Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Generator Construction

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 18

Q18.

  What are the three classifications of dc generators?


Q19.   What is the main disadvantage of series generators?

GENERATOR CONSTRUCTION

Figure 1-19, views A through E, shows the component parts of dc generators. Figure 1-20 shows
the entire generator with the component parts installed. The cutaway drawing helps you to see the physical
relationship of the components to each other.

Figure 1-19.—Components of a dc generator.

1-19
Figure 1-20.—Construction of a dc generator (cutaway drawing).

VOLTAGE REGULATION The regulation of a generator refers to the VOLTAGE CHANGE


that takes place when the load changes. It is usually expressed as the change in voltage from a no-load
condition to a full-load condition, and is expressed as a percentage of full-load. It is expressed in the
following formula:

where EnL is the no-load terminal voltage and EfL is the full-load terminal voltage of the generator.
For example, to calculate the percent of regulation of a generator with a no-load voltage of 462 volts and a
full-load voltage of 440 volts

Given:
No-load voltage 462 V
Full-load voltage 440 V
Solution:

1-20
NOTE: The lower the percent of regulation, the better the generator. In the above example, the 5%
regulation represented a 22-volt change from no load to full load. A 1% change would represent a change
of 4.4 volts, which, of course, would be better.

Q20.   What term applies to the voltage variation from no-load to full-load conditions and is expressed as a
percentage?

VOLTAGE CONTROL Voltage control is either (1) manual or (2) automatic. In most cases the process
involves changing the resistance of the field circuit. By changing the field circuit resistance, the field
current is controlled. Controlling the field current permits control of the output voltage. The major
difference between the various voltage control systems is merely the method by which the field circuit
resistance and the current are controlled.

VOLTAGE REGULATION should not be confused with VOLTAGE CONTROL. As described


previously, voltage regulation is an internal action occurring within the generator whenever the load
changes. Voltage control is an imposed action, usually through an external adjustment, for the purpose of
increasing or decreasing terminal voltage.

Manual Voltage Control


The hand-operated field rheostat, shown in figure 1-21, is a typical example of manual voltage
control. The field rheostat is connected in series with the shunt field circuit. This provides the simplest
method of controlling the terminal voltage of a dc generator.

1-21
Figure 1-21.—Hand-operated field rheostat.

This type of field rheostat contains tapped resistors with leads to a multiterminal switch. The arm
of the switch may be rotated to make contact with the various resistor taps. This varies the amount of
resistance in the field circuit. Rotating the arm in the direction of the LOWER arrow (counterclockwise)
increases the resistance and lowers the output voltage. Rotating the arm in the direction of the RAISE
arrow (clockwise) decreases the resistance and increases the output voltage.

Most field rheostats for generators use resistors of alloy wire. They have a high specific resistance
and a low temperature coefficient. These alloys include copper, nickel, manganese, and chromium. They
are marked under trade names such as Nichrome, Advance, Manganin, and so forth. Some very large
generators use cast-iron grids in place of rheostats, and motor-operated switching mechanisms to provide
voltage control.

1-22
Automatic Voltage Control

Automatic voltage control may be used where load current variations exceed the built-in ability of
the generator to regulate itself. An automatic voltage control device "senses" changes in output voltage and
causes a change in field resistance to keep output voltage constant.

The actual circuitry involved in automatic voltage control will not be covered in this chapter.
Whichever control method is used, the range over which voltage can be changed is a design characteristic
of the generator. The voltage can be controlled only within the design limits.

PARALLEL OPERATION OF GENERATORS

When two or more generators are supplying a common load, they are said to be operating in
parallel. The purpose of connecting generators in parallel is simply to provide more current than a single
generator is capable of providing. The generators may be physically located quite a distance apart.
However, they are connected to the common load through the power distribution system.

There are several reasons for operating generators in parallel. The number of generators used may
be selected in accordance with the load demand. By operating each generator as nearly as possible to its
rated capacity, maximum efficiency is achieved. A disabled or faulty generator may be taken off-line and
replaced without interrupting normal operations.

Q21. What term applies to the use of two or more generators to supply a common load?

AMPLIDYNES

Amplidynes are special-purpose dc generators. They supply large dc currents, precisely controlled,
to the large dc motors used to drive heavy physical loads, such as gun turrets and missile launchers.

