Functional Logic Diagram for WIP P-151001

This functional logic diagram shows the inputs, logic functions, and outputs for the water injection pump P-151001. It includes sensors for lube oil temperature, pressure, tank level, and filter differential pressure that provide input signals. Logic functions like AND, OR, greater/less than, and timers control outputs like trip signals, cooler fan running feedback, and alarms. The diagram legends define the symbols and transfer of signals to other sheets.

Uploaded by

SAPSHome
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
331 views34 pages

Functional Logic Diagram for WIP P-151001

This functional logic diagram shows the inputs, logic functions, and outputs for the water injection pump P-151001. It includes sensors for lube oil temperature, pressure, tank level, and filter differential pressure that provide input signals. Logic functions like AND, OR, greater/less than, and timers control outputs like trip signals, cooler fan running feedback, and alarms. The diagram legends define the symbols and transfer of signals to other sheets.

Uploaded by

SAPSHome
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

FUNCTIONAL LOGIC DIAGRAM

WATER INJECTION PUMP (P-151001)

.
FUNCTIONAL LOGIC DIAGRAM

LEGENDS

TRANSFER
INDICATOR OF
13-LAL- 13-LAL- DCS ALARM
SIGNALS TO
AND LOGIC 10022 10022
& ANOTHER
FUNCTION SHEET 13-LAL-10022
SHEET :001 SHEET :008

t1____0
ON DELAY
TIMER
HW 13-LT-10022 H> PHYSICAL
t = xx sec
OR LOGIC A TMRxx
I Diff level INPUT
FUNCTION IPS Transmitter

PULSE TIMER
T= xx sec

START 13-PMST-10022 V HW PHYSICAL


LESS THAN OR Diff level OUTPUT-
Transmitter W MCC Equipment
<= EQUAL TO
LOGIC
FUNCTION

13-KMXZ-13103 SL
S
O
OUTPUT
TRIP LO/WO F
COOLER FAN K- SERIAL LINK
GREATER T
THAN OR 13103 MOTOR IPS
>= EQUAL TO
LOGIC
FUNCTION
SL S 13-EMRN-10031C
O INPUT
F LO/WO COOLER FAN SERIAL LINK
IPS T RUNNING FB
S c
FCS TAGS IPS TAGS
RS RS FLIP FLOP NORMAL = 0 NORMAL = 1
LOGIC Note-1 ALARM = 0
ALARM = 1
R1 FUNCTION
d
SHEET NO :00

_
INPUT OUTPUT
FCS/FIELD
FCS LUBE OIL SYSTEM ANALOG INPUTS FOR WIP – P-151001 ALARM FIELD

15-TAH- 15-TAH-
HW 15-TT-10046 H 10046 10046 Refer Note 1
A 27 OC 15-TAH-10046
I P-151001 LUBE OIL SHEET :010 SHEET :015
FCS TEMPERATURE L
20 OC 15-TAL- 15-TAL-
10046 10046
15-TAL-10046
SHEET :010 SHEET :015
SHEET :027
HW 15-PT-100181
A
I P-151001 LUBE OIL
FCS PRESS BEFORE L 120 kPag 15-PAL-10181
COOLER

15-PAH- 15-PAH-
HW 15-PT-10182 H 10182 10182
A 220 kPag 15-PAH-10182
I P-151001 LUBE OIL SHEET :010 SHEET :013
FCS OUTLET PRESSURE L
120 kPag 15-PAL- 15-PAL-
10182 10182
15-PAL-10182
SHEET :010 SHEET :013
SHEET :027
HW 15-LT-10069 SHEET: 028
H
A 67.1 %
I P-151001 LUBE OIL 15-LAH-10069
FCS TANK LEVEL L
41.6 % 15-LAL- 15-LAL-
10069 10069
15-LAL-10069
SHEET :010 SHEET :013
SHEET :015
HW 15-PDT-10188 H
A
I P-151001 L.O.
FCS FILTER DIFF. PRESS 150 kPa 15-PDAH-10188

HW 13-TT-10045 H
A 80 OC
P-151001 LUBE OIL 15-TAH-10045
I
FCS TEMP AFTER L
COOLER 43 OC

15-TAL-10045
Note-1 FCS TAGS
NORMAL = 0 SHEET NO :010
ALARM = 1
INPUT OUTPUT
FCS/FIELD
FCS SEAL SYSTEM ANALOG INPUTS FOR WIP – P-151001 ALARM FIELD

HW 15-PT-100183 4500 kPag 15-PAH- 15-PAH- Refer Note 1


H 10183 10183
A 15-PAH-10183
I P-151001 SEAL SHEET :011 SHEET :018
FCS SYSTEM PRESS L
(NDE SEAL) 3100 kPag 15-PAL- 15-PAL-
10183 10183
15-PAL-10183
SHEET :011 SHEET :021
SHEET :022,029

4500 kPag 15-PAH- 15-PAH-


HW 15-PT-10184
H 10184 10184
A 15-PAH-10184
I P-151001 SEAL SHEET :011 SHEET :018
FCS SYSTEM PRESS (DE L
SEAL) 3100 kPag 15-PAL- 15-PAL-
10184 10184
15-PAL-10184
SHEET :011 SHEET :021
SHEET :022,029
HW 15-LT-10068 70.5 %
H
A
I P-151001 SEAL 15-LAH-10068
SYSTEM TANK L
FCS LEVEL 15-LAL- 15-LAL-
12.5 %
10068 10068
15-LAL-10068
SHEET :011 SHEET :013
SHEET :015
HW 15-TT-10044 H 70 OC
A
I P-151001 SEAL
SYSTEM TEMP (DE
FCS SEAL) 15-TAH-10044

HW 15-TT-10043 70 OC
H
A
15-TAH-10043
I P-151001 SEAL
SYSTEM TEMP
FCS (NDE SEAL)

