PowerFlex700DC en
PowerFlex700DC en
PowerFlex700DC en
USER MANUAL
PowerFlex, DriveExplorer, DriveTools SP, DPI, and SCANport are either trademarks or registered trademarks of Rockwell Automation, Inc.
Klixon® is a registered trademark of Sensata Technologies, Inc.
Manual Updates The information below summarizes the changes to the PowerFlex Digital
DC Drive User Manual, publication 20-UM001… since the October 2007
release.
Change Page(s)
Updated the Using Contactors section to include new Contactor Control selections 1-9
for configuring AC versus DC contactors.
Added the “Cable and Wiring Recommendations” table. 1-14
Updated the “Typical Power Wiring Diagrams” to include terminal and parameter 1-17
designations.
Added “Sourcing Digital Outputs, 24V DC external supply” diagram to I/O Wiring 1-39
examples.
Added an illustration and instructions for routing I/O and control wiring. 1-42
Added a graphical indicator for parameters accessible only when parameter 211 3-1
[Param Access Lvl] = 1 “Advanced”.
Added parameter 1409 [Jog Off Delay], to allow you to specify the minimum delay 3-24
between removing the Jog input and commanding the main contactor to open.
This delay reduces the wear on the contactor when repeatedly opening and
closing the Jog input over a short period of time.
Added parameter 1410 [Jog Ramp Time], to allow you to set the rate of 3-29
acceleration and deceleration while the Jog function is active.
Changed option 3 "Quick Stop" to "Fast Stop" for parameters 354 [Aux Inp Flt Cfg] 3-53
and 365 [OverTemp Flt Cfg].
Changed option 35 “Fld Weak En” to “Force MinFld” for parameters 133-144 3-65
[Digital Inx Sel].
Added option 64 “Invert Flt” to parameters 133-144 [Digital Inx Sel], to allow a 3-65
digital input wired to an inverting fault device to issue an “Inverting Fault” (F37).
Updated the options for parameter 1391 [ContactorControl] to accommodate the 3-67
use of a AC or DC contactor with or without a dynamic brake resistor.
Added the new “Inverting Fault” (F37) fault to indicate that the associated inverting 4-5
fault device has opened.
Updated the following drive specifications: A-2
• Maximum short circuit rating
• Control speed regulation
• Torque regulation
Updated the fuses identified in the “Drive Power Circuit Protection” tables. A-7
Updated the “Control Power Circuit Protection Fuses” tables and fuse location A-15
illustrations.
Added the “Lug Kit Specifications” table. A-21
Added the instructions for operating the PowerFlex DC drive in field weakening C-5
mode and using a DC contactor and/or an inverting fault device in the armature
circuit with firmware version 1.006.
Updated the “Fine Tuning the Speed Regulator” procedure. C-29
Updated the terminal numbers indicated in the Digital Inputs/Outputs block D-3
diagram.
Updated the Ramp Reference block diagram to include the new parameter 1410 D-7
[Jog Ramp Time].
Removed the 20-COMM-L communication adapter from the compatible E-1
Communication Adapter Kits table.
Preface Overview
Who Should Use this Manual? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p-1
What is in this Manual?. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p-1
Drive Storage Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p-1
Drive Nameplate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p-2
Drive Frame Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p-2
Reference Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p-2
Manual Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p-3
General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p-3
Catalog Number Explanation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p-4
Chapter 4 Troubleshooting
Faults and Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Drive Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
HIM Indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Manually Clearing Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Fault Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Clearing Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Alarm Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Common Drive Symptoms and Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
Drive will not start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
Drive starts but motor does not turn and no armature current. . . . . . . . . . . . . . . . . . . 4-12
The motor does not reach commanded speed.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
The motor is turning in the wrong direction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
The motor reaches maximum speed immediately.. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
Testpoint Codes and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
Index
Overview
The purpose of this manual is to provide you with the basic information
needed to install, start-up and troubleshoot the PowerFlex DC drive.
For information on . . . See page . . .
Who Should Use this Manual? Preface-1
What is in this Manual? Preface-1
Drive Storage Conditions Preface-1
Drive Nameplate Data Preface-2
Reference Materials Preface-2
Drive Frame Sizes Preface-2
Manual Conventions Preface-3
General Precautions Preface-3
Catalog Number Explanation Preface-4
Who Should Use this This manual is intended for qualified personnel. You must be able to
Manual? program and operate DC drives. In addition, you must have an
understanding of the parameter settings and functions detailed in this
manual.
What is in this Manual? The PowerFlex DC User Manual is designed to provide installation, basic
start-up information, and drive parameter definitions. For detailed drive
information, please refer to “Reference Materials” on page Preface-2 for a
list of additional publications.
Drive Storage Conditions If it is necessary to store the drive for any length of time before installation,
follow these storage guidelines in order to ensure satisfactory operation at
start up and to maintain warranty coverage:
• After receipt and inspection, repack the drive in its original shipping
container and store in a clean, dry place.
• Place where the relative air humidity range does not exceed 5% - 95%.
• At an altitude of less than 3,000 meters (10,000 ft.) above sea level.
Drive Nameplate Data The PowerFlex DC drive contains a data nameplate located on the side of
each drive that identifies the specific model number design, applicable AC
input power and DC output power data. All communication with Rockwell
Automation personnel concerning this product should include this
information.
LY
Marks Location.
Output: 500VDC 4.1A REGEN 1.0HP N223
C R
US
ON
1 Min Overload Amps 6.2 Listed
3 Sec Overload Amps 8.2
Ind. Cont.
Eq. 31KF Refer to the data
DC Field: nameplate label
E
Input: 460VAC 50/60 Hz 10A max. 1 Phase
PL
on your drive for
Output: 360VDC 10A max.
actual agency
AM
Regulator Power: 115/230VAC 50/60 Hz 1.0/0.5A 1 Phase certifications.
EX
MFD. in 2XXX on MMM DD Frame: A
Serial Number: A23E0042
Made in Italy
Drive Frame Sizes Similar PowerFlex DC drive sizes are grouped into frame sizes to simplify
spare parts ordering, dimensioning, etc. Refer to the Catalog Number
Explanation on page Preface-4 for a list of drive catalog numbers and their
respective frame sizes.
Reference Materials The following manuals are recommended for general drive information:
Title Publication Available Online at . . .
Preventive Maintenance of Industrial Control and DRIVES-TD001…
Drive System Equipment
Safety Guidelines for the Application, Installation SGI-1.1
and Maintenance of Solid State Control www.rockwellautomation.
com/literature
A Global Reference Guide for Reading Schematic 100-2.10
Diagrams
Guarding Against Electrostatic Damage 8000-4.5.2
Manual Conventions • To help differentiate parameter names and LCD display text from other
text, the following conventions will be used:
General Precautions
ATTENTION: This drive contains ESD (Electrostatic
! Discharge) sensitive parts and assemblies. Static control
precautions are required when installing, testing, servicing or
repairing this assembly. Component damage may result if ESD
control procedures are not followed. If you are not familiar with
static control procedures, reference A-B publication 8000-4.5.2,
“Guarding Against Electrostatic Damage” or any other applicable
ESD protection handbook.
ATTENTION: An incorrectly applied or installed drive can
! result in component damage or a reduction in product life. Wiring
or application errors, such as, undersizing the motor, incorrect or
inadequate AC supply, or excessive surrounding air temperatures
may result in malfunction of the system.
ATTENTION: Only qualified personnel familiar with DC drives
! and associated machinery should plan or implement the
installation, start-up and subsequent maintenance of the system.
Failure to comply may result in personal injury and/or equipment
damage.
ATTENTION: An incorrectly applied or installed bypass system
! can result in component damage or reduction in product life. The
most common causes are:
• Wiring AC line to drive output or control terminals.
• Improper bypass or output circuits not approved by
Allen-Bradley.
• Output circuits which do not connect directly to the motor.
Contact Allen-Bradley for assistance with application or wiring.
Catalog Number
Explanation
Position
1-3 4 5 6 7 8-10 11 12 13 14 15 16
20P 4 1 A D 4P1 R N 0 N N N
a b c d e f g h i j k l
a f1 g
Drive 230V, 60 Hz Input Field Supply
Code Type Armature Field Code Type
Code Hp Frame
Amps Amps A Three-Phase Regulated
20P PowerFlex DC
7P0 1.5 7 A 10 F Fixed Field w/Economy
9P0 2 9 A 10 R Single-Phase Regulated
b 012 3 12 A 10
Most start-up difficulties are the result of incorrect wiring. Every precaution
must be taken to assure that the wiring is done as instructed. All items must
be read and understood before the actual installation begins.
Important: The PowerFlex DC drive is not designed for use with multiple
motor applications.
MOD
NET A
NET B
PORT
MOD
NET A STS
NET B
STS
10 mm 10 mm 10 mm 50 mm Airflow through
(0.4 in.) (0.4 in.) 150 mm (6.0 in.) (0.4 in.) (2.0 in.) the drive must
not be impeded.
Mounting Dimensions and The PowerFlex DC drive is available in a NEMA/UL Type Open, IP20
Weights enclosure. Following all mounting instructions in order to ensure proper
operation.
A C
PORT
MOD
NET A
NET B
STS
B B1
A1
A C
A1
PORT
MOD
NET A
NET B
STS
B1 B
A2
A1 C
B4
PORT
MOD
NET A
NET B
B1 STS
B2
B3
Lifting PowerFlex DC Drives The dimensions and weights specified above must be taken into
consideration when mounting the device. Use the proper equipment to
safely lift and hold the weight of the drive while mounting.
Important: Verify that all mounting screws are properly tightened before
and after drive operation.
1. Verify the hole pattern on the panel to which the drive will be mounted.
Refer to Figure 1.4 on page 1-5.
2. Insert, but do not tighten, one bolt in one of the top holes in the panel.
The bolt must be fully threaded into the panel before hanging the drive.
3. Insert the properly sized and rated lifting hooks into the holes on the
lifting flanges at the top of the drive. To limit the pull in forces on the
drive, the lifting devices connected to the hooks must be long enough to
make the angle between the chain or cable and a vertical line extending
up from the flange center less than 45 degrees as illustrated below.
Figure 1.5 Lifting Angle
Lifting flange
4. Lift the drive into place on to the bolt installed in the panel.
5. Install the remaining five bolts into the panel. Tighten all bolts to a
torque of 22.6 N•m (200 lb•in).
Removing the Drive Covers The lower protective cover must be removed in order to access the drive’s
power and I/O terminals. The upper cover only needs to be removed to
install an optional communication adapter and service the drive. (Refer to
Installing a Communication Adapter on page E-1 for information.)
Frame A Drives
You must remove both the lower protective cover and the power terminal
cover on frame A drives to access the power terminals.
Remove the two screws as shown below and slide the cover down and off
the chassis.
Figure 1.6 Frame A Power Terminal Cover Removal
PORT
MOD
NET A
NET B
STS
Line Reactors / Filters When connecting the drive directly to the main distribution system an AC
line reactor must be used to guard against system disturbance. The type of
line reactor used depends upon the following:
Refer to AC Input Line Reactors and AC Input Contactors on page A-17 for
a list of recommended AC line reactors.
Using Contactors When using an AC input contactor, the IEC AC1 rating of the contactor
must be equal to the rated thermal (RMS) current value at the mains input of
the drive.
❏ Set one [Relay Out x Sel] parameter and one [Digital Inx Sel] to
“Contactor” (default value for parameters 1392 [Relay Out 1 Sel]
and 140 [Digital In8 Sel])
❏ Set one [Relay Out x Sel] parameter (1392 [Relay Out 1 Sel] or 629
[Relay Out 2 Sel]) to “Contactor” and the other relay output to
“ContactorDB”
(1)
Par 1391 [ContactorControl] is contained in the “Advanced” parameter configuration group. Refer to How
Parameters are Organized on page 3-3 for more information.
AC Input Contactors
Refer to AC Input Line Reactors and AC Input Contactors on page A-17 for
a list of recommended AC input contactors.
DC Output Contactors
A DC output contactor can be used to connect the output of the armature
circuit to the DC motor. If a DC output contactor is used, an AC input
contactor is not needed.
(1)
Par 1391 [ContactorControl] is contained in the “Advanced” parameter configuration group. Refer to How
Parameters are Organized on page 3-3 for more information.
Control Power Protection The 115V / 230V AC control circuit power input terminals U2 and V2 are
required to be short circuit protected. This protection can be provided by
using standard time delay fuses or a circuit breaker.
The time delay fuses or circuit breaker must be selected to survive the short
circuit available current of the feeder source for this circuit and the inrush
current of the drive’s power supply.
The rating of the fuses or circuit breaker should be sized mainly to protect
the wiring from the fuses/circuit breaker connections to terminals U2 and
V2, and not nuisance trip or blow from the inrush current.
The table below lists the input current characteristics of the control power.
Table 1.D Control Power Protection
Drive Current Control Power Supply
Rating Code(1) Rated input current Inrush input current
Frame 230V 460V Board ID Power 115V 230V 115V 230V
7P0 4P1
A through through SW1-31 60 W 1A 0.5 A 20 A 10 A
110 129
146 167
B&C through through SW2-32 110 W 1.2 A 0.7 A 15 A 7.5 A
521 667
(1)
Refer to Catalog Number Explanation on page Preface-4, positions 8-10 for corresponding drive HP rating,
armature amp rating and field amp rating.
General Grounding The drive Safety Ground - PE must be connected to system ground.
Requirements Ground impedance must conform to the requirements of national and local
industrial safety regulations and/or electrical codes. The integrity of all
ground connections should be periodically checked.
For installations within a cabinet, a single safety ground point or ground bus
bar connected directly to building steel should be used. All circuits
including the AC input ground conductor should be grounded
independently and directly to this point/bar.
PORT
MOD
NET A
NET B
STS
PE1/
W
U
C
D
V
AC Line
Reactor
Earth
AC Mains Supply
L1
L2
Power Feeder
Each power feeder from the substation transformer to the drive must be
provided with properly sized ground cables. The conduit or cable armor
should be bonded to the substation ground at both ends. Each transformer
enclosure and/or frame must be bonded to ground at a minimum of two
locations.
Power Circuit Protection It is recommended that you install the PowerFlex DC drive with fast acting
fuses to protect the armature converter on the AC input and DC output (for
four quadrant drives only) sides. Internally mounted fuses for armature
converter protection are provided with 230V, 521A and 460V, 495A and
667A frame C PowerFlex DC drives. Refer to Drive Power Circuit
Protection on page A-7 for a list of replacement fuses and general fuse
locations.
Cable and Wiring Use the following cable and spacing recommendations for all drives sizes:
Recommendations
Minimum Spacing Between Classes
Steel Conduit/Tray
See Spacing
Wiring Notes,
Category Class Signal Definition Signal Example Cable Type 1 2/3/4 5/6 7/8 9/10/11 page 1-15
Power 1 AC Power (600V 2.3kV 3/ph AC Lines Per NEC & 0 3/9 in. 3/9 in. 3/18 in. See Note 6 1/2/5
Or Greater) Local Codes (76/229 mm) (76/229 mm) (76/457 mm)
2 AC Power (Less 460V 3/ph AC Lines 3/9 in. 0 3/6 in. 3/12 in. See Note 6 1/2/5
Than 600V) (76/229 mm) (76/152 mm) (76/305 mm)
3 DC Power DC Motor Armature
4 DC Power DC Motor Field
Control 5 115V AC/DC Relay Logic/PLC I/O 3/9 in. 3/6 in. 0 3/9 in. See Note 6 1/2/5
Logic Motor Thermostat (76/229 mm) (76/152 mm) (76/229 mm)
115V AC Power Power Supplies,
Instruments
6 24V AC/DC Logic PLC I/O
Signal 7 Analog Signals, Reference/feedback Shielded Cable 3/18 in. 3/12 in. 3/9 in. 0 1/3 in. 2/3/4/5
(Process) DC Supplies Signal, 5 To 24V DC – Belden 8735, (76/457 mm) (76/305 mm) (76/229 mm) (25/76 mm)
Digital (Low TTL 8737, 8404
Speed)
8 Digital (High I/O, Encoder, Count Shielded Cable
Speed) Pulse Tach – Belden 9728,
9730
Signal 9 Serial RS-232 Shielded Cable See Note 6 1/3 in. 0 –
(Comm.) Communication (20-COMM-R), 422 – Belden (25/76 mm)
To Terminals/ RS-232 –
printers 8735, 8737
RS-422 –
9729, 9730
11 Serial PLC Remote I/O, Twinaxial
Communication PLC Data Highway Cable –
(Greater Than Belden 9463,
20k Baud) A-B 1770-CD
Example:
Spacing Notes:
1. Both outgoing and return current carrying conductors are to be pulled in same conduit or laid adjacent in
tray.
2. Cables of the following classes can be grouped together.
A. Class 1; Equal to or above 601 volts.
B. Classes 2, 3 and 4 may have their respective circuits pulled in the same conduit or layered in the same
tray.
C. Classes 5 and 6 may have their respective circuits pulled in the same conduit or layered in the same
tray. Note: Bundle may not exceed conditions of NEC 310.
D. Classes 7 and 8 may have their respective circuits pulled in the same conduit or layered in the same
tray. Note: Encoder cables run in a bundle may experience some amount of EMI coupling. The circuit
application may dictate separate spacing.
E. Classes 9, 10 and 11 may have their respective circuits pulled in the same conduit or layered in the
same tray. Communication cables run in a bundle may experience some amount of EMI coupling and
corresponding communication faults. The application may dictate separate spacing.
3. All wires of class 7 through 11 MUST be shielded per the recommendations.
4. In cable trays, steel separators are advisable between the class groupings.
5. If conduit is used, it must be continuous and composed of magnetic steel.
6. Spacing of communication cables classes 2 through 6 is:
CONDUIT SPACING: THROUGH AIR:
115 Volts – 1 in. (25 mm) 115 Volts – 2 in. (51 mm)
230 Volts – 1.5 in. (38 mm) 230 Volts – 4 in. (101.5 mm)
380/575 Volts – 3 in. (76 mm) 380/575 Volts – 8 in. (203 mm)
575 volts – proportional to 6 in. (152 mm) per 575 volts – proportional to 12 in. (305 mm) per 1000
1000 volts. volts.
DC Output Voltages
The output voltages below take into account an AC input undervoltage
within the stated tolerance limits and a voltage drop of 4% due to an AC
input line reactor. It is the same as the rated armature voltage suggested for
the connected motor.
Armature Circuit
AC Input Voltage DC Output Armature Voltage (Terminals C & D)
(Terminals U, V, W) Two Quadrant Drive Four Quadrant Drive
230V ±10 %, 3Ph 260V 240V
400V ±10 %, 3Ph 470V 420V
440V ±10 %, 3Ph 530V 460V
460V ±10 %, 3Ph 560V 480V
480V ±10 %, 3Ph 580V 500V
Field Circuit
AC Input Voltage DC Output Field Voltage(1) (Terminals C1 & D1)
(Terminals U1 & V1) Fixed Field Adjustable Field
230V ±15 %, 1Ph 200V 200V
400V ±15 %, 1Ph 310V 310V
460V ±10%, 1Ph 360V 360V
(1)
The max field voltage is equal to 0.85 x AC input line voltage
(1)
34 (on I/O TB4) (2)
FU1
(N.O. Relay) C
M1 AC Contactor
Aux 19 (+24V - on I/O TB2)
13 14
FU3 A1
L1 T1
L1 U
FU4
L2 T2
L2
FU5
V
M
L3 T3
3 Phase AC line L3 W
A1 A2 A2
FU8 FU9
PowerFlex DC (2)
FU2
Drive D
Control
U2 Board P/S
460V 115V V2
(3) Control Power /
35 Relay Terminal
(3)
36 Block
FU6
F1
U1 C1
FU7 Field Power
V1 Terminal Block D1
F2
(1)
Par 140 [Digital In8 Sel] set to 31 “Contactor”
(2) Armature output fuses are required on four quadrant and are recommended on two quadrant Frame A and B drives. Fuses with Trip Indicator
Switches are recommended for Inverting Fault protection when the motor will be Field Weakened and run above base speed. Refer to Figure 1.13 on
page 1-19.
(3)
Par 1391 [ContactorControl] = 1 “AC Cntctr” and Par 1392 [Relay Out 1 Sel] = 25 “Contactor”. Important: Terminal 35 and 36 are on the Control
Power / Relay Terminal block, NOT the I/O terminal blocks. See Figure 1.20 through Figure 1.22.
(1)
34 (on I/O TB4)
(N.O. Relay)
M1 DC Contactor
Aux
19 (+24V on I/O TB2) 13 14
(2)
FU1
FU3 L1 T1
C
L1 U
FU4 L2 T2
D
L2 V
FU5 A1 A2
A1
3 Phase AC line L3 W
PowerFlex DC
FU8 FU9 Drive M
A2
Control (2)
U2 Board P/S FU2
460V 115V V2
(3) Control Power /
35 Relay Terminal
(3)
36 Block
FU6
F1
U1 C1
FU7 Field Power
V1 Terminal Block D1
F2
(2)
Armature output fuses are required on four quadrant and are recommended on two quadrant Frame A and B drives. Fuses with Trip Indicator
Switches are recommended for Inverting Fault protection when the motor will be Field Weakened and run above base speed. Refer to Figure 1.13 on
page 1-19.
(3) Par 1391 [ContactorControl] = 3 “DC Cntctr” and Par 1392 [Relay Out 1 Sel] = 25 “Contactor”. Important: Terminal 35 and 36 are on the Control
Power / Relay Terminal block, NOT the I/O terminal blocks. See Figure 1.20 through Figure 1.22.
Figure 1.12 Power Wiring with DC Output Contactor and a Dynamic Brake
(1)
34 (on I/O TB4)
(N.O. Relay)
M1 DC Contactor
Aux
19 (+24V on I/O TB2) 13 14
FU3 L1 T1
C
L1 U
FU4 L2 T2
D FU1
(2)
L2 V
A1 A2 A1 L2 L1 13
FU5
Aux
3 Phase AC line L3 W
PowerFlex DC A2 T2 T1 14 A1
(2)
Armature output fuses are required on four quadrant and are recommended on two quadrant Frame A and B drives. Fuses with Trip Indicator
Switches are recommended for Inverting Fault protection when the motor will be Field Weakened and run above base speed. Refer to Figure 1.13 on
page 1-19.
(3)
Par 1391 [ContactorControl] = 4 “DC Cntctr+DB”, Par 1392 [Relay Out 1 Sel] = 25 “Contactor”, and Par 629 [Relay Out 2 Sel] = 24 “ContactorDB”.
Important: Terminal 35, 36, 75 and 76 are on the Control Power / Relay Terminal block, NOT the I/O terminal blocks. See Figure 1.20 through Figure
1.22.
Figure 1.13 Power Wiring with Armature Output Fuses and Inverting Fault Status
(1)
FU1
A1
PowerFlex DC M
Drive (1)
A2
FU2
(2)
33 (on I/O TB4)
(1)
Armature output fuses are required on four quadrant and are recommended
on two quadrant Frame A and B drives. Fuses with Trip Indicator Switches are
19 (+24V on I/O TB2) recommended for Inverting Fault protection when the motor will be Field
Weakened and run above base speed.
(2) Par 139 [Digital In7 Sel] set to 64 “Invert Flt”.
Front View
Note: Front view of drive shown with bottom protective and power terminal covers removed.
Refer to Removing the Drive Covers on page 1-7 for information on removing the drive covers.
PE U C V D W
PE U C V D W
Front View
PE U C V D W
Bottom View
Frame
Rating Code(1) Terminal Bolt Tightening Torque
230V 460V Terminals Wire Size and Type Size (mm) (N•m / lbs•in)
A 7P0 4P1
9P0 6P0
012 010
020 014
– 019 U, V, W, C, D, PE 5 6 / 53
029 027
038 035
055 045
– 052
073 073
093 086
110 – U, V, W, C, D, PE Terminal Block 12 / 106
– 100
– 129
B 146 167 U, V, W, C, D 10 50 / 442.5
PE 8 25 / 221
180 – U, V, W, C, D 10 50 / 442.5
PE 8 25 / 221
218 207 U, V, W, C, D See Cable and Wiring 10 50 / 442.5
Recommendations on
PE page 1-14 8 25 / 221
265 250 U, V, W
10 50 / 442.5
C, D
PE 8 25 / 221
– 330 U, V, W
10 50 / 442.5
C, D
PE 8 25 / 221
360 412 U, V, W
10 50 / 442.5
C, D
PE 8 25 / 221
434 – U, V, W
10 50 / 442.5
C, D
PE 8 25 / 221
C 521 495 U, V, W
10 50 / 442.5
C, D
PE 8 25 / 221
– 667 U, V, W
10 50 / 442.5
C, D
PE 8 25 / 221
(1)
See to Catalog Number Explanation on page Preface-4, positions 8-10 for corresponding drive HP rating,
armature amp rating and field amp rating.
U1
V1
C1
D1
Bottom of Drive
U1
V1
C1
D1
Top of drive
Front of drive
D1 C1 U1 V1
Compare the field current value of the motor to the rated value of the
internal field converter of the drive (see Table 1.G below) and set switch
S14 to the closest value.
Note: The configuration of switch S14 is not required if the motor’s field
control is provided via an external source, however, in this case it is
recommended that the switch settings be completed as described above.
Table 1.G DIP Switch S14 Field Current Configuration Settings
Equivalent
Switch ohms 148 330 182 36.4 845 1650 Resistance
Field current
scale S14-1 S14-2 S14-3 S14-4 S14-5 S14-6 S14-7 S14-8
1.0 A OFF OFF OFF OFF OFF ON 1650 ohm
2.0 A OFF OFF OFF OFF ON OFF 845 ohm
3.0 A OFF OFF OFF OFF ON ON 558.8 ohm
5.0 A OFF ON OFF OFF OFF OFF 330 ohm
10.0 A ON OFF OFF OFF OFF OFF Not used 168 ohm
12.9 A ON OFF OFF OFF ON ON 129.2 ohm
17.2 A OFF ON ON OFF ON ON 97 ohm
20.0 A ON OFF ON OFF OFF ON 83 ohm
24.1 A ON ON ON OFF OFF OFF 69 ohm
Relay Outputs
Maximum Maximum
Terminals Description Voltage Current
35, 36 Normally open contact. Configured with parameter 1392 [Relay
Out 1 Sel] - set to 25 “Contactor” by default.
75, 76 Normally open contact. Configured with parameter 629 [Relay 250V AC 1A
Out 2 Sel] - set to 5 “Ready” by default.
78, 79 Motor thermistor connections (PTC)
Terminals 35 and 36 and 75 and 76 are N.O. relay outputs. The relay output
between terminals 35 and 36 is configured with parameter 1392 [Relay Out
1 Sel]. The relay output between terminals 75 and 76 is configured with
parameter 629 [Relay Out 2 Sel]. See Using Contactors on page 1-9 for
more information.
Thermistors (PTC)
PTC thermistors fitted in the motor can be connected directly to the drive
via terminals 78 and 79. In this case the 1k ohm resistor is not required
between terminals 78 and 79.
Table 1.H Relay Outputs and Thermistor/Thermal Switch Wire Sizes and
Specifications
Wire Size and Type(1) Tightening
Flexible Multi-core Torque
Signal Type Terminals (mm2) (mm2) AWG N•m (lb•in)
Relay Outputs 35 & 36, 75 & 76
Thermistor and 78 & 79 0.140 - 1.500 0.140 - 1.500 26-14 0.5 (4.4)
Thermal Switches
(1)
See Cable and Wiring Recommendations on page 1-14 for more information.
Figure 1.20 Frame A Relay and Thermistor/Thermal Switch Terminal Block Locations
Figure 1.21 Frame B Relay and Thermistor/Thermal Switch Terminal Block Locations
78 79 35 36 75 76
Figure 1.22 Frame C Relay and Thermistor/Thermal Switch Terminal Block Locations
35 36 75 76 78 79
U2 V2
U2 V2
U2 V2
The SA-SB
terminal block is
located at the top
of the drive.
Front of drive
Switching Power Supply board SA-SB terminals Back of Control EMI shield
XSW connector
To access the SA-SB terminal block:
1. Remove the top protective cover from the drive. 2. Disconnect cables XFCD and XR.
3. Loosen 3. Loosen
captive captive
screws. screws.
4. Lower EMI
shield and
disconnect
cable XSW
from Switching
Power Supply
board (see
above).
Figure 1.28 Frame C Heatsink Cooling Fan and Internal Fuse Signal Terminal Block
Locations
81 82 U3 V3
I/O Wiring Observe the following points when installing I/O wiring:
= ON
➏
S15
= OFF
1
2
3
4
5
6
7
8
1
=OFF
➊S3
2
3
4
5
RST
S2
6
ACT
S1
7
RUN
8
PWR
➑ S14 ➎ S0
S20
➐
S12 S18
➋
➌ ➍
1
S4
2
➒ ON
3
4
S11
5
S10
S21
6
S9
7
8
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
ENC_5 ENC_12
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 DEBUG
- A B C+ A+ A- B+ B- Z+ Z- COM +V 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
- A B C + A+ A- B+ B- Z+ Z- COM +V
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Table 1.L Control Circuit Board Jumper and DIP Switch Settings
Jumper/ Factory
ID Switch Function Default
S0 For factory boot flashing only. Leave set to the factory setting. Jumper Off
➊ Jumper On Firmware boot
Jumper Off Normal function
S1 For factory boot flashing only. Leave set to the factory setting. Jumper Off
Jumper On Write firmware boot code
Jumper Off Boot code on flash is protected
S2 Not used. Leave set to the factory setting. Jumper Off
S3 For factory boot flashing only. Leave set to the factory setting. Jumper Off
Jumper On Reset
Jumper Off Normal function
S4 Configures the input voltage of the DC analog tachometer. 90V
➋ Refer to Table 1.M on page 1-34 for configuration.
S9 Configures the input signal of Analog Input 1 (terminals 1 and 2): On
➌ Off Position 0 - 20 mA / 4 - 20 mA
On Position 0 - 10V / ±10V
Note: The input signal type must also be programmed accordingly
using Par 71 [Anlg In1 Config].
S10 Configures the input signal of Analog Input 2 (terminal 3 and 4): On
Off Position 0 - 20 mA / 4 - 20 mA
On Position 0 - 10V / ±10V
Note: The input signal type must also be programmed accordingly
using Par 76 [Anlg In2 Config].
S11 Configures the input signal of Analog Input 3 (terminals 5 and 6): On
Off Position 0 - 20 mA / 4 - 20 mA
On Position 0 - 10V / ±10V
Note: The input signal type must also be programmed accordingly
using Par 81 [Anlg In3 Config].
S12 Not used. Leave set to the factory setting. Off
➍
S14 Field current resistors setting, see Table 1.G on page 1-25. Minimum
➎ field current
Important: In addition, the value selected with switch S14 must be rating
entered in Par 374 [Drv Fld Brdg Cur] in the control based on
software when the drive is commissioned. drive size.
S15 Configuration of the control circuit board to the appropriate drive size. Armature
➏ Leave set to the factory setting, unless the control board has been current
supplied as a spare part. Refer to Table 1.N on page 1-34 and Table based on
1.O on page 1-35 for switch configuration based on drive current drive size.
rating code.
S18 Not used. Leave set to the factory setting. Off
➐
S20 Monitoring of the Z channel of the Digital Encoder on connector XE2: On
➑ Off Position Z-channel monitored
On Position Z-channel not monitored
S21 Encoder power supply voltage and input selection: 12-15 V
➒ Note: When control power is supplied to the drive, the appropriate
LED lights to indicate the selection of the switch.
