Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
0% found this document useful (0 votes)
132 views146 pages

MAN2994 7 FireFinder Plus AS7240 Inst Comm 1

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 146

Fire detection and evacuation solutions that save lives.

Fire Alarm Control Panel


(AS7240–2 & 4 / AS4428-3)
Installation, Commissioning & Operation
MAN2994-7
MAN2994-7

Responding to a Fire

Access Level 1

The indicator will be illuminated. The applicable zone indicator will also be illuminated
if a Zone Board is installed otherwise details of the Loop, Sensor and Zones in alarm are displayed on the LCD as follows.

FIRST ALARM: L1 D1 Z1 15:31


D.DSC:Loop 1 Sensor 1
Z.DCS:Zone 1
LAST ALARM: L4 D49 Z5 15:31
D.DSC:Loop 4 Sensor 49
Z.DCS:Zone 5 Depend C
PRESS PREVIOUS/NEXT TO VIEW OTHER ALARMS
AC:2Z ALM:5 PALM:0 FLT:0 DIS:0

This control is used to silence the local buzzer. Pressing this button will silence the panel buzzer, which
sounds whenever there is a fire alarm or fault. The sound for a fire alarm is a steady sound where as for a
fault it is intermittent.

Access Level 2 – Default Access level when the door is opened.

When the alarm devices are active (FACP is in the fire condition), activating this control will silence all alarms
excluding the External Alarm device.

Activating the control again, will resound the previously silenced alarm devices.

If a new alarm is recognised whilst the alarm devices are “silenced”, then all alarm devices shall resound.

Note: If Delays to Outputs have been configured, to investigate the delayed Alarm condition press the “Next” button
and “Enter” button.

Previous and Next controls are used to scroll the events on the LCD. The events being displayed
depends on the current selected view, ie Zone Mode or Device Mode.

When the “SEVERAL ALARMS” indicator is illuminated, then multiple fire alarms are present on the FACP.
In order to view the alarms the PREVIOUS and NEXT controls are used.

A Zone or Device can be disabled when in an Alarm or Fault condition by pressing the Disable button.

Note: The Alarm condition takes precedence and no alarms must be present for using this button to disable faults.

**Note: The “Disable” button will not clear the Fire Alarm condition. A subsequent “Reset” operation is required to
clear the Fire Alarm condition as per the requirements of AS4428-3:2010 clause 2.2.10.
MAN2994-7

This control is used to reset the FACP from the fire condition and to clear the system fault indicator.

When using the Reset button to clear a fire condition, alarm devices must have been silenced first by means
of Alarms Silence / Resound control.

Disabling a Zone / Device

Zone Disablement

Press

FIREFINDER 17/10/2013 09:00:00

ZONE:______

SELECT ZONE NO. THEN TO OR DISPLAY OR


ZONE/DEVICE DISABLE/ENABLE KEY

AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

then Press for Zone 1 selection. Now Press the .

FIREFINDER 17/12/2012 09:00:00

ZONE:1
0:FULL ENABLE 1:FULL DISABLE

AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Then select to Disable the Zone.


MAN2994-7

Device Disablement

Press the then enter Loop number, Press then enter device number.

FIREFINDER 17/10/2013 09:00:00

LOOP:1 DEVICE:1

SELECT DEVICE NO. THEN TO OR DISPLAY OR


ZONE/DEVICE DISABLE/ENABLE KEY

AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Now Press the .

In either case the Disable LED will illuminate and the screen will display the disabled information

Loop 1 Sensor 1 MCP

L1 D1 Z1

STAT:NORMAL /DISB

ZONES DISABLES 1 of 1
AC:2Z ALM:0 PALM:0 FLT:0 DIS:1
MAN2994-7

Contents
Responding to a Fire 2
Access Level 1 2
Access Level 2 – Default Access level when the door is opened. 2
Disabling a Zone / Device 3
Zone Disablement 3
Device Disablement 4
1 About This Manual 1
1.1 Introduction 1
1.2 General Requirements 1
1.3 References 1
1.4 Symbols 1
2 Introduction 2
2.1 System Overview 2
2.2 Key Features 2
2.3 Compliance 3
2.4 FACP Configuration Examples 4
3 FireFinder PLUS Description 5
4 Placing The Basic System Into Operation 7
4.1 Unpacking 7
4.2 Anti-Static Precautions 7
4.3 Working on the System 7
4.4 The Cabinet 7
4.5 Cabling Recommendations 9
4.6 Power Supplies and AC Mains Installation 11
4.6.1 Connecting the Mains Earth 11
4.6.2 Connecting 5 AMP Power Supply 11
4.7 CORRECT Power Up / Turn “ON” Procedure 12
4.8 Brigade / PSU Monitor Board 12
4.8.1 Battery Connections 14
4.8.2 Auxiliary 27 Volt Power 15
4.8.3 Monitored Inputs 15
4.8.4 Monitored Outputs 17
4.8.5 Relay Output Connections 18
4.9 High Current Interface Board 19
MAN2994-7

4.10 Main Board 20


4.11 Front Panel Board 22
4.12 Main CPU 23
4.13 Slave CPU 24
4.14 Addressable Dual Loop Termination Board 25
4.14.1 Detector loop Isolator Installation 27
4.14.2 Loop Isolator calculator 27
4.14.3 Loop Open / Short Circuit. 28
5 FireFinder PLUS Control Panel 29
5.1 System Controls 29
5.2 System Indicators 33
6 Functions And Menus 36
6.1 The Default LCD Display 36
6.2 LCD Contrast 36
6.3 Accessing Functions and Menus 37
6.4 Function Menu and Access Levels 37
6.4.1 Forgotten Passwords 37
7 The Main Menu 38
7.1 Alarms 38
7.2 Stage 1 Alarms 38
7.3 Pre-Alarms 39
7.4 Faults 39
7.5 Disables 41
7.6 Walk Tests 41
7.7 Status 42
7.8 Tools 46
7.9 Setup 47
7.10 About 48
8 The Function Menu 49
8.1 Date 49
8.2 Time 49
8.3 Day/Night 50
8.4 Logs 50
8.5 TESTS 51
8.6 I/O 52
MAN2994-7

8.7 Global 53
8.8 Passwords (Level III) 54
8.9 Programming 55
8.9.1 Conv (Conventional) Zone 55
8.9.2 Device 56
8.9.3 Input 57
8.9.4 Output 58
8.9.5 Panel Based MCP 58
8.9.6 Sub Address 58
8.9.7 Zone programming 58
8.9.8 Extra Devices Detected 59
8.9.9 Mismatch Detected 60
9 Incoming Fire Alarm Signal 60
10 Accessing a Loop, Device or Zone 62
11 Modem / Programming / Debug Interfacing 63
12 Expanding the FACP with Compatible FireFinder PLUS Boards 64
12.1 Ancillary Services 64
12.2 Compatible FireFinder PLUS Boards 64
12.3 Expansion Board 65
12.4 8 Zone Conventional Board 66
12.5 16 Zone and 32 Zone Indicator Modules 67
12.6 8 Way Switch and Indicator Module 68
12.7 Zone Disable and Indicator Module 69
12.8 16 Way Input Board 70
12.9 8 Way Relay Board 71
12.9.1 Internal Relay Board 71
12.9.2 Remote Relay Board 72
12.10 8 Way Sounder Board 73
12.11 4 Way Fire Fan Module 74
12.12 4 Way Fan Termination Board 75
12.13 Bargraph Display Card 76
12.13.1 Mechanical 76
12.13.2 Front Panel Decal 76
12.13.3 Front Panel Controls 76
12.14 Communications Extender Board 77
MAN2994-7

12.15 SmartTerminal 77
12.15.1 Overview 78
12.15.2 Mechanical 78
12.15.3 Installation & Cabling 79
12.15.4 Setting the SmartTerminal Address 80
12.15.5 Operation 81
12.15.6 SmartTerminal Controls and Indicators 82
12.15.7 SmartTerminal Screen Format 82
12.16 Agent Release Control 85
12.16.1 Operation 85
12.16.2 Agent Release Module 89
12.16.3 Local Control Station 91
12.16.4 Agent Release Termination Board 95
12.16.5 Interface Wiring 97
12.16.6 Warning Signs 98
12.17 Occupant Warning Systems 103
12.17.1 Amplifier Board (25W and 50W) 103
12.17.2 Front Panel Switch and Indicator Module 105
12.17.3 Panel Interfacing 106
12.18 Printer 107
12.18.1 Indicators and Buttons 107
12.18.2 Maintenance 109
12.18.3 Printer Connections and Jumpering 111
12.18.4 Printer 5 Volt Power Supply 111
13 Expanding the System – Networking 112
13.1 Networking 112
13.2 Network Interface Card 112
14 High Level Interfacing 114
14.1 High Level Interface Expander (BRD43SPB) 114
14.2 High Level Interface Expander (BRD43HLI) 116
14.2.1 SmartView Graphics 116
15 Certification Information 117
16 Maintenance and Troubleshooting Chart 118
16.1 Maintenance 118
16.2 Troubleshooting FireFinder PLUS 119
MAN2994-7

17 Compatible Devices 120


18 Address Setting 122
19 Glossary of Terms 124
20 Definitions 125
21 Specifications 126
22 QUICK REFERENCE GUIDE 128
23 Statement of Compliance 129
23.1 Installation Details 131
24 Commissioning Test Report 132
24.1 Procedure 133
24.2 System Information 133
MAN2994-7

1 About This Manual


1.1 Introduction
This manual contains all the information required to install, commission and operate the FireFinder PLUS Fire
Alarm Control Panel (FACP) and is only available to and for the use of personnel engaged in its installation,
commissioning and operation.

1.2 General Requirements


The FireFinder PLUS FACP has been designed and manufactured from high quality commercial components
so as to comply with major world standards. To ensure these standards are not compromised in any way
installation staff and operators should;

✓ Be qualified and trained for the task they undertake;


✓ Be familiar with the contents of this manual prior to the installation, commissioning or operation
of a FireFinder PLUS control system;
✓ Observe anti-static pre-cautions at all times; and
✓ Be aware that if a problem is encountered or there is any doubt with respect to the operational
parameters of the installation the supplier should be contacted.

1.3 References
ConfigManager PLUS: Operation Manual

Apollo: Detector / Device Manuals

Ampac: Product Data Sheets

Australian Standard:

AS7240 - 2: 2004 Control and Indicating Equipment


AS7240 - 4: 2004 Power Supply Equipment
AS4428 - 3: 2010 Fire Brigade Panel

1.4 Symbols
 Important operational information

Note: Configuration considerations

Observe antistatic precautions

Mains supply earth

DANGER mains supply present


1
MAN2994-7

2 Introduction
2.1 System Overview
The purpose of the FireFinder PLUS Fire Alarm Control Panel (FACP) is to monitor changes in inputs, report
those changes and update selected outputs as programmed.

2.2 Key Features


The FireFinder PLUS panel is capable of supporting:

➢ Apollo Discovery and XP95 Intelligent Detectors, Multisensor, Photoelectric, Ionisation,


Thermal (heat) and CO detectors.

➢ Conventional two wire zone detector circuits

➢ Multiple input/outputs

➢ Agent Release

➢ Fan Control

➢ High Level Interfaces

➢ SmartGraphics

➢ EV3000 – Early Warning System

➢ Nurse Call

➢ SmartTerminal

➢ Remote LED mimics

➢ Peer to Peer networking

➢ Master Slave (Main - Sub) networking

➢ Main panel plus Data Gathering Panels networking

Figure 1: Typical Application

2
MAN2994-7

2.3 Compliance
The FireFinder PLUS FACP is approved to AS7240 – 2 & 4 and AS4428 – 3:2010 and includes the following
‘Optional requirements’ as defined by AS7240-2:2004:

➢ 7.8 Output to fire alarm devices

➢ 7.9.1 Output to fire alarm routing equipment

➢ 7.9.2 Input from fire alarm routing equipment

➢ 7.10.1 Output type A to fire protection equipment

➢ 7.11.1 Delays to outputs – configuration of delays (for item C)

➢ 7.11.2 Delays to outputs – control of delays (for item C)

➢ 7.12.1 Dependency Type A

➢ 7.12.2 Dependency Type B

➢ 7.12.3 Dependency Type C

➢ 9.3 Fault signals from points

➢ 9.9 Output to fault warning routing equipment

➢ 10 Disable condition

➢ 10.5 Disablement of addressable points

➢ 11 Test condition

➢ ZB Alarm Acknowledgement Facility

➢ ZD Ancillary Control function

The FireFinder PLUS PSE includes the following ‘Optional requirement’ as defined by AS7240-4:2004:

➢ 5.5 Battery function check

3
MAN2994-7

2.4 FACP Configuration Examples

FRONT PANEL CONTROL


EARTH
STUD
CN17

2 LOOP TERMINATION BOARD MAINS


MAIN CONTROL BOARD

GROUND
CH16
CH15

NEUTRAL
D13 CN20
SWITCH

ACTIVE
L2+ L1-
DANGER

A
CN13
CN14

+VE
240V
CN15

CN3

-VE
+35V
EXT
4 3 2

CN1
CN2

L2+ L1-
CN11 CN18

B
c

1
a b

+35V
16 WAY

EXT
CN2 CN2 CN2

LOOP COMMS
c
a b

U15

+ -
L2+ L1-
POWER
RN20 RN17

L(AC) N(AC) (AC) -V -V +V +V

A
CN2
SLAVE CPU

SLAVE CPU

SLAVE CPU

+35V
EXT
L2+ L1-
CPU BOARD

B
+35V
EXT
U13
CN1

CN1

CN1
U14 1
20 WAY
U11
POWER

N/O
SUPPLY

C N/C
CH8 CH8 CH6 CH8

UNIT

RELAY 4
U10

CN3 CN1

N/O
TP3
D14

PSU MONITOR
CN10

SERIAL RELAY

C N/C
CN16

10 WAY
BRIGADE I/F

BRD OR

RELAY 3
27V IN

C12
CN7

N/O
AGENT TERM BRD BRIGADE
CN6

R17

C N/C
CN8 MODEM
TH1
CN21

RELAY 2
CH1 CN2

CN4
CH2

OR O/P TERM

N/O
CN3

CN1

EXPANSION PANEL EXPANSION LEDS


BZ1
FRONT PANEL CN5 PRINTER
FAN TERM BRD BOARD

C N/C
RELAY 1
3 WAY ZD7

N/O
CN2 POWER TX1

-
AUX OUT 2
CN4

26 WAY

+
AUX OUT 1
-
BAT- BAT+ 0V +27V

+
E. BOARD SW. POWER
POWER

TB10
CN3
E. BOARD CONTROL
SGD

CN1
O/Ps

FAN CONTROL,
AGENT RELEASE, HPCI

OWS CONTROL OR
SWITCH & INDICATOR
X- PRINTER
C/W MOUNTING
PLATE. CABINET BACKPAN VIEW
SHOWING MODULES FITTED
TO THE BACKPAN
AND WIRING DETAILS
PRINTER PSU RESET COMMS IN
+ - SHD ZD 1
COMMS OUT
+ - SHD ZD 2

NETWORK

C4

C5
SW1
CN1
C/W CABLE
CN3
R3

26/07/2010
INTERFACE
MASTER
D1 TB1 TB2
LK1

MAIN BOARD INTERFACE


D2

HEARTBEAT

BRD86NIC1-
SHIELD
LINK
N1236

ISOLATED
D6
BOARD

COMMS
SW3

D11

D12
D 13 D 14

CN4 RX IN TX IN RX OUT TX OU T

POWER

D16
ZD 13
ZD 11
ACTIVE
CN5 CN6

TYPICAL FRONT DOOR LAYOUT FOR A FULLY POPULATED PANEL


OPTIONAL NETWORKING BOARDS
NOTE: PANEL LAYOUT MAY VARY DEPENDING ON CLIENT CONFIGURATION NETWORK INTERFACE CARD
NOTE: POSITION MAY VARY AS SHOWN
AND IS FOR INDICATION ONLY. TO BATTERIES

Figure 2: Typical Example of a SP1M/SP1X Layout

FRONT DOOR AND FRONT INNER DOOR REAR VIEW SHOWING


INSTALLED BOARDS ON FRONT INNER DOOR AND WIRING DETAILS AGENT TERM BRD OR MAINS
2 LOOP TERMINATION
8 ZONE BRD OR INPUT
BOARDs
FAN TERM BRD DANGER
240V
FRONT PANEL CONTROL EARTH
MAINS
RJ45/8 PIN STUD SWITCH
MAIN CONTROL BOARD
CN2

CH15

CH15

16 WAY
SLAVE CPU 2
SLAVE CPU 3

NEUTRAL
SLAVE CPU 4

GROUND
CPU BOARD

ACTIVE

+VE
-VE

20 WAY CN3 CN1

CN10
L(AC) N(AC) (AC) -V -V +V +V
10 WAY
PSU MONITOR
BRIGADE I/F

CN7
ZD7
CN6

CN8

CH2

CN1

CN5 PRINTER

3 WAY

POWER
RJ45/8 PIN SUPPLY
UNIT
AGENT RELEASE
GENERAL MODULE OR
INDICATOR FIRE FAN CONTROL
CARD MODULE
POWER OK
2+ 3+ 4+

BATT
MONITORED INPUTS

COMMS FAIL

ANCILLARIES or
CN11
1+

CN11
RS485
COMMS.

HOUSING BLANKS
COMMS.
C

OUT
4-

CN10
4+

CN10
MONITORED OUTPUTS

RS485
3-

COMMS.
COMMS.

20 WAY
IN
2+ 2- 3+
SLAVE CPU

1-
SLAVE CPU

SLAVE CPU

SLAVE CPU

1+

3 WAY
C N/C
RELAY 5
8
5

N/O C N/C N/O


6

RELAY 4

BLANK
N/O C N/C N/O C N/C

BRIGADE
RELAY 3

NETWORK
RESET COMMS IN COMMS OUT
+ - + -

PSU MON.
SHD ZD1 SHD ZD2
C4

C5
SW1

EXPANSION BOARD
CN1

CN3
RELAY 2

R3
26/07/2010

INTERFACE
MASTER
TB1 TB2

BOARD
D1
LK1
MAIN BOARD INTERFACE

D2

HEARTBEAT
BRD86NIC1-

SHIELD
LINK
N1236
C N/C

BOARD
RELAY 1

D6
N/O

ISOLATED
-
AUX OUT 2
COMMS

BLANK
+

SW3
D11

D12

D13 D14
AUX OUT 1
-

CN4 RX IN TX IN RX OUT TX OUT


POWER

BAT+ 0V +27V
+

E. BOARD SW. POWER BAT-


D16

POWER
TB10
CN3

E. BOARD CONTROL

X- PRINTER SGD
CN1

ZD11
ZD13 O/Ps
ACTIVE
CN5 CN6

C/W MOUNTING HPCI


PLATE.

NOTE: WIRING MAY VARY DUE TO CABINET BACKPAN VIEW


SHOWING MODULES FITTED TO THE BACKPAN
CLIENT PANEL CONFIGURATION AND WIRING DETAILS

CABINET
TO BATTERIES

Figure 3: Typical Example of a SP8 Layout


4
MAN2994-7

3 FireFinder PLUS Description


The following description does not relate to specific cabinets as the size of each cabinet will vary with the
amount of hardware fitted.

The heart of the FireFinder PLUS consists of two boards collectively known as the Controller. These boards
are the Main Board and the CPU Board. Combining these two boards with a front panel forms the basis for a
FireFinder PLUS FACP. A single Controller without an expansion board has the capacity to interface to four
(4) Slave CPU’s modules. These Slave CPU’s can be used for Loop Termination Boards.

The Main Board has the Slave CPU Board for the first Loop Termination Board and the provision for mounting
of up to three additional Slave CPU’s to interface to loops 2 - 4. The Slave CPU’s all have the same software
installed and the manner in which they operate is automatically determined by the type of termination or
interface board onto which they connect.

If the system is to be expanded to have more than four Loop’s an Expansion Board is required. This board
contains Slave CPU No. 5 and expansion sockets for three more to interface to loops 6 - 8. This configuration
allows for a maximum number of 8 Slave CPU’s that any one Controller can accommodate.

RESET BACKLIGHT
S W1
EXPANSION
CN17
MAIN BOARD MODULE

RS485 COMMS TO
CN20
SLAVE 4 SLAVE 3 SLAVE 2 BACKPAN BOARDS
CN100
4 CN13 3 CN14 2 CN15
CN11
NETWORK LOOP

LOOP COMMS
EXTERNAL LOOP
CN18

COMMUNICATION
COMMS

CONNECTS TO NIC

S W2
NODE ADDRESS

12 3 4 5 6 7 8

NODE ADDRESS
SLAVE CPU 4 SLAVE CPU 3 SLAVE CPU 2
TERMINATION BOARD

CN23
THE MAIN BOARD
IS FITTED WITH
CN2
CN2

CN2

CN10

SLAVE CPU 1
CN10 TO LOOP
DEBUG
DEBUG

DEBUG
LK1
LK1

LK1

TERMINATION BRD
MAIN CPU 1
TP1
TP1

TP1

27V IN

CN26

27VDC IN
+5V RS485 EOL
COMMS 2 LK2 BUZZER C N9 PRINTER 27V
BUZZER
PSU MONITOR

RS232 INHIBIT
BRIGADE I/F

OUT CN16
EXPANSION

LK3
MODULE

CN7

CN27
KEY SWITCH
0V CN21
COMMS2 RS232 (TOP) C N8
C N6
COMMS 3
CN25 EXTRA CONTROLS
COMMS1 C N2
C N3 C N4 FRONT PANEL PRINTER C N5
RS232/MODEM BZ1
+

C N1
(BOTTOM) EXPANSION PANEL USB
EXPANSION LEDS

RS485 COMMS TO USB TO FRONT KEYPAD INTERNAL PRINTER


20 WAY FRONT DOOR BRDS DEBUG (NOT USED IF THE KEYSWITCH O/P
RIBBON PANEL IS A NODE AND EXTRA
INTERNAL SERIAL
WITHIN THE SAME CONTROLS
COMMS PORT
PANEL)
EXPANSION LED'S (CN3)

CN2 CN3 CN4


6 7 8
CN1

SLAVE CPU 5
ON BOARD SLAVE CPU 6 SLAVE CPU 7 SLAVE CPU 8
CN2

CN2

CN2
CN5

DEBUG

DEBUG

DEBUG
LK1

LK1

LK1
TP1

TP1

TP1

AN EXPANSION BOARD (BRD86FEPB) CAN BE CONNECTED


TO FACILITATE UP TO FOUR ADDITIONAL SLAVE CPU'S IF REQ

Figure 4: Single Controller Board with Expansion Board

5
MAN2994-7

FireFinder PLUS has an internal RS485 communication bus that allows for various ancillary boards (add on
modules) to be connect to the panel. These boards can be used to control and monitor field plant equipment
or the addition of an agent release module.

Where the system design exceeds the capability of one FireFinder PLUS then other FireFinder PLUS panels
can be networked together to provide an expanded system containing multiple boards in a variety of
applications.

Some of these applications include:

➢ A Master / Slave (Main Sub) FACP arrangement (MFACP / SFACP)

➢ A Peer to Peer System

➢ Use of Data Gathering Panels (DGP’s)

➢ SmartTerminal

➢ SmartGraphics

A Network FireFinder PLUS System supports a combination or all these options on a single network. Each
panel on the network is regarded as a “node”. The NETWORK BUS is accessed using a Network Interface Card
(BRD86NIC). The network configuration determines whether a NIC is required. Configurations can be;

Master / Sub FACP: Where there is one or more FACP’s configured as local panels then each report the status
of their associated zones/devices to a MFACP. There is no control between local panels as the MFACP is
structured to have full control of the entire system.

Peer to Peer: Each FACP user can take control of the entire fire system from any FACP.

Data Gathering Panel: The use of this type of panel may be installed where there is a need to have field
terminations only at one location and all control is performed by an FACP that is remotely located.

SmartTerminal: Provides the user with the ability to monitor the status of designated areas or an entire site
as well as execute specific interrogation tasks.

SmartGraphics: Is an active graphics system connected to the FireFinder PLUS.

6
MAN2994-7

4 Placing The Basic System Into Operation


4.1 Unpacking
Carefully unpack the FireFinder PLUS.

The package should include:

✓ FireFinder PLUS Fire Alarm Control Panel

✓ A CD containing this “Installation and Commissioning” manual

✓ 003 keys

4.2 Anti-Static Precautions


To prevent damage to components, modules and boards, anti-static precautions MUST be observed while
performing any task within the FACP. The same applies to those situated in the field.

4.3 Working on the System


 Prior to unplugging any connector, connecting or disconnecting any wiring, removing or replacing
any module or board, ensure that both the Mains and Batteries have been isolated to prevent damage to
panel components.

4.4 The Cabinet


Features:

➢ The cabinet is available in four different styles. Each style has the capability of being either
surface or flush mounted. With flush mounting though a surround is required.

➢ Normally painted Surf Mist Ripple. Other colours are available on request.

➢ The inner and outer door hinges are mounted on the left-hand side of the cabinet which
allow the doors open to an angle of 100º. A keyed entry is provided

➢ Knockouts are positioned on gland plates and a cut out is available on the rear of the
cabinet to simplify cable entry. Mounting The Cabinet

 Note: It is recommended the cabinet should be installed in a clean, dry, vibration-free area.

Open the front door. Use the keyhole mounting holes in the top corners and the two holes along the bottom
of the unit to mount it on the wall. Cables to connect the system to its external actuating devices are brought
in through the knockouts on the top or bottom of the cabinet.

7
MAN2994-7

R 3 mm

12 mm

R 6mm.

Tap lightly around the


rim of the knockout

Figure 5: Example SP1 Back Pan Mounting Hole & Removing Knockouts

8
MAN2994-7

4.5 Cabling Recommendations


Conventional Zones

Cabled in red Twin Plastic Sheath (TPS), Fire rated Radox or approved equivalent.

Analogue Loop

Two core cable. The minimum cable size is 0.75mm 2, the maximum loop resistance is 50 ohms and the
maximum loop distance is 2km.

RS 485 Network

Single twisted pair screened (2 core) cable originating from FACP extending through the protected areas and
returning to the FACP.

Cable Specifications

Capacitance of 100 Pico farads per metre or less


Resistance of 100 milliohms per metre or less
Impedance of loop typical 100 to 120 ohms
Maximum distances between modules 1.2km providing cable meets above specifications.

Recommended cable type

Belden 8132 or 9842 (non fire rated)


Radox FR Communication 0.75mm 1 pair (fire rated) x 2

SmartTerminal

Single twisted pair shielded cable (2 core) plus 2 core power, or local supply. Maximum distance between
from the last SmartTerminal and the FACP is 1.2km.

LED Mimic (RS485)

Single twisted shielded cable (No return loop) plus 2 core power or local supply.
Maximum distance between each LED repeater card and FACP is 1.2km.

Recommended Cable Type

Hartland HC2335
Belden 9841
Radox FR Communication

Fire Alarm Bell Connection

Two core 1.5mm2 PVC sheathed MIMS (Mineral Insulated Metal Sheathed) to the bell location.

Brigade Connection via Telecom

Two core 1.5mm² PVC sheathed MIMS from the FACP to the Telecom MDF.

RJ45 Multi-drop Serial Port

8 core Flat cable

9
MAN2994-7

Power Supplies / AC Mains

The requirement for the mains supply to the FACP is fixed wiring, using three core cable (no less than
0.75mm and no more than 2.5mm ) or a suitable three conductor system, fed from an isolating switch fuse
spur, fused at 3A. This should be secured from unauthorised operation and be marked 'FIRE ALARM: DO NOT
SWITCH OFF. The Mains supply must be exclusive to the FACP.

Common Power Supply Features & Specifications


Switch Mode Design Over voltage protection
High efficiency, low working temp. High efficiency; low ripple noise
Universal AC input/ full range Soft start with limiting AC surge current
Short circuit/ over load Remote control on/off (option)
Built in EMI Filter and PFC Circuit Over temp. protection (option)

Input Voltage: 85 to 264 VAC Tolerance at 27V +/- 1%


Input Freq 47 to 63Hz. Load Regulation +/- 0.5%
PFC 0.95~230VAC Line Regulation +/- 0.5%

Power Supply Specifications


Type No Output Tolerance R&N Efficiency

PSU1888 27V @ 5.6A  1% 150mV 84%


PSU1890 24V @ 14A  1% 150mV 87%
330-0015 27VDC @ 22A  1% 240mV 86%

 Important: Under no circumstances should the FireFinder PLUS be operated without the
Power Supply PCB correctly mounted in the enclosure and the retaining screws securely tightened.

10
MAN2994-7

4.6 Power Supplies and AC Mains Installation


Generally the AC Mains will be connected to either a 5 Amp, 14Amp or 22 Amp 27 volt supply.

These supplies will be either mounted in the upper or lower right hand corner of the cabinet with the Brigade
Board mounted in close proximity.

The wiring should enter the cabinet through the nearest knockout entry hole on that side.

Refer to Figures 6 - on for the wiring and fusing details for each supply.