The amplidyne is really a motor and a generator. It consists of a constant-speed ac motor (the
prime mover) mechanically coupled to a dc generator, which is wired to function as a high-gain amplifier
(an amplifier is a device in which a small input voltage can control a large current source). For instance, in
a normal dc generator, a small dc voltage applied to the field windings is able to control the output of the
generator. In a typical generator, a change in voltage from 0-volt dc to 3-volts dc applied to the field
winding may cause the generator output to vary from 0-volt dc to 300-volts dc. If the 3 volts applied to the
field winding is considered an input, and the 300 volts taken from the brushes is an output, there is a gain of
100. Gain is expressed as the ratio of output to input:

In this case 300 V ÷ 3 V = 100. This means that the 3 volts output is 100 times larger than the input.

The following paragraphs explain how gain is achieved in a typical dc generator and how the
modifications making the generator an amplidyne increase the gain to as high as 10,000.

The schematic diagram in figure 1-22 shows a separately excited dc generator. Because of the 10-
volt controlling voltage, 10 amperes of current will flow through the 1-ohm field winding. This draws 100
watts of input power (P = IE).

1-23
Figure 1-22.—Ordinary dc generator.

Assume that the characteristics of this generator enable it to produce approximately 87 amperes of
armature current at 115 volts at the output terminals. This represents an output power of approximately
10,000 watts (P = IE). You can see that the power gain of this generator is 100. In effect, 100 watts controls
10,000 watts.

An amplidyne is a special type of dc generator. The following changes, for explanation purposes,
will convert the typical dc generator above into an amplidyne.

The first step is to short the brushes together, as shown in figure 1-23. This removes nearly all of
the resistance in the armature circuit.

Figure 1-23.—Brushes shorted in a dc generator.

Because of the very low resistance in the armature circuit, a much lower control-field flux
produces full-load armature current (full-load current in the armature is still about 87 amperes). The smaller
control

1-24
field now requires a control voltage of only 1 volt and an input power of 1 watt (1 volt across 1 ohm causes
1 ampere of current, which produces 1 watt of input power).

The next step is to add another set of brushes. These now become the output brushes of the
amplidyne. They are placed against the commutator in a position perpendicular to the original brushes, as
shown in figure 1-24. The previously shorted brushes are now called the "quadrature" brushes. This is
because they are in quadrature (perpendicular) to the output brushes. The output brushes are in line with the
armature flux. Therefore, they pick off the voltage induced in the armature windings at this point. The
voltage at the output will be the same as in the original generator, 115 volts in our example.

Figure 1-24.—Amplidyne load brushes.

As you have seen, the original generator produced a 10,000-watt output with a 100-watt input.
The amplidyne produces the same 10,000-watt output with only a 1-watt input. This represents a gain of
10,000. The gain of the original generator has been greatly increased.

As previously stated, an amplidyne is used to provide large dc currents. The primary use of an
amplidyne is in the positioning of heavy loads through the use of synchro/servo systems. Synchro/servo
systems will be studied in a later module.

Assume that a very large turning force is required to rotate a heavy object, such as an antenna, to a
very precise position. A low-power, relatively weak voltage representing the amount of antenna rotation
required can be used to control the field winding of an amplidyne. Because of the amplidyne's ability to
amplify, its output can be used to drive a powerful motor, which turns the heavy object (antenna). When the
source of the input voltage senses the correct movement of the object, it drops the voltage to zero. The field
is no longer strong enough to allow an output voltage to be developed, so the motor ceases to drive the
object (antenna).

The above is an oversimplification and is not meant to describe a functioning system. The intent is
to show a typical sequence of events between the demand for movement and the movement itself. It is
meant to strengthen the idea that with the amplidyne, something large and heavy can be controlled very
precisely by something very small, almost insignificant.

Q22.   What is the purpose of a dc generator that has been modified to function as an amplidyne?

1-25
Q23.   What is the formula used to determine the gain of an amplifying device?
Q24.   What are the two inputs to an amplidyne?

SAFETY PRECAUTIONS
You must always observe safety precautions when working around electrical equipment to avoid
injury to personnel and damage to equipment. Electrical equipment frequently has accessories that require
separate sources of power. Lighting fixtures, heaters, externally powered temperature detectors, and alarm
systems are examples of accessories whose terminals must be deenergized. When working on dc
generators, you must check to ensure that all such circuits have been de-energized and tagged before you
attempt any maintenance or repair work. You must also use the greatest care when working on or near the
output terminals of dc generators.

SUMMARY

This chapter introduced you to the basic principles concerning direct current generators. The
different types of dc generators and their characteristics were covered. The following information provides
a summary of the major subjects of the chapter for your review.

