Product Manual
Overview
The FDO181C is an optical smoke detector with an optical sensor. It works according
to the principle of forward scattering. The detector reacts extremely sensitive on light
aerosols caused by fire. The increased sensitivity makes the detection of smoldering
and open fire possible.
Characteristics
– Intelligent detector with built-in CPU, providing advanced distributed intelligence for
optimum reliable detection principle
– Opto-electronic sampling chamber detects fire more reliable and accurate
– Collective detector, no address setting, polarity free connection
– Particularly suited for the early detection of smoke-generating flaming and
smoldering fires
– Resistant to environment and interference factors such as dust, fibers, insects,
humidity, extreme temperatures, corrosive, vapors, vibration, synthetic aerosols.
With immunity against electro-magnetic interference
– Self-test of operating status, when fault occurs or low voltage happens, indicator can
prompt user
– Automatic drift compensation and dust prompt for reducing false alarm because of
dust accumulation
– 360° visible alarm indicator
– Dust cap protects the detector from being contaminated by construction work
Building Technologies
Fire safety and security products
Application
– Communication with FC18 controller via FDCI183 transponder, each FDCI183 can
connect max. 32 collective detectors.
– Communication with BC80 controller via BDS161 transponder, each BDS161 can
connect max. 10 collective detectors.
Indicator
The detector is provided with an internal alarm indicator to show its operating status.
Status Indicator
Normal Off
Fault Flash every 5s
Dust Prompt (Heavy dust) Double flash every 5s
Alarm Steady on
Installation
Uninstallation:
1.Turn it counterclockwisely and pull the detector out of base.
Base
Positioning pointer
Detector
Positioning pointer
After all the construction is finished, the dust cap must be taken away!
No painting!
Dimensions
Maintenance
Performance test
Recommendation:
– Submit all detectors to an annual visual check. Detectors that are strongly soiled or
mechanically damaged must be replaced.
– Long term backup detectors should be stored with sealed plastic bag.
– Carry out smoke test each year.
Technical data