PLC Connection Guide

Siemens S7-300 MPI


Supported Series: Siemens S7-300 series PLC
Website: http://www.siemens.com/entry/cc/en/

HMI Setting:
Parameters Recommende Options Notes
PLC type d
SIEMENS S7-300 MPI
PLC I/F RS-485 2W
Baud rate 187.5K 19200,187.5K
Data bits 8
Parity Even
Stop bits 1
PLC sta. no. 2 2 ~ 31

Online simulator NO Extend address mode Yes


Broadcast command NO

Device Address:
Bit/Word Device type Format Range Memo
B I DDDDo 0 ~ 40957 Input (I)

B Q DDDDo 0 ~ 40957 Output (O)

B M DDDDo 0 ~ 40957 Bit Memory

B DBnBit FFFFFDDDDo 0 ~ 6553599997 Data Register Bit

B DBxBit FFFFFDDDDDo 0 ~ 10700655327


DB1Bit ~
B DDDDDo 0 ~ 655327 Data Register Bit
DB99Bit
W IW DDDD 0 ~ 4095 Input (I)

W QW DDDD 0 ~ 4095 Output (O)

Byte MB DDDD 0 ~ 4095 Bit Memory Byte

W MW DDDD 0 ~ 4095 Bit Memory

DW MD DDDD 0 ~ 4094
Byte DBBn FFFFFDDDD 0 ~ 655359999 Data Register

Byte DBBx FFFFFDDDDD 0 ~ 1070065532


W DBn FFFFFDDDD 0 ~ 655359999 Data Register (must be even)
PLC Connection Guide
Bit/Word Device type Format Range Memo
W DBx FFFFFDDDDD 0 ~ 1070065532
Data Register Double Word
DW DBDn FFFFFDDDD 0 ~ 655359999
(must be even)

DW DBDx FFFFFDDDDD 0 ~ 1070065532

W DBn_String FFFFFDDDD 0 ~ 655359999


W DBx_String FFFFFDDDDD 0 ~ 1070065532
W DBn_String1 FFFFFDDDD 0 ~ 655359999
W DBx_String1 FFFFFDDDDD 0 ~ 1070065532
DW DBDn_String FFFFFDDDD 0 ~ 655359999
DW DBDx_String FFFFFDDDDD 0 ~ 1070065532
W DB1 ~ DB99 DDDDD 0 ~ 65532 Data Register (must be even)

 Double word and floating point value must use DBDn device type.

Multi-HMIs-Multi-PLCs Communication Setting:

For SIEMENS S7-300 MPI driver in Multi-HMIs-Multi-PLCs communication, [Max. station


no. (MPI network)] parameter must be correctly set. This setting is relevant to the station
no. of the devices, as shown, two HMI (station no. 0, 1) and two PLC (station no. 2, 3) are
in MPI network, Max. Station No. should be set to 3.
PLC Connection Guide

For the effectiveness of communication, users may set PLC device in STEP 7 as shown
below. In Properties MPI / Network Settings, set Highest MPI address to the number
closest to the actual device station number.

■ HMI sta. no. can not be the same as PLC sta. no.
■ Highly recommended that the device station numbers start from 0 sequentially and
correctly set [Max. station no. (MPI network)].
■ Available for EasyBuilder V4.50 and later.
■ X Series does not support multiple-HMI-to-multiple-PLC communication, and supports
only 1-HMI-to-1-PLC communication.
PLC Connection Guide

How to Import Tag:


SIEMENS STEP 7 program allows building files of user-defined tag (*.dif file and *.AWL
file), and import these files in EasyBuilder8000/EasyBuilderPro -> System Parameter
Settings. The following describes how to build and import these two types of files.
1. Building *.dif File
a、 In “Symbols” create user-defined tag.

b、 Click Export to export the edited file and click Save.


PLC Connection Guide
2. Building *.AWF File
a、 In Blocks create items as shown below:

b、 Open LAD/STL, FBD – Programming S7 Blocks, click File -> Generate


Source.

c、 Select Sources as storage path, specify the file name then click OK.
PLC Connection Guide
d、 Select the objects to be exported then click OK.

e、 Under Sources there will be names of the saved files, select Export
Source to build *.AWL file.
PLC Connection Guide
The generated *.dif and *.AWL files can be imported in EasyBuilder8000/EasyBuilderPro
System Parameter Settings, by clicking Import Tag.

Tag information successfully imported.


PLC Connection Guide

Pass-Through Settings:
[Designate client IP]: In Pass-through mode designate the client IP address to connect
HMI. The “client” usually refers to Siemens Step 7 application.