4.6.1 Connecting the Mains Earth


All earth cabling shall be terminated to the panel Chassis Earth Terminal in a star configuration.

The earth cable closest to the cabinet body shall have an M4 SPW beneath the lug then an M4 SPW and M4
nut.

Each additional earth cable shall be terminated with an M4 SPW and M4 nut.

An additional M4 nut and M4 SPW are fitted to the Chassis Earth Terminal for installers to connect their
Mains Earth.

CHASSIS EARTH TERMINAL


M4 Nut
* Extra M4 Nut and M4 SPW are
M4 Shake Proof Washer
provided finger tight on the Earth bolt.
M4 Nut Earth Cable
M4 Shake Proof Washer

Figure 6: Panel Earthing

4.6.2 Connecting 5 AMP Power Supply


Output Voltage: 27.4 Volts.
FUSE Rating: 2 Amp 3AG Slow Blow
Mains Cable: should be no less than 0.75mm

Figure 7: Mains Power Connection to the 5 AMP Power Supply

11
MAN2994-7

4.7 CORRECT Power Up / Turn “ON” Procedure


Once all the field devices are installed and the wiring has been correctly terminated the FireFinder PLUS is
ready to turn on. For reliable power up it is essential the following procedure be followed;

1. Turn the Mains power on, THEN

2. Connect the batteries observing correct polarity.

3. The green power on LED should be illuminated.

4.8 Brigade / PSU Monitor Board


The Brigade / PSU Monitor Board (BRD86BPSC) monitors and controls the power supply, battery charging,
monitored / un-monitored inputs, outputs and the 5 relay outputs.

Connections

TB(x) Function Type of Output


TB1 Aux Out x 2 Protected
TB2 Relay 1 1 Amp Voltage Free Contacts
TB3 Relay 2 1 Amp Voltage Free Contacts
TB4 Relay 3 1 Amp Voltage Free Contacts
TB5 Relay 4 1 Amp Voltage Free Contacts
TB6 Relay 5 1 Amp Voltage Free Contacts
TB7 Monitored Outputs x 4 24Vdc EOL
TB8 Monitored Inputs x 4 Switched Negative, EOL
TB9 Battery Out / 27VDC PSU IN Protected
TB10 External Board / SW POWER

CN(x) Function Type of Output


CN1 JTAG
CN1 SGD
CN3 External Board Controls
CN4-8 Power Out 1 Amp ( protected )

Relay Information

Voltage Free contacts are rated at 1A @ 30V

Back EMF Protection

 Inductive loads fitted to the Brigade PSU Monitor Board MUST be fitted with “Flyback” diodes at the
load for back EMF protection.

Transient Protection

 Recognised transient line protection methodologies at the FACP and the load MUST be considered
when connecting any control devices to the outputs be they in close or remote.

12
MAN2994-7

EXT TEMP
LK1
JTAG

MON EN
CN2

E TH
CN12 POWER OK
MONITORED

1+ 2+ 3+ 4+
MONITORED INPUTS
BATT
INPUTS FLT.
( EOL's Required )
COMMS FAIL

TB8
Note:

CN11
If a diode is NOT fitted CN11
RS485
internally to a bell / sounder

N1236

C58
C56

COMMS.
COMMS.

C
a diode MUST be fitted as OUT
shown - fit 1N4004 or similar ZD8

4-

BRD86BPSC4-
Bell

CN10
4+
EOL

MONITORED OUTPUTS
ZD4
ZD3 U8 D11 C36 CN10
10K To CN20 of the Main

EOL
ZD7 RS485

2 + 2- 3 + 3-

COMMS.
COMMS. Controller Board
Ohms

M16
IN
ZD2
TB7
U7 D10 C35
ZD6

MONITORED OUTPUTS

22/09/09
( EOL Required ) ZD1 U6 D9 C34
1-

ZD5

Sounder
EOL
1+

10K M10
U5
N/O C N/C N/O C N/C N/O C N/C N/O C N/C N/O C N/C

Ohms Batt Fail


RELAY 5

RL5
TB6

Relay M9
U2
T1

1
(Normally C43
Energised) M8 M15
RL4
RELAY 4

Isolate
TB5

M7
Relay
L6
M6 M14

Relays are
R75
RL3

Warning
RELAY 3

TH9
Programmable
TB4

R108

System M5 CN8
Default Setup
Alarm
Q5
R103

Shown
M4 M13
RL2
RELAY 2

HSNK2
Fault TH5 CN7
TB3

M3
Relay
L7
HSNK1

M2 M12

CN6
RELAY 1

Alarm
TB2

TH8

M1
L8

Relay
RL1

D7 CN4 to 8 Supplies
M11

CN5 Regulated +27VDC


to Internal Boards
- + -
AUX OUT 2

AUX OUT 2
1A / Connector
Q8
TH1

L9
TB1

2 x AUX OUT
27VDC @ 2A CN4
AUX OUT 1

TH4
TH7
TH2

AUX OUT 1
BAT- BAT+ 0 V +27V
+

E. BOARD SW. POWER


POWER
TB10
CN3

E. BOARD CONTROL
SGD
CN1

O/Ps
TB9

Note: N/C C N/O HPCI


Denotes Voltage Free Contacts +27VDC
N/C
N/C = Normally Closed from PSU
C = Common C - +
N/O = Normally Open Battery 1
+ -
Battery 2
N/O 12 Volts 12Volts

Figure 8: Brigade / PSU Monitor Board Layout

Note: When connecting to the Brigade PSU Monitor board transient and “Flyback” (Back EMF) protection
methodologies MUST be applied.

13
MAN2994-7

4.8.1 Battery Connections


A FireFinder PLUS requires two (2) 12 volt batteries (TB9). The batteries should be placed into the bottom
right hand side of the cabinet.

A red and black lead coming from TB1 on the Brigade Board will be clearly seen in the same area, this lead is
to be connected to the batteries red to positive and black to negative once the system is operating on Mains
supply.

Battery size is dependent on the system configuration and can vary from 12 AHr to over 100 AHr.

Note: Refer to Ampac’s battery calculation tool to calculate the required battery size.

EXT TEMP
LK1
JTAG

MON EN
CN2

ETH
CN12 POWER OK

1+ 2+ 3+ 4+
MONITORED INPUTS
BATT
FLT.

BAT- BAT+ 0V +27V


COMMS FAIL

TB8

CN11
CN1 1
RS4 85

N1236

C58
C56

CO MMS .
COMMS.

C
OUT
ZD8

4-

BRD86BPSC4-

CN10
4+
MONITORED OUTPUTS
ZD4
ZD3 U8 D11 C36 CN1 0

EOL
ZD7 RS4 85

2 + 2- 3 + 3-

CO MMS .
COMMS.

M16
IN

TB7
ZD2 U7 D10 C35
ZD6

22/09/09
ZD1 U6 D9 C34

1-
ZD5

1+
U5
M10

N/O C N/C N/O C N/C N/O C N/C N/O C N/C N/O C N/C
BRIGADE

RELAY 5

RL5
TB6
U2
M9
T1

1
C43

M8 M15

BOARD

RL4
RELAY 4
- + - + TB9 TB5
M7

M6 M14
L6

R75
RL3
RELAY 3 TH9
TB4

CN8

R108
M5

+27VDC
Q5
R103
M4 M13
RL2
RELAY 2

from PSU
HSNK2
TH5 CN7
TB3

M3

L7
HSNK1

M2 M12

CN6
RELAY 1
TB2

TH8
M1

L8
RL1

D7
M11

CN5
- + -
AUX OUT 2

Q8
TH1

L9
TB1

CN4
AUX OUT 1

TH4
TH7
TH2

BAT- BAT+ 0 V +27V


+

E. BOARD SW. POWER

- + POWER
TB10
CN3

E. BOARD CONTROL
SGD
CN1

TB9
O/Ps

+ -
Battery 1 Battery 2 HPCI
+27VDC
12 Volts 12Volts from PSU
TB9 is located on the bottom Battery 1
12 Volts
+
- +
-
Battery 2
12Volts

right hand side of the board

Figure 9: Battery Connections to the Brigade / PSU Monitor Board

14
MAN2994-7

4.8.2 Auxiliary 27 Volt Power


Two (2) 1 Amp outputs are available from TB1 terminals 1+ (plus) and 2- (minus) or 3+ and 4- on the Brigade
Board. It is important to note these outputs are short circuit monitored.

LK1
JTAG

EXT TEMP
MON EN
CN2

ETH
CN12 POWER OK

2+ 3+ 4+
BATT
FLT.

MONITORED INPUTS
COMMS FAIL

TB8

CN11
1+
CN11
RS485

N1236

C58
C56
COMMS.

COMMS.
C
OUT
ZD8

4-

BRD86BPSC4-

CN10
4+
ZD4
ZD3 U8 D11 C36 CN10

MONITORED OUTPUTS

EOL
ZD7 RS485

3-
COMMS.

COMMS.
M16
TB1
IN

3+
ZD2 U7 D10 C35

TB7
ZD6

2+ 2-

22/09/09
ZD1 D9 C34
+ - + -
U6

1-
ZD5

1+
AUX OUT 2 M10
U5

C N/C
2 X LIMITED 2A BRIGADE

RELAY 5

RL5
U2

TB6
M9
T1

1
N/O C N/C N/O
C43

AUX POWER M8 M15

BOARD

RL4
RELAY 4
TB5
OUTPUTS
M7

L6
M6 M14

AUX OUT 1

N/O C N/C N/O C N/C

R75
RL3
TH9

RELAY 3
TB4
CN8

R108
M5

Q5
R103
M4 M13

RL2
HSNK2
CN7

RELAY 2
TH5

TB3
M3

L7
HSNK1
M2 M12

N/O C N/C
CN6

RELAY 1
TB2

TH8
TB1 is located in the lower
M1

L8
RL1
D7

M11
left hand side of the board CN5

- + -
AUX OUT 2

Q8
TH1

L9
TB1
CN4

AUX OUT 1

TH4
TH7
TH2
BAT- BAT+ 0V +27V

+
E. BOARD SW. POWER
POWER

TB10
CN3
E. BOARD CONTROL
SGD
CN1
O/Ps

HPCI
+27VDC
from PSU
- +
+ -
Battery 1 Battery 2
12 Volts 12Volts

Figure 10: Auxiliary 27VDC Power Output

4.8.3 Monitored Inputs


Four independently monitored inputs (TB8) are provided and can be configured for a variety of uses.

➢ Manual Call Point (MCP) – if activated the FACP will go into alarm. Connected to the MCP on
the front of the FACP.
➢ Class Change – if activated all Alarm Devices/Sounders and Alarm Device/Sounder Outputs
in Sounder Group 1 are turned on.
➢ External Fault – if activated the FACP will indicate a Fault condition
➢ Ancillary Disable - if activated, the FACP’s “DISABLED” and ANC OUTPUT STATUS LEDs will
both be turned on. Note that this event is used to indicate an ancillary/auxiliary disablement
or a door-opened condition if a door switch is fitted. It also activates any Relays on the
Brigade board configured as “Isolate” relays and affects the Brigade Board’s “Aux/Anc”
outputs based on their “normally energised” settings.
➢ Evacuate – if activated the FACP goes into Evacuation.
➢ Sounder Silence – if activated all activated sounders are silenced.
➢ Reset – if activated a Master Reset is initiated.
➢ Fire/Feedback - if activated, the FACP’s “Fire Output On” LED will flash (AS7240.2 Clause
7.9.2). Note that this is a latched condition and will only be cleared a “Master Reset”
command from the FACP.
➢ General Purpose – for use in Functions (Cause and Effects)

15
MAN2994-7

The default configuration types for the inputs are as follows:

• Input 1 – MCP

• Input 2 – Evacuate

• Input 3 – External Fault

• Input 4 – Reset

The inputs have been designed to operate with a programmable EOL of 3K3Ω, 10KΩ 22KΩ or Unmonitored
(no EOL) the 10K EOL is the default. The normal and active ranges change according to the end of line
selected.

Line Resistance (10K EOL) Sensed Condition


0Ω– 150Ω Short circuit Fault
470Ω – 4KΩ Active condition
8KΩ – 15KΩ Normal
20KΩ to ∞ Open circuit Fault

LK1
JTAG

EXT TEMP
TB8 location

MON EN
CN2

ETH
CN12 POWER OK

2+ 3+ 4+
BATT
FLT.

MONITORED INPUTS
Note: Door Switch is Open for Normal Operation and not Monitored
COMMS FAIL

TB8

CN11
1+
CN11
RS485

N1236

C58
C56
COMMS.

COMMS.
C
OUT
ZD8

TB8 / 1+, 2+, 3+ or 4+

4-

BRD86BPSC4-

CN10
4+
ZD4
ZD3 U8 D11 C36 CN10

EOL
MONITORED OUTPUTS
ZD7 RS485

3+ 3-
COMMS.

(Config set to "unmonitored")

COMMS.
M16
IN
ZD2 U7 D10 C35

TB7
ZD6

2+ 2-
Door Switch TO TB11

22/09/09
ZD1 U6 D9 C34

1-
ZD5

1+
TB8 / C TB8 M10
U5
C 1+ 2+ 3+ 4+

N/O C N/C N/O C N/C

BRIGADE
RELAY 5

RL5
U2
TB6

M9
T1

1
C43

BOARD
M8 M15
RL4
RELAY 4
TB5

M7

L6
M6 M14
N/O C N/C N/O C N/C N/O C N/C

R75
RL3

TH9
RELAY 3
TB4

CN8
R108

DBA / MCP TB8 / 1+, 2+, 3+ or 4+


M5
Q5
R103

M4 M13
RL2

(EOL depends on config)


HSNK2
CN7
RELAY 2

TH5
TB3

M3

L7
HSNK1

M2 M12

CN6
EOL
RELAY 1
TB2

TH8
M1

L8
TO
RL1

D7

10K 4K7
M11

CN5
- + -
AUX OUT 2

Ohms
Q8
TH1

L9
TB1

CN4
AUX OUT 1

TH4
TH7
TH2

TB8 / C BAT- BAT+ 0V +27V


+

E. BOARD SW. POWER


POWER
TB10
CN3

E. BOARD CONTROL
SGD
CN1

O/Ps

HPCI
+27VDC
from PSU
- +
+ -
Battery 1 Battery 2
12 Volts 12Volts

Figure 11: Inputs DBA / MCP and Door Switch Wiring

16
MAN2994-7

4.8.4 Monitored Outputs


Four independently monitored and controlled outputs (TB7) are provided and can be configured for a variety
of uses.

➢ Alarm Devices - activated when any of its four sounder groups is active. (AS7240.2 Clause
7.7 and 7.8). The output is turned off during an Alarm (sounder) disable or Alarm (sounder)
silence condition.
➢ ASE – (Australia Firefinder Plus Only)
➢ Fire/FARE – activated by alarm condition (AS7240.2 Clause 7.7 and 7.9.1). The output is
turned off during a FIRE disable condition.
➢ Ancillary - activated on device alarm conditions. The Output is turned off during an Ancillary
disable condition.
➢ Warning System - activated on evacuation and device alarm conditions. The output is turned
off during an Alarm (sounder) disable or Alarm (sounder) silence condition.
➢ Fault - activated on all fault conditions (AS7240.2 Clause 9.9). The output is turned off during
a FAULT disable condition.
➢ General Purpose – activated via the Configmanager “Function” programmed logic.
➢ External Alarm Devices - activated by an Alarm condition when a Point (Detector) has been
configured as Fire/FARE. (AS7240.2 Clause 7.7 and 7.8). The output is turned off by the
removal of the alarm condition – Silence Alarms followed by Reset.

These monitored switched outputs, supply a nominal 24VDC, at up to 1 Amperes. Monitoring is for short,
open and earth faults when the output is OFF.

The outputs have been designed to operate with a programmable EOL of 3K3Ω, 10KΩ 22KΩ or Unmonitored
(no EOL) the 10K EOL is the default.

Line Impedance (10K EOL) Reported Condition


0Ω– 50Ω Short circuit Fault
50Ω – 150Ω Indeterminate: Maybe reported as shorted or normal
150Ω – 15KΩ Normal
15KΩ – 40KΩ Indeterminate: Maybe reported as normal or open circuit
40KΩ to ∞ Open circuit Fault

Warning systems and sounders are connected to the Brigade / PSU Monitor Board as shown below. If more
sounders are required, the Sounder / Bell Control Board must be used.
EXT TEMP

LK1
JTAG
M ON EN

+ / - are monitored 1A outputs. Un-used O/P's


CN2
ETH

CN12 POWER OK
1+ 2+ 3+ 4+
MONITORED INPUTS

BATT

must be terminated in 10K Ohms EOL COMMS FAIL


FLT.
TB8

CN11

CN11
RS485
N1236

C58
C56

COMMS.

COMMS.
C

O UT

TB7 Location ZD8


4-

BRD86BPSC4-

CN10
4+
MONITORED OUTPUTS

ZD4
4+ 4-

ZD3 U8 D11 C36 CN10


EOL

ZD7 RS485
2+ 2- 3+ 3-

COMMS.

COMMS.
M16

Bell
IN
ZD2
TB7

U7 D10 C35
ZD6
22/09/09

ZD1 U6 D9 C34
1-

ZD5
1+

TB7 U5
3+ 3-

M10
N/O C N/C N/O C N/C N/O C N/C N/O C N/C N/O C N/C
RELAY 5

BRIGADE
RL5
TB6

U2
M9

Sounder
T1
1

EOL
C43

BOARD
M8 M15

EOL
RL4
RELAY 4

10K
TB5

M7

L6

10K Ohms M6 M14


R75
RL3
1+ 1- 2+ 2-

TH9
RELAY 3
TB4

R108

M5 CN8

Ohms
Q5
R103

M4 M13
RL2
RELAY 2

HSNK2
TH5 CN7
TB3

M3
L7
HSNK1

M2 M12

CN6
RELAY 1
TB2

TH8

M1
L8
RL1

D7
M11

CN5

Warning System
- + -
AUX OUT 2

Q8
TH1

L9
TB1

CN4
AUX OUT 1

TH4
TH7
TH2

BAT- BAT+ 0 V +27V


+

E. BOARD SW. POWER


POWER
TB10
CN3

E. BOARD CONTROL
SGD
CN1

Note: If a diode is NOT fitted internally to a


O/Ps

bell / sounder a diode MUST be fitted as


HPCI
+27VDC
from PSU

shown - fit 1N4004 or similar Battery 1


12 Volts
+
- +
-
Battery 2
12Volts

Figure 12 Connecting a Bell / Sounders


17
MAN2994-7

4.8.5 Relay Output Connections


Five “voltage free” relay outputs (TB2 – TB6) are provided and can be configured for a variety of uses.

➢ Alarm - activated on device alarm conditions and “Function” programmed logics. The relay
is turned off during a ALARM disable condition.
➢ Sprinkler - activated on device alarm conditions and “Function” programmed logics.
➢ Fault - activated on all fault conditions and “Function” programmed logics. The relay is
turned off during a FAULT disable condition.
➢ Isolate - activated on all isolate conditions and “Function” programmed logics.
➢ Battery Fail - activated on battery fail conditions and “Function” programmed logics.
➢ Mains Fail - activated on a mains power fail condition and “Function” programmed logics.
➢ Warning System - activated on evacuation, device alarm conditions and “Function”
programmed logics. If the activation of this relay is due to an evacuation condition, then the
relay is turned off during an Alarm (sounder) disable or Alarm (sounder) silence condition.
➢ Ancillary - activated on device alarm conditions.
➢ General Purpose - activated via “Function” programmed logics

Relay Switching Characteristics

These outputs have been designed to be able to switch predominately resistive loads as listed below.

Switching voltage Maximum switching current


30VDC 1A
24VAC 1A
50VDC 250mA
40VAC 250mA

The default relay contacts are connected as shown below.


EXT TEMP

LK1
JTAG

Relays are Programmable. Default Setup Shown


M ON EN

CN2
ETH

CN12 POWER OK
1+ 2+ 3+ 4+
MONITORED INPUTS

BATT
FLT.

COMMS FAIL
TB8

BATT
CN11

CN11

FIRE FAULT EWIS ISOLATE


RS485
N1236

C58
C56

COMMS.

COMMS.
C

O UT

FAIL ZD8
4-

BRD86BPSC4-

CN10
4+
MONITORED OUTPUTS

ZD4
ZD3 U8 D11 C36 CN10
EOL

ZD7 RS485
2+ 2- 3+ 3-

COMMS.

COMMS.
M16

IN
ZD2
TB7

U7 D10 C35
ZD6

NO CC NC NO CC NC NO CC NC NO CC NC
22/09/09

NO C NC NO NC NO NC NO NC NO NC ZD1 U6 D9 C34
1-

ZD5
1+

U5
M10
N/O C N/C N/O C N/C N/O C N/C N/O C N/C N/O C N/C
RELAY 5

BRIGADE
RL5
TB6

U2
M9
T1
1

C43

BOARD
M8 M15

Note:
RL4
RELAY 4
TB5

M7

1A Un-monitored
L6
M6 M14
R75
RL3

TH9
RELAY 3
TB4

R108

M5 CN8

Voltage Free Conacts:


Q5
R103

M4 M13
RL2
RELAY 2

TB2 TB3 TB4 TB5 TB6


HSNK2
CN7

NO: Normally Open


TH5
TB3

M3
L7
HSNK1

M2 M12

NC: Normally Closed CN6


RELAY 1
TB2

TH8

M1

TB2 to TB6 are located on the


L8
RL1

D7

C: Common
M11

CN5
lower to mid left hand side of the board
- + -
AUX OUT 2

Q8
TH1

L9
TB1

CN4
AUX OUT 1

C
TH4
TH7
TH2

BAT- BAT+ 0 V +27V


+

NC
E. BOARD SW. POWER
POWER
TB10
CN3

E. BOARD CONTROL
SGD
CN1

O/Ps

HPCI
+27VDC

NO
from PSU
- +
+ -
Battery 1 Battery 2
12 Volts 12Volts

Figure 13: Relay Output

18
MAN2994-7

4.9 High Current Interface Board


When the 14Amp power supply is used in the FACP the High Current Interface Board is required to provide
protection for the boards, cards and other 27VDC distribution within the FACP.

The board plugs/connects into the Brigade / PSU Monitor Board (BRD86BPSC) and the 27V DC output from
the PSU is connected to TB1 of the BRD86HCI instead of TB9 on the BRD86BPSC

Figure 14: High Current Interface Board

Connections

TB Function
1 27VDC PSU IN
2 Battery Out
3 27VDC Out
4 27VDC Out
9 Battery Out / 27VDC PSU IN
10 External Board / SW POWER
CN Function
1 - 27VDC 3A Max
5

19
MAN2994-7

4.10 Main Board


The Main Board (BRD86MBA) carries the devices for interconnecting to all the other Boards, a buzzer for
auditory indication, the backlight power supply for the LCD and CPU Reset.

The Main CPU is mounted on this board and connected to it by CN11. The main connection board then
provides interfacing to:

➢ Up to 3 Slave CPU’s (Slave CPU 1 is onboard)

➢ A printer

➢ A Modem

➢ An Expansion Panel

➢ An Internal serial bus

➢ An External communication bus.

Connections

CN1 Extra Control (Not Fitted) CN15 Slave CPU connection


CN2 Expansion Panel CN16 Printer 27VDC Out
CN3 Expansion LED’s (Not Fitted) CN17 To LCD Backlight supply
CN4 Front Keypad CN18 External Loop Communication
CN5 Printer CN19 LCD Characters
CN6 Key Switch (Not Fitted) CN20 RS485 Communications Port 1
CN7 Brigade Output CN21 RS485 Communications Port 2
CN8 Modem and RS232 Comms CN22 To LCD Backlight supply
CN9 Ext Buzzer Output (Not Fitted) CN23 Slave CPU Debug (Not Fitted)
Jtag Programming Slave CPU1 (Not
CN10 Slave CPU output 1 CN24
Fitted)
CN11 Main CPU CN25 USB Programming
CN12 LCD Graphic CN26 27VDC In
CN13 Slave CPU connection CN27 Comms 2 RS232
CN14 Slave CPU connection CN28 27VDC In (not fitted)

20
MAN2994-7

R4 R5 R2
R1 C7 HY1 BACKLIGHT
C6 D1
BRD86MBA4- 30/06/10 Q6

C2
C3
C4

C1
D2 D3
R3

C8
C5 R6BACKLIGHT R62 C17
U1 C9 C10 C11
R7
SW1 R63
CN17 EXPANSION

C14
L1 C13
U4 U5 U6 Q1 MODULE
RN1
C12
RESET

C15
U2
C16 CN22 R8 LCD BACKLIGHT INVERTER
R9
R11 CHINESE N1236 U7
R12
GRAPH R13
CN20

R10
LCD
U3
CN15

TP69
L2
R14
R16
R15 SLAVE 4
CN13 SLAVE 3 CN14 C21
SLAVE 2

C18 CN100
C20
4 3 2
D4 CN11 U8
C22

NETWORK LOOP COMMS


U9 GRAPH LCD

CN19
NON-CHINESE
C23 C24 C26
R17 C25 C27 U10
C29
CN12 U13 U14 U15 CN18

CHAR LCD
C28 RN2
U11 U12

CN12
C30
U35

C31
U16
CN19

RN3

RN4
DEBUG R18 C33 TP3
C32

R65
C88
R67
LK1 U20
C34
C36

1 2 3 4 5 6 7 8
U18 C35

NODE ADDRESS
R66
TP4 X1
U17 Q2 Q8 SW2
U22
C38 C39
C40

D5

C41

R21
R22

D6
U19
C42 C43
C44
C45
U21 ZDN1
CN23 C46

C49
U23 R23

C47 C48 SLAVE 1


D7 R26 R24 RN5 DEBUG

TERMINATION BOARD
U25 D8

R27 U24 R28


C53 TP5 C50 C51
R29 C52 R30
C54
TP6 C55 R31 C56 R32

C64
C57
JTAG
C58 R33 C59 CN10 R34
C60
U26
CN24 C62
C65
R35 C63 R36
C61
C67 R37 C66 R38
C68 R39
R47

R48
R46
R43

R41
R42

R44
R45

C70 U27 C69 R40


C86

C85
C37
C87

C71 C72
1
C73 R49

27V IN CN26
R51 C74 C75
R50

U28 C76 R52


CN26
R54

U36 D9 Q3 C77 R53


Q4
U29 C91 C78

CN28 +5V C19


LK2
RS485 EOL
Q5
R55 R58 CN9
C79

U31
C80
D16
C81
PRINTER 27V U30
R56 D15 U33
D17
27V IN R25 R19 COMMS 2 C90 RN16
RN18
R59

PSU MONITOR
RS232

D11
LK3 R57

CN16
C89

C82

BRIGADE I/F
CN21 BUZZER
R20 R64
CN27 RN6
BUZZER C83
O UT
CN7

D10
EXPANSION

INHIBIT
CN6
MODULE

COMMS2 RS232 (TOP) RN19 D14 D12 R60 U34

RN7
R61
RN17
COMMS1 RS232/MODEM (BOTTOM) U32
KEY SWITCH
0V D13

RN8 RN9 TH1 RN12 RN13 RN15


RN14

CN2 CN25 ZDN2


RN10 RN11 CN4 C84
CN5
EXTRA CONTROLS

BZ1
+

CN8 EXPANSION PANEL EXPANSION LEDS CN3 USB FRONT PANEL CN1 PRINTER

Figure 15: Main Board Layout with no Main CPU or Slave CPU’s

21
MAN2994-7

4.11 Front Panel Board


The Front Panel Board (BRD86FPB) provides the buttons used to control the FACP as well as all LED
indications. All LED’s are surface mounted and the buttons are embedded within the board. The LCD is viewed
/ protected by a clear Perspex screen.

Connections

CN2 To CN4 Main Board

C1 C18

D1 R1 Q1

R31 D18
D2 R2

D3 R32 D19
R3
D10

D11 R33 D20


D4 R4 D12

D13

D5 R34 D21
R5

D6 R6

D7 R7
D14 D16 R29 D17 R36 D23
R23

D8 D22
R8
R26

D9 R35
R9
U4 C14 U6 C16

D30 R50 R37 D24


C23
C8
R28

U2 C4 R25 C15
C5 C13
BRD86FPB4-
U5 R38 D25
11/08/10 R30

N1236 U3
D28 R27 C11
R24
U7 D26
C6 R41 U8 R43 R39
C9 C10 R42
C12 C19
C7
R46
R45
R44

R10
R40 D27

R11
KEYSWITCH
L1

L3
L2

R12
C20

R17 R18 R19 L8 C3


R20
R22

C21
L6
L7
L5

L4

R13
R15 C2 R47 D15
R14 R16 C17

Q2 U1 C22 CN2
R21

CN1

KEYSWITCH

Figure 16: Front Panel Board

22
MAN2994-7

4.12 Main CPU


The Main CPU (BRD86MCPU) holds the main central processing unit including the Application software and
Configuration settings for the FACP.

➢ The Main CPU is a 4-layer surface mount board

➢ The processor runs at 60MHz.

