GIPRCNX Module Setup
GIPRCNX Module Setup
GIPRCNX Module Setup
Documentation Conventions
Convention Description
Italic Indicates emphasized text like notes and warnings.
Introduction
The GIPRCNX device provides 10 Base T Ethernet connectivity for the RCNX line of reader controllers. This
device will operate with both RCNX – 8 and RCNX – 16 board Revision “G” or higher with firmware versions 5.22 or
higher and RCNX 2 revision “A” or higher with firmware version 5.23 or higher.
If you orient your RCNX board as shown in the diagram below, the GIPRCNX device can only be installed on the
right hand side of the board (RCNX Rev. G). The jumper setting (W12) must be on 1 and 2 (LAN).
www.geoffreyaccess.com Page 2 of 8
GIPRCNX Configuration
If you orient your RCNX 2 board as shown in the diagram below, the GIPRCNX device is installed on the bottom
side. The jumper settings for the GIPRCNX (W7) must be on 1 and 2.
Jumper Setting: W7
WARNING: Failure in following these directions will lead to malfunctioning of the devices and also void the
warranty.
WARNING: Do not remove jumper settings or devices with the board powered on. The board must be powered off
before any changes or swapping of components.
Before you begin the configuration you must find out the following things.
1. The network IP address that will be assigned to the GIPRCNX module. See your network
administrator for this IP address.
2. The network IP address of the default gateway used by the GIPRCNX to reach the CIM if
applicable.
3. The net mask for the connection.
4. The node address / MAC address of the IP module.
5. The format for the node address / MAC address is displayed as: 00-20-4a-64-45-b3. This is
located on the white sticker on the IP module itself.
6. The IP address of the CIM workstation that will be communicating to the GIPRCNX.
www.geoffreyaccess.com Page 3 of 8
GIPRCNX Configuration
Configuration
1. Click on the Start button and click Run from the start menu. Type “CMD” into the Open field
on the window. This brings the DOS prompt. Press <Enter>.
2. Type “ARP – s <IP Address for RCNX> <Node Address of card on RCNX>”. (Please note
that there are spaces between characters) Press <Enter>.
Example: C:arp –s 192.168.0.60 00-20-4a-64-3d-da
3. Click on the Start button and click Run from the start menu. Type, “telnet <IP Address for
RCNX> 1” into the Open field. (Please note that there are spaces between characters). Click
<OK>
Example: telnet 192.168.0.60 1
If the operating system on your machine is Windows NT, the Telnet window will open and the connection will
FAIL, as shown in the example below.
www.geoffreyaccess.com Page 4 of 8
GIPRCNX Configuration
Leave the window open and continue with the following instructions.
If you are using Windows 2000, the Telnet window will open, and pause for a few moments and then will be
cleared from your screen. Continue with the following instructions.
4. Click on the Start button on your windows status bar. Click Run. Type, “telnet <IP Address for
RCNX> 9999” into the window. (Please note that there are spaces between characters)
Example: telnet 192.168.0.60 9999
NOTE: Press < Enter> quickly or the connection will time out.
www.geoffreyaccess.com Page 5 of 8
GIPRCNX Configuration
7. IP Address:
Enter each Octet of the IP address, or press <Enter> to confirm the Octet as it appears.
Example:
The above example shows the original Octet of the IP address as (172). To make a change we typed 192 and
pressed <Enter> key to accept this value. Now the next Octet of the IP address is displayed. Value was (016). To
accept the value we pressed the <Enter> key. The next value was (030). Again we accepted the value by
pressing the <Enter> key. The last Octet value was (030). We typed in 021 and pressed the <Enter> key to accept
the change.
8. Set Gateway IP Address “N”. Press <Enter>. If you have a gateway press “Y”. If you do not,
press <Enter> or type “N” to continue.
NOTE: This is the gateway of the IP module, not the CIM.
9. Net mask: Number of Bits for host part = 8. Local net mask 8 will be displayed. To accept the
value press <Enter>. To change the value type in the number and press <Enter>.
The Device Server prompts for the number of host bits to be entered, then calculates the net mask,
which is displayed in standard decimal-dot notation when the saved parameters are displayed (for
example, 255.255.255.0).
Example
Just count the number of zero’s in the subnet mask to get the number of host bits.
www.geoffreyaccess.com Page 6 of 8
GIPRCNX Configuration
255.255.255.248
This is how you determine the host bits for the GIPRCNX IP module subnet mask.
NOTE: The following items should use the values listed. If the values you see during this setup is different, change
the values to match this document. Start with 38400 as the baud rate, this may have to be adjusted later if there
are communication problems.
www.geoffreyaccess.com Page 7 of 8
GIPRCNX Configuration
The GIPRCNX has four status LEDs: serial port (Channel) 1 status, serial port (Channel)
2 status, diagnostics, and network link status. See the following table for a complete
description of status LED pin out location and function.
1 2
3 4
GIPRCNX Status LEDs
3 Diagnostics CON 4, Pin 3 Blinks or lights solid red in combination with the
green (Channel1) LED to indicate
diagnostics and error detection.
Red solid, green (Channel 1) blinking:
1x: EPROM checksum error
2x: RAM error
3x: Network controller error
4x: EEPROM checksum error
5x: Duplicated IP address on the network*
6x: Software does not match hardware*
Red blinking, green (Channel 1) blinking:
4x: Faulty network connection*
5x: No DHCP response received*
4 Network Link Status CON 4, Pin 8 Lights solid green to indicate network port is
connected to the network.
*Non-fatal error
www.geoffreyaccess.com Page 8 of 8