General EJX Series


FOUNDATION FieldbusTM
Specifications Communication
GS 01C25T02-01E

FOUNDATION fieldbus is the digital communication line


for the field instruments, whose signal is internationally
standardized by Fieldbus Foundation.
The Fieldbus bi-directional digital communication
performance makes possible for the field instruments
and the control devices to be a complete on-line
system, superseding the existing analog transmission
lines. EJX series differential pressure transmitters can
also measure and transmit the static pressure value.
Thus, based on FOUNDATION fieldbus specifications,
EJX Fieldbus models offer more flexible instrumenta-
tion through a higher level communication capability
and propose the cost reduction by multi-drop wirings
with less cables.

䊏 FEATURES

● Interoperability ● Alarm function


FOUNDATION fieldbus specifications grant the EJX Fieldbus models securely support various alarm
interoperability of the field instruments without functions, such as high/low alarm, notice of block
preparing designated softwares for the instrument. error, etc. based on FOUNDATION fieldbus specifica-
tions.
● Multi-sensing function
EJX110A Fieldbus model, for example, has three ● Self-diagnostic function
independent AI function blocks for differential The reliable self-diagnostic function detects the
pressure and static pressure. measuring range failure, the temperature·static
pressure failure, and the hardware failure, such as
● Function blocks pressure sensor, temperature sensor or amplifier
Arithmetic (AR), Integrator (IT) , Signal Characterizer assembly, etc.
(SC), and Input Selector (IS) function blocks are
available as standard function besides three AI ● Software download function(option)
function blocks. PID function block is also supported Software download function permits to update EJX
as an option. software via a FOUNDATION fieldbus.
Typical use of this function is to add new features
● Multi-signal display (Applicable when digital indicator such as function blocks and diagnostics to existing
is specified) devices.
Up to four I/O signals can be alternatively displayed
on the digital indicator. The block tags, the parameter
names, the process units and the statuses are also
displayed in order to show what the displayed signals
are.

● Link master function


EJX Fieldbus models support the Link Master
function. This function enables backup of network
manager and local control only by field devices.

Yokogawa Electric Corporation GS 01C25T02-01E


2-9-32 Nakacho, Musashino-shi, Tokyo, 180-8750 Japan ©Copyright Aug. 2004
Phone: 81-422-52-5690 Fax: 81-422-52-2018 5th Edition Sep. 2006
<<Contents>> <<Index>> 2
䊏 STANDARD SPECIFICATIONS Integral Indicator (LCD display)
5-digit Numerical Display, 6-digit Unit Display and Bar
For items other than those described below, refer graph. The indicator is configurable to display one or
to each General Specification sheet. up to four of the I/O signals periodically.
Functional Specifications:
Applicable Model: Functional specifications for Fieldbus communication
All DPharp EJX-A series, except for EJX910A conform to the standard specifications (H1) of
Multivariable Transmitter. FOUNDATION fieldbus.
For EJX910A Fieldbus communication type, refer to
Function Block:
GS 01C25R01-01E.
Output: Block Execution
Number Note
Digital communication signal based on FOUNDATION name time
fieldbus protocol. AI 3 30 mS For differential pressure, static
Supply Voltage: pressure and temperature
9 to 32 V DC for general use, flameproof type, Type SC 1 30 mS An output of Signal Characterizer
n, or nonincendive. block is a non-linear function of
9 to 24 V DC for intrinsically safe type Entity model the respective input. The function
9 to 17.5 V DC for intrinsically safe type FISCO model is determined by a table

Communication Requirements: IT 1 30 mS Integrator block integrates a


Supply Voltage: 9 to 32 V DC variable as a function of the
Current Draw: time or accumulates the counts
Steady state: 15 mA (max) IS 1 30 mS Input Selector block provides
Software download state: 24 mA (max) selection of up to eight inputs
and generate an output based
Response Time (for Primary Value) on the configured action
L capsule: 185 msec
M, H, A, B, C, D capsule: 150 msec AR 1 30 mS Arithmetic block permits simple
When amplifier damping is set to zero, and including use of popular measurement
math functions
dead time.
PID 1 45 mS Applicable when LC1 option is
Update Period:
specified
Differential Pressure: 100 msec T01.EPS
Static Pressure: 100 msec
Capsule Temperature: 1 sec LM Function:
Amplifier Temperature: 1 sec LM function is supported.

■ MODEL AND SUFFIX CODE

EJX䊐䊐䊐(䊐)-F䊐䊐䊐䊐-䊐䊐䊐䊐䊐/䊐
Output signal ... Digital communication (FOUNDATION Fieldbus protocol)

■ OPTIONAL SPECIFICATIONS
For items other than those described below, refer to each General Specification sheet.