➢ 16Mbytes of FLASH

➢ 32/64 Mbytes SDRAM

Connections

CN1 USB
CN2 To Main Board CN11

R1 R2
U4
R9
C2 C3
R4
R7 CN1
C1

ZDN1
R5 USB
R6

U1
C4
C5

R8

R3
C7
C6

Q1
C8

R10
Q2
R11
R30
U2 U3 C9 X1
C11 C12 C13

CN2
C14

R28 C10
U11
C15

U6 U7 U5
R29
ZDN2

C16

C19 D1
C18

C20 C17

C21 U10 R12 C22


U9
X2
R13
R14

C23

U8 D2
R15 C26
C24 C25
U12
ZDN3

U13
C29
R17
R18
R19
C30

C27 R16
D3
C28

R20

C31
C34
R21

C33
C32
C35 Q3
R22
U15 R23
R24
C37

R26

C36 U14 D4
C41 R25 +
C40

C38 C45
C42

R27
C39 C43 C44
U16
0V

Figure 17: The Main CPU Board PCB Layout

23
MAN2994-7

4.13 Slave CPU


The Slave CPU (BRD86SCPU) provides the interfacing signals and I/O’s required to allow the FACP to connect
/ communicate to a variety of termination boards.

A single chip micro controller U7 controls all operations of the FACP Slave CPU. This device contains the
control program within Read Only Memory (ROM).

Automatic Termination Board Sensing

A unique feature of the Slave CPU is its ability to automatically sense the type of board it is connected to
without the user having to configure the board to suit.

Connections

CN2 To Loop Termination Board


CN3 To Main Control Board

C6 BRD86SCB3-
C2 C4 C5 LK1
C3 R2 D3
DEBUG
U1 U3
R1 C1
Q1 C7

CN3 U4 R5

C8
Q2

R24
COMMS
C10 D1

U2 R4 R27 R26 U5
C9 D2
TP1
C11 U7
C17
C15

C21
C19

R13
R12
R10

R11
R6
C14

C16

C18

C20

R8

U6
C12
C13
C23

C27

R7
RN1
R14

C31
CN1 JTAG

C33

CN2
TP3 TP2

C32
CN4 C34
TP4

C35 X1
TP5 R25 C36 C37

Figure 18: Slave CPU Board

24
MAN2994-7

4.14 Addressable Dual Loop Termination Board


The Addressable Dual Loop Termination Board (BRD86DLTB) acts as the interface between the external
addressable devices and the control and monitoring functions of the FireFinder PLUS. Each board provides
terminations for two loops and can be used with the Apollo range of detectors. One slave CPU is required
per loop.

Note: Apollo devices L2 is +ve (positive), L1 is -ve (negative)

AMPAC strongly recommend that the LoopManager test set is used to check that the Apollo loop has been
correctly installed and commissioned before connecting it to the FireFinder PLUS.

Loop Parameters

➢ 126 Apollo Devices (i.e. maximum address range)

➢ When using Alarm Acknowledgement Facility’s (AAF’s) a max of 50 per Loop

➢ 500mA Current Max

➢ S/C protection circuitry activates at approximately 650mA

➢ Maximum length 1.2km

Note: To achieve full current, the Loop Trip current in Loop Parameters needs to be set to 300mA
(ConfigManager PLUS)

CONNECTIONS

CN1 / 2 To Slave CPU Board


CN3 / 4 27VDC in / out
TB1 / 2 To Addressable loop devices

25
MAN2994-7

LOOP 1 / 2 LED STATUS

C2
R2
R3
C1

C3
R4
ZD1
ZD2
INDICATION/S

Q1
LOOP 1

R5
Q2 R20
R12 L1
U1 C6

R9
+
Q4 + TB1

R14

Q6
OUT IN INDICATES OUT Q8
D1
R23
ZD4
OUT ZD5 OUT
-

ZD7
ZD6
LOOP 1

R30
U2
-

Q7
R44 L2 R34 +

C15
+
IN

C16
ON OFF OK C17

Q9
LOOPU31 RETURN SENSE IN IN OUT

R39

R40
R37
R38
U4 U5 ZD9
IN R43
ZD12 -
- L1

ZD11
ZD10
LOOP 2 RETURN SENSEC21 LOOP 1 L1
SHORT CCT U6 D7 + R+

C27 R56
C24
R55
ON ON / OPEN CCT

R61
R50

R51
R52 R54 DC

R62
C26

R63
D5 D6 TH1
-

ZD14
Q10 Q13

R71
R57
R64 Q11 ZD13

R77
L3 R67
-R
IN L2

R66
U7 U8 C34

+ TB2 L2

Q15
C31

C36
Q17 R76
ZD15 OUT
ZD16
OUT

ZD18
-

R81
C35

C40 R84
ZD17
LOOP2 OUT

R83
C38
U9 L4 R92
Q16
R85
R86
R87
+

R97
C39

R89
Q18 C41
ZD20
IN
R93
ZD23 - L1
U10 IN C45 R100 L1
C46
LOOP2
ZD22 R+
+

D14
ZD21

R104
R105
C49 D12 U12
R109 C48 R103 DC
D13 C51 C52

R106
-

R108
R110 L2
C50

L7 TH2
C55 C56 -R
T0 SLAVE CPU
L5

C53
L6 LOOP 2 L2
CN1 C54
CN1 CN2
R111

R113
R112 R114 L8
L1
R115 C57
LOOP 2 CONTROL L1
R116

R119 C58

R120
R117

R118

R121

R122
LOOP 1 CONTROL

R+
R125 Q19

R123

R124
R128 Q20
C59 C60
R127 R130

D16 D15 Q21 D17 D18 Q22


C61

C62
C63 R131 C64 R132 U14

C66
U13
L2
-R
C65

L2
R136 R139
R133

R134

Q25 Q26
C67

C68

R138
R135

Q23 Q24
R137

R144
R145 RN1 R147 RN2
R141 R143 R148
C69 R146 C70
R140 C72 R142 C74
C76

C79
R149 U18 D19 U20 D20
R152 R150

C71 C73
T0 SLAVE CPU C75 U15 C78
U16
R151

Q28
U17

Q27
U19

C77 C80

CN1 C81 C83


C82 C84
Wiring Shown
R158 C86

C85 R155 R156


R157
Above is for a
C87
R160

R161
C88
R159
R162
R163

R169

0V
R167

R168

N1236
R165
R164
C89

R170

R171
C91
R166
C90

R172
C92

XP95 Circuit
R173

U21 R174 C94 TRI WAVE +40V


R175

C96
with one Detector
R178

-5V BRD86DLTB2-
U22
Having LED
R177

R179

C95 +12V C98


C97 R176
+5V C100 C106
R180 R181 D21
Monitoring
C101

R183
R182

C102

C99
U23

R184

U24 U25 U26


C103 C104

C107
CN3 CN4 C105
D22 C109
C108

REGULATED - - L9
HSNK1

27VDC In / Out + +
- -
TH3
POWER

Figure 19: Addressable Loop Termination Board

26
MAN2994-7

4.14.1 Detector loop Isolator Installation


In applications where it is not necessary to use an isolating base for each detector, up to 20 detectors may
be installed between isolating bases.

Note: Refer to Apollo Isolating specifications and guidelines for further details.

If a short circuit or abnormally low impedance occurs, the base isolates the negative supply in the direction
of the fault. When the short circuit is removed the power will automatically be restored.

Note: Isolating base is polarity sensitive.

4.14.2 Loop Isolator calculator


The number of isolating devices on the loop can limit the maximum loop cable length depending on the type
of cable used and the total loop current. Refer to the tables below for reference.

Maximum Cable Length Using 1.5mm². Cable

Number of Isolators 0 5 10 15 20 25 30 35 40 45 50
Loop Current Total
MAX CABLE LENGTH USING 1.5mm².
(mA)
50 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
100 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
150 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
200 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 960
250 1000 1000 1000 1000 973 933 893 853 813 733 733
300 971 931 891 851 811 771 731 691 651 611 571
350 850 810 770 730 690 650 610 570 530 490 450
400 756 716 676 636 596 556 516 476 436 396 356
450 680 640 600 560 520 480 440 400 360 320 280
500 618 578 538 498 458 418 378 338 298 258 218

Maximum Cable Length Using 2.5mm². Cable

Number of Isolators 0 5 10 15 20 25 30 35 40 45 50
Loop Current Total
MAX CABLE LENGTH USING 2.5mm².
(mA)
50 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
100 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
150 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
200 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
250 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
300 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 952
350 1000 1000 1000 1000 1000 1000 1000 950 883 817 750
400 1000 1000 1000 1000 993 926 859 793 726 659 593
450 1000 1000 1000 933 867 800 733 667 600 53 467
500 1000 964 897 930 764 697 630 564 497 430 364

27
MAN2994-7

4.14.3 Loop Open / Short Circuit.


In the case of an Open Circuit or Short circuit (short circuit isolators used) on the Loop Line the Loop board
provides the ability to drive out from both sides of the loop (In and Out). When these Faults are repaired /
cleared the panel will still report a Loop Fault until a Loop Test is performed on the appropriate loop.

28
MAN2994-7

5 FireFinder PLUS Control Panel

#1

Figure 20: The FireFinder PLUS Control Panel

The LCD is used to display abnormal conditions and for interrogation, control and programming activities.
When the FACP is in its normal state a default screen is displayed.

In access level 2 or higher the backlight shall always be ON. Alarm, Fault and Disable information is accessed
through the Main Menu.

#1
Is the intended area for the Alarm Routing Address Code. This area is not printed on the
Decal.

5.1 System Controls

- Active at access level 1, 2 and 3

This control is used to silence the local buzzer. Pressing this button will silence the panel buzzer, which sounds
whenever there is a fire alarm or fault. The sound for a fire alarm is a steady sound where as for a fault it is
intermittent.

- Active at access level 2 and 3.

When the alarm devices are active (FACP is in the fire condition), activating the control will silence all alarms
excluding the External Alarm device.

29
MAN2994-7

Activating the control again, will resound the previously silenced alarm devices.

If a new alarm is recognised whilst in the alarm devices are “silenced”, then all alarm devices shall sound.

Note: If Delays to Outputs have been configured to investigate the delayed Alarm condition press the “Next”
button and “Enter” button.

- Active at access level 1, 2 and 3

Previous and Next controls are used to scroll events on the LCD. The events being displayed depends on the
current selected view.

When the “SEVERAL ALARMS” indicator is illuminated, then multiple fire alarms are present on the FACP. In
order to view the alarms the PREVIOUS and NEXT controls are used.

- Active at access 2 and 3

This control is used to reset the FACP from the fire condition and to clear the system fault indicator.

This control is used to reset the FACP from the fire condition and to clear the system fault indicator and won’t
function unless the alarm devices have been silenced by means of Alarm Silence / Resound control.

- Active at access level 2

This control is used to disable collective zones and/or individual addressable points in alarm or fault.

This control won’t function unless the alarm devices have been silenced first by means of Alarm Silence /
Resound control.

**Note: The “Disable” button will not clear the Fire Alarm condition.

A subsequent “Reset” operation is required to clear the Fire Alarm condition as per the requirements of
AS4428-3:2010 clause 2.2.10.

Entities which can be disabled are:

➢ Zones – to provide an option to distinguish between zone inputs (sensors, detectors etc)
and zone outputs (sounders, beacons, monitored outputs
➢ Sensors – loop based
➢ Loop devices – where the inputs have been configured as alarm initiating
➢ Sounders – loop based and monitored outputs

30
MAN2994-7

- Active at access level 2 and 3

This control is used to disable (and enable) individual Zones and/or Devices.

The indicator is lit steady a device have been disabled.

- Active at access level 2 and 3

This control is used to disable (and enable) the Alarm Devices.

If the indicator is “ON” Steady when any Alarm Devices (including Outputs configured as Alarm Devices) are
disabled and flashes if Alarm devices are in fault. Disable has priority over fault.

- Active at access level 2 and 3

This control is used to disable (and enable) all the ancillary outputs.

The indicator is “ON” Steady when Ancillary outputs are disabled and flashes if Ancillary Outputs have faults
present.

- Active at access 2 and 3 – only when the indicator is flashing.

When the indicator is lit the control is used to override any pre-configured delays to outputs.

The indicator is “ON” Steady when a Delay is programmed and flashes when a Delay Timer is running.

- Active at access level 2 and 3

This control is used to disable (and enable) the external alarm devices output.

If the indicator is “ON” Steady when any Ext Alarm Device output is disabled and flashes if Ext Alarm device
outputs are in fault. Disable has priority over fault.

- Active at access level 2 and 3

The selection keys are used to select a loop device (or range of devices by using the TO key)
or select a zone (or range of zones).

Once a device or zone (or range) has been selected, the DISPLAY or DEVICE DISABLE/ENABLE
controls can be used.

Press this button followed by a number to select the loop you wish to access. e.g. LOOP 4.

31
MAN2994-7

After selecting the Loop number press this button to enter the device number for the device
to be interrogated.

Press this button followed by a number e.g. ZONE 4 to select the required zone.

- Active at access level 2 and 3.

Press this button after selecting the Zone number or the Loop and Device numbers to display the state of the
device. Meaning it is used in conjunction with the selection keys and alpha numeric keypad to DISPLAY a zone
or loop device.

- Active at access level 2 and 3

Use this button to access a range of devices. E.g., 2 TO 7. The selection keys are used to select a loop device
(or range of devices by using the TO key) or select a zone (or range of zones).

Once a device or zone (or range) has been selected, the DISPLAY or DEVICE DISABLE/ENABLE controls can be
used

to - Active at access level 2 and 3.

These buttons are used to navigate around the panel’s menus and enter data. If entering a descriptor, or
some other data that contains characters as well as numbers, pressing the buttons multiple times will scroll
through the available letters written on the button, in sequence. Eg. 1,A,B,C.

Used for data entry into the current field. If he current field is alpha numeric (descriptor strings), then the
alphas are active and selected by consecutive operations of the appropriate key.

- Access level 2 / 3 required

The single arrows are used to select the entry (or insertion point) when entering data.

If the back arrow is used to move the entry point beyond the start of the current field – then the previous
data entry field will be displayed.

32
MAN2994-7

- Access level 2 / 3 required

Press and hold the “display” button while using these buttons to adjust the LCD contrast

The double arrows are use to select the data entry field. These are mostly used when performing on site
programming and selecting the data entry field which is to be edited.

- Active at access level 2 and 3

Used to enter / terminate data entry into the selected field

- Active at access level 2 and 3

Used to cancel data into the current field.

10 consecutive entry of this key exits the current access level to the default access level. For example, if the
current access level is “2”, 10 consecutive entry of this key will set the current access level to “1”.

- Active at access level 2 and 3

Pressing the MENU button will display the main menu on the LCD.

- Active at access level 2 and 3

Pressing the FUNCTION button will display the function menu on the LCD

5.2 System Indicators


Buzzer

The Buzzer is activated by any of the following

➢ Fire – Steady
➢ Fault – Unsteady

- This indicator is illuminated when the FACP is in the fire condition. The fire
condition is latched until it is manually reset, by the use of the RESET control.

The FACP enters the fire alarm condition, when one of the connected fire alarm initiating devices is activated.

Fire alarm initiating devices can be loop based sensors, conventional detectors connected via the 8 way
conventional Add-On, or monitored inputs that have been configured as alarm initiating.

In the “Evacuate” condition the indicator will be flashing.

33
MAN2994-7

When this indicator is illuminated, the nominated fire output has been activated during a fire condition.

If the FACP has been configured to receive a feedback signal from the fire routing equipment – then this
indicator will flash at 1Hertz (½ second on and ½ second off) when the feedback signal is present.

- This LED will be illuminated when mains power is connected to the FACP and
switched on.

The indicator will also flash at 1 Hertz (½ second on and ½ second off) if the mains power has failed and the
panel is running from the secondary supply (batteries).

- This LED will be illuminated when there is a fault associated with the main
or secondary power supply the following conditions constitute a fault.

Faults are:

➢ Charger failure
➢ Battery voltage low
➢ Battery missing
➢ HCI missing
➢ PSU overload

- The indicator is illuminated when there is a main system CPU fault present in
the FACP. The indicator is latching and is cleared by activating the RESET control. System fault is caused by

➢ Main CPU failure -> watchdog condition


➢ Software checksum failure
➢ Memory checksum failure

- This LED will be illuminated if there is an earth fault (+ or -) on any of the


signal cables of the system. An earth fault is when the impedance detected between the 0 volt line of the
FACP and earth is less than 50ohm’s. The indicator is non latching and extinguishes when the current flow
drops below the threshold

- When the indicator is illuminated, the FACP is in any of the “Test” modes.

- This LED will be illuminated when a device/detector is in the pre-alarm state.


Conditions – when at least one sensor has entered the pre-alarm condition. If the pre-alarm is the highest
priority abnormal condition present on the panel – then the sensor in pre-alarm shall be reported to the LCD.
If a higher priority condition is present, then the menu system shall be used to display the pre-alarm.
34
MAN2994-7

- When this indicator is lit, the FACP is in the fault condition. The fault condition
is non latching.

Sources of faults are:

➢ Loop devices – missing, type mismatch, out of calibration / out of maintenance range,
extra (or unexpected device), device related faults (esp. Hochiki)
➢ Analogue loops – short circuit, open circuit or over current
➢ Monitored inputs with open circuit or short circuit conditions
➢ Monitored outputs – with open circuit or short circuit conditions
➢ Main power supply faults – mains missing, charger fault
➢ Secondary supply faults – low battery voltage, missing battery
➢ High Current Interface (HCI) faults – missing, overload
➢ Onboard module faults – missing, failed
➢ Add-On faults – missing, failed, type mismatch
➢ Main CPU failure -> watchdog condition
➢ Software checksum failure
➢ Memory checksum failure

- When this indicator is lit, the FACP is in the Disable (or isolate) condition. The
disable condition is latching.

Entities which can be disabled are:

➢ Zones – to provide an option to distinguish between zone inputs (sensors, detectors etc)
and zone outputs (sounders, beacons, monitored outputs)
➢ Sensors – loop based
➢ Loop devices – where the inputs have been configured as alarm initiating
➢ Sounders – loop based and monitored outputs

- When this indicator is lit, the FACP has had Alarm conditions silenced by the
use of the “Silence/Resound Alarm” button. The condition is latching until another alarm is sounded or the
alarm conditions are cleared.

35
MAN2994-7

6 Functions And Menus


IMPORTANT NOTE: It is strongly recommended that all field programming changes be properly recorded.

6.1 The Default LCD Display


In its normal state the FireFinder PLUS will display a screen similar to that shown below.

FIREFINDER 17/10/2013 09:00:00

FIREFINDER PLUS SUBMISSION


BY AMPAC TECHNOLOGIES

SYSTEM IS NORMAL

AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 21: The Default LCD Display

This screen can be configured with the servicing company’s name and phone number via a laptop or modem.
The current date, time is set in the Function menu while system status is automatically displayed.

AC: is the current Access Level (ie 2Z is access level 2 Zone mode & 2D would be access level 2 device mode)

ALM: is the Alarm counter

PALM: is the Pre-Alarm counter

FLT: is the Fault counter

DIS: is the Disable counter

6.2 LCD Contrast


The Contrast can be adjusted using a combination or the button the and
buttons.

Keep the 'Display' button pressed while simultaneously pressing the '<' button to take the contrast down 1
level, the '>' to take up the contrast by 1 level, the '<<' to take the contrast down by 8 levels or the '>>' to
take the contrast up by 8 levels.

Note: This button combination will only work in access level 2 or higher.

36
MAN2994-7

6.3 Accessing Functions and Menus


At Levels 2 and 3, access to the panel Functions are password protected.

A new panel has a pre-programmed password of 2222 for Level 2 and 3333 for Level 3.

Note: Only Authorised Service Technicians / Engineers have the ability to change passwords.
Note: All menus are provided with screen prompts and a “Quick Reference Guide” (see Section 22) guides
the operator through the operation of the FACP.

From the DEFAULT DISPLAY, press MENU or FUNCTION. The FUNCTION menu is password
protected (actually a pass-number as it can only contain numbers) to prevent unauthorised changes to the
panel's configuration.

6.4 Function Menu and Access Levels


Three levels of ACCESS are available via separate passwords so that access to certain facilities can be
restricted (such as the ability to enter new passwords).

➢ Level I: Allows access to indications and controls to investigate and respond to a fire or
fault warning.
➢ Level II: In addition to the level I facilities, quiescent, fire alarm fault warning, disable and
test conditions.
➢ Level III: In addition to the level II facilities, reconfigure specific data or control and
maintain the panel in accordance with the manufacturers’ specifications.
➢ Level IV: In an addition to level III trained and authorised by the manufacturer to repair or
alter the firmware of a panel.

6.4.1 Forgotten Passwords


Follow the following process if a password has been forgotten or misplaced;

Entering 9999 into the password field;

1. Take note of the 4 digit password number displayed on the screen; then
2. Contact the AMPAC head office and quote the above number;
3. A temporary password will be issued and a new password can then be programmed into
the FACP.

Note: The temporary password becomes invalid if 9999 is entered again or if the panel is re-powered after
9999 has been entered.

37
MAN2994-7

7 The Main Menu


The MAIN MENU is accessed by pressing

MAIN MENU Numbering System:


 denotes the menu structure number
0:ALARMS 1:STAGE 1 ALARMS 2:PRE-ALARMS  denotes the sub-menu numbering
3:FAULTS 4:DISABLES 5:WALK TESTS  denotes a sub-menu within a sub-menu
6:STATUS 7:TOOLS 8:SETUP  denotes another sub-menu within a
9:ABOUT sub-menu
SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 22: The Main Menu (No Network)

Pressing the appropriate number on the keypad while in the MAIN MENU the user can view any;

7.1 Alarms
Pressing  Displays all Alarms present on the system.

ZONE: 1
Zone 1
STATUS: ALARM
‘DATE’ ‘TIME’

ZONE ALARM 1 OF 1
DEVICE>
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 23: The ALARMS display

Pressing the will display the Device Information the screen, pressing the will return it to
Zone Information

7.2 Stage 1 Alarms


Pressing  Displays all Stage 1 Alarms present on the system

ZONE: 1
Zone 1
STATUS: STAGE 1 ALARM
‘DATE’ ‘TIME’

ZONE STAGE 1 ALARM 1 OF 1


DEVICE>
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 24: The STAGE 1 ALARMS display

Pressing the will display the Device Information on the screen, pressing the will return it
to Zone Information

38
MAN2994-7

7.3 Pre-Alarms
Pressing  Displays all Pre-Alarms on the system

ZONE: 1
Zone 1
STATUS: PRE-ALARM
‘DATE’ ‘TIME’

ZONE PRE-ALARM 1 OF 1

DEVICE>
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 25: The PRE-ALARMS display

Pressing the will display the Device Information the screen, pressing the will return it to
Zone Information

7.4 Faults
Pressing  Displays all Faults on the system

FAULT MENU

0:ZONE/DEVICE 1:LOOP 2:MODULE


3:P/SUPPLY 4:BRIGADE 5:TFAILS
6:SOUNDERS 7:ADD ONS 8:SYSTEM

SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 26: The Fault Menu display (no network)

FAULT MENU

0:ZONE/DEVICE 1:LOOP 2:MODULE


3:COMMS 4:P/SUPPLY 5:BRIGADE
6:TFAILS 7:SOUNDERS 8:ADD ONS
9:SYSTEM
SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 27: The Fault Menu display (Network configured)

39
MAN2994-7

ZONE: 1
Zone 1
STATUS: FAULT
‘DATE’ ‘TIME’

ZONE FAULT 1 OF 1

DEVICE>
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 28: The FAULTS display

Pressing the will display the Device Information the screen, pressing the will return it to
Zone Information

40
MAN2994-7

7.5 Disables
Pressing  Displays all Disables on the system.

ZONE: 1
Zone 1
STATUS: DISABLE
‘DATE’ ‘TIME’

ZONE DISABLE 1 OF 1

DEVICE>
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 29: The DISABLES display

Pressing the will display the Device Information the screen, pressing the will return it to
Zone Information

Note: If there are no disables, a message, e.g. ‘NO ZONES OR DEVICES OR SOUNDERS OR ADDONS
DISABLED’, will be displayed for 1 to 2 seconds and then the display will return to the Main menu.

NO ZONES OR DEVICES OR

SOUNDERS OR ADDONS DISABLED

AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 30: No Zone , Devices, Sounders or Addons disabled screen

7.6 Walk Tests


Pressing  Displays all Walk Tests on the system

ZONE: 1
Zone 1
STATUS: WALK TEST

TERMINATE<KEY 0>
ZONE WALK TEST 1OF 1
DEVICE>
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 31: The WALK TEST display

Pressing the will display the Device Information the screen, pressing the will return it to
Zone Information

41
MAN2994-7

7.7 Status
Pressing  Displays the Status of the system

STATUS MENU

0:LOOPS 1:MODULES 2:I/O


3:BRIGADE 4:SYSTEM 5:AVALUES
6:ADD ONS

SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 32: The Status Menu (No networking)

STATUS MENU

0:LOOPS 1:MODULES 2:I/O


3:BRIGADE 4:NETWORK 5:SYSTEM
6:AVALUES 7:ADD ONS

SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 33: The Status Menu (Networking)

From the STATUS MENU the status of system components and settings can be selected and displayed as
listed below.

Note: Different screens are displayed for a system with and without networking.

Press

 Loops: Enter the loop number and the LCD will display its status, e.g. normal, type of fault etc. The
Loop current draw and noise levels will also be shown in panels that have Slave CPU software version V9.0
or higher

LOOP NO:1

STATUS: NORMAL
CURRENT (mA) 0 NOISE (mA) 0

0:PRINT ALL DEVICES 1:PRINT TOTAL


SELECT NO. _
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 34: Display Loop Status

42
MAN2994-7

 Modules: Select the type of module, Slave and P/S

DISPLAY MODULE STATUS

0:SLAVE 1:POWER SUPPLY

SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 35: The Display Module Status display

 I/O: The LCD will display the status of an input or output in a panel or on a loop, Outputs  and
Inputs .

DISPLAY INPUT/OUTPUT STATUS

0:OUTPUTS 1:INPUTS

SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 36: The Display I/O Status display

DISPLAY OUTPUT STATUS

0:IN A PANEL 1:ON A LOOP

SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 37: The Display Output Status display

Once entered the LCD will then display a description of what that input or output does and its current state.

 Brigade: Displays the Brigade Board I/O Status

BRIGADE STATUS (NP: 1)

OUTPUT 1: (FIRE ) OFF /NORM


OUTPUT 2: (FAULT ) OFF /NORM
OUTPUT 3: (SOUNDER ) OFF /NORM
OUTPUT 4: (SOUNDER ) OFF /NORM
PRESS > FOR INPUTS/RELAYS/AUXS
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 38: Display Brigade Status

43
MAN2994-7

Once entered, the LCD will then display the inputs, outputs, relays and auxiliary devices status.

 Network: Displays Network Status.

Is pressed to gain access to NETWORK STATUS.


Note: This option is only available if the system configuration is networked.

DISPLAY NETWORK STATUS


NIC VERSION: 0.0.00.00

0:NETWORK POINTS
1:REMOTE SLAVE MODULES
SELECT NO.

AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 39: Display Network Status

 Network Points:

DISPLAY NETWORK POINTS

0:STATUS 1:POWER SUPPLY 2:BRIGADE

SELECT NO.

AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 40: Display Network Points

Network Points Screens are

 STATUS: Press, Select network point e.g. Loop Number


 POWER SUPPLY: Press to display Charger Volts, Battery Detected and Mains OK
 BRIGADE: Press to display Operational or Non-Operational

 Remote Slave Modules:


Select from Network Status Remote Slave Modules, then Module number.

Apollo Loop 1
TYPE:APOLLO LOOP NO:1 VER: 6.1
NP:1 MOD:4 STAT:NORMAL
REMOTE MODULE STATUS

AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 41: Display Remote Module Status

Note: The SYSTEM, AVALUES and ADD-ONS will increment by 1 if the network is configured

44
MAN2994-7

/ SYSTEM: Is pressed to access SYSTEM STATUS

SYSTEM STATUS
ALARMS:000 PRE-ALARMS:000 DISABLES:000
DEVICE FAULTS:00 MOD FAULTS:00
LOOP FAULTS:00 EXTRA DEVICES:00
WALK TEST:00 WDOG:00
APP: V 1.0 EN54
CONFIG:
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 42: Display System Status

/ AValues: Is pressed to access AVALUES.

Select Loop Number and device number to show AVALUES

Loop 1 sensor 1

L1 S1 Z2
STAT: NORMAL
AVALUE:25 MODE:0 I:000 O:000

0:PRINT ENTRY
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 43: Analogue Values

/ ADD-ONS: Is pressed to access MODULE status

DISPLAY ADD-ON MODULE STATUS

NODE: 000
MODULE (1-32):

SELECT ADD-ON MODULE NO. THEN ENTER KEY

AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 44: Add on Module status

45
MAN2994-7

7.8 Tools
Pressing  allows for the Testing of the following selected fields

TOOLS MENU

0:ALARM 1:FAULT 2:LAMP

SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 45: The TOOLS menu

Pressing  brings up a further detailed selection sub-menu for an Alarm tests.

