MAN2994 7 FireFinder Plus AS7240 Inst Comm 1
MAN2994 7 FireFinder Plus AS7240 Inst Comm 1
MAN2994 7 FireFinder Plus AS7240 Inst Comm 1
Responding to a Fire
Access Level 1
The indicator will be illuminated. The applicable zone indicator will also be illuminated
if a Zone Board is installed otherwise details of the Loop, Sensor and Zones in alarm are displayed on the LCD as follows.
This control is used to silence the local buzzer. Pressing this button will silence the panel buzzer, which
sounds whenever there is a fire alarm or fault. The sound for a fire alarm is a steady sound where as for a
fault it is intermittent.
When the alarm devices are active (FACP is in the fire condition), activating this control will silence all alarms
excluding the External Alarm device.
Activating the control again, will resound the previously silenced alarm devices.
If a new alarm is recognised whilst the alarm devices are “silenced”, then all alarm devices shall resound.
Note: If Delays to Outputs have been configured, to investigate the delayed Alarm condition press the “Next” button
and “Enter” button.
Previous and Next controls are used to scroll the events on the LCD. The events being displayed
depends on the current selected view, ie Zone Mode or Device Mode.
When the “SEVERAL ALARMS” indicator is illuminated, then multiple fire alarms are present on the FACP.
In order to view the alarms the PREVIOUS and NEXT controls are used.
A Zone or Device can be disabled when in an Alarm or Fault condition by pressing the Disable button.
Note: The Alarm condition takes precedence and no alarms must be present for using this button to disable faults.
**Note: The “Disable” button will not clear the Fire Alarm condition. A subsequent “Reset” operation is required to
clear the Fire Alarm condition as per the requirements of AS4428-3:2010 clause 2.2.10.
MAN2994-7
This control is used to reset the FACP from the fire condition and to clear the system fault indicator.
When using the Reset button to clear a fire condition, alarm devices must have been silenced first by means
of Alarms Silence / Resound control.
Zone Disablement
Press
ZONE:______
ZONE:1
0:FULL ENABLE 1:FULL DISABLE
Device Disablement
Press the then enter Loop number, Press then enter device number.
LOOP:1 DEVICE:1
In either case the Disable LED will illuminate and the screen will display the disabled information
L1 D1 Z1
STAT:NORMAL /DISB
ZONES DISABLES 1 of 1
AC:2Z ALM:0 PALM:0 FLT:0 DIS:1
MAN2994-7
Contents
Responding to a Fire 2
Access Level 1 2
Access Level 2 – Default Access level when the door is opened. 2
Disabling a Zone / Device 3
Zone Disablement 3
Device Disablement 4
1 About This Manual 1
1.1 Introduction 1
1.2 General Requirements 1
1.3 References 1
1.4 Symbols 1
2 Introduction 2
2.1 System Overview 2
2.2 Key Features 2
2.3 Compliance 3
2.4 FACP Configuration Examples 4
3 FireFinder PLUS Description 5
4 Placing The Basic System Into Operation 7
4.1 Unpacking 7
4.2 Anti-Static Precautions 7
4.3 Working on the System 7
4.4 The Cabinet 7
4.5 Cabling Recommendations 9
4.6 Power Supplies and AC Mains Installation 11
4.6.1 Connecting the Mains Earth 11
4.6.2 Connecting 5 AMP Power Supply 11
4.7 CORRECT Power Up / Turn “ON” Procedure 12
4.8 Brigade / PSU Monitor Board 12
4.8.1 Battery Connections 14
4.8.2 Auxiliary 27 Volt Power 15
4.8.3 Monitored Inputs 15
4.8.4 Monitored Outputs 17
4.8.5 Relay Output Connections 18
4.9 High Current Interface Board 19
MAN2994-7
8.7 Global 53
8.8 Passwords (Level III) 54
8.9 Programming 55
8.9.1 Conv (Conventional) Zone 55
8.9.2 Device 56
8.9.3 Input 57
8.9.4 Output 58
8.9.5 Panel Based MCP 58
8.9.6 Sub Address 58
8.9.7 Zone programming 58
8.9.8 Extra Devices Detected 59
8.9.9 Mismatch Detected 60
9 Incoming Fire Alarm Signal 60
10 Accessing a Loop, Device or Zone 62
11 Modem / Programming / Debug Interfacing 63
12 Expanding the FACP with Compatible FireFinder PLUS Boards 64
12.1 Ancillary Services 64
12.2 Compatible FireFinder PLUS Boards 64
12.3 Expansion Board 65
12.4 8 Zone Conventional Board 66
12.5 16 Zone and 32 Zone Indicator Modules 67
12.6 8 Way Switch and Indicator Module 68
12.7 Zone Disable and Indicator Module 69
12.8 16 Way Input Board 70
12.9 8 Way Relay Board 71
12.9.1 Internal Relay Board 71
12.9.2 Remote Relay Board 72
12.10 8 Way Sounder Board 73
12.11 4 Way Fire Fan Module 74
12.12 4 Way Fan Termination Board 75
12.13 Bargraph Display Card 76
12.13.1 Mechanical 76
12.13.2 Front Panel Decal 76
12.13.3 Front Panel Controls 76
12.14 Communications Extender Board 77
MAN2994-7
12.15 SmartTerminal 77
12.15.1 Overview 78
12.15.2 Mechanical 78
12.15.3 Installation & Cabling 79
12.15.4 Setting the SmartTerminal Address 80
12.15.5 Operation 81
12.15.6 SmartTerminal Controls and Indicators 82
12.15.7 SmartTerminal Screen Format 82
12.16 Agent Release Control 85
12.16.1 Operation 85
12.16.2 Agent Release Module 89
12.16.3 Local Control Station 91
12.16.4 Agent Release Termination Board 95
12.16.5 Interface Wiring 97
12.16.6 Warning Signs 98
12.17 Occupant Warning Systems 103
12.17.1 Amplifier Board (25W and 50W) 103
12.17.2 Front Panel Switch and Indicator Module 105
12.17.3 Panel Interfacing 106
12.18 Printer 107
12.18.1 Indicators and Buttons 107
12.18.2 Maintenance 109
12.18.3 Printer Connections and Jumpering 111
12.18.4 Printer 5 Volt Power Supply 111
13 Expanding the System – Networking 112
13.1 Networking 112
13.2 Network Interface Card 112
14 High Level Interfacing 114
14.1 High Level Interface Expander (BRD43SPB) 114
14.2 High Level Interface Expander (BRD43HLI) 116
14.2.1 SmartView Graphics 116
15 Certification Information 117
16 Maintenance and Troubleshooting Chart 118
16.1 Maintenance 118
16.2 Troubleshooting FireFinder PLUS 119
MAN2994-7
1.3 References
ConfigManager PLUS: Operation Manual
Australian Standard:
1.4 Symbols
Important operational information
2 Introduction
2.1 System Overview
The purpose of the FireFinder PLUS Fire Alarm Control Panel (FACP) is to monitor changes in inputs, report
those changes and update selected outputs as programmed.
➢ Multiple input/outputs
➢ Agent Release
➢ Fan Control
➢ SmartGraphics
➢ Nurse Call
➢ SmartTerminal
2
MAN2994-7
2.3 Compliance
The FireFinder PLUS FACP is approved to AS7240 – 2 & 4 and AS4428 – 3:2010 and includes the following
‘Optional requirements’ as defined by AS7240-2:2004:
➢ 10 Disable condition
➢ 11 Test condition
The FireFinder PLUS PSE includes the following ‘Optional requirement’ as defined by AS7240-4:2004:
3
MAN2994-7
GROUND
CH16
CH15
NEUTRAL
D13 CN20
SWITCH
ACTIVE
L2+ L1-
DANGER
A
CN13
CN14
+VE
240V
CN15
CN3
-VE
+35V
EXT
4 3 2
CN1
CN2
L2+ L1-
CN11 CN18
B
c
1
a b
+35V
16 WAY
EXT
CN2 CN2 CN2
LOOP COMMS
c
a b
U15
+ -
L2+ L1-
POWER
RN20 RN17
A
CN2
SLAVE CPU
SLAVE CPU
SLAVE CPU
+35V
EXT
L2+ L1-
CPU BOARD
B
+35V
EXT
U13
CN1
CN1
CN1
U14 1
20 WAY
U11
POWER
N/O
SUPPLY
C N/C
CH8 CH8 CH6 CH8
UNIT
RELAY 4
U10
CN3 CN1
N/O
TP3
D14
PSU MONITOR
CN10
SERIAL RELAY
C N/C
CN16
10 WAY
BRIGADE I/F
BRD OR
RELAY 3
27V IN
C12
CN7
N/O
AGENT TERM BRD BRIGADE
CN6
R17
C N/C
CN8 MODEM
TH1
CN21
RELAY 2
CH1 CN2
CN4
CH2
OR O/P TERM
N/O
CN3
CN1
C N/C
RELAY 1
3 WAY ZD7
N/O
CN2 POWER TX1
-
AUX OUT 2
CN4
26 WAY
+
AUX OUT 1
-
BAT- BAT+ 0V +27V
+
E. BOARD SW. POWER
POWER
TB10
CN3
E. BOARD CONTROL
SGD
CN1
O/Ps
FAN CONTROL,
AGENT RELEASE, HPCI
OWS CONTROL OR
SWITCH & INDICATOR
X- PRINTER
C/W MOUNTING
PLATE. CABINET BACKPAN VIEW
SHOWING MODULES FITTED
TO THE BACKPAN
AND WIRING DETAILS
PRINTER PSU RESET COMMS IN
+ - SHD ZD 1
COMMS OUT
+ - SHD ZD 2
NETWORK
C4
C5
SW1
CN1
C/W CABLE
CN3
R3
26/07/2010
INTERFACE
MASTER
D1 TB1 TB2
LK1
HEARTBEAT
BRD86NIC1-
SHIELD
LINK
N1236
ISOLATED
D6
BOARD
COMMS
SW3
D11
D12
D 13 D 14
CN4 RX IN TX IN RX OUT TX OU T
POWER
D16
ZD 13
ZD 11
ACTIVE
CN5 CN6
CH15
CH15
16 WAY
SLAVE CPU 2
SLAVE CPU 3
NEUTRAL
SLAVE CPU 4
GROUND
CPU BOARD
ACTIVE
+VE
-VE
CN10
L(AC) N(AC) (AC) -V -V +V +V
10 WAY
PSU MONITOR
BRIGADE I/F
CN7
ZD7
CN6
CN8
CH2
CN1
CN5 PRINTER
3 WAY
POWER
RJ45/8 PIN SUPPLY
UNIT
AGENT RELEASE
GENERAL MODULE OR
INDICATOR FIRE FAN CONTROL
CARD MODULE
POWER OK
2+ 3+ 4+
BATT
MONITORED INPUTS
COMMS FAIL
ANCILLARIES or
CN11
1+
CN11
RS485
COMMS.
HOUSING BLANKS
COMMS.
C
OUT
4-
CN10
4+
CN10
MONITORED OUTPUTS
RS485
3-
COMMS.
COMMS.
20 WAY
IN
2+ 2- 3+
SLAVE CPU
1-
SLAVE CPU
SLAVE CPU
SLAVE CPU
1+
3 WAY
C N/C
RELAY 5
8
5
RELAY 4
BLANK
N/O C N/C N/O C N/C
BRIGADE
RELAY 3
NETWORK
RESET COMMS IN COMMS OUT
+ - + -
PSU MON.
SHD ZD1 SHD ZD2
C4
C5
SW1
EXPANSION BOARD
CN1
CN3
RELAY 2
R3
26/07/2010
INTERFACE
MASTER
TB1 TB2
BOARD
D1
LK1
MAIN BOARD INTERFACE
D2
HEARTBEAT
BRD86NIC1-
SHIELD
LINK
N1236
C N/C
BOARD
RELAY 1
D6
N/O
ISOLATED
-
AUX OUT 2
COMMS
BLANK
+
SW3
D11
D12
D13 D14
AUX OUT 1
-
BAT+ 0V +27V
+
POWER
TB10
CN3
E. BOARD CONTROL
X- PRINTER SGD
CN1
ZD11
ZD13 O/Ps
ACTIVE
CN5 CN6
CABINET
TO BATTERIES
The heart of the FireFinder PLUS consists of two boards collectively known as the Controller. These boards
are the Main Board and the CPU Board. Combining these two boards with a front panel forms the basis for a
FireFinder PLUS FACP. A single Controller without an expansion board has the capacity to interface to four
(4) Slave CPU’s modules. These Slave CPU’s can be used for Loop Termination Boards.
The Main Board has the Slave CPU Board for the first Loop Termination Board and the provision for mounting
of up to three additional Slave CPU’s to interface to loops 2 - 4. The Slave CPU’s all have the same software
installed and the manner in which they operate is automatically determined by the type of termination or
interface board onto which they connect.
If the system is to be expanded to have more than four Loop’s an Expansion Board is required. This board
contains Slave CPU No. 5 and expansion sockets for three more to interface to loops 6 - 8. This configuration
allows for a maximum number of 8 Slave CPU’s that any one Controller can accommodate.
RESET BACKLIGHT
S W1
EXPANSION
CN17
MAIN BOARD MODULE
RS485 COMMS TO
CN20
SLAVE 4 SLAVE 3 SLAVE 2 BACKPAN BOARDS
CN100
4 CN13 3 CN14 2 CN15
CN11
NETWORK LOOP
LOOP COMMS
EXTERNAL LOOP
CN18
COMMUNICATION
COMMS
CONNECTS TO NIC
S W2
NODE ADDRESS
12 3 4 5 6 7 8
NODE ADDRESS
SLAVE CPU 4 SLAVE CPU 3 SLAVE CPU 2
TERMINATION BOARD
CN23
THE MAIN BOARD
IS FITTED WITH
CN2
CN2
CN2
CN10
SLAVE CPU 1
CN10 TO LOOP
DEBUG
DEBUG
DEBUG
LK1
LK1
LK1
TERMINATION BRD
MAIN CPU 1
TP1
TP1
TP1
27V IN
CN26
27VDC IN
+5V RS485 EOL
COMMS 2 LK2 BUZZER C N9 PRINTER 27V
BUZZER
PSU MONITOR
RS232 INHIBIT
BRIGADE I/F
OUT CN16
EXPANSION
LK3
MODULE
CN7
CN27
KEY SWITCH
0V CN21
COMMS2 RS232 (TOP) C N8
C N6
COMMS 3
CN25 EXTRA CONTROLS
COMMS1 C N2
C N3 C N4 FRONT PANEL PRINTER C N5
RS232/MODEM BZ1
+
C N1
(BOTTOM) EXPANSION PANEL USB
EXPANSION LEDS
SLAVE CPU 5
ON BOARD SLAVE CPU 6 SLAVE CPU 7 SLAVE CPU 8
CN2
CN2
CN2
CN5
DEBUG
DEBUG
DEBUG
LK1
LK1
LK1
TP1
TP1
TP1
5
MAN2994-7
FireFinder PLUS has an internal RS485 communication bus that allows for various ancillary boards (add on
modules) to be connect to the panel. These boards can be used to control and monitor field plant equipment
or the addition of an agent release module.
Where the system design exceeds the capability of one FireFinder PLUS then other FireFinder PLUS panels
can be networked together to provide an expanded system containing multiple boards in a variety of
applications.
➢ SmartTerminal
➢ SmartGraphics
A Network FireFinder PLUS System supports a combination or all these options on a single network. Each
panel on the network is regarded as a “node”. The NETWORK BUS is accessed using a Network Interface Card
(BRD86NIC). The network configuration determines whether a NIC is required. Configurations can be;
Master / Sub FACP: Where there is one or more FACP’s configured as local panels then each report the status
of their associated zones/devices to a MFACP. There is no control between local panels as the MFACP is
structured to have full control of the entire system.
Peer to Peer: Each FACP user can take control of the entire fire system from any FACP.
Data Gathering Panel: The use of this type of panel may be installed where there is a need to have field
terminations only at one location and all control is performed by an FACP that is remotely located.
SmartTerminal: Provides the user with the ability to monitor the status of designated areas or an entire site
as well as execute specific interrogation tasks.
6
MAN2994-7
✓ 003 keys
➢ The cabinet is available in four different styles. Each style has the capability of being either
surface or flush mounted. With flush mounting though a surround is required.
➢ Normally painted Surf Mist Ripple. Other colours are available on request.
➢ The inner and outer door hinges are mounted on the left-hand side of the cabinet which
allow the doors open to an angle of 100º. A keyed entry is provided
➢ Knockouts are positioned on gland plates and a cut out is available on the rear of the
cabinet to simplify cable entry. Mounting The Cabinet
Note: It is recommended the cabinet should be installed in a clean, dry, vibration-free area.
Open the front door. Use the keyhole mounting holes in the top corners and the two holes along the bottom
of the unit to mount it on the wall. Cables to connect the system to its external actuating devices are brought
in through the knockouts on the top or bottom of the cabinet.
7
MAN2994-7
R 3 mm
12 mm
R 6mm.
Figure 5: Example SP1 Back Pan Mounting Hole & Removing Knockouts
8
MAN2994-7
Cabled in red Twin Plastic Sheath (TPS), Fire rated Radox or approved equivalent.
Analogue Loop
Two core cable. The minimum cable size is 0.75mm 2, the maximum loop resistance is 50 ohms and the
maximum loop distance is 2km.
RS 485 Network
Single twisted pair screened (2 core) cable originating from FACP extending through the protected areas and
returning to the FACP.
Cable Specifications
SmartTerminal
Single twisted pair shielded cable (2 core) plus 2 core power, or local supply. Maximum distance between
from the last SmartTerminal and the FACP is 1.2km.
Single twisted shielded cable (No return loop) plus 2 core power or local supply.
Maximum distance between each LED repeater card and FACP is 1.2km.
Hartland HC2335
Belden 9841
Radox FR Communication
Two core 1.5mm2 PVC sheathed MIMS (Mineral Insulated Metal Sheathed) to the bell location.
Two core 1.5mm² PVC sheathed MIMS from the FACP to the Telecom MDF.
9
MAN2994-7
The requirement for the mains supply to the FACP is fixed wiring, using three core cable (no less than
0.75mm and no more than 2.5mm ) or a suitable three conductor system, fed from an isolating switch fuse
spur, fused at 3A. This should be secured from unauthorised operation and be marked 'FIRE ALARM: DO NOT
SWITCH OFF. The Mains supply must be exclusive to the FACP.
Important: Under no circumstances should the FireFinder PLUS be operated without the
Power Supply PCB correctly mounted in the enclosure and the retaining screws securely tightened.