ENC_5 +5 V encoder (+2.5 - 5.4V input range)
ENC_12 +12-15 V encoder (+5.4V - 15.2V input range)
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Table 1.N Drives with 230V Input - DIP Switch S15 Configuration
Frame
Drive Current
Rating Code S15-1 S15-2 S15-3 S15-4 S15-5 S15-6 S15-7 S15-8
A 7P0 ON OFF OFF OFF OFF OFF OFF OFF
9P0 OFF ON OFF OFF OFF OFF OFF OFF
012 ON ON OFF OFF OFF OFF OFF OFF
020 OFF OFF ON OFF OFF OFF OFF OFF
029 ON OFF ON OFF OFF OFF OFF OFF
038 OFF ON ON OFF OFF OFF OFF OFF
055 ON ON ON OFF OFF OFF OFF OFF
073 OFF OFF OFF ON OFF OFF OFF OFF
093 ON OFF OFF ON OFF OFF OFF OFF
110 OFF ON OFF ON OFF OFF OFF OFF
B 146 ON ON OFF ON OFF OFF OFF OFF
180 OFF OFF ON ON OFF OFF OFF OFF
218 ON OFF ON ON OFF OFF OFF OFF
265 OFF ON ON ON OFF OFF OFF OFF
360 ON ON ON ON OFF OFF OFF OFF
434 OFF OFF OFF OFF ON OFF OFF OFF
C 521 ON OFF OFF OFF ON OFF OFF OFF
Table 1.O Drives with 460V Input - DIP Switch S15 Configuration
Frame
Drive Current
Rating Code S15-1 S15-2 S15-3 S15-4 S15-5 S15-6 S15-7 S15-8
A 4P1 OFF OFF OFF OFF OFF OFF ON OFF
6P0 ON OFF OFF OFF OFF OFF ON OFF
010 OFF ON OFF OFF OFF OFF ON OFF
014 ON ON OFF OFF OFF OFF ON OFF
019 OFF OFF ON OFF OFF OFF ON OFF
027 ON OFF ON OFF OFF OFF ON OFF
035 OFF ON ON OFF OFF OFF ON OFF
045 ON ON ON OFF OFF OFF ON OFF
052 OFF OFF OFF ON OFF OFF ON OFF
073 ON OFF OFF ON OFF OFF ON OFF
086 OFF ON OFF ON OFF OFF ON OFF
100 ON ON OFF ON OFF OFF ON OFF
129 OFF OFF ON ON OFF OFF ON OFF
B 167 ON OFF ON ON OFF OFF ON OFF
207 OFF ON ON ON OFF OFF ON OFF
250 ON ON ON ON OFF OFF ON OFF
330 OFF OFF OFF OFF ON OFF ON OFF
412 ON OFF OFF OFF ON OFF ON OFF
C 495 OFF ON OFF OFF ON OFF ON OFF
667 ON ON OFF OFF ON OFF ON OFF
Additional digital and analog I/O is available when using the optional I/O
Expansion circuit board. Refer to Appendix F Optional Analog and Digital
I/O Expansion Circuit Board for more information. Also, you can use the
optional 115V AC Converter circuit board to convert 115V AC digital input
signals to 24V DC digital inputs signals to interface with the digital inputs
on the standard I/O terminal blocks. Refer to Appendix G Optional 115V
AC to 24V DC I/O Converter Circuit Board for more information.
Table 1.P Analog I/O, Digital I/O and DC Analog Tachometer Wire Sizes and Terminal
Specifications
Wire Size and Type(1) Tightening
Terminal Block Flexible Multi-core Torque
Signal Type (Terminals) (mm2) (mm2) AWG N•m (lb•in)
Analog and Digital I/O TB1 - 4 (1 - 40)
0.140 - 1.500 0.140 - 1.500 26-16 0.4 (3.5)
DC Analog Tach M3 (+ and –)
(1)
See Cable and Wiring Recommendations on page 1-14 for more information.
Required Parameter
Input/Output Connection Example Changes
Analog Input Bipolar Speed • Set Direction Mode:
Reference (1) + 1 1322 [Direction Mode]
Common 2
±10V Input = 1 “Bipolar”
3
• Adjust Scaling:
4 72 [Anlg In1 Scale] and
5 73 [Anlg1 Tune Scale]
6 • View Signal Value:
7 1404 [Analog In1 Value]
8 • View Signal Output:
9 385 [Speed Ref Out]
10
Required Parameter
Input/Output Connection Example Changes
2-Wire Control • Set Digital Input 1:
11
Reversing(2) Run Fwd. 133 [Digital In1 Sel]
12 = 6 “Run Forward”
24V DC external supply
13 • Set Digital Input 2:
Run Rev. 14 134 [Digital In2 Sel]
15 = 7 “Run Reverse”
16
17
+24V Neutral/
Common 18
19
20
(1) Refer to the Attention statement on page 1-32 for important bipolar wiring information.
(2) Important: Programming inputs for 2 wire control deactivates the HIM Start and Jog buttons.
(3)
0-20mA or 4-20mA operation requires that the switch at S9, S10, or S11 be set to the “ON” position or drive
damage may occur. Refer to Table 1.L on page 1-33.
Common
Z-
Z+ to
+
Shield (1)
B- External
Power
B+ Supply
A-
A+
to Shield (1)
Encoder Signal –Differential,
Dual Channel +V
COM
Z NOT
Z-
Z
Z+
B NOT
B-
B
B+
A NOT
A-
A
A+
to Shield (1)
(1)
Shield connection is on drive Control EMI shield. Refer to Figure 1.33 on page 1-40.
Analog
Tachometer
terminal block
Drive Start Up
This chapter describes how to start up the PowerFlex DC drive. The drive is
configured at the factory for speed regulation with encoder feedback and
independant motor field current regulation with constant current to control
the motor from zero to base speed.
If using the LCD HIM (Human Interface Module) to commission the drive,
it is recommended that you read Appendix B before performing these
procedures.
Important: It is recommended that you uncouple the motor from all loads
at this time, until otherwise directed.
Drive Start Up Checklist This checklist contains the major steps required to complete the drive
commissioning procedure.
2. Verify all switch settings (S9, S10, and S11) for the analog inputs.
Refer to Table 1.L on page 1-33.
3. Verify all DIP switch and jumper settings for the digital encoder or
analog tachometer feedback device. Refer to Table 1.L on
page 1-33 and Figure 1.30 on page 1-34.
1. Verify that control power and I/O wiring is correct. A digital input
(1-8 only) must be wired and configured as a drive enable. Refer to
Control Circuit Input Power on page 1-28 and I/O Wiring on
page 1-32 for further information.
Applying Power to the Drive The remainder of the “Drive Start Up” procedure in this manual uses a HIM
to configure and autotune the drive. If you prefer, you can use the
DriveExplorer™ or DriveTools™ SP software(1) to program drive
parameters or use the drive “Start Up” wizard available with both software
packages.
2. If the STS LED is not flashing green at this point, refer to “Drive
Status Indicators” below.
(1)
You must use DriveExplorer v5.02 or higher or DriveTools SP v4.01 or higher with a PowerFlex DC drive
specific software patch. The patch can be downloaded from http://www.ab.com/support/abdrives/webupdate/
PORT
MOD
NET A
NET B
➋ ➊
STS
❏ Verify that the following voltages are present at I/O terminal block
1 and 2. Refer to I/O Signal and Control Wiring on page 1-35:
Terminal Number . . . Voltage to Terminal Number . . .
7 +10V 9
8 -10V 9
19 +24 - 30V 18
3. Press Enter.
1. At the Main menu, scroll to the Parameter option and press the ALT
and then Sel button.
10. With the “Motor Data” group selected, press Enter and configure
the following parameters:
❏ 179 [Nom Mtr Arm Amps] - Enter the rated motor nameplate
armature current.
❏ 374 [Drv Fld Brdg Cur] - Enter the rated current of the field
bridge regulator to match the value set using the DIP switch
S14. Refer to Field Current Resistors on page 1-24.
❏ 280 [Nom Mtr Fld Amps] - Enter the rated motor nameplate
field current.
11. Access the “Field Config” group and configure the following
parameters:
❏ Par 469 [Field Mode Sel] - select the desired field mode
(default = 0 “Base Speed”, constant field current):
❏ If you are utilizing field economy at zero speed, set 468 [Min
Fld Curr Pct] to the desired minimum field current for field
economy (default = 30%).
❏ If you are operating the drive in field weakening mode, set Par
456 [Fld Weaken Ratio] = Motor nameplate base speed / Par 45
[Max Ref Speed] x 100.
13. Access the “Alarms” group and configure the following parameters:
❏ Par 481 [UnderVolt Thresh] - Enter the value at which a drive
under voltage condition will be detected (default = 230V).
14. Access the “Input & Output” file and press Enter.
15. Access the “Analog Inputs” group and configure the following:
❍Set Par 72 [Anlg In1 Scale] and Par 74 [Anlg In1 Offset]
appropriately.
❏ If you are using the HIM on the drive cover (Port 1) for the
speed reference, set Par 70 [Anlg In1 Sel] to 0 “Off”.
16. Access the “Digital Inputs” group and configure the following
parameters:
17. Access the “Digital Outputs” group and configure the following
parameters:
18. If you are using the HIM on the drive cover (Port 1) for the speed
reference, access the “DPI Inputs” group and set the appropriate
[DPI Px Select] parameter to 1“Speed Ref A”.
Complete this test before running the drive for the first time. Upon
completing this tuning procedure, the armature resistance value is
stored in Par 453 [Arm Resistance] and the armature inductance value is
stored in Par 454 [Arm Inductance]. If needed, these values can be
manually adjusted.
2. Access the “Motor Control” file, the “Torq Attributes” group and
set Par 7 [Current Limit] to the appropriate level for your
application. This parameter defaults to 150%. The drive’s armature
output current will correspond to Par 179 [Nom Mtr Arm Amps] x
Par 7 [Current Limit].
Note: Par 8 [Current Lim Pos], the drive current limit for the
positive direction and Par 9 [Current Lim Neg], the drive
current limit for the negative direction, are set to 150% by
default. If necessary, you can change the value of these
parameters to suit your application.
3. Access the “Speed Feedback” group and verify that Par 414 [Fdbk
Device Type] is set to 3 “Armature” (default).
4. Press the Esc key until you return to the “File” menu and access Par
452 [CurrReg Autotune] in the “Autotune” group, in the “Motor
Control” file, and select 1 “On” and press Enter.
5. Press the Start button on the HIM. This will start the current
regulator auto tuning test, which could take several minutes.
At the end of the test, the drive will automatically be stopped and
Par 452 [CurrReg Autotune] will be set to 0 “Off”.
If the value of Par 587 [I Reg Error] is greater than -/+40, refer to
Manually Adjusting the Current Regulator Tune Settings on page C-26
for more information.
If a drive fault occurs during the tuning procedure, refer to Fault
Descriptions on page 4-4 for a list of fault descriptions and actions.
The jog function (on the HIM or terminal block) will be used to check
motor direction and encoder operation. If the STS LED is not flashing green
at this point, refer to Figure 2.1 on page 2-5 for more information.
1. When checking motor polarity, the drive will have power applied
and the motor will rotate. Verify that the motor is uncoupled from
the load. If the motor cannot be uncoupled from the load, the
following motor checks are recommended:
(2) (2)
D (-) A2 D (-) A2
10. Repeat steps 4 and 5 above and verify that the motor rotation is
correct.
❏ Par 414 [Fdbk Device Type] - Select the source for motor
velocity feedback: 1 “Encoder”, 2 “DC Tach” or 3 “Armature”
(default). If operating the drive in field weakening mode, Par
414 [Fdbk Device Type] must be set to 1 "Encoder" or 2 "DC
Tach".
❏ Par 457 [Spd Fdbk Control] - If you are using an encoder or
tachometer, set this parameter to 1 “Enabled” to activate speed
feedback control.
❏ If the speed feedback source is an analog tachometer, set the
fine scaling value in Par 562 [Anlg Tach Gain]. This value is
used to scale the analog tachometer feedback signal after it has
been conditioned by the drive hardware.
3. With the “Limits” group selected, press Enter and configure the
following parameters:
The speed regulator auto tuning test detects the total inertia value of the
motor shaft (in Kg-m2), the friction value (in N-m) and the calculation of the
proportional (P) and integral (I) gains of the speed regulator.
Important: The test is carried out by using the torque limit value set in
the Par 1048 [Autotune Cur Lim] (recommended value =
20%). The torque reference is applied via a step reference
(without a ramp); therefore there must not be any
“backlash” in the mechanical transmission and it must be
compatible with those operations using the torque limit
value set in the Par 1048 [Autotune Cur Lim]. You can
modify the torque limit value via this parameter.
Important: In applications where the system total inertia value is very
high, it is necessary to increase the value of Par 1048
[Autotune Cur Lim] in order to avoid “Time out” errors.
The speed regulator auto tuning test of the speed loop is not
suitable for drives used in “elevator” and/or lifting system
applications.
3. Press the Start button on the HIM. This will start the speed regulator
auto tuning test, which could take several minutes. When the test
has been completed, the drive will automatically stop.
❏ An acceleration test, with the torque limit value set in the Par
1048 [Autotune Cur Lim].
The drive will determine the speed loop gains (Pars 87 [Spd Reg Kp]
and 88 [Spd Reg Ki]) based on the motor and load inertia and friction
characteristics.
If any fault occur during the test, refer to Auto Tuning Faults on
page 2-17 for a description and more information.
Note: If any manual adjustments are required (due to vibrations,
etc.), these should be carried out according to the value of
the integral gain Par 88 [Spd Reg Ki]. If the speed regulator
auto tuning test does not provide satisfactory results, refer
to Fine Tuning the Regulators on page C-25.
The values determined by the Speed Regulator tuning tests are updated
in Pars 87 [Spd Reg Kp], 88 [Spd Reg Ki], 1014 [Inertia] and 1015
[Friction] and displayed in the corresponding Pars 1032 [Speed Tune
Kp], 1033 [Speed Tune Ki], 1030 [Spd Tune Inertia] and 1031
[SpdTune Friction], respectively. The values of Pars 1030 - 1033 can be
used as a record of the Speed Regulator auto tuning results if the values
of Pars 87, 88, 1014 and 1015 are subsequently changed.
1. Set the speed reference to “0” (zero) using the assigned source
(HIM or analog potentiometer). Refer to Reference Control on
page C-13 for more information on speed reference sources.
2. View Par 385 [Speed Ref Out] and verify that the value is “0”.
3. Press the Start button on the HIM and slowly increase the speed
reference until full speed is reached (viewed in Par 385 [Speed Ref
Out] ).
5. Press the Stop button on the HIM and verify that the drive ramps to
“0” speed and stops.
For additional regulator fine tuning procedures, refer to Fine Tuning the
Regulators on page C-25.
Speed-Up Function
Oscillation may occur during a speed change with loads presenting a high
moment of inertia. These oscillations can be reduced by enabling the
“Speed Up” function. Refer to Speed Up Function on page C-20 for more
information.
About Parameters To configure a drive to operate in a specific way, certain parameters may
need to be changed from the default value. Three types of parameters exist:
• ENUM Parameters
ENUM parameters allow a selection from two or more items. The LCD
HIM will display a text message for each item.
• Bit Parameters
Bit parameters have individual bits associated with features or
conditions. If the bit is “0”, the feature is off or the condition is false. If
the bit is “1”, the feature is on or the condition is true.
• Numeric Parameters
These parameters have a single numerical value and unit (i.e. 0.1 Volts).
The example on the following page shows how each parameter type is
presented in this manual.
(1)
You must use DriveExplorer v5.02 or higher or DriveTools SP v4.01 or higher with a PowerFlex DC drive
specific software patch. The patch can be downloaded from http://www.ab.com/support/abdrives/webupdate/
➊ ➋ ➌ ➍ ➎ ➏
Related
Group
File
from zero.
Main uses:
•To connect to a motor that is already spinning due to its
load (e.g. in the case of pumps, the flowing medium).
•Re–connection to a spinning motor after a fault or alarm.
Note: If the Flying Start function is disabled, ensure that the
motor is not spinning when the drive is turned on, or harsh
motor deceleration in current limit may occur.
445 [Spd Up Gain Pct] Default: 0.00
A The Speed Up function gain as a percentage of Par 446 Min/Max: 0.00 / 100.00
[Speed Up Base]. Units: %
Reserved.
DPI Port 5
DPI Port 4
DPI Port 3
DPI Port 2
DPI Port 1
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Digital In
Default x x x x x x x x x x 0 0 0 0 1 1
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
No. Description
➊ File – Lists the major parameter file category.
➋ Group – Lists the parameter group within a file.
➌ No. – Parameter number. A = The parameter is only accessible when Par 211 [Param Access Lvl] = 1 “Advanced”.
= The parameter value cannot be changed until the drive is stopped.
➍ Parameter Name & Description – Parameter name as it appears on an LCD HIM, with a brief description of the parameters function.
➎ Values – Defines the various operating characteristics of the parameter. Three types exist.
ENUM Default: Lists the value assigned at the factory. “Read Only” = no default.
Options: Displays the programming selections available.
Bit Bit: Lists the bit place holder and definition for each bit.
Numeric Default: Lists the value assigned at the factory. “Read Only” = no default.
Min/Max: The range (lowest and highest setting) possible for the parameter.
Units: Unit of measure and resolution as shown on the LCD HIM.
Important: Some parameters will have two unit values:
• E.g.: Analog inputs can be set for current or voltage as with Par 71 [Anlg Inx Config].
Important: When sending values through DPI ports, simply remove the decimal point to arrive at the correct value (i.e. to
send “5.00 RPM”, use “500”).
➏ Related – Lists parameters (if any) that interact with the selected parameter. The symbol “ ” indicates that additional parameter
information is available in Appendix C - Application Notes on page C-1.
How Parameters are The LCD HIM displays parameters in a File–Group–Parameter or Numbered
Organized List view order. To switch display mode, access the Main Menu, press ALT,
then Sel (View) while the cursor is on the Parameter menu selection. In
addition, using Par 211 [Param Access Lvl], you have the option to display
the most commonly used parameters (Basic Parameter view) or all
parameters (Advanced Parameter View).
File–Group–Parameter Order
This simplifies programming by grouping parameters that are used for
similar functions. The parameters are organized into files. Each file is
divided into groups, and each parameter is an element in a group. By
default, the LCD HIM displays parameters by File–Group–Parameter view.
Field Config [Field Reg Enable] 497 [Field Mode Sel] 469 [Fld Weaken Ratio] 456
[Field Economy En] 499 [Max Fld Curr Pct] 467
[Field Econ Delay] 1407 [Min Fld Curr Pct] 468
Torq Attributes [Current Limit] 7 [Torque Ref] 39 [Zero Torque] 353
[Current Lim Pos] 8 [Trim Torque] 40
[Current Lim Neg] 9 [Torque Reduction] 342
Speed Feedback [Fdbk Device Type] 414 [Anlg Tach Zero] 563 [SpdReg FB Bypass] 458
[Anlg Tach Gain] 562 [Spd Fdbk Control] 457
Autotune [Autotune Cur Lim] 1048 [Spd Reg Autotune] 1027 [Spd Tune Inertia] 1030
[CurrReg Autotune] 452 [Speed Tune Dir] 1029 [SpdTune Friction] 1031
[Arm Resistance] 453 [Speed Tune Kp] 1032
[Arm Inductance] 454 [Speed Tune Ki] 1033
Speed Command Limits [Minimum Speed] 1 [Min Speed Rev] 6 [Max Speed Fwd] 3
Speed
Comm
[Min Speed Fwd] 5 [Maximum Speed] 2 [Max Speed Rev] 4
and
Discrete Speeds [Jog Speed] 266 [Preset Speed 3] 156 [Preset Speed 7] 160
[Jog Off Delay] 1409 [Preset Speed 4] 157 [TB Manual Ref] 267
[Preset Speed 1] 154 [Preset Speed 5] 158
[Preset Speed 2] 155 [Preset Speed 6] 159
Speed [Trim Ramp] 42 [Trim Speed] 43 [Speed Ratio] 1017
References [Trim Ramp Pct] 378 [Trim Speed Pct] 379
Speed Regulator [Speed Reg En] 242 [Spd Reg Kp] 87 [Spd Reg Ki] 88
[Arm Volt Kp] 493 [Arm Volt Ki] 494
Dynamic Control Ramp Rates [Speed Ramp En] 245 [Accel Time 2] 24 [Jog Ramp Time] 1410
[Ramp Type Select] 18 [Decel Time 2] 32 [S Curve Time] 19
Dynam
ic Con
trol
[Accel Time 1] 660 [MOP Accel Time] 22
[Decel Time 1] 662 [MOP Decel Time] 30
Restart Modes [Start At Powerup] 1344 [Powerup Delay] 1345
Masks & Owners [Logic Mask] 591 [MOP Mask] 598 [Reference Owner] 604
[Start Mask] 592 [Local Mask] 599 [Accel Owner] 605
[Jog Mask] 593 [Decel Mask] 631 [Fault Clr Owner] 606
[Direction Mask] 594 [Stop Owner] 600 [MOP Owner] 607
[Reference Mask] 595 [Start Owner] 601 [Local Owner] 608
[Accel Mask] 596 [Jog Owner] 602 [Decel Owner] 609
[Fault Clr Mask] 597 [Direction Owner] 603
Datalinks [Data In A1] 610 [Data In D1] 616 [Data Out C1] 622
[Data In A2] 611 [Data In D2] 617 [Data Out C1] 623
[Data In B1] 612 [Data Out A1] 618 [Data Out D1] 624
[Data In B2] 613 [Data Out A2] 619 [Data Out D2] 625
[Data In C1] 614 [Data Out B1] 620 [Data In Val Sel] 1319
[Data In C2] 615 [Data Out B2] 621 [Data In SelData] 1320
Input / Output Analog Inputs [Anlg In1 Sel] 70 [Anlg In1 Target] 295 [Anlg In1 Cmp Eq] 1045
Inputs
[Anlg In1 Config] 71 [Anlg In2 Target] 296 [Analog In1 Value] 1404
/ Outpu
ts [Anlg In2 Sel] 75 [Anlg In3 Target] 297 [Analog In2 Value] 1405
[Anlg In2 Config] 76 [Anlg In1 Cmp] 1042 [Analog In3 Value] 1406
[Anlg In3 Sel] 80 [Anlg In1 Cmp Err] 1043
[Anlg In3 Config] 81 [Anlg In1 Cmp Dly] 1044
Analog Outputs [Anlg Out1 Sel] 66 [Anlg Out4 Sel] 69 [Analog Out3 Scale] 64
[Anlg Out2 Sel] 67 [Analog Out1 Scale] 62 [Analog Out4 Scale] 65
[Anlg Out3 Sel] 68 [Analog Out2 Scale] 63
Digital Inputs [Dig In Status] 564 [Digital In9 Sel] 141 [Dig In Term 6] 570
[Digital In1 Sel] 133 [Digital In10 Sel] 142 [Dig In Term 7] 571
[Digital In2 Sel] 134 [Digital In11 Sel] 143 [Dig In Term 8] 572
[Digital In3 Sel] 135 [Digital In12 Sel] 144 [Dig In Term 9] 573
[Digital In4 Sel] 136 [Dig In Term 1] 565 [Dig In Term 10] 574
[Digital In5 Sel] 137 [Dig In Term 2] 566 [Dig In Term 11] 575
[Digital In6 Sel] 138 [Dig In Term 3] 567 [Dig In Term 12] 576
[Digital In7 Sel] 139 [Dig In Term 4] 568
[Digital In8 Sel] 140 [Dig In Term 5] 569
Digital Outputs [Dig Out Status] 581 [Digital Out4 Sel] 148 [Digital Out8 Sel] 152
[Digital Out1 Sel] 145 [Digital Out5 Sel] 149 [Relay Out 1 Sel] 1392
[Digital Out2 Sel] 146 [Digital Out6 Sel] 150 [Relay Out 2 Sel] 629
[Digital Out3 Sel] 147 [Digital Out7 Sel] 151
DPI Inputs [DPI P1 Select] 1323 [DPI P3 Select] 1325 [DPI P5 Select] 1327
[DPI P2 Select] 1324 [DPI P4 Select] 1326
Monitor File
Related
Group
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
924 [Actual Speed] Default: Read Only 121
Filtered value of Par 122 [Spd Feedback]. Min/Max: –/+32766
Note: This parameter can be assigned to an analog output. Units: RPM
1018 [Speed Draw Out] Default: Read Only 45
Speed draw output value. Min/Max: –/+ Par 45 [Max Ref Speed] 1
Speed Meters
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
57 [FaultCode] Default: Read Only
A code that represents the fault that tripped the drive. Refer to Min/Max: 0 / 65535
Fault Descriptions on page 4-4 for a list of fault codes and
descriptions.
233 [Output Voltage] Default: Read Only
Armature Voltage UdA in VAV. Min/Max: -/+999.00
Note: This parameter can be assigned to an analog output. Units: Vdc
235 [Elapsed Lifetime] Default: Read Only
Shows the operating time of the drive. This parameter counts Min/Max: 0.00 / 65540.00
the time for which the drive is energized (even if the drive is Units: H.m
disabled).
300 [Drive Type] Default: Read Only
Displays of the drive type. Min/Max: 10 / 11
“10” = Non-Regenerative
“11” = Regenerative
Drive Data
MONITOR
Related
Group
No.
179 [Nom Mtr Arm Amps] Default: Based on drive current rating
Rated motor nameplate armature current. The settings for the Min/Max: 0.10 / Based on drive current rating
current limit and the overload function are based on this current Units: A
value.
201 [Drive Type Sel] Default: 0= “Off”
This parameter is only applicable to non-regenerative Options: 0= “Off”
(2-quadrant) drives. It allows non-regenerative drives to use an 1= “On”
A external 4-quadrant controller.
• “On” = Ramp, Speed, Torque current references and Speed
measurement have the same behavior of a four quadrant
drive.
280 [Nom Mtr Fld Amps] Default: Par 374 [Drv Fld Brdg Cur] x 0.33
Rated motor nameplate field current (IdFN). Min/Max: 0.00 / [Drv Fld Brdg Cur]
Units: A
374 [Drv Fld Brdg Cur] Default: 1.00
Drive rated field bridge current (IdFN). The value in this field must Min/Max: 0.50 / 80.00
be set equal to the value chosen with DIP switch S14 on the Units: A
Control board (refer to Table 1.G on page 1-25 for DIP switch
configuration).
91 [Fld Reg Kp] Default: 2.00 97
Proportional gain (KP) of the flux regulator expressed as a Min/Max: 0.00 / 100.00
A percentage of Par 97 [Fld Reg Kp Base]. Units: %
92 [Fld Reg Ki] Default: 1.00 98
Field Config
Integral gain (KI) of the flux regulator expressed as a percentage Min/Max: 0.00 / 100.00
A of Par 98 [Fld Reg Ki Base]. Units: %
97 [Fld Reg Kp Base] Default: 3277.00
The proportional gain (KP0) of the field current regulator (base Min/Max: 0.10 / 32770.00
value).
A
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
98 [Fld Reg Ki Base] Default: 3277.00
Integral gain (KI0) of the field current regulator in (base value). Min/Max: 0.10 / 32770.00
A
456 [Fld Weaken Ratio] Default: 100
The ratio of Motor Nameplate Base Speed to Par 45 [Max Ref Min/Max: 0 / 100
Speed] when Par 469 [Field Mode Sel] = 1 "Field Weaken". It is Units: %
the percentage of maximum application speed when field
weakening will begin. This value is "Motor Base Speed" / Par 45
[Max Ref Speed] x 100. If Par 469 [Field Mode Sel] = 0 “Base
Speed”, this parameter must be = 100%.
467 [Max Fld Curr Pct] Default: 100 468
Maximum allowable field current. The maximum value (100%) Min/Max: Par 468 [Min Fld Curr Pct] / 100
corresponds to the value set in Par 280 [Nom Mtr Fld Amps]. Units: %
The value of this field linearly affects the field current, unless a
flux curve is set in Pars 916, 917, and 918 [Fld Const xx Pct].
Note: This parameter can be assigned to an analog input or
output.
468 [Min Fld Curr Pct] Default: 30 467,
Minimum allowable field current. The value set in this parameter Min/Max: 0 / Par 467 [Max Fld Curr Pct] 499
also influences the threshold at which the “Fld Current Loss” Units: %
(F6) fault occurs. The threshold is half of the value of Par 468
[Min Fld Curr Pct]. The value of Par 351 [Field Current] equals
the value of this parameter when Par 499 [Field Economy En] =
MOTOR CONTROL
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
499 [Field Economy En] Default: 1= “Enabled” 395,
When this parameter is set to 1 = “Enabled” and the value in Par Options: 0= “Disabled” 468
107 [Speed Zero Level] is reached, the minimum field current 1= “Enabled”
(set via Par 468 [Min Fld Curr Pct]) is produced (field economy).
• “Disabled” = Disables the field economy function
• “Enabled” = Enables the field economy function
916 [Fld Const 40 Pct] Default: 40.00 469
Current value at 40% of the field current. Min/Max: 0.00 / 100.00
Units: %
A
917 [Fld Const 70 Pct] Default: 70.00 469
Current value at 70% of the field current. Min/Max: 0.00 / 100.00
Units: %
A
918 [Fld Const 90 Pct] Default: 90.00 469
Current value at 90% of the field current. Min/Max: 0.00 / 100.00
Units: %
A
919 [Set Fld Curve] Default: 1 916,
Field Config
When set to “0”, this parameter controls the motor field current Min/Max: 0/1 917,
to field reference curve according to the values specified in the 918
A [Fld Const xx Pct] parameters. With this curve is defined, the
MOTOR CONTROL
result of [Max Fld Curr Pct] / [Field Ref Pct] equals the
percentage of field current according to the characteristic of the
curve. This field is Write Only. After the value of this field is set to
“0”, it will automatically return to “1”.
920 [Reset Fld Curve] Default: 0
when set to “1”, resets the drive to use a linear field curve. When Min/Max: 0/1
this parameter is set, Par 280 [Nom Mtr Fld Amps] is linearly Units:
A changed through [Max Fld Curr Pct] / [Field Ref Pct]. This field is
Write Only. After the value of this field is set to “1”, it will
automatically return to “0”.
921 [Out Volt Level] Default: 100.00
The percentage of maximum output voltage based on the value Min/Max: 0.00 / 100.00
A in Par 175 [Rated Motor Volt]. This parameter allows you to Units: %
change the output voltage at the motor end when the drive is in
"Field Weaken" mode. Typically set to the default value when the
drive is in Field Weakening mode.
Note: This parameter can be assigned to an analog output or
analog input.
1407 [Field Econ Delay] Default: 300
Amount of time to elapse after the drive reaches zero speed (as Min/Max: 0 / 1800
determined by Par 107 [Speed Zero Level]) before field Units: s
economy becomes active.
7 [Current Limit] Default: 150 8,
Symmetrical current limit expressed as a percentage of the Min/Max: 0 / 200 9,
Torq Attributes
value in Par 179 [Nom Mtr Arm Amps]. This value applies to Units: % 179
both current directions for four quadrant drives.
• If Par 7 [Current Limit] is changed, Pars 8 [Current Lim Pos]
and 9 [Current Lim Neg] are set to the same value. If
subsequently changed, the value of Pars 8 [Current Lim Pos]
and/or 9 [Current Lim Neg] override the value of Par 7
[Current Limit].
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
8 [Current Lim Pos] Default: 150 7
The drive current limit for the positive current direction Min/Max: 0 / 200
expressed as a percentage of the value in Par 179 [Nom Mtr Units: %
Arm Amps].
Note: This parameter can be assigned to an analog input.
9 [Current Lim Neg] Default: 150 7
The drive current limit for the negative current direction Min/Max: 0 / 200
expressed as a percentage of the value in Par 179 [Nom Mtr Units: %
Arm Amps]. This parameter is not active for two quadrant drives.
Note: This parameter can be assigned to an analog input.
39 [Torque Ref] Default: 0
First current reference value, before any trim signals are Min/Max: – / +200
incorporated, as a percentage of the value set in Par 179 [Nom Units: %
Mtr Arm Amps]. This parameter is only used when Par 242
[Speed Reg En] = 0 "Disabled".
Note: The current reference value is proportional to the
armature current of the motor and determines the torque. The
polarity determines the torque direction.
40 [Trim Torque] Default: 0
MOTOR CONTROL
Second current reference value as a percentage of the value set Min/Max: – / +200
Torq Attributes
in Par 179 [Nom Mtr Arm Amps]. [Trim Torque] is added to Units: %
Torque Reference and can be used as a correction value for the
torque reference (regardless of the value of Par 242 [Speed Reg
En]).
342 [Torque Reduction] Default: 0= “Not Active” 13
Selection for torque reduction. When the torque reduction Options: 0= “Not Active”
function is active (1 “Active”), the current limit changes 1= “Active”
accordingly by the percentage defined in Par 13 [Torq Red
CurLim]. When this parameter is set to 0 “Not Active”, torque
reduction is not active.
For example:
Par 7 [Current Limit] (or Pars 8 [Current Lim Pos] and 9
[Current Lim Neg]) = 80 %
Par 13 [Torq Red CurLim] = 70%
If Par 342 [Torque Reduction] = 0 “Not Active”, the current
limit = 80 %
If Par 342 [Torque Reduction] = 1 “Active”, the current limit =
70 %
Note: This parameter can be assigned to a digital input.