ALARM TEST

0:ZONE 1:DEVICE

SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 46: The ALARMS test menu

Pressing  brings up a further detailed selection sub-menu for a Fault tests.

FAULT TEST

0:ZONE 1:DEVICE

SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 47: The FAULT test menu

Pressing  initiates a LAMP Test. Which will scroll thru and illuminate all LED’s and LCD screen

46
MAN2994-7

7.9 Setup
Pressing  Displays the setup for sounders, Zone Delay and Printer

SETUP MENU

0:SOUNDER 1:ZONE DELAY 2:PRINTER


3:LANGUAGE

SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 48: The SETUP menu

Pressing  brings up a further detailed selection sub-menu for Sounder O/P’s.

SOUNDER MENU

0:SOUNDER ENABLE 1:SOUNDER DISABLE


2:SOUNDER RE-TRIGGER(ON)
3:SOUNDER RE-TRIGGER(OFF)
CURRENT STATUS: ENABLE / RE-TRIGGER (ON)
SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 49: The SOUNDER menu

Note:Pressing  and  require access level 3.

Pressing  brings up a further detailed selection sub-menu for Zone delays

ZONE DELAY MENU

0:ALL ZONE DELAY ON 1:ALL ZONE DELAY OFF

CURRENT STATUS: DELAY ON

SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 50: The ZONE DELAY menu

Pressing  brings up a further detailed selection sub-menu for Printer

PRINTER MENU

0:GO OFF-LINE / GO ON-LINE

1:ALARM MODE ONLY

SELECT NO.
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 51: The PRINTER menu

47
MAN2994-7

Note: The GO OFF-LINE and GO ON-LINE is a toggle option

Pressing  toggles the alternative Language for the display text.

7.10 About
Pressing  Displays the panel’s application software version number and the title information. Title
information could be company name, contact information and so on.

ABOUT MENU
VERSION#:1.01.00.AS7240
AMPAC TECHNOLOGIES

AC:2Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 52: The About menu

48
MAN2994-7

8 The Function Menu


The FUNCTION MENU is accessed by pressing button.

A prompt will ask for a PASSWORD if the control panel is not currently active. Using the keypad key in the
Level 2 or 3 PASSWORD.

LEVEL III MAIN FUNCTIONS

0:DATE 1:TIME 2:DAY/NIGHT 3:LOGS


4:TESTS 5:I/O 6:GLOBAL 7:PASSWORD
8:PROG

SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 53: The Functions Menu (Level 3 screen shown)

8.1 Date
Press  To select the set DATE SCREEN. The prompt will ask for the date to be entered in this format,

DD/MM/YYYY (EG 01/01/2011), key in and press . The screen will then return to the MAIN
FUNCTIONS MENU.

DATE MENU 01/01/2012 12:00:00

DATE: DD/MM/YYYY

SELECT DAY OF MONTH

AC:3Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 54: DATE Menu

8.2 Time
Press  To select the set TIME SCREEN. Then in the following format key in the time, HH:MM using the 24

hour mode. Press and the screen will return to the MAIN FUNCTIONS MENU.

TIME MENU

TIME: HH:MM

SELECT HOURS (IN 24HR MODE)

AC:3Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 55: TIME Menu

49
MAN2994-7

8.3 Day/Night
Press  The DAY-NIGHT SETTINGS screen will appear. Time entry is the same as setting the “Time” facility.
Note this Function is available at Access Level 3 only.

Press  To enter the DAY ON time.


Press  To enter the NIGHT ON time.
Press  To ENABLE / DISABLE

DAY-NIGHT SETTINGS – CURRENTLY DISABLED

DAY ON TIME 08:00 NIGHT ON TIME 18:00

0:DAY TIME 1:NIGHT TIME 2:ENABLE

SELECT NO
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 56: DAY-NIGHT SETTINGS Menu

For this Function to have control it must be ENABLED by press  Re-pressing  will toggle to DISABLE.

8.4 Logs
Press  to access the EVENT LOG MENU will be displayed.

The LOGS MENU allows the operator to select and view the events that have occurred.

EVENT LOG MENU (MAXIMUM SIZE = 2000)

0:ALARM 1:FAULT 2:DISABLE 3:SYSTEM

4:I/O 5. ERASE ALL LOGS 6. WDOG

SELECT NO
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 57: DAY-NIGHT SETTINGS Menu

Once the type of log is selected, e.g. FAULT, each entry can be viewed by stepping through them

using the buttons

Note: Pressing  and  require access level 3.

The type of log, number and totals logged, date and time of the ALARM, FAULT, DISABLE, SYSTEM or I/O as
well as device information will be displayed. The SYSTEM screen displays events and watchdog activity. From
these screens the operator can select two other facilities, they are;

 PRINT ENTRY will print out the displayed information if a printer is installed, or
 SHOW OPTIONS allows the operator to select how the Logs are viewed.
 To VIEW BY ENTRY NUMBER,  to VIEW BY DATE or  to PRINT MULTIPLE ENTRIES. In each case the
screen will ask for the appropriate information (ENTRY NUMBER or DATE) to be entered before the selected
option will be displayed.
50
MAN2994-7

8.5 TESTS
Press  to access the TESTS menu. Note this is an Access Level 3 function only.

TESTING MENU

0: WALK TEST 1:LOOP TEST


2: DEVICE LED TEST

SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 58: The Testing Menu

Press  to initiate a WALK TEST:

WALK TEST MENU

0: NEW ZONE WALK TEST


1: NEW ZONE SILENCE WALK TEST
2: VIEW ZONE WALK TEST

SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 59: The Testing Menu

When in walk test the indicator is on.

Press  LOOP TEST requires the operator to select a LOOP for DIAGNOSTIC TESTING

Entering the LOOP number and pressing will initiate the DIAGNOSTIC TEST.

Note: The LED’s on the Brigade Board will indicate which leg is being tested.

The tests displayed are;

➢ TESTING SIDE A IDENTIFING DEVICES on SIDE A, and

➢ TESTING SIDE B IDENTIFING DEVICES on SIDE B.

Once the testing is completed the final screen will display the number of devices found and tested on the
LOOP and a Reset is requested to return the system to normal.

Note: If the data is not entered within 2 minutes the screen will time out and return to the DEFAULT SCREEN.

Note: A Loop Test needs to be conducted after a short / open circuit has occurred, corrected and cleared to
return the panel to its default Normal status otherwise the panel will display a loop fault.

Press  to initiate a DEVICE LED TEST:

This allows the user to turn on a device LED. Cancel out of the Device LED test screen will automatically turn
off the device LED. If the device LED test screen is left on after 30 minutes the LED will turn off and the panel
return to the Normal screen.

51
MAN2994-7

8.6 I/O
Press  To display the Manual I/O Control menu

MANUAL I/O CONTROL

0: INPUT 1 :OUTPUT

2: REMOVE ALL MANUAL CONTROL

SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 60: The Manual I/O Control Menu

Manual I/O control allows the technician to turn ON or OFF inputs and outputs off a device to facilitate testing
or isolation of plant during maintenance. Removal of manual control returns control to the panel.

Press  Input Selected:

MANUAL INPUT CONTROL

0:IN A PANEL 1 :ON A LOOP


2:ON A LOCAL ADDON MODULE
3:REMOVE ALL MANUAL INPUT CONTROL

SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 61: The Manual Input Control Menu example

Press

 IN A PANEL: Enter the I/O Controller number then the input number. This will display the description for
the input and its current state, you can then turn the input ON or OFF or remove manual control.

 ON A LOOP: Enter the loop number, the device number and the input number. This will display the
description for the input and its current state, you can then turn the input ON or OFF or remove manual
control.

 ON A LOCAL ADDON MODULE: Will bring up the list of Modules that have inputs. These can then be
manually turned on and off with the exception off the MCP configured input

LOCAL ADDON MODULE INPUT

1: BRIGADE
2: 16WAY INPUT BOARD

SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 62: Addon Module Input Controls example

52
MAN2994-7

 Remove All Manual Input Control: Will remove all manual input control.

 Output Selected: Same sequences as above for inputs but substitute outputs for inputs.

 Remove All Manual Control Selected: Globally removes all manual control.

8.7 Global
Press  To display the Global Output Control menu (These operates across all panels on the network)

GLOBAL OUTPUT CONTROL

0:FWRE OUTPUT 1:FARE OUTPUT


2:WARNING SYSTEM OUTPUT

SELECT NO.

AC:3Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 63: The Global Output Control Menu

Press

 FWRE OUTPUT:

Provides control to disable or enable the FWRE outputs. Press

 ENABLE

DISABLE

FARE OUTPUT:

Provides control to disable or enable the FARE outputs. Press

 ENABLE

DISABLE

WARNING SYSTEM OUTPUT:

Provides control to disable or enable the warning system outputs. Press

 ENABLE

DISABLE

53
MAN2994-7

8.8 Passwords (Level III)


Press

While in the Main Functions menu and enter the Level III Password if in Access Level II or, if in Access Level
III to display the Password Menu.

PASSWORD MENU

0: ADD PASSWORD 1 :DELETE PASSWORD

2: DELETE ALL PASSWORDS

SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 64: The Password Menu

 Add Password: Enter the new password, then press . The password is always a 4 digit number.

 Delete Password: Enter the password that you want to delete, then press .

 Delete All Passwords: This asks you to confirm that you want to delete all the passwords. Press

then again.

54
MAN2994-7

8.9 Programming
Press  To display the Level III Programming Menu.

ON SITE PROGRAMMING MENU

0: CONV ZONE 1 :DEVICE 2:INPUT 3: OUTPUT


4: PANEL BASED MCP 5:SUB ADDRESS
6:ZONE PROGRAMMING

SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 65: Programming Menu

8.9.1 Conv (Conventional) Zone


Press  CONV ZONE:

Key in the zone number and enter or change the description (DESC) by pressing buttons
to move the flashing underline or curser. The numeric buttons multiple times to access characters while at
the same time using

EDIT Zx DESC AND TYPE STRINGS


DESC < ZONE >
TYPE<
ALPHA KEYS ARE ACTIVE

AC:3Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 66: Zone Description & Type Programming

Press to move to the TYPE field or edit the information.

Press to move between fields use the reciprocal button

By going through all the fields a second screen can also be accessed to show the Output options.

Press to step through these fields.

EDIT ZX BRIGADE OPTIONS AND CONFIG


ALRM: Y/N BELL: Y/N AUX: Y/N SPRK: Y/N
AIF: Y/N
ALARM LED: Y/N CONFIG: LATCHING
Use < or > to change setting

AC:3Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 67: Brigade Options

55
MAN2994-7

The buttons are used to set the Y/N field, which is the selected Zone that will activate
the Brigade Options ALRM, BELL etc and Config.

EDIT Z CONFIGURATION
CONFIG: LATCHING

Use < or > to change alarm setting

AC:3Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 68: Zone Configuration Latching / Non-latching

Use or to change the setting

Configuration settings are Latching, Non-Latching, AVF, Self Reset ( 0 to 99 seconds ). After setting the
Configuration the ZONE I/O GROUPS are programmed.

EDIT Z I/O GROUPS


GROUP1: GROUP2: GROUP3:
GROUP4: GROUP5: GROUP6:
Enter GROUP NO.

AC:3Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 69: Zone I/O Groups

After scrolling through the groups and entering what I/O GROUPS will be turned on by what module/s or

device/s in a zone/s the operator is prompted to press to confirm the entries and / or changes.

8.9.2 Device
Press  DEVICE:

Use these buttons to EDIT and move through wording & numbering

Use these buttons to MOVE between fields i.e.: DESC & TYPE and next parameter

Enter the and number then scroll through the following screens.

56
MAN2994-7

Press or Press

 To EDIT or  to DELETE

1. EDIT LxSx DESCRIPTION AND TYPE STRING. Edit then. Press

e.g.: DESC Loop 1 Sensor 1

TYPE SMOKE

2. Allocate / Edit the Device to a Zone and set the device type then. Press

e.g.: XP95 Photo, XP95 Heat etc-

3. Set /Edit and display the Output Configurations or options then. Press

e.g.: Latching, AVF, Non-latching etc

4. Set / Edits and enables / disables the day/night settings then. Press

5. Allocates / Edits the Loop and Devices Groups.

After scrolling through the groups a prompt tells the operator to press to confirm the changes.

8.9.3 Input
Press  INPUT:

By following the screen prompts as above Edit or Delete an INPUT in a panel or a loop.

Screen: PROGRAM MENU SELECTING AN INPUT

 IN A PANEL  ON A LOOP
I/O MODULE LOOP

Select I/O MODULE NO. then Select LOOP NO. then


INPUT DEVICE

Select I/P NO then Select DEVICE NO. then


EDIT / DELETE DESC INPUT

Select INPUT NO. then button


ALPHA BUTTONS ARE ACTIVE EDIT Lx Sx I/Px DESC STRING DESC

57
MAN2994-7

8.9.4 Output
Press  OUTPUT:

By following the screen prompts as above Add, Edit or Delete an output in a panel or on a loop.

8.9.5 Panel Based MCP


Press  to EDIT

8.9.6 Sub Address


Press  to EDIT

8.9.7 Zone programming


Press  to EDIT.

Key in the zone number and select the key.

Enter or change the description ( DESCR ) by pressing buttons to move the flashing underline or curser. Press
the numeric buttons multiple times to access characters.

EDIT ZONE: 1 DESC STRING


DESCR<MY ZONE 1 DESCRIPTION

ALPHA KEYS ARE ACTIVE

[USE>> TO EDIT NEXT FIELD]

AC:3Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 70: Zone Programming - Description

Press the key to edit the next field (Day Night Settings).

EDIT ZONE: 1 DAY NIGHT SETTINGS


DAY_NIGHT ENABLE: Y
DAY MODE SETTING: A TIMEOUT: 0
NIGHT MODE SETTING: N TIMEOUT: 0
[USE < OR > TO EDIT]
[USE << OR >> TO NAVIGATE]
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 71: Zone Programming – Day/Night Setting 1

The keys are used to set the:

• Y/N field for the "DAY_NIGHT ENABLE”

• A/B/C/D/N field for the “DAY MODE SETTING” and “NIGHT MODE SETTING where “A, B, C”
refers to “Dependency A, B, C” respectively, “D” refers to “Delay to Outputs” and “N” refers
to “Normal” (i.e. no mode setting).

58
MAN2994-7

The numeric buttons are used to edit the TIMEOUT fields.

EDIT ZONE: 1 DAY NIGHT SETTINGS

DAY / NIGHT
MCP OVERRIDE: N / N
DELAY ALARM DEVICE: N / N
DELAY FARE: N / N
[USE < OR > TO EDIT]
[USE << OR >> TO NAVIGATE]
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 72: Zone Programming – Day/Night Setting 2

The keys are used to set the Y/N field for the "MCP OVERRIDE, DELAY ALARM DEVICE,
DELAY FARE”.

EDIT ZONE: 1 CONFIRMATION

SELECT ENTER TO SAVE

AC:3Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 73: Zone Programming – Confirmation

Select the key to confirm the changes.

8.9.8 Extra Devices Detected


The FireFinder PLUS LCD will indicate extra devices have been detected by displaying the screen below and
the FAULT LED will be illuminated.

FIREFINDER 26/2/2007 08:05:45


EXTRA DEVICES DETECTED
GOTO PROGRAMMING MENU TO RESOLVE
SYSTEM IS NOT NORMAL

AC:3Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 74: Resolving Extra Modules and Devices

To resolve select FUNCTION, enter PASSWORD, press  and the screen below will appear

59
MAN2994-7

PROGRAMMING MENU
0: RESOLVE EXTRA MODULES AND DEVICES
1: ON SITE PROGRAMMING

SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 75: Added Module or Device

Select  (Selecting  presents the PROGRAMMING MENU) then  or  (as seen below) then ENTER to ADD
the module or device to the configuration, or skip to resolve the changes manually in the Programming Menu.

0: ADD EXTRA MODULES 1: ADD EXTRA


DEVICES
2: DEVICE TYPE MISMATCH 3: MODE
MISMATCH
SELECT NO.

AC:3Z ALM:0 PALM:0 FLT:0 DIS:0

Figure 76: Resolving Extra Modules or Devices

8.9.9 Mismatch Detected


If a mismatch is detected the Normal Default Screen will change to that shown below. Go to the Programming
Menu and select either  Resolve Extra Modules and Devices then 

(Device Type) or  (Mode) to resolve the mismatch, OR On Site Programming to resolve manually.

Loop 1 Sensor 1
L1 S6 Z1 STAT: TYPE MISMATCH

ZONE FAULTS 1 of 1

Figure 77: Resolving a Mismatch

Self Learn is enabled / disabled in the EEPROM programming. If enabled FireFinder PLUS has the ability to
detect extra or missing modules or devices, (that is devices or modules that have been added or removed)
or there has been a change of the type of module or device.

Note: If a change does occur the FACP will take 30seconds to register the event on the LCD and illuminate
the FAULT LED.

9 Incoming Fire Alarm Signal

➢ Will operate the red common LED fire indicator


➢ Will display location of fire alarm origin on the LCD
➢ Will activate external alarm.
➢ Will activate the internal FACP buzzer.
➢ Will activate any ancillary equipment so programmed.
➢ Will abort any test in progress.

60
MAN2994-7

The LCD will always display the first fire alarm signal received in the top section of the LCD. The lower section
of the LCD will also permanently display the most recent zone in alarm. Other essential fire

alarm information and fault or disablement information is available via the

buttons. After 30 seconds if no button is pressed the top section of the display will revert to displaying the
first zone in alarm.

FIRST ALARM: L1 D1 Z1 15:31


D.DSC:Loop 1 Sensor 1
Z.DCS:Zone 1
LAST ALARM: L4 D49 Z5 15:31
D.DSC:Loop 4 Sensor 49
Z.DCS:Zone 5 Depend C
PRESS PREVIOUS/NEXT TO VIEW OTHER ALARMS
AC:2Z ALM:5 PALM:0 FLT:0 DIS:0

Figure 78: LCD Screen with 5 Devices in Alarm

Note: The displayed information changes to that associated with the device as the

push buttons are pressed. If there is a fault condition or a fire alarm and

the buzzer is sounding, press the button to stop it sounding

61
MAN2994-7

10 Accessing a Loop, Device or Zone

LOOP OR DEVICE

➢ From the default display, press

➢ Enter the loop number you wish to interrogate then press .

➢ Press the button for the device number.

➢ Press the button if you wish to access a range of devices on the loop,

➢ Press the button if you wish to display the status of a device,

➢ Press the button if you wish to disable a device

➢ Press the button to re-enable a device.

ZONE

➢ From the default display, press .

➢ Press the button for the zone number.

➢ Press the button if you wish to access a range of zones,

➢ Press the button if you wish to display the status of a zone,

➢ Press the button if you wish to disable a zone

➢ Press the button to re-enable a zone.

62
MAN2994-7

11 Modem / Programming / Debug Interfacing


The modem I/O port is a Dual DB9 connector (CN8 situated on the lower left hand corner of the Main Board
BRD86MBA) that is normally used for programming of the FACP via the serial port of a PC or Laptop. There is
also a USB connector (CN25) provided to allow programming of the FACP from a USB port of a PC.
COMMS PORT 2
MAIN BOARD BRD86MBA
RS485 EOL
LK2
Q5
R55 R58 CN9
27V IN R25 R19
COMMS 2 R56
C90 RN16
RS232 R57

C89
C82 LK3
CN21
C83
BUZZER
R20 R64
CN27 RN6
BUZZER
INHIBITCOMMS PORT 3 OUT

EXPANSION
MODULE
COMMS2 RS232 (TOP) U32
RN17
CN27 - 10 WAY IDC CN28 NOTE: CN8 (TOP)
CONNECTOR & CN27 ARE BOTH
COMMS 2 IN CFM TH1
CN2
ZDN2

CN8 COMMS PORT 1 CN25


BZ1
COMMS1 RS232/MODEM

+
CN3 COMMS 3 USB
SHIELD PIN 1 (BOTTOM) EXPANSION PANEL EXPANSION LEDS
RD TD

The Controller also has the required hand shaking to support connection to a Modem, thus allowing the FACP
to be programmed from a remote site that has an established telephone connection. This allows the system
software to be upgraded by simply transmitting a file via the serial port of the PC or Modem external to the
FACP. Diagnostic facilities are also available via the same connection.

Plug in DB9
Connector 1
6
2 Rx Data
7
3 Tx Data
8
4
9
5 Signal
Ground
Note: CN8 is located on the lower CN8
left hand side of the Main Board

Figure 79: FireFinder PLUS Debug Cable Connections

Note: Debug/Notebook cables


are available from AMPAC

Figure 80: FireFinder PLUS Debug Cable Connections

Note: the DB9F to DB9F cable is not sensitive to which end is plugged in to the FireFinder PLUS or serial
port of the PC or vice versa.

The connections between the PC/Modem and the panel are crossed. i.e. TD connects to RD.

Make sure the ConfigManagerPlus program is set to use the port you have connected the cable to and set
up the configuration as follows:

Bits per second: 115200


Data bits: 8
Parity: None
Stop bits: 1
Flow Control: None

63
MAN2994-7

12 Expanding the FACP with Compatible FireFinder PLUS Boards


12.1 Ancillary Services
The FACP has been designed such that detectors and/or call points, in addition to giving an alarm and calling
the fire brigade, will close or open circuits of ancillary services by means of relays or similar devices.
Examples of these services are:

➢ Actuation of fixed fire-extinguishing systems


➢ Closing of windows, smoke and fire doors
➢ Control of ventilating systems
➢ Covering of tanks containing flammable liquids and controlling their valves to isolate the
contents from direct contact with the fire, etc.

To facilitate safe maintenance of these services an option is available that allows for the isolation and visual
indication of the disablement of ancillary services that does not affect the normal operation of the fire alarm
system.

To ensure power to the fire alarm system is not prejudiced in any way, power for the ancillary services must
be included in the calculation of the power supply and battery capacity.

12.2 Compatible FireFinder PLUS Boards


Add- On Module / Board Max No
Brigade Board 1 Per Controller
8 Zone Conventional Card 15 per Controller
32 Zone Alarm Indicator Card 15 per Controller
8 Way Relay Board 15 per Controller
Smart terminal 30 per Controller
Agent release module 8 per Controller
4 way Fire Fan Module with Reset 15 per Controller
4 way Fan Control (Loop driven) 15 per Controller
8 way Switch and Indicator Card 15 per Controller
16 Way Input Board 15 per Controller
High Level Interface Expander 3 per Controller
8 Way Sounder Board 15 per Controller
Zone Control Card 15 Per Controller
Conventional Network Board 1 Per Controller
Bargraph Display Card ( BDC )
Printer 1 per Controller
Expansion Board 1 per Controller
Network Interface Card 1 per Controller
Apollo / Dual Loop Termination Board 8 Per Controller
Communication Extender Board 1 per Controller

 Note: The Max Numbers of modules/boards that can be installed and configured within the FACP depends
on the cabinet size and the number of Panels in the System.

 Note: Refer to individual Product datasheets and installation guides for complete details.

64
MAN2994-7

12.3 Expansion Board

The Expansion Connection Board (BRD86FEPB) is used to increase the capacity of the controller from 4 Slave
CPU’s to 8 allowing Loops 5 – 8 to be configured. Connection from the Controller to the Expansion Board,
which must be mounted within 200mm of the Controller, is made via a 20 way flat cable Slave CPU number
5 is an integral part of the Expansion Board, only Slave CPU’s 6 (CN2), 7 (CN3 and 8 (CN4)are plug ins.

Connections

CN1 To Main Connection Board


CN2 To Slave CPU 2
CN3 To Slave CPU 3
CN4 To Slave CPU 4
CN5 On board Slave CPU

TO CN2 OF MAIN BOARD


20 WAY
RIBBON CABLE

TP4 TP3 TP2 C2 CN1 CN2 CN3 CN4


TP5

N1236
CN6 JTAG
C10 D1 Slave CPU 6 Slave CPU 7 Slave CPU 8
C7
C35
COMMS C3 C4
U7

R24

C12 C11
RN1 R6

R25
CN7 C9
U4
C36 U2 U1 U3
C38
C37

R2

U8 U5

X1

BRD86FEPB2-
C39
C32 C33 R7 C13
C34
CN5 Slave CPU 5 R14
U6
C14
C15
C16 C5
C17
C18
R4 D2
R26 Q1
Q2 R1
C1
D3
DEBUG
R9
C40 LK1
R8 U10
R23
C27
R10 C41
R12
U9 R5
R11
R13
C31 TP1
C8

Figure 81: Expansion Board Overlay

65
MAN2994-7

12.4 8 Zone Conventional Board


This board (BRD43EZC) has 8 conventional zones. Up to 999 zones max may be configured.

The zones may be used in panel programming and Input / Output programming.

 Note 1: Each Zone circuit MUST be terminated with either a;

➢ 3k3 resistor ( Default )


➢ 10uF 50VDC bipolar capacitor
➢ 4k7 resistor
➢ 6k8 resistor, OR
➢ 10k resistor

Maximium of 32
devices per Zone
(See Note 2)

PRESS HERE

TO BREAK End Of Line


(See Note 1)
FIRE
ALARM

EOL EOL EOL EOL EOL EOL EOL

+ Z1 - + Z2 - + Z3 - + Z4 - + Z5 - + Z6 - + Z7 - + Z8 -
To Zones 1 to 4 + / - To Zones 5 to 8 + / -
TB1 TB2

To Zones 1 to 4 + / - To Zones 5 to 8 + / -

+ - + - + - + - + - + - + - + -
Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8
TB1 TB2
CN2
RS485 Control
Comms In

RS485 Control
EOL

CN3 Address SW
Comms Out
(see Note 3)
ON
+ Fit EOL Termination
Link 1 if Last Module
ON
CN4 CN5
on Comms Bus
- 1 2 3 4 SW1

27V IN 27V OUT

Figure 82: 8 Zone Conventional Board

Connections

Terminal/s Function
TB1&2 Terminals 1, 3, 5, 7, 9, 11, 13, 15 ZONES 1 to 8 +ve
TB1&2 Terminals 2, 4, 6, 8, 10, 12, 14, 16 ZONES 1 to 8 -ve

 Note 2: If Diode Bases are used ONLY the 10uF CAP can be used.
 Note 3: See Section 17 for Addressing Details (SW1)
 Note 4: Short circuits on the Zone is a “Fault” condition on the FACP NOT an “Alarm”
 Note 5: Hard contact MCP’s will require a 470Ω to 680Ω series activation resistor to generate an alarm
condition and to avoid hard contact MCPS putting the Zone into Short circuit fault”
66
MAN2994-7

12.5 16 Zone and 32 Zone Indicator Modules

This module (BRD43ZAMC) has 32 bi-coloured LED’s which can be used to display the status of up to 32
individual Zones or 16 Zones with dual LEDs.

The zone numbers assigned to each LED are configurable and the LED’s will operate in the following manner
for the respective zone statuses:

ZONE STATUS LED STATE LED COLOUR


FIRE ON STEADY RED
DEPENDENCY B FLASH RED
DISABLED ON STEADY YELLOW
FAULT FLASH YELLOW
ALL OTHER OFF n/a

The card will also respond to a lamp test when instigated on the panel to which it is connected.

Figure 83: 32 Zone and 16 Zone Indicator Decals

(See LAB1516.doc on the Web for Slip in Label)l

C C
N N Top Card &
1 2 PCB Securing Clips
Address SW
In Out (See Note)
RS485 Control RS485 Control ON
1 2 3 4

/ 27VDC / 27VDC
Comms In Comms Out

Fit EOL Termination Link


if Last Module
on Comms Bus

Bottom Card &


PCB Securing Clips

Figure 84: Zone Alarm Mimic Card Rear View showing connectors and Address Switch

 Note: See Section 17 for Addressing Details (SW1)

67
MAN2994-7

12.6 8 Way Switch and Indicator Module

This card (BRD25GIB-B) has 8 switch inputs and 8 LED indicator outputs.

The switch inputs and LED outputs may be used in Input Output programming.

The switches are configurable as either momentary or toggle switches. When configured as momentary
pressing the button once will cause an event to occur as programmed in I/O and the LED’s can be
programmed to operate as an output.

When configured as toggle, pressing the button once will cause a condition to be held until the button is
pressed again. The associated LED is not available as an output in and shall always be illuminated when the
toggle condition is active. Also, when configured as a toggle, there shall be an option for a timer override. If
the toggle switch is activated it shall be de-activated automatically after the timeout period.

Figure 85: 8 Way Switch and Indicator Card Decal (See LAB1483.doc for Slip in Label)

C C
N N Top Card &
1 2 PCB Securing Clips
Address SW
In Out (See Note)
RS485 Control RS485 Control ON
1 2 3 4

/ 27VDC / 27VDC
Comms In Comms Out

Fit EOL Termination Link


if Last Module
on Comms Bus

Bottom Card &


PCB Securing Clips

Figure 86: 8 Way Switch and Indicator Card Rear View showing connectors and Address Switch

 Note: See Section 17 for Addressing Details (SW1)

68
MAN2994-7

12.7 Zone Disable and Indicator Module

This module (BRD25GIB-F) has 8 switch and dual LED groups.