10
MAN2994-7
These supplies will be either mounted in the upper or lower right hand corner of the cabinet with the Brigade
Board mounted in close proximity.
The wiring should enter the cabinet through the nearest knockout entry hole on that side.
Refer to Figures 6 - on for the wiring and fusing details for each supply.
The earth cable closest to the cabinet body shall have an M4 SPW beneath the lug then an M4 SPW and M4
nut.
Each additional earth cable shall be terminated with an M4 SPW and M4 nut.
An additional M4 nut and M4 SPW are fitted to the Chassis Earth Terminal for installers to connect their
Mains Earth.
11
MAN2994-7
Connections
Relay Information
Inductive loads fitted to the Brigade PSU Monitor Board MUST be fitted with “Flyback” diodes at the
load for back EMF protection.
Transient Protection
Recognised transient line protection methodologies at the FACP and the load MUST be considered
when connecting any control devices to the outputs be they in close or remote.
12
MAN2994-7
EXT TEMP
LK1
JTAG
MON EN
CN2
E TH
CN12 POWER OK
MONITORED
1+ 2+ 3+ 4+
MONITORED INPUTS
BATT
INPUTS FLT.
( EOL's Required )
COMMS FAIL
TB8
Note:
CN11
If a diode is NOT fitted CN11
RS485
internally to a bell / sounder
N1236
C58
C56
COMMS.
COMMS.
C
a diode MUST be fitted as OUT
shown - fit 1N4004 or similar ZD8
4-
BRD86BPSC4-
Bell
CN10
4+
EOL
MONITORED OUTPUTS
ZD4
ZD3 U8 D11 C36 CN10
10K To CN20 of the Main
EOL
ZD7 RS485
2 + 2- 3 + 3-
COMMS.
COMMS. Controller Board
Ohms
M16
IN
ZD2
TB7
U7 D10 C35
ZD6
MONITORED OUTPUTS
22/09/09
( EOL Required ) ZD1 U6 D9 C34
1-
ZD5
Sounder
EOL
1+
10K M10
U5
N/O C N/C N/O C N/C N/O C N/C N/O C N/C N/O C N/C
RL5
TB6
Relay M9
U2
T1
1
(Normally C43
Energised) M8 M15
RL4
RELAY 4
Isolate
TB5
M7
Relay
L6
M6 M14
Relays are
R75
RL3
Warning
RELAY 3
TH9
Programmable
TB4
R108
System M5 CN8
Default Setup
Alarm
Q5
R103
Shown
M4 M13
RL2
RELAY 2
HSNK2
Fault TH5 CN7
TB3
M3
Relay
L7
HSNK1
M2 M12
CN6
RELAY 1
Alarm
TB2
TH8
M1
L8
Relay
RL1
D7 CN4 to 8 Supplies
M11
AUX OUT 2
1A / Connector
Q8
TH1
L9
TB1
2 x AUX OUT
27VDC @ 2A CN4
AUX OUT 1
TH4
TH7
TH2
AUX OUT 1
BAT- BAT+ 0 V +27V
+
E. BOARD CONTROL
SGD
CN1
O/Ps
TB9
Note: When connecting to the Brigade PSU Monitor board transient and “Flyback” (Back EMF) protection
methodologies MUST be applied.
13
MAN2994-7
A red and black lead coming from TB1 on the Brigade Board will be clearly seen in the same area, this lead is
to be connected to the batteries red to positive and black to negative once the system is operating on Mains
supply.
Battery size is dependent on the system configuration and can vary from 12 AHr to over 100 AHr.
Note: Refer to Ampac’s battery calculation tool to calculate the required battery size.
EXT TEMP
LK1
JTAG
MON EN
CN2
ETH
CN12 POWER OK
1+ 2+ 3+ 4+
MONITORED INPUTS
BATT
FLT.
TB8
CN11
CN1 1
RS4 85
N1236
C58
C56
CO MMS .
COMMS.
C
OUT
ZD8
4-
BRD86BPSC4-
CN10
4+
MONITORED OUTPUTS
ZD4
ZD3 U8 D11 C36 CN1 0
EOL
ZD7 RS4 85
2 + 2- 3 + 3-
CO MMS .
COMMS.
M16
IN
TB7
ZD2 U7 D10 C35
ZD6
22/09/09
ZD1 U6 D9 C34
1-
ZD5
1+
U5
M10
N/O C N/C N/O C N/C N/O C N/C N/O C N/C N/O C N/C
BRIGADE
RELAY 5
RL5
TB6
U2
M9
T1
1
C43
M8 M15
BOARD
RL4
RELAY 4
- + - + TB9 TB5
M7
M6 M14
L6
R75
RL3
RELAY 3 TH9
TB4
CN8
R108
M5
+27VDC
Q5
R103
M4 M13
RL2
RELAY 2
from PSU
HSNK2
TH5 CN7
TB3
M3
L7
HSNK1
M2 M12
CN6
RELAY 1
TB2
TH8
M1
L8
RL1
D7
M11
CN5
- + -
AUX OUT 2
Q8
TH1
L9
TB1
CN4
AUX OUT 1
TH4
TH7
TH2
- + POWER
TB10
CN3
E. BOARD CONTROL
SGD
CN1
TB9
O/Ps
+ -
Battery 1 Battery 2 HPCI
+27VDC
12 Volts 12Volts from PSU
TB9 is located on the bottom Battery 1
12 Volts
+
- +
-
Battery 2
12Volts
14
MAN2994-7
LK1
JTAG
EXT TEMP
MON EN
CN2
ETH
CN12 POWER OK
2+ 3+ 4+
BATT
FLT.
MONITORED INPUTS
COMMS FAIL
TB8
CN11
1+
CN11
RS485
N1236
C58
C56
COMMS.
COMMS.
C
OUT
ZD8
4-
BRD86BPSC4-
CN10
4+
ZD4
ZD3 U8 D11 C36 CN10
MONITORED OUTPUTS
EOL
ZD7 RS485
3-
COMMS.
COMMS.
M16
TB1
IN
3+
ZD2 U7 D10 C35
TB7
ZD6
2+ 2-
22/09/09
ZD1 D9 C34
+ - + -
U6
1-
ZD5
1+
AUX OUT 2 M10
U5
C N/C
2 X LIMITED 2A BRIGADE
RELAY 5
RL5
U2
TB6
M9
T1
1
N/O C N/C N/O
C43
BOARD
RL4
RELAY 4
TB5
OUTPUTS
M7
L6
M6 M14
AUX OUT 1
R75
RL3
TH9
RELAY 3
TB4
CN8
R108
M5
Q5
R103
M4 M13
RL2
HSNK2
CN7
RELAY 2
TH5
TB3
M3
L7
HSNK1
M2 M12
N/O C N/C
CN6
RELAY 1
TB2
TH8
TB1 is located in the lower
M1
L8
RL1
D7
M11
left hand side of the board CN5
- + -
AUX OUT 2
Q8
TH1
L9
TB1
CN4
AUX OUT 1
TH4
TH7
TH2
BAT- BAT+ 0V +27V
+
E. BOARD SW. POWER
POWER
TB10
CN3
E. BOARD CONTROL
SGD
CN1
O/Ps
HPCI
+27VDC
from PSU
- +
+ -
Battery 1 Battery 2
12 Volts 12Volts
➢ Manual Call Point (MCP) – if activated the FACP will go into alarm. Connected to the MCP on
the front of the FACP.
➢ Class Change – if activated all Alarm Devices/Sounders and Alarm Device/Sounder Outputs
in Sounder Group 1 are turned on.
➢ External Fault – if activated the FACP will indicate a Fault condition
➢ Ancillary Disable - if activated, the FACP’s “DISABLED” and ANC OUTPUT STATUS LEDs will
both be turned on. Note that this event is used to indicate an ancillary/auxiliary disablement
or a door-opened condition if a door switch is fitted. It also activates any Relays on the
Brigade board configured as “Isolate” relays and affects the Brigade Board’s “Aux/Anc”
outputs based on their “normally energised” settings.
➢ Evacuate – if activated the FACP goes into Evacuation.
➢ Sounder Silence – if activated all activated sounders are silenced.
➢ Reset – if activated a Master Reset is initiated.
➢ Fire/Feedback - if activated, the FACP’s “Fire Output On” LED will flash (AS7240.2 Clause
7.9.2). Note that this is a latched condition and will only be cleared a “Master Reset”
command from the FACP.
➢ General Purpose – for use in Functions (Cause and Effects)
15
MAN2994-7
• Input 1 – MCP
• Input 2 – Evacuate
• Input 4 – Reset
The inputs have been designed to operate with a programmable EOL of 3K3Ω, 10KΩ 22KΩ or Unmonitored
(no EOL) the 10K EOL is the default. The normal and active ranges change according to the end of line
selected.
LK1
JTAG
EXT TEMP
TB8 location
MON EN
CN2
ETH
CN12 POWER OK
2+ 3+ 4+
BATT
FLT.
MONITORED INPUTS
Note: Door Switch is Open for Normal Operation and not Monitored
COMMS FAIL
TB8
CN11
1+
CN11
RS485
N1236
C58
C56
COMMS.
COMMS.
C
OUT
ZD8
4-
BRD86BPSC4-
CN10
4+
ZD4
ZD3 U8 D11 C36 CN10
EOL
MONITORED OUTPUTS
ZD7 RS485
3+ 3-
COMMS.
COMMS.
M16
IN
ZD2 U7 D10 C35
TB7
ZD6
2+ 2-
Door Switch TO TB11
22/09/09
ZD1 U6 D9 C34
1-
ZD5
1+
TB8 / C TB8 M10
U5
C 1+ 2+ 3+ 4+
BRIGADE
RELAY 5
RL5
U2
TB6
M9
T1
1
C43
BOARD
M8 M15
RL4
RELAY 4
TB5
M7
L6
M6 M14
N/O C N/C N/O C N/C N/O C N/C
R75
RL3
TH9
RELAY 3
TB4
CN8
R108
M4 M13
RL2
TH5
TB3
M3
L7
HSNK1
M2 M12
CN6
EOL
RELAY 1
TB2
TH8
M1
L8
TO
RL1
D7
10K 4K7
M11
CN5
- + -
AUX OUT 2
Ohms
Q8
TH1
L9
TB1
CN4
AUX OUT 1
TH4
TH7
TH2
E. BOARD CONTROL
SGD
CN1
O/Ps
HPCI
+27VDC
from PSU
- +
+ -
Battery 1 Battery 2
12 Volts 12Volts
16
MAN2994-7
➢ Alarm Devices - activated when any of its four sounder groups is active. (AS7240.2 Clause
7.7 and 7.8). The output is turned off during an Alarm (sounder) disable or Alarm (sounder)
silence condition.
➢ ASE – (Australia Firefinder Plus Only)
➢ Fire/FARE – activated by alarm condition (AS7240.2 Clause 7.7 and 7.9.1). The output is
turned off during a FIRE disable condition.
➢ Ancillary - activated on device alarm conditions. The Output is turned off during an Ancillary
disable condition.
➢ Warning System - activated on evacuation and device alarm conditions. The output is turned
off during an Alarm (sounder) disable or Alarm (sounder) silence condition.
➢ Fault - activated on all fault conditions (AS7240.2 Clause 9.9). The output is turned off during
a FAULT disable condition.
➢ General Purpose – activated via the Configmanager “Function” programmed logic.
➢ External Alarm Devices - activated by an Alarm condition when a Point (Detector) has been
configured as Fire/FARE. (AS7240.2 Clause 7.7 and 7.8). The output is turned off by the
removal of the alarm condition – Silence Alarms followed by Reset.
These monitored switched outputs, supply a nominal 24VDC, at up to 1 Amperes. Monitoring is for short,
open and earth faults when the output is OFF.
The outputs have been designed to operate with a programmable EOL of 3K3Ω, 10KΩ 22KΩ or Unmonitored
(no EOL) the 10K EOL is the default.
Warning systems and sounders are connected to the Brigade / PSU Monitor Board as shown below. If more
sounders are required, the Sounder / Bell Control Board must be used.
EXT TEMP
LK1
JTAG
M ON EN
CN12 POWER OK
1+ 2+ 3+ 4+
MONITORED INPUTS
BATT
CN11
CN11
RS485
N1236
C58
C56
COMMS.
COMMS.
C
O UT
BRD86BPSC4-
CN10
4+
MONITORED OUTPUTS
ZD4
4+ 4-
ZD7 RS485
2+ 2- 3+ 3-
COMMS.
COMMS.
M16
Bell
IN
ZD2
TB7
U7 D10 C35
ZD6
22/09/09
ZD1 U6 D9 C34
1-
ZD5
1+
TB7 U5
3+ 3-
M10
N/O C N/C N/O C N/C N/O C N/C N/O C N/C N/O C N/C
RELAY 5
BRIGADE
RL5
TB6
U2
M9
Sounder
T1
1
EOL
C43
BOARD
M8 M15
EOL
RL4
RELAY 4
10K
TB5
M7
L6
TH9
RELAY 3
TB4
R108
M5 CN8
Ohms
Q5
R103
M4 M13
RL2
RELAY 2
HSNK2
TH5 CN7
TB3
M3
L7
HSNK1
M2 M12
CN6
RELAY 1
TB2
TH8
M1
L8
RL1
D7
M11
CN5
Warning System
- + -
AUX OUT 2
Q8
TH1
L9
TB1
CN4
AUX OUT 1
TH4
TH7
TH2
E. BOARD CONTROL
SGD
CN1
➢ Alarm - activated on device alarm conditions and “Function” programmed logics. The relay
is turned off during a ALARM disable condition.
➢ Sprinkler - activated on device alarm conditions and “Function” programmed logics.
➢ Fault - activated on all fault conditions and “Function” programmed logics. The relay is
turned off during a FAULT disable condition.
➢ Isolate - activated on all isolate conditions and “Function” programmed logics.
➢ Battery Fail - activated on battery fail conditions and “Function” programmed logics.
➢ Mains Fail - activated on a mains power fail condition and “Function” programmed logics.
➢ Warning System - activated on evacuation, device alarm conditions and “Function”
programmed logics. If the activation of this relay is due to an evacuation condition, then the
relay is turned off during an Alarm (sounder) disable or Alarm (sounder) silence condition.
➢ Ancillary - activated on device alarm conditions.
➢ General Purpose - activated via “Function” programmed logics
These outputs have been designed to be able to switch predominately resistive loads as listed below.
LK1
JTAG
CN2
ETH
CN12 POWER OK
1+ 2+ 3+ 4+
MONITORED INPUTS
BATT
FLT.
COMMS FAIL
TB8
BATT
CN11
CN11
C58
C56
COMMS.
COMMS.
C
O UT
FAIL ZD8
4-
BRD86BPSC4-
CN10
4+
MONITORED OUTPUTS
ZD4
ZD3 U8 D11 C36 CN10
EOL
ZD7 RS485
2+ 2- 3+ 3-
COMMS.
COMMS.
M16
IN
ZD2
TB7
U7 D10 C35
ZD6
NO CC NC NO CC NC NO CC NC NO CC NC
22/09/09
NO C NC NO NC NO NC NO NC NO NC ZD1 U6 D9 C34
1-
ZD5
1+
U5
M10
N/O C N/C N/O C N/C N/O C N/C N/O C N/C N/O C N/C
RELAY 5
BRIGADE
RL5
TB6
U2
M9
T1
1
C43
BOARD
M8 M15
Note:
RL4
RELAY 4
TB5
M7
1A Un-monitored
L6
M6 M14
R75
RL3
TH9
RELAY 3
TB4
R108
M5 CN8
M4 M13
RL2
RELAY 2
M3
L7
HSNK1
M2 M12
TH8
M1
D7
C: Common
M11
CN5
lower to mid left hand side of the board
- + -
AUX OUT 2
Q8
TH1
L9
TB1
CN4
AUX OUT 1
C
TH4
TH7
TH2
NC
E. BOARD SW. POWER
POWER
TB10
CN3
E. BOARD CONTROL
SGD
CN1
O/Ps
HPCI
+27VDC
NO
from PSU
- +
+ -
Battery 1 Battery 2
12 Volts 12Volts
18
MAN2994-7
The board plugs/connects into the Brigade / PSU Monitor Board (BRD86BPSC) and the 27V DC output from
the PSU is connected to TB1 of the BRD86HCI instead of TB9 on the BRD86BPSC
Connections
TB Function
1 27VDC PSU IN
2 Battery Out
3 27VDC Out
4 27VDC Out
9 Battery Out / 27VDC PSU IN
10 External Board / SW POWER
CN Function
1 - 27VDC 3A Max
5
19
MAN2994-7
The Main CPU is mounted on this board and connected to it by CN11. The main connection board then
provides interfacing to:
➢ A printer
➢ A Modem
➢ An Expansion Panel
Connections
20
MAN2994-7
R4 R5 R2
R1 C7 HY1 BACKLIGHT
C6 D1
BRD86MBA4- 30/06/10 Q6
C2
C3
C4
C1
D2 D3
R3
C8
C5 R6BACKLIGHT R62 C17
U1 C9 C10 C11
R7
SW1 R63
CN17 EXPANSION
C14
L1 C13
U4 U5 U6 Q1 MODULE
RN1
C12
RESET
C15
U2
C16 CN22 R8 LCD BACKLIGHT INVERTER
R9
R11 CHINESE N1236 U7
R12
GRAPH R13
CN20
R10
LCD
U3
CN15
TP69
L2
R14
R16
R15 SLAVE 4
CN13 SLAVE 3 CN14 C21
SLAVE 2
C18 CN100
C20
4 3 2
D4 CN11 U8
C22
CN19
NON-CHINESE
C23 C24 C26
R17 C25 C27 U10
C29
CN12 U13 U14 U15 CN18
CHAR LCD
C28 RN2
U11 U12
CN12
C30
U35
C31
U16
CN19
RN3
RN4
DEBUG R18 C33 TP3
C32
R65
C88
R67
LK1 U20
C34
C36
1 2 3 4 5 6 7 8
U18 C35
NODE ADDRESS
R66
TP4 X1
U17 Q2 Q8 SW2
U22
C38 C39
C40
D5
C41
R21
R22
D6
U19
C42 C43
C44
C45
U21 ZDN1
CN23 C46
C49
U23 R23
TERMINATION BOARD
U25 D8
C64
C57
JTAG
C58 R33 C59 CN10 R34
C60
U26
CN24 C62
C65
R35 C63 R36
C61
C67 R37 C66 R38
C68 R39
R47
R48
R46
R43
R41
R42
R44
R45
C85
C37
C87
C71 C72
1
C73 R49
27V IN CN26
R51 C74 C75
R50
U31
C80
D16
C81
PRINTER 27V U30
R56 D15 U33
D17
27V IN R25 R19 COMMS 2 C90 RN16
RN18
R59
PSU MONITOR
RS232
D11
LK3 R57
CN16
C89
C82
BRIGADE I/F
CN21 BUZZER
R20 R64
CN27 RN6
BUZZER C83
O UT
CN7
D10
EXPANSION
INHIBIT
CN6
MODULE
RN7
R61
RN17
COMMS1 RS232/MODEM (BOTTOM) U32
KEY SWITCH
0V D13
BZ1
+
CN8 EXPANSION PANEL EXPANSION LEDS CN3 USB FRONT PANEL CN1 PRINTER
Figure 15: Main Board Layout with no Main CPU or Slave CPU’s
21
MAN2994-7
Connections
C1 C18
D1 R1 Q1
R31 D18
D2 R2
D3 R32 D19
R3
D10
D13
D5 R34 D21
R5
D6 R6
D7 R7
D14 D16 R29 D17 R36 D23
R23
D8 D22
R8
R26
D9 R35
R9
U4 C14 U6 C16
U2 C4 R25 C15
C5 C13
BRD86FPB4-
U5 R38 D25
11/08/10 R30
N1236 U3
D28 R27 C11
R24
U7 D26
C6 R41 U8 R43 R39
C9 C10 R42
C12 C19
C7
R46
R45
R44
R10
R40 D27
R11
KEYSWITCH
L1
L3
L2
R12
C20
C21
L6
L7
L5
L4
R13
R15 C2 R47 D15
R14 R16 C17
Q2 U1 C22 CN2
R21
CN1
KEYSWITCH
22
MAN2994-7
➢ 16Mbytes of FLASH
Connections
CN1 USB
CN2 To Main Board CN11
R1 R2
U4
R9
C2 C3
R4
R7 CN1
C1
ZDN1
R5 USB
R6
U1
C4
C5
R8
R3
C7
C6
Q1
C8
R10
Q2
R11
R30
U2 U3 C9 X1
C11 C12 C13
CN2
C14
R28 C10
U11
C15
U6 U7 U5
R29
ZDN2
C16
C19 D1
C18
C20 C17
C23
U8 D2
R15 C26
C24 C25
U12
ZDN3
U13
C29
R17
R18
R19
C30
C27 R16
D3
C28
R20
C31
C34
R21
C33
C32
C35 Q3
R22
U15 R23
R24
C37
R26
C36 U14 D4
C41 R25 +
C40
C38 C45
C42
R27
C39 C43 C44
U16
0V
23
MAN2994-7
A single chip micro controller U7 controls all operations of the FACP Slave CPU. This device contains the
control program within Read Only Memory (ROM).