353 [Zero Torque] Default: 1= “Not Active” 41
Sets the reference value for the armature current (Par 41 Options: 0= “Active”
[Current Reg In]) to zero so that the drive has no torque. 1= “Not Active”
• “Not Active” = Par 41 [Current Reg In] is not set to zero.
• “Active” = Par 41 [Current Reg In] is set zero. The drive has
no torque.
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
750 [TrqTpr_Enable] Default: 0= “Disabled” 751,
Enables/Disables the current/speed function. The current/speed Options: 0= “Disabled” 752,
function allows you to change the current limits set in Pars 8 1= “Enabled” 753,
[Current Lim Pos] and 9 [Current Lim Neg] by setting up to five 754,
A 755,
setpoints using parameters [TrqTpr_Limx] and a threshold
speed in Par 756 [TrqTpr_Spd]. 756
• “Disabled” = The limits current /speed curve is disabled
• “Enabled” = The limits current /speed curve is enabled
Par 10 [Cur Lim Pos Out]
or
Par 11 [Cur Lim Neg Out]
Current/Speed
TrqTpr_Lim0]
TrqTpr_Lim1]
TrqTpr_Lim2]
TrqTpr_Lim3]
TrqTpr_Lim4]
Torq Attributes
Related
Torq Attributes Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
926 [Filt Torq Cur] Default: 0.100 1193
First rate low-pass filter for Par 1193 [Torq Current Pct]. Min/Max: 0.001 / 0.250
A Units: s
ATTENTION: If speed feedback control is disabled (Par 457 [Spd Fdbk Control] set to 0
“Disabled” and Par 414 [Device Type] is set to 1 “Encoder”, the motor could run at excessive
! speed or become damaged, which could result in personal injury or destruction of equipment.
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
652 [Encoder Err Chk] Default: 0 “Disabled” 457
Enables/Disables monitoring of the digital encoder connection Options: 0= “Disabled”
A status. When an alarm is detected, the HIM displays the 1= “Enabled”
“Encoder Loss” (F91) fault. This parameter can be programmed
on a digital output. This function is activated by setting Par 457
[Spd Fdbk Control] = “Enabled”.
911 [Z Channel Enable] Default: 0= “Disabled”
Determines whether the encoder zero pulse (qualification signal Options: 0= “Disabled”
A or “zero cam”) will be read by the drive. This parameter is used 1= “Enabled”
for systems implementing position control.
• “Enabled” = The encoder zero pulse is read.
• “Disabled” = The encoder zero pulse is not read.
Speed Feedback
the choice of the speed reference destination must be made 3= “Speed Ref A”
according to the configuration of the speed regulator (for 4= “Speed Ref B”
example "Speed Ref A" cannot be used with an active ramp).
452 [CurrReg Autotune] Default: 0= “Off”
Setting this parameter to 1 “On” and pressing Enter on the HIM Options: 0= “Off”
keypad initiates the current regulator auto tuning procedure. 1= “On”
When the auto tuning procedure is complete, this parameter
automatically resets to 0 “Off”. The resulting armature
resistance and inductance values are set in parameters 453
[Arm Resistance] and 454 [Arm Inductance], respectively.
453 [Arm Resistance] Default: 0.50 452
Motor armature resistance. This parameter can be manually Min/Max: Based on drive current rating
changed to a value other than the value obtained when the Units: Ohm
current regulator auto tuning is completed.
454 [Arm Inductance] Default: 4.00 452
Motor armature inductance. This parameter can be manually Min/Max: Based on drive current rating
Autotune
changed to a value other than the value obtained when the Units: mH
current regulator auto tuning is completed.
587 [I Reg Error] Default: Read Only 452
The auxiliary signal used to determine whether the current Min/Max: –/+80
A regulator is correctly tuned. The value should be as near to zero Units: V
as possible, but values between -/+40 are acceptable.
1012 [Inertia C Filter] Default: 0
First order low–pass filter used to reduce noise caused by the Min/Max: 0 / 1000
A speed differentiation process in the Inertia/Loss compensation Units: ms
block.
1013 [Torque Const] Default: Based on drive current rating
The Motor torque constant used to calculate inertia and friction Min/Max: 0.01 / 99.99
A compensation. The value in this parameter is automatically Units: N–m/A
adapted in the field weakening mode. This value is determined
during speed auto tuning.
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
1014 [Inertia] Default: Based on drive current rating
Motor inertia value. Min/Max: 0.001 / 999.999
A 1 Kg–m2 = 23.76 lb–ft2 Units: Kg–m2
1015 [Friction] Default: Based on drive current rating
Motor friction value. Min/Max: 0.000 / 99.990
A 1 N–m = 0.738 lb–ft Units: N–m
1027 [Spd Reg Autotune] Default: 0= “Ready”
Starts the auto tuning procedure for the speed regulator. Setting Options: 0= “Ready”
this parameter to 1 “On” and pressing Enter on the HIM keypad 1= “Start”
initiates the speed regulator auto tuning procedure. When the
auto tuning procedure is complete, this parameter automatically
resets to 0 “Off”.
1029 [Speed Tune Dir] Default: 1= “Forward”
Choice of the rotation direction of the motor shaft (rotation, as Options: 1= “Forward”
MOTOR CONTROL
seen from the motor shaft side) for the speed regulator auto 2= “Reverse”
tuning procedure.
Autotune
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
58 [TstGen Output] Default: 0= “NotConnected” 59,
Allows you to select a simulated parameter as the output for the Options: 0= “NotConnected” 60,
test generator. The test generator is used to manually tune the 1= “Reserved” 61
A regulators. It consists of a square wave generator whose 2= “Torq Cur Ref”
frequency, offset and amplitude can be manipulated. 3= “Field Ref”
• “NotConnected” - No internal parameters defined by the 4= “Ramp Ref”
generator. 5= “Speed Ref”
• “Reserved” - Not used.
• “Torq Cur Ref” - The output of the generator defines the
reference value of the torque current. 100% corresponds to
“full load torque current” (FLT).
• “Field Ref” - The output of the generator defines the field
reference value. 100% corresponds to the rated field current
based on the motor nameplate data parameters.
• “Ramp Ref” - The output of the generator defines the ramp
reference value. 100% corresponds to the value specified in
Par 45 [Max Ref Speed]. This is the value immediately before
the Ramp function.
• “Speed Ref” - The output of the generator defines the speed
reference value. This is the value immediately before the
Speed Regulator function.
P58
TstGen Output
MOTOR CONTROL
Test Generator
Generator
Output
P60
TstGen Amplitude
P61
TstGen Offset
Time
P59
TstGen Frequency
59 [TstGen Frequency] Default: 0.10 58
Output frequency of the test generator. Min/Max: 0.10 / 62.50
A Units: Hz
60 [TstGen Amplitude] Default: 0.00 58
Amplitude of the delta signal produced by the test generator. Min/Max: 0.00 / 200.00
A Units: %
61 [TstGen Offset] Default: 0.00 58
Offset of the test generator. Min/Max: –/+200.00
A Units: %
Related
Group
No.
See page 3-2 for symbol descriptions Values
1 [Minimum Speed] Default: 0 5,
Defines the minimum speed of the drive. This value applies to both Min/Max: 0 / Par 45 [Max Ref Speed] 6
directions of motor rotation for four quadrant drives. A speed below Units: RPM
the value set in [Minimum Speed] is not possible, regardless of the set
speed reference value. If the value of [Minimum Speed] is changed,
Pars 5 [Min Speed Fwd] and 6 [Min Speed Rev] are set to the same
value. If either Par 5 [Min Speed Fwd] or Par 6 [Min Speed Rev] is
changed later, the last change is valid.
2 [Maximum Speed] Default: 1750 3,
Defines the maximum speed of the drive. This value applies to both Min/Max: 0 / Par 45 [Max Ref Speed] 4
directions of motor rotation for four quadrant drives. The value of this Units: RPM
parameter is input to the speed regulator and therefore takes into
account the reference value that comes from the ramp as well as the
direction of rotation. If the value of [Maximum Speed] is changed,
Pars 3 [Max Speed Fwd] and 4 [Max Speed Rev] are set to the same
value. If either Par 3 [Max Speed Fwd] or Par 4 [Max Speed Rev] is
changed later, the last change is valid.
3 [Max Speed Fwd] Default: 1750 2
Limits
Defines the maximum speed for forward (clockwise) rotation of the Min/Max: 0 / Par 45 [Max Ref Speed]
motor. The value of [Max Speed Fwd] affects the input of the speed Units: RPM
regulator and therefore takes into account both the reference values
that come from the ramp as well as the direction of motor rotation.
4 [Max Speed Rev] Default: 1750 2
SPEED COMMAND
Defines the maximum speed for reverse (counterclockwise) rotation of Min/Max: 0 / Par 45 [Max Ref Speed]
the motor for four quadrant drives only. The value of [Max Speed Rev] Units: RPM
affects the input of the speed regulator and therefore takes into
account both the reference values that come from the ramp as well as
the direction of rotation.
5 [Min Speed Fwd] Default: 0 1
Defines the minimum speed for forward (clockwise) rotation of the Min/Max: 0 / Par 45 [Max Ref Speed]
motor. Speed reference values below the value in this parameter are Units: RPM
clamped until the reference exceeds this limit.
6 [Min Speed Rev] Default: 0 1
Defines the minimum speed for reverse (counterclockwise) rotation of Min/Max: 0 / Par 45 [Max Ref Speed]
the motor for four quadrant drives only. Speed reference values below Units: RPM
the value in this parameter are clamped until the reference exceeds
this limit.
154 [Preset Speed 1] Default: 150
155 [Preset Speed 2] Default: 300
156 [Preset Speed 3] Default: 600
157 [Preset Speed 4] Default: 900
158 [Preset Speed 5] Default: 1200
159 [Preset Speed 6]
Discrete Speeds
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
1409 [Jog Off Delay] Default: 1
Specifies the amount of time that will elapse between removing the Min/Max: 0 - 10
Jog input and commanding the main contactor to open. The amount Units: s
of time specified in [Jog Off Delay] will not begin to elapse until the
measured speed feedback is less than or equal to the value of
Discrete Speeds
parameter 107 [Speed Zero Level]. This delay reduces the wear on
the contactor when repeatedly opening and closing the Jog input over
a short period of time.
Note: This parameter was added with firmware version 2.001.
267 [TB Manual Ref] Default: 0
Reference value for the drive when the Terminal Block asserts Manual Min/Max: –/+ Par 45 [Max Ref Speed] (1)
reference control. Units: RPM
Note: This parameter can be assigned to an analog input. (1) The value of [Max Ref Speed] cannot exceed 8192
RPM.
42 [Trim Ramp] Default: 0 378
This value is added to the speed reference just before the Speed Min/Max: –/+Par 45 [Max Ref Speed] (1)
Ramp function. Units: RPM
Note: This parameter can be assigned to an analog input. (1)
The value of Par 45 [Max Ref Speed] cannot exceed
8192 RPM.
43 [Trim Speed] Default: 0 379
This value is added to the speed reference just before the speed Min/Max: –/+ Par 45 [Max Ref Speed] (1)
Speed References
Trim ramp value defined as a percentage of the value defined in Par Min/Max: –/+100.00
45 [Max Ref Speed]. Units: %
379 [Trim Speed Pct] Default: 0.00 43
Trim speed reference value defined as a percentage of the of the Min/Max: –/+100.00
value defined in Par 45 [Max Ref Speed]. Units: %
1017 [Speed Ratio] Default: 10000
Determines the speed ratio value for the Speed-Draw function. Min/Max: 0 / 32767
Note: This value can be input to the drive digitally, or via an analog
input.
87 [Spd Reg Kp] Default: 10.00 93,
Proportional gain of the speed regulator that can be adjusted while Min/Max: 0.00 / 100.00 99
the drive is running. Units: %
88 [Spd Reg Ki] Default: 1.00 94,
Integral gain of the speed regulator that can be adjusted while the Min/Max: 0.00 / 100.00 100
drive is running. Units: %
93 [Spd Reg Kp Base] Default: 0.30 x Par 93max 87,
The proportional gain (KP0) of the speed regulator (base value). Min/Max: 0.01 / Based on drive current rating 99
Speed Regulator
Units: A / RPM
A
94 [Spd Reg Ki Base] Default: 0.30 x Par 94max 88,
The integral gain (KI0) of the speed regulator (base value). Min/Max: 0.01 / Based on drive current rating 100
Units: A/ RPM x ms
A
99 [Spd Reg Kp Outpt] Default: Read Only 87,
Displays the active proportional coefficient of the speed regulator as a Min/Max: 0.00 / 100.00 93
A percentage of the value defined in Par 93 [Spd Reg Kp Base]. Units: %
100 [Spd Reg Ki Outpt] Default: Read Only 88,
Displays the active integral coefficient of the speed regulator as a Min/Max: 0.00 / 100.00 94
A percentage of the value defined in Par 94 [Spd Reg Ki Base]. Units: %
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
101 [Speed Thresh Pos] Default: 1000 393
Threshold speed for the drive above or below which the value of Par Min/Max: 1 / 32767
A 393 [Speed Threshold] changes. When the speed of the drive Units: RPM
exceeds the value of this parameter, Par 393 [Speed Threshold]
displays “Above Thresh” (0). When the speed of the drive is below the
value of this parameter, Par 393 [Speed Threshold] displays “Below
Thresh” (1).
102 [Speed Thresh Neg] Default: 1000 393
Threshold speed for the drive above or below which the value of Par Min/Max: 1 / 32767
A 393 [Speed Threshold] changes. When the speed of the drive Units: PRM
exceeds the value specified in this parameter, Par 393 [Speed
Threshold] displays “Above Thresh” (0). When the speed of the drive
is below this threshold, Par 393 [Speed Threshold] displays “Below
Thresh” (1).
103 [Threshold Delay] Default: 100 393
Amount of time that must elapse before indication that the drive speed Min/Max: 0 / 65535
A is above the value set in Par 101 [Speed Thresh Pos] or below the Units: ms
value set in Par 102 [Speed Thresh Neg].
104 [At Speed Error] Default: 100 394
Defines the speed above and below the speed reference (in Par 118 Min/Max: 1 / 32767
A [Speed Reg In]) at which the value of Par 394 [At Speed] changes. Units: RPM
When the difference between the speed reference and the actual
speed is greater than the value of this parameter, Par 394 [At Speed]
displays “Not Equal” (0). When the difference between the speed
reference and the actual speed is less than the value of this
parameter, Par 394 [At Speed] displays “Equal” (1).
SPEED COMMAND
Speed Regulator
Fwd
Actual Speed = 0
Rev
Par 395
[At Zero Speed]
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
123 [Spd Zero I En] Default: 0= “Disable”
Enables/Disables the output of the integral section of the speed Options: 0= “Disable”
regulator. Used in the Zero Speed function. 1= “Enable”
A • “Enabled” = The output of the integral section of the speed
regulator is set to zero when the speed reference and the speed
feedback are equal to zero. The I component is enabled when a
reference value is entered to restart acceleration.
• “Disabled” = Disables the output of the integral section of the speed
regulator.
124 [Spd Ref Zero En] Default: 0= “Disable”
This parameter is only active when Par 125 [Spd Zero P En] = 1 Options: 0= “Disable”
“Enabled”. Used in the Zero Speed function. 1= “Enable”
A • “Enabled” = The proportional gain, equal to Par 126 [Spd Zero P
Gain] at zero speed, is equal to Par 87 [Spd Reg Kp] when the
speed reference is higher than the value defined in Par 106 [Ref
Zero Level].
• “Disabled” = The proportional gain, equal to Par 126 [Spd Zero P
Gain] at zero speed, is equal to the value in Par 87 [Spd Reg Kp]
when the speed reference or the actual speed is higher than the
value defined in Par 106 [Ref Zero Level].
SPEED COMMAND
“Enabled” = When both the speed reference value and the actual Options: 0= “Disable”
speed value = 0, the proportional gain value in Par 126 [Spd Zero P 1= “Enable”
A Gain] is active after the delay time defined in Par 108 [Speed Zero
Delay]. Used in the Zero Speed function.
“Disabled” = The speed regulator keeps its proportional gain
component when the drive is stopped.
126 [Spd Zero P Gain] Default: 10.00
The proportional gain of the speed regulator that is only active when Min/Max: 0.00 / 100.00
A the value of the speed reference and actual speed = 0. This Units: %
parameter is only active when Par 125 [Spd Zero P En] = 1 “Enabled”.
Used in the Zero Speed function.
242 [Speed Reg En] Default: 1= “Enabled” 39,
Enables/Disables the speed regulator output to the torque/current Options: 0= “Disabled” 41,
regulator. 1= “Enabled” 236
• “Enabled” = The speed regulator output is connected to the input of
the torque/current regulator.
• “Disabled” = The speed regulator output is not connected to the
input of the torque/current regulator. Par 39 [Torque Ref] is
connected to the input of the current regulator.
348 [Lock Speed Integ] Default: 1= “Not active”
Enables or disables the integral (I) function of the speed regulator. Options: 0= “Active”
A • “Not active” = The integral component of the speed regulator is 1= “Not active”
enabled.
• “Active” = The integral component of the speed regulator is
disabled.
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
388 [Flying Start En] Default: 0= “Disabled”
Enables/Disables the ability of the drive to connect to a spinning Options: 0= “Disabled”
A motor at actual RPM when a start command is issued. 1= “Enabled”
• “Enabled” = When the drive is turned on, the speed of the motor is
measured and the ramp output is set accordingly. The drive then
runs at the set reference value.
• “Disabled” = When the drive is turned on, the ramp starts from
zero.
Main uses:
•To connect to a motor that is already spinning due to its load (e.g.
in the case of pumps, the flowing medium).
•Re–connection to a spinning motor after a fault or alarm.
Note: If the Flying Start function is disabled, ensure that the motor is
not spinning when the drive is turned on, or harsh motor deceleration
in current limit may occur.
444 [Spd Fdbk Filter] Default: 0 121,
Time constant used by the filter for the Speed Feedback circuit. Min/Max: 0 / 1000 122
A Filtering of the high frequency components of the speed feedback Units: ms
signal is useful in the case of elastic coupling between the motor and
load (i.e., joints or belts).
445 [Spd Up Gain Pct] Default: 0.00
The Speed Up function gain as a percentage of Par 446 [Speed Up Min/Max: 0.00 / 100.00
A Base]. Units: %
446 [Speed Up Base] Default: 1000.00
The Speed Up function maximum gain. This value corresponds to Min/Max: 0.00 / 16000.00
A
SPEED COMMAND
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
1016 [SpdFuncSelect] Default: 0= “Speed Up” 444,
Selection of the “Speed Up” or “Inertia/Loss compensation” function. Options: 0= “Speed Up” 445,
Note that these two functions are mutually exclusive - if one is 1= “Inertia/loss” 447,
1012,
A selected, the other is off. 1013,
SPEED COMMAND
Speed Regulator
1014,
1015
Related
Group
No.
See page 3-2 for symbol descriptions Values
18 [Ramp Type Select] Default: 0= “Linear”
Determines the type of ramp used. Options: 0= “Linear”
• 0 “Linear” = Linear ramp 1= “S shaped”
• 1 “S shaped” = S–shaped ramp
19 [S Curve Time] Default: 1.00 18,
S-shaped curve time constant. The value of Par 19 [S Curve Time] is Min/Max: 0.10 / 60.00 665,
added to the ramp time of linear ramps, regardless of speed changes. Units: s 666,
If the value of [S Curve Time] is changed, Pars 665 and 667 [S Curve 667,
Accel x] and 666 and 668 [S Curve Decel x] are set to the same value. 668
If any of parameters 665-668 are changed later, the last change is
valid.
S Curve Time
Par 20
[Ramp Delay]
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
32 [Decel Time 2] Default: 10 2
Sets the rate of deceleration for Ramp 2. Min/Max: 0 / 65535
Deceleration rate for Ramp 2 = Par 2 [Maximum Speed] / Par 30 Units: s
[Decel Time 2].
245 [Speed Ramp En] Default: 1= “Enabled”
Enables or disables the ramp function. The Ramp Reference block is Options: 0= “Disabled”
bypassed when this parameter is set to 0 “Disabled”. 1= “Enabled”
344 [Zero Ramp Output] Default: 1= “Not Active”
Activates either the ramp output (1) or the brake function (0). When Options: 0= “Active”
A this parameter is set to 0 “Active”, the drive brakes through the 1= “Not Active”
maximum available torque and the motor will perform a Current Limit
Stop. Two quadrant drives do not support a brake option.
• “Active” = The ramp output is disabled and Pars 113 [Ramp Out]
and 114 [Ramp Out Pct] are immediately set to zero.
• “Not Active” = The ramp output is enabled. and Pars 113 [Ramp
Out] and 114 [Ramp Out Pct] follow the Ramp Reference block
commands.
345 [Zero Ramp Input] Default: 1= “Not Active” 110,
Activates or deactivates the ramp input. Options: 0= “Active” 111
A • “Active” = The ramp input is not active and Pars 110 [Ramp In] and 1= “Not Active”
111 [Ramp In Pct] = 0.
• “Not Active” = The ramp input is activated and Pars 110 [Ramp In]
and 111 [Ramp In Pct] correspond to the set reference.
373 [Freeze Ramp] Default: 1= “Not Active”
DYNAMIC CONTROL
Determines whether the last ramp output reference value is retained Options: 0= “Active”
A or whether the ramp output reference value is active. 1= “Not Active”
Ramp Rates
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
13 [Torq Red CurLim] Default: 100 342
A The armature current limit, defined as a percentage of the value Min/Max: 0 / 200
defined in Par 179 [Nom Mtr Arm Amps] when Par 342 [Torque Units: %
Reduction] is set to 1 “Active”.
696 [Droop Percent] Default: 0.00 41,
Droop function gain is a percentage of the ratio between Par 45 [Max Min/Max: 0.00 / 100.00 45,
A Ref Speed] and the difference of Par 698 [Load Comp] – Par 41 Units: % 698
[Current Reg In]. Therefore, when the difference between Par 698
[Load Comp] and Par 41 [Current Reg In] = 100% and Par 696 [Droop
Percent] = 100%, the speed reference correction signal is equal to Par
45 [Max Ref Speed].
697 [Droop Filter] Default: 0
Droop filter time constant for the Droop function. Min/Max: 0 / 1000
A Units: ms
698 [Load Comp] Default: 0
The load compensation signal. This value is typically equal to the Min/Max: + / –200
A “master” drive’s current. The load compensation signal is a Units: %
percentage of Idn.
699 [Enable Droop] Default: 0= “Disabled”
Enables/Disables the Droop function. Options: 0= “Disabled”
A
Load Limits
Speed] / [Fast Stop Time]. This feature can be used when [Digital Inx
Sel] is set to 30 “Fast Stop” or when certain faults are configured for
“Quick Stop”.
627 [Spd 0 Trip Delay] Default: 0
The amount of time that will elapse after the drive reaches zero speed Min/Max: 0 / 40000
A before it is disabled. Units: ms
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
1262 [Closing Speed] Default: 30
A Motor speed at which the brake is closed. Used with External Brake
Control.
Min/Max:
Units:
0 / 200
RPM
1263 [Opening Delay] Default: 0
Stop Modes
A Amount of time before the brake will open after the drive has been
enabled. Used with External Brake Control.
Min/Max:
Units:
0 / 30000
ms
1265 [Ramp In Zero En] Default: 0= “Disabled”
A Enables/Disables the setting of the ramp input to zero. Used with
External Brake Control.
Options: 0=
1=
“Disabled”
“Enabled”
1266 [Actuator Delay] Default: 0
A Amount of time before the actuator releases the load. Used with
External Brake Control.
Min/Max:
Units:
0 / 30000
ms
1344 [Start At Powerup] Default: 0= “Disabled” 1345
Enables/Disables the ability to issue a “Run” command and Options: 0= “Disabled”
automatically resume running at commanded speed after drive input 1= “Enabled”
power is restored and the time in Par 1345 [Powerup Delay] has
elapsed. Requires a digital input configured for “Run” and a valid start
condition.
Restart Modes
ATTENTION: Equipment damage and/or personal injury may result if this parameter is used in
an inappropriate application. Do not use this function without considering applicable local,
! national and international codes, standards, regulations or industry guidelines.
Defines the programmed delay time, in seconds, before a start Min/Max: 1 / 10800
command is accepted after a power up. If a “Start”, “Run” or “Stop” Units: s
command is asserted before the time in this parameter expires, the
“Start At Powerup” function will be aborted.
181 [Adaptive Spd En] Default: 0= “Disabled” 182,
Enables/Disables adaptive speed regulation. Options: 0= “Disabled” 183
The adaptive speed regulator function enables different gains of the 1= “Enabled”
A speed regulator depending on the speed or another variable (Par 183
[Adaptive Ref]). This allows optimum adaptation of the speed
regulator to your specific application. When adaptive speed regulation
is disabled, the regulator operates based on the settings in the
individual regulation parameters.
182 [Adaptive Reg Typ] Default: 0= “Speed” 183
Selects the type of regulation used. Options: 0= “Speed”
• “Speed” = The regulator parameters follow a speed reference. 1= “Adaptive Ref”
A • “Adaptive Ref” = The regulator parameters follow the reference
Adaptv Regulator
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
186 [Adaptive Joint 1] Default: 6.11 184
Defines a range above and below the value set in Par 184 [Adaptive Min/Max: 0.00 / 200.00
A Spd 1] within which there is a linear change in gain from parameter Units: %
set 1 to parameter set 2 in order to prevent jumps in the adaptive
speed regulator. The value in this parameter is defined as percentage
of the value defined Par 45 [Max Ref Speed].
187 [Adaptive Joint 2] Default: 6.11 185
Defines a range above and below the value set in Par 185 [Adaptive Min/Max: 0.00 / 200.00
A Spd 2] with in which there is a linear change in gain from parameter Units: %
set 2 to parameter set 3 in order to prevent jumps in the adaptive
speed regulator. The value in this parameter is defined as percentage
of the value defined Par 45 [Max Ref Speed].
188 [Adaptive P Gain1] Default: 10.00 93,
Proportional gain for the range from zero to the value set in Par 184 Min/Max: 0.00 / 100.00 184
A [Adaptive Spd 1]. The value in this parameter is defined as Units: %
percentage of the value defined in Par 93 [Spd Reg Kp Base].
189 [Adaptive I Gain1] Default: 1.00 94,
DYNAMIC CONTROL
Adaptv Regulator
Integral gain for the range from zero to Par 184 [Adaptive Spd 1]. The Min/Max: 0.00 / 100.00 184
A value in this parameter is defined as percentage of the value defined Units: %
Par 94 [Spd Reg Ki Base].
190 [Adaptive P Gain2] Default: 10.00 93,
Proportional gain for the range of values defined beginning with the Min/Max: 0.00 / 100.00 184,
A value of Par 184 [Adaptive Spd 1] to the value defined in Par 185 Units: % 185
[Adaptive Spd 2]. The value in this parameter is defined as
percentage of the value defined Par 93 [Spd Reg Kp Base].
191 [Adaptive I Gain2] Default: 1.00 94,
Integral gain for the range of values defined beginning with the value Min/Max: 0.00 / 100.00 184,
A of Par 184 [Adaptive Spd 1] to the value defined in Par 185 [Adaptive Units: % 185
Spd 2]. The value in this parameter is defined as percentage of the
value defined Par 94 [Spd Reg Ki Base].
192 [Adaptive P Gain3] Default: 10.00 93,
Proportional gain for the range of values beginning above the value Min/Max: 0.00 / 100.00 185
A defined in Par 185 [Adaptive Spd 2]. The value in this parameter is Units: %
defined as percentage of the value defined Par 93 [Spd Reg Kp
Base].
193 [Adaptive I Gain3] Default: 1.00 94,
Integral gain for the range of values beginning above the value Min/Max: 0.00 / 100.00 185
A defined in Par 185 [Adaptive Spd 2]. The value in this parameter is Units: %
defined as percentage of the value defined Par 94 [Spd Reg Ki Base].
Applications File
Related
Group
No.
digital input, this parameter must be brought at a high logical level 1= “Enabled”
(+24V).
771 [PI Output] Default: Read Only 784,
Output value of the PI block, adapted to the value between the values Min/Max: 0 / 10000 785,
A defined in Pars 784 [PI Upper Limit] and 785 [PI Lower Limit]. When 779
the drive is turned on, the value of this parameter is acquired
automatically based on the value of Par 779 [PI Central v sel] x 1000.
776 [PI Central v1] Default: 0.00 784,
The first value that can be selected, via Par 779 [PI Central v sel], as Min/Max: Par 785 [PI Lower Limit] / Par 784 785,
A the initial output of the PID regulator’s integral component [PI Upper Limit] 779
(corresponding to initial diameter 1). The value entered in this
parameter must be less than the value set in Par 784 [PI Upper Limit]
and greater than the value set in Par 785 [PI Lower Limit].
777 [PI Central v2] Default: 0.00 784,
The second value that can be selected, via Par 779 [PI Central v sel], Min/Max: Par 785 [PI Lower Limit] / Par 784 785,
A as the initial output of the PID regulator’s integral component (corre- [PI Upper Limit] 779
sponding to initial diameter 2). The value entered in this parameter
must be less than the value set in Par 784 [PI Upper Limit] and great-
er than the value set in Par 785 [PI Lower Limit].
778 [PI Central v3] Default: 0.00 784,
The third value that can be selected, via Par 779 [PI Central v sel], as Min/Max: Par 785 [PI Lower Limit] / Par 784 785,
A the initial output of the PID regulator’s integral component [PI Upper Limit] 779
(corresponding to initial diameter 3). The value entered in this
parameter must be less than the value set in Par 784 [PI Upper Limit]
and greater than the value set in Par 785 [PI Lower Limit].
Note: This parameter can be assigned to an analog input.
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
779 [PI Central v sel] Default: 1 769,
Selects one of the four possible initial output values of the PID Min/Max: 0/3 776,
A regulator integral component (corresponding to the initial diameter) of 777,
the PI block. 778,
• “0” = When the PI block is disabled (Par 769 [Enable PI] = 780,
“Disabled”), the last value of the integral component calculated 781
(corresponding to swift diameter) is stored in Par 771 [PI Output].
This value is used by the PID regulator when the PI block is
enabled again and the drive is restarted. This function is useful
when for any reason the drive must be turned off or if incoming
power is removed from the drive.
• “1”, “2”, or “3” = When the PI block is disabled (Par 769 [Enable PI]
= “Disabled”), the value of [PI Output] will be set to the value of the
selected parameter (“1” = 776 [PI Central v1], “2” = 777, [PI Central
v2], or “3” = 778 [PI Central v3] x1000). This value is only used by
the PID regulator when the drive is powered up and Par 769
[Enable PI] is already enabled.
Note: Par 779 [PI Central v sel] can be set directly from the HIM or
through two digital inputs set respectively as “PI central vs0” and “PI
central vs1”. Refer to Pars 780 [PI Central vs0] and 781 [PI Central
vs1] for more information on this configuration.
780 [PI Central vs0] Default: 0
When assigned to a digital input and used in combination with Par Min/Max: 0/1
A 781 [PI Central vs1], through binary selection, determines which of
the four possible output values is used as the initial level of the
integral component (corresponding to the initial diameter) of the PI
block.
APPLICATIONS
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
421 [PD Output PID] Default: Read Only
Proportional / Derivative (PD) block output. Min/Max: –/+10000
A
766 [PD Deriv Gain 1] Default: 1.00 181
First derivative gain of the PD block. The value specified in this field Min/Max: 0.00 / 100.00
A depends on the enabling and configuration of Par 181 [Adaptive Spd
En].
767 [PD Deriv Filter] Default: 0
Time constant of the filter from the derivative portion of the PD block. Min/Max: 1 / 1000
A Units: ms
768 [PD Prop Gain 1] Default: 10.00 181
First proportional gain of the block PD. The value specified in this field Min/Max: 0.00 / 100.00
A depends on the enabling and configuration of Par 181 [Adaptive Spd
En].
770 [Enable PD] Default: 0= “Disabled”
PD Control
When Par 758 [Feed Fwd PID] = +8000, the positive limit of Par 771
[PI Output] will be automatically set at 10000 / ( 8000 / 1000 ) = 1250.
731 [PID Steady Delay] Default: 0 695,
The amount of time for which the gains in Pars 793 [PI Init Prop Gn] Min/Max: 0 / 60000 734,
A and 734 [PI Init Intgl Gn] will remain enabled after feed–forward has Units: ms 793
exceeded the threshold value defined in Par 695 [PI Steady Thrsh].
