Aerial Bundle Conductor Self support Application:

Phase core(s) aluminium HD, XLPE insulation + For use in power circuits of 600 / 1 000V. installed in air suspended by all phase +
aluminium HD, XLPE insulated neutral neutral cores.
Voltage Rating: 600 / 1 000V Specification: SANS 1418
1 Phase core + aluminium insulated neutral AS1x(conductor size)+(conductor size)NSS
Short

Impedance
Reactance
Maximum Resistance
Insulated Gross Current Single Three
Conductor Conductor Insulation Cable Cable pull force circuit
Phase Aluminium Mass rating Phase Phase
size diameter diameter diameter mass on Cores dc @ ac @ ratings
Cores / Neutral Volt Drop Volt Drop
500m combined In air 20°C 90°C Symmetrical
Cable
mm² mm mm mm kg/m kg Ω/km Ω/km
mm² nom kN Amps Ω/km Ω/km kA (1sec) A/m/(mV)
nom nom Nom. Nom. Nom. Nom. max max
1x25 25 6.0 9.4 25 20 0.20 252 2.48 105 1.200 1.535 0.091 1.541 2.3 3.07
1x35 35 7.1 10.9 35 24 0.28 292 3.38 144 0.868 1.113 0.090 1.117 3.2 2.23
1x50 50 8.2 12.0 50 26 0.36 329 4.65 183 0.641 0.822 0.084 0.826 4.6 1.64
1x70 70 9.8 14.2 70 31 0.59 445 6.68 228 0.443 0.568 0.083 0.574 6.4 1.14
1x95 95 11.8 16.0 95 35 0.67 484 9.23 277 0.320 0.411 0.080 0.419 8.7 0.82
1x120 120 13.1 17.5 120 38 0.74 522 11.70 322 0.253 0.325 0.078 0.334 11.0 0.65
1x150 150 14.8 18.6 150 45 0.97 686 14.40 340 0.206 0.265 0.077 0.276 12.7 0.53

3 Phase cores + aluminium insulated neutral


AS3x(conductor size)+(conductor size)NSS
Short

Impedance
Reactance
Maximum Resistance
Insulated Gross Current Single Three
Conductor Conductor Insulation Cable Cable pull force circuit
Phase Aluminium Mass rating Phase Phase
size diameter diameter diameter mass on Cores dc @ ac @ ratings
Cores / Neutral Volt Drop Volt Drop
500m combined In air 20°C 90°C Symmetrical
Cable
mm² mm mm mm kg/m kg Ω/km Ω/km
mm² nom kN Amps Ω/km Ω/km kA (1sec) A/m/(mV)
nom nom Nom. Nom. Nom. Nom. max max
3x25 25 6.0 9.4 25 23 0.41 314 3.30 105 1.200 1.535 0.091 1.541 2.3 2.66
3x35 35 7.1 10.9 35 26 0.56 429 4.50 144 0.868 1.113 0.090 1.117 3.2 1.93
3x50 50 8.2 12.0 50 29 0.72 510 6.20 183 0.641 0.822 0.084 0.826 4.6 0.14
3x70 70 9.8 14.2 70 34 1.01 732 8.90 228 0.443 0.568 0.083 0.574 6.4 0.98
3x95 95 11.8 16.0 95 39 1.33 867 12.30 277 0.320 0.411 0.080 0.419 8.7 0.71
3x120 120 13.1 17.5 120 42 1.64 1088 15.60 322 0.253 0.325 0.078 0.334 11.0 0.44
3x150 150 14.8 18.6 150 45 1.95 1239 19.20 340 0.206 0.265 0.077 0.276 12.7 0.46
If 25mm² Street light is required. (code)+25A
Conductor diameter mm app. 6.3
Insulation diameter mm app. 9.4
Additional Cable mass kg/m app. 0.10
The information contained within this document must not be copied, reprinted or reproduced in any form, either wholly or in part, without the written
consent of M-TEC, The information is believed to be correct at the time of issue to the best of M-TEC’s knowledge. M-TEC reserves the right to
amend this specification without prior notification. This specification is not contractually valid unless specifically authorised by M-TEC. M-TEC shall
not be liable for any damages whatsoever (including indirect, incidental, special, punitive or consequential damages and loss of profits,
opportunities or information) arising from or result from the use of or reliance on information contained in this document, and/or any inaccuracy or
omission in such information contained in this document.

Revision: R06 19/01/2022