Siemens S7 300 MPI
Siemens S7 300 MPI
Siemens S7 300 MPI
HMI Setting:
Parameters Recommende Options Notes
PLC type d
SIEMENS S7-300 MPI
PLC I/F RS-485 2W
Baud rate 187.5K 19200,187.5K
Data bits 8
Parity Even
Stop bits 1
PLC sta. no. 2 2 ~ 31
Device Address:
Bit/Word Device type Format Range Memo
B I DDDDo 0 ~ 40957 Input (I)
DW MD DDDD 0 ~ 4094
Byte DBBn FFFFFDDDD 0 ~ 655359999 Data Register
Double word and floating point value must use DBDn device type.
For the effectiveness of communication, users may set PLC device in STEP 7 as shown
below. In Properties MPI / Network Settings, set Highest MPI address to the number
closest to the actual device station number.
■ HMI sta. no. can not be the same as PLC sta. no.
■ Highly recommended that the device station numbers start from 0 sequentially and
correctly set [Max. station no. (MPI network)].
■ Available for EasyBuilder V4.50 and later.
■ X Series does not support multiple-HMI-to-multiple-PLC communication, and supports
only 1-HMI-to-1-PLC communication.
PLC Connection Guide
c、 Select Sources as storage path, specify the file name then click OK.
PLC Connection Guide
d、 Select the objects to be exported then click OK.
e、 Under Sources there will be names of the saved files, select Export
Source to build *.AWL file.
PLC Connection Guide
The generated *.dif and *.AWL files can be imported in EasyBuilder8000/EasyBuilderPro
System Parameter Settings, by clicking Import Tag.
Pass-Through Settings:
[Designate client IP]: In Pass-through mode designate the client IP address to connect
HMI. The “client” usually refers to Siemens Step 7 application.
The following table lists the error codes, the description of each code, and the
possible reason.
Error Code Description Possible Reason
0 Successfully executed
1 Prohibit client from connecting HMI is already running pass-through
HMI and won’t accept any request from
other client.
2 Prohibit client from connecting When LW-10850 is set to 1, the
HMI client IP for connecting HMI is
different from the IP specified in
LW-10858 ~ LW-10861.
3 Invalid communication Invalid setting in LW-10853.
protocol
4 Invalid PLC station number The PLC station number specified in
LW-10852 does not exist.
5 Delayed communication PLC connection failure.
6 Busy communication PLC does not accept pass-through
request, please confirm PLC
settings.
7 Invalid pass-through request Environment setup failure.
PLC Connection Guide
Wiring Diagram:
S7-200 PPI , S7-300 MPI :RS485 2W
Diagram 1
cMT Series cMT3151
HMI PLC
COM1 COM3 RS485 2W
RS485 2W RS485 2W 9P D-Sub
9P Male 9P Male Male
Data- 1 6 8 Data-
Data+ 2 9 3 Data+
GND 5 5 5 GND
Diagram 2
cMT Series cMT-SVR / cMT-G01 / cMT-G02 / cMT-HDM / cMT-FHD
mTV mTV
HMI PLC
COM2 COM3 RS485 2W
RS485 2W RS485 2W 9P D-Sub
9P Female 9P Female Male
Data- 7 4 8 Data-
Data+ 6 1 3 Data+
GND 5 5 5 GND
PLC Connection Guide
Diagram 3
MT-iE MT8070iE / MT6070iE / MT8100iE / MT8121iE / MT8150iE
HMI PLC
COM1 COM3 RS485 2W
RS485 2W RS485 2W 9P D-Sub
9P Male 9P Male Male
Data- 1 7 8 Data-
Data+ 2 8 3 Data+
GND 5 9 5 GND
Diagram 4
cMT Series cMT3071 / cMT3072 / cMT3090 / cMT3103
HMI PLC
COM2 COM3 RS485 2W
RS485 2W RS485 2W 9P D-Sub
9P Male 9P Male Male
Data- 1 6 8 Data-
Data+ 2 9 3 Data+
GND 5 5 5 GND
PLC Connection Guide
Diagram 5
MT-iE MT8050iE / MT8053iE
HMI PLC
COM1 COM3 RS485 2W
RS485 2W RS485 2W 9P D-Sub
9P Female 9P Female Male
Data- 1 7 8 Data-
Data+ 2 8 3 Data+
GND 5 5 5 GND
Diagram 6
MT-iP MT6071iP / MT8071iP
HMI PLC
COM2 RS485 2W
RS485 2W 9P D-Sub
9P Female Male
Data- 1 8 Data-
Data+ 2 3 Data+
GND 5 5 GND