734 [PI Init Intgl Gn] Default: 10.00 695,
The initial value of the integral gain. This parameter is active when Min/Max: 0.00 / 100.00 731,
A feed–forward is greater than the value defined in Par 695 [PI Steady 769
Thrsh], or Par 769 [Enable PI] transitions from “0” (low) to “1” (high)
and the amount of time defined in Par 731 [PID Steady Delay] has
elapsed.
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
757 [PID Clamp] Default: 10000 759,
The PID “clamp” allows a smooth tension setting of a controlled Min/Max: 0 / 10000 763,
A system winder/unwinder when the calculation of the initial diameter 770
function cannot be used.
• When enabling the drive, the dancer is at the lowest point of its full
scale. In this case, with Par 759 [PID Error] at its maximum value,
the motor could accelerate too fast to properly configure the dancer
for its central operating position. By setting the value of Par 757
[PID Clamp] sufficiently low. e.g, = 1000, when the drive starts and
Par 770 [Enable PD] = 1 “Enable”, the value of Par 759 [PID Error]
is limited to 1000 until the signal coming from the dancer (via Par
763 [PID Feedback]) goes above the value in this field. Then, the
value of [PID Clamp] is automatically returned to its maximum
value of 10000. The PID clamp is kept at 10000 until the drive
stops or Par 770 [Enable PD] = 0 “Disabled”.
758 [Feed Fwd PID] Default: Read Only
Feedback from the transducer position (dancer) or tension. Min/Max: –/+10000
A
759 [PID Error] Default: Read Only
Error value input to the PID function (output of the PID Clamp block). Min/Max: –/+10000
A
APPLICATIONS
First offset value added to Par 763 [PID Feedback]. This parameter Min/Max: –/+10000
A can be assigned to an analog input, e.g., for the tension setting when
a load cell must be used as feedback.
761 [PID Setpoint 1] Default: 0 763
Second offset value added to Par 763 [PID Feedback]. Min/Max: –/+10000
A
762 [PID Setpoint Sel] Default: 0= “Setpoint 0” 763
Selects the offset value added to Par 763 [PID Feedback]. This Options: 0= “Setpoint 0”
A parameter can be assigned to a digital input. 1= “Setpoint 1”
763 [PID Feedback] Default: 0
Analog input feedback value received from the transducer position Min/Max: –/+10000
A (dancer) or tension (load cell).
772 [PID Output Sign] Default: 1= “Bipolar”
Determines whether the output of the PID regulator is bipolar or Options: 0= “Positive”
A positive (clamp of the negative side). 1= “Bipolar”
773 [PID Output Scale] Default: 1.00 774
Scale factor for Par 774 [PID Output]. The value of this parameter Min/Max: –/+100.00
A depends on to which parameter you want to send the PID regulator
output.
774 [PID Output] Default: Read Only
Displays the PID regulator output. Min/Max: –/+10000
A Note: This parameter can be assigned to an analog output in order to
provide a cascaded reference in multi-drive systems.
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
782 [PID Target] Default: 0= “Not Used”
Parameter number to which the PID Output value will be written.
A
Options:
Options:
PID Control
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
1254 [PID Error Gain] Default: 1.005 759
PID Control
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
490 [Scale1 In Off] Default: 0.00
559 [Scale2 In Off]
1224 [Scale3 In Off] Min/Max: – 231/ +231 – 1
1233 [Scale4 In Off]
1242 [Scale5 In Off]
1251 [Scale6 In Off]
Offset to be added to the input quantity. Resolution: 5 digits. Refer to
A the Scale Blocks block diagram on page D-18 for more information.
491 [Scale1 Out Off] Default: 0.00
560 [Scale2 Out Off]
1225 [Scale3 Out Off] Min/Max: – 231/ +231 – 1
1234 [Scale4 Out Off]
1243 [Scale5 Out Off]
Scale Blocks
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
1153 [Max Diameter] Default: 1.00
Maximum roll diameter. Min/Max: 0.00 / 32.00
Units: m
A
1154 [Roll Diameter] Default: Read Only
A Displays the calculated roll diameter. Note: This parameter can be
assigned to an analog output as a percentage of Par 1153 [Max
Min/Max:
Units:
0.00 / 32.00
m
Diameter].
1155 [Line Spd Thresh] Default: 5.00 1162,
1206,
A Line speed detecting threshold. When the value of Par 1286 [Ref Line
Speed] is lower than the value of [Line Spd Thresh], the diameter
Min/Max:
Units:
0.00 / 150.00
% 1207,
calculation stops and the diameter is kept at a constant value. When 1286
the value of [Ref Line Speed] overcomes the threshold, the diameter
calculation is enabled with an initial filter corresponding to the value in
Par 1206 [Diam init filter] for the time set in Par 1207 [Diam stdy
delay]. At the end of this time the filter will be set to the value of Par
1162 [Diameter Filter].
1156 [Line Spd Gain] Default: 0 1160,
1284
A Calibration value used to obtain Par 1160 [Line Speed Pct] = 100% at
its maximum value. The value of this parameter depends on the value
Min/Max: 0 / 32767
1159
A Diameter threshold as a percentage of Par 1153 [Max Diameter]. Par
1159 [Diameter Reached] is set to “1” when the value in this
Min/Max:
Units:
0.00 / 150.00
%
parameter is exceeded.
1159 [Diameter Reached] Default: Read Only 1158
A Indication that the diameter threshold set in Par 1158 [Diam
Threshold] has been exceeded.
Min/Max: 0/1
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
1166 [Diam Preset 2] Default: 1.00 799,
1153
A Third preset starting diameter. The value of this parameter must be
set between the value of Pars 799 [Minimum Diameter] and 1153
Min/Max:
Units:
0.00 / 32.00
m
[Max Diameter].
1167 [Diam Preset 3] Default: 1.00 799,
1153
A Fourth preset starting diameter. The value of this parameter must be
set between the value of Pars 799 [Minimum Diameter] and 1153
Min/Max:
Units:
0.00 / 32.00
m
[Max Diameter]. This parameter can be assigned to an analog input. If
an analog input is used, +10V corresponds to the value of [Max
Diameter] and the voltage corresponding to the minimum diameter =
10 x ([Minimum Diameter] / [Max Diameter]).
1168 [Diam Preset Sel] Default: 0 1164,
1165,
A Selects the starting diameter for the Diameter Calculation function.
• 0 = Par 1164 [Diam Preset 0]
Min/Max: 0/3
1166,
• 1 = Par 1165 [Diam Preset 1] 1167
• 2 = Par 1166 [Diam Preset 2]
• 3 = Par 1167 [Diam Preset 3]
This parameter can also be set via two digital inputs programmed as
Diameter Calc
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
1176 [Taper Enable] Default: 0= “Disabled”
Enables/Disables the Taper function. Options: 0= “Disabled”
A 1= “Enabled”
1177 [Initial Diameter] Default: 0.10
Diameter that starts the taper tension reduction. Min/Max: 0.00 / 32.00
A Units: m
1178 [Final Diameter] Default: 1.00
Diameter that ends the taper tension reduction. Min/Max: 0.00 / 32.00
A Units: m
1179 [Tension Reduct] Default: 0.00 1180
Taper tension reduction as a percentage of Par 1180 [Tension Ref]. Min/Max: 0.00 / 199.99
A Units: %
1180 [Tension Ref] Default: 0.00
A Tension reference.
Note: This parameter can be assigned to an analog output.
Min/Max:
Units:
0.00 / 199.99
%
1181 [Tension Scale] Default: 100
A Scale factor of the torque current. This parameter is used when the
value of the maximum winding torque must be limited or when a
Min/Max:
Units:
0 / 200
%
closed loop control is used in order to adjust the torque current value
to the real tension on the material measured by the load cell.
1182 [Time AccDec Min] Default: 9.00
A The amount of time corresponding to the lower acceleration, deceler-
ation and fast deceleration time.
Min/Max:
Units:
0.15 / 300
s
1183 [Int Acc Calc En] Default: 1= “Enabled” 1182,
Enables/Disables the calculation for coil acceleration. 1184,
Winder Functions
Options: 0= “Disabled”
APPLICATIONS
• “Enabled” = This function carries out the calculation of the angular 1= “Enabled” 1185,
acceleration inside the drive. In this case it is necessary to set just 1186
A
the value of Par 1182 [Time AccDec Min].
• “Disabled” = It is necessary to set Pars 1184 [Line Accel Pct], 1185
[Line Decel Pct], 1186 [Line FastStp Pct] and 1182 [Time AccDec
Min] and to supply the corresponding status indication to the digital
inputs.
1184 [Line Accel Pct] Default: 100.00 1182
Acceleration time as a percentage Par 1182 of [Time AccDec Min]. Min/Max: 0.00 / 100.00
A Units: %
1185 [Line Decel Pct] Default: 100.00 1182
Deceleration time as a percentage of Par 1182 [Time AccDec Min]. Min/Max: 0.00 / 100.00
A Units: %
1186 [Line FastStp Pct] Default: 100.00 1182
A Fast
Min].
deceleration time as a percentage of Par 1182 [Time AccDec Min/Max:
Units:
0.00 / 100.00
%
1187 [Winder Type] Default: 0= “Winder”
A Winder/unwinder selection. If the selection is carried out via a digital
input: 0V = “Winder” , +24V = “Unwinder”.
Options: 0=
1=
“Winder”
“Unwinder”
1193 [Torq Current Pct] Default: Read Only
A Displays the amount of torque current required.
Note: This parameter can be assigned to an analog output.
Min/Max:
Units:
0.00 / 200.00
%
1194 [Act Ten Ref Pct] Default: Read Only 1179,
1180
A Displays the percentage of tension reference less the Taper
percentage set via Par 1179 [Tension Reduct]. If the Taper function is
Min/Max:
Units:
0.00 / 199.99
%
not enabled, it corresponds to the value displayed in Par 1180
[Tension Ref].
1195 [Speed Match] Default: 0= “Off”
A Coil “launching” phase command for automatic switching.
Note: This parameter can be assigned to a digital input.
Options: 0=
1=
“Off”
“On”
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
1196 [Spd Match Acc] Default: 83.88
Motor acceleration time during the launching phase. Min/Max: 0.30 / 300.00
A Units: s
1197 [Spd Match Dec] Default: 83.88
A Motor deceleration time. If the motor decelerates during the launching
phase a stop command is issued.
Min/Max:
Units:
0.30 / 300.00
s
1198 [Offs Accel Time] Default: 83.88
A Ramp time for the initial phase when the machine is stopped. It refers
to Par 45 [Max Ref Speed].
Min/Max:
Units:
0.30 / 300.00
s
1199 [W Offset] Default: 0
A Speed reference offset for the initial phase of the winder/unwinder
when the line is stopped.
Min/Max:
Units:
0 / 1000
RPM
1200 [Spd Match Gain] Default: 100
A Speed reference gain during the launching phase. 100% corresponds
to a peripheral speed equal to the line speed.
Min/Max:
Units:
0 / 150
%
1201 [Winder Side] Default: 0
A Selection
• “0” = Up
of the winding/unwinding side. Min/Max: 0/1
• “1” = Down
Note: This parameter can be assigned to a digital input.
1202 [W Gain] Default: 0
A Sets the speed reference gain used to saturate the speed loop. This
parameter is a percentage of the increasing/decreasing value of the
Min/Max:
Units:
0 / 100
%
angular speed reference.
Winder Functions
can be changed.
• “1” = Launching ramp completed
• “0” = Launching ramp not completed
1204 [Line Spd Source] Default: 0
Number of the sampling parameter for the line speed. Min/Max: 0 / 65535
A
1208 [Close Loop Comp] Default: Read Only
Active compensation status (output of the PID regulator). Min/Max: – / +32767
A
1209 [Torque Winder En] Default: 0= “Disabled”
Enables/disables the center winder function. Options: 0= “Disabled”
A 1= “Enabled”
1210 [W Target] Default: 0
Parameter number of the speed reference address. Min/Max: 0 / 65535
A
1213 [Actual Comp] Default: Read Only
A Active compensation status (sums up the static, dynamic and inertial
frictions) as a percentage of the drive rated current.
Min/Max:
Units:
–/+200
%
Note: This parameter can be assigned to an analog output.
1214 [Closed Loop En] Default: 0= “Disabled”
Enables/Disables closed loop tension control (used with a load cell). Options: 0= “Disabled”
1= “Enabled”
A
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
1215 [Speed Demand En] Default: 0= “Disabled”
A Enables/Disables the speed reference calculation for the Torque
Winder application.
Options: 0=
1=
“Disabled”
“Enabled”
1216 [Spd match torque] Default: 100
Sets the torque current during the launching and change phase. Min/Max: 0 / 200
A Units: %
1217 [W Reference] Default: Read Only 1160
A Angular speed reference.
Note: This parameter can be assigned to an analog output; 10V =
Min/Max:
Units:
–/+8192
RPM
100% of Par 45 [Max Ref Speed].
1255 [Jog TW Speed] Default: 0 1160
A Torque Winder jog reference. The parameter is entered as a
percentage of Par 1160 [Line Speed Pct].
Min/Max:
Units:
0 / 100
%
1256 [Jog TW Enable] Default: 0= “Disabled”
Winder Functions
Utility File
Related
Group
No.
At Pwr Down
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Default x x x x x x x x x x x x x x x 1
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Enables/Disables the feature that saves the present MOP frequency reference at power down or at stop.
Note: This parameter can be assigned to a digital input.
• Bit 0 “At Pwr Down” - When set to “0” = Do not save, “1” = Save
• Bit 1 “At Stop” - When set to “0” = Do not save, “1” = Save
At Pwr Down
UTILITY
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
At Stop
Default x x x x x x x x x x x x x x 0 0
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
346 [Torque Positive] Default: Read Only 20
Indicates whether the drive is operating with a positive torque Min/Max: 0/1
A reference.
• 1 “Active” = The drive is operating with a positive torque reference.
The motor is accelerating in the forward direction or decelerating in
the negative direction and Par 20 [Ramp Delay] has timed out.
• 0 “Not Active” = The drive is not operating with a positive torque
reference.
Note: This parameter can be assigned to a digital output.
347 [Torque Negative] Default: Read Only 20
Indicates whether the drive is operating with a negative torque Min/Max: 0/1
A reference.
• 1 “Active” = The drive is operating with negative torque reference.
The motor is accelerating in the reverse direction or decelerating in
the forward direction and Par 20 [Ramp Delay] has timed out.
• 0 “Not Active” = The drive is not operating with negative torque
Diagnostics
UTILITY
reference.
Note: This parameter can be assigned to a digital output and is used
for four quadrant drives only.
349 [CurrLimit Active] Default: Read Only
Indicates whether or not the drive is working within the set current Min/Max: 0/1
limits.
• 1 “Active” = The drive is currently in a current limited state.
• 0 “Not Active” =The drive is not in a current limited state.
Note: This parameter is assigned to digital output 4 (Par 148 [Digital
Out4 Sel]) by default.
372 [Spd Limit Active] Default: Read Only
Indicates whether the current speed reference value is limited by the Min/Max: 0/1
defined minimum and maximum limit values.
• 1 “Active” = The reference value is currently limited since the value
entered is out of range of the limit values defined.
• 0 “Not Active” = The reference value is within the defined limit
values.
Note: This parameter can be assigned to a digital output.
Related
Group
Parameter Name & Description
File
Command Dir
Decelerating
Local ID 2 (1)
Local ID 1 (1)
Local ID 0 (1)
Accelerating
Actual Dir
At Speed
Faulted
Ready
Active
Default 0 0 0 0 0 0 1 0 0 Alarm
0 0 0 1 1 0 1
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
(2) (1)
Bits Bits
15 14 13 12 Description 11 10 9 Description
0 0 0 0 Spd Ref A Auto 0 0 0 Port 0 (TB)
0 0 0 1 Spd Ref B Auto 0 0 1 DPI Port 1
0 0 1 0 Preset Spd 2 Auto 0 1 0 DPI Port 2
Diagnostics
UTILITY
Stopping
Running
Jogging
Ready
Active
Default x x x x x x x x 0 0 0 0 0 0 0 1
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
393 [Speed Threshold] Default: Read Only 101,
Indicates if the drive is above or below the threshold speed specified Min/Max: 0/1 102,
A in parameters 101 [Speed Thresh Pos] (clockwise rotation) and 102 103
[Speed Thresh Neg] (counter-clockwise rotation).
• “0 Above Thresh” = The speed has exceeded the set speed
threshold.
• “1 Below Thresh” = The speed has not exceeded the set speed
threshold.
Note: This parameter can be assigned to a digital output.
394 [At Speed] Default: Read Only 104,
Indicates whether or not the current speed of the drive corresponds Min/Max: 0/1 105
to the speed reference (specified in Par 118 [Speed Reg In]) before
the speed regulator and the ramp reference (if enabled) are applied.
The speed above and below the speed reference at which [At Speed]
will indicate “1 Equal” is set in Par 104 [At Speed Error].
• “0 Not Equal” - The drive is not working at the set speed reference.
• “1 Equal” - The drive is working at the set speed reference.
Note: This parameter can be assigned to a digital output. It also
corresponds to the "At Speed" indication on the Status Line of the
HIM.
395 [At Zero Speed] Default: Read Only 107,
Indicates whether or not the actual speed of the motor is below the Min/Max: 0/1 108
zero speed threshold as specified in Par 107 [Speed Zero Level].
• “0 Equal” - The actual speed is below the value of Par 107 [Speed
Diagnostics
UTILITY
Zero Level] and Par 108 [Speed Zero Delay] has timed out.
• “1 Not Equal” - The actual speed is above the value of Par 107
[Speed Zero Level].
Note: This parameter can be assigned to a digital output.
396 [MOP Inc Active] Default: Read Only
Indicates whether or not the drive is accelerating using the Min/Max: 0/1
A preselected ramp.
• 0 “No Accel” = the drive is not accelerating using a preselected
ramp
• 1 “Accel” = the drive is accelerating using a preselected ramp
397 [MOP Dec Active] Default: Read Only
Indicates whether the drive is decelerating using the preselected Min/Max: 0/1
A ramp.
• 0 “No Decel” = The drive is not decelerating using a preselected
ramp
• 1 “Decel” = The drive is decelerating using a preselected ramp
400 [Spd Select 0] Default: Read Only 401,
Indicates the state of the assigned digital input, [Digital Inx Sel], set to Min/Max: 0/1 402
A 17 “Speed Sel 1”. Refer to Option Definitions for [Digital Inx Sel] on
page 3-66 for instructions on how to set digital input speed selects to
different speed references.
• “0” = Digital input [Digital Inx Sel] set to 17 “Speed Sel 1” not
asserted
• “1” = Digital input [Digital Inx Sel] set to 17 “Speed Sel 1” asserted
Note: By default, the state of this parameter is determined by digital
input 5.
Related
Group
Parameter Name & Description
File
page 3-66 for instructions on how to set digital input speed selects to
different speed references.
• “0” = Digital input [Digital Inx Sel] set to 18 “Speed Sel 2” not
asserted
• “1” = Digital input [Digital Inx Sel] set to 18 “Speed Sel 2” asserted
Note: By default, the state of this parameter is determined by digital
input 6.
402 [Spd Select 2] Default: Read Only 400,
401
A Indicates the state of the assigned digital input, [Digital Inx Sel], set to
19 “Speed Sel 3”. Refer to Option Definitions for [Digital Inx Sel] on
Min/Max: 0/1
page 3-66 for instructions on how to set digital input speed selects to
different speed references.
• “0” = Digital input [Digital Inx Sel] set to 19 “Speed Sel 3” not
asserted
• “1” = Digital input [Digital Inx Sel] set to 19 “Speed Sel 3” asserted
Note: By default, the state of this parameter is determined by digital
input 7.
403 [Ramp Select 0] Default: Read Only 404
A Indicates the state of the assigned digital input, [Digital Inx Sel], set to
25 “Acc2 & Dec2” or 26 “Accel 2”.
Min/Max: 0/1
input.
404 [Ramp Select 1] Default: Read Only 403
A Indicates the state of the assigned digital input, [Digital Inx Sel], set to
25 “Acc2 & Dec2” or 27 “Decel 2”.
Min/Max: 0/1
• ‘1” = OK
This parameter can be assigned to a digital output.
1188 [Accel Status] Default: Read Only
A Indicates the drive acceleration status.
• “0” = Off - Drive not accelerating
Min/Max: 0/1
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
1328 [Drive Logic Rslt]
The final logic command resulting from the combination of all DPI and discrete inputs. This parameter has the same
structure as the product specific logic command received via DPI and is used in peer to peer communications. For each bit,
1=Condition true and 0=Condition false.
Bit 0 “Stop” - Stop command
Bit 1 “Start” - Start command
Bit 2 “Jog” - Jog command
Bit 3 “Clear Faults” - Clear faults command
Bit 4 “Forward” - Forward direction command
Bit 5 “Reverse” - Reverse direction command
Bit 6 “Local” - Local control command”
Bit 7 “MOP Inc” - MOP Increment command
Bit 8 “Accel 1” - Acceleration Rate 1 command
Bit 9 “Accel 2” - Acceleration Rate 2 command
Bit 10 “Decel 1” - Deceleration Rate 1 command
Bit 11 “Decel 2” - Deceleration Rate 2 command
Bit 12-14 “Spd Ref ID 0-2” - Speed reference source(1)
Bit 15 “MOP Dec” - MOP Decrement command
Spd Ref ID 2
Spd Ref ID 1
Spd Ref ID 0
Clear Faults
MOP Dec
MOP Inc
Reverse
Forward
Decel 2
Decel 1
Accel 2
Accel 1
Local
Start
Stop
Jog
Default 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
(1)
Bits
14 13 12 Description
Diagnostics
Related
Group
Parameter Name & Description
File
13 = “Reserved”
1403 [Start Inhibits]
Displays the inputs currently preventing the drive from starting. For each bit, 1=Inhibit condition true and 0=Inhibit condition
false.
Type 2 Alarm
Stop Assertd
Startup Actv
DPI Port 5
DPI Port 4
DPI Port 3
DPI Port 2
DPI Port 1
Reserved
Reserved
Reserved
Reserved
Reserved
Digital In
Enable
Fault
Default x x x 0 0 0 0 0 x 0 0 1 x 0 0 0
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Allows you to reset drive faults and/or clear the fault queue. Options: 0= “Ready”
1= “Clear Faults”
2= “Clr Flt Que”
1348 [Fault Clr Mode] Default: 1= “Enabled”
Enables/Disables a fault reset (clear faults) attempt from any source. Options: 0= “Disabled”
This does not apply to fault codes which are cleared indirectly via 1= “Enabled”
other actions.
1349 [Status1 at Fault] 381
Captures and displays Par 381 [Drive Status 1] bit pattern at the time of the last fault. 0=Condition False, 1=Condition True.
Command Dir
Faults
Spd Ref ID 3
Spd Ref ID 2
Spd Ref ID 1
Spd Ref ID 0
Decelerating
Accelerating
Local ID 2
Local ID 1
Local ID 0
Actual Dir
At Speed
Faulted
Ready
Active
Alarm
Default 0 0 0 0 1 1 1 0 1 0 0 0 1 1 0 0
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Stopping
Running
Jogging
Ready
Active
Default x x x x x x x x x 0 0 0 1 1 0 0
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
1351 [Fault 1 Code] Default: Read Only
1352 [Fault 2 Code]
1353 [Fault 3 Code] Min/Max: 0 / 32768
1354 [Fault 4 Code]
1355 [Fault 5 Code]
1356 [Fault 6 Code]
1357 [Fault 7 Code]
1358 [Fault 8 Code]
1359 [Fault 9 Code]
1360 [Fault 10 Code]
A code that represents the fault that tripped the drive. The codes will
A appear in these parameters in the order they occur (i.e., [Fault 1
Code] = the most recent fault). Refer to Fault Descriptions on
page 4-4 for a list of possible codes.
Note: Par 1351 [Fault 1 Code] is accessible via the Basic Parameter
view.
1361 [Fault 1 Time] Default: Read Only
1362 [Fault 2 Time]
1363 [Fault 3 Time] Min/Max: 0.000 / 134000000.000
1364 [Fault 4 Time] Units: hr.
1365 [Fault 5 Time]
Faults
Related
Group
Parameter Name & Description
File
Bit 1 “DigInCflctB” - A digital Start input has been configured without a Stop input or other functions are in conflict.
Bit 2 “DigInCflctC” - More than one physical input has been configured to the same input function.
Bit 3 “BipolarCflct” - Parameter 1322 [Direction Mode] is set to “Bipolar” or “Reverse Dis” and one or more of the following
digital input functions is configured: “Fwd/Reverse,” “Run Forward,” “Run Reverse,” “Jog Forward” or “Jog Reverse.”
Bit 4 “AnalogCflct” - Analog input functions are in conflict.
Bit 5 “CntactrCflct” - Contactor input functions are in conflict.
Bit 6 “Encoder Cflc” - Indicates an encoder configuration conflict.
Bit 7 “Overvoltage” - There is an overvoltage on the armature circuit.
UTILITY
Bit 8 “Over Temp” - The motor has exceeded its temperature rating (as signaled by the thermistor connected to the drive
terminals 78 and 79).
Bit 9 “Aux Input” - An auxiliary input interlock is open or a voltage (15 - 30 V) or reference signal is missing for the digital
input set to 14 “Aux Fault”.
Bit 10 “Field Loss” - The field current is too low.
Bit 11 “Encoder Loss” - The drive is not receiving a speed feedback signal.
Bit 12 “PwrUp Start” - Indicates that the drive is starting or has automatically resumed running at commanded speed after
drive input power is restored.
Note: Refer to Chapter 4 Troubleshooting on page 4-1 for information.
Encoder Loss
Encoder Cflc
PwrUp Start
Overvoltage
CntactrCflct
AnalogCflct
BipolarCflct
DigInCflctC
DigInCflctB
DigInCflctA
Over Temp
Field Loss
Reserved
Reserved
Reserved
Aux Input
Default x x x x x 0 0 0 0 0 0 0 0 0 0 0
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
50 [UsrDsplyMult0] Default: 1
Numerator in the calculation for user-defined, drive speed display Min/Max: 1 / 1073741823
units.
A Note: This parameter is not used.
User Defined
51 [UsrDsplyDiv0] Default: 1
Denominator in the calculation for user-defined, drive speed display Min/Max: 1 / 1073741823
units.
A Note: This parameter is not used.
53 [UsrValMult1] Default: 1
Numerator in the calculation for scaling the user-defined, drive speed Min/Max: 1 / 32767
A display units.
Note: This parameter is not used.
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
54 [UsrValDiv1] Default: 1
Denominator in the calculation for scaling the user-defined, drive Min/Max: 1 / 32767
A speed display units.
Note: This parameter is not used.
503 [UserDefined0] Default: 0
504 [UserDefined1]
505 [UserDefined2] Min/Max: –32768/+32767
506 [UserDefined3]
507 [UserDefined4]
508 [UserDefined5]
509 [UserDefined6]
510 [UserDefined7]
511 [UserDefined8]
512 [UserDefined9]
513 [UserDefined10]
514 [UserDefined11]
515 [UserDefined12]
516 [UserDefined13]
517 [UserDefined14]
518 [UserDefined15]
General use signed 16 bit variables used for data exchange.
A Note: Pars 503–506 can be assigned to analog inputs. The values of
Pars 503, 504, and 507 - 509 can be assigned to an analog output.
User Defined
Related
Group
Parameter Name & Description
File
529 [UsrDefBitWrdA9]
UTILITY
530 [UsrDefBitWrdA10]
531 [UsrDefBitWrdA11]
532 [UsrDefBitWrdA12]
533 [UsrDefBitWrdA13]
534 [UsrDefBitWrdA14]
535 [UsrDefBitWrdA15]
Bit variables. The individual "User Defined" bits can be read or written
A to. It is possible to process a word with Par 519 [UsrDefBitWrdA] (see
example).
Note: You can read bits 0-7 of a digital input with Par 519
[UsrDefBitWrdA] and write all of the bits associated with
[UsrDefBitWrdA] to a digital output.
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
536 [UsrDefBitWrdB] Default: 0 537 -
A bitmap of Pars 537 [UsrDefBitWrdB0] through 552 Min/Max: 0 / 65535 552
A [UsrDefBitWrdB15]. With a parameter it is possible to read or write all
of the bits inside a word.
Example:
[UsrDefBitWrdB0] 0
[UsrDefBitWrdB1] 1 = 21 =2
[UsrDefBitWrdB2] 0
[UsrDefBitWrdB3] 0
[UsrDefBitWrdB4] 0
[UsrDefBitWrdB5] 1 = 25 = 32
[UsrDefBitWrdB6] 1 = 26 = 64
[UsrDefBitWrdB7] 0
[UsrDefBitWrdB8] 0
[UsrDefBitWrdB9] 0
[UsrDefBitWrdB10] 1 = 210 = 1024
[UsrDefBitWrdB11] 0
[UsrDefBitWrdB12] 1 = 212 = 4096
[UsrDefBitWrdB13] 0
[UsrDefBitWrdB14] 0
[UsrDefBitWrdB15] 0
User Defined
Communications File
Related
Group
No.
3= “DPI Port 3”
4= “DPI Port 4”
5= “DPI Port 5”
1321 [DPI Fdbk Select] Default: 0= “Speed”
Selects the feedback variable and DPI units displayed on the Options: 0= “Speed”
feedback line of the HIM. 1= “Current”
• 0 “Speed” = Speed feedback units are in RPM
• 1 “Current” = Current feedback units are in %
1343 [DPI Port Value] Default: Read Only 590
Unscaled value of the DPI reference selected in Par 590 [DPI Min/Max: –/+32767
Port Sel].
591 [Logic Mask]
Determines which ports can control the drive when Par 1377 [Write Mask Act], bit 15 is set to “1.” If the bit for a port is
set to “0,” the port will have no control functions except for stop. 0 = Control Masked, 1 = Control Permitted, x =
Reserved.
DPI Port 5
DPI Port 4
DPI Port 3
DPI Port 2
DPI Port 1
COMMUNICATIONS
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Digital In
Default x x x x x x x x x x 1 1 1 1 1 1
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
599 [Local Mask] See [Logic Mask]
Controls which adapters are allowed to take exclusive control
of drive logic commands (except stop). Exclusive “local”
control can only be taken while the drive is stopped.
600 [Stop Owner]
The adapters that are presently issuing a valid stop command. 0 = No Command, 1 = Issuing Command, x = Reserved.
DPI Port 5
DPI Port 4
DPI Port 3
DPI Port 2
DPI Port 1
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Digital In
Default x x x x x x x x x x 0 0 0 0 0 0
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Related
Group Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
610 [Data In A1] – Link A Word 1 Default: 0 (0 = “Disabled”)
611 [Data In A2] – Link A Word 2
Min/Max: 0 / 1408
Parameter number whose value will be written from a
communications device data table. The value will not be
updated until the drive is stopped.
Refer to your communications option manual for datalink
information.
612 [Data In B1] – Link B Word 1 See [Data In A1] – Link A Word 1.
613 [Data In B2] – Link B Word 2
614 [Data In C1] – Link C Word 1 See [Data In A1] – Link A Word 1.
615 [Data In C2] – Link C Word 2
616 [Data In D1] – Link D Word 1 See [Data In A1] – Link A Word 1.
Datalinks
624 [Data Out D1] – Link D Word 1 See [Data Out A1] – Link A Word 1.
625 [Data Out D2] – Link D Word 2
1319 [Data In Val Sel] Default: 610 1320
Selects the Datalink parameter register to display in Par 1320 Min/Max: 610 / 617
[Data In Sel Data].
1320 [Data In SelData] Default: Read Only 1319
Displays the value selected in Par 1319 [Data In Val Sel]. Min/Max: - / +231
591 [Logic Mask]
Determines which ports can control the drive when Par 1377 [Write Mask Act], bit 15 is set to “1.” If the bit for a port is
set to “0,” the port will have no control functions except for stop. 0 = Control Masked, 1 = Control Permitted, x =
Reserved.
DPI Port 5
DPI Port 4
DPI Port 3
DPI Port 2
DPI Port 1
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Digital In
Default x x x x x x x x x x 1 1 1 1 1 1
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Security
DPI Port 5
DPI Port 4
DPI Port 3
DPI Port 2
DPI Port 1
Advanced
Reserved
Digital In
Default 0 x x x x x x x x x 1 1 1 1 1 1
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
1377 [Write Mask Act] Read Only 1378
The status of write access for the DPI ports. When bit 15 is set, network
A security is controlling the write mask instead of Par 1378 [Write Mask Cfg]. 0 =
Read Only, 1 = Write Permitted, x = Reserved.