Note-1 FCS TAGS


NORMAL = 0
ALARM = 1 SHEET NO :011
INPUT OUTPUT
FCS/FIELD
LUBE OIL PUMP P-151003 ALARM FIELD

HW 15-PMRN-1003
D
LO PUMP RUNNING RUNNING =1
FCS I FB NOT RUNNING =0

&
HW 15-PMAV-1003
D
LO PUMP AVAIABLE AVAILABLE=1
I
FCS FB
NOT AVAILABLE =0 START 15-PMST-1003 V HW
& S c P151003
LO PUMP START W MCC
RS
R1
SK S 15-HS-10267 d STOP 15-PMSP-1003 V HW
A P151003
O
F AUTO /MANUAL AUTO=1 LO PUMP STOP W MCC
FCS
SELECTION FROM M
T GRAPHICS MANUAL =0

t=1sec
&

SK S 15-HS-10268
O
F MANUAL START
FCS T FROM GRAPHICS ST

SK S 15-HS-10269
O 1
&
F MANUAL STOP
SP t=1sec
FCS T FROM GRAPHICS

AUTO AUTO
START START INTER INTER SHEET NO :012
SHEET :012 LOCK LOCK
SHEET :013
SHEET :013 SHEET :012
INPUT OUTPUT
FCS/FIELD
AUX LO PUMP P-151003 ALARM FIELD

t1____0
15-PAL- 15-PAL-
10182 10182
t = 15 sec
HW 15-PMRN-1003 SHEET :010 SHEET :013 TMR28
D
& AUTO AUTO
LO PUMP RUNNING RUNNING =1 START START
I
FCS FB NOT RUNNING =0
SHEET :013 SHEET :012
Ref note 1

15-LAL- 15-LAL- &


10069 10069

SHEET :010 SHEET :013

ST_SEQ ST_SEQ
ST-1 ST-21 SP_SEQ SP_SEQ
SHEET :027 SHEET :013 ST-1 ST-1
SHEET :035 SHEET: 013

15-PAH- 13-PAH-
10182 10182 INTER INTER
LOCK LOCK
SHEET :010 SHEET :013
SHEET :013 SHEET :012

SP_SEQ SP_SEQ
ST-4 ST-4
SHEET :036 SHEET: 013

TRP SEQ TRP SEQ


ST-3 ST-3
SHEET :040 SHEET: 013

ST_SEQ ST_ SEQ


ST-8 ST-8
Note 1: During running,
Pressure Low due to leak in the SHEET :032 SHEET: 013 SHEET NO :013
LO system ,LO pump restart
INPUT OUTPUT
FCS/FIELD
L.O HEATER E-151017 ALARM FIELD

HW 15-EMRN-10017
D
LO HEATER RUNNING =1
FCS I RUNNING FB NOT RUNNING =0

&
15-EMAV-10017
HW D
LO HEATER AVAILABLE=1
FCS I AVAILABLE FB
NOT AVAILABLE =0 HW
START 15-EMST-10017 V
& S c
LO HEATER
START W MCC
RS
R1
HW
SK S 15-HS-10273 d STOP 15-EMSP-10017 V
A
O LO HEATER
F AUTO /MANUAL AUTO=1 STOP W MCC
FCS
SELECTION FROM M
T GRAPHICS MANUAL =0

t=1sec

&
SK S 15-HS-10274
O
F MANUAL START
FCS T FROM GRAPHICS ST

HW 15-PMRN-1001
D
MAIN PUMP P-151001 RUNNING =1
FCS I RUNNING FB NOT RUNNING =0

SK S 15-HS-10275
O 1
&
F MANUAL STOP t=1sec
SP
FCS T FROM GRAPHICS

AUTO AUTO INTER INTER


START START LOCK LOCK
SHEET :015 SHEET :014 SHEET NO :014
SHEET :015 SHEET :014
INPUT OUTPUT
FCS/FIELD
L.O HEATER E-151017 ALARM FIELD

13-TAL- 13-TAL- AUTO AUTO


10064 10064 START START
SHEET :010 SHEET :015 SHEET :015 SHEET :014

15-LAL- 15-LAL-
10069 10069

SHEET :010 SHEET :015 &

ST_SEQ ST_SEQ
ST-1 ST-1
SHEET :021 SHEET :015

15-TAH- 15-TAH- INTER INTER


10046 10046 LOCK LOCK
SHEET :010 SHEET :015 SHEET :015 SHEET :014

15-LAL- 15-LAL-
10069 10069
SHEET :010 SHEET :015
t1____0
TRP SEQ TRP SEQ
END END t = 60 sec
SHEET :040 SHEET :015 TMR30

SHEET NO :015
INPUT OUTPUT
FCS/FIELD
LUBE OIL FAN COOLER E-151015 ALARM FIELD

HW 15-EMRN-1005
D
LO FAN COOLER RUNNING =1
FCS I RUNNING FB NOT RUNNING =0

&
HW 15-EMAV-1005
D
LO FAN COOLER AVAILABLE=1
I
FCS AVAILABLE FB
NOT AVAILABLE =0 HW
START 15-EMST-1005 V
S c
& LO FAN COOLER
START W MCC
SR
R1
d HW
SK S 15-HS-10270 STOP 15-EMSP-1005 V
A
O LO FAN COLLER
F AUTO /MANUAL AUTO=1 STOP W MCC
FCS
SELECTION FROM M
T GRAPHICS MANUAL =0

t=1sec
SK S 15-HS-10271
O &
F MANUAL START
FCS ST
T FROM GRAPHICS

HW 15-PMRN-1001
D
MAIN PUMP P-151001 RUNNING =1
I
FCS RUNNING FB NOT RUNNING =0

SK S 15-HS-10272 &
O 1
F MANUAL STOP t=1sec
SP
FCS T FROM GRAPHICS

AUTO AUTO
START START INTER INTER
SHEET :017 SHEET :016 LOCK LOCK
SHEET :017 SHEET :016 SHEET NO :016
INPUT OUTPUT
FCS/FIELD
LUBE OIL FAN COOLER E-151015 ALARM FIELD