Each group can be associated to a single Zone.

The switch is used to disable the associated zone, while the LEDs are used to indicate the zone status. The
top LED is Red in colour and is used to indicate if the zone is in Alarm while the bottom LED is Amber and is
used to indicate both Fault (LED flashing) and Disable (LED steady).

Figure 87: Zone Disable & Indicator decal (See LAB1483.doc for Slip in Label)

C C
N N Top Card &
1 2 PCB Securing Clips
Address SW
In Out (See Note)
RS485 Control RS485 Control ON
1 2 3 4

/ 27VDC / 27VDC
Comms In Comms Out

Fit EOL Termination Link


if Last Module
on Comms Bus

Bottom Card &


PCB Securing Clips

Figure 88: Module Rear View showing connectors and Address Switch

 Note: See Section 17 for Addressing Details (SW1)

69
MAN2994-7

12.8 16 Way Input Board

The 16 Way Input Board (BRD25SIP) makes provision for 16 voltage free contacts to be terminated to 16
optically coupled inputs. Its application is primarily for the monitoring of controlled ancillary equipment or
to initiate an action / event due to a change of state from what is accepted as the norm.

 Note: These inputs are not monitored for faults.

0V 1 2 3 4 0V 5 6 7 8 0V 9 10 11 12 0V 13 14 15 16 0V
TB2 TB3 TB4 TB5 TB6 TB7 TB8 TB9

INPUTS 1 - 4 INPUTS 5 - 8 INPUTS 9 - 12 INPUTS 13 - 16

INPUTS INPUTS INPUTS INPUTS


0V 1 2 3 4 0V 5 6 7 8 0V 9 10 11 12 0V 13 14 15 16 0V
TB2 TB3 TB4 TB5 TB6 TB7 TB8 TB9

CN1 RS485 Control / 27VDC


Comms In

RS485 Control / 27VDC


CN2 Comms Out

ON
+ CN3 CN4
Fit EOL Termination
Link 1 if Last Module
ON
Address SW
- on Comms Bus 1 2 3 4 (See Note)

Not used optional 27V

Figure 89: Typical Input Wiring and Board Layout Front View showing connectors and Address Switch

Connections

Terminal/s Function
Taking note of the Common 0v
TB2 to 9 terminals connect the voltage free Inputs 1 to 16
contacts as shown above.

 Note: See Section 17 for Addressing Details (SW1)

70
MAN2994-7

12.9 8 Way Relay Board


The Relay Board (BRD25EWRB) provides 8 programmable relays with 30VDC 1 Amp voltage free change over
contacts for control or monitoring purposes and comes fitted for internal or external FACP use.

The functionality and programming of the relays is similar to the relays on the main board of the FACP. By
default the relays default to Common Alarm functionality.

All terminal points are protected.

The board switches the relays as determined by the panel. The relays can be controlled by:

➢ Zones Alarm
➢ Group Alarm
➢ Device Alarm
➢ Internal Output
➢ Panel Output
➢ Loop Output
➢ Panel Input
➢ Loop Input
➢ Reset – relay is activated for 3 seconds when reset depressed

12.9.1 Internal Relay Board


N/0 = Normally Open
COM = Common
N/C = Normally Closed
O/P 1
COM
N/0 O/P 2 O/P 3 O/P 4 O/P 5 O/P 6 O/P 7 O/P 8
N/C N/0 COM N/C N/0 COM N/C N/0 COM N/C N/0 COM N/C N/0 COM N/C N/0 COM N/C N/0 COM N/C

TB1 TB2 TB3 TB4 TB5 TB6 TB7 TB8

O/P 1 O/P 2 O/P 3 O/P 4 O/P 5 O/P 6 O/P 7 O/P 8


N/0 COM N/C N/0 COM N/C N/0 COM N/C N/0 COM N/C N/0 COM N/C N/0 COM N/C N/0 COM N/C N/0 COM N/C

TB1 TB2 TB3 TB4 TB5 TB6 TB7 TB8

CN1 RS485 Control / 27VDC


Comms In
CN2 RS485 Control / 27VDC
Comms Out Address SW
Fit EOL Termination (See Note)
+ CN4
Link 1 if Last Module ON
ON
CN3
- on Comms Bus
1 2 3 4

SW1

Not used optional 27VDC

Figure 90: Internal 8 Way Relay Board Front View showing connectors and Address Switch

Relay Connections

Terminal/s Function
N/O = Normally Open,
TB1 to 8 C = Common Relay 1 to 8
N/C = Normally Closed
 Note: See Section 17 for Addressing Details (SW1)

71
MAN2994-7

12.9.2 Remote Relay Board


In the remote version the Comms In and Out Terminal Block TB9 is cabled to the RS485 Comms terminal
block TB1on the Communications Extender Board (see section 5.12) and can be installed up to 1.2kms from
the FACP.

Note: Can be powered from the panel or an external 27 volt source.

N/0 = Normally Open


COM = Common
N/C = Normally Closed
O/P 1
COM
N/0 O/P 2 O/P 3 O/P 4 O/P 5 O/P 6 O/P 7 O/P 8
N/C N/0 COM N/C N/0 COM N/C N/0 COM N/C N/0 COM N/C N/0 COM N/C N/0 COM N/C N/0 COM N/C

TB1 TB2 TB3 TB4 TB5 TB6 TB7 TB8

O/P 1 O/P 2 O/P 3 O/P 4 O/P 5 O/P 6 O/P 7 O/P 8


N/0 COM N/C N/0 COM N/C N/0 COM N/C N/0 COM N/C N/0 COM N/C N/0 COM N/C N/0 COM N/C N/0 COM N/C

TB1 TB2 TB3 TB4 TB5 TB6 TB7 TB8

Fit EOL Termination


Link 1 if Last Module
on Comms Bus To TB3 on the Main Address SW
TB10 Card and/or Zone
(See Note)
+ - + - Mimic Card
O N ON
TB9 1 2 3 4
RS485+ SHD RS485+ SHD
RS485-
SW1
RS485-

RS485 COMMS IN / OUT

27 Volts In 27 Volts Out


(External Supply) (External Supply)

Figure 91: Remote 8 Way Relay Board Front View showing connectors and Address Switch

Relay Connections

Terminal/s Function
N/O = Normally Open,
TB1 to 8 C = Common Relay 1 to 8
N/C = Normally Closed

Communications Connections

Terminal Function
RS485+
TB9 RS485- Communications In
Shield
RS485+
TB9 RS485- Communications Out
Shield
Note: See Section 17 for Addressing Details (SW1)

72
MAN2994-7

12.10 8 Way Sounder Board

The Sounder Board (BRD25SOP) expands the number of sounders that can be used on an FACP by 8. Each
output is of a solid state design, rated at 24VDC / 750mA and requires a 10KΩ End of Line (EOL) resistor
regardless of whether or not a sounder is wired to the circuit.

The sounder board will switch ON the sounders as configured (output off, continuous or pulsed) at the FACP
and supervise the sounders for their open circuit, short circuit & line fault conditions.

Note 1: Sounder polarity MUST be observed.

10K EOL
Resistor

EOL EOL EOL EOL EOL EOL EOL

POWER
DC IN SOUNDER 1 SOUNDER 2 SOUNDER 3 SOUNDER 4 SOUNDER 5 SOUNDER 6 SOUNDER 7 SOUNDER 8
0V 27V +VE -VE +VE -VE +VE -VE +VE -VE +VE -VE +VE -VE +VE -VE +VE -VE

TB3 TB2 TB1

27V To Sounders 1 to 4 + / - To Sounders 5 to 8 + / -


- +
To Sounders 1 to 4 + / - To Sounders 5 to 8 + / -
POWER
DC IN SOUNDER 1 SOUNDER 2 SOUNDER 3 SOUNDER 4 SOUNDER 5 SOUNDER 6 SOUNDER 7 SOUNDER 8
0V 27V +VE -VE +VE -VE +VE -VE +VE -VE +VE -VE +VE -VE +VE -VE +VE -VE

TB3 TB2 TB1

CN1 RS485 Control


Comms In

CN2 RS485 Control


Comms Out Address SW
(See Note)
+ CN4
Fit EOL Termination ON ON

CN3 SW1
- Link 1 if Last Module
on Comms Bus
1 2 3 4

27VDC In 27VDC Out

Figure 92: 8 Way Sounder Board Front View showing connectors and Address Switch

Note 2: Maximum Current per Output: 750mA.

Note 3: A +27VDC external power supply feed is required

Note 4: In addition filtering and protection devices are used to reject transients.

Connections

Terminal/s Function
+ve
TB1 to 2 Sounder 1 to 8
-Ve
0V
TB3 Power DC IN
27V
Note 5: See Section 17 for Addressing Details (SW1)

73
MAN2994-7

12.11 4 Way Fire Fan Module

The Fire Fan Module (BRD25FCB) has four (4) separate fan controls each having an On, Auto and Off function
switch and a set of three (3) monitoring LED’s. The LED’s indicate the status of the equipment e.g. Run, Fault
or Stop. The two (2) arrow head buttons are used to step up and / or down through the three (3) conditions.
A slip in label can also be inserted into the hinged cover for identification purposes.

The “Plant Trip” Reset is used to locally restart plant and equipment that has been automatically shut down
because the FACP has initiated an alarm once that alarm has been cleared.

Figure 93: DEC2944-T1 4 Way Fire Fan Module (Slip in label fitted see LAB1486.doc)

In Out CN3
ON
C C
1 2 3 4

N N
1 2
Address
CN1 CN2 Switch
TERMINATOR
LINK Set to 1
CN2: Communications & 27V OUT
to Next Front Panel Card.
LK1 If Unsed the Termination Link Must be Inserted.

BRD25FCB4

CN1: Communications & 27V IN from CN2 off the previous


Front Panel Card or CN20 on the Main Control Board

PCB Securing Clips

Figure 94: 4 Way Fire Fan Module Rear View showing connectors and Address Switch

Note: The Fan Control module can also be used a Selector Switch & Indicator module. Refer to MAN3016
for details.

Note: See Section 17 for Addressing Details (SW1)

74
MAN2994-7

12.12 4 Way Fan Termination Board

The Fan Termination Board (BRD25FTB) interfaces between the Fire Fan Module and the plant/equipment it
controls via the 24 Volt 250mA Start, Stop, current limited, relay outputs and monitor inputs. Programmable
monitoring of the field equipment is achieved using 0 volts as an input level to indicate run, fault and stop
conditions of that equipment. Monitoring is programmed in the Function Menu for a 3, 4 or 5 Wire Start /
Stop, Run, Fault, Stop & Common functions. The inputs are protected by way of resettable transorbs and
resistive / capacitive networks.

Connections

TB2 – 5 Terminals Function


1 Start
2 Stop
3 Run
4 FLT
5 Stop
6 Com

FAN CONTROL FAN CONTROL FAN CONTROL


SOLID STATE OR SOLID STATE OR SOLID STATE OR
RELAY INTERFACE FAN MONITORING RELAY INTERFACE FAN MONITORING RELAY INTERFACE FAN MONITORING
STOP STOP RUN STOP RUN

RUN FLT

START START STOP START


STOP
COM COM COM

Cabling from FACP Cabling from FACP Cabling from FACP


to Plant / Equipment to Plant / Equipment to Plant / Equipment

+24V O/P INPUT 1 0V +24V O/P INPUT 1, 2 0V +24V O/P INPUT 1, 2, 3 0V

1 2 3 4 5 6 1 2 3 4 5 6

3 Wire Fan Control 4 Wire Fan Control 5 Wire Fan Control

Figure 95: 3, 4, 5 Wire Fan Control to Termination Board

FAN 1 FAN 1 FAN 2 FAN 2 FAN 3 FAN 3 FAN 4 FAN 4


START STOP RUN FLT STOP COM START STOP RUN FLT STOP COM START STOP RUN FLT STOP COM START STOP RUN FLT STOP COM
TB2 TB3 TB4 TB5

Termination to Control I/F


CN1 RS485 Control FAN "N" FAN "N"
Comms Out START STOP RUN FLT STOP C O M

TB2, 3, 4, 5

CN2 RS485 Control


Comms In Address SW
Fit EOL Termination
Link if Last Module (See Note)
0 V +27V

on Comms Bus
POWER

CN3 CN4 ON ON

SW1
1 2 3 4

27VDC In 27VDC Out

Figure 96: Fan Termination Board Layout and Typical I/O Wiring

Note: See Section 17 for Addressing Details (SW1)


75
MAN2994-7

12.13 Bargraph Display Card


The Bargraph display card (BDC) provides a smoke obscuration bargraph, alarm indicators, a reset and disable
facility for a Pro-Sens fitted with an Ampac version of an APID fitted.

The BDC supports two detectors, which can be located in the same Pro-Sens unit or separate Pro-Sens units.

12.13.1 Mechanical
The BDC is an a Add On, so can be mounted locally into a standard FACP into the cabinet door cut out (as per
SP1X, SP8X etc) or remotely using an enclosure

12.13.2 Front Panel Decal


The following is the propose decal for the BDC

Figure 97: Bargraph Display Card Decal

12.13.3 Front Panel Controls


RESET

This control is used to send a reset command to the linked (configured) APID device.

Note: This control does not reset the FACP.

DISABLE/ENABLE

This control is used to disable / enable the linked (configured) APID device.

Note: This control can’t be invoked if the system’s sounders (Alarm Devices) have not been silenced by
means of FACP’s ALARMS SILENCE/RESOUND key.

76
MAN2994-7

12.14 Communications Extender Board

The Communications Extender Board (BRD82LTB-C) is mounted inside the FACP and provides protected
RS485 communications and 27VDC to the SmartTerminal and other external modules.

CH16

+ - COM TB4 +24VDC


CN20 TB1 0V
RJ45 TO NEXT SmartTerminal
CN18
SHIELD +24V 0 V or LED MIMIC
CABLE
L2 L1
RS485 OUT
LOOP COMMS

SHIELDED COMMS CABLE


ZD3 TH1 TH2 ZD2 L6

RN20 RN17 C15 C12

BRD82LTB2
COMMUNICATIONS EXTENDER BOARD
27VDC
CN2
M1
CN3 IN OUT
M2

CN4 CN5
FACP MAIN
BOARD IN OUT TO AVAILABLE 27VDC
CONNECTOR (3 WAY)

Figure 98: Communications Extender Board PCB Layout

12.15 SmartTerminal
SmartTerminal connects to the FireFinder Plus Fire Alarm Control Panel (FACP) via the RS485
Communications Extender Board. Generally it is designed to be used anywhere where the status of the FACP
is required to be monitored by local personnel and limited control is required. It can also be tailored as a
Nurse Fire Station (NFS).

SmartTerminal has been designed for use with the FireFinder PLUS series of FACP’s.

➢ 4 line by 40 character LCD with backlight and navigation buttons   buttons allow the
SmartTerminal to be used for FACP operation and interrogation. Note: the backlight is
only energised when alarms are present, a key has been pressed or controls enable key
switch is enabled

➢ Buzzer and system Reset.

➢ System expansion capabilities / options:

➢ A wide range of secure user functions. This includes the ability to disable / re-enable a
large number of system functions.

➢ Flush or surface mountable enclosure.

➢ Controls have tactile and audible feedback of operation.

➢ All terminals cater for 2.5mm cables.

➢ Reports events from devices that are accessible to the host FACP. For example if the host
FACP is configured with global access then the connected SmartTerminal reports events
from all devices. If the host FACP is configured as local then the connected SmartTerminal
reports events from devices that are directly connected to the host FACP

77
MAN2994-7

12.15.1 Overview
SmartTerminal consists of two PCBs;

1. A Termination Board mounted in each SmartTerminal to protect and interface the RS485
communications and 27VDC supply to the LCD Board

2. BRD82ZICC – Control, LCD Communications and LCD Driver Board

Note: A maximum of 30 SmartTerminal’s / Nurse Fire Stations (NFS) may be connected to the
communications bus over a distance of approximately 1.2Kms. When fitting multiple SmartTerminals
consideration must be given to the 24V voltage drop due to cable loss and the need for external power supplies
for the SmartTerminals.

12.15.2 Mechanical

SmartTerminal is supplied in an ABS cabinet and consists of;

➢ The Main Card, with all controls and indicators mounted directly onto it
➢ 1 X Termination Board
➢ 2 X ABS door keys
➢ 2 X 003 Enable / Disable keys
➢ 2 X Jumper links
➢ 2A Power Supply ( only if internally powered )

Note: A Communications Extender Board will be required if the Comms Bus in the FACP is fully utilised and
/ or if one is not fitted.

The front door of the ABS version is locked by way of two clips on the right hand side of the cabinet. A special
locating key which has two raised pins that are inserted into the side of the cabinet unlocks the door.

DOOR RELEASE PINS


DOOR RELEASE PINS

Figure 99: ABS Door Key and Front Panel Add On Card Surround Release Clip

78
MAN2994-7

KNOCKOUTS
TOP ( x15 )
KEY HOLE KEY HOLE
BACK ( x 4 )
MOUNTING MOUNTING
HOLE HOLE

Q7 Q1 CN1

TB2 TB1 TB3 TB4


D25
U1
CN3 + - COM + - C OM +24V 0 V +24V 0 V
28/04/2006
BRD82ICC2-

CN2
RS485 RS485 24V 27V
DISCHARGE POINT
TOUCH HERE FIRST IN OUT IN OUT
LCD
R47 R45 R43

R12 R46 R42

D26

BRD82LTB2-
CONFIG
U2

SW27

CN5 CN1 LK1


U3 C9
U4
RN2

D35
D2 D3 D4 D5 D6 D7 D8 R13
RN1
C12
C13

LCDA Main
R44
DIAGNOSTIC R14
C15
RESET
BRD82LTB

U6
R15

U5

BZ 1 CN6 Control PCB SW28


C16
R16

C17
TH1
RN3 R19
U7

CAB2116
U8 C21 U9 C19
X1
U10 U11 RN4 C20
D17 C22 C23 D13 D9
KEYSWITCH Q2
R20

RN5

KEY HOLE
D21 D10
D18 D14
R34 R32 C36 C29 C26 C25

1
BRD82ICC
RN10
RN7

RN8

RN9

U12

CN8
8
3 2

D22
R23 PRINTER D29
CN7
7 6

U14 D19 D15 D11

CN7
MOUNTING
PWR LINK PWR LINK R30
4

5 Q3
Q4
LK1 D23 CN11 CN12

CN9 D20 R35


CN10
D16 Q5 D12
D24

U15

HOLE
Q6 D32 D31 RN13
D24

CN10 CN11 CN12

TECHNOLOGIES PTY LTD


TECHNOLOGIES PTY LTD
ORDER CODE
SERIAL NO
I/P VOLTAGE 27VDC
ORDER CODE
I/P CURRENT
ADDRESS
TESTED SERIAL NO
QA APPR
DATE OF MAN
CERTIFICATE OF
COMPLIANCE No. I/P VOLTAGE 27VDC 12 mm
N1236

I/P CURRENT
COMPLIANCE & ADDRESS R 6mm.
CONFIGURATION LABEL TESTED
QA APPR
DATE OF MAN
CERTIFICATE OF
COMPLIANCE No. FRONT DOOR HINGES
N1236

Figure 100: Typical Layout (Externally Powered) and Location of Keyholes

12.15.3 Installation & Cabling

SmartTerminal is connected to the FACP as shown below.

SHIELDED COMMS CABLE


Main Panel
TO NEXT SmartTerminal RS485 OUT
or LED MIMIC SHIELD
CN20 +24VDC
TB1 + - C OM TB4
RJ45 0V
CN18
+24V 0 V
CABLE L2 L1
LOOP COMMS

ZD3 TH1 TH2 ZD2 L6


COMMUNICATIONS
RN20 RN17 C15 C12
EXTENDER BOARD
BRD82LTB2

27VDC
CN2 CN3 IN OUT
M1
M2

FACP MAIN CN4 CN5


BOARD IN OUT TO AVAILABLE 27VDC
CONNECTOR (3 WAY)

RS485
OUT
RS485
IN +24V TO NEXT LCDA
MAXIMUM OF 30
VDC VDC 0V
IN OUT
TB2 TB1 TB3 TB4 TB2 TB1 TB3 TB4
+ - COM + - +24V 0 V +24V 0 V + - COM + - COM +24V 0V +24V 0V
COM
POWER IN POWER OUT RS485 IN RS485 OUT POWER IN POWER OUT
CN1
CN1

TO TO
BRD82LTB2-

LCD
BRD82LTB2-

03/05/2006

LCD
03/05/2006

LK1 NOT FITTED LK1 MUST BE FITTED TO SmartTerminal 2


THE LAST BOARD ON (IF FITTED)
SmartTerminal 1 THE COMMS BUS

TERMINATION BOARD No.1 ( BRD82LTB2 ) TERMINATION BOARD No.2 ( BRD82LTB2 )

Figure 101: Connecting SmartTerminal’s to the FACP

79
MAN2994-7

12.15.4 Setting the SmartTerminal Address


Open the front door; locate the “CONFIG” button situated on the left hand side of the PCB and press for 3
seconds. The buzzer and “Config” LED will double beep and flash respectively to indicate that the
Configuration mode has been entered.

The LCD will now display the Configuration screen. This screen consists of the code version number, current
address and four adjustment markers. These markers A-, A+, C-, and C+ are used to indicate the buttons that
adjust the address and LCD contrast.

Use the “PREVIOUS (A-) and NEXT” (A+) buttons to select the desired address. The default value for this
address is 255 which is not a valid SmartTerminal address. The user must then select an address value from
1 to 30, i.e. the same address as that set in the FACP. The buttons corresponding to C- (SILENCE BUZZER) and
C+ (RESET) are used in a similar manner to decrease and increase the LCD contrast level. There is audible
feedback for all button presses.

Once the address has been set press the “CONFIG” button again for 3 seconds and the screen will return to
its default and the “DIAGNOSTIC” LED will return to a slow flash. This slow flash indicates SmartTerminal and
the FACP are communicating normally i.e. the LED flashes if communications data is being received from the
FACP.

Note: If the address is not set within the time out period of approximately 75 seconds SmartTerminal will
return to its previous state.

80
MAN2994-7

12.15.5 Operation
The operation of SmartTerminal can be considered to be in one of three states, these are;

1. Power up - when the SmartTerminal is initialising

2. Normal - when the SmartTerminal address has been set and is communicating with the FACP,
reporting normal / abnormal conditions and controlling the FACP via the front panel controls

3. Fault where the SmartTerminal is in fault and/or is unable to communicate with the FACP.

Power Up

The LCD displays a message telling the operator SmartTerminal is being powered up and that the hardware
is being initialized. Once the hardware has been successfully initialized set the address and SmartTerminal
should automatically transition to the normal state. Should a failure occur on power up press the “RESET”
button located on the LCD PCB and check the address is correct.

Normal

The Normal state is entered from the “Power-up” or a return from the “Fault” state and is displayed on the
LCD if the SmartTerminal is communicating with the FACP and operating correctly. In this state the front
panel Power indicator is illuminated.

Fault

SmartTerminal enters the Fault state upon;

➢ A hardware failure

➢ LCD module failure or

➢ A loss of communications with the FACP (indicated by the “DIAGNOSTIC” LED – not
flashing and the “no communications “message being displayed)

In a Fault condition the front panel NORMAL indicator is extinguished and the details of the fault are displayed
on the LCD. The FACP will also indicate a fault in a similar manner.

Access levels

There are two levels of access.

Access level 1 - only the silence buzzer control is operative. All other controls operate in access level 2.

Access level 2 - is entered when the key-switch is in the ENABLED position.

81
MAN2994-7

12.15.6 SmartTerminal Controls and Indicators


All controls, except for the controls Enable / Disable Keyswitch, are of a momentary push button style and
operate in exactly the same way as does the FACP itself.

Figure 102: SmartTerminal Front Panel Layout

12.15.7 SmartTerminal Screen Format


There are 3 events that can be reported and displayed by SmartTerminal. The types of event are;

➢ Fire
➢ Faults and
➢ Disables.

The types of events are only associated with devices and detectors hence faults associated with modules,
loops O/C – S/C, power supplies and so forth are not reported on the LCD.

The SmartTerminal has front panel indicators for each type of event. When SmartTerminal is configured not
to report a type of event and that event type is present (and the corresponding front panel indicator is
illuminated on the SmartTerminal), then a standard information screen is displayed on the LCD stating the
system is not normal and the operator should see the FACP.

Alarm: If configured the screen format for reporting loop / device / zone fire condition is:

FIRE – ORIGIN:Zzzz RECENT:Zzzz TOTAL:XXX


-------------------------------------
Zzzz FIRE
<zone descriptor>
<date> <time> CONTROL*
ZONE FIRE XXX OF XXX DEVICE►
-------------------------------------

82
MAN2994-7

Fault: If configured the screen format for reporting loop / device / zone fault condition is:

Zzzz FAULT
<zone descriptor>
<date> <time> CONTROL*
FAULT XXX OF XXX DEVICE►

Note: The fault types only relate to devices.

In the event of a loss of communications, for a period of greater than 15 seconds the SmartTerminal will
default to the No Communications screen. The format for this screen is:

No Communication

Device Isolate / Disables: If configured the screen format for reporting loop / device / zone disable condition
is:

Zzzz DISABLED
<zone descriptor>
<date><time> CONTROL*
ZONE DISABLED XXX OF XXX DEVICE►

Pre-alarm: If configured the screen format for reporting loop / device / zone Pre-alarm condition is:

Zzzz PRE-ALARM
<zone descriptor>
<date> <time> CONTROL*
ZONE PRE-ALARM XXX OF XXX DEVICE►

83
MAN2994-7

Normal / Default: The format for reporting that everything is normal is:

<DATE> <TIME> ACCESS LEVEL:


1
<USER DESCRIPTOR LINE 1>
<USER DESCRIPTOR LINE 2>
<SYSTEM STATUS> <DAY MODE-MAN I/O>

The screen is only displayed when there are no alarms, fault or disables on the panel.

The highest priority current system status will be displayed and can be one of the following listed in order of
highest to lowest priority:

“SYSTEM ALARM”
“SYSTEM PRE-ALARM”
“SYSTEM FAULT”
“SYSTEM ISOLATE”
“SYSTEM NORMAL”

Config: The Config screen displays the following.

VX.X (software version number


Address

A- A+ C- C+

A - , A + : adjusts the address 1 to 30, 30 being the maximum number of SmartTerminal’s that can be
connected to the FACP, ( default is 255 which is not a valid address).

The function buttons as in the above screen A- A+ C- C+ perform the following;

A – Press “Previous” A+ press “Next”

C - C+: decreases [-] and increases [+] the LCD contrast level.

C – Press “Silence Buzzer” C+ Press “Reset”

84
MAN2994-7

12.16 Agent Release Control


Agent Release control consists of an Agent Release Module, Termination Board and an optional Local Control
Station.

12.16.1 Operation
Introduction

The Agent Release Module and Termination Board communicate with the FACP via the RS485 multi-drop bus.

The Local Control Station communicates only with the Termination Board via a separate RS485 bus. Up to 7
Local Control Stations can be connected to one termination board.

Agent discharge operates in two modes – automatic and manual. The manual mode is selected by pressing
the Inhibit switch on any Local Control Station. To indicate the system is in manual the Inhibit LED will be
illuminated. Pressing Inhibit again will toggle or return the mode to automatic and extinguish the Inhibit LED.

The “Agent Released” Pressure Switch (PSW) is wired to the PSW input on the Termination Board and is used
to confirm that the agent has been released. The circuitry involved in this process can be configured to accept
a normally open contact, normally closed contact, normally open mechanically operated (manual) or is
ignored (not fitted) and is selected via FACP on-site programming. If the mechanical (manually operated)
option is selected the module monitors the pressure switch input and provides notification the agent has
been released manually, initiates an alarm and illuminates the “Agent Released” indicator.

Manual Mode

When the system is in manual mode, then;

➢ The Local Control Station Inhibit indicator is lit at the FACP and all Local Control Station’s.
➢ The buzzer at all Local Control Stations will sound until the inhibit button is released.
➢ The System Inoperative output is turned on.
➢ The Automatic discharge sequences are prevented from starting.
➢ If an automatic discharge sequence was underway and the inhibit switch is activated
(switched to manual mode) the discharge sequence is aborted and the sequence is reset.
This means the Stage 1 and Stage 2 outputs are switched off.
To manually discharge the agent the “ Lock Off Valve “ must be open and the Manual Release switch on the
Local Control Station pressed. The manual discharge sequence is;

➢ Manual Activation indicator is lit on the FACP and Local Control Station.
➢ The FACP activates its brigade alarm output.
➢ Stage 1 outputs are switched to +24VDC. (FIRE ALARM sign illuminated, aural alarm
sounds)
➢ Stage 2 outputs are switched to +24VDC. (FIRE ALARM, EVACUATE & DO NOT ENTER signs
illuminated, aural alarm sounds).
➢ The optional pre-release start delay is activated (Selected via FACP on-site programming);
time out and an ON Interlock signal will then operate the selected release circuitry.
➢ The Agent Discharge LED on the Agent Release Module and Local Control Station will
illuminate when the Pressure Switch input on the Termination Board is activated.
➢ Activate gas-fired output.