Aux Port 14
Aux Port 13
Aux Port 12
Aux Port 11
Aux Port 10
Aux Port 9
Aux Port 8
Aux Port 7
DPI Port 5
DPI Port 4
DPI Port 3
DPI Port 2
DPI Port 1
Advanced
Reserved
Digital In
Default 0 x x x x x x x x x 1 1 1 1 1 0
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Aux Port 14
Aux Port 13
Aux Port 12
Aux Port 11
Aux Port 10
Aux Port 9
Aux Port 8
Aux Port 7
DPI Port 5
DPI Port 4
DPI Port 3
DPI Port 2
DPI Port 1
Reserved
Reserved
Digital In
Default 0 x x x x x x x x x 1 1 1 1 1 0
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
DPI Port 5
DPI Port 4
DPI Port 3
DPI Port 2
DPI Port 1
Reserved
Security
Host
Default 0 x x x x x x x x x 1 1 1 1 1 1
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Related
Group
No.
0= “Off” (No signal) 9= “Neg Cur Lim” (Par 9) 18 = “PI CentralV3” (Par 778)
1= “Speed Ref A” (Par 44) 10 = “Jog Ref” (Par 266) 19 = “PID Feedback” (Par 763)
2= “Speed Ref B” (Par 48) 11 = “Adaptive Ref” (Par 183) 20 = “Fld Cur Max” (Par 467)
3= “Trim Ramp” (Par 42) 12 = “UserDefined0” (Par 503) 21 = “OutVoltLevel” (Par 233)
4= “Trim Speed” (Par 43) 13 = “UserDefined1” (Par 504) 22 = “Speed Ratio” (Par 1017)
5= “Torque Ref” (Par 39) 14 = “UserDefined2” (Par 505) 23 = “Tension Red” (Par 1179)
6= “Trim Torque” (Par 40) 15 = “UserDefined3” (Par 506) 24 = “Tension Ref” (Par 1180)
7= “TB Man Ref” (Par 267) 16 = “Load Comp” (Par 698) 25 = “Diam Preset3” (Par 1167)
8= “Pos Cur Lim” (Par 8) 17 = ‘PID Setpt 0” (Par 760)
are factory set for voltage signals. Refer to DIP Switch and
Analog Inputs
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
74 [Anlg In1 Offset] Default: 0
79 [Anlg In2 Offset]
84 [Anlg In3 Offset] Min/Max: –32768/+32767
Offset value for the analog inputs. If the input has an offset or if
A the variable assigned to the input already has a value although
there is no input signal present, this can be compensated for via
the value in this parameter.
259 [Anlg In1 Tune] Default: 0= “Ready”
260 [Anlg In2 Tune]
261 [Anlg In3 Tune] Options: 0= “Ready”
1= “Tune”
Automatic fine tuning of the analog inputs. If this command is
A given, parameter [Ainx Tune Scale] is automatically selected so
that the input signal present, normally full scale, corresponds to
the maximum variable value, such as the value of Par 45 [Max
Ref Speed]. Two conditions are necessary for automatic fine
tuning:
• An input voltage greater than 1V or an input current greater
than 2 mA.
• Positive polarity. The value found is automatically set for the
opposite direction for four quadrant drives.
Note: The automatically calculated value can, if necessary, be
modified manually via parameter [Ainx Tune Scale]. When using
analog input tuning, Pars [Analog Inx Scale] are normally set to
1.0.
295 [Anlg In1 Target] Default: 0= “Assigned”
296 [Anlg In2 Target]
297 [Anlg In3 Target] Options: 0= “Assigned”
1= “Not Assigned”
Enables sampling for the analog inputs.
INPUT / OUTPUT
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
1404 [Analog In1 Value] Default: Read Only 71
Value of the signal at analog input 1. Units based on the value Min/Max: -/+20.00
set in Par 71 [Anlg In1 Config]. Units: V or mA
Analog Inputs
Selects the source of the value that drives the analog output.
*This parameter is used to configure the analog output on the
I/O Expansion circuit board.
Options:
Analog Outputs
0= “Off” (Not used) 12 = “Motor Speed” (Par 121)(1) 24 = “Field Ref” (Par 500)
1= “Spd Ref Out” (Par 385) 13 = “Motor Curr” (Par 199)(2) 25 = “PID Output” (Par 774)
2= “Trim Ramp” (Par 42) 14 = “Motor Volts” (Par 233) 26 = “Out Volt Lvl” (Par 921)
3= “Ramp In” (Par 110) 15 = “Analog In 1” (Par 70) 27 = “Fld Cur Max” (Par 467)
4= “Ramp Out” (Par 113) 16 = “Analog In 2” (Par 75) 28 = “Filtered Spd” (Par 924)(1)
5= “Spd Draw Out” (Par 1018) 17 = “Analog In 3” (Par 80) 29 = “Filtered Cur” (Par 928)(2)
6= “Trim Speed” (Par 43) 18 = “Fld Current” (Par 234) 30 = “Output Power” (Par 1052)(3)
7= “Spd Reg In” (Par 118) 19 = “UserDefined0” (Par 503) 31 = “Roll Diam” (Par 1154)(4)
8= “Spd Reg Out” (Par 236) 20 = “UserDefined1” (Par 504) 32 = “Tension Ref” (Par 1180)
9= “Torque Ref” (Par 39) 21 = “UserDefined4” (Par 507) 33 = “Torque Curr” (Par 1193)(2)
10 = “Trim Torque” (Par 40) 22 = “UserDefined5” (Par 508) 34 = “Winder Ref” (Par 1217)(1)
11 = “Torq Reg In” (Par 41) 23 = “UserDefined6” (Par 509) 35 = “Active Comp” (Par 1213)(2)
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
133 [Digital In1 Sel] Default: 2= “Stop/CF”
134 [Digital In2 Sel] Default: 3= “Start”
135 [Digital In3 Sel] Default: 11 = “Jog”
136 [Digital In4 Sel] Default: 1= “Enable”(1)
137 [Digital In5 Sel] Default: 17 = “Speed Sel 1”
138 [Digital In6 Sel] Default: 18 = “Speed Sel 2”
139 [Digital In7 Sel] Default: 19 = “Speed Sel 3”
140 [Digital In8 Sel] Default: 31 = “Contactor”
141 [Digital In9 Sel]* Default: 0= “Not Used”
142 [Digital In10 Sel]* Default: 0= “Not Used”
143 [Digital In11 Sel]* Default: 0= “Not Used”
144 [Digital In12 Sel]* Default: 0= “Not Used”
Selects the function driven by the digital input.
Refer to Option Definitions for [Digital Inx Sel] on page 3-66.
*These parameters are used to configure the digital inputs on
the I/O Expansion circuit board.
Note: Option 35 was changed from “Fld Weaken En” to “Force
MinFld” and option 64 “Invert Flt” was added with firmware
version 2.001.
Options:
INPUT / OUTPUT
Digital Inputs
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
Option Definitions for [Digital Inx Sel]
Note: When assigning digital inputs to certain options that are associated with parameters, those parameter values may be overwritten by the state
of the digital input.
Option Description
Enable(1)(2) Asserting the input causes the motor to coast-to-stop without generating a fault.
Stop/CF(2) Stops the drive if running or jogging or clears a fault if the drive is already stopped.
Start(2) Issues a Start command, removal does not Stop the drive (3-wire control).
Fwd/Reverse(2) Selects the operating direction of the drive.
Run(2) Issues a Start command, removal causes the drive to Stop (2-wire control).
Run Forward(2) Issues a Run command in the Forward direction.
Run Reverse(2) Issues a Run command in the Reverse direction.
Run Level(2) Level sensitive Run command (no off-to-on transition required).
RunFwd Level(2) Run Level command in the Forward direction.
RunRev Level(2) Run Level command in the Reverse direction.
Jog(2) Starts the drive and runs at the speed in Par 266 [Jog Speed], removal causes the drive to Stop.
Jog Forward(2) Issues a Jog command in the Forward direction.
Jog Reverse(2) Issues a Jog command in the Reverse direction.
Aux Fault Asserting causes an Auxiliary Input fault (F2).
Clear Faults Issues a Clear Faults command.
Auto/Manual Selects between Automatic and Manual speed reference values.
Speed Sel 1 - 3 Selects one of eight speed references. Bit enumerations: 000 = Par 44 [Speed Ref A], 001 = Par 48 [Speed Ref B], 010 = Par 155 [Preset Speed 2], 011
= Par 156 [Preset Speed 3], 100 = Par 157 [Preset Speed 4], 101 = Par 158 [Preset Speed 5], 110 = Par 159 [Preset Speed 6], 111 = Par 160 [Preset
Speed 7]
PI Enable Enables/disables the PI block of the PID regulator (Par 769 [Enable PI]).
PI Hold Enables/disables a hold on the PI output.
PI Reset Asserting causes a reset of the PI output.
PI Invert Asserting causes an inversion of the PI output.
Local Enables exclusive drive control via the I/O Terminal Block only.
Acc2 & Dec2 Switches between the Accel/Decel 1 and Accel/Decel 2 ramp rates.
INPUT / OUTPUT
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
564 [Dig In Status] Read Only
Status of the digital inputs.
Digital In12
Digital In11
Digital In10
Digital In9
Digital In8
Digital In7
Digital In6
Digital In5
Digital In4
Digital In3
Digital In2
Digital In1
Reserved
Reserved
Reserved
Reserved
Default x x x x 0 0 0 0 0 0 0 0 0 0 0 0
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
1278 [Inversion In 3]
1= “Enabled”
Digital Inputs
1279 [Inversion In 4]
1280 [Inversion In 5]
1281 [Inversion In 6]
1282 [Inversion In 7]
1283 [Inversion In 8]
1387 [Inversion In 9]
1388 [Inversion In 10]
1389 [Inversion In 11]
1390 [Inversion In 12]
inverts the digital input signal.
A
1391 [ContactorControl] Default: 1= “AC Cntctr”
Selects the type of contactor to be controlled by the drive. Either
Options: 0= “None”
style of contactor (AC or DC) can be used, with or without 1= “AC Cntctr”
dynamic braking (DB) contactor. 2= “AC Cntctr+DB”
A • “AC Cntctr” indicates an AC contactor is used 3= “DC Cntctr”
• “AC Cntctr+DB” indicates that an AC contactor and dynamic 4= “DC Cntctr+DB”
brake resistor is used
• “DC Cntctr” indicates a DC contactor is used
• “DC Cntctr+DB” indicates that a DC contactor and dynamic
brake resistor is used
The type of control selected determines how many I/O points
will be required for contactor control and status.
• “AC Cntctr” or “DC Cntctr” = 1 (relay) digital output, 1 digital
input is used
• “AC Cntctr+DB” or “DC Cntctr+DB” = 2 (relay) digital outputs,
1 digital input is used
Note: Options 1 and 2 changed from “Contactor” and
“Contactor+DB” to “AC Cntctr” and AC Cntctr+DB”, respectively,
and options 3 and 4 added with firmware version 2.001.
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
145 [Digital Out1 Sel] Default: 5= “Ready”
146 [Digital Out2 Sel] Default: 9= “Fault”
147 [Digital Out3 Sel] Default: 2= “Spd Thresh”
148 [Digital Out4 Sel] Default: 4= “CurrentLimit”
149 [Digital Out5 Sel]* Default: 26 = “Alarm”
150 [Digital Out6 Sel]* Default: 0= “Not Used”
151 [Digital Out7 Sel]* Default: 0= “Not Used”
152 [Digital Out8 Sel]* Default: 0= “Not Used”
Selects the source of the value that drives the digital output.
Refer to “Option Definitions” on Option Definitions for [Digital
Outx Sel], [Relay Out 1 Sel] and [Relay Out 2 Sel] on page 3-69.
INPUT / OUTPUT
Digital Outputs
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
Option Definitions for [Digital Outx Sel], [Relay Out 1 Sel] and [Relay Out 2 Sel]
Option Description
Spd Zero Thr “0” indicates that the drive is operating below the value set in Par 107 [Speed Zero Level] , “1”
indicates that the drive is operating above Par 107 [Speed Zero Level].
Spd Thresh “0” indicates that the drive is operating above the value set in Par 101 [Speed Thresh Pos], “1”
indicates that the drive is operating below Par 101 [Speed Thresh Pos].
At Speed “0” indicates that the actual speed is within the range specified in Par 104 [At Speed Error], “1”
indicates that the actual speed is outside the range specified in Par 104 [At Speed Error].
CurrentLimit “0” indicates that the drive is not limiting output current, “1” indicates that the drive is limiting the
output current.
Ready “1” indicates that the drive is powered, Enabled and no Start Inhibits exist. The state of the assigned
digital output matches the state of bit 2 “Ready” of Par 381 [Drive Status 1].
Ramp Pos “1” indicates that the actual speed of the drive is going positive. Follows the state of Par 346 [Torque
Positive]. Not asserted until after the amount of time in Par 20 [Ramp Delay] has elapsed.
Ramp Neg “1” indicates that the actual speed of the drive is going negative. Follows the state of Par 347 [Torque
Negative]. Not asserted until after the amount of time in Par 20 [Ramp Delay] has elapsed.
Spd Limited “1” indicates that the speed is being limited to the value of Par 3 [Max Speed Fwd], “0” indicates that
the speed is not being limited.
Fault “0” indicates that a drive fault has occurred. Refer to Par 57 [Fault Code].
Power Loss “0” indicates that the drive has detected a loss of the internal power supply.
UserDefinedA Indicates the status of Par 519 [UsrDefBitWrdA] (digital output 1 uses bit 0, digital output 2 uses bit 1,
etc.). Par 1392 [Relay Out 1 Sel] uses bit 14 (only). Par 629 [Relay Out 2 Sel] uses bit 15 (only).
UserDefinedB Indicates the status of Par 536 [UsrDefBitWrdB] (digital output 1 uses bit 0, digital output 2 uses bit 1,
etc.). Par 1392 [Relay Out 1 Sel] uses bit 14 (only). Par 629 [Relay Out 2 Sel] uses bit 15 (only).
INPUT / OUTPUT
Digital Outputs
Stop Control Energized (“1”) at run and de-energized (“0”) based on the value of Par 627 [Spd 0 Trip Delay].
Field Loss “0” indicates the loss of the field voltage/current while the drive is running.
Spd Fbk Loss “0” indicates the loss of Speed Feedback/Encoder due to an excessive calculated error, as
determined by the drive firmware.
Encoder Err “0” indicates a loss of the DC tachometer or encoder. Matches the state of Par 651 [Encoder State].
Diam Calc Energized (“1”) when Par 800 [Diameter Calc St] = 1 and de-energized (“0”) when [Diameter Calc St]
= 0.
Input1 Cmp “1” indicates that the value of analog input 1 is inside the comparison window,“0” indicates that the
value of analog input 1 is outside the comparison window (Par 1045 [Anlg In1 Cmp Eq]).
Diam Reached Energized (“1”) when the value of Par 1158 [Diam Threshold] has been exceeded.
Speed Match Energized (“1”) when the value of Par 1203 [Spd Match Compl] = “1” (launching ramp completed).
Accelerating “1” indicates that the drive is actively accelerating. The state of the assigned digital output matches
the state of bit 4 “Accelerating” of Par 381 [Drive Status 1] and the state of Par 1188 [Accel Status].
Decelerating When set to “1” the drive is actively decelerating. The state of the assigned digital output matches the
state of bit 5 “Decelerating” of Par 381 [Drive Status 1] and the state of Par 1189 [Decel Status].
Brake Cmd Energized (“1”) at run (opens the brake) after the value in Par 1263 [Opening Delay] has been
exceeded. De-energized (“0”) at stop (closes the brake) after the drive speed goes below the value of
Par 1262 [Closing Speed].
ContactorDB “1” issues the close command to the main contactor and dynamic brake contactor.
Contactor “1” issues the close command to the main contactor.
Alarm “0” indicates that a drive alarm has occurred. Refer to Par 1380 [Drive Alarm 1].
Running “1” indicates that the drive is active in Run mode. The state of the assigned digital output matches the
state of bit 2 “Running” of Par 381 [Drive Status 1].
Jogging “1” indicates that the drive is active in Jog mode. The state of the assigned digital output matches the
state of bit 3 “Jogging” of Par 381 [Drive Status 1].
Active “1” indicates that the drive is active in Run or Jog mode. The state of the assigned digital output
matches the state of bit 1 “Active” of Par 381 [Drive Status 1].
Related
Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
581 [Dig Out Status] Read Only
Status of the standard digital outputs and relay outputs on the drive and on the
optional I/O Expansion circuit board (if present).
Digital Out8
Digital Out7
Digital Out6
Digital Out5
Digital Out4
Digital Out3
Digital Out2
Digital Out1
Relay Out2
Relay Out1
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Default 0 0 x x x x x x 0 0 0 0 0 0 0 0
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Digital Outputs
A
1275 [Inversion Relay2] Default: 0= “Disabled”
Inverts the signal for Relay Output 2. Options: 0= “Disabled”
1= “Enabled”
A
1392 [Relay Out 1 Sel] Default: 25 = “Contactor”
Selects the source of the value that drives the N.O. relay
between the terminals 35 and 36.
Refer to “Option Definitions” on page 3-69.
Options:
Related
Digital Outputs Group
Parameter Name & Description
File
No.
See page 3-2 for symbol descriptions Values
1393 [Inversion Relay1] Default: 0= “Disabled”
Inverts the signal for Relay Output 1. Options: 0= “Disabled”
1= “Enabled”
A
1323 [DPI P1 Select] Default: 0= “Off”
Selects the destination of the reference value from DPI Port 1. Options: 0= ”Off”
1= “Speed Ref A”
2= “Speed Ref B”
3= “Trim Ramp”
INPUT / OUTPUT
4= “Trim Speed”
5= “Torque Ref”
6= “Trim Torque”
7= “Pos Cur Lim”
8= “Neg Cur Lim”
DPI Inputs
No. Parameter Name Group Page No. Parameter Name Group Page
152 Digital Out8 Sel Digital Outputs 3-68 374 Drv Fld Brdg Cur Motor Data 3-14
154 Preset Speed 1 Discrete Speeds 3-23 378 Trim Ramp Pct Speed Reference 3-24
155 Preset Speed 2 Discrete Speeds 3-23 379 Trim Speed Pct Speed Reference 3-24
156 Preset Speed 3 Discrete Speeds 3-23 381 Drive Status 1 Diagnostics 3-48
157 Preset Speed 4 Discrete Speeds 3-23 382 Drive Status 2 Diagnostics 3-48
158 Preset Speed 5 Discrete Speeds 3-23 384 Spd Ref Out Pct Speed Meters 3-11
159 Preset Speed 6 Discrete Speeds 3-23 385 Speed Ref Out Speed Meters 3-11
160 Preset Speed 7 Discrete Speeds 3-23 388 Flying Start En Speed Regulator 3-27
162 Max Feedback Spd Motor Data 3-14 393 Speed Threshold Diagnostics 3-49
169 Encoder PPR Speed Feedback 3-19 394 At Speed Diagnostics 3-49
175 Rated Motor Volt Motor Data 3-14 395 At Zero Speed Diagnostics 3-49
179 Nom Mtr Arm Amps Motor Data 3-14 396 MOP Inc Active Diagnostics 3-49
181 Adaptive Spd En Adaptv Regulator 3-32 397 MOP Dec Active Diagnostics 3-49
182 Adaptive Reg Typ Adaptv Regulator 3-32 400 Spd Select 0 Diagnostics 3-49
183 Adaptive Ref Adaptv Regulator 3-32 401 Spd Select 1 Diagnostics 3-50
184 Adaptive Spd 1 Adaptv Regulator 3-32 402 Spd Select 2 Diagnostics 3-50
185 Adaptive Spd 2 Adaptv Regulator 3-32 403 Ramp Select 0 Diagnostics 3-50
186 Adaptive Joint 1 Adaptv Regulator 3-33 404 Ramp Select 1 Diagnostics 3-50
187 Adaptive Joint 2 Adaptv Regulator 3-33 414 Fdbk Device Type Speed Feedback 3-19
188 Adaptive P Gain1 Adaptv Regulator 3-33 418 Real FF PID PID Control 3-36
189 Adaptive I Gain1 Adaptv Regulator 3-33 420 Encoder Speed Speed Meters 3-11
190 Adaptive P Gain2 Adaptv Regulator 3-33 421 PD Output PID PD Control 3-36
191 Adaptive I Gain2 Adaptv Regulator 3-33 444 Spd Fdbk Filter Speed Regulator 3-27
192 Adaptive P Gain3 Adaptv Regulator 3-33 445 Spd Up Gain Pct Speed Regulator 3-27
193 Adaptive I Gain3 Adaptv Regulator 3-33 446 Speed Up Base Speed Regulator 3-27
199 Arm Current Pct Current Meters 3-12 447 Speed Up Filter Speed Regulator 3-27
200 Arm Current Current Meters 3-12 452 CurrReg Autotune Autotune 3-20
201 Drive Type Sel Motor Data 3-14 453 Arm Resistance Autotune 3-20
203 OverVolt Flt Cfg Alarms 3-53 454 Arm Inductance Autotune 3-20
209 Save HIM Ref HIM Ref Config 3-46 455 Spd Fdbk Error Speed Feedback 3-19
210 Man Ref Preload HIM Ref Config 3-46 456 Fld Weaken Ratio Field Config 3-15
211 Param Access Lvl Drive Memory 3-46 457 Spd Fdbk Control Speed Feedback 3-19
233 Output Voltage Drive Data 3-13 458 SpdReg FB Bypass Speed Feedback 3-19
234 Fld Current Pct Torque Attribute 3-12 459 SpdReg Kp Bypass Speed Regulator 3-27
235 Elapsed Lifetime Drive Data 3-13 460 SpdReg Ki Bypass Speed Regulator 3-27
236 Spd Reg Out Pct Speed Regulator 3-11 465 Drive Size Drive Data 3-13
242 Speed Reg En Speed Regulator 3-26 466 AC Line Voltage Drive Data 3-13
245 Speed Ramp En Ramp Rates 3-30 467 Max Fld Curr Pct Field Config 3-15
249 Save MOP Ref Reference Config 3-46 468 Min Fld Curr Pct Field Config 3-15
258 Reset Defaults Drive Memory 3-46 469 Field Mode Sel Field Config 3-15
259 Anlg In1 Tune Analog Inputs 3-63 473 FldLoss Flt Cfg Alarms 3-54
260 Anlg In2 Tune Analog Inputs 3-63 478 Spd Loss Flt Cfg Alarms 3-54
261 Anlg In3 Tune Analog Inputs 3-63 481 UnderVolt Thresh Alarms 3-54
263 Clear Fault Que Faults 3-52 484 Scale1 Input Scale Blocks 3-39
266 Jog Speed Discrete Speeds 3-23 485 Scale1 Output Scale Blocks 3-39
267 TB Manual Ref Discrete Speeds 3-24 486 Scale1 Mul Scale Blocks 3-39
280 Nom Mtr Fld Amps Motor Data 3-14 487 Scale1 Div Scale Blocks 3-39
295 Anlg In1 Target Analog Inputs 3-63 488 Scale1 In Max Scale Blocks 3-39
296 Anlg In2 Target Analog Inputs 3-63 489 Scale1 In Min Scale Blocks 3-39
297 Anlg In3 Target Analog Inputs 3-63 490 Scale1 In Off Scale Blocks 3-40
300 Drive Type Drive Data 3-13 491 Scale1 Out Off Scale Blocks 3-40
331 Software Version Configuration 3-13 492 Scale1 In Abs Scale Blocks 3-40
342 Torque Reduction Torque Attribute 3-17 493 Arm Volt Kp Speed Regulator 3-27
344 Zero Ramp Output Ramp Rates 3-30 494 Arm Volt Ki Speed Regulator 3-27
345 Zero Ramp Input Ramp Rates 3-30 495 Arm Volt Kp Base Speed Regulator 3-27
346 Torque Positive Diagnostics 3-47 496 Arm Volt Ki Base Speed Regulator 3-27
347 Torque Negative Diagnostics 3-47 497 Field Reg Enable Field Config 3-15
348 Lock Speed Integ Speed Regulator 3-26 498 Force Min Field Field Config 3-15
349 CurrLimit Active Diagnostics 3-47 499 Field Economy En Field Config 3-16
351 Field Current Current Meters 3-12 500 Field Ref Pct Current Meters 3-12
353 Zero Torque Torque Attribute 3-17 503 UserDefined0 User Defined 3-55
354 Aux Inp Flt Cfg Alarms 3-53 504 UserDefined1 User Defined 3-55
365 OverTemp Flt Cfg Alarms 3-53 505 UserDefined2 User Defined 3-55
372 Spd Limit Active Diagnostics 3-47 506 UserDefined3 User Defined 3-55
373 Freeze Ramp Ramp Rates 3-30 507 UserDefined4 User Defined 3-55
No. Parameter Name Group Page No. Parameter Name Group Page
508 UserDefined5 User Defined 3-55 573 Dig In Term 9 Digital Inputs 3-67
509 UserDefined6 User Defined 3-55 574 Dig In Term 10 Digital Inputs 3-67
510 UserDefined7 User Defined 3-55 575 Dig In Term 11 Digital Inputs 3-67
511 UserDefined8 User Defined 3-55 576 Dig In Term 12 Digital Inputs 3-67
512 UserDefined9 User Defined 3-55 581 Dig Out Status Digital Outputs 3-70
513 UserDefined10 User Defined 3-55 584 OverCurrent Thr Alarms 3-54
514 UserDefined11 User Defined 3-55 587 I Reg Error Autotune 3-20
515 UserDefined12 User Defined 3-55 588 AC Line Freq Drive Data 3-13
516 UserDefined13 User Defined 3-55 589 DPI Baud Rate Comm Control 3-58
517 UserDefined14 User Defined 3-55 590 DPI Port Sel Comm Control 3-58
518 UserDefined15 User Defined 3-55 591 Logic Mask Masks & Owners 3-58
Security 3-60
519 UsrDefBitWrdA User Defined 3-55
592 Start Mask Masks & Owners 3-58
520 UsrDefBitWrdA0 User Defined 3-56
593 Jog Mask Masks & Owners 3-58
521 UsrDefBitWrdA1 User Defined 3-56
594 Direction Mask Masks & Owners 3-58
522 UsrDefBitWrdA2 User Defined 3-56
595 Reference Mask Masks & Owners 3-58
523 UsrDefBitWrdA3 User Defined 3-56
596 Accel Mask Masks & Owners 3-58
524 UsrDefBitWrdA4 User Defined 3-56
597 Fault Clr Mask Masks & Owners 3-58
525 UsrDefBitWrdA5 User Defined 3-56
598 MOP Mask Masks & Owners 3-58
526 UsrDefBitWrdA6 User Defined 3-56
599 Local Mask Masks & Owners 3-59
527 UsrDefBitWrdA7 User Defined 3-56
600 Stop Owner Masks & Owners 3-59
528 UsrDefBitWrdA8 User Defined 3-56
601 Start Owner Masks & Owners 3-59
529 UsrDefBitWrdA9 User Defined 3-56
602 Jog Owner Masks & Owners 3-59
530 UsrDefBitWrdA10 User Defined 3-56
603 Direction Owner Masks & Owners 3-59
531 UsrDefBitWrdA11 User Defined 3-56
604 Reference Owner Masks & Owners 3-59
532 UsrDefBitWrdA12 User Defined 3-56
605 Accel Owner Masks & Owners 3-59
533 UsrDefBitWrdA13 User Defined 3-56
606 Fault Clr Owner Masks & Owners 3-59
534 UsrDefBitWrdA14 User Defined 3-56
607 MOP Owner Masks & Owners 3-59
535 UsrDefBitWrdA15 User Defined 3-56
608 Local Owner Masks & Owners 3-59
536 UsrDefBitWrdB User Defined 3-57
609 Decel Owner Masks & Owners 3-59
537 UsrDefBitWrdB0 User Defined 3-57
610 Data In A1 Datalinks 3-60
538 UsrDefBitWrdB1 User Defined 3-57
611 Data In A2 Datalinks 3-60
539 UsrDefBitWrdB2 User Defined 3-57
612 Data In B1 Datalinks 3-60
540 UsrDefBitWrdB3 User Defined 3-57
613 Data In B2 Datalinks 3-60
541 UsrDefBitWrdB4 User Defined 3-57
614 Data In C1 Datalinks 3-60
542 UsrDefBitWrdB5 User Defined 3-57
615 Data In C2 Datalinks 3-60
543 UsrDefBitWrdB6 User Defined 3-57
616 Data In D1 Datalinks 3-60
544 UsrDefBitWrdB7 User Defined 3-57
617 Data In D2 Datalinks 3-60
545 UsrDefBitWrdB8 User Defined 3-57
618 Data Out A1 Datalinks 3-60
546 UsrDefBitWrdB9 User Defined 3-57
619 Data Out A2 Datalinks 3-60
547 UsrDefBitWrdB10 User Defined 3-57
620 Data Out B1 Datalinks 3-60
548 UsrDefBitWrdB11 User Defined 3-57
621 Data Out B2 Datalinks 3-60
549 UsrDefBitWrdB12 User Defined 3-57
622 Data Out C1 Datalinks 3-60
550 UsrDefBitWrdB13 User Defined 3-57
623 Data Out C2 Datalinks 3-60
551 UsrDefBitWrdB14 User Defined 3-57
624 Data Out D1 Datalinks 3-60
552 UsrDefBitWrdB15 User Defined 3-57
553 Scale2 Input Scale Blocks 3-39 625 Data Out D2 Datalinks 3-60
627 Spd 0 Trip Delay Stop Modes 3-31
554 Scale2 Output Scale Blocks 3-39
629 Relay Out 2 Sel Digital Outputs 3-70
555 Scale2 Mul Scale Blocks 3-39
631 Decel Mask Masks & Owners 3-59
556 Scale2 Div Scale Blocks 3-39
651 Encoder State Diagnostics 3-50
557 Scale2 In Max Scale Blocks 3-39
652 Encoder Err Chk Speed Feedback 3-20
558 Scale2 In Min Scale Blocks 3-39
660 Accel Time 1 Ramp Rates 3-30
559 Scale2 In Off Scale Blocks 3-40
662 Decel Time 1 Ramp Rates 3-30
560 Scale2 Out Off Scale Blocks 3-40
665 S Curve Accel 1 Ramp Rates 3-30
561 Scale2 In Abs Scale Blocks 3-40
666 S Curve Decel 1 Ramp Rates 3-30
562 Anlg Tach Gain Speed Feedback 3-19
667 S Curve Accel 2 Ramp Rates 3-30
563 Anlg Tach Zero Speed Feedback 3-19
668 S Curve Decel 2 Ramp Rates 3-30
564 Dig In Status Digital Inputs 3-67
695 PI Steady Thr PI Control 3-34
565 Dig In Term 1 Digital Inputs 3-67
696 Droop Percent Load Limits 3-31
566 Dig In Term 2 Digital Inputs 3-67
697 Droop Filter Load Limits 3-31
567 Dig In Term 3 Digital Inputs 3-67
698 Load Comp Load Limits 3-31
568 Dig In Term 4 Digital Inputs 3-67
699 Enable Droop Load Limits 3-31
569 Dig In Term 5 Digital Inputs 3-67
700 Droop Limit Load Limits 3-31
570 Dig In Term 6 Digital Inputs 3-67
715 Torq Limit Type Load Limits 3-31
571 Dig In Term 7 Digital Inputs 3-67
731 PID Steady Delay PID Control 3-36
572 Dig In Term 8 Digital Inputs 3-67
No. Parameter Name Group Page No. Parameter Name Group Page
734 PI Init Intgl Gn PID Control 3-36 1013 Torque Const Autotune 3-20
750 TrqTpr_Enable Torque Attribute 3-18 1014 Inertia Autotune 3-21
751 TrqTpr_Lim0 Torque Attribute 3-18 1015 Friction Autotune 3-21
752 TrqTpr_Lim1 Torque Attribute 3-18 1016 SpdFuncSelect Speed Regulator 3-28