A unique feature of the Slave CPU is its ability to automatically sense the type of board it is connected to
without the user having to configure the board to suit.
Connections
C6 BRD86SCB3-
C2 C4 C5 LK1
C3 R2 D3
DEBUG
U1 U3
R1 C1
Q1 C7
CN3 U4 R5
C8
Q2
R24
COMMS
C10 D1
U2 R4 R27 R26 U5
C9 D2
TP1
C11 U7
C17
C15
C21
C19
R13
R12
R10
R11
R6
C14
C16
C18
C20
R8
U6
C12
C13
C23
C27
R7
RN1
R14
C31
CN1 JTAG
C33
CN2
TP3 TP2
C32
CN4 C34
TP4
C35 X1
TP5 R25 C36 C37
24
MAN2994-7
AMPAC strongly recommend that the LoopManager test set is used to check that the Apollo loop has been
correctly installed and commissioned before connecting it to the FireFinder PLUS.
Loop Parameters
Note: To achieve full current, the Loop Trip current in Loop Parameters needs to be set to 300mA
(ConfigManager PLUS)
CONNECTIONS
25
MAN2994-7
C2
R2
R3
C1
C3
R4
ZD1
ZD2
INDICATION/S
Q1
LOOP 1
R5
Q2 R20
R12 L1
U1 C6
R9
+
Q4 + TB1
R14
Q6
OUT IN INDICATES OUT Q8
D1
R23
ZD4
OUT ZD5 OUT
-
ZD7
ZD6
LOOP 1
R30
U2
-
Q7
R44 L2 R34 +
C15
+
IN
C16
ON OFF OK C17
Q9
LOOPU31 RETURN SENSE IN IN OUT
R39
R40
R37
R38
U4 U5 ZD9
IN R43
ZD12 -
- L1
ZD11
ZD10
LOOP 2 RETURN SENSEC21 LOOP 1 L1
SHORT CCT U6 D7 + R+
C27 R56
C24
R55
ON ON / OPEN CCT
R61
R50
R51
R52 R54 DC
R62
C26
R63
D5 D6 TH1
-
ZD14
Q10 Q13
R71
R57
R64 Q11 ZD13
R77
L3 R67
-R
IN L2
R66
U7 U8 C34
+ TB2 L2
Q15
C31
C36
Q17 R76
ZD15 OUT
ZD16
OUT
ZD18
-
R81
C35
C40 R84
ZD17
LOOP2 OUT
R83
C38
U9 L4 R92
Q16
R85
R86
R87
+
R97
C39
R89
Q18 C41
ZD20
IN
R93
ZD23 - L1
U10 IN C45 R100 L1
C46
LOOP2
ZD22 R+
+
D14
ZD21
R104
R105
C49 D12 U12
R109 C48 R103 DC
D13 C51 C52
R106
-
R108
R110 L2
C50
L7 TH2
C55 C56 -R
T0 SLAVE CPU
L5
C53
L6 LOOP 2 L2
CN1 C54
CN1 CN2
R111
R113
R112 R114 L8
L1
R115 C57
LOOP 2 CONTROL L1
R116
R119 C58
R120
R117
R118
R121
R122
LOOP 1 CONTROL
R+
R125 Q19
R123
R124
R128 Q20
C59 C60
R127 R130
C62
C63 R131 C64 R132 U14
C66
U13
L2
-R
C65
L2
R136 R139
R133
R134
Q25 Q26
C67
C68
R138
R135
Q23 Q24
R137
R144
R145 RN1 R147 RN2
R141 R143 R148
C69 R146 C70
R140 C72 R142 C74
C76
C79
R149 U18 D19 U20 D20
R152 R150
C71 C73
T0 SLAVE CPU C75 U15 C78
U16
R151
Q28
U17
Q27
U19
C77 C80
R161
C88
R159
R162
R163
R169
0V
R167
R168
N1236
R165
R164
C89
R170
R171
C91
R166
C90
R172
C92
XP95 Circuit
R173
C96
with one Detector
R178
-5V BRD86DLTB2-
U22
Having LED
R177
R179
R183
R182
C102
C99
U23
R184
C107
CN3 CN4 C105
D22 C109
C108
REGULATED - - L9
HSNK1
27VDC In / Out + +
- -
TH3
POWER
26
MAN2994-7
Note: Refer to Apollo Isolating specifications and guidelines for further details.
If a short circuit or abnormally low impedance occurs, the base isolates the negative supply in the direction
of the fault. When the short circuit is removed the power will automatically be restored.
Number of Isolators 0 5 10 15 20 25 30 35 40 45 50
Loop Current Total
MAX CABLE LENGTH USING 1.5mm².
(mA)
50 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
100 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
150 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
200 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 960
250 1000 1000 1000 1000 973 933 893 853 813 733 733
300 971 931 891 851 811 771 731 691 651 611 571
350 850 810 770 730 690 650 610 570 530 490 450
400 756 716 676 636 596 556 516 476 436 396 356
450 680 640 600 560 520 480 440 400 360 320 280
500 618 578 538 498 458 418 378 338 298 258 218
Number of Isolators 0 5 10 15 20 25 30 35 40 45 50
Loop Current Total
MAX CABLE LENGTH USING 2.5mm².
(mA)
50 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
100 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
150 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
200 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
250 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
300 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 952
350 1000 1000 1000 1000 1000 1000 1000 950 883 817 750
400 1000 1000 1000 1000 993 926 859 793 726 659 593
450 1000 1000 1000 933 867 800 733 667 600 53 467
500 1000 964 897 930 764 697 630 564 497 430 364
27
MAN2994-7
28
MAN2994-7
#1
The LCD is used to display abnormal conditions and for interrogation, control and programming activities.
When the FACP is in its normal state a default screen is displayed.
In access level 2 or higher the backlight shall always be ON. Alarm, Fault and Disable information is accessed
through the Main Menu.
#1
Is the intended area for the Alarm Routing Address Code. This area is not printed on the
Decal.
This control is used to silence the local buzzer. Pressing this button will silence the panel buzzer, which sounds
whenever there is a fire alarm or fault. The sound for a fire alarm is a steady sound where as for a fault it is
intermittent.
When the alarm devices are active (FACP is in the fire condition), activating the control will silence all alarms
excluding the External Alarm device.
29
MAN2994-7
Activating the control again, will resound the previously silenced alarm devices.
If a new alarm is recognised whilst in the alarm devices are “silenced”, then all alarm devices shall sound.
Note: If Delays to Outputs have been configured to investigate the delayed Alarm condition press the “Next”
button and “Enter” button.
Previous and Next controls are used to scroll events on the LCD. The events being displayed depends on the
current selected view.
When the “SEVERAL ALARMS” indicator is illuminated, then multiple fire alarms are present on the FACP. In
order to view the alarms the PREVIOUS and NEXT controls are used.
This control is used to reset the FACP from the fire condition and to clear the system fault indicator.
This control is used to reset the FACP from the fire condition and to clear the system fault indicator and won’t
function unless the alarm devices have been silenced by means of Alarm Silence / Resound control.
This control is used to disable collective zones and/or individual addressable points in alarm or fault.
This control won’t function unless the alarm devices have been silenced first by means of Alarm Silence /
Resound control.
**Note: The “Disable” button will not clear the Fire Alarm condition.
A subsequent “Reset” operation is required to clear the Fire Alarm condition as per the requirements of
AS4428-3:2010 clause 2.2.10.
➢ Zones – to provide an option to distinguish between zone inputs (sensors, detectors etc)
and zone outputs (sounders, beacons, monitored outputs
➢ Sensors – loop based
➢ Loop devices – where the inputs have been configured as alarm initiating
➢ Sounders – loop based and monitored outputs
30
MAN2994-7
This control is used to disable (and enable) individual Zones and/or Devices.
If the indicator is “ON” Steady when any Alarm Devices (including Outputs configured as Alarm Devices) are
disabled and flashes if Alarm devices are in fault. Disable has priority over fault.
This control is used to disable (and enable) all the ancillary outputs.
The indicator is “ON” Steady when Ancillary outputs are disabled and flashes if Ancillary Outputs have faults
present.
When the indicator is lit the control is used to override any pre-configured delays to outputs.
The indicator is “ON” Steady when a Delay is programmed and flashes when a Delay Timer is running.
This control is used to disable (and enable) the external alarm devices output.
If the indicator is “ON” Steady when any Ext Alarm Device output is disabled and flashes if Ext Alarm device
outputs are in fault. Disable has priority over fault.
The selection keys are used to select a loop device (or range of devices by using the TO key)
or select a zone (or range of zones).
Once a device or zone (or range) has been selected, the DISPLAY or DEVICE DISABLE/ENABLE
controls can be used.
Press this button followed by a number to select the loop you wish to access. e.g. LOOP 4.
31
MAN2994-7
After selecting the Loop number press this button to enter the device number for the device
to be interrogated.
Press this button followed by a number e.g. ZONE 4 to select the required zone.
Press this button after selecting the Zone number or the Loop and Device numbers to display the state of the
device. Meaning it is used in conjunction with the selection keys and alpha numeric keypad to DISPLAY a zone
or loop device.
Use this button to access a range of devices. E.g., 2 TO 7. The selection keys are used to select a loop device
(or range of devices by using the TO key) or select a zone (or range of zones).
Once a device or zone (or range) has been selected, the DISPLAY or DEVICE DISABLE/ENABLE controls can be
used
These buttons are used to navigate around the panel’s menus and enter data. If entering a descriptor, or
some other data that contains characters as well as numbers, pressing the buttons multiple times will scroll
through the available letters written on the button, in sequence. Eg. 1,A,B,C.
Used for data entry into the current field. If he current field is alpha numeric (descriptor strings), then the
alphas are active and selected by consecutive operations of the appropriate key.
The single arrows are used to select the entry (or insertion point) when entering data.
If the back arrow is used to move the entry point beyond the start of the current field – then the previous
data entry field will be displayed.
32
MAN2994-7
Press and hold the “display” button while using these buttons to adjust the LCD contrast
The double arrows are use to select the data entry field. These are mostly used when performing on site
programming and selecting the data entry field which is to be edited.
10 consecutive entry of this key exits the current access level to the default access level. For example, if the
current access level is “2”, 10 consecutive entry of this key will set the current access level to “1”.
Pressing the MENU button will display the main menu on the LCD.
Pressing the FUNCTION button will display the function menu on the LCD
➢ Fire – Steady
➢ Fault – Unsteady
- This indicator is illuminated when the FACP is in the fire condition. The fire
condition is latched until it is manually reset, by the use of the RESET control.
The FACP enters the fire alarm condition, when one of the connected fire alarm initiating devices is activated.
Fire alarm initiating devices can be loop based sensors, conventional detectors connected via the 8 way
conventional Add-On, or monitored inputs that have been configured as alarm initiating.
33
MAN2994-7
When this indicator is illuminated, the nominated fire output has been activated during a fire condition.
If the FACP has been configured to receive a feedback signal from the fire routing equipment – then this
indicator will flash at 1Hertz (½ second on and ½ second off) when the feedback signal is present.
- This LED will be illuminated when mains power is connected to the FACP and
switched on.
The indicator will also flash at 1 Hertz (½ second on and ½ second off) if the mains power has failed and the
panel is running from the secondary supply (batteries).
- This LED will be illuminated when there is a fault associated with the main
or secondary power supply the following conditions constitute a fault.
Faults are:
➢ Charger failure
➢ Battery voltage low
➢ Battery missing
➢ HCI missing
➢ PSU overload
- The indicator is illuminated when there is a main system CPU fault present in
the FACP. The indicator is latching and is cleared by activating the RESET control. System fault is caused by
- When the indicator is illuminated, the FACP is in any of the “Test” modes.
- When this indicator is lit, the FACP is in the fault condition. The fault condition
is non latching.
➢ Loop devices – missing, type mismatch, out of calibration / out of maintenance range,
extra (or unexpected device), device related faults (esp. Hochiki)
➢ Analogue loops – short circuit, open circuit or over current
➢ Monitored inputs with open circuit or short circuit conditions
➢ Monitored outputs – with open circuit or short circuit conditions
➢ Main power supply faults – mains missing, charger fault
➢ Secondary supply faults – low battery voltage, missing battery
➢ High Current Interface (HCI) faults – missing, overload
➢ Onboard module faults – missing, failed
➢ Add-On faults – missing, failed, type mismatch
➢ Main CPU failure -> watchdog condition
➢ Software checksum failure
➢ Memory checksum failure
- When this indicator is lit, the FACP is in the Disable (or isolate) condition. The
disable condition is latching.
➢ Zones – to provide an option to distinguish between zone inputs (sensors, detectors etc)
and zone outputs (sounders, beacons, monitored outputs)
➢ Sensors – loop based
➢ Loop devices – where the inputs have been configured as alarm initiating
➢ Sounders – loop based and monitored outputs
- When this indicator is lit, the FACP has had Alarm conditions silenced by the
use of the “Silence/Resound Alarm” button. The condition is latching until another alarm is sounded or the
alarm conditions are cleared.
35
MAN2994-7
SYSTEM IS NORMAL
This screen can be configured with the servicing company’s name and phone number via a laptop or modem.
The current date, time is set in the Function menu while system status is automatically displayed.
AC: is the current Access Level (ie 2Z is access level 2 Zone mode & 2D would be access level 2 device mode)
Keep the 'Display' button pressed while simultaneously pressing the '<' button to take the contrast down 1
level, the '>' to take up the contrast by 1 level, the '<<' to take the contrast down by 8 levels or the '>>' to
take the contrast up by 8 levels.
Note: This button combination will only work in access level 2 or higher.
36
MAN2994-7
A new panel has a pre-programmed password of 2222 for Level 2 and 3333 for Level 3.
Note: Only Authorised Service Technicians / Engineers have the ability to change passwords.
Note: All menus are provided with screen prompts and a “Quick Reference Guide” (see Section 22) guides
the operator through the operation of the FACP.
From the DEFAULT DISPLAY, press MENU or FUNCTION. The FUNCTION menu is password
protected (actually a pass-number as it can only contain numbers) to prevent unauthorised changes to the
panel's configuration.
➢ Level I: Allows access to indications and controls to investigate and respond to a fire or
fault warning.
➢ Level II: In addition to the level I facilities, quiescent, fire alarm fault warning, disable and
test conditions.
➢ Level III: In addition to the level II facilities, reconfigure specific data or control and
maintain the panel in accordance with the manufacturers’ specifications.
➢ Level IV: In an addition to level III trained and authorised by the manufacturer to repair or
alter the firmware of a panel.
1. Take note of the 4 digit password number displayed on the screen; then
2. Contact the AMPAC head office and quote the above number;
3. A temporary password will be issued and a new password can then be programmed into
the FACP.
Note: The temporary password becomes invalid if 9999 is entered again or if the panel is re-powered after
9999 has been entered.
37
MAN2994-7
Pressing the appropriate number on the keypad while in the MAIN MENU the user can view any;
7.1 Alarms
Pressing Displays all Alarms present on the system.
ZONE: 1
Zone 1
STATUS: ALARM
‘DATE’ ‘TIME’
ZONE ALARM 1 OF 1
DEVICE>
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0
Pressing the will display the Device Information the screen, pressing the will return it to
Zone Information
ZONE: 1
Zone 1
STATUS: STAGE 1 ALARM
‘DATE’ ‘TIME’
Pressing the will display the Device Information on the screen, pressing the will return it
to Zone Information
38
MAN2994-7
7.3 Pre-Alarms
Pressing Displays all Pre-Alarms on the system
ZONE: 1
Zone 1
STATUS: PRE-ALARM
‘DATE’ ‘TIME’
ZONE PRE-ALARM 1 OF 1
DEVICE>
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0
Pressing the will display the Device Information the screen, pressing the will return it to
Zone Information
7.4 Faults
Pressing Displays all Faults on the system
FAULT MENU
SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0
FAULT MENU
39
MAN2994-7
ZONE: 1
Zone 1
STATUS: FAULT
‘DATE’ ‘TIME’
ZONE FAULT 1 OF 1
DEVICE>
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0
Pressing the will display the Device Information the screen, pressing the will return it to
Zone Information
40
MAN2994-7
7.5 Disables
Pressing Displays all Disables on the system.