Note: The Interlock Input can be defaulted to the on position by placing a 10K EOL termination resistor
across the terminals TB2. 7 / 8 of the Agent Release Module and Local Control Station.
85
MAN2994-7

Auto Mode

Automatic discharge is when one or two zones going into alarm initiate the agent discharge sequence.

Note: A “manual release” can still be initiated in “auto mode” but the LCS “Inhibit” control WILL NOT inhibit
/ abort the agent release sequence.

Single Zone Activation, the following discharge sequence is executed;

➢ Automatic Activation LED is illuminated on the Agent Release Module and Local Control
Station.
➢ Stage 1 outputs are switched to +24VDC. (FIRE ALARM sign illuminated, aural alarm
sounds).
➢ Stage 2 outputs are switched to +24VDC. (FIRE ALARM, EVACUATE & DO NOT ENTER signs
illuminated, aural alarm sounds).
➢ Optional pre-release delay is started (Selected via FACP on-site programming).
➢ The delay times out and if the Interlock signal is ON, the selected circuit will activate.
➢ The Pressure Switch field input on the Termination Board is activated and the Agent
Discharge LED on the Agent Release Module and Local Control Station will be illuminated.
➢ Activate gas-fired output.

Dual Zone Activation, if the first zone goes into alarm the following steps are initiated;

➢ The automatic activation LED on the Agent Release Module and Local Control Station will
flash.
➢ Stage 1 outputs are switch to –24VDC. [FIRE ALARM sign illuminated, aural alarm sounds].

When the second zone goes into alarm, then the following steps occur;

➢ Automatic activation LED goes steady.


➢ Stage 1 outputs are switched to +24VDC. (FIRE ALARM & EVACUATE signs illuminated,
aural alarm sounds)
➢ Stage 2 outputs are switched to +24VDC. (DO NOT ENTER sign illuminated)
➢ Optional pre-release delay commences (Selected via FACP on-site programming).
➢ The delay times out and if the Interlock signal is on the selected circuit will activate.
➢ The Pressure Switch field input on the Termination Board is activated and the Agent
discharge LED on the Agent Release Module and Local Control Station will be illuminated.
➢ Activate gas-fired relay output.

Service Switch

The service switch is situated on the Agent Release Module when activated causes the following;

➢ Electrically isolates the activation circuitry from the agent release device.
➢ Operates the System Inoperative output.

Note: The service switch is NOT overridden by a manual discharge.

86
MAN2994-7

Lock-Off Valve

When the manual lock-off valve is operated;

➢ The agent is blocked from reaching the release valve.


➢ The lock-off valve inhibit indicator LED’s on the Agent Release Module and Local Control
Station are illuminated.
➢ The system inoperative output operates.

Fault Monitoring

Fault conditions are initiated by:

➢ The Pressure Switch monitoring circuit.


➢ The Low Pressure Switch monitoring circuit.
➢ The Lock-off Valve monitoring circuit.
➢ Activation circuitry.
➢ Stage 1 outputs. (Aural & visual discharge alarms).
➢ Stage 2 outputs. (Aural & visual discharge alarms).
➢ A Zone Fault.
➢ A Fault on the interlock input.
➢ A Fault with a LCS.

Note #1: The common fault indicator on the Agent Release Module and Local Control Station is
illuminated for any Fault condition.

Note #2: For a pressure switch fault, low pressure switch fault, lock-off valve fault, stage 1 output
fault, stage 2 output fault and interlock fault, the FACP will signal the brigade.

Note #3: When there is a fault in the activation circuit or in the trigger zones, in addition to the above,
the system inoperative output is operated.

Note #4: The FACP fault buzzer will sound for all faults.

Note #5: The FACP will report the type of fault on the LCD.

Isolation

If a trigger zone is isolated at the FACP the trigger zone isolated indicator at the Agent Release Module and
Local Control Station is illuminated, and the system inoperative output is operated.

System Inoperative Output

The system inoperative output is switched to +24VDC under the following conditions;

➢ Operation of the Service Switch.


➢ A Fault in the selected trigger circuit.
➢ Operation of the Lock-off valve.
➢ Operation of the Inhibit at an Local Control Station.
➢ A Fault in any of the activation zones.
➢ If any of the activation zones are isolated.
87
MAN2994-7

Manual Mechanical Release of the Agent

With agent release systems, a manual mechanical means can be provided to release the agent.

If the pressure switch is activated (indicating that the agent has been released), and the agent release module
has not activated the selected activation circuit, then the following will occur:

➢ Stage 1 output is switched to +24VDC and stage 1 relay is output closed


➢ Stage 2 output is switched to +24VDC and stage 2 relay output is closed
➢ Light the agent release led on the ACC and LCS’s
➢ Activate gas-fired relay output

Monitoring of the Pressure Switch

Due to the requirements of Manual Mechanical Release of the Agent, the pressure switch input conveys two
pieces of information:

When the pressure switch input is active, it signals that the agent has been released. The release can be as a
result of the agent release module or due to a manual mechanical release.

When the pressure switch is not active, it signals that there is a full bottle of agent available to be discharged.

In order for the agent release module to respond to a manual mechanical release, the pressure switch must
have been previously not active, to signify that a full bottle of agent is available

88
MAN2994-7

12.16.2 Agent Release Module


The Agent Release Module controls and monitors all the requirements for agent release.

C C EOL
N N TERMINATOR
LINK
Top Module & PCB
1 2 Securing Clips
LK1
In Out ADDRESS
Fit EOL Termination SWITCH
S W2
Link 1 if Last Module

ON
1 2 3 4
on Comms Bus INHIBIT
LK2

+
RS485 Control RS485 Control SWITCH MON
DISABLE
/ 27VDC / 27VDC
Comms In Comms Out

MANUAL
RELEASE
TB4

AGENT RELEASE
MCP

10K
EOL

Figure 103: Exploded View of Module and Front Panel Layout

The PCB is fitted with two 2 x RJ45 connectors CN6 & 7 for power (27VDC) and communications (RS485) for
communications between the Agent Release Module and the FACP Main Control Board.

Controlled Access

It is a requirement that control be secured from unauthorised use. A keyswitch has


therefore been included in the control process.

The FCP goes into service mode when the keyswitch is switched to SERVICE INHIBIT. This results in the
selected agent activation circuit being electrically isolated and a Common Isolate condition being indicated
at the FACP. This condition can also be confirmed through the Status Menu. To remove the key it is necessary
for the switch to be in the OFF position.

Pressing Select toggles the selection of either the Main or Reserve release agent. Selection is
indicated by the Main and Reserve Agent LED’s

89
MAN2994-7

Pressing the Agent Inhibit switch will inhibit the gas from release in either the Manual or
Automatic mode. The Agent Inhibit switch has an internal lamp fitted with yellow lens and is illuminated
when the Inhibit switch is activated at the FACP or any of the LCS’s. To prevent accidental operation this
switch has a hinged clear plastic cover that has to be raised to access the switch.

90
MAN2994-7

12.16.3 Local Control Station


The Local Control Station is supplied fitted into an IP40 rated enclosure and has the same indicators and
Manual Release switch as the Agent Release Module within the Fire Alarm Control Panel (FACP) but no Agent
Select button or Service Inhibit keyswitch.

The Comms line is RS485 and is cabled to the Agent Termination Board.

The Interlock is a monitored input with 10KΩ EOL. This input is used to determine if air conditioning dampers
and doors are closed but can be defaulted to the “ON” condition by terminating the input with a 2K2Ω EOL.

Double action switching is achieved by way of protective lift up covers seen here and manual operation of the
MCP or Inhibit switch. To ensure correct operation and prevent accidental release of the agent these covers
should not be disabled for any reason

Figure 104: Local Control Station

ENCLOSURE

CONTROL
PANEL

SURROUND

MCP

STANDOFFS KNOCKOUTS BACK


TOP AND SIDES

8 X ENCLOSURE MOUNTING HOLES

Figure 105: Local Control Station Layout

LCS Operation & Controls


Lifting the cover and pressing the MCP starts the manual agent release sequence. This two action safety
feature prevents any accidental operation of the control and should not be disabled.

91
MAN2994-7

Agent Release / LCS Indicators

There are 12 indicators on both the Agent Release Module and Local Control Station. They are;

MANUAL
ACTIVATION (Red) Illuminated when a manual release sequence has commenced. A Manual release
sequence can only be started by activating the manual release at the FACP or LCS.

The indicator is extinguished by activating RESET on the FACP.

MANUAL
ACTIVATION (Red) Illuminated when a manual release sequence has commenced. This occurs when
the selected zone(s) on the FACP have gone into alarm. For dual zones, the indicator should flash when the
first zone goes into alarm, and steady when the second zone goes into alarm.

Indicator is extinguished by activating RESET on the FACP.

AGENT
DISCHARGED (Blue) Illuminated when the pressure switch indicates the agent has been released. For
Pyrogen, feedback is from the thermal switch. If there is no pressure switch fitted, the indicator shall be
illuminated immediately the agent release signal is activated (Selected via FACP on-site programming – refer
to relevant FACP Manual)

The indicator is extinguished by activating RESET on the FACP.

LOCK OFF
VALVE INHIBITED (Yellow) Illuminated when the lock-off valve has been activated.

STAGE 2
TIMER RUNNING (Yellow) Illuminated when the pre-discharge delay timer is running.

The indicator is extinguished by activating the RESET control on the FACP.

AGENT CIRCUIT
FAULT (Yellow) Illuminated when there is a fault on the monitored Main or Reserve activation
circuits e.g. S/C or O/C.

AGENT LOW
PRESSURE (Yellow) Illuminated when the low pressure switch is activated. This indicates a leakage
at the agent cylinder. The low pressure switch is a separate switch.

92
MAN2994-7

TRIGGER ZONE
ISOLATED (Yellow) Illuminated when any of the programmed trigger zones on the FACP are
isolated.

COMMON FAULT
(Yellow) Illuminated under the following fault conditions;

➢ pressure switch monitoring fault,


➢ low pressure switch monitoring fault,
➢ lock-off valve monitoring fault,
➢ activation circuit fault,
➢ stage 1 output fault,
➢ stage 2 output fault,
➢ LCS fault (missing or extra),
➢ trigger zone(s) fault,
➢ low agent pressure and interlock fault.

INTERLOCK
(Yellow) Illuminated when the interlock input (e.g. from dampers, doors etc) is off
during the discharge sequence – meaning the dampers, doors etc are not closed as they should be or a fault
exists. The “Interlock” is overridden after 10 seconds and the agent is released

Note: The Interlock is a Monitored Input and can be defaulted to the ON position by terminating the input
(TB2 7 & 8) into a 2K2 resistor.

INITIAL AGENT
(Yellow) Illuminated when the “Initial Agent” is selected.

RESERVE AGENT
(Yellow) Illuminated when the “Reserve Agent” is selected.

Local Control Panel Inhibit

The agent inhibit switch has an internal lamp fitted with yellow lens. Illuminated when the inhibit switch is
activated at the FACP or any of the LCS’s.

93
MAN2994-7

Buzzer (located at the FACP)

The Buzzer sounds;

➢ Under all fault conditions and can be silenced by using the appropriate FACP buzzer
silence control.
➢ When the LCS Inhibit control is activated – after 8 hours – treated as an isolate condition.
➢ When the service inhibit is activated - after 8 hours – treated as an isolate condition

Connecting the LCS to the Agent Termination Board

1. ISOLATE THE AGENT


2. Check the FACP is functioning correctly then power down
3. Connect the LCS to the Agent Termination Board within the Fire Alarm Control Panel and
Interlock as shown below. If applicable take into consideration warning signs at this point
4. Insert the link LK1 onto the last LCS in the chain. If un-used place the link onto one of the LK1
pins
5. Set the address of the LCS,
6. Power up the system and program the FACP for the addition of the LCS
7. Check the FACP is functioning correctly and test
8. De-isolate the Agent

 CAUTION - TO PREVENT ACCIDENTAL AGENT RELEASE DO NOT DE-ISOLATE THE AGENT UNDER ANY
CIRCUMSTANCES UNTIL THE SYSTEM AS A WHOLE IS FUNCTIONING CORRECTLY

CN5

EOL
TERMINATOR
LINK JTAG
ON
1 2 3 4

ONLY USED ON THE LAST


LCS ON THE COMMS BUS
LK1 BRD25ARB5-

Address 2
Switch
Set to 1 S W2
ON
ON

1 2 3 4
1 2 3 4

1
LK2 2
+ INHIBIT 3
Local Control Station T1 CN1
SWITCH MON.
DISABLE
4

MANUAL HOLD/
AGENT
3
INHIBIT
ON
1 2 3 4

MANUAL RS 485 IN RS 485 OUT INTER- 4


+ - + LOCK -
+24V 0 V +24V 0 V RELEASE
-
COM COM
+

TB1 TB4 TB2

+
-

+27VDC OUT
SCRN

+27VDC IN FROM
TERMINATION BRD. TO NEXT LCS INTER
SIG

10K 2K2
SIG

LOCK
EOL
10K INSERT A 2K2 ACROSS
EOL THE 10K EOL TO
DEFAULT TO "ON"
Agent Termination Board TB1
within the FACP
+ 27V 0 V RS 485 COMMS BUS

Figure 106: PCB Layout & Cabling Details

Note 1: Dipswitch No 4 on SW2 when set to “ON” activates the alternate buzzer feature where the buzzer
will sound for 5 seconds every 30 minutes when the LCS Inhibit button is activated.

94
MAN2994-7

12.16.4 Agent Release Termination Board

22K

22K

22K

10K

10K
LCS CABLE INPUTS GAS SYST. STAGE1 STAGE2 RELEASE
0VDC SIG+ + L.PSW- MAIN RESV
+24VDC SCRN SIG- + PSW - + LOCK- N/0 COM + - + - N/0 C O M + - N/0 C O M + - + -
TB1 TB2 TB3 TB4 TB5 TB6 TB7

MONITORED FIRED INOP + - Outputs are Monitored


C
N RS485 Control
1 Comms In

C RS485 Control
N Fit EOL Termination
2
Comms Out
Link 1 to Last Module
on Comms Bus
ON
CN3 CN4
1 2 3 4 SW1 Address Setting

Optional 27VDC In

Figure 107: Agent Termination Board PCB Layout

The Agent Termination Board interfaces to;

1. The FACP via CN1, CN2 continuing the RS485 communications bus if required. LK1 is inserted if
this is the last backpan board on the bus.
2. LCS’s (up to 7) via TB1. LK1 is inserted in the last board in the RS485 Bus
3. Monitored Inputs: via TB2. (EOL Resistance 22K, Series Resistance 4K7)
i. Pressure Switch (PSW) agent released
ii. Low Pressure Switch (LPSW) agent storage cylinder pressure has dropped to a pre-
determined level; and
iii. Interlock, the manual lock-off valve has been operated.
4. Gas Fired: Output via RL2 N/O contacts rated at 1A @ 24VDC wired to TB3. Used to indicate to
other monitoring devices the agent has been released.
5. System Inoperative: via RL1 N/O contacts rated at 1A @ 24VDC wired to TB4. Used to warn by
way of signage / audible alarm and/or monitoring that the system is inoperative.

Note: The “System Inoperative” output will operate (turn on) when all zones or groups used in the
Activation columns are "Disabled" or in "Fault".

When “Dual activation” is used, 50% or more of the configured Activation columns are “Disabled” or in “Fault”
the “System Inoperative” output will operate.

6. Stage 1: Output; initiates the visual and audible Fire Alarm and Evacuate warnings.

i. Monitored; via RL4 C/O contacts wired to TB5 1 & 2 (EOL required 10K) and
ii. Un-monitored; via RL5 N/O contacts wired to TB5 3 & 4.

95
MAN2994-7

7. Stage 2: output; initiates the visual and audible Fire Alarm and Do No Enter warnings

i. Monitored; via RL6 C/O contacts wired to TB6 1 &2; (EOL required is 10K) and
ii. Un-monitored; via RL3 N/O contacts wired to TB6 3 & 4

8. Release: Main actuating circuit, monitored (10KΩ EOL required) via TB7 1 & 2 (2A current
limited),

9. Release: Reserve actuating circuit, monitored (10KΩ EOL required) via TB7 3 & 4 (2A current
limited)

Note 1: Metron Igniters - (max of 10 – a series 2watt 18 resister must be added to the circuit)

Note2 : Solenoid valve - (max current of 2 amps & 27VDC)

96
MAN2994-7

12.16.5 Interface Wiring


Monitored Inputs TB2 1 & 2

Solenoid & Metron

This input relies on N/O or N/C relay contacts used in conjunction with 22K EOL and 4K7 series resistors.
The type of agent release mechanism and contacts used has to be set in the Programming Menu for the input
to function as per the manufacturers specifications and be in accordance with the relevant Standard.
Note: The PSW, LPSW & the Interlock Mechanisms are all
mounted onto the top of the cylinder containing the Agent
Agent
10K EOL Distribution 22K EOL
4K7
To TB7 22K
Solenoid MAIN or EOL 4K7
RESERVE 22K EOL
+ - + - Release
TB7
Termination 4K7
MAIN RESV Board
+ - + - + -
MAIN / RESERVE Agent
RELEASE
PSW LPSW LOCK

Figure 108: Solenoid, Metron PSW, LPSW and “LOCK” TB3 Wiring

LPSW & Lock

These inputs are also monitored and should be wired as shown above

RL2A TB3 1
To Monitoring
* Interface / Device
= MOV 2
* 35V *
0V

Figure 109 Gas Fired Wiring

TB4 1 +
RL1A To Sys
System Inoperative

Inop Mon
+27V Current
Limited to1A 0V 2
-

Figure 110: System Inoperative Wiring

As can be seen from above the;


1. Gas Fired Output can be wired to any interfacing or 1A monitoring circuit that requires a closed
relay contact to indicate a change of state. This could be a relay or a solid state device.
2. System Inoperative Outputs 27V @ 1A to supply interfacing, signage and aural alarms to indicate
the system has been taken out of service or has developed a fault.

Stage 1, Stage 2
TB5 / 6
Stage 1 or Stage 2
+ve 1 +(-)
RL4A RL6A 10K
-ve * 2
1 or 2 Way
Signage

RL4B RL6B EOL


-(+)
3
RL5A RL3A
To audible / visual
* 4 device or interface
*
The above circuitry applies to both * = MOV
35V
TB5 ( Stage 1 ) and TB6 ( Stage 2 ) 0V TB5 = Stage 1
TB6 = Stage 2
Termination Board Relays

Figure 111: Stage 1 & 2 Wiring


97
MAN2994-7

12.16.6 Warning Signs


Introduction

The Ampac Warning Signs provide clear, visual and audible indication of an alarm event and are designed for
use with fire detection and alarm systems which may incorporate agent release capability. The display may
also be customised as required to cater for a variety of applications.

The Warning Signs are available in two standard formats, the 4210-0110 for semi-flush or surface mount
indoor applications while the 4210-0120 affords IP65 weatherproof capabilities.

The Warning Signs incorporate a split level design that enables two text messages to be independently
controlled through the application of input voltages. The two levels may be activated by either a voltage
reversing DC input or through application of a common positive and two switched negative DC inputs.

Option switches located inside the unit enable the commissioning engineer to further configure the Warning
Sign for continuous or flashing Red or Yellow LEDs, enable an integral buzzer in continuous or pulsing mode
of operation, to enable a mute facility to silence the buzzer and or optional external sounder. A facility to
synchronise the flashing between multiple signs is also provided.

Illuminated using high efficiency, high intensity LEDs to greatly reduce power consumption and reliability
ensures that the brightness is maintained even when running on depleted stand-by batteries.

Specifications:

Operational Voltage 17 to 27VDC


At 24VDC 50mA Stage 1
Power Consumption Continuous
At 24VDC 100mA Stage 2 (100mA Muted)
IP30 195mm (H) x 325mm (W) x 50mm (D)
IP Ratings
IP65 212mm (H) x 338mm (W) x 67mm (D)
-20˚C to +55˚C Dry heat
Environmental
+40˚C @ 0 to 93% Relative Humidity

Installation (4210-0110 enclosure)

Open the outer door using the plastic key device provided. Using the back box as a template, mark the
position of the four fixings in the required position on the mounting surface. For semi-flush fixing
applications, cut a hole in the mounting surface to the dimensions shown below ensuring adequate depth is
provided for the unit to be recessed.

Figure 112: Enclosure Dimensions


98
MAN2994-7

Before fixing the unit decide which entry points are to be used for the in-coming cables. The back box has 7
20mm knockouts in the top and bottom which can be easily removed by sharply tapping them with a blunt
instrument and small hammer.

Top entry is recommended on this product however, back entry can be achieved by drilling additional holes
in the back box to suite. Fix the back box to the mounting surface using 4 appropriate sized bolts or screws
and install the acrylic text fascia plate using the 6 screws provided.

Installation (4210-0120 - weatherproof enclosure)

The weatherproof enclosure should be surface mounted using appropriate fixings and sealing washers.

1. Using the 6x outer screws, remove the clear Perspex lid.


2. Using the 4x black dome nuts, remove the text legend fascia plate bezel.
3. Remove the internal printed circuit board using the 2x screws located in the centre of the PCB.
4. Drill 4 x 4mm fixing holes in the rear of the back box near each corner and fix the back box to
the wall using appropriate fixing screws or bolts. Ensure that a watertight seal is maintained
around the fixing holes.
5. Re-instate the printed circuit board and fit the acrylic text legend to the fascia plate bezel using
the 6x M4 nuts provided.
6. It is recommended that the fascia plate bezel complete with acrylic text legend should be re-
instated following initial testing of the system.

Cabling

The maximum size of cable that the terminals will accommodate is 2.5mm². The interconnecting external
cables should be connected to the back box using suitable cable glands. On the 4210-0120 back box,
waterproof lock-tight glands should be used to ensure a weatherproof seal is maintained. Ensure that cable
tails of sufficient length are maintained to reach the terminals without cutting across the front surface of the
internal printed circuit board as this will impair the illumination of the sign.

The Warning Sign can be configured to illuminate in two ways. For voltage reversal, 2 wire applications and
for use with the Ampac Agent Release module, refer figure 1. For common positive, switched negative 3 wire
applications, refer figure 2.

Setting the Configuration Switches

The Warning Sign can be configured to operate in a variety of ways using SW2 8 way DIL switches located on
the printed circuit board.

Operational LED Colour Selection SW1 - Red or Yellow and should be set to suit the application of the Warning
Sign.

Operational Functionality SW2 - Table 1 outlines the functionality of the on-board switches located at SW2,
switches 1 - 8.

99
MAN2994-7

Table 1

Switch Off On
1 Level Two Extinguished for Stage 1 Level Two Illuminates for Stage 1 Input.
Input.
2 Level One Illuminates for Stage 2 Level One Extinguished for Stage 2 Input.
Input
3 Level 1 LEDs Constant Level 1 LEDs Flashing
4 Level 2 LEDs Constant Level 1 LEDs Flashing
5 Internal Buzzer Disabled Internal Buzzer Enabled
6 Buzzer Continuous Buzzer Pulsing
7 External Mute Input Enabled External Mute Input Disabled
8 Output Synchronizing Disabled Output Synchronizing Enabled (enable on first sign
only)

Cabling

TB2 (Buzzer / Sounder Mute)

MUTE - Normally Open (N/O) contacts with momentary push button switch (Optional)

INPUT

TB1 ( Single pair polarity reversing / 2 Stage Input )


Stage 1 ( Level 1 ) Minus ( - ) Positive ( + ) 24VDC
Stage 2 ( Level 2 ) Positive ( + ) Minus ( - ) 24VDC

Testing

Ensure the;

1. cabling is correctly wired to the Warning Sign .

2. sign is configured for purpose

3. AGENT IS ISOLATED and test from the Agent Release Module.

100
Momentary Push Button
Silence Buzzer / Sounder
Agent Release Board Input
To Next Warning Sign

+
10K If multiple signs are used

-
TB5 (Maximum 6) fit 10K EOL
Stage 1 to last sign
Output
Voltage Reversal

N/O COM
2 Wire BiPolar
Stage 1 Stage 2 Sounder
Stage 1 (Level 1) = - + - +
(+) POS
+ -
Stage 2 (Level 2) = + - (-) POS

INPUT SOUNDER/ OUTPUT SOUNDER


FROM BUZZER TO OUTPUT
D1 D2 D3 D4
FIRE MUTE NEXT
PANEL INPUT SIGN
D5 D6 D7 D8

TB1
TB2
TB3
TB4

DC+
ST1
ST2
DC+
ST1
ST2
DC+
ST1
ST2
VOLTAGE REVERSING
2 WIRE SOUNDER CONNECTION

TB4
DC+
ST1
+
SOUNDER
ST2

WARNING SIGN
BRD42WSB1-
D22
02/04/13 POLARISED (VANTAGE)
D20 D21 D23 D24
3 WIRE SOUNDER CONNECTION
D27
N1236
D25 D26 D28 D29
TB4
DC+
+
ALERT
ST1 SOUNDER
EVAC
ST2

LEVEL 1 WARNING SIGN

2 WIRE SYSTEM CONNECTION


LEVEL 2 10K
+ EOL
YELLOW RED -

STAGE 1
D31 D34 OUTPUT
D32 D33 D35
TB1
TB3
TB1
TB3

AGENT
D40
DC+
ST1
ST2
DC+
ST1
ST2
DC+
ST1
ST2
DC+
ST1
ST2

D37 D38 D39 RELEASE D41


SW1 SYSTEM (CIE)
IN OUT IN OUT
SW2 SW. OFF ON SIGN 1 SIGN 2
1
1 LEVEL 2 OFF FOR STAGE 1 INPUT LEVEL 2 ON FOR STAGE 1 INPUT 3 WIRE SYSTEM CONNECTION
2
3 2 LEVEL 1 ON FOR STAGE 2 INPUT LEVEL 1 OFF FOR STAGE 2 INPUT +24V DC
3 LEVEL 1 LEDs CONSTANT LEVEL 1 LEDs FLASHING -ve
4
-ve
5 4 LEVEL 2 LEDs CONSTANT LEVEL 2 LEDs FLASHING
6 5 INTERNAL BUZZER DISABLED INTERNAL BUZZER ENABLED
TB1
TB3
TB1
TB3

7
6 BUZZER CONTINUOUS BUZZER PULSING
DC+
ST1
ST2
DC+
ST1
ST2
DC+
ST1
ST2
DC+
ST1
ST2

8 BZ1
7 EXTERNAL MUTE INPUT ENABLED EXTERNAL MUTE INPUT DISABLED IN OUT IN OUT
+

8 SYNCHRONIZING OUTPUT DISABLED SYNCHRONIZING OUTPUT ENABLED* SIGN 1 SIGN 2

D45 *SET ON FIRST SIGN IN LINE ONLY D46 D47 D48

D49 FOR FURTHER INFORMATION D50 D51 D52

Figure 113: Two Wire Voltage Reversing Connection (Ampac Agent Release Module)
PLEASE REFER TO WWW.AMPAC.NET BZ2
MAN2994-7

101
Momentary Push Button
Silence Buzzer / Sounder To Next
Input Warning Sign Conventional 3 wire
+24 Volts DC Sounder - Vantage
Level 1 -ve 1 (-) EVAC
2 (-) EVAC
Level 2 -ve
3 (-) ALERT
4 (-) ALERT
5 (+) POS
6 (+) POS

INPUT SOUNDER/ OUTPUT SOUNDER


FROM BUZZER TO OUTPUT
D1 D2 D3 D4
FIRE MUTE NEXT
PANEL INPUT SIGN
D5 D6 D7 D8

TB1
TB2
TB3
TB4

DC+
ST1
ST2
DC+
ST1
ST2
DC+
ST1
ST2
VOLTAGE REVERSING
2 WIRE SOUNDER CONNECTION

TB4
DC+
ST1
+
SOUNDER
ST2

WARNING SIGN
BRD42WSB1-
D22
02/04/13 POLARISED (VANTAGE)
D20 D21 D23 D24
3 WIRE SOUNDER CONNECTION
D27
N1236
D25 D26 D28 D29
TB4
DC+
+
ALERT
ST1 SOUNDER
EVAC
ST2

LEVEL 1 WARNING SIGN

2 WIRE SYSTEM CONNECTION


LEVEL 2 10K
+ EOL
YELLOW RED -

STAGE 1
D31 D34 OUTPUT
D32 D33 D35
TB1
TB3
TB1
TB3

AGENT
D40
DC+
ST1
ST2
DC+
ST1
ST2
DC+
ST1
ST2
DC+
ST1
ST2

D37 D38 D39 RELEASE D41


SW1 SYSTEM (CIE)
IN OUT IN OUT
SW2 SW. OFF ON SIGN 1 SIGN 2
1
1 LEVEL 2 OFF FOR STAGE 1 INPUT LEVEL 2 ON FOR STAGE 1 INPUT 3 WIRE SYSTEM CONNECTION
2

Figure 114: Polarised 3 Wire Connection


3 2 LEVEL 1 ON FOR STAGE 2 INPUT LEVEL 1 OFF FOR STAGE 2 INPUT +24V DC
3 LEVEL 1 LEDs CONSTANT LEVEL 1 LEDs FLASHING -ve
4
-ve
5 4 LEVEL 2 LEDs CONSTANT LEVEL 2 LEDs FLASHING
6 5 INTERNAL BUZZER DISABLED INTERNAL BUZZER ENABLED
TB1
TB3
TB1
TB3

7
6 BUZZER CONTINUOUS BUZZER PULSING
DC+
ST1
ST2
DC+
ST1
ST2
DC+
ST1
ST2
DC+
ST1
ST2

8 BZ1
7 EXTERNAL MUTE INPUT ENABLED EXTERNAL MUTE INPUT DISABLED IN OUT IN OUT
+

8 SYNCHRONIZING OUTPUT DISABLED SYNCHRONIZING OUTPUT ENABLED* SIGN 1 SIGN 2

D45 *SET ON FIRST SIGN IN LINE ONLY D46 D47 D48

D49 FOR FURTHER INFORMATION D50 D51 D52


PLEASE REFER TO WWW.AMPAC.NET BZ2
MAN2994-7

102
MAN2994-7

12.17 Occupant Warning Systems


The OWS system is intended to broadcast information (voice announcements for emergency purposes, alert
signals, evacuate signals, visual and tactile warning devices) to provide warning to the occupants within one
or more specified areas in an emergency, to effect a rapid and orderly mobilisation of occupants in an indoor
or outdoor area.