753 TrqTpr_Lim2 Torque Attribute 3-18 1017 Speed Ratio Speed References 3-24
754 TrqTpr_Lim3 Torque Attribute 3-18 1018 Speed Draw Out Speed Meters 3-12
755 TrqTpr_Lim4 Torque Attribute 3-18 1019 Spd Draw Out Pct Speed Meters 3-12
756 TrqTpr_Spd Torque Attribute 3-18 1021 Encoder Out Sel Speed Feedback 3-20
757 PID Clamp PID Control 3-37 1027 Spd Reg Autotune Autotune 3-21
758 Feed Fwd PID PID Control 3-37 1029 Speed Tune Dir Autotune 3-21
759 PID Error PID Control 3-37 1030 Spd Tune Inertia Autotune 3-21
760 PID Setpoint 0 PID Control 3-37 1031 SpdTune Friction Autotune 3-21
761 PID Setpoint 1 PID Control 3-37 1032 Speed Tune Kp Autotune 3-21
762 PID Setpoint Sel PID Control 3-37 1033 Speed Tune Ki Autotune 3-21
763 PID Feedback PID Control 3-37 1042 Anlg In1 Cmp Analog Inputs 3-63
764 PI Integral Gain PI Control 3-34 1043 Anlg In1 Cmp Err Analog Inputs 3-63
765 PI Prop Gain PID PI Control 3-34 1044 Anlg In1 Cmp Dly Analog Inputs 3-63
766 PD Deriv Gain 1 PD Control 3-36 1045 Anlg In1 Cmp Eq Analog Inputs 3-63
767 PD Deriv Filter PD Control 3-36 1046 PID Accel Time PID Control 3-38
768 PD Prop Gain 1 PD Control 3-36 1047 PID Decel Time PID Control 3-38
769 Enable PI PI Control 3-34 1048 Autotune Cur Lim Auto Tune 3-21
770 Enable PD PD Control 3-36 1052 Output Power Drive Data 3-13
771 PI Output PI Control 3-34 1153 Max Diameter Diameter Calc 3-41
772 PID Output Sign PID Control 3-37 1154 Roll Diameter Diameter Calc 3-41
773 PID Output Scale PID Control 3-37 1155 Line Spd Thresh Diameter Calc 3-41
774 PID Output PID Control 3-37 1156 Line Spd Gain Diameter Calc 3-41
776 PI Central v1 PI Control 3-34 1157 Diameter Reset Diameter Calc 3-41
777 PI Central v2 PI Control 3-34 1158 Diam Threshold Diameter Calc 3-41
778 PI Central v3 PI Control 3-34 1159 Diameter Reached Diameter Calc 3-41
779 PI Central v sel PI Control 3-35 1160 Line Speed Pct Diameter Calc 3-41
780 PI Central vs0 PI Control 3-35 1161 Diam Calc Dis Diameter Calc 3-41
781 PI Central vs1 PI Control 3-35 1162 Diameter Filter Diameter Calc 3-41
782 PID Target PID Control 3-38 1163 Base Omega Diameter Calc 3-41
783 PI integr freeze PI Control 3-35 1164 Diam Preset 0 Diameter Calc 3-41
784 PI Upper Limit PI Control 3-35 1165 Diam Preset 1 Diameter Calc 3-41
785 PI Lower Limit PI Control 3-35 1166 Diam Preset 2 Diameter Calc 3-42
786 PID Source PID Control 3-38 1167 Diam Preset 3 Diameter Calc 3-42
787 PID Source Gain PID Control 3-38 1168 Diam Preset Sel Diameter Calc 3-42
788 PD Prop Gain 2 PD Control 3-36 1171 Variable J Comp Winder Functions 3-42
789 PD Deriv Gain 2 PD Control 3-36 1172 Constant J Comp Winder Functions 3-42
790 PD Prop Gain 3 PD Control 3-36 1173 Materl Width Pct Winder Functions 3-42
791 PD Deriv Gain 3 PD Control 3-36 1174 Static Friction Winder Functions 3-42
792 Anlg In 1 Filter Analog Inputs 3-63 1175 Dynamic Friction Winder Functions 3-42
793 PI Init Prop Gn PI Control 3-35 1176 Taper Enable Winder Functions 3-43
794 Diameter Calc Diameter Calc 3-40 1177 Initial Diameter Winder Functions 3-43
795 DncrPosSpd Diameter Calc 3-40 1178 Final Diameter Winder Functions 3-43
796 Max Deviation Diameter Calc 3-40 1179 Tension Reduct Winder Functions 3-43
797 Gear Box Ratio Diameter Calc 3-40 1180 Tension Ref Winder Functions 3-43
798 Dancer Constant Diameter Calc 3-40 1181 Tension Scale Winder Functions 3-43
799 Minimum Diameter Diameter Calc 3-40 1182 Time AccDec Min Winder Functions 3-43
800 Diameter Calc St Diameter Calc 3-40 1183 Int Acc Calc En Winder Functions 3-43
911 Z Channel Enable Speed Feedback 3-20 1184 Line Accel Pct Winder Functions 3-43
912 Z Capture Pos En Speed Feedback 3-20 1185 Line Decel Pct Winder Functions 3-43
913 Z Captured Pos Speed Feedback 3-20 1186 Line FastStp Pct Winder Functions 3-43
916 Fld Const 40 Pct Field Config 3-16 1187 Winder Type Winder Functions 3-43
917 Fld Const 70 Pct Field Config 3-16 1188 Accel Status Diagnostics 3-50
918 Fld Const 90 Pct Field Config 3-16 1189 Decel Status Diagnostics 3-50
919 Set Fld Curve Field Config 3-16 1190 Fast Stop Status Diagnostics 3-50
920 Reset Fld Curve Field Config 3-16 1191 InertiaCompAct Speed Regulator 3-28
921 Out Volt Level Field Config 3-16 1192 InertiaCompVar Speed Regulator 3-28
923 Act Spd Filter Speed Feedback 3-20 1193 Torq Current Pct Winder Functions 3-43
924 Actual Speed Speed Meters 3-12 1194 Act Ten Ref Pct Winder Functions 3-43
926 Filt Torq Cur Torque Attribute 3-19 1195 Speed Match Winder Functions 3-43
928 Filt TorqCur Pct Current Meters 3-12 1196 Spd Match Acc Winder Functions 3-44
1012 Inertia C Filter Autotune 3-20 1197 Spd Match Dec Winder Functions 3-44
No. Parameter Name Group Page No. Parameter Name Group Page
1198 Offs Accel Time Winder Functions 3-44 1269 Inversion Out 3 Digital Outputs 3-70
1199 W Offset Winder Functions 3-44 1270 Inversion Out 4 Digital Outputs 3-70
1200 Spd Match Gain Winder Functions 3-44 1271 Inversion Out 5 Digital Outputs 3-70
1201 Winder Side Winder Functions 3-44 1272 Inversion Out 6 Digital Outputs 3-70
1202 W Gain Winder Functions 3-44 1273 Inversion Out 7 Digital Outputs 3-70
1203 Spd Match Compl Winder Functions 3-44 1274 Inversion Out 8 Digital Outputs 3-70
1204 Line Spd Source Winder Functions 3-44 1275 Inversion Relay2 Digital Outputs 3-70
1205 Diam Inc Dec En Diameter Calc 3-42 1276 Inversion In 1 Digital Inputs 3-67
1206 Diam init filter Diameter Calc 3-42 1277 Inversion In 2 Digital Inputs 3-67
1207 Diam stdy delay Diameter Calc 3-42 1278 Inversion In 3 Digital Inputs 3-67
1208 Close Loop Comp Winder Functions 3-44 1279 Inversion In 4 Digital Inputs 3-67
1209 Torque Winder En Winder Functions 3-44 1280 Inversion In 5 Digital Inputs 3-67
1210 W Target Winder Functions 3-44 1281 Inversion In 6 Digital Inputs 3-67
1212 Acc Dec Filter Ramp Rates 3-30 1282 Inversion In 7 Digital Inputs 3-67
1213 Actual Comp Winder Functions 3-44 1283 Inversion In 8 Digital Inputs 3-67
1214 Closed Loop En Winder Functions 3-44 1284 Ref Spd Source Winder Functions 3-45
1215 Speed Demand En Winder Functions 3-45 1285 Ref Speed Gain Winder Functions 3-45
1216 Spd match torque Winder Functions 3-45 1286 Ref Line Speed Winder Functions 3-45
1217 W Reference Winder Functions 3-45 1287 Static F Zero Winder Functions 3-45
1218 Scale3 Input Scale Blocks 3-39 1319 Data In Val Sel Datalinks 3-60
1219 Scale3 Output Scale Blocks 3-39 1320 Data In SelData Datalinks 3-60
1220 Scale3 Mul Scale Blocks 3-39 1321 DPI Fdbk Select Comm Control 3-58
1221 Scale3 Div Scale Blocks 3-39 1322 Direction Mode Reference Config 3-46
1222 Scale3 In Max Scale Blocks 3-39 1323 DPI P1 Select DPI Inputs 3-71
1223 Scale3 In Min Scale Blocks 3-39 1324 DPI P2 Select DPI Inputs 3-71
1224 Scale3 In Off Scale Blocks 3-40 1325 DPI P3 Select DPI Inputs 3-71
1225 Scale3 Out Off Scale Blocks 3-40 1326 DPI P4 Select DPI Inputs 3-71
1226 Scale3 In Abs Scale Blocks 3-40 1327 DPI P5 Select DPI Inputs 3-71
1227 Scale4 Input Scale Blocks 3-39 1328 Drive Logic Rslt Diagnostics 3-51
1228 Scale4 Output Scale Blocks 3-39 1343 DPI Port Value Comm Control 3-58
1229 Scale4 Mul Scale Blocks 3-39 1344 Start At Powerup Restart Modes 3-32
1230 Scale4 Div Scale Blocks 3-39 1345 Powerup Delay Restart Modes 3-32
1231 Scale4 In Max Scale Blocks 3-39 1347 Fault Clear Faults 3-52
1232 Scale4 In Min Scale Blocks 3-39 1348 Fault Clr Mode Faults 3-52
1233 Scale4 In Off Scale Blocks 3-40 1349 Status1 at Fault Faults 3-52
1234 Scale4 Out Off Scale Blocks 3-40 1350 Status2 at Fault Faults 3-52
1235 Scale4 In Abs Scale Blocks 3-40 1351 Fault 1 Code Faults 3-53
1236 Scale5 Output Scale Blocks 3-39 1352 Fault 2 Code Faults 3-53
1237 Scale5 Input Scale Blocks 3-39 1353 Fault 3 Code Faults 3-53
1238 Scale5 Mul Scale Blocks 3-39 1354 Fault 4 Code Faults 3-53
1239 Scale5 Div Scale Blocks 3-39 1355 Fault 5 Code Faults 3-53
1240 Scale5 In Max Scale Blocks 3-39 1356 Fault 6 Code Faults 3-53
1241 Scale5 In Min Scale Blocks 3-39 1357 Fault 7 Code Faults 3-53
1242 Scale5 In Off Scale Blocks 3-40 1358 Fault 8 Code Faults 3-53
1243 Scale5 Out Off Scale Blocks 3-40 1359 Fault 9 Code Faults 3-53
1244 Scale5 In Abs Scale Blocks 3-40 1360 Fault 10 Code Faults 3-53
1245 Scale6 Output Scale Blocks 3-39 1361 Fault 1 Time Faults 3-53
1246 Scale6 Input Scale Blocks 3-39 1362 Fault 2 Time Faults 3-53
1247 Scale6 Mul Scale Blocks 3-39 1363 Fault 3 Time Faults 3-53
1248 Scale6 Div Scale Blocks 3-39 1364 Fault 4 Time Faults 3-53
1249 Scale6 In Max Scale Blocks 3-39 1365 Fault 5 Time Faults 3-53
1250 Scale6 In Min Scale Blocks 3-39 1366 Fault 6 Time Faults 3-53
1251 Scale6 In Off Scale Blocks 3-40 1367 Fault 7 Time Faults 3-53
1252 Scale6 Out Off Scale Blocks 3-40 1368 Fault 8 Time Faults 3-53
1253 Scale6 In Abs Scale Blocks 3-40 1369 Fault 9 Time Faults 3-53
1254 PID Error Gain PID Control 3-39 1370 Fault 10 Time Faults 3-53
1255 Jog TW Speed Winder Functions 3-45 1371 Fault Arm Amps Faults 3-53
1256 Jog TW Enable Winder Functions 3-45 1372 Fault Speed Diagnostics 3-53
1258 Enable PID PID Control 3-39 1373 Fault Field Amps Diagnostics 3-53
1262 Closing Speed Stop Modes 3-32 1374 Fault Voltage Diagnostics 3-53
1263 Opening Delay Stop Modes 3-32 1375 MOP Select Reference Config 3-46
1265 Ramp In Zero En Stop Modes 3-32 1376 Logic Mask Act Security 3-60
1266 Actuator Delay Stop Modes 3-32 1377 Write Mask Act Security 3-61
1267 Inversion Out 1 Digital Outputs 3-70 1378 Write Mask Cfg Security 3-61
1268 Inversion Out 2 Digital Outputs 3-70 1379 Port Mask Act Security 3-61
Troubleshooting
Faults and Alarms A fault is a condition that always stops the drive and prevents it from
starting until the fault condition is corrected. There are two fault types.
Type Description
➀ User Configurable This type of fault allows you to configure the drive’s response to the
condition that caused the error.
• When configured for a fault, the drive will be stopped, the error condition will
be annunciated on the HIM or a via digital output (if programmed) and the
drive will not be allowed to start until the fault condition is corrected.
• When configured for an alarm, the error condition will be annunciated on the
HIM or via a digital output (if programmed) and the drive will continue to run
and/or be allowed to start.
• When configured for ignore or disabled, the error condition will not be
recognized by the drive or be indicated on the HIM or via a programmed
digital output.
➁ Non-Configurable This type of fault is always enabled and will cause the drive to stop
running in order to protect the drive and/or motor from damage. In
some cases, drive or motor repair may be required. The cause of the
fault must be corrected before the fault can be cleared (via a fault reset
using the HIM or programmed digital input). The fault will be reset on
power up after repair.
An alarm indicates a drive error condition that does not stop the drive, but
may prevent it from starting. There are two types of alarms.
Type Description
➀ User Configurable This type of alarm indicates a drive error condition but does not stop
the drive from starting or running. However, if this type of alarm is left
uncorrected, a fault condition may eventually occur.
➁ Non-Configurable This type of alarm is always enabled and will prevent the drive from
starting until the alarm condition is corrected.
Drive Status The condition or state of your drive is constantly monitored. Any changes
will be indicated through the LEDs and/or the HIM (if present).
Figure 4.1 Drive Status Indicators
PORT
MOD
NET A
NET B
➋ ➊
STS
HIM Indication
The LCD HIM also provides visual notification of a fault or alarm
condition.
Condition Display
The drive is indicating a fault.
The LCD HIM immediately reports the fault condition by F-> Faulted Auto
displaying the following: 0.0 Hz
• “Faulted” appears in the status line — Fault — F 5
Main
Arm Menu:
• Fault number OverVoltage
Diagnostics
Time Since Fault
• Fault name 0000:23:52
Parameter
• Time that has passed since the fault occurred
Press “Esc” to regain HIM control.
The drive is indicating an alarm.
The LCD HIM immediately reports the alarm condition by F-> DigInCflctA Auto
displaying the following: 0.0 RPM
• Alarm name Main Menu:
• Alarm bell graphic Diagnostics
Parameter
Device Select
3. After corrective action has been taken, clear the fault by one of these
methods.
• Press “Stop”
• Cycle drive power
• Set parameter 1347 [Fault Clear] to 1 “Clear Faults”
• “Clear Faults” on the HIM Diagnostic menu
Port 1-5 Adapter 71 - 75 ➁ The communications card has a fault. Check the DPI device event queue and corresponding
fault information for the device.
STune CurLimit 59 ➁ The value of Par 1048 [Autotune Cur Lim] for auto
tuning the speed regulator is set too high.
Decrease the value of Par 1048 [Autotune Cur Lim]
and repeat the auto tune procedure.
STune FrictionLo 60 ➁ The friction value attained during the auto tuning
procedure is zero or lower than the control
Decrease the value of Par 1048 [Autotune Cur Lim]
and repeat the auto tune procedure.
precision limit.
STune LoadHi 58 ➁ The loading torque value is too high at zero speed
to complete the speed regulator auto tuning
Decrease the load torque, where applicable, and
repeat the auto tune procedure.
procedure.
STune Overspeed 56 ➁ The measured motor speed is too high during the
speed regulator auto tuning procedure.
Decrease the value of Par 1048 [Autotune Cur Lim]
and repeat the auto tune procedure.
STune Stalled 57 ➁ The drive stalled during the speed regulator auto
tuning procedure.
Increase the value of Par 1048 [Autotune Cur Lim] and
repeat the auto tune procedure.
STune Timeout 61 ➁ The speed regulator auto tuning procedure did
not complete within the available time.
Verify the value in Par 1048 [Autotune Cur Lim]. If this
value is set to low, the motor will not be able to reach a
maximum speed of 33% of the lower of the values in
Par 45 [Max Ref Speed] or Par 3 [Max Speed Fwd] or
Par 4 [Max Speed Rev] and not be able to complete
the test. Set these values appropriately and repeat the
auto tuning procedure.
Sustained Curr 70 ➁ The motor CEMF is too high or the line voltage is • Check the line voltage and frequency.
too low. • Check the motor brushes and connections.
• Check the Main and DB Contactor connections if
present.
• Verify that there are no overhauling loads present.
(1)
See page 4-1 for a description of fault types.
Clearing Alarms Alarms are automatically cleared when the condition that caused the alarm
is no longer present.
Alarm Descriptions The status of the alarms can be viewed in 1380 [Drive Alarm 1].
Table 4.C Alarm Descriptions and Actions
Alarm Type Description
AnalogCflct ➁ Sel],
More than one of the drive's reference inputs (Pars 70, 75 and 80 [Anlg Inx
Pars 1323-1327 [DPI Px Select], or Par 1021 [Encoder Out Sel]) are set
to "Speed Ref A" or "Speed Ref B". This alarm takes precedence over the
“EncoderCflct” alarm when both are present. Refer to Figure C.1 or Speed
Reference Selection on page D-5 for a graphical representation of the drive's
reference selections.
Arm
Overvoltage
➀ Motor
There is a possible overvoltage on the armature circuit or Par 175 [Rated
Volt] is set too low for the application. Refer to the “Arm Overvoltage”
fault description on page 4-4 for more information.
Auxiliary Input ➀ An auxiliary input interlock is open or a voltage (+15 - 30 V) or reference
signal is missing for the digital input set to 14 “Aux Fault”. Refer to the
“Auxiliary Input” fault description on page 4-4 for more information.
BipolarCflct ➁ ofParthe1322 [Direction Mode] is set to “Bipolar” or “Reverse Dis” and one or more
following digital input functions is configured: “Fwd/Reverse,” “Run
Forward,” “Run Reverse,” “Jog Forward” or “Jog Reverse.”
Acc2/Dec2 Accel 2 Decel 2 Jog 1/2 Jog Fwd Jog Rev Fwd/Rev
Acc2/Dec2
Accel 2
Decel 2
Jog 1/2
Jog Fwd
Jog Rev
Fwd/Rev
DigInCflctC ➁ More than one physical input has been configured to the same input function.
Multiple configurations are not allowed for the following input functions.
Forward/Reverse Run Reverse Run Forward
Jog Forward Jog Reverse Speed Select 1
Speed Select 2 Speed Select 3 Acc2 / Dec2
Accel 2 Decel 2 Run
Encoder Loss ➀ The drive is not receiving a speed feedback signal from the encoder. Refer to
the “Encoder Loss” fault description on page 4-4 for more information.
EncoderCflct ➁ One of the following has occurred:
• Par 414 [Fdbk Device Type] is set to 1 “Encoder” and Par 1021 [Encoder
Out Sel] is not set to 0 “Off”. If you are using an encoder, set Par 1021
[Encoder Out Sel] to 0 “Off”.
• More than one of the following parameters contains the same value: Pars
1021 [Encoder Out Sel], 70, 75 and 80 [Anlg Inx Sel], and/or 1323 - 1327
[DPI Px Select].
Drive starts but motor does not turn and no armature current.
Drive Symptom Action
The drive starts but there is no armature current • Verify the wiring to the analog input(s)
and the motor does not respond to a speed signal. selected for speed reference (refer to I/O
Wiring Examples on page 1-37).
• Verify the setting(s) of switch S9 and Par 71
[Anlg In1 Config]; or S10 and Par 76 [Anlg
In2 Config]; or S11 and Par 81 [Anlg In3
Config] (refer to DIP Switch and Jumper
Settings on page 1-32).
• Verify the speed selection digital input(s) and
the respective input terminal voltage(s), if
used.
• Verify the analog input(s) voltage(s)
displayed in parameters 1404 [Analog In1
Value], 1405 [Analog In2 Value] or 1406
[Analog In3 Value].
The drive starts and armature current is present • The Load may be too great for the motor and
but the motor does not turn. drive.
• Remove the load from the motor and test for
motor rotation. If the motor rotates, then
verify that the measured armature current,
using an in-line current meter or DC clamp
on meter, equals the armature current
feedback value displayed in parameters 200
[Arm Current] and 199 [Arm Current Pct].
Increase the value of parameter 7 [Current
Limit], 8 [Current Lim Pos] or 9 [Current Lim
Neg].
• Verify that the measured motor field current,
using an in-line current meter or DC clamp
on meter, equals the feedback value
displayed in parameter 351 [Field Current].
• Verify that the motor nameplate value equals
the value displayed in parameter 280 [Nom
Mtr Field Amps].
• Measure the DC voltage supplied to the
motor field. Verify that the value of
parameter 374 [Drv Fld Brdg Cur] equals the
setting of DIP Switch S14.
• If the motor does not rotate with the load
removed, check the motor.
• Verify that parameter 353 [Zero Torque] is
not enabled.
ATTENTION: If the motor is turning the wrong direction and the drive is
using an encoder or DC analog tachometer for feedback and the speed
! feedback is correct, then the feedback wiring must be changed. If using an
encoder, then two encoder connections must be reversed (A with A-Not or B
with B-Not). If using a DC analog tachometer, then the tachometer leads
must be reversed.
Testpoint Codes and Select a testpoint with Par 1381 [TestPoint Sel]. Values can be viewed with
Functions Par 1382 [TestPoint Data].
Values
No. (1) Description Minimum Maximum Default
566 Rx count
567 Tx count
568 BusLoss count
569 Port 1 Timeout
570 Port 2 Timeout 0 65535 0
571 Port 3 Timeout
572 Port 4 Timeout
573 Port 5 Timeout
574 Port 6 Timeout
(1)
Enter in [TestPoint Sel].
Specifications
Category Specification
Agency According to file E59272 for the series of the approved devices.
Certification
The drive is also designed to meet the following specifications:
NFPA 70 - US National Electrical Code
Category Specification
Drive Type Full Wave Regen, 6 Pulse, Regulated Field Supply
Protection Heat Sink Thermistor: Monitored by microprocessor overtemp trip
Drive Overcurrent Trip
Software Overcurrent Trip: 200% of rated current (typical)
Hardware Overcurrent Trip: 220-300% of rated current (dependent on drive rating)
Line transients: Up to 2000 volts peak per IEC 6100-4-5
Control Logic Noise Showering arc transients up to 1500V peak
Immunity:
Power Ride-Thru: 15 milliseconds at full load
Logic Control Ride-Thru: 0.5 seconds minimum, 2 seconds typical
Ground Fault Trip: Phase-to-ground on drive output
Short Circuit Trip: Phase-to-phase on drive output
Environment Altitude: 1000 m (3300 ft) max. without derating.
(1)
De-rate output power by 1.2% for every 100 meters
(328ft) above 1000 meters (3300ft).
Maximum Surrounding Air
Temperature IP20, NEMA
Type Open: 0 to 50 degrees C (32 to 122 degrees F), typical.
Storage Temp. (all const.): –25 to 55 degrees C (–13 to 131 degrees F)
Atmosphere: Important: Drive must not be installed in an area where
the ambient atmosphere contains volatile or corrosive
gas, vapors or dust. If the drive is not going to be installed
for a period of time, it must be stored in an area where it
will not be exposed to a corrosive atmosphere.
Relative Humidity: Operating: 5 to 85% non-condensing
Storage: 5 - 95% non-condensing
Shock: 15G peak for 11ms duration (±1.0 ms)
Vibration: 0.152 mm (0.006 in.) displacement, 1G peak
(1)
PowerFlex DC drives must be installed in a Pollution Degree 2 environment.
Category Specification
Drive Type Full Wave Regen, 6 Pulse, Regulated Field Supply
Electrical Input Voltages: 230 to 480V AC +/- 10%, 3 Phase
Input Frequency: 50/60 Hz +/- 5%
Armature Output Voltage: Two Quadrant Drives Four Quadrant Drives
260V DC @ 230V AC 240V DC @ 230V AC
470V DC @ 400V AC 420V DC @ 400V AC
530V DC @ 440V AC 460V DC @ 440V AC
560V DC @ 460V AC 480V DC @ 460V AC
580V DC @ 480V AC 500V DC @ 480V AC
Output Horsepower (Cont.) 1.5 to 150 HP @ 230V AC
2 to 400 HP @ 460V AC
Output Current: 4.1 to 667A
Overload Capability: 100% rated continuous current
150% rated current for one minute then fault
200% rated current for three seconds then fault
Field Output Voltage 200V DC @ 230V AC
310V DC @ 400V AC
360V DC @ 460V AC
Maximum field output voltage is 0.85 x AC input line
voltage.
Controller Current Overload: 150% rated current for one minute
200% rated current for three seconds
Max. Short Circuit Rating: 100,000 A, with the following exceptions:
• 230V AC input, 521 A, two quadrant drives are short
circuit rated at 10,000 A
• 460V AC input, 495 A and 667 A, two quadrant drives
are short circuit rated at 18,000 A
Control Speed Regulation:* All operating modes:
Max. speed: 8000 rpm
Digital reference resolution: 0.25 rpm
Analog reference resolution: ≥ 0.25 rpm
with Digital Incremental Encoder
Speed feedback resolution 0.5 rpm
Operating range better than 1000:1 rpm, bi-directional
Performance Accuracy ±0.02% typical
170 rad/sec bandwidth
with DC Analog Tachometer
Speed feedback resolution better than 2000:1 rpm
Operating range better than 1000:1 rpm, bi-directional
Performance accuracy ±0.1%
170 rad/sec bandwidth
with Armature Voltage Feedback
Voltage feedback resolution better than 2000:1 rpm
Operating range better than 100:1 rpm, bi-directional
Performance accuracy: ±2.0% typical
80 rad/sec bandwidth
*Subject to motor specs, current loop tuning.
Torque Regulation Current feedback resolution better than 2000:1 rpm
Performance accuracy: 1.0% typical
500 rad/sec bandwidth
Category Specification
Feedback Encoder Type: Incremental, dual channel, two channel optional
Devices (with jumper), differential (recommended) or
single-ended
Input Voltage: Configurable for +2.5V - 5.2V (switch S21
in ENC_5 position) or +5.4V - 15.2V (switch S21 in
ENC_12 position)
Input Current: 4.5 mA / 6.8 - 10.9 mA each channel
Quadrature: 90° ± 27° @ 25° C
Duty cycle: 50% ± 10% Source/Sink capable
Pulses Per Revolution: 600 to 9999
Maximum Frequency: 150 kHz
Maximum Cable Length: Shielded, 150m (0.75 mm2),
125m (0.5 mm2), 55m (0.22 mm2)
DC Analog Tachometer Input Voltage: 22.7, 45.4, 90.7, 181.6, & 302.9V max.
Input Current: 8 mA full scale
Maximum Cable Length: Shielded, depends on the
installation, typical 150m.
Inputs Analog Inputs Three configurable, isolated, differential
±10V, 0-10V, 0-20mA or 4-20mA.
Digital Inputs Eight standard configurable, four additional configurable
with the I/O Expansion circuit board.
Max Voltage +30V DC input, 200mA (total current draw is
the sum of encoder power, digital outputs and any other
loads connected to terminal 19)
Outputs Analog Outputs Two standard configurable, two additional configurable
with the I/O Expansion circuit board. Sampling rate 2 ms.
± 10V, 5mA, bipolar (current is not bipolar)
Digital Outputs Four standard configurable, four additional configurable
with the I/O Expansion circuit board.
+ 30V, 50mA
Relay Outputs Two configurable, N.O. contacts
Max. 250V AC, 1A AC1
IP20 (NEMA UL/Type Open) Watts loss data shown below is based on the rated current of the drive.
Watts Loss Important: For drives with 230V input, rated 150 HP / 521 A, the cooling
fans must be powered by an external 230V 50/60 Hz power
supply at terminals U3 & V3.
Drive Current Rating
Frame
Code(1) Total Watts Fans
@ 230V @ 460V Loss (W) Voltage (V) Rated Current (A) Air Capacity (m3/h)
A 7P0 4P1
9P0 6P0
012 010 131 – – –
020 014
– 019
029 027 186 – – –
038 035
055 045 254 80
– 052
073 073 408 160
093 086
476 160
110 –
– 100
553 160
– 129 Internal power supply
B 146 167
781 320
180 –
218 207 939 320
265 250 1038 320
– 330 1248 320
360 412
1693 680
434 –
C 521 495 2143 230 0.75 1050
– 667 2590 230 0.75 1050
(1) Refer to Catalog Number Explanation on page Preface-4, positions 8-10 for corresponding drive HP rating,
armature amp rating and field amp rating.
Drive Power Circuit The tables on the following pages provide drive ratings and the
Protection recommended fuses for protecting the armature and field circuits.
Externally mounted fuses (as indicated in Figure A.3 on page A-7) must be
sourced separately when installing the drive. Internally mounted fuses are
provided with the drive.
FS1 = Externally
FS1
mounted fuses for
the armature
converter on the
AC input side.
U V W U1 V1 FS3 = Internally
mounted fuses
FS3
for the field
circuit on the AC
C D C1 D1 input side.
