Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Ficha Tecnica 880 Kva Ad880-6

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

AD880-6

880 kVA / 704 kW


POWERED by Doosan

DIESEL GENERATING SET 480/277V,380/220V,220/127V- 60 Hz

MODEL AD880‐6
kVA 880
Standby
Power kW 704
Pf. 0.8 kVA 800
Prime
kW 640

Standby: Continuous running at variable load for duration of an emergency. No overload is permitted on these ratings. In accordance with ISO 3046 .
Prime: Continuous running at variable load for unlimited periods with 10% overload available for 1 hour in any 12 hour period. In accordance with ISO 8528,ISO 3046.

 High quality, reliable and complete power unit


 Compact design
 Easy start and maintenance possibility
 Every generating set is subject to a comprehensive test program which includes full load testing, checking and provision of all
control and safety shut down functions testing
 Fully engineered with a wide range of options and accessories: Canopy, sound proof canopy and on-road trailer

Manufacturer reserves the right to make changes in model, technical specifications, color, equipment and accessories without prior notice.

www.aksapowergen.com
ENGINE

DOOSAN
Model DP222LB

Engine Power Output kWm 782


at rated rpm HP 1048.7
Aspiration and Cooling Turbocharged intercooled
Total Displacement Litre 21.927
No. of Cylinders and Build 12-Cyliner ,V-type
Engine Speed rpm 1800
Bore and Stroke mmxmm 128x142
Compression Ratio 15:1
Governor Electronic control
Fuel Consumption at full load L/hr 172.7
Fuel Tank Capacity Litre Open:1000/Canopy:1000
Oil Capacity Litre 40
Coolant Capacity Litre 114
Radiator Cooling Air m³/min 1050
Air Intake – Engine m³/min 56
Exhaust Gas Flow m³/min 124

 Heavy duty DOOSAN diesel engine  Cooling radiator and fan


 Four stroke, water cooled  Starter battery (with lead acid) including Rack and Cables
 Direct injection fuel system  Flexible fuel connection hoses and manual oil sump drain valve
 Electronic Governor system  Industrial capacity exhaust silencer and steel bellows
 12/24 V D.C. starter and charge alternator  Jacket water heater(at automatic models)
 Replaceable fuel filter, oil filter and dry element air filter  Operation manuals and circuit diagram documents

ALTERNATOR

Design Brushless single bearing, revolving field


Stator 2/3 pitch
Rotor Single bearing, flexible disc
Insulation System Class H
Standard Temperature Rise 125 - 163°C Continuous
Exciter Type Self Excited
Phase Rotation A (U), B (V), C (W)
Alternator Cooling Direct drive centrifugal blower fan
AC Waveform Total Harmonic Distortion No load < 1.5%. Non distorting balanced linear load < 5%
Telephone Influence Factor (TIF) <50 per NEMA MG1-22.43
Telephone Harmonic Factor (THF) <2%

 Brushless, single bearing system, flexible disc, 4 poles  Impregnation with tropicalised epoxy varnish
 Insulation class H  Solid state Automatic Voltage Regulator
 Standard degree of protection IP21 (*IP22/IP23 is available.)  Stator winding with 2/3 pitch for improved harmonics
 Self-exciting and self-regulating

www.aksapowergen.com
CONTROL SYSTEM

Control supervision and protection panel is mounted on the genset base frame.
The control panel is equipped as follows:

1. Auto Mains Failure Control Panel


Panel equipments:
 Control with AMF module
 Static battery charger
 Emergency stop push button
DSE 7320

a) Generating set control module DSE 7320 features: c) Alarms:


 The module is used to monitor a mains supply and starts and stops a  Over and Under Speed
standby generating set  Low and High Battery Volt.
 Micro-processor based design  Start and Stop Failure
 Automatic control of mains and generator contactors  Charge fail
 Monitors engine performance and AC power output  Over Current
 LED alarm indication  Under / Over Generator Voltage
 Front panel configuration of timers and alarm trip points  Low Oil Pressure
 Easy push button control  Emergency stop
STOP/RESET - MANUAL –TEST- AUTO – MUTE ALARM – START  High engine temperature
 kW overload
b) Metering via LED display:  Unbalanced load
 Generator Volts (L-L / L-N)  Independent earth fault trip
 Engine oil pressure (PSI-Bar)
 Generator Ampere (L1,L2,L3) d) LED indications
 Engine temperature (°C&°F) Four configurable LED’s like:
 Generator Frequency (Hz)  Mains available
 Plant battery volts  Generator available
 Engine hours run  Mains on load
 Mains Volts (Ph-Ph/Ph-N)  Generator on load
 Generator kVA, kWh
 Generator kW as % of rated kW setting
 Generator Cos (σ)

2. Power Outlet Terminal Board Mounted on the Genset Base Frame

OPTIONAL EQUIPMENTS

Diesel Engine Panel Accessories


 Oil heater  Charge ammeter  Bulk fuel tank
 Transfer Switch 3 Pole  Automatic filling system
Alternator  Transfer Switch 4 Pole  Fuel-water separator filter
 3/4 Pole Output Circuit Breaker  Earth Fault ,single set  Low fuel level alarm
 Anti-condensation Heater  Residential silencer
 Enclosure or sound proof canopy
 Trailer
 Manual oil drain pump
 Tool kit for maintenance

www.aksapowergen.com
CHASSIS

 The complete gen-set is mounted as whole on a heavy-duty fabricated, steel base frame
 Anti-vibration pads are fixed between the engine/ alternator feet and the base frame
 Base frame design incorporates an integral fuel tank (Up to 1000 kVA)
 The generating set can be lifted or carefully pushed / pulled by the base frame
 Dial type fuel gauge and drain plug on the fuel tank
 Forklift pockets within base frame (up to 500kVA)

DIMENSIONS

OPEN TYPE
DIMENSIONS (LxWxH) mm 4500x1550x2302
DRY WEIGHT kg 4725
SOUND ATTENUATED TYPE
DIMENSIONS (LxWxH) mm 5813x1606x2652
DRY WEIGHT kg 5820

CANOPY

 All canopy parts are designed with modular principles  Exhaust silencer is protected against environment influences
 Without welding assembly  Thermally insulated engine exhaust system
 Doors on each side  Emergency stop push button is installed outside of the canopy
 All metal canopy parts are painted by electrostatic  Easy lifting and moving
polyester powder paint  Easy maintenance and operation

Aksa Power Generation


Ruzgarlibahce Mahallesi - Özalp Cikmazi No:10 34805 Kavacik Beykoz - Istanbul / Turkey
Tel:+90 212 444 46 30 E-mail: aksa@aksapowergen.com
www.aksapowergen.com
Aksa Power Generation is a member of www.aksa.com.tr