ST_SEQ ST_SEQ AUTO


& AUTO
ST-5A ST-5A START START
SHEET :031 SHEET :017 SHEET :017 SHEET :016

SP_SEQ SP_SEQ
ST-4 ST-4 INTER INTER
SHEET :036 LOCK LOCK
SHEET: 017
SHEET :017 SHEET :016
TRP SEQ TRP SEQ
ST-3 ST-3
SHEET :040 SHEET: 017

ST_SEQ ST_ SEQ


ST-8 ST-8
SHEET :027 SHEET: 017

SHEET NO :017
INPUT OUTPUT
FCS/FIELD
SEAL SYSTEM PUMP – P151004/P151005 –DUTY / STANDBY SELECTION ALARM FIELD

SK S 15-HS-10262 P151004 P151004


O P151004/P151005 DUTY DUTY
F DUTY SELECTION
D
FCS T FROM GRAPHICS ST SHEET :018 SHEET :019

1 P151005 P151005
STANDBY STANDBY

SHEET :018 SHEET :020

SK S 15-HS-10262
O P151004 P151004
P151004/P151005
F STANDBY STANDBY
STANDY S
FCS T ST
SELECTION FROM
SHEET :018 SHEET :019
GRAPHICS

1 P151005 P151005
DUTY DUTY

SHEET :018 SHEET :020

13-PMAV-10005
HW D
P151004 AVAILABLE=1
FCS I
PUMP AVAIABLE NOT AVAILABLE =0 START START
& P151004 P151004
& STANDBY STANDBY
P151005 P151005
FAILED FAILED SHEET :018 SHEET :019
PRES PRES
SHEET :022 SHEET :018

13-PMAV-10004
HW D
P151005 AVAILABLE=1
FCS I
PUMP AVAIABLE NOT AVAILABLE =0 START START
& P151005 P151005
& STANDBY STANDBY
P151004 P151004
FAILED FAILED SHEET :018 SHEET :020
PRES PRES
SHEET :021 SHEET :018

SHEET NO :018
INPUT OUTPUT
FCS/FIELD
SEAL SYSTEM PUMP – P151004 ALARM FIELD

P151004 P151004
DUTY DUTY
HW 13-PMRN-10004
D SHEET :018 SHEET :019
RUNNING =1
FCS I PUMP RUNNING FB
NOT RUNNING =0
&
13-PMAV-10004
HW D

FCS I PUMP AVAIABLE FB AVAILABLE=1


NOT AVAILABLE =0 START 13-PMST-10004 V
S c
& MAIN PUMP HW
START W MCC
RS
R1
SK S 13-HS-10203 d STOP 13-PMSP-10004 V
A
O MAIN PUMP HW
F AUTO /MANUAL AUTO=1 STOP W MCC
FCS
SELECTION FROM M
T GRAPHICS MANUAL =0

START START
1
P151004 P151004
STANDBY STANDBY t=1sec

SHEET :018 SHEET :019 &

SK S 13-PMST-10004
O
F MANUAL START
FCS T FROM GRAPHICS ST

P151004 P151004 &


STANDBY STANDBY

SHEET :018 SHEET :019

SK S 13-PMSP-10004
O 1
&
F MANUAL STOP t=1sec
SP
FCS T FROM GRAPHICS

AUTO AUTO INTER INTER


START START LOCK LOCK
SHEET :021 SHEET :019 SHEET NO :019
SHEET :021 SHEET :019
INPUT OUTPUT
FCS/FIELD
SEAL SYSTEM PUMP – P151005 ALARM FIELD
STBY STBY
PUMP PUMP
HW 13-PMRN-10005
D SHEET :018 SHEET :020
PUMP RUNNING RUNNING =1
FCS I
FB NOT RUNNING =0

&
13-PMAV-10005
HW D

FCS I PUMP AVAIABLE AVAILABLE=1


NOT AVAILABLE =0 START 13-PMST-10005 V
S c
& STBY PUMP HW
START W MCC
RS
R1
SK S 13-HS-10205 d STOP 13-PMSP-10005 V
A
O AUTO /MANUAL STBY PUMP HW
F SELECTION STOP W MCC
M AUTO=1
FCS T FROM GRAPHICS MANUAL =0

START START
P151005 P151005 1
STANDBY STANDBY t=1sec
AND
SHEET :018 SHEET :020

SK S 13-PMST-10005
O
F MANUAL START
FCS T FROM GRAPHICS ST

P151005 P151005
&
STANDBY STANDBY

SHEET :018 SHEET :020


SK S 13-PMSP-10005
O & 1

F MANUAL STOP t=1sec


SP
FCS T FROM GRAPHICS
AUTO AUTO
START START
INTER INTER
SHEET :022 SHEET :020 LOCK LOCK SHEET NO :020
SHEET :022 SHEET :020
INPUT OUTPUT
FCS/FIELD
SEAL SYSTEM PUMP – P151004 – INTERLOCK ALARM FIELD

15-LAL- AUTO AUTO


15-LAL-
10068 START START
10068 &
SHEET :011 SHEET :021 SHEET :021 SHEET :019

ST_SEQ ST_SEQ
ST-3 ST-3
SHEET :028 SHEET :021

TRP SEQ TRP SEQ


15-PAH- 15-PAH- ST-3 ST-3
10083 10083
SHEET :040 SHEET: 021
SHEET :011 SHEET :021
INTER INTER
SP_SEQ SP_SEQ LOCK LOCK
15-PAH- 15-PAH- ST-4 ST-4
10084 SHEET :021 SHEET :019
10084 SHEET :036 SHEET: 021
SHEET :011 SHEET :021

15-LAL- 15-LAL-
10068 10068 .