Table A.A AC Input Line Fuses - 230V AC Input Frame A and B (Regenerative and
Non-Regenerative Drives)
Fuse Code FS1 (See Figure A.3 above)
Drive Bussmann Ferraz Shawmut (Gould Shawmut)
Current AC North
Frame
Rating DC Line Ferrule FWP Ferrule North American American Ferrule A70QS North American
Code Amps Amps Type Fuse Block FWP Type Fuse Block Type A70P / A70QS Type
A 7P0 7 5.7 FWP-10A14F CH143D FWP-10B – A70QS10-14F A70P10-4
9P0 9 7.4 FWP-15A14F FWP-15B – A70QS16-14F A70P15-4
012 12 9.8 FWP-20A14F FWP-20B – A70QS20-14F A70P20-4
020 20 16 FWP-25A14F FWP-25B – A70QS25-14F A70QS25-4
029 29 24 FWP-40A22F CH223D FWP-40B – A70QS40-22F A70QS40-4
038 38 31 FWP-63A22F FWP-60B – A70QS63-22F A70QS60-4
055 55 45 FWP-80A22F FWP-80B – A70QS80-22F A70QS80-4
073 73 60 – – FWP-100A ST14 – A70QS100-4K
093 93 76 – – FWP-150A – A70QS150-4K
110 110 90 – – FWP-175A – A70QS175-4K
B 146 146 119 – – FWP-250A – A70QS250-4
180 180 147 – – FWP-300A – A70QS300-4
218 218 178 – – FWP-350A – A70QS350-4
265 265 217 – – FWP-400A ST38-72612 – A70QS400-4
360 360 294 – – FWP-600A – A70QS600-4K
434 434 355 – – FWP-600A – A70QS600-4
Table A.B Recommended AC Input Line Fuses - 460V AC Input Frame A and B
(Regenerative and Non-Regenerative Drives)
Fuse Code FS1 (See Figure A.3 on page A-7)
Drive Bussmann Ferraz Shawmut (Gould Shawmut)
Current AC North
Frame
Rating DC Line Ferrule FWP Ferrule North American American Ferrule A70QS North American
Code Amps Amps Type Fuse Block FWP Type Fuse Block Type A70P / A70QS Type
A 4P1 4.1 3.3 FWP-10A14F CH143D FWP-10B – A70QS10-14F A70P10-4
6P0 6 4.9 FWP-10A14F FWP-10B – A70QS10-14F A70P10-4
010 10 8.2 FWP-20A14F FWP-20B – A70QS20-14F A70P25-4
014 14 11.4 FWP-25A14F FWP-25B – A70QS25-14F A70P25-4
019 19 15.5 FWP-25A14F FWP-25B – A70QS25-14F A70P25-4
027 37 22.1 FWP-40A22F CH223D FWP-40B – A70QS40-22F A70QS40-4
035 35 28.6 FWP-63A22F FWP-60B – A70QS63-22F A70QS60-4
045 45 36.8 FWP-80A22F FWP-80B – A70QS80-22F A70QS80-4
052 52 42.5 FWP-80A22F FWP-80B – A70QS80-22F A70QS80-4
073 73 59.6 – – FWP-100A ST14 – A70QS100-4K
086 86 70.3 – – FWP-150A – A70QS150-4K
100 100 81.7 – – FWP-175A – A70QS175-4K
129 129 105.4 – – FWP-175A – A70QS175-4K
B 167 167 136.4 – – FWP-300A – A70QS300-4
207 207 169.1 – – FWP-350A – A70QS350-4
250 250 204.3 – – FWP-400A ST38-72612 – A70QS400-4
330 330 269.6 – – FWP-600A – A70QS600-4K
412 412 336.6 – – FWP-600A – A70QS600-4
Table A.C Recommended Armature DC Output Fuses - 230V AC Input Frame A and B
(Regenerative Drives Only)
Fuse Code FS2(1) (See Figure A.3 on page A-7)
Drive Bussmann Ferraz Shawmut (Gould Shawmut)
Current AC North
Frame
Rating DC Line Ferrule FWP Ferrule North American American Ferrule North American
Code Amps Amps Type Fuse Block FWP Type Fuse Block A70QS Type A70P / A70QS Type
A 7P0 7 5.7 FWP-15A14F CH142D FWP-15B – A70QS16-14F A70P15-4
9P0 9 7.4 FWP-20A14F FWP-20B – A70QS20-14F A70P20-4
012 12 9.8 FWP-25A14F FWP-25B – A70QS25-14F A70P25-4
020 20 16 FWP-40A14F FWP-40B – A70QS40-14F A70QS40-4
029 29 24 FWP-63A22F CH222D FWP-60B – A70QS63-22F A70QS60-4
038 38 31 FWP-80A22F FWP-80B – A70QS80-22F A70QS80-4
055 55 45 – – FWP-125A ST14 – A70QS125-4K
073 73 60 – – FWP-150A – A70QS150-4K
093 93 76 – – FWP-200A – A70QS200-4K
110 110 90 – – FWP-225A – A70QS250-4
B 146 146 119 – – FWP-300A – A70QS300-4
180 180 147 – – FWP-350A A70QS350-4
218 218 178 – – FWP-450A ST38-72612 – A70QS450-4
265 265 217 – – FWP-600A – A70QS600-4K
360 360 294 – – FWP-700A – A70QS700-4
434 434 355 – – FWP-900A – – A70P900-4
(1) Required on four quadrant drives only, highly recommended on two quadrant drives.
Table A.D Recommended Armature DC Output Fuses - 460V AC Input Frame A and B
(Regenerative Drives Only)
Fuse Code FS2(1) (See Figure A.3 on page A-7)
Drive Bussmann Ferraz Shawmut (Gould Shawmut)
Current AC North
Frame
Rating DC Line Ferrule FWP Ferrule North American American Ferrule North American
Code Amps Amps Type Fuse Block FWP Type Fuse Block A70QS Type A70P / A70QS Type
A 4P1 4.1 3.3 FWP-10A14F CH142D FWP-10B – A70QS10-14F A70P10-4
6P0 6 4.9 FWP-15A14F FWP-15B – A70QS16-14F A70P15-4
010 10 8.2 FWP-20A14F FWP-20B – A70QS20-14F A70P20-4
014 14 11.4 FWP-30A14F FWP-30B – A70QS32-14F A70P30-4
019 19 15.5 FWP-40A14F FWP-40B – A70QS40-14F A70QS40-4
027 37 22.1 FWP-63A22F CH222D FWP-60B – A70QS63-22F A70QS60-4
035 35 28.6 FWP-80A22F FWP-70B – A70QS80-22F A70QS70-4
045 45 36.8 FWP-100A22F FWP-90B – – A70QS90-4
052 52 42.5 FWP-100A22F FWP-100B – – A70QS100-4
073 73 59.6 – – FWP-150A ST14 – A70QS150-4K
086 86 70.3 – – FWP-175A – A70QS175-4K
100 100 81.7 – – FWP-200A – A70QS200-4K
129 129 105.4 – – FWP-250A – A70QS250-4
B 167 167 136.4 – – FWP-350A – A70QS350-4
207 207 169.1 – – FWP-400A – A70QS400-4
250 250 204.3 – – FWP-500A ST38-72612 – A70QS500-4K
330 330 269.6 – – FWP-700A – A70QS700-4
412 412 336.6 – – FWP-800A – A70QS800-4
(1) Required on four quadrant drives only, highly recommended on two quadrant drives.
Table A.E Recommended Field Circuit Fuses - 230V AC Input Frame A and B
(Regenerative and Non-Regenerative Drives)
Drive Fuse Code FS3(1) (SeeFigure A.3 on page A-7, Figure A.4 on
Current page A-10 and Figure A.5 on page A-11 for location)
Frame
Table A.F Recommended Field Circuit Fuses - 460V AC Input Frame A and B
(Regenerative and Non-Regenerative Drives)
Drive Fuse Code FS3(1) (SeeFigure A.3 on page A-7, Figure A.4 below
Current and Figure A.5 on page A-11 for location)
Frame
Rating Field Ferraz Shawmut
Code Amps Type Bussmann (Gould Shawmut) SIBA
A 4P1 10 6 x 32 mm FWH-016A6F E085449 70 125 40.16
6P0
010
014
019
027
035
045
052
073 14
086
100
129
B 167 20 10 x 38 mm FWC-25A10F A60Q25-2 60 033 05.25
207
250
330
412
(1) Internal fuses - provided with the drive.
Bottom View of Drive with Fan Bottom View of Drive without Fan
Table A.G Recommended Field Circuit Fuses - 230V AC Input Frame C (Regenerative
and Non-Regenerative Drives)
Drive Fuse Code FS3 (See Figure A.6 on page A-11 and Figure A.7
Current below for location)
Rating Field Ferraz Shawmut
Code Amps Type Bussmann (Gould Shawmut) SIBA
521 20 10 x 38 mm FWC-25A10F A60Q25-2 60 033 05.25
Table A.H Recommended Field Circuit Fuses -460V AC Input Frame C (Regenerative
and Non-Regenerative Drives)
Drive Fuse Code FS3 (See Figure A.6 on page A-11 and Figure A.7
Current below for location)
Rating Field Ferraz Shawmut
Code Amps Type Bussmann (Gould Shawmut) SIBA
495 20 10 x 38 mm FWC-25A10F A60Q25-2 60 033 05.25
667 A60Q25-8
Table A.I Recommended Leg Fuses - 230V AC Input Frame C (Regenerative Drives
Only)
Drive Fuse Code FS4 (See Figure A.6 on page A-11 and Figure A.8 below for location)
Current AC Bussmann Ferraz Shawmut (Gould Shawmut) SIBA
Rating DC Line
Code Amps Amps Square Body - Flush End Contact
521 521 426 170M5464 + switch 170H0069 6,9 URD 32 TTF 800 + switch MS3-V1-5BS 20 671 32.800 + switch 2800104
Table A.J Recommended Leg Fuses - 460V AC Input Frame C (Regenerative Drives
Only)
Drive Fuse Code FS4 (See Figure A.6 on page A-11 and Figure A.9 on page A-14 for location)
Current AC Bussmann Ferraz Shawmut (Gould Shawmut) SIBA
Rating DC Line
Code Amps Amps Square Body - Flush End Contact
495 495 404.4 170M5462 + switch 170H0069 6,9 URD 32 TTF 630 + switch MS3-V1-5BS 20 671 32.630 + switch 2800104
667 667 544.9 170M5464 + switch 170H0069 6,9 URD 32 TTF 800 + switch MS3-V1-5BS 20 671 32.800 + switch 2800104
Note: Drive shown with front covers removed and Control EMI shield lowered.
Note: Drive shown with front covers removed and Control EMI shield lowered.
Control Power Circuit The following fuses are used to protect the Switching Power Supply circuit
Protection Fuses and the MOVs on the Pulse Transformer circuit board (frame B drives only)
or Transient Noise Filter circuit board (frame C drives only).
Frame Mounted on Designation Fuse
A Switching Power Supply circuit board F1 1A, 250V slow, 5x20mm
B and C Switching Power Supply circuit board F1 3.15A, 250V slow, 5x20mm
F2 2.5A, 250V fast, 5x20mm
B Pulse Transformer circuit board F1/F2/F3 16A, 500V fast, 6x32mm
C Transient Noise Filter circuit board F11/F21/F31 25A, 500V fast, 6x32mm
AC Input Line Reactors and If a DC Contactor is used, an AC Input contactor is not needed.
AC Input Contactors
Table A.M 230V AC Input, Regenerative Drives
AC Line IP00 (Open Style) Line Reactor
Drive Cat. No. DC Amps Amps HP Cat No. Line Reactor kW (HP) AC Input Contactor Cat. No.
20P-41AB7P0 7 5.7 1.5 1321-3R8-A .75 (1) 100-C12D10
20P-41AB9P0 9 7.4 2 1321-3R12-A 1.49 (2) 100-C12D10
20P-41AB012 12 9.8 3 1321-3R18-A 0.75-3.7 (1-5) 100-C12D10
20P-41AB020 20 16 5 1321-3R18-A 0.75-3.7 (1-5) 100-C23D10
20P-41AB029 29 24 7.5 1321-3R55-A 5.5-11 (7.5-15) 100-C30D10
20P-41AB038 38 31 10 1321-3R55-A 5.5-11 (7.5-15) 100-C37D10
20P-41AB055 55 45 15 1321-3R55-A 5.5-11 (7.5-15) 100-C60D10
20P-41AB073 73 60 20 1321-3R80-A 15 (20) 100-C60D10
20P-41AB093 93 76 25 1321-3R100-A 18.5-22 (25-30) 100-C85D10
20P-41AB110 110 90 30 1321-3R100-A 18.5-22 (25-30) 100-D110D11
20P-41AB146 146 119 40 1321-3R160-A 30-37 (40-50) 100-D140D11
20P-41AB180 180 147 50 1321-3R160-A 30-37 (40-50) 100-D180D11
20P-41AB218 218 178 60 1321-3RB250-A 45-56 (60-75) 100-D180D11
20P-41AB265 265 217 75 1321-3RB250-A 45-56 (60-75) 100-D250ED11
20P-41AB360 360 294 100 1321-3RB320-A 75 (100) 100-D300ED11
20P-41AB434 434 355 125 1321-3RB400-A 93 (125) 100-D420ED11
20P-41AB521 521 426 150 1321-3R500-A 112 (150) 100-D630ED11
20P-41AB434 434 355 125 (1) 240 0.5 1458 651 (5) (7)
(5) (7)
20P-41AB521 521 426 150 (2) 240 0.322 6221 781
(1)
Qty 4-CUTLER-HAMMER_G3AP50 Two in series, two in parallel. Must be sourced separately from drive.
(2)
HUBBELL_Y139W322GB - Must be sourced separately from drive.
(3) Coil voltage = 115V AC, 50/60Hz.
(4)
ABB_EHDB360C-1L-22 - ABB Contactor for drives with a dynamic brake. Must be sourcing separately from drive.
(5)
ABB_EHDB520C2P-1L - ABB Contactor for drives with no Dynamic Brake. ABB_EHDB520C-1L - ABB Contactor for drives with Dynamic Brake. Must be sourced separately from drive.
(6) See DC Contactor Crimp Lug Kit Specifications on page A-21 for more information.
(7)
Wire and Lug size dependant on Cabinet dims and local codes.
20P-21AB434 434 355 125 (1) 240 0.5 1458 – (5) (7)
(5) (7)
20P-21AB521 521 426 150 (2) 240 0.322 6221 –
(1)
Qty 4-CUTLER-HAMMER_G3AP50 Two in series, two in parallel. Must be sourced separately from drive.
(2)
HUBBELL_Y139W322GB - Must be sourced separately from drive.
(3) Coil voltage = 115V AC, 50/60Hz.
(4)
ABB_EHDB360C-1L-22 - ABB Contactor for drives with a dynamic brake. Must be sourcing separately from drive.
(5)
ABB_EHDB520C2P-1L - ABB Contactor for drives with no Dynamic Brake. ABB_EHDB520C-1L - ABB Contactor for drives with Dynamic Brake. Must be sourced separately from drive.
(6) See DC Contactor Crimp Lug Kit Specifications on page A-21 for more information.
(7)
Wire and Lug size dependant on Cabinet dims and local codes.
20P-41AD412 412 336.6 250 (1) 500 0.808 7292 – (6) (10)
20P-41AD495 495 404.4 300 (2) 500 0.595 6069 – (7) (10)
20P-41AD667 667 544.9 400 (3) 500 0.542 6439 – (8) (10)
(1)
HUBBELL_Y95W808GB - Must be sourced separately from drive.
(2)
HUBBELL_Y101W595GB - Must be sourced separately from drive.
(3) HUBBELL_Y109W542GB - Must be sourced separately from drive.
(4)
Coil voltage = 115V AC, 50/60Hz.
(5)
ABB_EHDB360C-1L-22 - ABB Contactor for drives with a dynamic brake. Must be sourcing separately from drive.
(6) ABB_EHDB520C2P-1L - ABB contactor for drives with no dynamic brake. ABB_EHDB520C-1L - ABB contactor for drives with a dynamic brake. Must be sourced separately from drive.
(7)
ABB_EHDB650C2P-1L - ABB contactor for drives with no dynamic brake. ABB_EHDB650C-1L - ABB contactor for drives with a dynamic brake. Must be sourced separately from drive.
(8)
ABB_EHDB800C2P-1L - ABB contactor for drives with no dynamic brake. ABB_EHDB800C-1L - ABB contactor for drives with a dynamic brake. Must be sourced separately from drive.
(9) See DC Contactor Crimp Lug Kit Specifications on page A-21 for more information.
(10)
Wire and Lug size dependant on Cabinet dims and local codes.
DC Contactor Crimp Lug Kit Use the information provided in the table below to assist you in ordering the
Specifications correct Lug kit for your application.
Notes:
HIM Overview
External and Internal The PowerFlex DC drive provides a number of cable connection points for
Connections the HIM (Frame A shown).
➊ ➍
PORT
MOD
NET A
NET B
STS
➋
2
3ro
1
➌ DPI Port 3 or 2 Splitter cable connected to DPI Port 2 provides additional port.
F-> Power Loss Auto Direction⎥ Drive Status⎥ Alarm⎥ Auto/Man⎥ Information
0.0 RPM Commanded or Output Speed or Current
Main Menu:
Diagnostics
Parameter
Programming / Monitoring / Troubleshooting
Device Select
The top line of the HIM display can be configured with parameter 1321 [DPI Fdbk Select].
ALT Functions To use an ALT function, press the ALT key, release it, then press the
programming key associated with the function printed on the HIM above
the key:
Table B.A ALT Key Functions
Press the ALT Key
and then … Performs this function …
S.M.A.R.T. Displays the S.M.A.R.T. list screen. See Using the S.M.A.R.T. List Screen
below for more information.
ALT Esc
View Allows the selection of how parameters will be viewed or detailed information
about a parameter or component.
Sel
Lang Displays the language selection screen (Not available on the PowerFlex DC
drive).
Remove Allows HIM removal without causing a fault if the HIM is not the last controlling
device and does not have Manual control of the drive.
User
Display
Device Identity
Preferences Change Password
User Dspy Lines
Key:
Press to move between menu items
Press to select a menu item
Press Esc to move 1 level back in the menu structure
Press ALT Sel to select how to view parameters
Diagnostics Menu
When a fault trips the drive, use this menu to access detailed data about the
drive.
Option Description
Faults View fault queue or fault information, clear faults or reset
drive.
Status Info View parameters that display status information about the
drive.
Device Items View statistics associated with DPI Communications.
Device Version View the firmware version and hardware series of
components.
Parameter Menu
Use this menu to view and edit parameters for the drive. When you enter the
the Parameter menu, by default the File–Group–Parameter view is displayed. To
access other views for the Parameter menu, with "Parameter" highlighted in
the Main menu, press Alt then Sel (View), select the desired view in the list
and press Enter. The following selections are available:
Option Description
Param Access Lvl Displays parameter 211 [Param Access Level]. The PowerFlex DC drive is
initially set to the Basic Parameter view. To view all parameters, set parameter
211 [Param Access Lvl] to option 1 “Advanced”.
File-Group-Par (FGP) Displays all parameters in a File - Group - Parameter structure. This simplifies
programming by grouping parameters that are used for similar functions.
Numbered List Displays all parameters in numerical order.
Changed Params Displays the most recently changed parameter. You can scroll through the list
of all changed parameters to the least recently changed. The new and default
values are listed for each parameter.
Refer to Viewing and Editing Parameters on page B-5 for more information.
Preferences Menu
The HIM and drive have features that you can customize.
Option Description
Drive Identity Add text to identify the drive.
User Dspy Lines Select the display, parameter, scale and text for the User
Display. The User Display is two lines of user-defined data
that appears when the HIM is not being used for
programming.
Removing/Installing the HIM The HIM can be removed or installed while the drive is powered.
Important: HIM removal is only permissible in Auto mode. If the HIM is
removed while in Manual mode or the HIM is the only
remaining control device, a fault will occur.
Step Key(s) Example Displays
To remove the HIM . . . ALT +
1. Press ALT and then Enter (Remove). Remove Op Intrfc:
The Remove HIM confirmation screen Press Enter to
appears. Disconnect Op Intrfc?
(Port 1 Control)
2. Press Enter to confirm that you want to
remove the HIM.
To install HIM . . .
1. Insert into drive or connect cable.
Application Notes
For information on . . See page For information on . . See page
Analog Input Configuration C-1 Speed Feedback C-15
Current / Speed Curve C-4 Scale Blocks C-16
Droop Compensation C-5 Speed Regulation Functions C-17
Field Weakening Mode Configuration C-5 Start At Powerup C-24
(v1.006)
PID Function C-8 Fine Tuning the Regulators C-25
Reference Control C-13
Analog Input Configuration The analog inputs default to ±10V. To configure the analog inputs for
0-10V, set parameters [Anlg Inx Config] to 1, “0-10V”. To configure the
analog inputs for a current signal, set parameters [Anlg Inx Config] to 2, “0
- 20mA” or 3, “4 to 20mA”. In addition, switches S9, S10 and S11 must be
properly configured (refer to Table 1.L on page 1-33 for more information).
Refer to the “Analog Inputs / Outputs & Mapping” block diagram on page D-4 for more information.
Example 1:
The speed reference value of a drive is defined with an external voltage of
5V. With this value the drive should reach the maximum allowable speed set
in Par 45 [Max Ref Speed]. Enter a scaling factor of 2 in [Anlg Inx Scale] to
scale the input voltage from 5V to 10V.
Example 2:
An external analog reference reaches a maximum value of 9.8V. Enter a
scaling factor of 1.020 in [Anlg Inx Scale] to scale the maximum voltage
from 9.8V to 10V.
The same result could be obtained via parameter [Anlgx Tune Scale], by
entering the values of the appropriate parameters via the HIM. The
maximum possible analog value (in this case 9.8V) would have to be
present at the terminal with a positive polarity.
Calculations used to determine Pars1042 [Anlg In1 Cmp] and 1043 [Anlg
In1 Cmp Err]:
Example 1:
• For Analog Input 1, 10V or 20mA sets the maximum value of Par 44
[Speed Ref A] = Par 45 [Max Ref Speed]
• Set Par 1042 [Anlg In1 Cmp] = 4667 (700 x 10000 / 1500)
• Set Par 1043 [Anlg In1 Cmp Err] = 666 (100 x 10000 / 1500 )
• Par 1045 [Anlg In1 Cmp Eq] = “1” (high) when the signal on Analog
Input 1 is within the range specified in Par 1043 [Anlg In1 Cmp Err]. Par
1045 [Anlg In1 Cmp Eq] = “0” (low) when the signal on Analog Input 1
is outside the range specified in Par 1043 [Anlg In1 Cmp Err].
Example 2:
An application requires an indication via a digital output that the output
current is within ±2% of 50% of the maximum current limit.
• For Analog Input 1, 10V or 20mA sets the maximum value = Par 7
[Current Limit]
• Set Par 1042 [Anlg In1 Cmp] = 5000 (50 x 10000 / 100)
• Set Par 1043 [Anlg In1 Cmp Err] = 200 (2 x 10000 / 100 )
Current / Speed Curve The current/speed curve function allows you to establish a current limit
lower than the standard current limits of the drive (specified in parameters 8
[Current Lim Pos] and 9 [Current Lim Neg]) and reduce the output current
(torque) of the drive through a defined curve of five equally divided set
points as the speed increases based on a threshold speed, effectively
reducing torque.
• Set the current limit (for both directions of rotation in four quadrant
drives) in parameter 751 [TrqTpr_Lim0]. The value specified in this
parameter overrides the value of parameters 8 [Current Lim Pos] and 9
[Current Lim Neg].
• Set the threshold speed at which current (torque) reduction begins in
parameter 756 [TrqTpr_Spd].
• Set the first reduced current limit in parameter 752 [TrqTpr_Lim1]. The
value defined in this parameter must be less than the value in parameter
751 [TrqTpr_Lim0] and greater than the values in parameters 753
[TrqTpr_Lim2], 754 [TrqTpr_Lim3] and 755 [TrqTpr_Lim4].
• Set the second, third and final reduced current limits in parameters 753
[TrqTpr_Lim2], 754 [TrqTpr_Lim3] and 755 [TrqTpr_Lim4],
respectively. The value of each subsequent parameter must be less than
the previous parameter’s value. The drive will maintain the value
specified in parameter 755 [TrqTpr_Lim4] up to the value set in
parameter 162 [Max Feedback Spd].
Droop Compensation The Droop function is used when the current must be balanced between two
drives. A typical situation is when two motors are mechanically coupled and
must run at the same speed. If, because of differences in the drive’s speed
regulators, one of the motors runs at a higher speed, it will be overloaded
and the second motor will function, essentially, as a brake.
The Droop function allows you to overcome this difference by adding a load
compensation component to the speed reference, which is proportional to
the actual load differences of the drives.
For Example:
Master Drive Slave Drive
[Anlg In1 Sel] = “Speed Ref A” [Anlg In1 Sel] = “Speed Ref A”
[Anlg Out1 Sel] = “Torque Ref” [Anlg In2 Sel] = “Load Comp”
[Enable Droop] = “Enabled”
[Droop Percent] = 5%
[Droop Filter] = 100 ms
[Droop Limit] = 1000
Field Weakening Mode Important: This configuration applies only to firmware version 1.006. For
Configuration (v1.006) instructions on configuring a drive with firmware version 2.001
for use with an AC or DC contactor, with or without a dynamic
brake, refer to Using Contactors on page 1-9.
2. Set one relay output parameter (1392 [Relay Out 1 Sel] or 629 [Relay
Out 2 Sel]) to "Contactor" and the other relay output parameter to
"ContactorDB".
3. Set one [Digital Inx Sel] parameter to "Contactor" (default value for
parameter 140 [Digital In8 Sel]).
2. Set one [Relay Out x Sel] parameter and one [Digital Inx Sel] parameter
to "Contactor" (default value for parameters 1392 [Relay Out 1 Sel] and
140 [Digital In8 Sel]).
3. Set one [Digital Inx Sel] parameter to "Contactor" (default value for
parameter 140 [Digital In8 Sel]).
PID Function The PID function is used to increase or reduce the reference signal output to
the speed or current regulator of the drive. The PID function can be used for
nip-roll, winder/unwinder, roll doctor/salvage machine, pump and extruder
pressure control and extruder temperature control applications. (Refer to the
complete “PID Control” block diagram on page D-17.)
❏ Line speed signal (see Configure a Line Speed Signal on page C-9)
❏ Closed loop dancer / load cell feedback (see Configure the
Feedback Signal in the Follower Drive(s) on page C-10)
❏ Tension set point (see Configure the Tension Set Point Signal in the
Follower Drive(s) on page C-12)
• Torque winder with a load cell and tension control
❏ Line speed signal (see Configure a Line Speed Signal on page C-9)
❏ Closed loop dancer / load cell feedback (see Configure the
Feedback Signal in the Follower Drive(s) on page C-10)
❏ Tension set point (see Configure the Tension Set Point Signal in the
Follower Drive(s) on page C-12)
• Configure an analog output for the main speed reference (1 “Spd Ref
Out”)
• Set Par 786 [PID Source] to 8695 (503 + 8192). “503” = the parameter
number to which the signal from analog input 3 is sent (Par 503
[UserDefined0]), and “8192” is a drive internal fixed offset value.
Line Speed
Master NIP-Roll
Reverse
Forward
Load Cell
0 - +10V
M E M E
Tension Set
-10V
Master Slave
Drive Set Drive
Feedback
+10V Forward
-10V Reverse
Line Speed Reference
• Enter the gain for the feed-forward signal in Par 787 [PID Source Gain]
• Monitor the feed-forward signal after the gain is applied in Par 758 [Feed
Fwd PID]
P758
Feed Fwd PID
P786
Gain
PID Source
P787
PID Source Gain
Line Speed
Master NIP-Roll
Reverse
Forward
Load Cell
0 - +10V
M E M E
Tension Set
-10V
Master Slave
Drive Set Drive
Feedback
+10V Forward
-10V Reverse
Line Speed Reference
• Par 763 [PID Feedback] contains the raw feedback counts from the
analog input signal received from the transducer position (dancer) or
tension (load cell)
• Monitor the tension set point for a torque winder application in Par 1194
[Act Ten Ref Pct]
• Configure the PID feedback gain in Par 1254 [PID Error Gain]
• Limit the PID correction error using Par 757 [PID Clamp]
• Monitor the actual error input to the PI and PD blocks in Par 759 [PID
Error]
P760 P762
PID Setpoint 0 PID Setpoint Sel
P761
PID Setpoint 1
P1254 P763
PID Error Gain PID Feedback
+ +
+ +
P763
PID Feedback
+ Σ Σ
Load Cell
0 - +10V
M E M E
Tension Set
-10V
Master Slave
Drive Set Drive
Feedback
+10V Forward
-10V Reverse
Line Speed Reference
P760 P762
PID Setpoint 0 PID Setpoint Sel
P761
PID Setpoint 1
P1254 P763
PID Error Gain PID Feedback
+ +
+ +
P763
PID Feedback
+ Σ Σ
Reference Control The drive speed command can be obtained from a number of different
sources. The source is determined by drive programming and the condition
of the digital inputs configured as speed selects, a digital input configured
for “Auto/Manual” or Reference Select bits of a command word (see
Communication Configurations on page A-5 for more information).
Auto/Manual Examples
A process is run by a PLC when in Auto mode and requires manual control
from the HIM during set-up. The speed reference is issued by the PLC
through a communications module installed in the drive (Port 5). Therefore,
parameter 1327 [DPI P5 Select] is set to “Speed Ref A” with the drive
running from the Auto source.
• Press ALT then Auto/Man on the HIM. When the HIM acquires manual
control, the drive speed command comes from the HIM speed control
keys.
• Press ALT then Auto/Man on the HIM again. When the HIM releases
manual control, the drive speed command returns to the PLC.
A process is run by a PLC when in Auto mode and requires manual control
from an analog potentiometer wired to the drive terminal block. The auto
speed reference is issued by the PLC through a communications module
installed in the drive (Port 5). Therefore, parameter 1327 [DPI P5 Select] is
set to “Speed Ref A” with the drive running from the Auto source. Since the
Manual speed reference is issued by analog input 2, parameter 75 [Anlg in2
Sel] is set to “TB Man Ref”. The value of analog input 2 can be viewed in
parameter 267 [TB Manual Ref]. To switch between Auto and Manual,
parameter 136 [Digital In4 Sel] is set to “Auto/ Manual”.
• Close the digital input. With the input closed, the speed command comes
from the pot.
• Open the digital input. With the input open, the speed command returns
to the PLC.
Auto/Manual Notes
2. If a HIM has manual control and power is removed from the drive, the
drive will return to Auto mode when power is reapplied.
Speed Feedback The value of parameters 169 [Encoder PPR] and 162 [Max Feedback Spd]
must be inside the allowed area shown in the figure below regardless of the
value selected in Par 414 [Fdbk Device Type].
10000
6000
5000
Par 162 [Max Feedback Spd]
4000
3000
All
ow
2000
ed
Ar
1000
ea
900
800
700
600
500
400
300
200
100 900
100 200 300 400 500 600 700 800 1000 2000 3000 4000
Scale Blocks The Scale Blocks function allows you to link or rescale dissimilar parameter
types (e.g., integer vs. real) though multiply, divide, maximum and
minimum limits, input and output offsets and absolute value functions.
There are six individually configurable Scale Blocks. A representative block
diagram is shown below.
• All input [Scalex Input] and output [Scalex Output] values are specified
as a parameter number (not parameter values).
• Both Sink (read/write) and Source (read only) parameters can be used as
input values ([Scalex Input]).
• Only Sink (read/write) parameters can be used as the output value
([Scalex Output]).
• Configuration parameters (parameters that can only be changed while
the drive is stopped) can be used as the output value ([Scalex Output]).
However, any value written to a configuration parameter will not take
effect in the drive until it is stopped.
• The output value is truncated to a whole number when different
parameter types are used (e.g., a real input value of 54.97% becomes an
integer output value of 54 RPM).
• Dividing by zero (0) does not cause an error, but will result in an output
value of zero (0).
• Turning off (setting = “0”) the input parameter or changing the output
parameter number does not reset or change the original output value (i.e.,
the output parameter remains at the last value written).
+ +
P484
Scale1 Input Σ X Σ P485
Scale1 Output
+ +
P491
P492 P489 Scale1 Out Off
Scale1 In Abs Scale1 In Min
P487
Scale1 Div
P490 P486
Scale1 In Off Scale1 Mul
For example, the value of an analog input 1, parameter 70 [Anlg In1 Sel],
can be linked to parameter 660 [Accel Time 1]. In order to do so:
In this way, rather than entering an acceleration time directly (via HIM), the
link allows the value to change by varying the analog signal. This can
provide additional flexibility for certain applications. This functionality
should be tested for the desired response before applying to an application.
Speed Regulation Functions The PowerFlex DC Digital drive provides a flexible speed regulator circuit
that can be adapted to the requirements of a variety of applications. The
drive is set to PI regulation by default.
P188 P189
Adaptive P Gain1 Adaptive I Gain1
P190 P191
Adaptive P Gain2 Adaptive I Gain2
P192 P193
Adaptive P Gain3 Adaptive I Gain3
P183
Adaptive Ref
P184 P185
Adaptive Spd 1 Adaptive Spd 2
The adaptive speed regulator is enabled with parameter 181 [Adaptive Spd
En] = “1 Enabled”. Normally the gain depends on the speed of the drive. It
can, however, vary according to a variable defined in parameter 183 [Adap
Ref]. The type of regulation used is selected in parameter 182 [Adaptive
Reg Typ]; 0 = “Speed”, or 1 = “Adaptive Ref”.
Parameters 184 [Adaptive Spd 1] and 185 [Adaptive Spd 2] are used to
define the three ranges that may have different gains. A parameter set can be
defined for each of these ranges, with each set containing an individually
definable P and I component (i.e., Pars 188 [Adaptive P Gain1] and 189
[Adaptive I Gain1], 190 [Adaptive P Gain2] and 191 [Adaptive I Gain2],
and 192 [Adaptive P Gain3] and 193 [Adaptive I Gain3]). When the
adaptive speed regulator is enabled, the first set of parameters is active until
the speed specified in Par 184 [Adaptive Spd 1] or Par 183 [Adap Ref] is
reached.
• If the gain must be changed on the basis of units other than the drive’s
speed reference, set Par 182 [Adaptive Reg Typ] = 1 “Adaptive Ref”. The
adaptive reference is provided to the drive as an analog value via an
analog input. For this reason Par 183 [Adaptive Ref] must be assigned to
an analog input. The other possibility is to enter the value of Par 183
[Adaptive Ref] via the HIM. In this case the an analog input is not
necessary.
• Enter the appropriate values in Par 184 [Adaptive Spd 1] and Par 185
[Adaptive Spd 2] to define the three speed ranges. Values are expressed
as a percentage of Par 45 [Max Ref Speed] and the maximum value of
Par 183 [Adaptive Ref].