This OWS system consists of the Amplifier (25W, 50W, 120W, 250W and 500W variants) and a Front Panel
Switch and Indicator Card.

The amplifier communicates to the Front Panel Switch & Indicator via a CAN protocol, where input events
are received from the Front Panel Switch & Indicator board and feedbacks are returned to it.

The Front Panel Switch & Indicator communicates to the FACP via the FACP’s internal RS485 communications
bus.

Below are some of the features the OWS contains. For detailed specifications and functional information
refer to MAN3072 OWS Technical Manual.

12.17.1 Amplifier Board (25W and 50W)

The Amplifier features 4 digital inputs, 3 relay outputs (1A), a strobe output and a 100V line output.

Figure 115: Amplifier Board

103
MAN2994-7

The Digital input functions are as follows:

Active high input. Tie to 24V to activate


Input (non-latching); 10kΩ load opens on fault;
Bell Input (FIB)
1(+/-) (Connect to FireFinder and ZoneSense Plus
FACP’s Warning System Output)
Reset or Evacuate Active low input. Short to 0V to activate
Input 2
(Default = Reset) (non-latching).
Silence or Alert Active low input. Short to 0V to activate
Input 3
(Default = Silence) (non-latching).
External Fault or Custom Tone
Active low input. Short to 0V to activate
Input 4 400/450Hz @ 0.5Hz
(non-latching).
(Default = External fault input)
Note: The digital inputs are not necessary when using the Front Panel Switch & Indicator board in the
FireFinder Plus.

The Relays are rated to 1A and function as follows:

Emergency: Relay Closed (energised)


Emergency Warning Condition
Relay 1 Quiescent: Relay Open (de-energised)
No Power: Relay Open (de-energised)
Disabled: Relay Closed (energised)
Relay 2 Test Mode Enabled: Relay Open (de-energised)
No Power: Relay Open (de-energised)
Fault: Relay Closed (energised)
Fault Relay
Relay 3 No Fault: Relay Open (de-energised)
No Power: Relay Open (de-energised)

The Strobe Output functions as follows:

Provides a Bi-polar output for driving Visual Warning Devices.


The output is monitored and requires 10kΩ 5% 1/3Watt EOL.
Strobe
Allows for 8 x Ampac Xenon Strobes (208-0011) or 40 x Ampac LED strobes 4107-
1005/6)

The 100V line Output functions as follows:

Provides an isolated 100VAC Audio Output. Supports up to 3 branches.


100V Out The output is monitored. EOL value is 47kΩ 5% 1/3 Watt. For 2 branches use 100kΩ 5%
¼ Watt on each branch, and for 3 branches use 150kΩ 5% ¼ Watt on each branch.

104
MAN2994-7

12.17.2 Front Panel Switch and Indicator Module

Figure 116: OWS Control Module Front

Figure 117: OWS Control Module PCB

105
MAN2994-7

12.17.3 Panel Interfacing

106
MAN2994-7

12.18 Printer
Specifications

➢ Printing method: directed impact dot matrix


➢ Interface: 8 bit parallel interface
➢ Printing mechanism: 4/6 pin shuttle
➢ Interface port: 26 PIN flat plug

12.18.1 Indicators and Buttons


The front panel has an LED indicator and two buttons SEL (SELECT), LF (LINE FEED).

Figure 118: Printer Front Panel Layout (Front Cover Closed / Open)

Indicator

When the 3 colour LED indicator is illuminated;

➢ Red indicates the printer is offline with no paper;


➢ Green indicates the printer is On Line;
➢ Yellow indicates the printer is On Line with no paper; or if it is
➢ Off indicates the printer is Off Line or the printer is busy.

SEL Button

a) On Line / Off Line State

The printer enters the On Line state automatically when power is applied or on exiting from the Self-Test
mode. (LED is green).

Press the SEL button, the LED is turned off and the printer goes Off Line.

Press the SEL button again, the LED turns on and the printer is On Line again.

Note: The printer will not receipt data when the printer is off line.

b) Pausing the Printer While It Is Printing.

Press the SEL button while the printer is printing, the printer will pause and enter the Off Line mode after it
finishes printing the row it was currently printing. The printer will continue to print when the SEL button is
pressed again.
107
MAN2994-7

c) Enter the HEX-DUMP mode

Remove power from the printer, press the SEL button, then reconnect the printer to the power supply. The
printer will enter the HEX-DUMP mode. In this mode any programs sent from the host CPU will be printed
out in Hexadecimal.

LF Button

While the printer is Off Line press and hold the LF button, paper feed will be initiated. Release the LF button
and the paper feed will be cancelled.

Self-Test Mode

With power applied (green LED illuminated) push the SEL button. This will turn off the LED. Press and hold in
the LF button, then press the SEL button again and the printer will enter the Self Test mode. Self-test will
print out all the valid characters in the character sets.

Exit the Self-Test Mode:

After printing out the complete Self-Test list the printer will exit the mode automatically; or

Press the SEL button and the printer will immediately exit the Self-Test mode.

108
MAN2994-7

12.18.2 Maintenance
Installing the Ribbon Cassette

The printer has a factory loaded ink ribbon cassette. Remove the power from the printer.

Unlock the front cover by pushing down on the tab at the top of the front panel.

Push the mechanism release button in the top right corner to release the print head.

To remove the ribbon cassette gently pull out the left end then the right.

Replace the cassette by putting the right end of the new cassette slightly onto the drive axle then gentle
pushing the left end into the clips.

The left end of the cassette can only be pressed in after the right end has been correctly seated onto the
drive axle. If alignment is difficult it may be necessary to turn the knob on the cassette slightly. Now check
that the ribbon is tight across the face of the cassette, which is on the inside of the cassette and across the
paper. Turn the knob clockwise again if the ribbon is on the outside of the cassette.

Figure 119: Paper Access

Ribbon Replacement;

Push back the mechanism head and lock it, close the cover of the printer and reconnect the power.

Loading the Paper Roll

Disconnect the power, unlock and open the front cover.

Push down on the mechanism release button in the top right corner to release the head.

Lift the mechanism as shown below.

109
MAN2994-7

Figure 120: Head Mechanism Rotation and Paper Roll Removal / Insertion

1. Take out the empty paper roll and roller


2. Put the new paper roll onto the paper roller and replace as shown above.
3. Connect to the power supply.
4. Press the SEL button to take the printer Off Line, (LED is off).
5. Press the LF button, (paper feed).
6. Feed the edge of the paper into the mechanism and allow it to feed through.
7. Once it established the paper is feeding through the head mechanism correctly press the SEL
button to stop the paper feed.
8. Return the printer head to its original position.
9. Pushing on the affixed label PUSH the head mechanism back into position.
10. Close the front cover.

Note: Press only on the PUSH label to return the head mechanism back into position.

Note: The above instructions are graphically displayed on the inside of the front cover.

110
MAN2994-7

12.18.3 Printer Connections and Jumpering


Mounted on the back of the printer mechanism is the PCB that carries the;

➢ Connectors for interconnection to the Main Board,


➢ Jumper links required to set the programmed print modes; and
➢ Printer 5 volt DC Power Supply.

Figure 121: PCB Layout

Jumper Settings

Designator Jumper State Function


J1 NOT Inserted Selects ESC Commands
Inserted Selects UP Commands
J2 Set as
NOT Inserted Selects ASCII Character Printing Mode
Default
Inserted Selects Chinese Character Printing Mode
J3 NOT Inserted Select Printing by Contrary Direction
Inserted Select printing in the Normal Direction
J7 Set as Insert the Shorting Clip Between Pins 1
Selects the 12 X 12 Font
Default and 2
Insert the Shorting Clip Between Pin 2
Selects the 15 X 16 Font
and 3

12.18.4 Printer 5 Volt Power Supply


27 volts DC is taken from Main Board (BRD86MBA) and fed to CN1 of the 5volt Printer Power Supply Board.
It is this board that drops this voltage from 27volts to 5volts for use by the Printer. Mounted to rear of printer

Figure 122: Printer Power Supply Board Layout

111
MAN2994-7

13 Expanding the System – Networking


Expanding the system can be achieved in various ways and requires the use of boards specifically designed
for communications purposes and boards that actually expand the system.

13.1 Networking
When FACP’s are connected to each other they form a “NETWORK“. Individual FACP’s in the Network are
referred to as NODES. The Network as defined by the limitations of the installation can consist of a number
of Nodes, the number of Nodes being dependant on the configuration of each Node. Typically an entire
Network could consist of 60 Slave CPU’s connected to loops and or input / output devices spread over several
nodes. The Network is Peer to Peer with the entire system configuration being stored at each Node. The
system is then programmed so that information can be made invisible to particular Nodes or visible to all
Nodes. Likewise system commands can be global or restricted to specific parts of the network.
The entire system can be programmed from any Node in the Network and is connected as a data loop which
provides redundancy should there be a single cabling fault.

 IMPORTANT

While it is important that proper documentation is kept and maintained for any installation it becomes
even more important as a system develops into the larger types described above.

13.2 Network Interface Card


The Network Interface Card provides the RS485 communication buses via CN18 on the Main Controller (Loop
Comms) to allow the networking of multiple panels in different combinations, e.g. from Data Gathering
Panels (DGP) to Peer to Peer panels. Enabling the bias increases the immunity and stability of the line.

The Bias SW2 defaults to ON. SW2 is only switched to OFF when direct connecting the network to external
devices such as Optical Fibre Modems.

The Isolate SW3 Allows the network node to be isolated from the network

TO CN18 RS485 RS485


BRD86MBA COMMS COMMS
BOARD IN OUT
JTAG RESET COMMS IN COMMS OUT
+ - S HD ZD1 + - S HD ZD2
C1
SW1

C4

C5
CN1

CN2

C2
U1
C3

26/07/2010

R3
CN3 TB1 TB2
ZDN1

MASTER
R4

ZDN2 R6 R1
R2
R5
C6
MAIN BOARD INTERFACE

0V
R8

R9

R7 D1 L1 L2
ZD4 LK1 ZD5
C7

R10 D2 D3
ZD3
C8

C9
ZD6

BRD86NIC1-

C11
Q1 R11 HEARTBEAT
R12

C10
SHIELD
TH1

LINK
R13

R14 N1236
TH2 TH3 TH4

U2 X1
C12
0V
OFF RL1 RL2
+L

-L
+L

-L

D4
ZD8
ZD9

NC2

ZD10
ZD7

NC1
BIAS

NC2

NC1

L3 D5
R15
R16

PANEL
C13

C2

C1
C2

C1

U3
L4
C19 C16
C20 C17

C18

TX
NO2

NO1
NO2

D6
NO1

L5 C15
L6 PANEL U4
C14 3V3 ON SW2
R22 ISOLATED
C24 R17 R18 R19 R20 R21
C21

RX
R23

C22
C25

U5 C23
D7 U8
L7 C26
C30

R26

L8
C28
COMMS

U6 C27 C29
C36

C32
R24 R25
D9

C35
D8

C31 U7
SW3
C33

D10
R27 C34
R32

R33

R28
R35

D11 R30

D12 R31

R29
C38

L9 C37
R34

C40
R36 D13 D14
C39
T1
POWER TH5

CN4 C41
R40

C44
R37
U9 R38 U10
RX IN R39 TX IN RX OUT TX OUT
C42 C47

Q2
D15

D16

R43
R41

C43 R42
C46

ZD11 CN5 CN6 D17


ZD12
TH6
C45
ZD13
ACTIVE
D18
C48

R44

R45

R46

27VDC
IN / OUT

Figure 123: Network Interface Card Layout


112
MAN2994-7

PANEL 1
RESET BACKLIGHT 16 Way
MAIN BOARD SW1
EXPANSION
CN17 MODULE

CN20
SLAVE 4 SLAVE 3 SLAVE 2 CN3
CN100
4 CN13 3 CN14 2 CN15 MAIN BOARD INTERFACE

0V
CN11

NETWORK
CN5

CN18
COMMS
LOOP

D5
D7

TX
PANEL
RX
PANEL
CN6
POWER
SW2

NODE ADDRESS

12 3 4 5 6 7 8
27VDC NETWORK INTERFACE
IN
SLAVE CPU 4 SLAVE CPU 3 SLAVE CPU 2 CARD SW1

RESET
HEARTBEAT

MASTER
0V
3V3
TERMINATION BOARD

D2

D1
CN23 BIAS

ON

OFF
CN2
CN2

CN2
RS485

SW2
CN10
ZD7
TB1 COMMS

RX IN
D11

IN

DEBUG
DEBUG

DEBUG
LK1
LK1

LK1

+ -

COMMS IN
+
TX IN

-
1 D12

SHD

SHD
MAIN CPU

TP1
TP1

TP1

27V IN
RS485

LINK
SHIELD
CN26
LK1
RS485 EOL COMMS
+5V
LK2 CN9 PRINTER 27V TB2
COMMS 2 BUZZER O UT

COMMS OUT
+ -
RS232

+
PSU MONITOR

RX OUT
LK3 OUT CN16
EXPANSION

BRIGADE I/F

D13
CN27 BUZZER

-
MODULE

INHIBIT

ACTIVE

SHD
CN7

SHD
D16

0V CN21 KEY SWITCH


COMMS2 RS232 (TOP) CN8

TX OUT
CN6

ISOLATED
C18

D14
CN2 5 EXTRA CONTROLS
CN2

SW3
COMMS1 CN3 CN4 CN5
RS232/MODEM BZ1
+

CN1

D6
(BOTTOM) EXPANSION PANEL EXPANSION LEDS US B FRONT PANEL PRINTER

PANEL 2
BACKLIGHT 16 Way
MAIN BOARD RESET
SW1
EXPANSION
CN17 MODULE

CN20
SLAVE 4 SLAVE 3 SLAVE 2 CN3
CN100
4 CN13 3 CN14 2 CN15 MAIN BOARD INTERFACE

0V
CN11
NETWORK

CN18
CN5
COMMS
LOOP

D7

D5
TX
PANEL
RX
PANEL
CN6
P O WE R

SW2
NODE ADDRESS

NETWORK INTERFACE
12 3 4 5 6 7 8

27VDC
IN CARD
SLAVE CPU 4 SLAVE CPU 3 SLAVE CPU 2 SW1

RESET
HEARTBEAT

MASTER
0V
3V3
TERMINATION BOARD

D2

D1
CN23 BIAS

OFF
ON

RS485
CN2
CN2

CN2

SW2
CN10

ZD7
COMMS
RX IN

D11
TB1
IN
DEBUG
DEBUG

DEBUG
LK1
LK1

LK1

+-

COMMS IN
+
TX IN

-
1 D12
SHD

SHD
MAIN CPU
TP1
TP1

TP1

CN26
27V IN

LINK
SHIELD

RS485
LK1

RS485 EOL COMMS


+5V
LK2 CN9 PRINTER 27V TB2
COMMS 2 BUZZER O UT
COMMS OUT

RS232
+-

+
PSU MONITOR

RX OUT TX OUT

LK3 OUT CN16


EXPANSION

BRIGADE I/F

D13

BUZZER
CN7

CN27
-
MODULE

INHIBIT
ACTIVE

SHD

SHD

D16

0V CN21 KEY SWITCH


COMMS2 RS232 (TOP) CN8
CN6
ISOLATED

C18
D14

CN2 5 EXTRA CONTROLS


CN2
SW3

COMMS1 CN3 CN4 CN5


RS232/MODEM BZ1
+

CN1
D6

(BOTTOM) EXPANSION PANEL EXPANSION LEDS US B FRONT PANEL PRINTER

Figure 124: Basic 2 Node System using a Network Interface Card

113
MAN2994-7

14 High Level Interfacing

14.1 High Level Interface Expander (BRD43SPB)


The High Level Interface Expander (BRD43SPB) consists of a serial port under the control of a microcontroller.
Communications between the FACP and this board is via the RS485 control bus with each board having a
dedicated link and selectable 4 bit address.

The Serial/Parallel Board consists of serial ports, a parallel port and an Ethernet port all under the control of
a microcontroller.

The parallel port supports a standard printer.

The Ethernet port provides an additional option to print to an Ethernet printer.

The serial port (RS232) has the capability to support a GSM Modem.

SERIAL
RS485
ZD1
PARALLEL TB1
TH1

( TB2
EXT FACP CN2
CN1
TH2

COMMS ) + - SHD
ZD2

ZD3

ZD4
+

RN1 RN2
ETHERNET
C1

R2 CN3

C15
-

C6

C10
C11
C12

C13

R1
C17
C7
C9
C8

C14
C18

L2
R6 R7 R8 R9

C20
C19
L1
SHD

R4
CN4 C16 RN3 RN4 RN5 RN6
TP89 TP1
R3 RS485 TP2

R10
EOL

R5
C30 C21

U1 C23
C22

C25
C26
+ INTERNAL FACP 3.3V 0V
U2
C27
0V
C24 R12
COMMS
C28 U4 U5 U3
C31

R13
R11
C29 C33 X1 C32 R35
-

R16
TB2 LK2 BRD43SPB4- U6
R14
C36

C34
0 V +27V 0 V +27V SHD

C35 C38
FACP U7

R15
C37
CN5
C44

L3 R17
L4EOL

R21
C40 R18
R19
C45 C41
C51 R20
C46 C49
C48

LK3 U8 C47
U9

C42 R22 C43


C54 C50

- + FACP 0V
C63 L5
C52 C53 U10
R23
R25

C58
C59
C57

TP88 U11
C62 C56

R24
R27
C64
C65
R26

R28

C55
R29

ZDN1
RN7

5V
M1 C61
R30 N1236
TB3 C60 C67 R31
C68
R32

TH5 +
INTERNAL D1 C66 D2 D5 LSB MSB
CN7

M2 T1
ZD5

+/-27V JTAG U12 R36


POWER D3
L6

CN8 ZD6 D4 D6 D7 ZDN2


TH6 D8 C70 U13
S

C71
ER

M
M3

C74
( TB3
C72 EXTERNAL +/-27V ) R34 1 2 3 4 SW1 ADDRESS
M
W

R33 Q1 C73
O
PO

Figure 125: High Level Interface Expander PCB Layout

Software

The Serial/USB port supports the following protocols:-

HLI – Functionality matches the FireFinder PLUS panel which supports text or positive ack protocol.
Configurable attributes are: logical output, physical output, alarm output, pre-alarm output, fault output,
isolate output and descriptors

SmartGraphics interface - Serial Port or RS485 Port

MODBUS interface - Serial Port or RS485 Port

EV3000 - RS485 port

SMS capability via GSM modem - Serial or USB port

114
MAN2994-7

NODE 1 RS 232
CN17
RS 485
CH15

D13
MAIN CONTROL BOARD CH16

TB1
+ - SHD
CN20
RJ45 CN2 SERIAL
CN13
CN14

PARALLEL

+
CN15

4 3 2 CN4

-
FACP COMMS
CN11

CN18 RS485

S HD
c

1
a b
CN2 CN2 CN2
EOL
a b
c
+
LOOP CN5
HLI CONTROLLER MODBUS

-
SLAVE CPU

SLAVE CPU

SLAVE CPU

LK2
U15
C OMMS

S HD
+2 7 V
FACP LK3
CPU BOARD

RN20 RN17

CN2
0V - + EOL
FACP 0V
+2 7V ADDRESS

0V LSB M SB
- +
U13 TB3
CN8 D6 D7 ZDN2

PO W ER

CO M MS
1 2 3 4 SW1
CN1

CN1

CN1
U14 1

U11
RJ45 RS 232
U10
CH8 CH8 CH6 CH8 RS 485
TP3
D14 CN10 TB1
+ - SHD
CN16
PSU MONITOR

CN2
BRIGADE I/F

SERIAL
27V IN

C12
CN7

CN6
PARALLEL

+
TH1
CN8 MODEM
R17

CN4
CN21

-
+

CH1 CN2
CH2
FACP COMMS RS485

S HD
EV3000
CN4

EOL
CN3

CN1
BZ1
EXPANSION PANEL EXPANSION LEDS FRONT PANEL CN5 PRINTER +

16 Way CN5 HLI CONTROLLER

S HD -

LK2
+2 7 V

0V - +
FACP LK3 HLI
EOL FACP 0V

2 WIRE & SHIELD +2 7V

0V
ADDRESS
LSB M SB
- +
RS422 COMMS IN TB3
CN8 D6 D7 ZDN2

PO W ER

CO M MS
1 2 3 4 SW1

RJ45 RS 232
2 WIRE & SHIELD
RS422 COMMS OUT RS 485
RESET COMMS IN COMMS OUT TB1
+ - SHD + - SHD
SW1

CN3 C N1
CN2 + - SHD

TB1 TB2
BRD86NIC1-

SERIAL
MAIN BOARD MASTER
D1 PARALLEL

+
INTERFACE HEARTBEAT
D2
CN4

-
LK1 FACP COMMS RS485

S HD
N1236
SHIELD
LINK
+
EOL
BMS
CN5
HLI CONTROLLER
S HD -

LK2
NETWORK ISOLATED
D6
+2 7 V FACP LK3
Nurse Call
0V - + EOL
INTERFACE +2 7V
FACP 0V
ADDRESS
COMMS

LSB M SB

BOARD
0V
SW3
- +
TB3
CN8 D6 D7 ZDN2

PO W ER

CO M MS
D11

D12

D13 D14

CN4 RX IN TX IN RX OUT TX OUT 1 2 3 4 SW1


POWER

D16

ZD13
ZD11

CN5 CN6 ACTIVE

27V IN/OUT SmartTerminal


NODE 2 RJ45
CN17

CH15
MAIN CONTROL BOARD CH16
TB1 TB4
D13
+ - COM +24V 0 V
RS485 OUT POWER OUT
CN13 CN20
COMMUNICATIONS
CN14

CN15

4 3 2
CN18
CN11

c
EXTENDER BOARD
1

a b
CN2 CN2 CN2

a b
c LOOP BRD82LTB2
C OMMS
CN4 Ancilliary Module
SLAVE CPU

SLAVE CPU

SLAVE CPU

U15

CN2 CN3 (Agent Release Module,


CPU BOARD

RN20 RN17

CN2
CN5
Fire Fan Module,
U13

RJ45 8 Way Switch Indicator)


CN1

CN1

CN1

U14 1

U11

CH8 CH8 CH6 CH8


U10

TP3
D14 CN10

CN16
PSU MONITOR
BRIGADE I/F
27V IN

C12
CN7

CN6

R17
CN8 MODEM
TH1
CN21

CH1 CN2
CH2

CN4
CN3

CN1
BZ1
EXPANSION PANEL EXPANSION LEDS FRONT PANEL CN5 PRINTER

16 Way
2 WIRE & SHIELD
RS422 COMMS IN

2 WIRE & SHIELD


RESET COMMS IN COMMS OUT
CN3 + - SHD + - SHD RS422 COMMS OUT
SW1

C N1
TB1 TB2
BRD86NIC1-

MA S T ER

MAIN BOARD D1

D2
LK1
INTERFACE H EARTBEAT

N1236 SHIELD
LINK

D6

NETWORK ISOLATED

INTERFACE
COMMS

SW3

CARD
D11

D12

D13 D14

CN4 RX IN TX IN RX OUT TX OUT


POWER

D16

ZD13
ZD11

CN5 CN6
ACTIVE

27V IN/OUT

Figure 126: Example of Networking Configurations

Note: Maximum distances between panels = 1.2km.

115
MAN2994-7

14.2 High Level Interface Expander (BRD43HLI)

The High Level Interface board (BRD43HLI) provides RS232, RS485 and RS422 communications for interfacing
to various external systems.

Figure 127: High Level Interface Expander PCB Layout

14.2.1 SmartView Graphics


RS232 or RS422

SmartView is an extensible web-based, client server application whose primary role is dedicated to the
monitoring and reporting of Ampac’s fire detection system events.

SmartView provides clear and precise alarm information using graphical and text formats.

116
MAN2994-7

15 Certification Information

The FireFinder Plus is designed and manufactured by:

AMPAC TECHNOLOGIES PTY LTD

7 Ledgar Rd

Balcatta 6021

Western Australia

PH: 61-8-9242 3333

FAX: 61-8-9242 3334

Manufactured to:

Certificate of Compliance Number:

Equipment Serial Number:

Date of Manufacture:

117
MAN2994-7

16 Maintenance and Troubleshooting Chart


16.1 Maintenance
The FireFinder PLUS FACP should be maintained so as to comply with all standards / regulations applicable
to the country and location it has been installed. Failure to do so could put at risk compliance and the integrity
of the system. As a minimum it is recommended the following be used as a guide to periodic maintenance
especially if there is an absence of standards regulations.

General

To implement a site maintenance regime, responsibilities should be established by responsible persons,


training implemented if required, maintenance delegates appointed and all outcomes clearly communicated
to all parties.

Daily Operations (operator level)

✓ The delegated operator checks for normal operation


✓ If any faults are detected, record them in an established “Site Log Book” and report them to the
assigned body.
✓ Ensure all faults are signed off as they are resolved and follow up on those that are still
outstanding.

Monthly Operations (operator level)

In addition to Daily Operational checks

✓ Visually inspect in and around the panel for any signs of pests, moisture or general damage
✓ Ensure any non FACP standby power facilities are in a state of operational readiness
✓ Force a suitable device, such as an MCP or detector, into an alarm state so that it generates a
know alarm outcome. This process should be controlled and established in consultation with all
interested parties (installing engineers include) so that maximum benefit is obtained from the
test.
✓ Ensure the Site Log Book” is up to date, faults have been attended to and the latest test are
recorded

Quarterly Operations (service contractor)

In addition to Monthly Operational checks

✓ Check all internal connections and perform “alarm”, “fault” and site specific tests
✓ Perform a “walk around” of the site to determine if the system integrity is free of possible faults
✓ Ensure the Site Log Book” is up to date, faults have been attended to and the latest test are
recorded

Annual Operations (service contractor)

In addition to Monthly Operational checks

✓ Initiate both a “lamp” and “walk” test and any other tests as determined necessary for the site
✓ Inspect and test ( as per the manufacturers specifications ) batteries
✓ Ensure the Site Log Book” is up to date, faults have been attended to and the latest test are
recorded

118
MAN2994-7

Replacement Components (service contractor)

✓ Batteries and fuses are seen as the only field replaceable components.
✓ If a board field change is required all necessary anti-static precautions must be taken.

Note: If the Main Board is changed the power supply may require re-calibration.

16.2 Troubleshooting FireFinder PLUS


 Resolution of all suspected faults MUST only be carried out by suitably qualified technical operatives.