Item Description Code


PID function PID control function LC1
Data configuration at
Software damping CC
factory *1
Software download function Based on FOUNDATION Fieldbus Specification(FF-883)
EE
Download class: Class1
T03.EPS
*1: Also see ‘Ordering Information’

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25T02-01E Sep. 22, 2006-00
<<Contents>> <<Index>> 3
■ OPTIONAL SPECIFICATIONS (For Explosion Protected type)
Item Description Code
FM Explosionproof Approval *1
Applicable Standard: FM3600, FM3615, FM3810, ANSI/NEMA 250
Explosionproof for Class I, Division 1, Groups B, C and D
Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G FF1
in Hazardous locations, indoors and outdoors (NEMA 4X)
Temperature class: T6 Amb. Temp.:–40 to 60°C (–40 to 140°F)
FM Intrinsically Safe and Nonincendive Approval *1
Applicable Standard: FM3600, FM3610, FM3611, FM3810, ANSI/NEMA 250, IEC60079-27
Intrinsically Safe for Class I,II, & III, Division 1, Groups A,B,C,D,E,F & G, Entity, FISCO.
Factory Mutual (FM) Class I, Zone 0, AEx ia IIC,
Enclosure: "NEMA 4X", Temp. Class: T4, Amb. Temp.: 40 to 60°C (40 to 140°F).
Intrinsically Apparatus Parameters :
[FISCO (IIC)] Ui=17.5 V, Ii=380 mA, Pi=5.32 W, Ci=1.76 nF, Li=0 µH
FS15
[FISCO (IIB)] Ui=17.5 V, Ii=460 mA, Pi=5.32 W, Ci=1.76 nF, Li=0 µH
[Entity] Ui=24 V, Ii=250 mA, Pi=1.2 W, Ci=1.76 nF, Li=0 µH
Nonincendive for Class I, Division 2, Groups A, B, C and D, NIFW, FNICO
Class I, Zone 2, Group IIC, NIFW, FNICO
Class II, Division 2, Groups F&G, and Class III, Division 1
Enclosure: “NEMA 4X”, Temp. Class: T4, Amb. Temp.: 40 to 60°C (40 to 140°F)
Nonincendive Apparatus Parameters : Vmax.= 32 V, Ci = 1.76 nF, Li = 0
ATEX (KEMA) Flameproof Approval *1
Applicable Standard: EN 50014, EN 50018, EN 50281-1-1
Certificate: KEMA 03ATEX2570
II 2G, 1D EExd IIC T4, T5, T6
Amb. Temp. (Tamb) for gas-proof: T4; 50 to 75C (58 to 167F),
T5; –50 to 80°C (–58 to 176°F), T6; 50 to 70C (58 to 158F) KF2
Max. process Temp. (Tp): T4; 120C (248F), T5; 100C (212F), T6; 85C (185F)
Max. surface Temp. for dust-proof:
T80°C (Tamb: –40 to 40°C, Tp: 80°C), T100°C (Tamb: –40 to 60°C, Tp: 100°C),
T120°C (Tamb: –40 to 80°C, Tp: 120°C)
CENELEC ATEX (KEMA) Intrinsically safe Approval *1
Certificate: KEMA 04ATEX1116X
CENELEC ATEX
Applicable standards: EN 50014, EN 50020, EN 50284, EN 50291-1-1
II 1GD EEx ia IIB/IIC T4 Amb. Temp. : 40 to 60°C (40 to 140°F)
Max. Process Temp. (Tp) : 120°C (248°F)
Max. Surface Temp. for dust-proof: T85°C (Tp:80°C), T100°C (Tp:100°C), T120°C (Tp:120°C) KS25
Enclosure : IP66 and IP67
[FISCO (IIC)] Ui=17.5V, Ii=380mA, Pi=5.32W, Ci=1.76nF, Li=0µH
[FISCO (IIB)] Ui=17.5V, Ii=460mA, Pi=5.32W, Ci=1.76nF, Li=0µH
[Entity] Ui=24V, Ii=250mA, Pi=1.2W, Ci=1.76nF, Li=0µH
CENELEC ATEX Type n Approval *1
Applicable standards: EN 50021, EN 60529
KN25
EEx nL IIC T4 Amb. Temp. : 40 to 60°C (40 to 140°F), Enclosure : IP66 and IP67
Ui=32V, Ci=1.76nF, Li=0
CSA Explosionproof Approval *2
Certificate: 1589701
[For CSA C22.2]
Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25, C22.2
No.30, C22.2 No.94
Explosion-Proof for Class I, Groups B, C and D.
Dust-ignitionproof for Class II/III, Groups E, F and G.
When installed in Division 2, “SEAL NOT REQUIRED”
Canadian Standards Enclosure: TYPE 4X, Temp. Code: T6...T4 CF1
Association (CSA) Max.Process Temp.: T4;135°C (275°F), T5;100°C (212°F), T6; 85°C (185°F)
Amb.Temp.: 50 to 80°C (58 to 176°F) for T5 & T4, 50 to 75 °C (58 to 167°F) for T6
[For CSA E60079]
Applicable Standard: CAN/CSA E60079-0, CAN/CSA E60079-1
Flameproof for Zone 1, Ex d IIC T6...T4 Enclosure: IP66 and IP67
Max.Process Temp.: T4;120°C (248°F), T5;100°C (212°F), T6; 85°C (185°F)
Amb.Temp.: 50 to 75°C (58 to 167°F) for T4, 50 to 80 °C (58 to 176°F) for T5,
50 to 70°C (58 to 158°F) for T6
T02.EPS
Contact Yokogawa representative for the codes indicated as ‘-’.
*1: Applicable for Electrical connection code 2, 4, 7 and 9.
*2: Applicable for Electrical connection code 2 and 7.