ZONE: 1
Zone 1
STATUS: DISABLE
‘DATE’ ‘TIME’
ZONE DISABLE 1 OF 1
DEVICE>
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0
Pressing the will display the Device Information the screen, pressing the will return it to
Zone Information
Note: If there are no disables, a message, e.g. ‘NO ZONES OR DEVICES OR SOUNDERS OR ADDONS
DISABLED’, will be displayed for 1 to 2 seconds and then the display will return to the Main menu.
NO ZONES OR DEVICES OR
ZONE: 1
Zone 1
STATUS: WALK TEST
TERMINATE<KEY 0>
ZONE WALK TEST 1OF 1
DEVICE>
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0
Pressing the will display the Device Information the screen, pressing the will return it to
Zone Information
41
MAN2994-7
7.7 Status
Pressing Displays the Status of the system
STATUS MENU
SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0
STATUS MENU
SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0
From the STATUS MENU the status of system components and settings can be selected and displayed as
listed below.
Note: Different screens are displayed for a system with and without networking.
Press
Loops: Enter the loop number and the LCD will display its status, e.g. normal, type of fault etc. The
Loop current draw and noise levels will also be shown in panels that have Slave CPU software version V9.0
or higher
LOOP NO:1
STATUS: NORMAL
CURRENT (mA) 0 NOISE (mA) 0
42
MAN2994-7
SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0
I/O: The LCD will display the status of an input or output in a panel or on a loop, Outputs and
Inputs .
0:OUTPUTS 1:INPUTS
SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0
SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0
Once entered the LCD will then display a description of what that input or output does and its current state.
43
MAN2994-7
Once entered, the LCD will then display the inputs, outputs, relays and auxiliary devices status.
0:NETWORK POINTS
1:REMOTE SLAVE MODULES
SELECT NO.
Network Points:
SELECT NO.
Apollo Loop 1
TYPE:APOLLO LOOP NO:1 VER: 6.1
NP:1 MOD:4 STAT:NORMAL
REMOTE MODULE STATUS
Note: The SYSTEM, AVALUES and ADD-ONS will increment by 1 if the network is configured
44
MAN2994-7
SYSTEM STATUS
ALARMS:000 PRE-ALARMS:000 DISABLES:000
DEVICE FAULTS:00 MOD FAULTS:00
LOOP FAULTS:00 EXTRA DEVICES:00
WALK TEST:00 WDOG:00
APP: V 1.0 EN54
CONFIG:
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0
Loop 1 sensor 1
L1 S1 Z2
STAT: NORMAL
AVALUE:25 MODE:0 I:000 O:000
0:PRINT ENTRY
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0
NODE: 000
MODULE (1-32):
45
MAN2994-7
7.8 Tools
Pressing allows for the Testing of the following selected fields
TOOLS MENU
SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0
ALARM TEST
0:ZONE 1:DEVICE
SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0
FAULT TEST
0:ZONE 1:DEVICE
SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0
Pressing initiates a LAMP Test. Which will scroll thru and illuminate all LED’s and LCD screen
46
MAN2994-7
7.9 Setup
Pressing Displays the setup for sounders, Zone Delay and Printer
SETUP MENU
SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0
SOUNDER MENU
SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0
PRINTER MENU
SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0
47
MAN2994-7
7.10 About
Pressing Displays the panel’s application software version number and the title information. Title
information could be company name, contact information and so on.
ABOUT MENU
VERSION#:1.01.00.AS7240
AMPAC TECHNOLOGIES
48
MAN2994-7
A prompt will ask for a PASSWORD if the control panel is not currently active. Using the keypad key in the
Level 2 or 3 PASSWORD.
SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
8.1 Date
Press To select the set DATE SCREEN. The prompt will ask for the date to be entered in this format,
DD/MM/YYYY (EG 01/01/2011), key in and press . The screen will then return to the MAIN
FUNCTIONS MENU.
DATE: DD/MM/YYYY
8.2 Time
Press To select the set TIME SCREEN. Then in the following format key in the time, HH:MM using the 24
hour mode. Press and the screen will return to the MAIN FUNCTIONS MENU.
TIME MENU
TIME: HH:MM
49
MAN2994-7
8.3 Day/Night
Press The DAY-NIGHT SETTINGS screen will appear. Time entry is the same as setting the “Time” facility.
Note this Function is available at Access Level 3 only.
SELECT NO
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
For this Function to have control it must be ENABLED by press Re-pressing will toggle to DISABLE.
8.4 Logs
Press to access the EVENT LOG MENU will be displayed.
The LOGS MENU allows the operator to select and view the events that have occurred.
SELECT NO
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Once the type of log is selected, e.g. FAULT, each entry can be viewed by stepping through them
The type of log, number and totals logged, date and time of the ALARM, FAULT, DISABLE, SYSTEM or I/O as
well as device information will be displayed. The SYSTEM screen displays events and watchdog activity. From
these screens the operator can select two other facilities, they are;
PRINT ENTRY will print out the displayed information if a printer is installed, or
SHOW OPTIONS allows the operator to select how the Logs are viewed.
To VIEW BY ENTRY NUMBER, to VIEW BY DATE or to PRINT MULTIPLE ENTRIES. In each case the
screen will ask for the appropriate information (ENTRY NUMBER or DATE) to be entered before the selected
option will be displayed.
50
MAN2994-7
8.5 TESTS
Press to access the TESTS menu. Note this is an Access Level 3 function only.
TESTING MENU
SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Press LOOP TEST requires the operator to select a LOOP for DIAGNOSTIC TESTING
Entering the LOOP number and pressing will initiate the DIAGNOSTIC TEST.
Note: The LED’s on the Brigade Board will indicate which leg is being tested.
Once the testing is completed the final screen will display the number of devices found and tested on the
LOOP and a Reset is requested to return the system to normal.
Note: If the data is not entered within 2 minutes the screen will time out and return to the DEFAULT SCREEN.
Note: A Loop Test needs to be conducted after a short / open circuit has occurred, corrected and cleared to
return the panel to its default Normal status otherwise the panel will display a loop fault.
This allows the user to turn on a device LED. Cancel out of the Device LED test screen will automatically turn
off the device LED. If the device LED test screen is left on after 30 minutes the LED will turn off and the panel
return to the Normal screen.
51
MAN2994-7
8.6 I/O
Press To display the Manual I/O Control menu
0: INPUT 1 :OUTPUT
SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Manual I/O control allows the technician to turn ON or OFF inputs and outputs off a device to facilitate testing
or isolation of plant during maintenance. Removal of manual control returns control to the panel.
SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Press
IN A PANEL: Enter the I/O Controller number then the input number. This will display the description for
the input and its current state, you can then turn the input ON or OFF or remove manual control.
ON A LOOP: Enter the loop number, the device number and the input number. This will display the
description for the input and its current state, you can then turn the input ON or OFF or remove manual
control.
ON A LOCAL ADDON MODULE: Will bring up the list of Modules that have inputs. These can then be
manually turned on and off with the exception off the MCP configured input
1: BRIGADE
2: 16WAY INPUT BOARD
SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
52
MAN2994-7
Remove All Manual Input Control: Will remove all manual input control.
Output Selected: Same sequences as above for inputs but substitute outputs for inputs.
Remove All Manual Control Selected: Globally removes all manual control.
8.7 Global
Press To display the Global Output Control menu (These operates across all panels on the network)
SELECT NO.
Press
FWRE OUTPUT:
ENABLE
DISABLE
FARE OUTPUT:
ENABLE
DISABLE
ENABLE
DISABLE
53
MAN2994-7
While in the Main Functions menu and enter the Level III Password if in Access Level II or, if in Access Level
III to display the Password Menu.
PASSWORD MENU
SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Add Password: Enter the new password, then press . The password is always a 4 digit number.
Delete Password: Enter the password that you want to delete, then press .
Delete All Passwords: This asks you to confirm that you want to delete all the passwords. Press
then again.
54
MAN2994-7
8.9 Programming
Press To display the Level III Programming Menu.
SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Key in the zone number and enter or change the description (DESC) by pressing buttons
to move the flashing underline or curser. The numeric buttons multiple times to access characters while at
the same time using
By going through all the fields a second screen can also be accessed to show the Output options.
55
MAN2994-7
The buttons are used to set the Y/N field, which is the selected Zone that will activate
the Brigade Options ALRM, BELL etc and Config.
EDIT Z CONFIGURATION
CONFIG: LATCHING
Configuration settings are Latching, Non-Latching, AVF, Self Reset ( 0 to 99 seconds ). After setting the
Configuration the ZONE I/O GROUPS are programmed.
After scrolling through the groups and entering what I/O GROUPS will be turned on by what module/s or
device/s in a zone/s the operator is prompted to press to confirm the entries and / or changes.
8.9.2 Device
Press DEVICE:
Use these buttons to EDIT and move through wording & numbering
Use these buttons to MOVE between fields i.e.: DESC & TYPE and next parameter
Enter the and number then scroll through the following screens.
56
MAN2994-7
Press or Press
To EDIT or to DELETE
TYPE SMOKE
2. Allocate / Edit the Device to a Zone and set the device type then. Press
3. Set /Edit and display the Output Configurations or options then. Press
4. Set / Edits and enables / disables the day/night settings then. Press
After scrolling through the groups a prompt tells the operator to press to confirm the changes.
8.9.3 Input
Press INPUT:
By following the screen prompts as above Edit or Delete an INPUT in a panel or a loop.
IN A PANEL ON A LOOP
I/O MODULE LOOP
57
MAN2994-7
8.9.4 Output
Press OUTPUT:
By following the screen prompts as above Add, Edit or Delete an output in a panel or on a loop.
Enter or change the description ( DESCR ) by pressing buttons to move the flashing underline or curser. Press
the numeric buttons multiple times to access characters.
Press the key to edit the next field (Day Night Settings).
• A/B/C/D/N field for the “DAY MODE SETTING” and “NIGHT MODE SETTING where “A, B, C”
refers to “Dependency A, B, C” respectively, “D” refers to “Delay to Outputs” and “N” refers
to “Normal” (i.e. no mode setting).
58
MAN2994-7
DAY / NIGHT
MCP OVERRIDE: N / N
DELAY ALARM DEVICE: N / N
DELAY FARE: N / N
[USE < OR > TO EDIT]
[USE << OR >> TO NAVIGATE]
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
The keys are used to set the Y/N field for the "MCP OVERRIDE, DELAY ALARM DEVICE,
DELAY FARE”.
To resolve select FUNCTION, enter PASSWORD, press and the screen below will appear
59
MAN2994-7
PROGRAMMING MENU
0: RESOLVE EXTRA MODULES AND DEVICES
1: ON SITE PROGRAMMING
SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Select (Selecting presents the PROGRAMMING MENU) then or (as seen below) then ENTER to ADD
the module or device to the configuration, or skip to resolve the changes manually in the Programming Menu.
(Device Type) or (Mode) to resolve the mismatch, OR On Site Programming to resolve manually.
Loop 1 Sensor 1
L1 S6 Z1 STAT: TYPE MISMATCH
ZONE FAULTS 1 of 1
Self Learn is enabled / disabled in the EEPROM programming. If enabled FireFinder PLUS has the ability to
detect extra or missing modules or devices, (that is devices or modules that have been added or removed)
or there has been a change of the type of module or device.
Note: If a change does occur the FACP will take 30seconds to register the event on the LCD and illuminate
the FAULT LED.
60
MAN2994-7
The LCD will always display the first fire alarm signal received in the top section of the LCD. The lower section
of the LCD will also permanently display the most recent zone in alarm. Other essential fire
buttons. After 30 seconds if no button is pressed the top section of the display will revert to displaying the
first zone in alarm.
Note: The displayed information changes to that associated with the device as the
push buttons are pressed. If there is a fault condition or a fire alarm and
61
MAN2994-7
LOOP OR DEVICE
➢ Press the button if you wish to access a range of devices on the loop,
ZONE
62
MAN2994-7
C89
C82 LK3
CN21
C83
BUZZER
R20 R64
CN27 RN6
BUZZER
INHIBITCOMMS PORT 3 OUT
EXPANSION
MODULE
COMMS2 RS232 (TOP) U32
RN17
CN27 - 10 WAY IDC CN28 NOTE: CN8 (TOP)
CONNECTOR & CN27 ARE BOTH
COMMS 2 IN CFM TH1
CN2
ZDN2
+
CN3 COMMS 3 USB
SHIELD PIN 1 (BOTTOM) EXPANSION PANEL EXPANSION LEDS
RD TD
The Controller also has the required hand shaking to support connection to a Modem, thus allowing the FACP
to be programmed from a remote site that has an established telephone connection. This allows the system
software to be upgraded by simply transmitting a file via the serial port of the PC or Modem external to the
FACP. Diagnostic facilities are also available via the same connection.
Plug in DB9
Connector 1
6
2 Rx Data
7
3 Tx Data
8
4
9
5 Signal
Ground
Note: CN8 is located on the lower CN8
left hand side of the Main Board
Note: the DB9F to DB9F cable is not sensitive to which end is plugged in to the FireFinder PLUS or serial
port of the PC or vice versa.
The connections between the PC/Modem and the panel are crossed. i.e. TD connects to RD.
Make sure the ConfigManagerPlus program is set to use the port you have connected the cable to and set
up the configuration as follows:
63
MAN2994-7
To facilitate safe maintenance of these services an option is available that allows for the isolation and visual
indication of the disablement of ancillary services that does not affect the normal operation of the fire alarm
system.
To ensure power to the fire alarm system is not prejudiced in any way, power for the ancillary services must
be included in the calculation of the power supply and battery capacity.
Note: The Max Numbers of modules/boards that can be installed and configured within the FACP depends
on the cabinet size and the number of Panels in the System.
Note: Refer to individual Product datasheets and installation guides for complete details.
64
MAN2994-7
The Expansion Connection Board (BRD86FEPB) is used to increase the capacity of the controller from 4 Slave
CPU’s to 8 allowing Loops 5 – 8 to be configured. Connection from the Controller to the Expansion Board,
which must be mounted within 200mm of the Controller, is made via a 20 way flat cable Slave CPU number
5 is an integral part of the Expansion Board, only Slave CPU’s 6 (CN2), 7 (CN3 and 8 (CN4)are plug ins.
Connections
N1236
CN6 JTAG
C10 D1 Slave CPU 6 Slave CPU 7 Slave CPU 8
C7
C35
COMMS C3 C4
U7
R24
C12 C11
RN1 R6
R25
CN7 C9
U4
C36 U2 U1 U3
C38
C37
R2
U8 U5
X1
BRD86FEPB2-
C39
C32 C33 R7 C13
C34
CN5 Slave CPU 5 R14
U6
C14
C15
C16 C5
C17
C18
R4 D2
R26 Q1
Q2 R1
C1
D3
DEBUG
R9
C40 LK1
R8 U10
R23
C27
R10 C41
R12
U9 R5
R11
R13
C31 TP1
C8
65
MAN2994-7
The zones may be used in panel programming and Input / Output programming.
Maximium of 32
devices per Zone
(See Note 2)
PRESS HERE
+ Z1 - + Z2 - + Z3 - + Z4 - + Z5 - + Z6 - + Z7 - + Z8 -
To Zones 1 to 4 + / - To Zones 5 to 8 + / -
TB1 TB2
To Zones 1 to 4 + / - To Zones 5 to 8 + / -
+ - + - + - + - + - + - + - + -
Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8
TB1 TB2
CN2
RS485 Control
Comms In
RS485 Control
EOL
CN3 Address SW
Comms Out
(see Note 3)
ON
+ Fit EOL Termination
Link 1 if Last Module
ON
CN4 CN5
on Comms Bus
- 1 2 3 4 SW1
Connections
Terminal/s Function
TB1&2 Terminals 1, 3, 5, 7, 9, 11, 13, 15 ZONES 1 to 8 +ve
TB1&2 Terminals 2, 4, 6, 8, 10, 12, 14, 16 ZONES 1 to 8 -ve
Note 2: If Diode Bases are used ONLY the 10uF CAP can be used.
Note 3: See Section 17 for Addressing Details (SW1)
Note 4: Short circuits on the Zone is a “Fault” condition on the FACP NOT an “Alarm”
Note 5: Hard contact MCP’s will require a 470Ω to 680Ω series activation resistor to generate an alarm
condition and to avoid hard contact MCPS putting the Zone into Short circuit fault”
66
MAN2994-7
This module (BRD43ZAMC) has 32 bi-coloured LED’s which can be used to display the status of up to 32
individual Zones or 16 Zones with dual LEDs.
The zone numbers assigned to each LED are configurable and the LED’s will operate in the following manner
for the respective zone statuses:
The card will also respond to a lamp test when instigated on the panel to which it is connected.
C C
N N Top Card &
1 2 PCB Securing Clips
Address SW
In Out (See Note)
RS485 Control RS485 Control ON
1 2 3 4
/ 27VDC / 27VDC
Comms In Comms Out
Figure 84: Zone Alarm Mimic Card Rear View showing connectors and Address Switch
67
MAN2994-7
This card (BRD25GIB-B) has 8 switch inputs and 8 LED indicator outputs.
The switch inputs and LED outputs may be used in Input Output programming.
The switches are configurable as either momentary or toggle switches. When configured as momentary
pressing the button once will cause an event to occur as programmed in I/O and the LED’s can be
programmed to operate as an output.
When configured as toggle, pressing the button once will cause a condition to be held until the button is
pressed again. The associated LED is not available as an output in and shall always be illuminated when the
toggle condition is active. Also, when configured as a toggle, there shall be an option for a timer override. If
the toggle switch is activated it shall be de-activated automatically after the timeout period.
Figure 85: 8 Way Switch and Indicator Card Decal (See LAB1483.doc for Slip in Label)
C C
N N Top Card &
1 2 PCB Securing Clips
Address SW
In Out (See Note)
RS485 Control RS485 Control ON
1 2 3 4
/ 27VDC / 27VDC
Comms In Comms Out
Figure 86: 8 Way Switch and Indicator Card Rear View showing connectors and Address Switch
68
MAN2994-7
The switch is used to disable the associated zone, while the LEDs are used to indicate the zone status. The
top LED is Red in colour and is used to indicate if the zone is in Alarm while the bottom LED is Amber and is
used to indicate both Fault (LED flashing) and Disable (LED steady).