Problem Solution
No Mains Power Check mains Fuse
Check output voltage it should be set to 27.6V.
Low = (less than 26.5V )
Power Fault LED illuminated
High = (greater than 28V )
Check the battery has been connected properly
Check all input and output cabling and wiring
Earth Fault LED illuminated assemblies for short to ground or resistance <50
Ohms
Ensure correct software is installed
System Fault LED illuminated
Check all connections for loose wiring
Maintenance Alarm cleared but FireFinder
Carry out Loop Test
PLUS still displays Maintenance Alarm
Check in and out legs are connected correctly at
LCD displays LOOP (number) open circuit the loop termination board

Unable to clear an O/C or S/C on a loop You must perform a loop test to clear the fault.
Check for correct software installed in all
communication boards.
Communication Loop not working
Check LCD at Main controller. This may identify
where there is a break in the communication line
Can not access Function menu Incorrect Password entered
Ring AMPAC and directions will be given to
Forgotten password
provide you with a temporary code
An Analogue Fault occurs when using a A 1.8k Ohm resistor must be placed in series with
Zone Monitor to monitor a switch. the switch contacts.
Make sure you have a 10K Ohm EOL resistor fitted
Sounder Fault
and a diode (1N4004) in series with the sounder

119
MAN2994-7

17 Compatible Devices
AMPAC Auto Learn
Device Type Displayed Type (19 chars) Type Desc
Type Code Default
Optical
05h  XP95 Optical XP95 PHOTO PHOTO
05h XP95 Optical with base sounder XP95 PHOTO + SNDR PHOTO
05h XPander Optical XPANDER PHOTO PHOTO
05h S90 Optical S90 PHOTO PHOTO
05h Xplorer Optical XPLORER PHOTO PHOTO
05h Xplorer Optical with base sounder XPLR PHOTO + SNDR PHOTO
05h XP95 Beam XP95 BEAM PHOTO
0Dh  XP95 Reflective beam XP95 REFLECT BEAM BEAM
105h  Discovery Optical DISC PHOTO PHOTO
105h Discovery Optical with base sounder DISC PHOTO + SNDR PHOTO
11Dh  Discovery Multisensor DISC MULTISENSOR MULTI
11Dh Discovery Multisensor with base sounder DISC MULTI + SNDR MULTI
15h  XP95 Flame XP95 FLAME FLAME
1Dh  XP95 Multisensor XP95 MULTISENSOR MULTI
1Dh XP95 Multisensor with base sounder XP95 MULTI + SNDR MULTI
1Dh XPander Multisensor XPANDER MULTI MULTI
31Dh  Enhanced Discovery Multisensor EDSC MULTISENSOR MULTI
31Dh Enhanced Discovery Multi + base sounder EDSC MULTI + SNDR MULTI

Heat Detectors
06h  XP95 Heat XP95 HEAT HEAT
06h XP95 Heat with base sounder XP95 HEAT + SNDR HEAT
06h XPander Heat XPANDER HEAT HEAT
06h S90 Heat S90 HEAT HEAT
06h Xplorer Heat XPLORER HEAT HEAT
06h Xplorer Heat with base sounder XPLR HEAT + SNDR HEAT
0Eh  XP95 Hi temp XP95 HI HEAT HHEAT
0Eh XP95 Hi temp with base sounder XP95 HI HEAT + SNDR HHEAT
0Eh XPander Hi temp XPANDER HI HEAT HHEAT
0Eh Xplorer Hi temp XPLORER HI HEAT HHEAT
0Eh Xplorer Hi temp with base sounder XPLR HI HEAT + SNDR HHEAT
106h  Discovery Heat DISC HEAT HEAT
106h Discovery Heat with base sounder DISC HEAT + SNDR HEAT

Ionisation
03h  XP95 Ion XP95 ION ION
03h XP95 Ion with base sounder XP95 ION + SNDR ION
03h S90 Ion S90 ION ION
103h  Discovery Ion DISC ION ION
103h Discovery Ion with base sounder DISC ION + SNDR ION
10Bh  Discovery Carbon Monoxide DISC CO CO
10Bh Discovery Carbon Monoxide with base sndr DISC CO + SNDR CO

120
MAN2994-7

AMPAC Auto Learn


Device Type Displayed Type (19 chars) Type Desc
Type Code Default
Manual Call Points
07h  S90 MCP S90 MCP MCP
11Fh  Discovery MCP DISC MCP MCP
1Fh  XP95 MCP XP95 MCP MCP
1Fh XPander MCP XPANDER MCP MCP
1Fh XP95 Mini switch monitor with interrupt XP95 MINI SW + INT MCP
1Fh Xplorer MCP XPLORER MCP MCP

Sounders
01h  XP95 sounder / sounder control unit XP95 SOUNDER SNDR
01h XPander sounder XPANDER SOUNDER SNDR
01h XP95 integrated base sounder XP95 INTGR BSE SNDR SNDR
01h XP95 Intelligent base sounder XP95 INTEL BSE SNDR SNDR
01h XP95 sounder beacon base XP95 SND BEACN BSE SNDR
01h XP95 loop powered beacon XP95 LOOP PWR BEACN SNDR
01h S90 sounder control unit S90 SCU SNDR
111h  Discovery sounder beacon base/open area DISC SOUNDER BEACN SNDR

I/O Units
02h  XP95 input / output module XP95 I/O I/O
02h XPander I/O (Relay) Unit XPANDER I/O I/O
02h XP95 three channel input / output module XP95 3I/O I/O
02h XP95 output module XP95 OUTPUT I/O
02h XP95 mains switching input / output module XP95 MAINS I/O I/O
02h S90 single channel I/O unit S90 SINGLE I/O I/O
02h S90 3 channel I/O unit S90 3I/O I/O
02h S90 3 channel analogue I/O unit S90 3I/O + ANALOGUE I/O
02h S90 switch monitor unit S90 SWITCH I/O
02h Xplorer output module XPLORER OUTPUT I/O

Zone Monitors
04h  XP95 zone monitor XP95 ZONE MONITOR CONV
04h XPander Loop Interface XPANDER INTERFACE RADIO
04h S90 zone monitor S90 ZONE MONITOR CONV

0Ch  XP95 switch monitor XP95 SWITCH SWITCH


0Ch XP95 mini switch monitor XP95 MINI SWITCH SWITCH
0Ch XP95 switch monitor plus XP95 SWITCH PLUS SWITCH

1Ch  FastSense XP95 APIC XP95 FASTSENSE FSENSE

User Defined
10h  XP95 AAF XP95 AAF AAF

121
MAN2994-7

18 Address Setting
BINARY ADDRESS SETTING (APOLLO)
SERIES XP95 - ADDRESS DATA
DIL SWITCH: ON = 1 OFF = 0 ADDRESS TAG FOR DETECTORS (I/O DEVICES)

DIL switch setting DIL switch setting DIL switch setting DIL switch setting DIL switch setting
Address 1234567 Address 1234567 Address 1234567 Address 1234567 Address 1234567
1 1000000 26 0101100 51 1100110 76 0011001 101 1010011
2 0100000 27 1101100 52 0010110 77 1011001 102 0110011
3 1100000 28 0011100 53 1010110 78 0111001 103 1110011
4 0010000 29 1011100 54 0110110 79 1111001 104 0001011
5 1010000 30 0111100 55 1110110 80 0000101 105 1001011
6 0110000 31 1111100 56 0001110 81 1000101 106 0101011
7 1110000 32 0000010 57 1001110 82 0100101 107 1101011
8 0001000 33 1000010 58 0101110 83 1100101 108 0011011
9 1001000 34 0100010 59 1101110 84 0010101 109 1011011
10 0101000 35 1100010 60 0011110 85 1010101 110 0111011
11 1101000 36 0010010 61 1011110 86 0110101 111 1111011
12 0011000 37 1010010 62 0111110 87 1110101 112 0000111
13 1011000 38 0110010 63 1111110 88 0001101 113 1000111
14 0111000 39 1110010 64 0000001 89 1001101 114 0100111
15 1111000 40 0001010 65 1000001 90 0101101 115 1100111
16 0000100 41 1001010 66 0100001 91 1101101 116 0010111
17 1000100 42 0101010 67 1100001 92 0011101 117 1010111
18 0100100 43 1101010 68 0010001 93 1011101 118 0110111
19 1100100 44 0011010 69 1010001 94 0111101 119 1110111
20 0010100 45 1011010 70 0110001 95 1111101 120 0001111
21 1010100 46 0111010 71 1110001 96 0000011 121 1001111
22 0110100 47 1111010 72 0001001 97 1000011 122 0101111
23 1110100 48 0000110 73 1001001 98 0100011 123 1101111
24 0001100 49 1000110 74 0101001 99 1100011 124 0011111
25 1001100 50 0100110 75 1101001 100 0010011 125 1011111
126 0111111

ON ON

1 2 3 4 1 2 3 4 5 6 7 8

Figure 128: 4 and 8 way Switch addressing set to Address 11

122
MAN2994-7

2 8 32

11
1 4 16 64

= PUNCH OUT
Figure 129: Xpert Card addressing set to Address 11

123
MAN2994-7

19 Glossary of Terms
ACF: ANCILLARY CONTROL FACILITY
ACKD: ACKNOWLEDGED
AHU: AIR HANDLING UNIT
ALM: ALARM
AVF: ALARM VERIFICATION FACILITY
AZF: ALARM ZONE FACILITY
AZC: ALARM ZONE CIRCUIT
C: RELAY COMMON CONTACT (WIPER)
CIC: CONTROLLER INTERFACE CARD
CN: CONNECTOR
CPU: COMMON PROCESSOR UNIT
DGP: DATA GATHERING POINT
EARTH: BUILDING EARTH
EOL: END OF LINE
FACP: FIRE ALARM CONTROL PANEL
FLT: FAULT
GND: GROUND (0 VOLTS) NOT EARTH
I/O: INPUT/OUTPUT
LCD: LIQUID CRYSTAL DISPLAY
MAF: MASTER ALARM FACILITY
MCP: MANUAL CALL POINT
MOV: METAL OXIDE VARISTOR (TRANSIENT PROTECTION)
NIC: NETWORK INTERFACE CARD
N/C: NORMALLY CLOSED RELAY CONTACTS
N/O: NORMALLY OPEN RELAY CONTACTS
N/W: NETWORK
PCB: PRINTED CIRCUIT BOARDS
P/S: POWER SUPPLY
REM: REMOTE
TB: TERMINAL BLOCK

124
MAN2994-7

20 Definitions
Addressable system - a fire alarm and detection system that contains addressable alarm zone facilities or
addressable control devices.
Alarm Verification Facility (AVF) - that part of the FACP, which provides an automatic resetting function for
spurious alarm signals so that they will not inadvertently initiate Master Alarm Facility (MAF), or ACF
functions. Using ConfigManager PLUS prior to downloading to the FireFinder PLUS sets this option
Alarm zone - the specific portion of a building or complex identified by a particular alarm zone facility.
Alarm Zone Circuit (AZC) - the link or path that carries signals from an actuating device(s) to an alarm zone
facility(s).
Alarm Zone Facility (AZF) - that part of the control and indicating equipment that registers and indicates
signals (alarm and fault) received from its alarm zone circuit. It also transmits appropriate signals to other
control and indicating facilities.
Alert signal - an audible signal or combination of audible and visible signals, from the occupant warning
system to alert wardens / personnel as necessary to commence prescribed actions.
Ancillary Control Facility (ACF) - that portion of the control and indicating equipment that on receipt of a
signal initiates predetermined actions in external ancillary devices.
Ancillary equipment - remote equipment connected to FACP.
Ancillary relay - relay within FACP to operate ancillary equipment.
Ancillary output - output for driving ancillary equipment.
Approved and approval - approved by, or the approval of, the Regulatory Authority concerned.
Card-detect link - a link on a module connector to indicate the disconnection of the module.
Conventional System - is a fire detection system using a dedicated circuit for each alarm zone.
Distributed system-a fire alarm and detection system where sections of the control and indicating equipment
are remotely located from the FACP or where sub-indicator panel(s) communicate with a main FACP.
Field connections - are connections made to FACP or ancillary equipment during installation.
Fire Alarm Control Panel (FACP) - a panel on which is mounted an indicator or indicators together with
associated equipment for the fire alarm or sprinkler system.
Fire resisting - an element of construction, component or structure which, by requirement of the Regulatory
Authority, has a specified fire resistance.
Indicating equipment - the part of a fire detection and or alarm system, which provides indication of any
warning signals (alarm and fault), received by the control equipment.
Interface - The interconnection between equipment that permits the transfer of data.
Master Alarm Facility (MAF) - that part of the equipment which receives alarm and fault signals from any
alarm zone facility and initiates the common signal (alarm and/or fault) for transmission to the fire control
station. Bells and other ancillary functions may be initiated from this facility.
Power Supply - that portion of the FACP which supplies all voltages necessary for its operation.
Regulatory Authority - an authority administering Acts of Parliament or Regulations under such Acts

125
MAN2994-7

21 Specifications
Metal SP1M (Europe Only) Metal SP8X
Mechanical
845 (H) x 518.5 (W) x 173(D)
Dimensions Cabinet: ( mm ) 505 (H) x 407 (W) x 150 (D)
Includes window outer door
Material 1.2mm Mild Steel 1.2mm Mild Steel
Environmental
Temperature: -5ºC to + 40ºC
Humidity: 0% to 95% non-condensing
IP rating IP30
Mains Input
Input Voltage: 195 - 264VAC 195 - 264VAC
Protection (Quick Acting Fuse):
5 AMP Supply 2Amp 3AG Slow Blow 2A 3AG Slow Blow
18 AMP Supply N/A 5A 3AG Slow Blow
Minimum Cable Requirements: Not less than 0.75mm² Not less than 0.75mm²
Power Supply

Operating Voltage Range: 20 - 28.2VDC 20 - 28.2VDC


Power Supply Ripple Voltage: <250mV <250mV
Power Supply Output Current: 5.6Amps 5.6Amps / 18Amps
Imax A 3Amps
Imax B 5.5Amps
Protection Current Limiting Current Limiting

Batteries / Battery Charger


Charger Float Voltage 26.6-28.2VDC 26.6-28.2VDC
(Temp compensated): (27.3VDC nom @ 20°C) (27.3VDC nom @ 20°C)
Approved LPCB Battery: Genesis NP24-12R
Battery Type: 2x12V Sealed Lead Acid 2x12V Sealed Lead Acid
Max Battery Capacity: 24AH 40AH
Max Charger Current Limited: 1.25A 2A
Battery Supply Current Limited: 3A and 2A PTC 3A and 2A PTC
Battery Low: <23VDC <23VDC
Battery Discharged Cut-off Voltage: <21VDC <21VDC
Max Battery Resistance 0.75Ω 0.43Ω
Panel
Quiescent Current ( QI ) 1 Loop 220mA
Max Number of Zone LEDs: 64 128
Loop
Maximum number of Loops:
4 8
Maximum Number of Zones:
64 128
Maximum Number of Devices:
126 / loop 126 / loop
Loop Current
500mA / loop 500mA / loop
Cabling Requirements:
2 core 1.5 -2.5mm² Max length 1km 2 core 1.5 -2.5mm² Max length 1km
O/C, S/C , over current O/C, S/C , over current
Fault supervision:
Outputs
Supervised Alarm (Current Limited) 24VDC @ 1A Max O/C, S/C, 10K EOL
Alarm / Fault Relay Contacts 24VDC @ 1A
Auxiliary VDC – Protected 24VDC @ 2A
Cabling Requirements: 2 core 1 -2.5mm2 Max length 1km
Inputs
Supervised O/C, S/C, 10K EOL
Cabling Requirements: 2 core 1 -2.5mm2 Max length 1km
Communications
Add-on Module Internal to FACP RS485
External to FACP RS485

126
MAN2994-7

Metal SP1X Metal SP16X


Mechanical
505 (H) x 407 (W) x 150 (D) 1200 (H) x 625 (W) x 240 (D)
Dimensions Cabinet: ( mm )
Includes window outer door Includes window outer door
Material 1.2mm Mild Steel 1.2mm Mild Steel
Environmental
Temperature: -5ºC to + 40ºC
Humidity: 25% to 95% non condensing
IP rating IP30
Mains Input
Input Voltage: 195 - 264VAC 195 - 264VAC
Protection (Quick Acting Fuse):
5 AMP Supply 2Amp 3AG Slow Blow N/A
18 AMP Supply N/A 5A 3AG Slow Blow
Minimum Cable Requirements: Not less than 0.75mm² Not less than 0.75mm²
Power Supply

Operating Voltage Range: 20 - 28.2VDC 20 - 28.2VDC


Power Supply Ripple Voltage: <250mV <250mV
Power Supply Output Current: 5.6Amps 18Amps
Imax A 3Amps
Imax B 5.5Amps
Protection Current Limiting Current Limiting

Batteries / Battery Charger


Charger O/P Voltage 26.6-28.2VDC 26.6-28.2VDC
(Temp compensated): (27.3VDC nom @ 20°C) (27.3VDC nom @ 20°C)
Approved LPCB Battery:
Battery Type: 2x12V Sealed Lead Acid 2x12V Sealed Lead Acid
Max Battery Capacity: 18AH 40AH
Max Charger Current Limited: 1.25A 2A
Battery Supply Current Limited: 3A and 2A PTC 3A and 2A PTC
Battery Low: <23VDC <23VDC
Battery Discharged Cut-off Voltage: <21VDC <21VDC
Max Battery Resistance 0.75Ω 0.43Ω
Panel
Quiescent Current ( QI ) 1 Loop 220mA
Max Number of Zone LEDs: 64 128 +
Loop
Maximum number of Loops:
4 16
Maximum Number of Devices:
126 / loop 126 / loop
Loop Current
500mA / loop 500mA / loop
Cabling Requirements:
2 core 1.5 -2.5mm² Max length 1km 2 core 1.5 -2.5mm² Max length 1km
O/C, S/C , over current O/C, S/C , over current
Fault supervision:
Outputs
Supervised Alarm (Current Limited) 24VDC @ 1A Max O/C, S/C, 10K EOL
Alarm / Fault Relay Contacts 24VDC @ 1A
Auxiliary VDC – Protected 24VDC @ 2A
Cabling Requirements: 2 core 1 -2.5mm2 Max length 1km
Inputs
Supervised O/C, S/C, 10K EOL
Cabling Requirements: 2 core 1 -2.5mm2 Max length 1km
Communications
Add-on Module Internal to FACP RS485
External to FACP RS485

127
NOTE:
1: At Access Level 1, the entire MENU is not accessible.
2: At Access Level 2, the MENU is active and partial FUNCTION options are active
= ACCESS LEVEL 2 The user shall be presented with the ACCESS option to enter the level 3 FUNCTION's
3: At access level 3, all FUNCTION options are available
= ACCESS LEVEL 3

MENU
0 1 2 3 4
ALARMS STAGE-1 ALARM PRE-ALARMS FAULTS DISABLES
0 1 2 3 3/4 4/5 5/6 6/7 7/8 8/9
ZONE /
DEVICE LOOP MODULES * COMMS P/SUPPLY BRIGADE TFAILS SOUNDERS ADD ONS SYSTEMS
* APPLICABLE ONLY WHEN PANEL NETWORKED
5 6
WALK TEST STATUS * APPLICABLE ONLY WHEN PANEL NETWORKED
0 1 2 3 4 4/5 5/6 6/7
LOOPS MODULES I/O BRIGADE * NETWORK SYSTEM AVALUES ADD ONS
0 1 0 1 0 1 0 1
PRINT PRINT POWER NETWORK REMOTE
ALL DEVICES TOTAL SLAVE SUPPLY OUTPUTS INPUTS POINTS SLAVE MODULE

0 1 0 1 2
POWER
22 QUICK REFERENCE GUIDE

IN A PANEL ON A LOOP STATUS SUPPLY BRIGADE

7 8 9
TOOLS SETUP ABOUT
0 1 2 0 1 2
ZONE
ALARM FAULT LAMP SOUNDER DELAY PRINTER
* = ACCESS LEVEL 3
0 1 0 1 0 1 2* 3* 0 1 0 1
SOUNDER SOUNDER SOUNDER SOUNDER ALL ZONE ALL ZONE GO OFF-LINE ALARM
ZONE DEVICE ZONE DEVICE ENABLE DISABLE RE TRIGGER (ON) RE TRIGGER (OFF) DELAY ON DELAY OFF / GO ON-LINE MODE ONLY

FUNCTION
0 1 3 5
GLOBAL
DATE TIME LOGS * = ACCESS LEVEL 3 I/O
0 1 2 3 4 5* 4* 0 1 2 3 4 5
ERASE ALL REMOVE ALL
ALARM FAULT DISABLE SYSTEM I/O WDOG INPUT OUTPUT MANUAL CONTROL FWRE FARE WARNING SYSTEM
LOGS

0 1 0 0 1 2 0 1
PRINT SHOW PRESS ENTER CLEAR WATCH REMOVE ALL
ENTRY OPTIONS TO CONFIRM COUNTER IN A PANEL ON A LOOP MANUAL CONTROL ENABLE DISABLE
7 0 1 2
* ENTER ACCESS CODE VIEW BY VIEW BY PRINT MULTIPLE
ACCESS* ENTRY NUMBER DATE ENTRIES
FOR LEVEL 3 FUNCTIONS
FUNCTION
2 4 7 8
DAY/NIGHT TESTS PASSWORD PROGRAMMING
0 1 2 0 1 0 1 2 0 1 2 3 4 5 6
ENABLE / ADD DELETE DELETE ALL CONV PANEL SUB ZONE
DAY TIME NIGHT TIME DISABLE WALK TEST LOOP TEST PASSWORD PASSWORD PASSWORDS ZONE DEVICE INPUT OUTPUT BASED MCP ADDRESS PROGRAMMING

Menu Flow v1_2


MAN2994-7

128
MAN2994-7

23 Statement of Compliance
Please PRINT

1. Name of Building:

2. Address:

3. I/We have installed in the above building an alteration to the system manufactured by, OR a system
manufactured by. (Name of Service Provider)

4. The system is connected to monitoring service provider by a Permanent , Non-Permanent 


connection

5. Date of connection / /

6. Ancillary equipment installed / connected to the control and indicating equipment.

(See Commissioning Of Cards and Boards) Yes  No 

7. Current drain of ancillary loads powered from the FACP power supply

8. Primary power source voltage

9. Battery type and capacity Manufacturer AH

10. Is maintenance agreement held for the system? Yes  No 

11. Operator's handbook supplied? Yes  No 

12. Logbook supplied? Yes  No 

13. 'As-installed' drawings supplied? Yes  No 

14. Portions of the building not protected by this system are; (Please PRINT)

1 6

2 7

3 8

4 9

5 10

129
MAN2994-7

15. I/We

1.

2.

3.

Print Name/s

Hereby certify that the installation has been thoroughly tested from each actuating device and that a test of
the transmission of the alarm signal to the monitoring service provider has been satisfactorily carried out.

I/We further certify that the whole system and all components called up in Clause 1.3 in connection therewith
are installed entirely in accordance with the current requirements of AS 1670.l, -

Except with regard to the following details which have already been approved, approval attached.

Strike out the bolded sentence if there have not been any exceptions.

Signature Date / /

Installing Company

Please PRINT or Stamp

130
MAN2994-7

23.1 Installation Details


# Indicate with a number in brackets the number of actuating devices in concealed spaces.
* Add addressable loop number in brackets where applicable.

Zone Number and Type of Actuating Devices


Alarm Zone * No of actuating Thermal Fire Flame
MCP Other
# devices per Zone A B C D E Smoke CO IR UV
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

Additional Information:
(Attach if necessary)

Name Company Signature Date

131
MAN2994-7

24 Commissioning Test Report


This FireFinder PLUS Fire Alarm Control Panel is installed at:
Company Name

Street

Suburb

State / Country

Post Code
(Company Name & Installation Address )

Owner or Owners' Authorized Representative:


Company Name

Street

Suburb

State / Country

Post Code

Type of Installation: NEW MODIFIED ADDITION UPGRADE


(Circle)

Date of commissioning tests: / /


Name and address of commissioning company, (in 'BLOCK LETTERS')
Company Name

Street

Suburb

State / Country

Post Code

Commissioning Representative: Name ( Print )

Signature:

132
MAN2994-7

24.1 Procedure
The following tests are the minimum that shall be performed when commissioning a system using the
FireFinder PLUS Fire Alarm Control Panel. Supplements to these tests may be added by way of attachments
or notation (using waterproof ink) to this documentation. If supplements or tests are added reference to
them shall be made at an appropriate point on this document.

This Commissioning Record provides a complete description of the installed system and its tested
performance at the time of being commissioned and should be completed in conjunction with the -.

➢ installer's statement(s); including 'as-installed' drawings; and


➢ detector test records,

24.2 System Information


Check relevant box
GENERAL YES  NO  NA
(a) Equipment: Equipment has been designed and constructed in
accordance with the relevant Standards.   
(b) Installation: Equipment has been located, installed and interconnected
in accordance with the system documentation   
(c) Compatibility: All detectors and other devices used in the system are—
(i) listed in the operator’s manual;   
(ii) compatible with the relevant parts of CIE, particularly that the permitted
number of detectors and other devices for each circuit is not exceeded;   
(iii) installed in an environment for which they are suitable;   
(iv) not set to a sensitivity outside that prescribed in the relevant product
Standard.   
(d) Alarm zone limitations: The alarm zone limitations in Clause 2.4 of AS
1670.1 are not exceeded.   
(e) Primary power source:
(i) The primary power source for the system has been provided in
accordance with AS/NZS 3000.   
(ii) The isolating switch disconnects all active conductors.   
(iii) Five operations of the primary power source switch did not cause an
alarm to be indicated on the system.   
(f) Secondary power source:
(i) The secondary power source is of a suitable type and capacity complying
with the requirements of Clause 3.16.2 of AS 1670.1.   
(ii) The float voltage, charger type and setting is correct and in accordance
with the battery manufacturer’s recommendation.   
(g) Battery temperature and voltage: The battery voltage corresponds to
that specified by the battery manufacturer for the temperature measured   
after 24 hour quiescent operation.

133
MAN2994-7

(h) Alarm zone parameters: Each alarm zone circuit is within the equipment
manufacturer’s specifications.   
(i) Wire-free alarm zones: Wire-free actuating device parameters meet the
minimum parameters specified by the manufacturer,
including that the receiver responds to signals from an actuating device for   
alarm, tamper, low standby power signals and gives a fault signal when the
supervisory signal condition is absent.
(j) Operation of fault and alarm signals: Fault and alarm conditions correctly
detect and indicate as the correct. alarm zone, operating other required   
indicators, and operate relevant outputs of the CIE.

(k) Mimic panel: All mimic panels, annunciators, etc., operate correctly.   
(l) Alarm zone controls: Alarm test, fault test, isolate and reset facility of
each alarm zone operates correctly.   
(m) Alarm dependency: Alarm dependency works correctly and does not
apply to devices listed in Clause 3.3 of AS 1670.1.   
(n) CIE response to actuating device operation: Each actuating device has
operated when tested with a medium suitable for the device type and the   
alarm has indicated on the FIP and at the tested device.
(o) Fault response time: The response to a fault does not exceed 100 s for
each alarm zone circuit.   
(p) Alarm response time: At least one detector in each alarm zone has been
tested and the response to the alarm does not exceed 10 s or the period   
specified when dependency on more than one alarm signal is used.
(q) Supervisory signal response time: At least one supervisory device in each
alarm zone circuit has been tested and the response to the supervisory   
device does not exceed 100 s.
(r) Alarm acknowledgment facility: Alarm acknowledgement facilities
operate in accordance with the requirements of Clause 3.2 AS 1670.1.   
(s) Occupant warning system:

(i) A fault signal is displayed at the CIE when the circuit wiring at the last
speaker or sounder is short or open circuited.   
(ii) Each sounder/speaker operates in accordance with the requirements of
Clause 3.22 of AS 1670.1 and a record of the sound pressure level has been   
made.
(t) The external alarm indication: is visible from the main approach to the
building.   
(u) Manual call points

(i) Each manual call point operates correctly.   


(ii) The activation of manual call points do not cause existing detector alarm
indications to be extinguished.   
134
MAN2994-7

(iii) Manual call points are not subject to alarm dependency.   


(v) Smoke and fire door release: Each door-release device operates
correctly.   
(w) Flame detectors
(i) The number and type of flame detectors provide adequate protection for
the area.   
(ii) There are no ‘blind’ spots in the area protected.   
(iii) Detectors are rigidly fixed.   
(iv) Detector lenses are clean and adequately protected from dust and
extraneous radiation sources.   
(v) Detectors respond to a flame or simulated flame source.   
(x) Multi-point aspirating smoke detectors:
(i) Response time of all sampling points meets the requirements of AS
1670.1.   
(ii) Alarm settings and indicators operate correctly.   
(iii) Remote indication of alarm and fault signals operate correctly.   
(iv) Airflow failure indicator operates correctly.   
(v) System (signal) failure indicators operate correctly.   
(vi) Isolate and reset functions operate correctly.   
(vii) Alarm and fault test facilities operate correctly.   
(y) Duct sampling unit: The alarm indicator is clearly visible from a trafficable
area and the duct air velocity exceeds the minimum velocity specified for
the unit. If not, the measured differential pressure is at least the minimum   
specified for the unit.
(z) Ancillary control functions: Each ancillary control function operates with
the activation of associated alarm zones.   
(aa) Alarm signaling equipment: Alarm signaling equipment initiates a fire
alarm signal to the monitoring service provider.   
(bb) Labeling: Alarm zone location is immediately apparent from the alarm
zone labeling.   

DOCUMENTATION
The following documentation is located in or adjacent to the FIP:
(a) ‘As-installed’ drawings.   
(b) CIE documentation required by AS 4428.1 or AS 7240.2.   
135
MAN2994-7

(c) Commissioning test report.   


(d) Installer’s statement in accordance with Appendix E of AS 1670.1.   
(e) A log complying with the requirements of Clause 7.3 of AS 1670.1.   
(f) Aspirating system design tool calculation.   

136
MAN2994-7

UNCONTROLLED DOCUMENT

NOTE: Due to AMPAC’s commitment to continuous improvement specifications may change without
notice.

137

You might also like