• When Par 182 [Adaptive Reg Typ] = 0 “Speed”, tuning is completed via
Fine Tuning the Regulators on page C-25. In this case the following
points must be taken into consideration:
❏ The value entered in Par 61 [TstGen Offset] must be at the low end
of the speed range to be tuned, but is also outside the range set in
Par [Adaptive Joint x].
❏ Enter the step value in Par 60 [TstGen Amplitude], so that the speed
remains inside the range to be tuned.
❏ The optimization is carried out separately for each range and the
parameters of the regulator are set for each range with Pars
[Adaptive P Gainx] and [Adaptive I Gainx].
❏ After the optimization of the different phases review the entire
speed range. By changing the value of [Adaptive Joint x] it is
possible to reduce the instabilities present in the transients during
the changes from one range to the other. Increasing the values
transients are slighter.
• When the speed zero logic (see page C-22) is disabled (factory default
setting) and the drive is disabled, the gains of the speed regulator are
active. These are set via Pars 188 [Adaptive P Gain1] and 189 [Adaptive
I Gain1]. When the speed zero logic is enabled, the values set when the
motor is stopped are valid.
Speed Up Function
The Speed-up function is used to avoid oscillations in the presence of loads
with a high moment of inertia. When this function is enabled (default value
of 0 “Speed Up” in Par 1016 [SpdFuncSelect]), a D (derivative) value is
added to the speed feedback circuit, which allows you to increase the
integral gain of the speed regulator. It is also useful in the case of cyclical
non-constant loads on the motor (e.g., cams). The feedback applied to the
speed regulator is made of two components:
Figure C.2 Speed-Up function inactive Figure C.3 Speed-up function active
Oscillation during a speed change due to a high moment of The same drive with Speed-up function active.
inertia. Top: Par 122 [Spd Feedback]
Top: Par 122 [Spd Feedback] Bottom: Par 199 [Arm Current Pct]
Bottom: Par 199 [Arm Current Pct]
Par 393 [Speed Threshold] displays whether the speed of the drive is above
or below a set speed for clockwise and counter-clockwise rotation. Set the
threshold speed for clockwise rotation in Par 101 [Spd Thresh Pos] and set
the threshold speed for counter-clockwise rotation in Par 102 [Speed Thresh
Neg]. You can specify a delay time before indication that the speed has
fallen below the threshold values in Par 103 [Threshold Delay]. Par 393
[Speed Threshold] can be assigned to a digital output. A digital output so
assigned will only change state at the clockwise (positive) speed threshold.
P101
Speed Thresh Pos
P102
Speed Thresh Neg
P103 0 t
Threshold Delay
Par 394 [At Speed] indicates whether or not the speed of the drive
corresponds to the set speed reference (specified in Par 118 [Speed Reg In])
before the speed regulator and the ramp reference (if enabled) are applied.
The speed above and below the speed reference at which indication will
occur is set in Par 104 [At Speed Error]. You can specify a delay time before
indication that the speed reference is within the range set in Par 104 [At
Speed Error] will occur using Par 105 [At Speed Delay]. Par 394 [At Speed]
can be assigned to a digital output.
P118
Speed Reg In P104
At Speed Error
P122
Spd Feedback P394
At Speed
P105 0 t
At Speed Delay
• If the speed reference is above the value set in Par 106 [Ref Zero Level]:
Set Par 124 [Spd Ref Zero En] = 1 “Enabled”
• If the speed reference and/or the reaction are above the value set in Par
106 [Ref Zero Level], set Par 124 [Spd Ref Zero En] = 0 “Disabled”
Par 124 [Spd Ref Zero En] is active only when Par 125 [Spd Zero P En] = 1
“Enabled”.
• If the P gain corresponds to the value set in Par 126 [Spd Zero P Gain],
then set Par 125 [Spd Zero P En] = 1 “Enabled”
• If the P gain corresponds to the normal P gain, then set Par 125 [Spd
Zero P En] = 0 “Disabled”
The P gain at zero speed is set via Par 126 [Spd Zero P Gain] when Par 125
[Spd Zero P En] = 1 “Enabled”.
The threshold for the recognition of zero speed is determined by the value in
Par 106 [Ref Zero Level].
M M M
+
Line Speed
Drive A:
Drive C:
Start At Powerup The “Start At Powerup” function allows you to automatically resume
running at commanded speed after drive input power is restored, a run
command is issued and all of the start permissive conditions indicated in the
diagram below are met. To enable this feature, parameter 1344 [Start At
Powerup] must be set to 1 “Enable”.
Start At PowerUp
[Powerup Delay] No
Time Expired?
Yes
During the time specified in parameter 1345 [Powerup Delay], the alarm
indicator “ ” is displayed on the HIM and bit 12 “PwrUp Start” of
parameter 380 [Drive Status 1] is set to “1”.
Fine Tuning the Regulators The PowerFlex DC drive control regulators have predefined values meant to
provide consistent drive performance without performing any further
configuration, with the exception of the armature current regulator, which
must always be tuned. When the armature current regulator has been tuned
to meet the requirements of the application, the fine tuning procedures for
the other regulators are not necessary. However, the fine tuning procedures
can be used to optimize the output and control features of the drive.
The fine tuning procedures are included below. In order to obtain a step
function, the internal “Test generator” is used. The goal of the fine tuning
procedures is to obtain an optimal step response. For example, it is
recommended that you directly measure the step response for the field
current regulator.
The analog output can be connected to the terminal strip, with a sampling
rate of two milliseconds.
The “Test Generator” function creates signals with a rectangular wave form
based on a specific frequency and amplitude. The frequency and amplitude
can be added to a configurable offset value, if needed. Par 58 [TstGen
Output] determines which regulator input signal (reference) is active; torque
current, field, ramp, or speed.
❏ If the value of Par 587 [I Reg Error] is positive, increase the value
of Par 454 [Arm Inductance].
❏ If the value of Par 587 [I Reg Error] is negative, decrease the value
of Par 454 [Arm Inductance].
The procedure below is used for drives that use constant torque and power
(mixed armature and field regulation). In these cases it is necessary to
configure the field converter according to this method.
Important: Do not issue a “Start” command to the drive during the field
current regulator fine tuning procedure.
Follow the procedure below to fine tune and optimize the field current
regulator:
❏ Set Par 467 [Max Fld Curr Pct] = 100% of the field rated current of
the connected motor
5. Increase the value of the Par 91 [Fld Reg Kp] until the overshoot of the field
current (displayed in Par 234 [Fld Current Pct]) is lower than 4%.
6. Increase the value of Par 92 [Fld Reg Ki] until the overshoot is higher than 4%.
Then, decrease the value of this parameter until it becomes slightly lower than
4%.
Important: Because of the relatively high field time constant, the rising
speed of the field current is limited. The rising time with
optimal tuning conditions could be up to 100 milliseconds.
9. Set Par 468 [Min Fld Curr Pct] to the desired value.
Figure C.5 Increase in the field current with oscillation Figure C.7 Increase in the field current without
Non-optimal response of the regulator. oscillation
Top: Par 500 [Field Ref Pct] This graph, as compared to the graph in Figure C.5, shows an
Bottom: Par 234 [Fld Current Pct] increase in [Fld Reg Kp] from 2% to 10% with [Fld Reg Ki] = 5%.
Top: Par 500 [Field Ref Pct]
Bottom: Par 234 [Fld Current Pct]
8. Increase the value of Par 87 [Spd Reg Kp] until the overshoot is lower than 4%
with the shortest possible acceleration or deceleration time.
9. Increase the value of Par 88 [Spd Reg Ki] until the overshoot is higher than 4%.
Then, decrease the value of this parameter until its value becomes slightly
lower than 4%.
When it is necessary to have different gains for the speed regulator above
the speed range, you can utilize the adaptive speed regulator. For further
information about this function refer to the Adaptive Speed Regulator block
diagram page C-17.
Figure C.8 [Spd Reg Kp] too low Figure C.10 [Spd Reg Ki] too high
Top: Par 122 [Spd Feedback] Top: Par 122 [Spd Feedback]
Bottom: Par 199 [Arm Current Pct] Bottom: Par 199 [Arm Current Pct]
Figure C.9 [Spd Reg Kp] too high Figure C.11 [Spd Reg Ki] correct
Top: Par 122 [Spd Feedback] Top: Par 122 [Spd Feedback]
Bottom: Par 199 [Arm Current Pct] Bottom: Par 199 [Arm Current Pct]
When field weakening occurs, the voltage regulator keeps the armature
voltage at a constant level. The critical point for this regulator is at the
beginning of field weakening, because with the saturation of the motor field
the system requires more consistent changes in the field current in order to
carry out a flux change. Tune the regulator so that the armature voltage
undergoes very small changes.
Important: Before the optimization of the voltage regulator, the speed and
field current regulators must have already been tuned. Refer to
Tune the Current Regulator: on page 2-10 and Fine Tuning the
Field Current Regulator on page C-26.
2. Measure the field current and the armature voltage using analog outputs 1 and
2, by setting:
4. Check the armature voltage via analog output 2. After a possible short
oscillation, the voltage should remain constant. Refer to the Field Voltage
Regulator examples below. You can change the Proportional and Integral gains
of the Field Voltage regulator via Pars 493 [Arm Volt Kp] and 494 [Arm Volt Ki].
Figure C.12 Field voltage oscillation Figure C.14 Optimal field regulation
Oscillation after a speed change where [Arm Volt Kp] = 10% and After a short transient, the field current and armature voltage are
[Arm Volt Ki] = 80%. constant. [Arm Volt Kp] = 40%, [Arm Volt Ki] = 5%.
Top: Par 234 [Fld Current Pct] Top: Par 234 [Fld Current Pct]
Bottom: Par 233 [Output Voltage] Bottom: Par 233 [Output Voltage]
Important: Complete the procedures in the order listed below when tuning
the field current curve:
Examples:
• Curve A - If the default settings of the drive are retained, the flux current
to flux reference will remain linear when the value of Par 500 [Field Ref
Pct] changes. E.g.,
o If Par 467 [Max Fld Curr Pct] / Par 500 [Field Ref Pct] = 100%,
then Par 234 [Fld Current Pct] / Par 500 [Field Ref Pct] = Par 280
[Nom Mtr Fld Amps]
o If Par 467 [Max Fld Curr Pct] / Par 500 [Field Ref Pct] = 50%, then
Par 234 [Fld Current Pct] / Par 500 [Field Ref Pct] = 50% of Par
280 [Nom Mtr Fld Amps]
1. Reset the field current curve by setting Par 920 [Reset Fld Curve] to “1”.
4. Increase the motor speed until the value (electromotive force) displayed in Par
233 [Output Voltage] corresponds to the value previously set in Par 175 [Rated
Motor Volt].
5. Decrease the value of Par 467 [Max Fld Curr Pct] until the value displayed in
Par 233 [Output Voltage] is equal to 90% of Par 175 [Rated Motor Volt]. When
you have reached this value, read the value displayed in Par 234 [Fld Current
Pct] and enter the value into Par 918 [Fld Const 90 Pct].
6. Decrease the value of Par 467 [Max Fld Curr Pct] until the value displayed in
Par 233 [Output Voltage] is equal to 70% of Par 175 [Rated Motor Volt]. When
you have reached this value, read the value displayed in Par 234 [Fld Current
Pct] and enter the value into Par 917 [Fld Const 70 Pct].
7. Decrease the value of Par 467 [Max Fld Curr Pct] until the value displayed in
Par 233 [Output Voltage] is equal to 40% of Par 175 [Rated Motor Volt]. When
you have reached this value, read the value displayed in Par 234 [Fld Current
Pct] and enter the value into Par 916 [Fld Const 40 Pct].
9. Set the desired method of field control in Par 469 [Field Mode Sel] (0 “Base
Speed” or 1 “Field Weaken”)
10. Reset the value of 467 [Max Fld Curr Pct] to 100%.
If you change the value of Par 175 [Rated Motor Volt] or par 280 [Nom Mtr
Fld Amps], the field current curve will need to be re-tuned.
Diagram Conventions
Examples:
PXXX
ParName
PXXX
ParName
BASIC CONFIGURATION
P45 P162
PowerFlex DC Drive Overview Max Ref Speed Max Feedback Spd
P175 P179
Rated Motor Volt Nom Mtr Arm Amps
P280 P374
Nom Mtr Fld Amps Drv Fld Brdg Cur
P2 P414
Maximum Speed Fdbk Device Type
P660 P662
Drive Reference, Feedback and Status Accel Time 1 Decel Time 1
Control Block Diagrams
P199
Arm Current Pct
Reference Ramp Speed / Current Regulator
P924
Select Actual Speed
P110 P113 P118 Speed Regulator Current Regulator
Analog In 1-3 Ramp In Ramp Out Speed Reg In
Reference
DPI Port 1-5 Motor Control
Generation P122
MOP
Spd Feedback
Speed Feedback
Digital Inputs Status
Terminal Block 2 Terminal Block 4 Expansion I/O P41
Current Reg In
P565 P569 P573
Dig In Term 1 Dig In Term 5 Dig In Term 9
P351
Field Current
P500
Field Ref Pct
P567 P571 P575
Dig In Term 3 Dig In Term 7 Dig In Term 11
DG2- P1269 28
14 P147 Inversion out 3
D03
* P1278 75 30
DG3+ P629 P1275 F
Inversion In 3 Digital Out3 Sel
P135 Relay Out 2 Sel Inversion Relay 2
R2NO +24V DC
F 76
16 Digital In3 Sel F
R2COM
P1270 29
DG3-
P148 Inversion out 4
15 D04
P1279 F 30
DG4+ * Digital Out4 Sel
Inversion In 4
P136 +24V DC
F
16 Digital In4 Sel
DG4-
Digital Inputs/Outputs & Mapping Standard and I/O Expansion Card
2 type P1043 D
- Anlg In1 Cmp Err P67 A AO2
Ref_1- Window comparator Anlg Out2 Sel C 24
P72 P792 2
Anlg In1 Scale Anlg In1 Filter ACOM
P1404
Analog In1 Value P63
P1042 Anlg Out2 Scale
P74 Anlg In1 Cmp
Anlg In1 Offset
Expansion Analog Outputs (Optional)
D 1
P1045
P68 A AO3
Anlg In1 Cmp Eq
Anlg Out3 Sel C 2
Analog Inputs/Outputs and Mapping
1
ACOM
+V
Speed Reference Selection
MOP Reset
P70 (digital input)
Terminal Block
Anlg In1 Sel
Digital Inputs
P75 (”0” if not defined) MOP Inc Reset
Anlg In2 Sel (digital input) INC
P80 MOP
Anlg In3 Sel MOP Dec DEC
(digital input)
Speed Sel 3
Speed Sel 2
Speed Sel 1
P1323
DPI P1 Select P47 P1375
P2 OUT MOP Select
Speed Ref A Pct MAX
P1324 P44 000 Maximum Speed
DPI P2 Select Speed Ref A
P1
P1325 P48 001 MIN
Minimum Speed
DPI P3 Select Speed Ref B Auto / Manual
P1326 P49 (Par 381 Drive Status 1, b15) ACCEL DECEL
P155 010
DPI P4 Select Speed Ref B Pct
Preset Speed 2
b15
P1327 P156 011 P22 P30
DPI P5 Select Preset Speed 3 Auto (0) MOP Accel Time MOP Decel Time
Speed Reference Selection
Preset Speed 7
Off
Manual Source
P70 (Par 381 Drive Status 1, b12-14)
Anlg In1 Sel
b14
b13
b12
P75 P6
Anlg In2 Sel Min Speed Rev
P267 000
P80 TB Manual Ref
Anlg In3 Sel 001
DPI Port 1 Reference
P1375
MOP Select 010
DPI Port 2 Reference Manual (1) P384
Spd Ref Out Pct
011 P385 To Speed Reference
DPI Port 3 Reference
Spd Ref Out
Generation Diagram
DPI Port 4 Reference 100
P70
Anlg In1 Sel
On
P75 P266
Anlg In2 Sel Jog Speed
P80
Anlg In3 Sel
Control Block Diagrams
DPI P3 Select
P1326
DPI P4 Select
P345 P344
Zero Ramp Input Zero Ramp Output Speed ratio To Speed
/ Current
10000 Overview
Off
Ramp Reference Block
0 t
Ramp Reference
P20 P114
P111 P373
Ramp In Pct Ramp Delay Ramp Out Pct
Freeze Ramp
P110 P113
Ramp In T Ramp Out
Freeze Ramp
Ramp Reference Block
P662 S-Shape
Decel Time 1
P32
Decel Time 2
P19
S Curve Time
P665
S Curve Accel 1
P667
S Curve Accel 2
P666
S Curve Decel 1
P668
S Curve Decel 2
Control Block Diagrams
P698 +
Load Comp -
P41 P696
Current Reg In Droop Percent
P2 Inertia/loss
Maximum Speed P117
P3 Speed Reg In Pct
Max Speed Fwd P118
From Speed Reference Speed Reg In
Generation Diagram P4
Max Speed Rev
P1019 Speed Reg P/I P242 P353
Spd Draw Out Pct + + Speed Reg En Zero Torque
P1018
+ + P236
+ +
Σ Σ Σ Σ To Current Regulator
Speed Draw Out Spd Reg Out Pct T T Block Diagram
+ + +
Speed / Torque Regulator
P6
P70 Min Speed Rev
Anlg In1 Sel P99 P40 Zero Torque
P698 P697
Load Comp Droop Filter P700
Droop Limit
P699
+ Enable Droop
P41 To Trim Speed
Current Reg In Σ
+ T Reference Sum
Low Pass Filter
P696
Droop Percent Zero
Droop Compensation - Inertia / Loss Compensation
Speed
P1012
Inertia C Filter
P1015
Friction
P1016
1 SpdFuncSelect
n
P118
Speed Reg In +
T
P1013
d Torque Const
Low Pass Filter To Speed Regulator
Ouput Sum
Control Block Diagrams
P1014 P500
Inertia Field Ref Pct
Speed Feedback
P458
SpdReg FB Bypass
P414 = 3
P233
Fdbk Device Type
A Output Voltage
Speed Feedback Loss Motor
H
CEMF
Armature
Speed Feedback
P175
Rated Motor Volt
P1408
Tachometer Speed
DC Tachometer
Spd Fdbk Error P121
Spd Feedback Pct
Speed P122
P420 Spd Feedback
Encoder Speed
A+ P651
Encoder State
A- P421
PD Output PID
P414 = 1
B+ Fdbk Device Type
B-
Encoder
Speed Z+
P169
Digital Encoder
+V
P457
Spd Fdbk Control P911
Z Channel Enable
Speed Regulator PI Block
Speed P / I Base
P93 P459
Spd Reg Kp Base SpdReg Kp Bypass Bypass gains are used when P458 [SpdReg FB Bypass] = “Enabled” (1)
and the Encoder or Tachometer signal is lost, causing Armature Voltage
P94 P460 Feedback to be used.
Spd Reg Ki Base SpdReg Ki Bypass
P444
P181 Spd Fdbk Filter
Adaptive Spd En Anti-Windup
P87 P99 Torque Current Limits
Spd Reg Kp F Spd Reg Kp Out
Speed Regulator PI Block
P188
Adaptive P Gain1
P190
Adaptive P Gain2
P192
Adaptive P Gain3
+
+ P236
P118 Anti-Windup Σ
Spd Reg In Σ Spd Reg Out Pct
+ +
P183
Adaptive Ref Speed Adaptive P122
Spd Feedback P348
and Lock Speed Integ
P117 Speed Zero Logic
Spd Reg In Pct
T
P181
Adaptive Spd En
P88 P100 Zero
Spd Reg Ki F Spd Reg Ki Out
P189
Adaptive I Gain1
P191
Adaptive I Gain1
P193
Adaptive I Gain3
Control Block Diagrams
P182
Adaptive Reg Typ
Gain
Control Block Diagrams
P188 P189
Adaptive P Gain1 Adaptive I Gain1
P190 P191
Adaptive P Gain2 Adaptive I Gain2
P192 P193
Speed Adaptive and Speed Zero Logic
P184 P185
Speed Zero Logic Adaptive Spd 1 Adaptive Spd 2
P126 P125
Spd Zero P Gain Spd Zero P En
P106 T
Ref Zero Level >= Lock speed I
P124
&
Ref 0 level Spd Ref Zero En
Ramp Ref / Speed Ref
& T
>=
P123
Spd Zero I En Lock speed I
&
>
&
T =
Speed Zero
Speed
0 t
P108
Speed Zero Delay
Current Regulator
Current Limits
P7 P453
Current Limit Arm Resistance
Go to Motor
P454
P8 P10 Arm Inductance Parameters
Current Lim Pos Cur Lim Pos Out
P / I Regulator Modulator
P41
+ DC
From Speed / Torque Regulator Σ
Current Reg In Motor
-
Current Regulator
P9 P11
Current Lim Neg Cur Lim Neg Out P/I Regulator Includes
Feedback
Anti-Windup Logic P233 (Option)
Output Voltage
P715
Torq Limit Type
P199
P13
Arm Current Pct
T Torq Red CurLim P200
Arm Current
Torque
P342
Reduction
Torque Reduction
Torque Reduction
T Command
To rq ue To rq ue
Fwd Brdg Cur Lim Fwd Brdg Cur Lim
Fwd Brdg Cur Lim
Rev Brdg Cur Lim
Speed Speed
Out Volt Level Max Fld Curr Pct Max Field Output V oltage
Curr
Min Field
Voltage Regulator Curr
+ T
P175
Rated Motor Volt
Σ
_ P469
Field Mode Sel
P233 P498
Output Voltage Force Min Field
Field Current Regulator
P468
Min Fld Curr Pct
P499
Fld Economy En
P374
Drv Fld Brdg Cur
P919 P916
Set Fld Curve Fld Const 40 Pct
P234
P920 P917 Fld Current Pct C1
Reset Fld Curve Fld Const 70 Pct
M
P918 D1
Fld Const 90 Pct
P280
Nom Mtr Fld Amps
Motor Parameters
Output
Voltage / Constant Torque Field Regulator
Torque Management
P175 P469
Rated Motor Volt Field Mode Sel
P374
Constant Power Drv Fld Brdg Cur
P468
Min Fld Curr Pct
P467
Max Fld Curr Pct
g
Motor Parameters
sin r
Ri owe
P
Speed
P456 P162
Fld Weaken Ratio Max Feedback Spd
P45
Max Ref Speed
P453 P454
Arm Resistance Arm Inductance P280
Nom Mtr Fld Amps
A C1
(A1)
P351
P199 Field Current
Arm Current Pct
P200
P233 Arm Current
Output Voltage M
P587
I Reg Error
Control Block Diagrams
H
(A2) D1
P101
Speed Thresh Pos
P122
Spd Feedback
[Digital Outx Sel]
Control Block Diagrams
= 2 “Spd Thresh”
P393
Speed Threshold
P102
Speed Thresh Neg
Speed Threshold / Speed Control
P118
Speed Reg In P104
At Speed Error
P122
Spd Feedback P394
At Speed
P105 0 t
At Speed Delay
P758 PID Control
Feed Fwd PID
Gain
P731 P773
PID Steady Delay PID Output Scale
P786
PID Source Thr
Steady P782
Gain
P787 PID Target
State
PID Source Gain
P765
PI Prop Gain PID
P793
PI Init Prop Gn
P418
Thr 2 sign PID Real FF PID
PID Control
P785 P774
PI Lower Limit
PID Output
P771
P1046 PI Output
PID Accel Time P776
PI Central v1
P764 P777
PI Integral Gain PI Central v2
P734 P783
P1047 PI Init Intgl Gn PI integr freeze
PID Decel Time P779
PI Central v sel
P800 P794
Diameter Calc St Diameter Calc
T
P778
P763 PI Central v3
PID Feedback
P768 P770
+ PD Prop Gain 1 Enable PD
+ P788 P799
Σ PD Prop Gain 2 T + Minimum Diameter
ON
P790 P797
PD Prop Gain 3 Gear Box Ratio
P763
PID Feedback
P757 P771
PID Clamp P414 Diameter PI Output
Fdbk Device Type Calculator
P795
P759 DncrPosSpd
PID Error P766
PD Deriv Gain 1 P796
P789 P767 Encoder 1 Position Max Deviation
PD Deriv Gain 2 PD Deriv Filter
Control Block Diagrams
P791 P798
PD Deriv Gain 3 Dancer Constant
Scale Blocks
Scale Block 1
P488
Scale1 In Max
Control Block Diagrams
P484
+ + P485
Scale1 Input Σ X Σ Scale1 Output
+ +
Scale Blocks
P491
P489 Scale1 Out Off
Scale1 In Min
P492 P486 P487
Scale1 In Abs Scale1 Mul Scale1 Div
P553
+ + P554
Scale2 Input Σ X Σ Scale2 Output
+ +
P560
P558 Scale2 Out Off
Scale2 In Min
P561 P555 P556
Scale2 In Abs Scale2 Mul Scale2 Div
P559
Scale2 In Off
Note: Up to six scale blocks are available. Scale blocks 3-6 follow the same flow as scale blocks 1 and 2, shown here.
User Defined Parameters
User Defined Variables
output
input
output
Analog
Analog
Analog
input
input
Digital
Analog
General Parameters
P751
TrqTpr_Lim0
Taper Current Limits
P753
TrqTpr_Lim2
P754
TrqTpr_Lim3
P755
TrqTpr_Lim4
Test Generator
Test Generator
P58
TstGen Output
Generator
output
P60
TstGen Amplitude
P61
TstGen Offset
Time
P59
TstGen Frequency
0 0 0 P44
Speed Ref A
0 0 1 P48
Speed Ref B
0 1 0 P155
Preset Speed 2
0 1 1 P156
Preset Speed 3
P157
1 0 0 Preset Speed 4
1 0 1 P158
Preset Speed 5
1 1 0 P159
Preset Speed 6
1 1 1 P160
Preset Speed 7
Fault/Alarm Mapping
Communication Adapter The following Communication Adapter kits are available for use with the
Kits PowerFlex® DC drive:
Comm Option Catalog Number
BACnet® MS/TP RS-485 Communication Adapter 20-COMM-B
ControlNet™ Communication Adapter (Coax) 20-COMM-C
DeviceNet™ Communication Adapter 20-COMM-D
EtherNet/IP™ Communication Adapter 20-COMM-E
HVAC Communication Adapter 20-COMM-H
Interbus™ Communication Adapter 20-COMM-I
PROFIBUS™ DP Communication Adapter 20-COMM-P
ControlNet™ Communication Adapter (Fiber) 20-COMM-Q
Remote I/O Communication Adapter 20-COMM-R
RS-485 DF1 Communication Adapter 20-COMM-S
External Comms Power Supply 20-XCOMMAC-PS1
DPI External Communications Kit 20-XCOMMDC-BASE
External DPI I/O Option Board(1) 20-XCOMMIO-OPT1
Compact I/O to DPI/SCANport Module 1769-SM1
Serial Null Modem Adapter 1203-SNM
Smart Self-powered Serial Converter (RS-232) 1203-SSS
includes 1203-SFC and 1202-C10 Cables
Universal Serial Bus™ (USB) Converter 1203-USB
includes 2m USB, 20-HIM-H10 & 22-HIM-H10 Cables
(1) For use only with External DPI Communications Kits 20-XCOMM-DC-BASE.
Safety Precautions
ATTENTION: Only qualified personnel familiar with drives,
! power products and associated machinery should plan or
implement the installation, start-up, configuration and
subsequent maintenance of the system. Failure to comply may
result in personal injury and/or equipment damage.
ATTENTION: To avoid an electric shock hazard, ensure that all
! power to the drive has been removed before performing the
following.
ATTENTION: This drive contains ESD (Electrostatic
! Discharge) sensitive parts and assemblies. Static control
precautions are required when installing, testing, servicing or
repairing this assembly. Component damage may result if ESD
control procedures are not followed. If you are not familiar with
static control procedures, reference A-B publication 8000-4.5.2,
“Guarding Against Electrostatic Damage” or any other
applicable ESD protection handbook.
L1 L2 L3
I
a. On frame A drives, remove the screws that secure the bottom cover to
the drive, then slide the cover down and off the drive chassis.
Frame A
=
PORT
MOD
NET A
NET B
STS
b. On frame B and C drives, loosen, but do not remove, the screws that
secure the bottom cover to the drive, then slide the cover down and off
the drive chassis.
a. For frame A drives, press in on the sides at the bottom edge of the top
cover and at the same time pull the cover toward you to pull it
partially off the drive chassis. Next, at the top of the drive, pull the
cover forward, away from the drive, until the pins fit in the keyhole in
the top of the cover, then carefully lift the cover off of the drive
chassis.
=
PORT
MOD
NET A
NET B
STS
b. On frame B and C drives, loosen, but do not remove, the screws that
secure the top cover to the drive, then slide the cover up and off the
drive chassis.
U C V D W
Secure adapter to
EMI Shield with
four (4) screws.
Connect cable to
DPI connectors
on adapter and
control board.
Notes:
What This Option Board The optional I/O Expansion circuit board(1) is mounted on the Control
Provides board of the drive and provides these additional I/O signals:
I/O Expansion Board I/O Expansion Board Control Board Standard Drive I/O
Terminal Blocks Terminal Blocks
I/O Expansion Board Wiring Table F.A Recommended Signal Wire Size
Wire Type and Size Tightening Torque
Flexible (mm2) multi-core (mm2) AWG N•m (lb•in)
0.14 - 1.5 0.14 - 1.5 28-16 0.4 (3.5)
(1) The Analog and Digital I/O Expansion circuit board is not factory installed.
Control Board
I/O Expansion Board
+ 24 V
0 V 24
3 4 5 6 7 8 9 10 11 12
Supply
19 18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
+ 24 V
0V
What This Option Board The 115V AC to 24V DC I/O Converter circuit board(1) allows you to
Provides convert 115V AC digital input signals to 24V DC digital input signals in
order to interface with the standard digital I/O terminal blocks on the
PowerFlex DC drive Control board.
• Eight (8) interface outputs for the digital inputs on Control board of the
drive(2)
• Two (2) input terminals for the 24V DC power supply voltage
Figure G.1 115V AC to 24V DC I/O Converter Circuit Board Mounting Location
(1)
The 115V AC to 24V DC I/O Converter circuit board is not factory installed.
(2) If more than eight 115V AC digital input signals require conversion to 24V DC (i.e., the optional PowerFlex DC
drive I/O Expansion circuit board is used - see Appendix F), a second Converter board is required and must be
sourced and wired independently from the 115V AC to 24V DC I/O Converter board mounted on the Control
board and be mounted in an appropriate enclosure external to the PowerFlex DC drive enclosure.
I/O Converter Board Wiring Table G.A Recommended Signal Wire Size
Wire Type and Size Tightening Torque
Flexible (mm2) multi-core (mm2) AWG N•m (lb•in)
0.14 - 1.5 0.14 - 1.5 28-16 0.4 (3.5)
Figure G.2 I/O Converter Board with Internal Supply Wiring Diagram
15k 15k
DC OUTPUT AC INPUT
24V 1 2 3 4 5 6 7 8 0V 1 2 3 4 5 6 7 8 COM
M_OUT M_IN
To Digital Inputs
(Terminals 12-15, 31-34)
on Control Board
Figure G.3 I/O Converter Board with External Supply Wiring Diagram
Main Control Board
OPTO OPTO
15k 15k
DC OUTPUT AC INPUT
24V 1 2 3 4 5 6 7 8 0V 1 2 3 4 5 6 7 8 COM
M_OUT M_IN
To Digital
From Input Common To External External 115V AC
External (Terminal 16 or 35) 24V DC
+24V DC Supply
Supply Internal Wiring Common Customer Wiring
Notes:
Masks & Owners Group 3-2, 3-58, 3-59 Option Definitions, Digital Outputs 3-69
Wiring 1-1
2-Wire Control Non-Reversing 1-38
2-Wire Control Reversing 1-39
3-Wire Control 1-39
Analog Input Bipolar Speed Reference
1-38
Analog Input Unipolar Speed Reference
1-38
Analog Output Bipolar Signal 1-38
Enable Input 1-38
Encoder 1-41
Joystick 1-37
Potentiometer 1-37
Sourcing Digital Output 1-39
Write Mask Act 3-61
Write Mask Cfg 3-61
Z
Z Capture Pos En 3-20
Z Captured Pos 3-20
Z Channel Enable 3-20
Zero Ramp Input 3-30
Zero Ramp Output 3-30
Zero Torque 3-17
www.rockwellautomation.com