Figure 87: Zone Disable & Indicator decal (See LAB1483.doc for Slip in Label)
C C
N N Top Card &
1 2 PCB Securing Clips
Address SW
In Out (See Note)
RS485 Control RS485 Control ON
1 2 3 4
/ 27VDC / 27VDC
Comms In Comms Out
Figure 88: Module Rear View showing connectors and Address Switch
69
MAN2994-7
The 16 Way Input Board (BRD25SIP) makes provision for 16 voltage free contacts to be terminated to 16
optically coupled inputs. Its application is primarily for the monitoring of controlled ancillary equipment or
to initiate an action / event due to a change of state from what is accepted as the norm.
0V 1 2 3 4 0V 5 6 7 8 0V 9 10 11 12 0V 13 14 15 16 0V
TB2 TB3 TB4 TB5 TB6 TB7 TB8 TB9
ON
+ CN3 CN4
Fit EOL Termination
Link 1 if Last Module
ON
Address SW
- on Comms Bus 1 2 3 4 (See Note)
Figure 89: Typical Input Wiring and Board Layout Front View showing connectors and Address Switch
Connections
Terminal/s Function
Taking note of the Common 0v
TB2 to 9 terminals connect the voltage free Inputs 1 to 16
contacts as shown above.
70
MAN2994-7
The functionality and programming of the relays is similar to the relays on the main board of the FACP. By
default the relays default to Common Alarm functionality.
The board switches the relays as determined by the panel. The relays can be controlled by:
➢ Zones Alarm
➢ Group Alarm
➢ Device Alarm
➢ Internal Output
➢ Panel Output
➢ Loop Output
➢ Panel Input
➢ Loop Input
➢ Reset – relay is activated for 3 seconds when reset depressed
SW1
Figure 90: Internal 8 Way Relay Board Front View showing connectors and Address Switch
Relay Connections
Terminal/s Function
N/O = Normally Open,
TB1 to 8 C = Common Relay 1 to 8
N/C = Normally Closed
Note: See Section 17 for Addressing Details (SW1)
71
MAN2994-7
Figure 91: Remote 8 Way Relay Board Front View showing connectors and Address Switch
Relay Connections
Terminal/s Function
N/O = Normally Open,
TB1 to 8 C = Common Relay 1 to 8
N/C = Normally Closed
Communications Connections
Terminal Function
RS485+
TB9 RS485- Communications In
Shield
RS485+
TB9 RS485- Communications Out
Shield
Note: See Section 17 for Addressing Details (SW1)
72
MAN2994-7
The Sounder Board (BRD25SOP) expands the number of sounders that can be used on an FACP by 8. Each
output is of a solid state design, rated at 24VDC / 750mA and requires a 10KΩ End of Line (EOL) resistor
regardless of whether or not a sounder is wired to the circuit.
The sounder board will switch ON the sounders as configured (output off, continuous or pulsed) at the FACP
and supervise the sounders for their open circuit, short circuit & line fault conditions.
10K EOL
Resistor
POWER
DC IN SOUNDER 1 SOUNDER 2 SOUNDER 3 SOUNDER 4 SOUNDER 5 SOUNDER 6 SOUNDER 7 SOUNDER 8
0V 27V +VE -VE +VE -VE +VE -VE +VE -VE +VE -VE +VE -VE +VE -VE +VE -VE
CN3 SW1
- Link 1 if Last Module
on Comms Bus
1 2 3 4
Figure 92: 8 Way Sounder Board Front View showing connectors and Address Switch
Note 4: In addition filtering and protection devices are used to reject transients.
Connections
Terminal/s Function
+ve
TB1 to 2 Sounder 1 to 8
-Ve
0V
TB3 Power DC IN
27V
Note 5: See Section 17 for Addressing Details (SW1)
73
MAN2994-7
The Fire Fan Module (BRD25FCB) has four (4) separate fan controls each having an On, Auto and Off function
switch and a set of three (3) monitoring LED’s. The LED’s indicate the status of the equipment e.g. Run, Fault
or Stop. The two (2) arrow head buttons are used to step up and / or down through the three (3) conditions.
A slip in label can also be inserted into the hinged cover for identification purposes.
The “Plant Trip” Reset is used to locally restart plant and equipment that has been automatically shut down
because the FACP has initiated an alarm once that alarm has been cleared.
Figure 93: DEC2944-T1 4 Way Fire Fan Module (Slip in label fitted see LAB1486.doc)
In Out CN3
ON
C C
1 2 3 4
N N
1 2
Address
CN1 CN2 Switch
TERMINATOR
LINK Set to 1
CN2: Communications & 27V OUT
to Next Front Panel Card.
LK1 If Unsed the Termination Link Must be Inserted.
BRD25FCB4
Figure 94: 4 Way Fire Fan Module Rear View showing connectors and Address Switch
Note: The Fan Control module can also be used a Selector Switch & Indicator module. Refer to MAN3016
for details.
74
MAN2994-7
The Fan Termination Board (BRD25FTB) interfaces between the Fire Fan Module and the plant/equipment it
controls via the 24 Volt 250mA Start, Stop, current limited, relay outputs and monitor inputs. Programmable
monitoring of the field equipment is achieved using 0 volts as an input level to indicate run, fault and stop
conditions of that equipment. Monitoring is programmed in the Function Menu for a 3, 4 or 5 Wire Start /
Stop, Run, Fault, Stop & Common functions. The inputs are protected by way of resettable transorbs and
resistive / capacitive networks.
Connections
RUN FLT
1 2 3 4 5 6 1 2 3 4 5 6
TB2, 3, 4, 5
on Comms Bus
POWER
CN3 CN4 ON ON
SW1
1 2 3 4
Figure 96: Fan Termination Board Layout and Typical I/O Wiring
The BDC supports two detectors, which can be located in the same Pro-Sens unit or separate Pro-Sens units.
12.13.1 Mechanical
The BDC is an a Add On, so can be mounted locally into a standard FACP into the cabinet door cut out (as per
SP1X, SP8X etc) or remotely using an enclosure
This control is used to send a reset command to the linked (configured) APID device.
DISABLE/ENABLE
This control is used to disable / enable the linked (configured) APID device.
Note: This control can’t be invoked if the system’s sounders (Alarm Devices) have not been silenced by
means of FACP’s ALARMS SILENCE/RESOUND key.
76
MAN2994-7
The Communications Extender Board (BRD82LTB-C) is mounted inside the FACP and provides protected
RS485 communications and 27VDC to the SmartTerminal and other external modules.
CH16
BRD82LTB2
COMMUNICATIONS EXTENDER BOARD
27VDC
CN2
M1
CN3 IN OUT
M2
CN4 CN5
FACP MAIN
BOARD IN OUT TO AVAILABLE 27VDC
CONNECTOR (3 WAY)
12.15 SmartTerminal
SmartTerminal connects to the FireFinder Plus Fire Alarm Control Panel (FACP) via the RS485
Communications Extender Board. Generally it is designed to be used anywhere where the status of the FACP
is required to be monitored by local personnel and limited control is required. It can also be tailored as a
Nurse Fire Station (NFS).
SmartTerminal has been designed for use with the FireFinder PLUS series of FACP’s.
➢ 4 line by 40 character LCD with backlight and navigation buttons buttons allow the
SmartTerminal to be used for FACP operation and interrogation. Note: the backlight is
only energised when alarms are present, a key has been pressed or controls enable key
switch is enabled
➢ A wide range of secure user functions. This includes the ability to disable / re-enable a
large number of system functions.
➢ Reports events from devices that are accessible to the host FACP. For example if the host
FACP is configured with global access then the connected SmartTerminal reports events
from all devices. If the host FACP is configured as local then the connected SmartTerminal
reports events from devices that are directly connected to the host FACP
77
MAN2994-7
12.15.1 Overview
SmartTerminal consists of two PCBs;
1. A Termination Board mounted in each SmartTerminal to protect and interface the RS485
communications and 27VDC supply to the LCD Board
Note: A maximum of 30 SmartTerminal’s / Nurse Fire Stations (NFS) may be connected to the
communications bus over a distance of approximately 1.2Kms. When fitting multiple SmartTerminals
consideration must be given to the 24V voltage drop due to cable loss and the need for external power supplies
for the SmartTerminals.
12.15.2 Mechanical
➢ The Main Card, with all controls and indicators mounted directly onto it
➢ 1 X Termination Board
➢ 2 X ABS door keys
➢ 2 X 003 Enable / Disable keys
➢ 2 X Jumper links
➢ 2A Power Supply ( only if internally powered )
Note: A Communications Extender Board will be required if the Comms Bus in the FACP is fully utilised and
/ or if one is not fitted.
The front door of the ABS version is locked by way of two clips on the right hand side of the cabinet. A special
locating key which has two raised pins that are inserted into the side of the cabinet unlocks the door.
Figure 99: ABS Door Key and Front Panel Add On Card Surround Release Clip
78
MAN2994-7
KNOCKOUTS
TOP ( x15 )
KEY HOLE KEY HOLE
BACK ( x 4 )
MOUNTING MOUNTING
HOLE HOLE
Q7 Q1 CN1
CN2
RS485 RS485 24V 27V
DISCHARGE POINT
TOUCH HERE FIRST IN OUT IN OUT
LCD
R47 R45 R43
D26
BRD82LTB2-
CONFIG
U2
SW27
D35
D2 D3 D4 D5 D6 D7 D8 R13
RN1
C12
C13
LCDA Main
R44
DIAGNOSTIC R14
C15
RESET
BRD82LTB
U6
R15
U5
C17
TH1
RN3 R19
U7
CAB2116
U8 C21 U9 C19
X1
U10 U11 RN4 C20
D17 C22 C23 D13 D9
KEYSWITCH Q2
R20
RN5
KEY HOLE
D21 D10
D18 D14
R34 R32 C36 C29 C26 C25
1
BRD82ICC
RN10
RN7
RN8
RN9
U12
CN8
8
3 2
D22
R23 PRINTER D29
CN7
7 6
CN7
MOUNTING
PWR LINK PWR LINK R30
4
5 Q3
Q4
LK1 D23 CN11 CN12
U15
HOLE
Q6 D32 D31 RN13
D24
I/P CURRENT
COMPLIANCE & ADDRESS R 6mm.
CONFIGURATION LABEL TESTED
QA APPR
DATE OF MAN
CERTIFICATE OF
COMPLIANCE No. FRONT DOOR HINGES
N1236
27VDC
CN2 CN3 IN OUT
M1
M2
RS485
OUT
RS485
IN +24V TO NEXT LCDA
MAXIMUM OF 30
VDC VDC 0V
IN OUT
TB2 TB1 TB3 TB4 TB2 TB1 TB3 TB4
+ - COM + - +24V 0 V +24V 0 V + - COM + - COM +24V 0V +24V 0V
COM
POWER IN POWER OUT RS485 IN RS485 OUT POWER IN POWER OUT
CN1
CN1
TO TO
BRD82LTB2-
LCD
BRD82LTB2-
03/05/2006
LCD
03/05/2006
79
MAN2994-7
The LCD will now display the Configuration screen. This screen consists of the code version number, current
address and four adjustment markers. These markers A-, A+, C-, and C+ are used to indicate the buttons that
adjust the address and LCD contrast.
Use the “PREVIOUS (A-) and NEXT” (A+) buttons to select the desired address. The default value for this
address is 255 which is not a valid SmartTerminal address. The user must then select an address value from
1 to 30, i.e. the same address as that set in the FACP. The buttons corresponding to C- (SILENCE BUZZER) and
C+ (RESET) are used in a similar manner to decrease and increase the LCD contrast level. There is audible
feedback for all button presses.
Once the address has been set press the “CONFIG” button again for 3 seconds and the screen will return to
its default and the “DIAGNOSTIC” LED will return to a slow flash. This slow flash indicates SmartTerminal and
the FACP are communicating normally i.e. the LED flashes if communications data is being received from the
FACP.
Note: If the address is not set within the time out period of approximately 75 seconds SmartTerminal will
return to its previous state.
80
MAN2994-7
12.15.5 Operation
The operation of SmartTerminal can be considered to be in one of three states, these are;
2. Normal - when the SmartTerminal address has been set and is communicating with the FACP,
reporting normal / abnormal conditions and controlling the FACP via the front panel controls
3. Fault where the SmartTerminal is in fault and/or is unable to communicate with the FACP.
Power Up
The LCD displays a message telling the operator SmartTerminal is being powered up and that the hardware
is being initialized. Once the hardware has been successfully initialized set the address and SmartTerminal
should automatically transition to the normal state. Should a failure occur on power up press the “RESET”
button located on the LCD PCB and check the address is correct.
Normal
The Normal state is entered from the “Power-up” or a return from the “Fault” state and is displayed on the
LCD if the SmartTerminal is communicating with the FACP and operating correctly. In this state the front
panel Power indicator is illuminated.
Fault
➢ A hardware failure
➢ A loss of communications with the FACP (indicated by the “DIAGNOSTIC” LED – not
flashing and the “no communications “message being displayed)
In a Fault condition the front panel NORMAL indicator is extinguished and the details of the fault are displayed
on the LCD. The FACP will also indicate a fault in a similar manner.
Access levels
Access level 1 - only the silence buzzer control is operative. All other controls operate in access level 2.
81
MAN2994-7
➢ Fire
➢ Faults and
➢ Disables.
The types of events are only associated with devices and detectors hence faults associated with modules,
loops O/C – S/C, power supplies and so forth are not reported on the LCD.
The SmartTerminal has front panel indicators for each type of event. When SmartTerminal is configured not
to report a type of event and that event type is present (and the corresponding front panel indicator is
illuminated on the SmartTerminal), then a standard information screen is displayed on the LCD stating the
system is not normal and the operator should see the FACP.
Alarm: If configured the screen format for reporting loop / device / zone fire condition is:
82
MAN2994-7
Fault: If configured the screen format for reporting loop / device / zone fault condition is:
Zzzz FAULT
<zone descriptor>
<date> <time> CONTROL*
FAULT XXX OF XXX DEVICE►
In the event of a loss of communications, for a period of greater than 15 seconds the SmartTerminal will
default to the No Communications screen. The format for this screen is:
No Communication
Device Isolate / Disables: If configured the screen format for reporting loop / device / zone disable condition
is:
Zzzz DISABLED
<zone descriptor>
<date><time> CONTROL*
ZONE DISABLED XXX OF XXX DEVICE►
Pre-alarm: If configured the screen format for reporting loop / device / zone Pre-alarm condition is:
Zzzz PRE-ALARM
<zone descriptor>
<date> <time> CONTROL*
ZONE PRE-ALARM XXX OF XXX DEVICE►
83
MAN2994-7
Normal / Default: The format for reporting that everything is normal is:
The screen is only displayed when there are no alarms, fault or disables on the panel.
The highest priority current system status will be displayed and can be one of the following listed in order of
highest to lowest priority:
“SYSTEM ALARM”
“SYSTEM PRE-ALARM”
“SYSTEM FAULT”
“SYSTEM ISOLATE”
“SYSTEM NORMAL”
A- A+ C- C+
A - , A + : adjusts the address 1 to 30, 30 being the maximum number of SmartTerminal’s that can be
connected to the FACP, ( default is 255 which is not a valid address).
C - C+: decreases [-] and increases [+] the LCD contrast level.
84
MAN2994-7
12.16.1 Operation
Introduction
The Agent Release Module and Termination Board communicate with the FACP via the RS485 multi-drop bus.
The Local Control Station communicates only with the Termination Board via a separate RS485 bus. Up to 7
Local Control Stations can be connected to one termination board.
Agent discharge operates in two modes – automatic and manual. The manual mode is selected by pressing
the Inhibit switch on any Local Control Station. To indicate the system is in manual the Inhibit LED will be
illuminated. Pressing Inhibit again will toggle or return the mode to automatic and extinguish the Inhibit LED.
The “Agent Released” Pressure Switch (PSW) is wired to the PSW input on the Termination Board and is used
to confirm that the agent has been released. The circuitry involved in this process can be configured to accept
a normally open contact, normally closed contact, normally open mechanically operated (manual) or is
ignored (not fitted) and is selected via FACP on-site programming. If the mechanical (manually operated)
option is selected the module monitors the pressure switch input and provides notification the agent has
been released manually, initiates an alarm and illuminates the “Agent Released” indicator.
Manual Mode
➢ The Local Control Station Inhibit indicator is lit at the FACP and all Local Control Station’s.
➢ The buzzer at all Local Control Stations will sound until the inhibit button is released.
➢ The System Inoperative output is turned on.
➢ The Automatic discharge sequences are prevented from starting.
➢ If an automatic discharge sequence was underway and the inhibit switch is activated
(switched to manual mode) the discharge sequence is aborted and the sequence is reset.
This means the Stage 1 and Stage 2 outputs are switched off.
To manually discharge the agent the “ Lock Off Valve “ must be open and the Manual Release switch on the
Local Control Station pressed. The manual discharge sequence is;
➢ Manual Activation indicator is lit on the FACP and Local Control Station.
➢ The FACP activates its brigade alarm output.
➢ Stage 1 outputs are switched to +24VDC. (FIRE ALARM sign illuminated, aural alarm
sounds)
➢ Stage 2 outputs are switched to +24VDC. (FIRE ALARM, EVACUATE & DO NOT ENTER signs
illuminated, aural alarm sounds).
➢ The optional pre-release start delay is activated (Selected via FACP on-site programming);
time out and an ON Interlock signal will then operate the selected release circuitry.
➢ The Agent Discharge LED on the Agent Release Module and Local Control Station will
illuminate when the Pressure Switch input on the Termination Board is activated.
➢ Activate gas-fired output.
Note: The Interlock Input can be defaulted to the on position by placing a 10K EOL termination resistor
across the terminals TB2. 7 / 8 of the Agent Release Module and Local Control Station.
85
MAN2994-7
Auto Mode
Automatic discharge is when one or two zones going into alarm initiate the agent discharge sequence.
Note: A “manual release” can still be initiated in “auto mode” but the LCS “Inhibit” control WILL NOT inhibit
/ abort the agent release sequence.
➢ Automatic Activation LED is illuminated on the Agent Release Module and Local Control
Station.
➢ Stage 1 outputs are switched to +24VDC. (FIRE ALARM sign illuminated, aural alarm
sounds).
➢ Stage 2 outputs are switched to +24VDC. (FIRE ALARM, EVACUATE & DO NOT ENTER signs
illuminated, aural alarm sounds).
➢ Optional pre-release delay is started (Selected via FACP on-site programming).
➢ The delay times out and if the Interlock signal is ON, the selected circuit will activate.
➢ The Pressure Switch field input on the Termination Board is activated and the Agent
Discharge LED on the Agent Release Module and Local Control Station will be illuminated.
➢ Activate gas-fired output.
