissioning
5.1 Switching on the measuring device
On completion of the installation (successful post-installation check), wiring (successful
post-connection check) and after making the necessary hardware settings, where applicable, the
permitted power supply (see nameplate) can be switched on for the measuring device.
When the power supply is switched on, the measuring device performs a number of power-up
checks and device self-checks. As this procedure progresses the following messages can appear
on the onsite display:
Display examples:
PROMASS 83
Start-up message
START-UP
RUNNING
Æ
PROMASS 83
Displays the current software
DEVICE SOFTWARE
V XX.XX.XX
Æ
CURRENT OUTPUT
FREQUENCY OUTPUT
List of input/output modules available
RELAY
STATUS INPUT
Æ
SYSTEM OK
Beginning of operation
OPERATION
The measuring device starts operating as soon as the startup procedure is complete.
Various measured values and/or status variables appear on the display.
! Note!
If an error occurs during startup, this is indicated by an error message.
The error messages that occur most frequently when a measuring device is commissioned are
described in the Troubleshooting section ä 27.
20 Endress+Hauser
Proline Promass 83 Commissioning
5.2 Operation
5.2.1 Display elements
4 5 6 Display lines/fields
1. Main line for primary measured values
+24.502
2. Additional line for additional measured
1 v x variables/status variables
y 3. Information line for bar graph display for example
2 S 3 +1863.97 x
y
4. Info icons, e.g. volume flow
v 5. Current measured values
3 –50 +50 %
6. Engineering units/time units
A0007663
Operating keys
Esc
- +
1. (–) Minus key for entering, selecting
E
2. (+) Plus key for entering, selecting
3. Enter key for calling the function matrix, saving
1 2 3 When the +/– keys are pressed simultaneously (Esc):
A0007559 • Exit the function matrix step-by-step:
• > 3 sec. = cancel data input and
return to the measured value display
1. Type of error:
+24.502
P = Process error, S = System error
v x
2. Error message type:
y $ = Fault message, ! = Notice message
1 P XXXXXXXXXX 5 3. Error number
4. Duration of the last error that occurred:
2 #000 00:00:05 Hours: Minutes: Seconds
5. Error designation
3 4 • List of the most common error messages during
commissioning ä 27
A0007664
• List of all error messages, see associated Operating
Instructions on the CD-ROM
Endress+Hauser 21
Commissioning Proline Promass 83
Esc
+
Esc Esc
- E >3s
– + s t – +
m E
o p q
E E E E E E E
– + – + – + r
s s s
+
+ –
+ –
n –
A0007665
22 Endress+Hauser
Proline Promass 83 Commissioning
! Note!
Observe the following when performing the Quick Setup:
• Configuration selection: Select the ACTUAL SETTING option
• Unit selection: This is not offered again for selection after configuring a unit
• Output selection: This is not offered again for selection after configuring an output
• Automatic configuration of the display: select YES
– Main line = Mass flow
– Additional line = Totalizer 1
– Information line = Operating/system conditions
• If asked whether additional Quick Setups should be executed: select NO
All the available functions of the measuring device and their configuration options as well as
additional Quick Setups, if available, are described in detail in the "Description of Device
Functions" Operating Instructions. The related Operating Instructions can be found on the
CD-ROM.
The measuring device is ready for operation on completion of the Quick Setup.
Endress+Hauser 23
Commissioning Proline Promass 83
! Note!
The COMMISSIONING SETUP must be executed before setting the device address.
24 Endress+Hauser
Proline Promass 83 Commissioning
Software addressing is performed in the "Network Configuration" menu of the Webserver. Both
the IP address for the EtherNet/IP network and the IP address for the Webserver can be
configured. The measuring device has the following default addresses when delivered:
Addresses in the range from 0 to 254 are permitted (the address 255 is reserved for the broadcast
address).
! Note!
• Software addressing is disabled if hardware addressing is activated ä 16.
• When changing from software addressing to hardware addressing, the first nine digits (first
three octets) that were configured using software addressing, remain unchanged.
• A reset of the software addressing to the default setting is possible see SD00138D.
DHCP client
If a DHCP server is used within the EtherNet/IP network, the IP address, gateway and subnet
mask are set automatically when the DHCP client function of the Webserver is enabled. The
MAC address of the measuring device is used for identification purposes.
The DHCP client function is enabled in the "Network Configuration" menu.
The measuring device has the following DHCP default settings when delivered:
! Note!
The DHCP client function is disabled if hardware addressing is enabled ä 18.
Endress+Hauser 25
Commissioning Proline Promass 83
Esc
- + E
>3s Esc
E – +
…
+
BASIC FUNCTION E
–
…
+
– ETHERNET E
…
+
– CONFIGURATION E IP ADDRESS 1
SUBNETMASK 1
GATEWAY 1
… E
+ IP ADDRESS 2
SUPERVISION E
–
SUBNETMASK 2
… GATEWAY 2
+
– VERSION-INFO E
…
+
– ETHERNET E SW-REV. SUB A/E
MAC ADD. 1
E
MAC ADD. 2
A0015115
Parameter Assignment
SUBNETMASK 1
GATEWAY 1
MAC ADD. 1
IP ADDRESS 2 Webserver
SUBNETMASK 2
GATEWAY 2
MAC ADD. 2
26 Endress+Hauser
Proline Promass 83 Commissioning
5.6 Troubleshooting
The error messages that can occur most frequently when a measuring device is commissioned
are described here.
A complete description of all the error messages Operating Instructions on the CD-ROM.
General
! Note!
The output signals (e.g. pulse, frequency) of the measuring device must correspond to the
higher-order controller.
HART
The maximum current value for the measuring tube exciter coils
has been reached since certain fluid characteristics, e.g. high gas or
solid content, are in the limit range. The device continues to work
correctly.
Process error message (P)/
Notice message (!) In particular with outgassing fluids and/or increased gas content,
701 the following measures are recommended to increase system
EXC. CURR. LIM pressure:
# 701 1. Install the measuring device downstream of a pump
2. Mount the device at the lowest point in an ascending pipeline
3. Install a valve or an orifice plate downstream from the
measuring device
FOUNDATION Fieldbus
Endress+Hauser 27
Commissioning Proline Promass 83
PROFIBUS
No. Device status message PROFIBUS measured value status Extended Cause/remedy
(onsite display) diagnostic
message in
the
PROFIBUS
master
MODBUS RS485
28 Endress+Hauser
Proline Promass 83 Commissioning
Endress+Hauser 29
Commissioning Proline Promass 83
30 Endress+Hauser
Proline Promass 83 Commissioning
Endress+Hauser 31
KA00024D/06/EN/14.11
71141449