Instrument Data For Coriolis Flow Transmitter

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

GPP- 2

INSTRUMENT DATA SHEET


C-200
ODUM ENERGY FZE

Revision No. 0 CORIOLIS FLOW METER Page No. 1


1 Tag Number QTY FIT 341A 1 Nos.
2 Service Propane (C3) Rundown
3 Location Propane (C3) Rundown Header
4 P&ID Number Line Size/Rating SEEPA15008-GPP1-PS-P&ID-001-036 6"- 300#
GENERAL 5 Ambient Temperature Min Max °C 25 45
6 Humidity Min Max % RH 38 97
7 Area Classification Zone 1, Gas Group IIA, T3
8 Certification Ex 'd' ATEX,IEC-60079
9 Ingress Protection IP 67
10 Fluid State Propane (C3) Liquid
11 Design Pressure PSIG Design Temp °C 300 80
12 Propane Flow Rate Min Nor Max Kg / Hr 8,500 17000 - 21500 25,000
13 Operating Pressure Min Max PSIG 200 250
14 Process Temperature Min Max °C 20 45
PROCESS CONDITIONS
15 Differential Pressure Min Nor Max PSI VTA VTA VTA
16 Operating Density Liquid Min Max kg/m3 457.400 499.400
17 Operating Viscosity cP 0.08157 - 0.1043
18 Pulsation Vibration YES NO
19 Corrosive / Erosive Components NO
20 Type of Meter Mass Flow Meter
21 Type of Transmitter Type of Communication Electronic, HART Smart Type 4-20mA, Analog, 4 Wire, HART
22 Instrument Range Min Max * *
23 Calibration Range Min Max * *
24 Engineering Flow Rate Range Min Max * *
25 Transmitetr Output Signal Analog Output
26 Power Supply Load Driving Capacity 230 VAC/* *
27 Accuracy Response Time Note 2 100 ms
28 Repeatability Output Signal Note 2 4-20mA Loop Power + HART
TRANSMITTER
29 Fill Fluid Wetted o-rings Material MFR Std. MFR Std.
30 Bolts Housing SS 316 Dicast Aliminium
31 Secondary Housing Required Yes
32 Process Connection Size & Rating Electrical Connection/Cable Entry 1/2" NPT
33 Allowable Temperature °C *
34 Over Range of Protection 130% of Range
35 Enclosure Class IP 67
36 RFI Compliance & Electromagnetic Compatability Required
37 Integral Meter Indication Scale & Unit Required, LCD Display *
OPTIONS 38 Hydrostatic Testing Yes
39 Tag Plate SS316, Tag Name to be printed
40 Communication Type HART Communication (with 4-20mA)
COMMUNICATION & 41 Baud Rate *
SOFTWARE 42 Communication With Internal Diagnostics PLC Yes
43 Hand Held terminal Yes
44 Manufacturer YOKOGAWA
45 Model Number RCUP1HS- 80BA20 -0C72-KF22-2-M61 /BG/P13/RT/TC
PURCHASE 46 Serial Number Purchase Order Number * OEF/GPP-2/PR/155+197/2022/VI146
47 Price *
48 Item Number *

NOTES:
1 *' - VENDOR to specify / furnish.
2 Vendor to suggest Flow Meter size to compensate provided process parameter in data sheet
3 Transmitter Accuracy including the combined effects of Linearity, Hysterises and Repeatability shall be equal to or better than +/- 0.05% of calibrated
span or better , temperature effects at calibrated span will be at 50 Deg cel.

DOCUMENT:
1 Data sheets.
2 Calbration Certificate.
3 Ingress Protection rating compliance certificates and ATEX Certificates.
4 Test reports of radiography, ultrasonic & MPI Inspection.
5 Test Certificate of Hydrostatic complete with duration and pressure records of each test.
GPP- 2
INSTRUMENT DATA SHEET
C-200
ODUM ENERGY FZE

Revision No. 0 CORIOLIS FLOW METER Page No. 2


1 Tag Number QTY FIT 351A 1 Nos.
2 Service Butane (C4) Rundown
3 Location Butane (C4) Rundown Header
4 P&ID Number Line Size/Rating SEEPA15008-GPP1-PS-P&ID-001-036 6"- 300#
GENERAL 5 Ambient Temperature Min Max °C 25 45
6 Humidity Min Max % RH 38 97
7 Area Classification Zone 1, Gas Group IIA, T3
8 Certification Ex 'd' ATEX,IEC-60079
9 Ingress Protection IP 67
10 Fluid State Butane (C4) Liquid
11 Design Pressure PSIG Design Temp °C 300 80
12 Propane Flow Rate Min Nor Max Kg / Hr 5,000 13000 - 16000 17,500
13 Operating Pressure Min Max PSIG 58 75
14 Process Temperature Min Max °C 20 45
PROCESS CONDITIONS
15 Differential Pressure Min Nor Max PSI VTA VTA VTA
16 Operating Density Liquid Min Max kg/m3 457.000 562.000
17 Operating Viscosity cP 0.081 - 0.165
18 Pulsation Vibration YES NO
19 Corrosive / Erosive Components NO
20 Type of Meter Mass Flow Meter
21 Type of Transmitter Type of Communication Electronic, HART Smart Type 4-20mA, Analog, 4 Wire, HART
22 Instrument Range Min Max * *
23 Calibration Range Min Max * *
24 Engineering Flow Rate Range Min Max * *
25 Transmitetr Output Signal Analog Output
26 Power Supply Load Driving Capacity 230 VAC/* *
27 Accuracy Response Time Note 2 100 ms
28 Repeatability Output Signal Note 2 4-20mA Loop Power + HART
TRANSMITTER
29 Fill Fluid Wetted o-rings Material MFR Std. MFR Std.
30 Bolts Housing SS 316 Dicast Aluminum
31 Secondary Housing Required Yes
32 Process Connection Size & Rating Electrical Connection/Cable Entry 1/2" NPT
33 Allowable Temperature °C *
34 Over Range of Protection 130% of Range
35 Enclosure Class IP 67
36 RFI Compliance & Electromagnetic Compatability Required
37 Integral Meter Indication Scale & Unit Required, LCD Display *
OPTIONS 38 Hydrostatic Testing Yes
39 Tag Plate SS316, Tag Name to be printed
40 Communication Type HART Communication (with 4-20mA)
COMMUNICATION & 41 Baud Rate *
SOFTWARE 42 Communication With Internal Diagnostics PLC Yes
43 Hand Held terminal Yes
44 Manufacturer YOKOGAWA
45 Model Number RCUP1HS- 80BA20 -0C72-KF22-2-M61 /BG/P13/RT/TC
PURCHASE 46 Serial Number Purchase Order Number * OEF/GPP-2/PR/155+197/2022/VI146
47 Price *
48 Item Number *
NOTES:

1 *' - VENDOR to specify / furnish.


2 Vendor to suggest Flow Meter size to compensate provided process parameter in data sheet
3 Transmitter Accuracy including the combined effects of Linearity, Hysterises and Repeatability shall be equal to or better than +/- 0.05% of calibrated
span or better , temperature effects at calibrated span will be at 50 Deg cel.

DOCUMENT:

1 Data sheets.
2 Calbration Certificate.
3 Ingress Protection rating compliance certificates and ATEX Certificates.
4 Test reports of radiography, ultrasonic & MPI Inspection.
5 Test Certificate of Hydrostatic complete with duration and pressure records of each test.