MAGNETIC INDUCTION takes place when a conductor is moved in a


magnetic field in such a way that it cuts flux lines, and a voltage (emf) is induced in the conductor.

THE LEFT-HAND RULE FOR GENERATORS states that when the thumb,
forefinger, and middle finger of the left hand are extended at right angles to each other so that the thumb
indicates the direction of movement of the conductor in the magnetic field, and the forefinger points in the
direction of the flux lines (north to south), the middle finger shows the direction of induced emf in the
conductor.

1-26
AN ELEMENTARY GENERATOR consists of a single coil rotated in a magnetic field.
It produces an ac voltage.

A BASIC DC GENERATOR results when you replace the slip rings of an elementary
generator with a two-piece commutator, changing the output voltage to pulsating dc.

A MULTIPLE COIL ARMATURE (adding coils to the armature) decreases the ripple
voltage in the output of a dc generator, and increases the output voltage.

1-27
A MULTIPOLE GENERATOR is the result of adding more field poles to a dc generator.
They have much the same effect as adding coils to the armature. In practical generators, the poles are
electromagnets.

COMMUTATION is the process used to get direct current from a generator. The
coil connections to the load must be reversed as the coil passes through the neutral plane. The brushes
must be positioned so that commutation is accomplished without brush sparking.

1-28
ARMATURE REACTION takes place when armature current causes the armature
to become an electromagnet. The armature field disturbs the field from the pole pieces. This results in a
shift of the neutral plane in the direction of rotation.

COMPENSATING WINDINGS AND INTERPOLES are used to counteract the


effects of armature reaction. They are supplied by armature current and shift the neutral plane back to its
original position.
1-29
MOTOR REACTION is caused by the magnetic field that is set up in the
armature. It tends to oppose the rotation of the armature, due to the attraction and repulsion forces
between the armature field and the main field.

ARMATURE LOSSES in dc generator armatures affect the outputs. These losses


are as follows:

1.    Copper losses are simply 12R (heat) losses caused by current flowing through the resistance of the
armature windings.

2.    Eddy currents are induced in core material and cause heat.

3.    Hysteresis losses occur due to the rapidly changing magnetic fields in the armature, resulting in heat.
1-30
ARMATURE TYPES used in dc generators are the Gramme-ring (seldom used) and the
drum-type, used in most applications.

1-31
FIELD EXCITATION is the voltage applied to the main field windings. The current in the field
coils determines the strength and the direction of the magnetic field.

SEPARATELY EXCITED GENERATORS receive current for field coils from an outside
source such, as a battery or another dc generator.

SELF-EXCITED GENERATORS use their own output voltage to energize field coils.

SERIES-WOUND DC GENERATORS have field windings and armature windings connected


in series. Outputs vary directly with load currents. Series-wound generators have few practical applications.

SHUNT-WOUND DC GENERATORS have field windings and armature windings connected in


parallel (shunt). The output varies inversely with load current.

COMPOUND-WOUND DC GENERATORS have both series field windings and shunt field
windings. These generators combine the characteristics of series and shunt generators. The output voltage
remains relatively constant for all values of load current within the design of the generator. Compound
generators are used in many applications because of the relatively constant voltage.
1-32

AMPLIDYNES are dc generators that are designed to act as high-gain amplifiers. By short-
circuiting the brushes in a normal dc generator and adding another set of brushes perpendicular to the
original ones, an amplidyne is formed. Its power output may be up to 10,000 times larger than the power
input to its control windings.

1-33
ANSWERS TO QUESTIONS Q1. THROUGH Q24.

A1. Magnetic induction.

A2. The left-hand rule for generators.

A3. To conduct the currents induced in the armature to an external load.

A4. No flux lines are cut.

A5. A commutator

A6. The point at which the voltage is zero across the two segments.

A7. Two.

A8. Four

A9. By varying the input voltage to the field coils.

A10. Improper commutation.

A11. Distortion of the main field due to the effects of armature current.

A12. To counter act armature reaction.

A13. A force which causes opposition to applied turning force.

A14. Resistance in the armature coils, which increases with temperature.

A15. By laminating the core material.

A16. Drum-type armatures are more efficient, because flux lines are cut by both sides of each coil.

A17. Higher load currents are possible.

A18. Series-wound, shunt-wound, and compound-wound.

A19. Output voltage varies as the load varies.

A20. Voltage regulation.

A21. Parallel operation.

A22. It can serve as a power amplifier.

A23. Gain = output ÷ input.

A24. The mechanical force applied to turn the amplidyne, and the electrical input signal.

1-34

You might also like