SHEET :011 SHEET :021

15-PAL- 15-PAL-
10183 10183
SHEET :011 SHEET :021

15-PAL- 15-PAL- NOTE : 1


10184 10184
t1____0
SHEET :011 SHEET :021
t = 10sec ` P151004 P151004 P151004 FAIL TO BUILD
HW 13-PMRN-10004 & FAILED FAILED
D UP PRESSURE
PRES PRES
P151004 PUMP RUNNING =1 SHEET :021 SHEET :018
FCS I
RUNNING FB NOT RUNNING =0

NOTE 1 : TIME DURATION SHALL BE


DECIDED DURING COMMISSIONING
SHEET NO :021
INPUT OUTPUT
FCS/FIELD
SEAL SYSTEM PUMP – P151005– INTERLOCK ALARM FIELD

15-LAL- 15-LAL- AUTO AUTO


10068 10068 START START
&
SHEET :011 SHEET :022 SHEET :022 SHEET :020

ST_SEQ ST_SEQ
ST-3 ST-3
SHEET :028 SHEET :022

TRP SEQ TRP SEQ


15-PAH- 15-PAH- ST-3 ST-3
10083 10083
SHEET :040 SHEET: 022
SHEET :011 SHEET :022 INTER INTER
OR LOCK LOCK
SP_SEQ SP_SEQ
15-PAH- ST-4 ST-4 SHEET :022 SHEET :020
15-PAH-
10084 10084 SHEET :036 SHEET: 022
SHEET :011 SHEET :022
15-LAL- 15-LAL-
10068 10068
SHEET :011 SHEET :022

15-PAL- 15-PAL-
10183 10183
SHEET :011 SHEET :022 OR

15-PAL- 15-PAL-
NOTE : 1
10184 10184
t1____0
SHEET :011 SHEET :022 P151005 P151005 P151005 FAIL TO BUILD
HW 13-PMRN-10005 t = 10sec & FAILED FAILED UP PRESSURE
D
PRES PRES
P-151005 PUMP RUNNING =1
FCS I SHEET :022 SHEET :018
RUNNING FB NOT RUNNING =0

NOTE 1 : TIME DURATION SHALL BE


DECIDED DURING COMMISSIONING SHEET NO :022
INPUT OUTPUT
FCS/FIELD
SEAL SYSTEM COOLER FAN E-151016 ALARM FIELD

HW 15-EMRN-10016
D
RUNNING =1
FCS I RUNNING FB
NOT RUNNING =0

&
13-EMAV-10001
HW D

DCS I AVAIABLE FB AVAILABLE=1


NOT AVAILABLE =0 HW
START 15-EMST-10016 V
S c
& START
W MCC
RS
R1
HW
SK S 15-HS-10263 d STOP 13-EMSP-10016 V
A
O STOP
F AUTO /MANUAL AUTO=1
W MCC
FCS
SELECTION FROM M
T GRAPHICS MANUAL =0

t=1sec

&
SK S 15-EMST-10264
O
F MANUAL START
FCS T FROM GRAPHICS ST

HW 15-PMRN-1001
D
MAIN PUMP P-151001 RUNNING =1
FCS I RUNNING FB NOT RUNNING =0

SK S 15-EMSP-10265
1
O
&
F MANUAL STOP t=1sec
SP
FCS T FROM GRAPHICS

AUTO AUTO
START INTER INTER
START LOCK LOCK SHEET NO :023
SHEET :024 SHEET :023 SHEET :024 SHEET :023
INPUT OUTPUT
FCS/FIELD
SEAL SYSTEM COOLER FAN E-151016 ALARM FIELD

ST_SEQ ST_SEQ AUTO AUTO


ST-1 ST-1 START START
SHEET :027 SHEET :023 SHEET :024 SHEET :023

INTER INTER
LOCK LOCK
SHEET :024 SHEET :023
SP_SEQ SP_SEQ
ST-4 ST-4
SHEET :036 SHEET: 024

TRP SEQ TRP SEQ


ST-3 ST-3
SHEET :040 SHEET: 024

SHEET NO :024
INPUT OUTPUT
IPS/FCS / FIELD
STARTUP PERMISSIVE WI PUMP P-151001 CONTROL LOGIC ALARM FIELD

15-FCS-DS-IPS-003
RESET RESET ON S SL
15-HS-10004 O
SEQ SEQ F
SEQUENCE REST T
SHEET :025 ` SH-025 TO SH -003
SHEET :026 IPS

STARUP PERMISSIVE CONDITION

1
S c STARTUP STARTUP
t=2sec PERM PERM
RS
SHEET :025 SHEET :026
R1
SL S 15-IPS-DS-FCS-003 d
O HW 15-PMAV-1003
D
F 15-PMXZ-1001 TRIP
IPS T SH-004 TO SH -025 I
LO PUMP AVAIABLE
FCS FB

15-EMAV-10017
SL S 15-IPS-DS-FCS-004 HW D
O 15-GBSC-10002
LO HEATER
F CLOSE FB FCS I AVAILABLE FB
IPS T SH-005 TO SH -025

HW 15-EMAV-1005
SL S 15-IPS-DS-FCS-005 D
O 15-GBSC-10001 LO FAN COOLER
F CLOSE FB I
FCS AVAILABLE FB
IPS T SH-005 TO SH -025 & &
13-EMAV-10001
HW 15-PMAV-1001 HW D
D
SEAL COOLER FAN
MAIN PUMP DCS I AVAIABLE FB
FCS I AVAILABLE FB