[Utility Manager Settings]:


Utility manager -> Serial Pass-through
Mode: MPI ISOTCP
PLC Connection Guide
The following lists the system registers relevant to Siemens S7-200 PPI and
Siemens S7-300 MPI Pass-through feature.
 [LW-10850: disable/enable (0 : disable, 1 : normal, 2 : IP limited) (siemens
pass-through)]
 [LW-10851: destination COM port (siemens pass-through)]: Generally refers to the
COM port connected with PLC.
 [LW-10852: destination PLC station no. (siemens pass-through)]
 [LW-10853: communication protocol (0 : invalid, 1 : PPI, 2 : MPI) (siemens
pass-through)]
 [LW-10854 to LW-10857: IP of connecting client (siemens pass-through)]: Displays
current client IP address connected with HMI.
 [LW-10858 to LW-10861: IP of designated client (siemens pass-through)]: If
LW-10850 is set to 1, the system registers can be used to designate the client IP
connected with HMI.
 [LW-10862: connection status (0 : ready, 1 : client connecting) (siemens
pass-through)]
 [LW-10863: execution status (0 : normal, 1 : error) (siemens pass-through)]
 [LW-10864: the last error (siemens pass-through)]

The following table lists the error codes, the description of each code, and the
possible reason.
Error Code Description Possible Reason
0 Successfully executed
1 Prohibit client from connecting HMI is already running pass-through
HMI and won’t accept any request from
other client.
2 Prohibit client from connecting When LW-10850 is set to 1, the
HMI client IP for connecting HMI is
different from the IP specified in
LW-10858 ~ LW-10861.
3 Invalid communication Invalid setting in LW-10853.
protocol
4 Invalid PLC station number The PLC station number specified in
LW-10852 does not exist.
5 Delayed communication PLC connection failure.
6 Busy communication PLC does not accept pass-through
request, please confirm PLC
settings.
7 Invalid pass-through request Environment setup failure.
PLC Connection Guide

Wiring Diagram:
S7-200 PPI , S7-300 MPI :RS485 2W
Diagram 1
cMT Series cMT3151

eMT Series eMT3070/ eMT3105 / eMT3120 / eMT3150

HMI PLC
COM1 COM3 RS485 2W
RS485 2W RS485 2W 9P D-Sub
9P Male 9P Male Male
Data- 1 6 8 Data-
Data+ 2 9 3 Data+
GND 5 5 5 GND

Diagram 2
cMT Series cMT-SVR / cMT-G01 / cMT-G02 / cMT-HDM / cMT-FHD

mTV mTV

HMI PLC
COM2 COM3 RS485 2W
RS485 2W RS485 2W 9P D-Sub
9P Female 9P Female Male
Data- 7 4 8 Data-
Data+ 6 1 3 Data+
GND 5 5 5 GND
PLC Connection Guide

Diagram 3
MT-iE MT8070iE / MT6070iE / MT8100iE / MT8121iE / MT8150iE

MT-XE MT8121XE / MT8150XE

HMI PLC
COM1 COM3 RS485 2W
RS485 2W RS485 2W 9P D-Sub
9P Male 9P Male Male
Data- 1 7 8 Data-
Data+ 2 8 3 Data+
GND 5 9 5 GND

Diagram 4
cMT Series cMT3071 / cMT3072 / cMT3090 / cMT3103

MT-iE MT8071iE / MT6071iE / MT8072iE / MT6072iE / MT8073iE /


MT8101iE / MT8102iE / MT8103iE
MT-XE MT8090XE / MT8092XE

MT-iP MT6103iP / MT8102iP

HMI PLC
COM2 COM3 RS485 2W
RS485 2W RS485 2W 9P D-Sub
9P Male 9P Male Male
Data- 1 6 8 Data-
Data+ 2 9 3 Data+
GND 5 5 5 GND
PLC Connection Guide

Diagram 5
MT-iE MT8050iE / MT8053iE

MT-iP MT6051iP / MT8051iP

HMI PLC
COM1 COM3 RS485 2W
RS485 2W RS485 2W 9P D-Sub
9P Female 9P Female Male
Data- 1 7 8 Data-
Data+ 2 8 3 Data+
GND 5 5 5 GND

Diagram 6
MT-iP MT6071iP / MT8071iP

HMI PLC
COM2 RS485 2W
RS485 2W 9P D-Sub
9P Female Male
Data- 1 8 Data-
Data+ 2 3 Data+
GND 5 5 GND