UL, ULC, CSFM Listed; FM 4009 IDNAC Repeater; Power and Distance Extender
Approved; MEA (NYC)
Acceptance*
Features
4009 IDNAC Repeaters provide enhanced power delivery to
TrueAlert/TrueAlert ES addressable notification appliances
controlled by IDNAC SLCs:
• Output voltage in alarm is maintained by an efficient switching
regulator at 29 VDC during both AC input and battery backup
conditions allowing strobes to operate at lower current
• With lower current strobes and regulated output voltage, wiring
distance can be extended 2 to 3 times that of conventional notification,
appliance loading can be increased, or smaller wire gauge can be used,
all resulting in installation savings with high assurance that appliances
that operate during normal system testing will operate during worst
case alarm conditions
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165 0026:0378 for allowable
values and/or conditions concerning material presented in this document. NYC Fire Dept COA #6151. Additional listings may be applicable; contact your local Simplex product supplier for the latest
status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.
Introduction
Repeating IDNAC SLCs
Simplex fire alarm control panels with IDNAC SLC outputs provide individual address and control of TrueAlert and TrueAlert ES addressable notification
appliances. When an IDNAC SLC reaches the current limit or the distance limit of the source IDNAC SLC, use of 4009 IDNAC Repeaters extends the
IDNAC SLC with an additional 3 A of SLC current and up to 139 unit loads of additional supervisory capacity.
With IDNAC SLCs, a constant 29 VDC source voltage is maintained in alarm, even during battery standby, allowing strobes to operate at higher voltage
with lower current and ensuring a consistent current draw and voltage drop margin under both primary power and secondary battery standby.
Efficiencies include wiring distances up to 2 to 3 times farther than with conventional notification, or support for more appliances per IDNAC SLC, or
use of smaller gauge wiring, or combinations of these benefits, all providing installation and maintenance savings with high assurance that appliances
that operate during normal system testing will operate during worst case alarm conditions.
Description
Three wiring configurations
Three wiring configurations are available to provide a variety of system solutions: Class B branch extension, Class A loop extension, and Class A riser to
Class B branch extension or Class A loop output.
Product Selection
Table 1: IDNAC Repeater Selection
Model* Cabinet Color Description
4009-9601(BA) Platinum 4009 IDNAC Repeater with cabinet; provides a single 3 A IDNAC SLC output, 200 mA auxiliary power output,
4009-9602(BA) Red and battery charger; 120/240 VAC, 50/60 Hz input, auto-select
* Model numbers ending with BA suffix are assembled in the USA.
Table 2: Aftermarket Accessories (installed on-site, select per system requirements)
Model Description
4009-9814 Class A Adapter Module, mounts on repeater controller board; required for Class A output
2975-9813 Platinum semi-flush box trim 7
1 / " (37 mm) wide, four corners and trim pieces for top, bottom,
16
2975-9812 Red semi-flush box trim and sides; (will need to be cut to fit 4009 IDNAC Repeater cabinet)
Table 3: External Accessories (select per system requirements)
Model Description Comments
4905-9929 Remote TrueAlert Communications Isolator Refer to data sheet S4905-0001 for details
16 ¼" W x 13 ½" H x 5 ¾" D (413 mm x 343 mm x 146 mm); refer to
4009-9801 External Battery Cabinet for 25 Ah batteries
data sheet S2081-0006 for details
Table 4: Battery Selection (select battery size per system requirements; two batteries are required for 24 VDC operation)
Model Description
2081-9272 6.2 Ah Battery, 12 VDC
2081-9274 10 Ah Battery, 12 VDC
2081-9288 12.7 Ah Battery, 12 VDC
2081-9275 18 Ah Battery, 12 VDC
Requires 4009-9801 External Battery Cabinet
2081-9287 25 Ah Battery, 12 VDC
Wiring Reference, Class A Riser Input with Class A Loop and Class B Branch Outputs
© 2019 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without
notice. Additional listings may be applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co.
Simplex, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are
registered trademarks of the National Fire Protection Association (NFPA).
S4009-0004 Rev. 6 9/2019