Dual Zone Activation, if the first zone goes into alarm the following steps are initiated;
➢ The automatic activation LED on the Agent Release Module and Local Control Station will
flash.
➢ Stage 1 outputs are switch to –24VDC. [FIRE ALARM sign illuminated, aural alarm sounds].
When the second zone goes into alarm, then the following steps occur;
Service Switch
The service switch is situated on the Agent Release Module when activated causes the following;
➢ Electrically isolates the activation circuitry from the agent release device.
➢ Operates the System Inoperative output.
86
MAN2994-7
Lock-Off Valve
Fault Monitoring
Note #1: The common fault indicator on the Agent Release Module and Local Control Station is
illuminated for any Fault condition.
Note #2: For a pressure switch fault, low pressure switch fault, lock-off valve fault, stage 1 output
fault, stage 2 output fault and interlock fault, the FACP will signal the brigade.
Note #3: When there is a fault in the activation circuit or in the trigger zones, in addition to the above,
the system inoperative output is operated.
Note #4: The FACP fault buzzer will sound for all faults.
Note #5: The FACP will report the type of fault on the LCD.
Isolation
If a trigger zone is isolated at the FACP the trigger zone isolated indicator at the Agent Release Module and
Local Control Station is illuminated, and the system inoperative output is operated.
The system inoperative output is switched to +24VDC under the following conditions;
With agent release systems, a manual mechanical means can be provided to release the agent.
If the pressure switch is activated (indicating that the agent has been released), and the agent release module
has not activated the selected activation circuit, then the following will occur:
Due to the requirements of Manual Mechanical Release of the Agent, the pressure switch input conveys two
pieces of information:
When the pressure switch input is active, it signals that the agent has been released. The release can be as a
result of the agent release module or due to a manual mechanical release.
When the pressure switch is not active, it signals that there is a full bottle of agent available to be discharged.
In order for the agent release module to respond to a manual mechanical release, the pressure switch must
have been previously not active, to signify that a full bottle of agent is available
88
MAN2994-7
C C EOL
N N TERMINATOR
LINK
Top Module & PCB
1 2 Securing Clips
LK1
In Out ADDRESS
Fit EOL Termination SWITCH
S W2
Link 1 if Last Module
ON
1 2 3 4
on Comms Bus INHIBIT
LK2
+
RS485 Control RS485 Control SWITCH MON
DISABLE
/ 27VDC / 27VDC
Comms In Comms Out
MANUAL
RELEASE
TB4
AGENT RELEASE
MCP
10K
EOL
The PCB is fitted with two 2 x RJ45 connectors CN6 & 7 for power (27VDC) and communications (RS485) for
communications between the Agent Release Module and the FACP Main Control Board.
Controlled Access
The FCP goes into service mode when the keyswitch is switched to SERVICE INHIBIT. This results in the
selected agent activation circuit being electrically isolated and a Common Isolate condition being indicated
at the FACP. This condition can also be confirmed through the Status Menu. To remove the key it is necessary
for the switch to be in the OFF position.
Pressing Select toggles the selection of either the Main or Reserve release agent. Selection is
indicated by the Main and Reserve Agent LED’s
89
MAN2994-7
Pressing the Agent Inhibit switch will inhibit the gas from release in either the Manual or
Automatic mode. The Agent Inhibit switch has an internal lamp fitted with yellow lens and is illuminated
when the Inhibit switch is activated at the FACP or any of the LCS’s. To prevent accidental operation this
switch has a hinged clear plastic cover that has to be raised to access the switch.
90
MAN2994-7
The Comms line is RS485 and is cabled to the Agent Termination Board.
The Interlock is a monitored input with 10KΩ EOL. This input is used to determine if air conditioning dampers
and doors are closed but can be defaulted to the “ON” condition by terminating the input with a 2K2Ω EOL.
Double action switching is achieved by way of protective lift up covers seen here and manual operation of the
MCP or Inhibit switch. To ensure correct operation and prevent accidental release of the agent these covers
should not be disabled for any reason
ENCLOSURE
CONTROL
PANEL
SURROUND
MCP
91
MAN2994-7
There are 12 indicators on both the Agent Release Module and Local Control Station. They are;
MANUAL
ACTIVATION (Red) Illuminated when a manual release sequence has commenced. A Manual release
sequence can only be started by activating the manual release at the FACP or LCS.
MANUAL
ACTIVATION (Red) Illuminated when a manual release sequence has commenced. This occurs when
the selected zone(s) on the FACP have gone into alarm. For dual zones, the indicator should flash when the
first zone goes into alarm, and steady when the second zone goes into alarm.
AGENT
DISCHARGED (Blue) Illuminated when the pressure switch indicates the agent has been released. For
Pyrogen, feedback is from the thermal switch. If there is no pressure switch fitted, the indicator shall be
illuminated immediately the agent release signal is activated (Selected via FACP on-site programming – refer
to relevant FACP Manual)
LOCK OFF
VALVE INHIBITED (Yellow) Illuminated when the lock-off valve has been activated.
STAGE 2
TIMER RUNNING (Yellow) Illuminated when the pre-discharge delay timer is running.
AGENT CIRCUIT
FAULT (Yellow) Illuminated when there is a fault on the monitored Main or Reserve activation
circuits e.g. S/C or O/C.
AGENT LOW
PRESSURE (Yellow) Illuminated when the low pressure switch is activated. This indicates a leakage
at the agent cylinder. The low pressure switch is a separate switch.
92
MAN2994-7
TRIGGER ZONE
ISOLATED (Yellow) Illuminated when any of the programmed trigger zones on the FACP are
isolated.
COMMON FAULT
(Yellow) Illuminated under the following fault conditions;
INTERLOCK
(Yellow) Illuminated when the interlock input (e.g. from dampers, doors etc) is off
during the discharge sequence – meaning the dampers, doors etc are not closed as they should be or a fault
exists. The “Interlock” is overridden after 10 seconds and the agent is released
Note: The Interlock is a Monitored Input and can be defaulted to the ON position by terminating the input
(TB2 7 & 8) into a 2K2 resistor.
INITIAL AGENT
(Yellow) Illuminated when the “Initial Agent” is selected.
RESERVE AGENT
(Yellow) Illuminated when the “Reserve Agent” is selected.
The agent inhibit switch has an internal lamp fitted with yellow lens. Illuminated when the inhibit switch is
activated at the FACP or any of the LCS’s.
93
MAN2994-7
➢ Under all fault conditions and can be silenced by using the appropriate FACP buzzer
silence control.
➢ When the LCS Inhibit control is activated – after 8 hours – treated as an isolate condition.
➢ When the service inhibit is activated - after 8 hours – treated as an isolate condition
CAUTION - TO PREVENT ACCIDENTAL AGENT RELEASE DO NOT DE-ISOLATE THE AGENT UNDER ANY
CIRCUMSTANCES UNTIL THE SYSTEM AS A WHOLE IS FUNCTIONING CORRECTLY
CN5
EOL
TERMINATOR
LINK JTAG
ON
1 2 3 4
Address 2
Switch
Set to 1 S W2
ON
ON
1 2 3 4
1 2 3 4
1
LK2 2
+ INHIBIT 3
Local Control Station T1 CN1
SWITCH MON.
DISABLE
4
MANUAL HOLD/
AGENT
3
INHIBIT
ON
1 2 3 4
+
-
+27VDC OUT
SCRN
+27VDC IN FROM
TERMINATION BRD. TO NEXT LCS INTER
SIG
10K 2K2
SIG
LOCK
EOL
10K INSERT A 2K2 ACROSS
EOL THE 10K EOL TO
DEFAULT TO "ON"
Agent Termination Board TB1
within the FACP
+ 27V 0 V RS 485 COMMS BUS
Note 1: Dipswitch No 4 on SW2 when set to “ON” activates the alternate buzzer feature where the buzzer
will sound for 5 seconds every 30 minutes when the LCS Inhibit button is activated.
94
MAN2994-7
22K
22K
22K
10K
10K
LCS CABLE INPUTS GAS SYST. STAGE1 STAGE2 RELEASE
0VDC SIG+ + L.PSW- MAIN RESV
+24VDC SCRN SIG- + PSW - + LOCK- N/0 COM + - + - N/0 C O M + - N/0 C O M + - + -
TB1 TB2 TB3 TB4 TB5 TB6 TB7
C RS485 Control
N Fit EOL Termination
2
Comms Out
Link 1 to Last Module
on Comms Bus
ON
CN3 CN4
1 2 3 4 SW1 Address Setting
Optional 27VDC In
1. The FACP via CN1, CN2 continuing the RS485 communications bus if required. LK1 is inserted if
this is the last backpan board on the bus.
2. LCS’s (up to 7) via TB1. LK1 is inserted in the last board in the RS485 Bus
3. Monitored Inputs: via TB2. (EOL Resistance 22K, Series Resistance 4K7)
i. Pressure Switch (PSW) agent released
ii. Low Pressure Switch (LPSW) agent storage cylinder pressure has dropped to a pre-
determined level; and
iii. Interlock, the manual lock-off valve has been operated.
4. Gas Fired: Output via RL2 N/O contacts rated at 1A @ 24VDC wired to TB3. Used to indicate to
other monitoring devices the agent has been released.
5. System Inoperative: via RL1 N/O contacts rated at 1A @ 24VDC wired to TB4. Used to warn by
way of signage / audible alarm and/or monitoring that the system is inoperative.
Note: The “System Inoperative” output will operate (turn on) when all zones or groups used in the
Activation columns are "Disabled" or in "Fault".
When “Dual activation” is used, 50% or more of the configured Activation columns are “Disabled” or in “Fault”
the “System Inoperative” output will operate.
6. Stage 1: Output; initiates the visual and audible Fire Alarm and Evacuate warnings.
i. Monitored; via RL4 C/O contacts wired to TB5 1 & 2 (EOL required 10K) and
ii. Un-monitored; via RL5 N/O contacts wired to TB5 3 & 4.
95
MAN2994-7
7. Stage 2: output; initiates the visual and audible Fire Alarm and Do No Enter warnings
i. Monitored; via RL6 C/O contacts wired to TB6 1 &2; (EOL required is 10K) and
ii. Un-monitored; via RL3 N/O contacts wired to TB6 3 & 4
8. Release: Main actuating circuit, monitored (10KΩ EOL required) via TB7 1 & 2 (2A current
limited),
9. Release: Reserve actuating circuit, monitored (10KΩ EOL required) via TB7 3 & 4 (2A current
limited)
Note 1: Metron Igniters - (max of 10 – a series 2watt 18 resister must be added to the circuit)
96
MAN2994-7
This input relies on N/O or N/C relay contacts used in conjunction with 22K EOL and 4K7 series resistors.
The type of agent release mechanism and contacts used has to be set in the Programming Menu for the input
to function as per the manufacturers specifications and be in accordance with the relevant Standard.
Note: The PSW, LPSW & the Interlock Mechanisms are all
mounted onto the top of the cylinder containing the Agent
Agent
10K EOL Distribution 22K EOL
4K7
To TB7 22K
Solenoid MAIN or EOL 4K7
RESERVE 22K EOL
+ - + - Release
TB7
Termination 4K7
MAIN RESV Board
+ - + - + -
MAIN / RESERVE Agent
RELEASE
PSW LPSW LOCK
Figure 108: Solenoid, Metron PSW, LPSW and “LOCK” TB3 Wiring
These inputs are also monitored and should be wired as shown above
RL2A TB3 1
To Monitoring
* Interface / Device
= MOV 2
* 35V *
0V
TB4 1 +
RL1A To Sys
System Inoperative
Inop Mon
+27V Current
Limited to1A 0V 2
-
Stage 1, Stage 2
TB5 / 6
Stage 1 or Stage 2
+ve 1 +(-)
RL4A RL6A 10K
-ve * 2
1 or 2 Way
Signage
The Ampac Warning Signs provide clear, visual and audible indication of an alarm event and are designed for
use with fire detection and alarm systems which may incorporate agent release capability. The display may
also be customised as required to cater for a variety of applications.
The Warning Signs are available in two standard formats, the 4210-0110 for semi-flush or surface mount
indoor applications while the 4210-0120 affords IP65 weatherproof capabilities.
The Warning Signs incorporate a split level design that enables two text messages to be independently
controlled through the application of input voltages. The two levels may be activated by either a voltage
reversing DC input or through application of a common positive and two switched negative DC inputs.
Option switches located inside the unit enable the commissioning engineer to further configure the Warning
Sign for continuous or flashing Red or Yellow LEDs, enable an integral buzzer in continuous or pulsing mode
of operation, to enable a mute facility to silence the buzzer and or optional external sounder. A facility to
synchronise the flashing between multiple signs is also provided.
Illuminated using high efficiency, high intensity LEDs to greatly reduce power consumption and reliability
ensures that the brightness is maintained even when running on depleted stand-by batteries.
Specifications:
Open the outer door using the plastic key device provided. Using the back box as a template, mark the
position of the four fixings in the required position on the mounting surface. For semi-flush fixing
applications, cut a hole in the mounting surface to the dimensions shown below ensuring adequate depth is
provided for the unit to be recessed.
Before fixing the unit decide which entry points are to be used for the in-coming cables. The back box has 7
20mm knockouts in the top and bottom which can be easily removed by sharply tapping them with a blunt
instrument and small hammer.
Top entry is recommended on this product however, back entry can be achieved by drilling additional holes
in the back box to suite. Fix the back box to the mounting surface using 4 appropriate sized bolts or screws
and install the acrylic text fascia plate using the 6 screws provided.
The weatherproof enclosure should be surface mounted using appropriate fixings and sealing washers.
Cabling
The maximum size of cable that the terminals will accommodate is 2.5mm². The interconnecting external
cables should be connected to the back box using suitable cable glands. On the 4210-0120 back box,
waterproof lock-tight glands should be used to ensure a weatherproof seal is maintained. Ensure that cable
tails of sufficient length are maintained to reach the terminals without cutting across the front surface of the
internal printed circuit board as this will impair the illumination of the sign.
The Warning Sign can be configured to illuminate in two ways. For voltage reversal, 2 wire applications and
for use with the Ampac Agent Release module, refer figure 1. For common positive, switched negative 3 wire
applications, refer figure 2.
The Warning Sign can be configured to operate in a variety of ways using SW2 8 way DIL switches located on
the printed circuit board.
Operational LED Colour Selection SW1 - Red or Yellow and should be set to suit the application of the Warning
Sign.
Operational Functionality SW2 - Table 1 outlines the functionality of the on-board switches located at SW2,
switches 1 - 8.
99
MAN2994-7
Table 1
Switch Off On
1 Level Two Extinguished for Stage 1 Level Two Illuminates for Stage 1 Input.
Input.
2 Level One Illuminates for Stage 2 Level One Extinguished for Stage 2 Input.
Input
3 Level 1 LEDs Constant Level 1 LEDs Flashing
4 Level 2 LEDs Constant Level 1 LEDs Flashing
5 Internal Buzzer Disabled Internal Buzzer Enabled
6 Buzzer Continuous Buzzer Pulsing
7 External Mute Input Enabled External Mute Input Disabled
8 Output Synchronizing Disabled Output Synchronizing Enabled (enable on first sign
only)
Cabling
MUTE - Normally Open (N/O) contacts with momentary push button switch (Optional)
INPUT
Testing
Ensure the;
100
Momentary Push Button
Silence Buzzer / Sounder
Agent Release Board Input
To Next Warning Sign
+
10K If multiple signs are used
-
TB5 (Maximum 6) fit 10K EOL
Stage 1 to last sign
Output
Voltage Reversal
N/O COM
2 Wire BiPolar
Stage 1 Stage 2 Sounder
Stage 1 (Level 1) = - + - +
(+) POS
+ -
Stage 2 (Level 2) = + - (-) POS
TB1
TB2
TB3
TB4
DC+
ST1
ST2
DC+
ST1
ST2
DC+
ST1
ST2
VOLTAGE REVERSING
2 WIRE SOUNDER CONNECTION
TB4
DC+
ST1
+
SOUNDER
ST2
WARNING SIGN
BRD42WSB1-
D22
02/04/13 POLARISED (VANTAGE)
D20 D21 D23 D24
3 WIRE SOUNDER CONNECTION
D27
N1236
D25 D26 D28 D29
TB4
DC+
+
ALERT
ST1 SOUNDER
EVAC
ST2
STAGE 1
D31 D34 OUTPUT
D32 D33 D35
TB1
TB3
TB1
TB3
AGENT
D40
DC+
ST1
ST2
DC+
ST1
ST2
DC+
ST1
ST2
DC+
ST1
ST2
7
6 BUZZER CONTINUOUS BUZZER PULSING
DC+
ST1
ST2
DC+
ST1
ST2
DC+
ST1
ST2
DC+
ST1
ST2
8 BZ1
7 EXTERNAL MUTE INPUT ENABLED EXTERNAL MUTE INPUT DISABLED IN OUT IN OUT
+
Figure 113: Two Wire Voltage Reversing Connection (Ampac Agent Release Module)
PLEASE REFER TO WWW.AMPAC.NET BZ2
MAN2994-7
101
Momentary Push Button
Silence Buzzer / Sounder To Next
Input Warning Sign Conventional 3 wire
+24 Volts DC Sounder - Vantage
Level 1 -ve 1 (-) EVAC
2 (-) EVAC
Level 2 -ve
3 (-) ALERT
4 (-) ALERT
5 (+) POS
6 (+) POS
TB1
TB2
TB3
TB4
DC+
ST1
ST2
DC+
ST1
ST2
DC+
ST1
ST2
VOLTAGE REVERSING
2 WIRE SOUNDER CONNECTION
TB4
DC+
ST1
+
SOUNDER
ST2
WARNING SIGN
BRD42WSB1-
D22
02/04/13 POLARISED (VANTAGE)
D20 D21 D23 D24
3 WIRE SOUNDER CONNECTION
D27
N1236
D25 D26 D28 D29
TB4
DC+
+
ALERT
ST1 SOUNDER
EVAC
ST2
STAGE 1
D31 D34 OUTPUT
D32 D33 D35
TB1
TB3
TB1
TB3
AGENT
D40
DC+
ST1
ST2
DC+
ST1
ST2
DC+
ST1
ST2
DC+
ST1
ST2
7
6 BUZZER CONTINUOUS BUZZER PULSING
DC+
ST1
ST2
DC+
ST1
ST2
DC+
ST1
ST2
DC+
ST1
ST2
8 BZ1
7 EXTERNAL MUTE INPUT ENABLED EXTERNAL MUTE INPUT DISABLED IN OUT IN OUT
+
102
MAN2994-7
This OWS system consists of the Amplifier (25W, 50W, 120W, 250W and 500W variants) and a Front Panel
Switch and Indicator Card.
