DALI64 DLS DALI Lighting Control System

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Installation Instructions

Flush Mount

Switch Input

wireless BLE
Commission

Addressable
Connection
Lens tilting

Luminaires
1) Determine Position

Works with

per system
Touch app
with Light
DALI Bus

(to BMS)
Provides

switches
power to

Wallbus
Surface

(Mains)
Mount

SYLK/
The unit should be positioned on the ceiling in the centre of the occupied space

DALI
Part Number either flush mounted or surface mounted (e.g on a BESA box). Avoid exceeding h
DALI64F • • • • 64 maximum recommended mounting height.
DALI64S • • • • 64
DALI64SYLKF • • • • • 64 Aspect Ratio (diameter : height)
DALI64SYLKS • • • • • 64 Micro Detection - High Macro Detection - Standard Max recommended mounting
DALI64PSUF • • • 1 • • 64 Sensitivity Sensitivity height (h)
DALI64PSUS • • • 1 • • 64 2.8:1 4:1
DALI64SYLKPSUF • • • 1 • • • 64 3.5m
7m diameter @2.5m height 10m diameter @2.5m height
DALI64SYLKPSUS • • • 1 • • • 64
DALINETF •
DALINETS • Avoid mounting next to an AC unit. For additional positioning please refer to ‘9 Set
Tilt’ overleaf.
Warning: Total current provided on DALI Bus must never exceed 250mA. If
using an additional power supply the DALI64PSU’s integrated power supply

32345911-001 REVE
must be disabled before external power is applied. PSU variants supply 150mA
to the bus, never connect more than one PSU variant to the same DALI Bus. The unit is more sensitive to movement when
Security direction of travel is along the vertical and horizontal
DLS-DALI Lighting Control System Warning: After installation the DALI64 will NOT be protected by a password until it is planes. To achieve optimal occupancy detection the
Macro Macro
Only suitably qualified personnel should install this equipment configured using the Light Touch app. For details of securing the product and system sensor must be orientated as shown. High Sensitivity Macro Detection
Optimum Orientation Detection Detection
see the General Security Best Practice for Ex-Or Products Information Sheet - D6004.

2) Prepare Mounting Location and Run Cables Flush mount variants Surface mount variants 3) Remove Terminal Cover
Product variants with ‘S’ suffix are supplied with the surface fitting kit (SURFMT) as
DALI Topology standard. The surface mount kit can be ordered separately, order SURFMT.
DALI permits a free topology which means wiring can be done in daisy chain, star
or a combination of these. Do not close the loop or ring connections. 73mm
The sensor may be mounted to any suitable surface, but is most commonly fixed to a
DALI DALI DALI DALI DALI
conduit stop-end (BESA) box or bushed to trunking.

DALI

DALI DALI DALI DALI DALI

DALI DALI DALI DALI  DALI

DALI

DALI DALI DALI DALI DALI

Route cables through hole and


DALI DALI DALI
Note: SYLK/Wallbus cable must be secure LOCKRING (if used)

DALI DALI DALI


 routed separately from other cables
Drill hole
Note: If the LOCKRING is to be used route cables
through the LOCKRING.

4) Make Electrical Connections Mains Switch Input Connections (PSU only) DALI Bus Connections Additional
DALI Bus DALI Bus
Additional Mains Power Connections (PSU only)
For example wiring configurations see Wiring Examples. DALI devices DALI
Note: To prevent loose strands being outside the devices
1. DALI gears (ballasts or drivers) are normally wired from an unswitched supply. terminal a tool, e.g. a screwdriver, must be
DA DA
2. Ballasts or drivers must be DALI Control Gears complying to IEC 62386 V1 or V2. used to push the button on the terminal DA+ DA DA+ DA