13-PMAV-10004 S 15-IPS-DS-FCS-005
HW D SL
O
SEAL PUMP 151004 F 15-PZI-10003
FCS I IPS
AVAIABLE FB T SUCTION PRESSURE

13-PMAV-10005
HW D
SEAL PUMP 151005
FCS I AVAIABLE FB SHEET NO :025
INPUT OUTPUT
FCS / FIELD
START SEQUENCE – WI PUMP P-151001 ALARM FIELD

START SEQUENCE FROM GRAPHICS`

SK S 15-HS-10006
O START
F START SEQ FROM SEQ
FCS T GRAPHICS ST
START SEQ
SK S 15-ABORT-10006
O ABORT ABORT
F ABORT SEQ FROM
SP
FCS T GRAPHICS ABORT ABORT SHEET :026 SHEET :027,028,029,030, ABORT SEQ
SEQ SEQ 031,032
SHEET :026,028,030, SHEET :026
030/1,031
SK S 15-HS-10004 RESET RESET
O SEQ SEQ
F SEQUENCE RESET
FCS ST SHEET :026 SHEET :025 RESET SEQ
T FROM GRAPHICS
SHEET :032

SEQUENCE START` - STEP-SEQUENCE -ON

START
SEQ
SEQUENCE START
& ACTIVATED

STARTUP STARTUP SEQUENCE START


PERM PERM ST_SEQ ST_SEQ
S c
ON ON
SHEET :025 SHEET :026 RS
SHEET :026 SHEET :027
R1 d
ST_SEQ ST_SEQ
END END
SHEET :032 SHEET :026

ABORT ABORT

SHEET :026 SHEET :26


SHEET NO :026
INPUT OUTPUT
FCS / FIELD
START SEQUENCE –WI PUMP P-151001 CONTROL LOGIC ALARM FIELD

STEP 1 LO PUMP ,LO HEATER AND SEAL COOLER START

ST_SEQ ST_SEQ S c ST_SEQ ST_SEQ


ON ON ST-1 ST-1
RS
SHEET :026 SHEET :027 SHEET :027 SHEET: 013
R1 d SHEET :015
SHEET -024
ST_SEQ ST_SEQ ACTIVATE MCMS S
END END ON TRIP MULTIPLY SL
O
x3 F
SHEET :032 SHEET :027 OFF T
IPS
ABORT ABORT
TRIP MULTIPLIER SHALL
SHEET :026 SHEET :27 BE ENABLED AS PER
15-EMRN-10016 VENDOR
HW
D RECOMMENDATION IN
BN SYSTEM
SEAL COOLER FAN RUNNING =1
I
FCS RUNNING FB NOT RUNNING =0

t1____0
HW 15-EMRN-10017 ST_SEQ ST_SEQ
D ST-2 ST-2
t = 15sec
LO HEATER RUNNING =1 TMR28 SHEET :027 SHEET :028
I
FCS RUNNING FB NOT RUNNING =0

HW 15-PMRN-1003
D &
LO PUMP RUNNING RUNNING =1
I
FCS FB NOT RUNNING =0

ST_SEQ ST_SEQ
ST-1 ST-1
SHEET :021 SHEET: 027

15-TAL- 15-TAL-
10046 10046
15-PAL- 15-PAL- t1____0
SHEET :010 SHEET :027 10182 10182
t = 15sec
SHEET :010 SHEET :027 TMR22 SHEET NO :027
INPUT OUTPUT
FCS / FIELD
START SEQUENCE –WI PUMP P-151001 CONTROL LOGIC ALARM FIELD

STEP 2--LO PUMP PRESSURE CHECK , SUCTION INLET PRESSURE,START SEAL SYSTEM AND SEAL
SYSTEM COOLER RUNNING FB

ST_SEQ ST_SEQ
ST-1 ST-1
SHEET :027 SHEET :028

HW 13-PMRN-1003 t1____0
D
LO PUMP RUNNING RUNNING =1 & t = 15sec LO HEADER
I
FCS FB NOT RUNNING =0 TMR22 PRESSURE NOT
15-PAL-100182 HEALTHY

13-PAL- 15-PAL-
100182 100182
SHEET :012 SHEET :028

ST_SEQ ST_SEQ
ST-2 ST-2
ST_SEQ ST_SEQ
SHEET :027 SHEET :028 S c ST-3 ST-3
RS SHEET :028 SHEET :021
HW 13-PMRN-10001
D SHEET :022
R1 d SHEET :024
AUX LO PUMP RUNNING =1
I ST_SEQ ST_SEQ
FCS RUNNING FB NOT RUNNING =0
END END
&
SHEET :032 SHEET :028 OR
13-PAL- 15-PAL-
100182 100182 ABORT
ABORT
SHEET :012 SHEET :028

SK S 15-IPS-DS-FCS-007 SHEET :026 SHEET :28


O 15-PZI-10003
SUCTION PRESSURE
F
LOW LOW >500 kPag
IPS T SH-005 TO SH-028

SUCTION
t1____0 PRESSURE NOT
SK S 15-IPS-DS-FCS-007 HEALTHY
O 15-PZI-10003
F SUCTION PRESSURE t = 30sec ABORT ABORT
IPS
LOW LOW TMR08 SEQ SEQ 15-PALL-10003
T SH-005 TO SH-028
SHEET NO :028
SHEET :028 SHEET :26
INPUT OUTPUT
FCS / FIELD
START SEQUENCE –WI PUMP P-151001 CONTROL LOGIC ALARM FIELD