The amplifier communicates to the Front Panel Switch & Indicator via a CAN protocol, where input events
are received from the Front Panel Switch & Indicator board and feedbacks are returned to it.
The Front Panel Switch & Indicator communicates to the FACP via the FACP’s internal RS485 communications
bus.
Below are some of the features the OWS contains. For detailed specifications and functional information
refer to MAN3072 OWS Technical Manual.
The Amplifier features 4 digital inputs, 3 relay outputs (1A), a strobe output and a 100V line output.
103
MAN2994-7
104
MAN2994-7
105
MAN2994-7
106
MAN2994-7
12.18 Printer
Specifications
Figure 118: Printer Front Panel Layout (Front Cover Closed / Open)
Indicator
SEL Button
The printer enters the On Line state automatically when power is applied or on exiting from the Self-Test
mode. (LED is green).
Press the SEL button, the LED is turned off and the printer goes Off Line.
Press the SEL button again, the LED turns on and the printer is On Line again.
Note: The printer will not receipt data when the printer is off line.
Press the SEL button while the printer is printing, the printer will pause and enter the Off Line mode after it
finishes printing the row it was currently printing. The printer will continue to print when the SEL button is
pressed again.
107
MAN2994-7
Remove power from the printer, press the SEL button, then reconnect the printer to the power supply. The
printer will enter the HEX-DUMP mode. In this mode any programs sent from the host CPU will be printed
out in Hexadecimal.
LF Button
While the printer is Off Line press and hold the LF button, paper feed will be initiated. Release the LF button
and the paper feed will be cancelled.
Self-Test Mode
With power applied (green LED illuminated) push the SEL button. This will turn off the LED. Press and hold in
the LF button, then press the SEL button again and the printer will enter the Self Test mode. Self-test will
print out all the valid characters in the character sets.
After printing out the complete Self-Test list the printer will exit the mode automatically; or
Press the SEL button and the printer will immediately exit the Self-Test mode.
108
MAN2994-7
12.18.2 Maintenance
Installing the Ribbon Cassette
The printer has a factory loaded ink ribbon cassette. Remove the power from the printer.
Unlock the front cover by pushing down on the tab at the top of the front panel.
Push the mechanism release button in the top right corner to release the print head.
To remove the ribbon cassette gently pull out the left end then the right.
Replace the cassette by putting the right end of the new cassette slightly onto the drive axle then gentle
pushing the left end into the clips.
The left end of the cassette can only be pressed in after the right end has been correctly seated onto the
drive axle. If alignment is difficult it may be necessary to turn the knob on the cassette slightly. Now check
that the ribbon is tight across the face of the cassette, which is on the inside of the cassette and across the
paper. Turn the knob clockwise again if the ribbon is on the outside of the cassette.
Ribbon Replacement;
Push back the mechanism head and lock it, close the cover of the printer and reconnect the power.
Push down on the mechanism release button in the top right corner to release the head.
109
MAN2994-7
Figure 120: Head Mechanism Rotation and Paper Roll Removal / Insertion
Note: Press only on the PUSH label to return the head mechanism back into position.
Note: The above instructions are graphically displayed on the inside of the front cover.
110
MAN2994-7
Jumper Settings
111
MAN2994-7
13.1 Networking
When FACP’s are connected to each other they form a “NETWORK“. Individual FACP’s in the Network are
referred to as NODES. The Network as defined by the limitations of the installation can consist of a number
of Nodes, the number of Nodes being dependant on the configuration of each Node. Typically an entire
Network could consist of 60 Slave CPU’s connected to loops and or input / output devices spread over several
nodes. The Network is Peer to Peer with the entire system configuration being stored at each Node. The
system is then programmed so that information can be made invisible to particular Nodes or visible to all
Nodes. Likewise system commands can be global or restricted to specific parts of the network.
The entire system can be programmed from any Node in the Network and is connected as a data loop which
provides redundancy should there be a single cabling fault.
IMPORTANT
While it is important that proper documentation is kept and maintained for any installation it becomes
even more important as a system develops into the larger types described above.
The Bias SW2 defaults to ON. SW2 is only switched to OFF when direct connecting the network to external
devices such as Optical Fibre Modems.
The Isolate SW3 Allows the network node to be isolated from the network
C4
C5
CN1
CN2
C2
U1
C3
26/07/2010
R3
CN3 TB1 TB2
ZDN1
MASTER
R4
ZDN2 R6 R1
R2
R5
C6
MAIN BOARD INTERFACE
0V
R8
R9
R7 D1 L1 L2
ZD4 LK1 ZD5
C7
R10 D2 D3
ZD3
C8
C9
ZD6
BRD86NIC1-
C11
Q1 R11 HEARTBEAT
R12
C10
SHIELD
TH1
LINK
R13
R14 N1236
TH2 TH3 TH4
U2 X1
C12
0V
OFF RL1 RL2
+L
-L
+L
-L
D4
ZD8
ZD9
NC2
ZD10
ZD7
NC1
BIAS
NC2
NC1
L3 D5
R15
R16
PANEL
C13
C2
C1
C2
C1
U3
L4
C19 C16
C20 C17
C18
TX
NO2
NO1
NO2
D6
NO1
L5 C15
L6 PANEL U4
C14 3V3 ON SW2
R22 ISOLATED
C24 R17 R18 R19 R20 R21
C21
RX
R23
C22
C25
U5 C23
D7 U8
L7 C26
C30
R26
L8
C28
COMMS
U6 C27 C29
C36
C32
R24 R25
D9
C35
D8
C31 U7
SW3
C33
D10
R27 C34
R32
R33
R28
R35
D11 R30
D12 R31
R29
C38
L9 C37
R34
C40
R36 D13 D14
C39
T1
POWER TH5
CN4 C41
R40
C44
R37
U9 R38 U10
RX IN R39 TX IN RX OUT TX OUT
C42 C47
Q2
D15
D16
R43
R41
C43 R42
C46
R44
R45
R46
27VDC
IN / OUT
PANEL 1
RESET BACKLIGHT 16 Way
MAIN BOARD SW1
EXPANSION
CN17 MODULE
CN20
SLAVE 4 SLAVE 3 SLAVE 2 CN3
CN100
4 CN13 3 CN14 2 CN15 MAIN BOARD INTERFACE
0V
CN11
NETWORK
CN5
CN18
COMMS
LOOP
D5
D7
TX
PANEL
RX
PANEL
CN6
POWER
SW2
NODE ADDRESS
12 3 4 5 6 7 8
27VDC NETWORK INTERFACE
IN
SLAVE CPU 4 SLAVE CPU 3 SLAVE CPU 2 CARD SW1
RESET
HEARTBEAT
MASTER
0V
3V3
TERMINATION BOARD
D2
D1
CN23 BIAS
ON
OFF
CN2
CN2
CN2
RS485
SW2
CN10
ZD7
TB1 COMMS
RX IN
D11
IN
DEBUG
DEBUG
DEBUG
LK1
LK1
LK1
+ -
COMMS IN
+
TX IN
-
1 D12
SHD
SHD
MAIN CPU
TP1
TP1
TP1
27V IN
RS485
LINK
SHIELD
CN26
LK1
RS485 EOL COMMS
+5V
LK2 CN9 PRINTER 27V TB2
COMMS 2 BUZZER O UT
COMMS OUT
+ -
RS232
+
PSU MONITOR
RX OUT
LK3 OUT CN16
EXPANSION
BRIGADE I/F
D13
CN27 BUZZER
-
MODULE
INHIBIT
ACTIVE
SHD
CN7
SHD
D16
TX OUT
CN6
ISOLATED
C18
D14
CN2 5 EXTRA CONTROLS
CN2
SW3
COMMS1 CN3 CN4 CN5
RS232/MODEM BZ1
+
CN1
D6
(BOTTOM) EXPANSION PANEL EXPANSION LEDS US B FRONT PANEL PRINTER
PANEL 2
BACKLIGHT 16 Way
MAIN BOARD RESET
SW1
EXPANSION
CN17 MODULE
CN20
SLAVE 4 SLAVE 3 SLAVE 2 CN3
CN100
4 CN13 3 CN14 2 CN15 MAIN BOARD INTERFACE
0V
CN11
NETWORK
CN18
CN5
COMMS
LOOP
D7
D5
TX
PANEL
RX
PANEL
CN6
P O WE R
SW2
NODE ADDRESS
NETWORK INTERFACE
12 3 4 5 6 7 8
27VDC
IN CARD
SLAVE CPU 4 SLAVE CPU 3 SLAVE CPU 2 SW1
RESET
HEARTBEAT
MASTER
0V
3V3
TERMINATION BOARD
D2
D1
CN23 BIAS
OFF
ON
RS485
CN2
CN2
CN2
SW2
CN10
ZD7
COMMS
RX IN
D11
TB1
IN
DEBUG
DEBUG
DEBUG
LK1
LK1
LK1
+-
COMMS IN
+
TX IN
-
1 D12
SHD
SHD
MAIN CPU
TP1
TP1
TP1
CN26
27V IN
LINK
SHIELD
RS485
LK1
RS232
+-
+
PSU MONITOR
RX OUT TX OUT
BRIGADE I/F
D13
BUZZER
CN7
CN27
-
MODULE
INHIBIT
ACTIVE
SHD
SHD
D16
C18
D14
CN1
D6
113
MAN2994-7
The Serial/Parallel Board consists of serial ports, a parallel port and an Ethernet port all under the control of
a microcontroller.
The serial port (RS232) has the capability to support a GSM Modem.
SERIAL
RS485
ZD1
PARALLEL TB1
TH1
( TB2
EXT FACP CN2
CN1
TH2
COMMS ) + - SHD
ZD2
ZD3
ZD4
+
RN1 RN2
ETHERNET
C1
R2 CN3
C15
-
C6
C10
C11
C12
C13
R1
C17
C7
C9
C8
C14
C18
L2
R6 R7 R8 R9
C20
C19
L1
SHD
R4
CN4 C16 RN3 RN4 RN5 RN6
TP89 TP1
R3 RS485 TP2
R10
EOL
R5
C30 C21
U1 C23
C22
C25
C26
+ INTERNAL FACP 3.3V 0V
U2
C27
0V
C24 R12
COMMS
C28 U4 U5 U3
C31
R13
R11
C29 C33 X1 C32 R35
-
R16
TB2 LK2 BRD43SPB4- U6
R14
C36
C34
0 V +27V 0 V +27V SHD
C35 C38
FACP U7
R15
C37
CN5
C44
L3 R17
L4EOL
R21
C40 R18
R19
C45 C41
C51 R20
C46 C49
C48
LK3 U8 C47
U9
- + FACP 0V
C63 L5
C52 C53 U10
R23
R25
C58
C59
C57
TP88 U11
C62 C56
R24
R27
C64
C65
R26
R28
C55
R29
ZDN1
RN7
5V
M1 C61
R30 N1236
TB3 C60 C67 R31
C68
R32
TH5 +
INTERNAL D1 C66 D2 D5 LSB MSB
CN7
M2 T1
ZD5
C71
ER
M
M3
C74
( TB3
C72 EXTERNAL +/-27V ) R34 1 2 3 4 SW1 ADDRESS
M
W
R33 Q1 C73
O
PO
Software
HLI – Functionality matches the FireFinder PLUS panel which supports text or positive ack protocol.
Configurable attributes are: logical output, physical output, alarm output, pre-alarm output, fault output,
isolate output and descriptors
114
MAN2994-7
NODE 1 RS 232
CN17
RS 485
CH15
D13
MAIN CONTROL BOARD CH16
TB1
+ - SHD
CN20
RJ45 CN2 SERIAL
CN13
CN14
PARALLEL
+
CN15
4 3 2 CN4
-
FACP COMMS
CN11
CN18 RS485
S HD
c
1
a b
CN2 CN2 CN2
EOL
a b
c
+
LOOP CN5
HLI CONTROLLER MODBUS
-
SLAVE CPU
SLAVE CPU
SLAVE CPU
LK2
U15
C OMMS
S HD
+2 7 V
FACP LK3
CPU BOARD
RN20 RN17
CN2
0V - + EOL
FACP 0V
+2 7V ADDRESS
0V LSB M SB
- +
U13 TB3
CN8 D6 D7 ZDN2
PO W ER
CO M MS
1 2 3 4 SW1
CN1
CN1
CN1
U14 1
U11
RJ45 RS 232
U10
CH8 CH8 CH6 CH8 RS 485
TP3
D14 CN10 TB1
+ - SHD
CN16
PSU MONITOR
CN2
BRIGADE I/F
SERIAL
27V IN
C12
CN7
CN6
PARALLEL
+
TH1
CN8 MODEM
R17
CN4
CN21
-
+
CH1 CN2
CH2
FACP COMMS RS485
S HD
EV3000
CN4
EOL
CN3
CN1
BZ1
EXPANSION PANEL EXPANSION LEDS FRONT PANEL CN5 PRINTER +
S HD -
LK2
+2 7 V
0V - +
FACP LK3 HLI
EOL FACP 0V
0V
ADDRESS
LSB M SB
- +
RS422 COMMS IN TB3
CN8 D6 D7 ZDN2
PO W ER
CO M MS
1 2 3 4 SW1
RJ45 RS 232
2 WIRE & SHIELD
RS422 COMMS OUT RS 485
RESET COMMS IN COMMS OUT TB1
+ - SHD + - SHD
SW1
CN3 C N1
CN2 + - SHD
TB1 TB2
BRD86NIC1-
SERIAL
MAIN BOARD MASTER
D1 PARALLEL
+
INTERFACE HEARTBEAT
D2
CN4
-
LK1 FACP COMMS RS485
S HD
N1236
SHIELD
LINK
+
EOL
BMS
CN5
HLI CONTROLLER
S HD -
LK2
NETWORK ISOLATED
D6
+2 7 V FACP LK3
Nurse Call
0V - + EOL
INTERFACE +2 7V
FACP 0V
ADDRESS
COMMS
LSB M SB
BOARD
0V
SW3
- +
TB3
CN8 D6 D7 ZDN2
PO W ER
CO M MS
D11
D12
D13 D14
D16
ZD13
ZD11
CH15
MAIN CONTROL BOARD CH16
TB1 TB4
D13
+ - COM +24V 0 V
RS485 OUT POWER OUT
CN13 CN20
COMMUNICATIONS
CN14
CN15
4 3 2
CN18
CN11
c
EXTENDER BOARD
1
a b
CN2 CN2 CN2
a b
c LOOP BRD82LTB2
C OMMS
CN4 Ancilliary Module
SLAVE CPU
SLAVE CPU
SLAVE CPU
U15
RN20 RN17
CN2
CN5
Fire Fan Module,
U13
CN1
CN1
U14 1
U11
TP3
D14 CN10
CN16
PSU MONITOR
BRIGADE I/F
27V IN
C12
CN7
CN6
R17
CN8 MODEM
TH1
CN21
CH1 CN2
CH2
CN4
CN3
CN1
BZ1
EXPANSION PANEL EXPANSION LEDS FRONT PANEL CN5 PRINTER
16 Way
2 WIRE & SHIELD
RS422 COMMS IN
C N1
TB1 TB2
BRD86NIC1-
MA S T ER
MAIN BOARD D1
D2
LK1
INTERFACE H EARTBEAT
N1236 SHIELD
LINK
D6
NETWORK ISOLATED
INTERFACE
COMMS
SW3
CARD
D11
D12
D13 D14
D16
ZD13
ZD11
CN5 CN6
ACTIVE
27V IN/OUT
115
MAN2994-7
The High Level Interface board (BRD43HLI) provides RS232, RS485 and RS422 communications for interfacing
to various external systems.
SmartView is an extensible web-based, client server application whose primary role is dedicated to the
monitoring and reporting of Ampac’s fire detection system events.
SmartView provides clear and precise alarm information using graphical and text formats.
116
MAN2994-7
15 Certification Information
7 Ledgar Rd
Balcatta 6021
Western Australia
Manufactured to:
Date of Manufacture:
117
MAN2994-7
General
✓ Visually inspect in and around the panel for any signs of pests, moisture or general damage
✓ Ensure any non FACP standby power facilities are in a state of operational readiness
✓ Force a suitable device, such as an MCP or detector, into an alarm state so that it generates a
know alarm outcome. This process should be controlled and established in consultation with all
interested parties (installing engineers include) so that maximum benefit is obtained from the
test.
✓ Ensure the Site Log Book” is up to date, faults have been attended to and the latest test are
recorded
✓ Check all internal connections and perform “alarm”, “fault” and site specific tests
✓ Perform a “walk around” of the site to determine if the system integrity is free of possible faults
✓ Ensure the Site Log Book” is up to date, faults have been attended to and the latest test are
recorded
✓ Initiate both a “lamp” and “walk” test and any other tests as determined necessary for the site
✓ Inspect and test ( as per the manufacturers specifications ) batteries
✓ Ensure the Site Log Book” is up to date, faults have been attended to and the latest test are
recorded
118
MAN2994-7
✓ Batteries and fuses are seen as the only field replaceable components.
✓ If a board field change is required all necessary anti-static precautions must be taken.
Note: If the Main Board is changed the power supply may require re-calibration.
Problem Solution
No Mains Power Check mains Fuse
Check output voltage it should be set to 27.6V.
Low = (less than 26.5V )
Power Fault LED illuminated
High = (greater than 28V )
Check the battery has been connected properly
Check all input and output cabling and wiring
Earth Fault LED illuminated assemblies for short to ground or resistance <50
Ohms
Ensure correct software is installed
System Fault LED illuminated
Check all connections for loose wiring
Maintenance Alarm cleared but FireFinder
Carry out Loop Test
PLUS still displays Maintenance Alarm
Check in and out legs are connected correctly at
LCD displays LOOP (number) open circuit the loop termination board
Unable to clear an O/C or S/C on a loop You must perform a loop test to clear the fault.
Check for correct software installed in all
communication boards.
Communication Loop not working
Check LCD at Main controller. This may identify
where there is a break in the communication line
Can not access Function menu Incorrect Password entered
Ring AMPAC and directions will be given to
Forgotten password
provide you with a temporary code
An Analogue Fault occurs when using a A 1.8k Ohm resistor must be placed in series with
Zone Monitor to monitor a switch. the switch contacts.