when stranded conductors are inserted. DALI Loop in DA+ DA DALI OUT

DALI Loop out DALI16

Warning: Do not connect to 230V. DALI64, DALINET


SYLK/Wallbus Connections (SYLK only) e.g IQ™ECO
E.g connection to BEMS Warning: The DALI Bus is not classified as SELV. The same procedures and
safeguards must be applied as when working with mains voltage.
Switch Input Terminal type Pluggable screwless Terminal type Pluggable rising cage clamp
Terminal capacity 1 x 0.5-2.5mm2 solid or stranded.
WMB
220-240VAC
50-60Hz WM1 WM2 Terminal capacity 1 x 0.5-1.5mm2 solid or stranded.
Terminal type Pluggable rising cage clamp Recommended cable 2 core 0.5-1.5mm2 Recommended cable 1.5-2.5mm2
Terminal capacity 1 x 0.5-2.5mm2 solid or stranded. Cross Section Maximum cable length at 25 °C Max cable length Refer to appropriate regulations
SYLK/Wallbus Recommended cable 2 core 1.5-2.5mm2 Copper 0.50 mm2 112m Operating voltage 220 – 240V 50-60Hz.
Max cable length 10m Max cable length Copper 0.75 mm2 168m Power consumption 3W active, <0.5W static
Operating voltage 220 – 240V 50-60Hz. Copper 1.00 mm2 224m Recommended circuit protection 16A MCB
Terminal type Pluggable rising cage clamp Power consumption Negligible Copper 1.50 mm2 300m Warning: Total current provided on DALI Bus must never exceed 250mA. If
Terminal capacity 1 x 0.5-2.5mm2 solid or stranded. Recommended circuit 64 DALI control gears (ballasts or drivers), 64 DALI control devices (switch using an additional power supply the DALI64PSU’s integrated power supply
16A MCB must be disabled before external power is applied. PSU variants supply
Recommended cable 2 core 0.5-1.5mm2 protection input Modules, network sensors etc); Dependant on power requirements of
Max devices 150mA to the bus, never connect more than one PSU variant to the same
Max cable length 60m connected devices. 250mA max available depending on how DALI Bus is
powered. PSU variants can supply 150mA to DALI Bus. DALI Bus.

5) Connect DALI PSU (If required) 6) Fix Cable Clamps (optional for 1mm²-2.5mm² sheathed round cables) 7) Replace the Terminal Cover 8a) Fix to Ceiling (Flush mount)
DALI64 and DALINET are powered by the DALI bus. If a PSU variant is not being Insert screw for Class II compliance
Standard Method
used a separate DALI PSU is required. Cable clamps can be reversed to reduce
The DALI PSU must be installed according to the manufacturer’s instructions. An aperture
example is shown below.
Note: SYLK/Wallbus cable must be routed
N N
separately from other cables.
L L
DALI PSU DA+
Note: If using cables larger than 3x1.5mm²
DALI Bus Ceiling tile thickness
DA- the outer sheath on the supply cable should
only be removed after the sheathed cable 1 to 20mm
Recommended cable 2 core 1mm2 has been clamped in position.
Max DALI cable length 300m
Output DC voltage - 16V, Current - 240mA, Power - 3.84W
Voltage range - 120 to 370Vdc, Typical AC current - 0.4A/100-
Input
240VAC, Power consumption (no load) - 0.5W

Warning: Total current provided on DALI Bus must never exceed 250mA.
8b) Fix to Ceiling (Flush mount) 9) Fix to Ceiling (Surface mount) 10) Set Tilt (if required) 11) Mask Lens (if required)
LOCKRING Method 8 segments on the collar allow up to four different rotational positions for the Some variants feature the ability to tilt the sensor (before fitting) by up to 10° in Two lens masks are provided which may be used to restrict the viewable footprint of
The LOCKRING cannot be used when there is no access to ceiling void. sensor, when inserting the tabs into slots (1-8). 2° increments, in order to extend the range in one direction up to 67% (at full tilt). the sensor e.g. unwanted detection through a doorway. Cut the mask segment(s)
This may be useful in cases where the ideal mounting location is not available. The as desired and install by pushing the mask lip between the bezel and the lens on
Setting the correct position is important when using products with tilting lenses. increased range is indicated below. the sensor as shown.
LOCKRING

2 3
1 4
Remove springs
8 5
7 6

Ceiling tile thickness


1mm to 20mm tab

increased range
Drill point for optional secure locking with NOTE: Do not place in a position where access is limited
NOTE: To remove sensor rotate LOCKRING and pull up a 3mm tamperproof screw (not supplied)