STEP 3 – SEAL SYSTEM PRESSURE CHECK

ST_SEQ ST_SEQ
ST-3 ST-3
SHEET :028 SHEET :029
HW 13-PMRN-10001
D
AUX LO PUMP RUNNING =1
FCS I RUNNING FB NOT RUNNING =0
ST_SEQ ST_SEQ
S c ST-4 ST-4
15-PAL- 15-PAL- RS
10083 10083 SHEET :029 SHEET :030
SHEET :011 SHEET :029 R1 d
15-PAL- ST_SEQ ST_SEQ
15-PAL-
10084 & END END
10084
SHEET :011 SHEET :029 SHEET :032 SHEET :029
HW 15-EMRN-10016
D
SEAL COOLER RUNNING =1 ABORT ABORT
I
FCS RUNNING FB NOT RUNNING =0
SHEET :026 SHEET :029
HW 15-PMRN-10004
D
SEAL PUMP 10004 RUNNING =1
FCS I
RUNNING FB NOT RUNNING =0 OR

HW 15-PMRN-10005
D
SEAL PUMP 10005 RUNNING =1
FCS I
RUNNING FB NOT RUNNING =0

15-PAL- 15-PAL-
10083 10083
t1____0 SEAL SYSTEM
SHEET :011 SHEET :029 & HEADER
t = 15sec PRESSURE NOT
15-PAL- 15-PAL- ABORT ABORT HEALTHY
TMR09 15-PAL-
10084 10084 SEQ SEQ
100183/100184
SHEET :011 SHEET :029 SHEET :029 SHEET :026

SHEET NO :029
INPUT OUTPUT
FCS / FIELD
START SEQUENCE –WI PUMP P-151001 CONTROL LOGIC ALARM FIELD

STEP 4 – VENT VALVE (OPEN/CLOSE) 15-KSV-10007

ST_SEQ ST_SEQ
ST-4 ST-4
SHEET :029 SHEET :030 S c ST_SEQ
ST-4A
RS
`` O 15-KSV-10007 HW
ST_SEQ ST_SEQ VENT VALVE - V
R1 d C SOV W DCS
END END
SHEET :032 SHEET :030

ABORT ABORT

SHEET :026 SHEET :030

ST_SEQ
ST-4B

ST_SEQ t1____0
ST-4A 15-FIC-10001B HW
HW 15-GBSO-10007 & ST_SEQ MIINIMUM BY-PASS A
D t = 300sec LINE
TMR11 ST-4B
CASING VENT SET 80% AND IN O
I FCS
FCS VALVE OPEN FB MANUAL MODE
t1____0
& ABORT ABORT CASING VENT
t = 5sec SEQ SEQ VALVE OPEN
TMR10 FB NOT
ST_SEQ SHEET :030 SHEET :026 AVAILABLE
ST-4B 15-GBSO-10007
S c
SR
ST_SEQ ST_SEQ
ST-5A ST-5A R1 d
SHEET :031 SHEET: 030 ST_SEQ ST_SEQ
ST-5 ST-5
ABORT ABORT
SHEET :030 SHEET :031
CASING VENT
SHEET :026 SHEET :030 VALVE CLOSE
t1____0 FB NOT
HW 15-GBSC-10007 ST_SEQ ABORT ABORT AVAILABLE
D ST-4B SEQ SEQ
& t = 5sec 15-GBSC-10007
I
CASING VENT TMR11 SHEET NO :030
DCS VALVE CLOSE FB SHEET :030/1 SHEET :026
INPUT OUTPUT
FCS / FIELD
START SEQUENCE –WI PUMP P-151001 CONTROL LOGIC ALARM FIELD

STEP 5-- MAIN MOTOR START AND LO COOLER START

HW 15-GBSC-10007
D ST_SEQ
S ST_SEQ
c
CASING VENT ST-5A ST-5A
I RS
FCS VALVE CLOSE FB
SHEET :031 SHEET :030
& SHEET :017
R1 d SHEET :034
ST_SEQ ST_SEQ ST_SEQ ST_SEQ
ST-5 ST-5 END END
SHEET :030 SHEET :031 SHEET :032 SHEET :031

ABORT SIGNAL
ABORT
TRANSFER FROM
SHEET :026 SHEET :031 FCS TO IPS FOR
START SEQ STEP 6

HW 15-PMRN-10001
D
15-FCS-DS-IPS-001
MAIN PUMP RUNNING =1 t1____0 ON S SL
FCS I RUNNING FB ST_SEQ ST_SEQ O
NOT RUNNING =0
& t = 20sec ST-6 ST-6 START-SEQ STEP-6 F
T
TMR14 SH-031 TO SH -003 IPS
HW 15-EMRN-1005 SHEET :031 SHEET :003
D
LO FAN COOLER
I
FCS RUNNING FB ST_SEQ
ST-5A MAIN PUMP
RUNNING FB
t1____0 NOT
& ABORT ABORT
15-PMRN-10001 AVAILABLE
t = 5sec SEQ SEQ
TMR13 SHEET :031 SHEET :026
LO FAN
t1____0 COOLER
& STOP STOP RUNNING FB
15-EMRN-10005
t = 30sec SEQ SEQ NOT
TMR25 AVAILABLE
SHEET :031 SHEET :035

SHEET NO :031
INPUT OUTPUT
FCS / FIELD
START SEQUENCE –WI PUMP P-151001 CONTROL LOGIC ALARM FIELD
STEP 8— LO PUMP STOP AND START SEQUENCE END

SL S 15-IPS-DS-FCS-001 ON 15-FIC-10001B HW
O t1____0 A
F START SEQ STEP-8 MIINIMUM BY-PASS
IPS T SH-003 TO SH -032 LINE
T = 360 sec IN AUTO MODE O FCS
TMR23
S ST_SEQ ST_SEQ
SL S 15-IPS-DS-FCS-001 ON c ST-8 ST-8
&
O
F 15-GBSC-10002 RS SHEET :032 SHEET :013
IPS T SH-005 TO SH -032 R1
d
SL S 15-IPS-DS-FCS-001 ON
O
F 15-GBSO-10001 ST_SEQ ST_SEQ
IPS T SH-005 TO SH -032 END END
SHEET :032 SHEET :032