Make sure you have a 10K Ohm EOL resistor fitted
Sounder Fault
and a diode (1N4004) in series with the sounder
119
MAN2994-7
17 Compatible Devices
AMPAC Auto Learn
Device Type Displayed Type (19 chars) Type Desc
Type Code Default
Optical
05h XP95 Optical XP95 PHOTO PHOTO
05h XP95 Optical with base sounder XP95 PHOTO + SNDR PHOTO
05h XPander Optical XPANDER PHOTO PHOTO
05h S90 Optical S90 PHOTO PHOTO
05h Xplorer Optical XPLORER PHOTO PHOTO
05h Xplorer Optical with base sounder XPLR PHOTO + SNDR PHOTO
05h XP95 Beam XP95 BEAM PHOTO
0Dh XP95 Reflective beam XP95 REFLECT BEAM BEAM
105h Discovery Optical DISC PHOTO PHOTO
105h Discovery Optical with base sounder DISC PHOTO + SNDR PHOTO
11Dh Discovery Multisensor DISC MULTISENSOR MULTI
11Dh Discovery Multisensor with base sounder DISC MULTI + SNDR MULTI
15h XP95 Flame XP95 FLAME FLAME
1Dh XP95 Multisensor XP95 MULTISENSOR MULTI
1Dh XP95 Multisensor with base sounder XP95 MULTI + SNDR MULTI
1Dh XPander Multisensor XPANDER MULTI MULTI
31Dh Enhanced Discovery Multisensor EDSC MULTISENSOR MULTI
31Dh Enhanced Discovery Multi + base sounder EDSC MULTI + SNDR MULTI
Heat Detectors
06h XP95 Heat XP95 HEAT HEAT
06h XP95 Heat with base sounder XP95 HEAT + SNDR HEAT
06h XPander Heat XPANDER HEAT HEAT
06h S90 Heat S90 HEAT HEAT
06h Xplorer Heat XPLORER HEAT HEAT
06h Xplorer Heat with base sounder XPLR HEAT + SNDR HEAT
0Eh XP95 Hi temp XP95 HI HEAT HHEAT
0Eh XP95 Hi temp with base sounder XP95 HI HEAT + SNDR HHEAT
0Eh XPander Hi temp XPANDER HI HEAT HHEAT
0Eh Xplorer Hi temp XPLORER HI HEAT HHEAT
0Eh Xplorer Hi temp with base sounder XPLR HI HEAT + SNDR HHEAT
106h Discovery Heat DISC HEAT HEAT
106h Discovery Heat with base sounder DISC HEAT + SNDR HEAT
Ionisation
03h XP95 Ion XP95 ION ION
03h XP95 Ion with base sounder XP95 ION + SNDR ION
03h S90 Ion S90 ION ION
103h Discovery Ion DISC ION ION
103h Discovery Ion with base sounder DISC ION + SNDR ION
10Bh Discovery Carbon Monoxide DISC CO CO
10Bh Discovery Carbon Monoxide with base sndr DISC CO + SNDR CO
120
MAN2994-7
Sounders
01h XP95 sounder / sounder control unit XP95 SOUNDER SNDR
01h XPander sounder XPANDER SOUNDER SNDR
01h XP95 integrated base sounder XP95 INTGR BSE SNDR SNDR
01h XP95 Intelligent base sounder XP95 INTEL BSE SNDR SNDR
01h XP95 sounder beacon base XP95 SND BEACN BSE SNDR
01h XP95 loop powered beacon XP95 LOOP PWR BEACN SNDR
01h S90 sounder control unit S90 SCU SNDR
111h Discovery sounder beacon base/open area DISC SOUNDER BEACN SNDR
I/O Units
02h XP95 input / output module XP95 I/O I/O
02h XPander I/O (Relay) Unit XPANDER I/O I/O
02h XP95 three channel input / output module XP95 3I/O I/O
02h XP95 output module XP95 OUTPUT I/O
02h XP95 mains switching input / output module XP95 MAINS I/O I/O
02h S90 single channel I/O unit S90 SINGLE I/O I/O
02h S90 3 channel I/O unit S90 3I/O I/O
02h S90 3 channel analogue I/O unit S90 3I/O + ANALOGUE I/O
02h S90 switch monitor unit S90 SWITCH I/O
02h Xplorer output module XPLORER OUTPUT I/O
Zone Monitors
04h XP95 zone monitor XP95 ZONE MONITOR CONV
04h XPander Loop Interface XPANDER INTERFACE RADIO
04h S90 zone monitor S90 ZONE MONITOR CONV
User Defined
10h XP95 AAF XP95 AAF AAF
121
MAN2994-7
18 Address Setting
BINARY ADDRESS SETTING (APOLLO)
SERIES XP95 - ADDRESS DATA
DIL SWITCH: ON = 1 OFF = 0 ADDRESS TAG FOR DETECTORS (I/O DEVICES)
DIL switch setting DIL switch setting DIL switch setting DIL switch setting DIL switch setting
Address 1234567 Address 1234567 Address 1234567 Address 1234567 Address 1234567
1 1000000 26 0101100 51 1100110 76 0011001 101 1010011
2 0100000 27 1101100 52 0010110 77 1011001 102 0110011
3 1100000 28 0011100 53 1010110 78 0111001 103 1110011
4 0010000 29 1011100 54 0110110 79 1111001 104 0001011
5 1010000 30 0111100 55 1110110 80 0000101 105 1001011
6 0110000 31 1111100 56 0001110 81 1000101 106 0101011
7 1110000 32 0000010 57 1001110 82 0100101 107 1101011
8 0001000 33 1000010 58 0101110 83 1100101 108 0011011
9 1001000 34 0100010 59 1101110 84 0010101 109 1011011
10 0101000 35 1100010 60 0011110 85 1010101 110 0111011
11 1101000 36 0010010 61 1011110 86 0110101 111 1111011
12 0011000 37 1010010 62 0111110 87 1110101 112 0000111
13 1011000 38 0110010 63 1111110 88 0001101 113 1000111
14 0111000 39 1110010 64 0000001 89 1001101 114 0100111
15 1111000 40 0001010 65 1000001 90 0101101 115 1100111
16 0000100 41 1001010 66 0100001 91 1101101 116 0010111
17 1000100 42 0101010 67 1100001 92 0011101 117 1010111
18 0100100 43 1101010 68 0010001 93 1011101 118 0110111
19 1100100 44 0011010 69 1010001 94 0111101 119 1110111
20 0010100 45 1011010 70 0110001 95 1111101 120 0001111
21 1010100 46 0111010 71 1110001 96 0000011 121 1001111
22 0110100 47 1111010 72 0001001 97 1000011 122 0101111
23 1110100 48 0000110 73 1001001 98 0100011 123 1101111
24 0001100 49 1000110 74 0101001 99 1100011 124 0011111
25 1001100 50 0100110 75 1101001 100 0010011 125 1011111
126 0111111
ON ON
1 2 3 4 1 2 3 4 5 6 7 8
122
MAN2994-7
2 8 32
11
1 4 16 64
= PUNCH OUT
Figure 129: Xpert Card addressing set to Address 11
123
MAN2994-7
19 Glossary of Terms
ACF: ANCILLARY CONTROL FACILITY
ACKD: ACKNOWLEDGED
AHU: AIR HANDLING UNIT
ALM: ALARM
AVF: ALARM VERIFICATION FACILITY
AZF: ALARM ZONE FACILITY
AZC: ALARM ZONE CIRCUIT
C: RELAY COMMON CONTACT (WIPER)
CIC: CONTROLLER INTERFACE CARD
CN: CONNECTOR
CPU: COMMON PROCESSOR UNIT
DGP: DATA GATHERING POINT
EARTH: BUILDING EARTH
EOL: END OF LINE
FACP: FIRE ALARM CONTROL PANEL
FLT: FAULT
GND: GROUND (0 VOLTS) NOT EARTH
I/O: INPUT/OUTPUT
LCD: LIQUID CRYSTAL DISPLAY
MAF: MASTER ALARM FACILITY
MCP: MANUAL CALL POINT
MOV: METAL OXIDE VARISTOR (TRANSIENT PROTECTION)
NIC: NETWORK INTERFACE CARD
N/C: NORMALLY CLOSED RELAY CONTACTS
N/O: NORMALLY OPEN RELAY CONTACTS
N/W: NETWORK
PCB: PRINTED CIRCUIT BOARDS
P/S: POWER SUPPLY
REM: REMOTE
TB: TERMINAL BLOCK
124
MAN2994-7
20 Definitions
Addressable system - a fire alarm and detection system that contains addressable alarm zone facilities or
addressable control devices.
Alarm Verification Facility (AVF) - that part of the FACP, which provides an automatic resetting function for
spurious alarm signals so that they will not inadvertently initiate Master Alarm Facility (MAF), or ACF
functions. Using ConfigManager PLUS prior to downloading to the FireFinder PLUS sets this option
Alarm zone - the specific portion of a building or complex identified by a particular alarm zone facility.
Alarm Zone Circuit (AZC) - the link or path that carries signals from an actuating device(s) to an alarm zone
facility(s).
Alarm Zone Facility (AZF) - that part of the control and indicating equipment that registers and indicates
signals (alarm and fault) received from its alarm zone circuit. It also transmits appropriate signals to other
control and indicating facilities.
Alert signal - an audible signal or combination of audible and visible signals, from the occupant warning
system to alert wardens / personnel as necessary to commence prescribed actions.
Ancillary Control Facility (ACF) - that portion of the control and indicating equipment that on receipt of a
signal initiates predetermined actions in external ancillary devices.
Ancillary equipment - remote equipment connected to FACP.
Ancillary relay - relay within FACP to operate ancillary equipment.
Ancillary output - output for driving ancillary equipment.
Approved and approval - approved by, or the approval of, the Regulatory Authority concerned.
Card-detect link - a link on a module connector to indicate the disconnection of the module.
Conventional System - is a fire detection system using a dedicated circuit for each alarm zone.
Distributed system-a fire alarm and detection system where sections of the control and indicating equipment
are remotely located from the FACP or where sub-indicator panel(s) communicate with a main FACP.
Field connections - are connections made to FACP or ancillary equipment during installation.
Fire Alarm Control Panel (FACP) - a panel on which is mounted an indicator or indicators together with
associated equipment for the fire alarm or sprinkler system.
Fire resisting - an element of construction, component or structure which, by requirement of the Regulatory
Authority, has a specified fire resistance.
Indicating equipment - the part of a fire detection and or alarm system, which provides indication of any
warning signals (alarm and fault), received by the control equipment.
Interface - The interconnection between equipment that permits the transfer of data.
Master Alarm Facility (MAF) - that part of the equipment which receives alarm and fault signals from any
alarm zone facility and initiates the common signal (alarm and/or fault) for transmission to the fire control
station. Bells and other ancillary functions may be initiated from this facility.
Power Supply - that portion of the FACP which supplies all voltages necessary for its operation.
Regulatory Authority - an authority administering Acts of Parliament or Regulations under such Acts
125
MAN2994-7
21 Specifications
Metal SP1M (Europe Only) Metal SP8X
Mechanical
845 (H) x 518.5 (W) x 173(D)
Dimensions Cabinet: ( mm ) 505 (H) x 407 (W) x 150 (D)
Includes window outer door
Material 1.2mm Mild Steel 1.2mm Mild Steel
Environmental
Temperature: -5ºC to + 40ºC
Humidity: 0% to 95% non-condensing
IP rating IP30
Mains Input
Input Voltage: 195 - 264VAC 195 - 264VAC
Protection (Quick Acting Fuse):
5 AMP Supply 2Amp 3AG Slow Blow 2A 3AG Slow Blow
18 AMP Supply N/A 5A 3AG Slow Blow
Minimum Cable Requirements: Not less than 0.75mm² Not less than 0.75mm²
Power Supply
126
MAN2994-7
127
NOTE:
1: At Access Level 1, the entire MENU is not accessible.
2: At Access Level 2, the MENU is active and partial FUNCTION options are active
= ACCESS LEVEL 2 The user shall be presented with the ACCESS option to enter the level 3 FUNCTION's
3: At access level 3, all FUNCTION options are available
= ACCESS LEVEL 3
MENU
0 1 2 3 4
ALARMS STAGE-1 ALARM PRE-ALARMS FAULTS DISABLES
0 1 2 3 3/4 4/5 5/6 6/7 7/8 8/9
ZONE /
DEVICE LOOP MODULES * COMMS P/SUPPLY BRIGADE TFAILS SOUNDERS ADD ONS SYSTEMS
* APPLICABLE ONLY WHEN PANEL NETWORKED
5 6
WALK TEST STATUS * APPLICABLE ONLY WHEN PANEL NETWORKED
0 1 2 3 4 4/5 5/6 6/7
LOOPS MODULES I/O BRIGADE * NETWORK SYSTEM AVALUES ADD ONS
0 1 0 1 0 1 0 1
PRINT PRINT POWER NETWORK REMOTE
ALL DEVICES TOTAL SLAVE SUPPLY OUTPUTS INPUTS POINTS SLAVE MODULE
0 1 0 1 2
POWER
22 QUICK REFERENCE GUIDE
7 8 9
TOOLS SETUP ABOUT
0 1 2 0 1 2
ZONE
ALARM FAULT LAMP SOUNDER DELAY PRINTER
* = ACCESS LEVEL 3
0 1 0 1 0 1 2* 3* 0 1 0 1
SOUNDER SOUNDER SOUNDER SOUNDER ALL ZONE ALL ZONE GO OFF-LINE ALARM
ZONE DEVICE ZONE DEVICE ENABLE DISABLE RE TRIGGER (ON) RE TRIGGER (OFF) DELAY ON DELAY OFF / GO ON-LINE MODE ONLY
FUNCTION
0 1 3 5
GLOBAL
DATE TIME LOGS * = ACCESS LEVEL 3 I/O
0 1 2 3 4 5* 4* 0 1 2 3 4 5
ERASE ALL REMOVE ALL
ALARM FAULT DISABLE SYSTEM I/O WDOG INPUT OUTPUT MANUAL CONTROL FWRE FARE WARNING SYSTEM
LOGS
0 1 0 0 1 2 0 1
PRINT SHOW PRESS ENTER CLEAR WATCH REMOVE ALL
ENTRY OPTIONS TO CONFIRM COUNTER IN A PANEL ON A LOOP MANUAL CONTROL ENABLE DISABLE
7 0 1 2
* ENTER ACCESS CODE VIEW BY VIEW BY PRINT MULTIPLE
ACCESS* ENTRY NUMBER DATE ENTRIES
FOR LEVEL 3 FUNCTIONS
FUNCTION
2 4 7 8
DAY/NIGHT TESTS PASSWORD PROGRAMMING
0 1 2 0 1 0 1 2 0 1 2 3 4 5 6
ENABLE / ADD DELETE DELETE ALL CONV PANEL SUB ZONE
DAY TIME NIGHT TIME DISABLE WALK TEST LOOP TEST PASSWORD PASSWORD PASSWORDS ZONE DEVICE INPUT OUTPUT BASED MCP ADDRESS PROGRAMMING
128
MAN2994-7
23 Statement of Compliance
Please PRINT
1. Name of Building:
2. Address:
3. I/We have installed in the above building an alteration to the system manufactured by, OR a system
manufactured by. (Name of Service Provider)
5. Date of connection / /
7. Current drain of ancillary loads powered from the FACP power supply
14. Portions of the building not protected by this system are; (Please PRINT)
1 6
2 7
3 8
4 9
5 10
129
MAN2994-7
15. I/We
1.
2.
3.
Print Name/s
Hereby certify that the installation has been thoroughly tested from each actuating device and that a test of
the transmission of the alarm signal to the monitoring service provider has been satisfactorily carried out.
I/We further certify that the whole system and all components called up in Clause 1.3 in connection therewith
are installed entirely in accordance with the current requirements of AS 1670.l, -
Except with regard to the following details which have already been approved, approval attached.
Strike out the bolded sentence if there have not been any exceptions.
Signature Date / /
Installing Company
130
MAN2994-7
Additional Information:
(Attach if necessary)
131
MAN2994-7
Street
Suburb
State / Country
Post Code
(Company Name & Installation Address )
Street
Suburb
State / Country
Post Code
Street
Suburb
State / Country
Post Code
Signature:
132
MAN2994-7
24.1 Procedure
The following tests are the minimum that shall be performed when commissioning a system using the
FireFinder PLUS Fire Alarm Control Panel. Supplements to these tests may be added by way of attachments
or notation (using waterproof ink) to this documentation. If supplements or tests are added reference to
them shall be made at an appropriate point on this document.
This Commissioning Record provides a complete description of the installed system and its tested
performance at the time of being commissioned and should be completed in conjunction with the -.
133
MAN2994-7
(h) Alarm zone parameters: Each alarm zone circuit is within the equipment
manufacturer’s specifications.
(i) Wire-free alarm zones: Wire-free actuating device parameters meet the
minimum parameters specified by the manufacturer,
including that the receiver responds to signals from an actuating device for
alarm, tamper, low standby power signals and gives a fault signal when the
supervisory signal condition is absent.
(j) Operation of fault and alarm signals: Fault and alarm conditions correctly
detect and indicate as the correct. alarm zone, operating other required
indicators, and operate relevant outputs of the CIE.
(k) Mimic panel: All mimic panels, annunciators, etc., operate correctly.
(l) Alarm zone controls: Alarm test, fault test, isolate and reset facility of
each alarm zone operates correctly.
(m) Alarm dependency: Alarm dependency works correctly and does not
apply to devices listed in Clause 3.3 of AS 1670.1.
(n) CIE response to actuating device operation: Each actuating device has
operated when tested with a medium suitable for the device type and the
alarm has indicated on the FIP and at the tested device.
(o) Fault response time: The response to a fault does not exceed 100 s for
each alarm zone circuit.
(p) Alarm response time: At least one detector in each alarm zone has been
tested and the response to the alarm does not exceed 10 s or the period
specified when dependency on more than one alarm signal is used.
(q) Supervisory signal response time: At least one supervisory device in each
alarm zone circuit has been tested and the response to the supervisory
device does not exceed 100 s.
(r) Alarm acknowledgment facility: Alarm acknowledgement facilities
operate in accordance with the requirements of Clause 3.2 AS 1670.1.
(s) Occupant warning system:
(i) A fault signal is displayed at the CIE when the circuit wiring at the last
speaker or sounder is short or open circuited.
(ii) Each sounder/speaker operates in accordance with the requirements of
Clause 3.22 of AS 1670.1 and a record of the sound pressure level has been
made.
(t) The external alarm indication: is visible from the main approach to the
building.
(u) Manual call points
DOCUMENTATION
The following documentation is located in or adjacent to the FIP:
(a) ‘As-installed’ drawings.
(b) CIE documentation required by AS 4428.1 or AS 7240.2.
135
MAN2994-7
136
MAN2994-7
UNCONTROLLED DOCUMENT
NOTE: Due to AMPAC’s commitment to continuous improvement specifications may change without
notice.
137