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25T02-01E Sep. 22, 2006-00
<<Contents>> <<Index>> 4
<Ordering Information> Calibration range:
Specify the following when ordering Higher value 1000
1. Model, suffix codes, and optional codes Lower value 50
2. Calibration range and unit (XD_SCALE of AI1); Calibration unit: mmH2O
1) Calibration range can be specified with range Output range:
value specifications up to 5 digits (excluding any Higher value 100
decimal point) for low or high range limits within Lower value 0
the range of –32000 to 32000. Unit of output range: %
2) Specify only one unit from the table, ‘Factory Output mode: Indirect Linear
Setting’.
3. Output mode (L_TYPE of AI1); Explanation of Fieldbus parameters:
Select ‘Direct’, ‘Indirect Linear’ or ‘Indirect SQRT’. (1) XD_SCALE: Set the input value from Transducer
4. Output scale and unit (OUT_SCALE of AI1); block (input range of sensor) which
When digital indicator is required, the scale range corresponds to 0% value and 100% value
can be specified with range limit specifications up to of the calculation in the AI function block.
5 digits (excluding any decimal point) for low or high In the case of EJX series, the value set as
range limits within the range of –32000 to 32000. Unit calibration range should be entered to this
display consists of 6-digit, therefore, if the specified parameter.
scaling unit excluding ‘/’ is longer than 6-characters, (2) OUT_SCALE: Output scaling parameter. Set the
the first 6 characters will be displayed on the unit output value which corresponds to 0%
display. When L_TYPE is Direct, these setting does value and 100% value of the calculation in
not affect the output of the AI block the AI function block. In the case of
5. Tag Number; EJXseries, the value set as output scale
Specify software tag (up to 30 letters) to be written on should be entered to this parameter.
the amplifier memory and Tag number (up to 18 When integral indicator is required, this
letters) to be engraved on the tag plate separately. output is shown on LCD.
6. Node Address (3) L_TYPE: Determines if the values passed by the
7. Operation Functional Class tranducer block to the AI block may be
Select ‘BASIC’ or ‘LINK MASTER’ used directly (Direct) or if the value is in
different units and must be converted
[When /CC option is specified] linearly (Indirect Linear) or with square
8. Software damping (PRIMARY_VALVE_FTIME of TB); root (Indirect SQRT), using the input
Specify software damping : 0.00 to 100.00 (sec) range defined by XD_SCALE and the
Example; When 50 to 1000 mmH2O for calibration associated output range (OUT_SCALE).
range and 0 to 100% output range is required,
specify the values as follows: < Related Instruments >
The customer should prepare instrument maintenance
tool, terminator, fieldbus power supply etc.
<Reference>
FOUNDATION; Trademark of Fieldbus Foundation.
< Factory Setting >

Tag Number (Tag plate) As specified in order


Software Tag (PD_TAG) ‘PT2001’ unless otherwise both Tag Number and
Software Tag specified in order
Node Address ‘0xF5’ unless otherwise specified in order
Operation Functional Class ‘BASIC’ or as specified
Primary value *1 Output Mode (L_TYPE) ‘Direct’ unless otherwise specified in order
Calibration Range (XD_SCALE) Lower/Higher As specified in order
Range Value
Calibration Range Unit Selected from mmH2O, mmH2O(68°F), mmHg, Pa, hPa,
kPa, MPa, mbar, bar, gf/cm2, kgf/cm2, inH2O,
inH2O(68°F), inHg, ftH2O, ftH2O(68°F) or psi.
(Only one unit can be specified)
Output Scale (OUT_SCALE) Lower/Higher ‘0 to 100%’ unless otherwise specified.
Range Value
Software Damping *2 ‘2 seconds’ or as specified in order
Static pressur display range ‘0 to 25 MPa’ for M and H capsule and ‘0 to 16 MPa’ for L
capsule, absolute value. Measuring high pressure side.
T04.EPS
*1: Primary means differential pressure in case of differential presser transmitters and pressure in case of pressure
transmitters.
*2: To specify this item, /CC option is required.

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25T02-01E Sep. 22, 2006-00
Subject to change without notice.