ABORT ABORT

SHEET :026 SHEET :032

ST_SEQ ST_SEQ ST_SEQ ST_SEQ


ST-8 ST-8 END END
SHEET :032 SHEET :032 SHEET :032 SHEET :026
& SHEET :027
HW 15-PMRN-1003 SHEET :028
D SHEET :029
LO PUMP RUNNING RUNNING =1 SHEET :030
FCS I FB SHEET :031
NOT RUNNING =0

RESET RESET
SEQ SEQ
SHEET :026 SHEET :032

SHEET NO :032
INPUT OUTPUT
FCS/FIELD
MANI PUMP -P-131001 ALARM FIELD

HW 15-PMRN-1001
D
MAIN PUMP RUNNING =1
FCS I RUNNING FB NOT RUNNING =0

&
HW 15-PMAV-1001
D
MAIN PUMP AVAILABLE=1
I
FCS AVAILABLE FB
NOT AVAILABLE =0 START 15-PMST-1001 V
& S c MAIN PUMP HW
START W MCC
RS
R1
SK S MAIN PUMP d STOP 15-PMSP-1001 V
A
O MAIN PUMP HW
F AUTO /MANUAL AUTO=1 STOP W MCC
SELECTION FROM M
FCS T GRAPHICS MANUAL =0

t=1sec
&

SK S MAIN PUMP
O
F MANUAL START
FCS T FROM GRAPHICS ST

SK S MAIN PUMP
1
O
&
F MANUAL STOP t=1sec
SP
FCS T FROM GRAPHICS

AUTO AUTO INTER INTER


START START LOCK LOCK SHEET NO :033
SHEET :034 SHEET :033 SHEET :034 SHEET :033
INPUT OUTPUT
FCS/FIELD
MANI PUMP -P-131001 ALARM FIELD

ST_SEQ ST_SEQ AUTO AUTO


ST-5A ST-5A START START
SHEET :031 SHEET :034 SHEET :034 SHEET :033

SP_SEQ SP_SEQ INTER INTER


ST-2 ST-2 LOCK LOCK
SHEET :035 SHEET: 034 SHEET :034 SHEET :033

TRP SEQ TRP SEQ


ST-1 ST-1
SHEET :039 SHEET: 034

HW 15-PMRN-1001
D ON 15-FCS-DS-IPS-004 S SL
MAIN PUMP O
MAIN PUMP RUNNING =1 F
FCS I RUNNING FB RUNNING FB
NOT RUNNING =0 T
SH-034 TO SH -009 IPS

SHEET NO :034
INPUT OUTPUT
FCS / FIELD
STOP SEQUENCE – WI PUMP P-151001 CONTROL LOGIC ALARM FIELD

STOP SEQUENCE FROM GRAPHICS`


SK S 15-HS-10005
O STOP
F STOP SEQ FROM SEQ
FCS T GRAPHICS ST
STOP SEQ

SL S 15-IPS-DS-FCS-002
ON
O
F STOP SEQ – B6
IPS T SH-003 TO SH -035 STOP STOP
SEQ-B7 SEQ-B7
SHEET :031 SHEET :035

START AUX LO PUMP

STOP
SEQ
SP_SEQ SP_SEQ
HW 15-PMRN-1001 & ST-1 ST-1
D
MAIN PUMP RUNNING =1 SHEET :035 SHEET: 013
FCS I RUNNING FB NOT RUNNING =0

STOP MAIN PUMP

SP_SEQ SP_SEQ
ST-1 ST-1
SHEET :035 SHEET: 035
&
HW 15-PMRN-1003
D
LO PUMP RUNNING RUNNING =1 S c SP_SEQ SP_SEQ
I
FCS FB NOT RUNNING =0 ST-2 ST-2
RS SHEET :035 SHEET: 034
R1 SHEET: 035
SP_SEQ SP_SEQ
END d
END
SHEET :037 SHEET :035

RESET RESET
SEQ SEQ
SHEET :026 SHEET :035
SHEET NO :035
INPUT OUTPUT
FCS / FIELD
STOP SEQUENCE – WI PUMP P-151001 CONTROL LOGIC ALARM FIELD

STOP - SEAL SYSTEM ,SEAL COOLER,LO COOLER ,LO HEATER

SP_SEQ SP_SEQ
ST-2 ST-2
SP_SEQ SP_SEQ
SHEET :035 SHEET: 036 ST-3 ST-3
HW 15-PMRN-1001
D
SHEET :036 SHEET: 016
MAIN PUMP RUNNING =1 & SHEET: 018
FCS I RUNNING FB NOT RUNNING =0 SHEET: 024

HW 15-PMRN-1003
D
LO PUMP RUNNING RUNNING =1
I
FCS FB NOT RUNNING =0

STOP – LO PUMP

SP_SEQ SP_SEQ
ST-4 ST-4
t1____0 SHEET :036 SHEET: 037
SP_SEQ SP_SEQ
ST-3 ST-3 S c SHEET: 013 15-FCS-DS-IPS-002 S SL
t = 20sec
TMR15 O
SHEET :036 SHEET: 036 RS STOP-SEQ STEP-3 F
R1 SH-036 TO SH -003 T IPS
SP_SEQ SP SEQ
END END d

SHEET :037 SHEET :036

RESET RESET
SEQ SEQ
SHEET :026 SHEET :036

SHEET NO :036
INPUT OUTPUT
FCS / FIELD
STOP SEQUENCE – WI PUMP P-151001 CONTROL LOGIC ALARM FIELD

HW 15-EMRN-1005
D
LO FAN COOLER RUNNING =1
FCS I RUNNING FB NOT RUNNING =0 SP_SEQ SP SEQ
END END

SP_SEQ SP_SEQ SHEET :037 SHEET:035


ST-4 ST-4 SHEET:036
15-FIC-10001B HW
SHEET :036 SHEET: 037 t1____0 A
HW 15-PMRN-1003
D MIINIMUM BY-PASS
t = 30sec LINE , IN MANUAL O
LO PUMP RUNNING RUNNING =1 MODE,OUTPUT 0%
FCS
I TMR27
FCS FB NOT RUNNING =0