12) Perform Walk Test 13) Out of Box Behaviour 15) Diagnostics Uninstall (Surface mount)
In order to verify correct installation, walk testing is recommended. Follow the Prior to commissioning the unit operates in DALI broadcast (all lights on/off/dim), LED indications are provided to help with fault-finding. Insert a flat headed screwdriver into the slot as shown and twist the collar anti-
instructions provided with the Light Touch commissioning app. During the walk all DALI switches act as OneSwitch. The default settings are as follows: clockwise to release. To separate the unit from the surface mount casing, push a
NOTE: With regard to safety, the DALI Bus connections should be treated flat headed screwdriver onto the tab via the inside void of the casing and pull the
test the connected lights will be switched off until movement is detected.
with the same respect as mains. unit upwards.
Password Protection Not configured
Time Delay 15 Minutes
Photocell Setting Always turn on when occupied
Dimming Level 100% LED indication Meaning
Occupancy Mode Automatic (lights Auto On, Auto OFF)
G G G
Movement detected Tab
Movement Sensitivity Very high Flashing green
Mains Switch input One Switch DALI Bus error – e.g. Possible short
Stand out of the unit’s viewable footprint or remain motionless within the viewable DLS2IM Switch inputs One Switch circuit, too many luminaires, too many
footprint and wait for the lights to go out. R R R
R R R sensors or input modules, or DALI
If fitted remove
3 red flashes every 2 seconds power supply or Lighting Control
tamperproof Max 4mm
Application sensors connected with
screw
14) Configuration wrong polarity.
B Communication with IR hand-held
Once installed the unit must be configured using the Light Touch commissioning Intermittent blue remote or Bluetooth device in progress
app to create the required lighting control installation, and configure a password.
Wait a further 2 seconds for the unit to stabilise then make a movement, the lights This is especially important when the DALI Bus is across multiple rooms. DALI64
should come back on. Observe that the detection / non-detection is as expected. uses the Light Touch app for commissioning - see the Light Touch by Honeywell
Manual - W6024.

IMPORTANT NOTES Wiring Examples


Basic System Extended System
1. A means for disconnection must be incorporated in the fixed wiring in accord- A basic system can be created similar to the example wiring shown below. Additional devices can be used to extend the functionality of the system.
ance with the current wiring regulations.
2. DALI terminals have only basic isolation from mains and therefore should be
wired in mains-rated cable and treated with the same respect.
3. In order to achieve satisfactory light level regulating operation, a sensor must DALI DALI
observe a substantially greater proportion of artificial light from the luminaire(s) DALI DALI
under its control than from neighbouring luminaires not under its control. This
is particularly important when planning the installed layout of linear luminaires
that have an integral detector positioned at one end.
4. Due to limited space within the enclosure, it is not recommended that this DA DA DA DA
product be used as a wiring junction box. System connections should be made DALI Loop in DA DA
DALI Loop in DA DA

elsewhere and wiring not looped within the product enclosure. DALI Loop out
DALI Loop out

5. All information given in this document was correct at the time of publication. DALI64SYLKPSU DALI64
DALINET
IEC 60669-2-1
IEC 61347-2-11
220-240VAC
50-60Hz

DALI Input Module


IQECO DLS4IM
DALI64 DALI64 DALINET
COM T4 T3 T2 T1

Switch
SW 1 Switch
L L L SW 2
L DA DA
N N DALI Gear N N DALI Gear
DALI64 Power E E DA E E DA
Switch
Supply
Supply L Supply L SW 3
DA DA
N DALI Gear N DALI Gear
L L E DA E DA
N DA
N DALI Gear Switch
DALI Gear E E DA
L More DALI DA L More DALI DA SW 4
N N
Supply L E Gear DA E Gear DA
Supply DA
N DALI Gear Switch
DALI Gear E DA
SW 5
L More DALI DA
N
More DALI E Gear DA
Gear
At the end of their useful life the Honeywell
Room 1 Room 2 packaging and product should St Marks Court, North Street
be disposed of via a suitable
Horsham, West Sussex RH12 1BW
recycling centre.
Warning: Total current provided on DALI Bus must never exceed 250mA. If Do not dispose of with normal Tel: +44 (0)1942 719229

TECHNICAL SUPPORT using an additional power supply the DALI64PSU’s integrated power supply
must be disabled before external power is applied. PSU variants supply
household waste. Do not burn. Web: www.ex-or.com

+44 (0)1942 719229 150mA to the bus, never connect more than one PSU variant to the same
DALI Bus.