DB1550500EN
DB1550500EN
DB1550500EN
valid from:
2021-10-20 NYCWY
Application
NYCWY are cables with insulation and outer sheathing of PVC and a wave-like concentric conductor. They are used for fixed installation in
dry or damp rooms as well as outdoors and underground.
NYCWY is used for power supply and as control cable.
Design
Design acc. to DIN VDE 0276-603 (VDE 0276-603) resp. HD 603
Certification The cable is marked with the ⌉ VDE ⌊ HAR-sign or HAR-identification thread.
Classification of fire behaviour
according to EN 13501-6 and EN 50575
(article/dimension range see www.lappkabel.com/cpr)
Conductor single or multi-wire,
bare copper wire conductor acc. IEC 60228 resp. EN 60228, class 1 or 2
Insulation PVC compound DIV4 acc. DIN VDE 0276-603 (VDE 0276-603) resp. HD 603
Core identification code colour-coded acc. to VDE 0293-308 (VDE 0293-308)
Screen concentric conductor: helical, outer conductor made of bare copper strands
Outer sheath PVC compound DMV5 acc. DIN VDE 0276-603 (VDE 0276-603) resp. HD 603
.
colour: black
Electrical properties at 20 °C
Nominal voltage U₀/U: 600/1000 V
Test voltage 4000 V AC