SK S 15-IPS-DS-FCS-004
O 15-FCS-DS-IPS-001 SL
F 15-GBSC-10002 ENABLE OVERRIDE S
IPS T SH-005 TO SH -037 & 15-FZI-10003,15-PZI- O
10185,15-PZI- F
SK S 15-IPS-DS-FCS-005 10186,15-PZI-10187 T IPS
O SH-37 TO SH-009
F 15-GBSC-10001
IPS T SH-005 TO SH -037

HW 15-EMRN-10016
D
SEAL COOLER RUNNING =1
FCS I RUNNING FB NOT RUNNING =0

HW 13-PMRN-10004
D
SEAL PUMP RUNNING =1
DCS I RUNNING FB NOT RUNNING =0

HW 13-PMRN-10005
D
SEAL PUMP RUNNING =1
I
DCS RUNNING FB NOT RUNNING =0

SHEET NO :037
INPUT OUTPUT
FCS / FIELD
TRIP CONDITION – WI PUMP P-151001 CONTROL LOGIC ALARM FIELD

TRIP CONDITION

1 13- 13-
RESET RESET S c PMXZ- PMXZ-
SEQ SEQ t=2sec
10001 10001
SHEET :026 SHEET :038 RS SHEET :038 SHEET :039
R1
SL S 15-IPS-DS-FCS-003 d
O
F 15-PMXZ-1001 TRIP
IPS T SH-004 TO SH -025
&
S 15-IPS-DS-FCS-005
SL
O
15-PZI-10003
F
IPS SUCTION PRESSURE
T SH-005 TO SH-038

SHEET NO :038
INPUT OUTPUT
FCS / FIELD
TRIP SEQUENCE – WI PUMP P-151001 CONTROL LOGIC ALARM FIELD

TRIP MAIN PUMP


TRIP CONDITION

13- 13-
PMXZ- PMXZ-
10001 10001
SHEET :038 SHEET :392 & S c TRP SEQ TRP SEQ
ST-1 ST-1
HW 15-PMRN-1001 RS
D SHEET: 039
SHEET :039
MAIN PUMP RUNNING =1 R1
FCS I RUNNING FB d
NOT RUNNING =0

TRP SEQ TRP SEQ


END END
SHEET :040 SHEET :039

RESET RESET
SEQ SEQ
SHEET :026 SHEET :039

CLOSE DISCHARGE VALVE, FIC VALVE OPEN AND AUTO MODE

TRP SEQ TRP SEQ CLOSE DISCHARGE


ST-1 ST-1 VALVE
SHEET :039 SHEET: 039
& 15-FCS-DS-IPS-005 S SL
15-PMRN-1001 C
HW O
D
TRIP-SEQ STEP-2 F
MAIN PUMP RUNNING =1 S c TRP SEQ TRP SEQ SH-039 TO SH -003 T IPS
FCS I RUNNING FB ST-2 ST-2
NOT RUNNING =0
RS SHEET :039 SHEET: 040
R1 13-FIC-10002 A HW
TRP SEQ TRP SEQ
END END d MIINIMUM BY-PASS
SHEET :039 LINE, IN MANUAL
SHEET :040 O DCS
MODE,OUTPUT 0%

RESET RESET
SEQ SEQ
SHEET :026 SHEET :039 SHEET NO :039
INPUT OUTPUT
FCS / FIELD
TRIP SEQUENCE – WI PUMP P-151001 CONTROL LOGIC ALARM FIELD

TRIP - AUX LO PUMP, SEAL SYSTEM,SEAL COOLER ,LO COOLER

TRP SEQ TRP SEQ


ST-2 ST-2
SHEET :039 SHEET: 040

HW 15-PMRN-1001
D
&
MAIN PUMP RUNNING =1 S c TRP SEQ TRP SEQ
FCS I RUNNING FB ST-3 ST-3
NOT RUNNING =0
RS SHEET :040 SHEET: 014
SK S 15-IPS-DS-FCS-005 R1 SHEET: 016
O SHEET: 018
d
F 15-GBSC-10001 SHEET :025
IPS T SH-005 TO SH -040 SHEET: 041

TRP SEQ TRP SEQ


END END
SHEET :041 SHEET :040

RESET RESET
SEQ SEQ
SHEET :026 SHEET :040

SHEET NO :040
INPUT OUTPUT
FCS / FIELD
TRIP SEQUENCE– WI PUMP P-151001 CONTROL LOGIC ALARM FIELD

TRP SEQ TRP SEQ


ST-3 ST-3
SHEET :040 SHEET: 041
13-EMRN-1005
HW D
TRP SEQ TRP SEQ
FCS LO COOLER FAN RUNNING =1 END END
I RUNNING FB NOT RUNNING =0 SHEET :41 SHEET :039
SHEET :040
HW 13-PMRN-1003
D
LO PUMP RUNNING RUNNING =1
I 15-FCS-DS-IPS-001
FCS FB NOT RUNNING =0 SL
ENABLE OVERRIDE S
15-FZI-10003,15-PZI- O
10185,15-PZI- F
HW 15-EMRN-10016 & 10186,15-PZI-10187 T IPS
D
SH-041 TO -SH-009
SEAL COOLER RUNNING =1
I
FCS RUNNING FB NOT RUNNING =0

HW 13-PMRN-10004
D
SEAL PUMP RUNNING =1
I
FCS RUNNING FB NOT RUNNING =0

HW 13-PMRN-10005
D
SEAL PUMP RUNNING =1
I
FCS RUNNING FB NOT RUNNING =0

SHEET NO :041