䊏 FEATURES
EJX䊐䊐䊐(䊐)-F䊐䊐䊐䊐-䊐䊐䊐䊐䊐/䊐
Output signal ... Digital communication (FOUNDATION Fieldbus protocol)
■ OPTIONAL SPECIFICATIONS
For items other than those described below, refer to each General Specification sheet.
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25T02-01E Sep. 22, 2006-00
<<Contents>> <<Index>> 3
■ OPTIONAL SPECIFICATIONS (For Explosion Protected type)
Item Description Code
FM Explosionproof Approval *1
Applicable Standard: FM3600, FM3615, FM3810, ANSI/NEMA 250
Explosionproof for Class I, Division 1, Groups B, C and D
Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G FF1
in Hazardous locations, indoors and outdoors (NEMA 4X)
Temperature class: T6 Amb. Temp.:–40 to 60°C (–40 to 140°F)
FM Intrinsically Safe and Nonincendive Approval *1
Applicable Standard: FM3600, FM3610, FM3611, FM3810, ANSI/NEMA 250, IEC60079-27
Intrinsically Safe for Class I,II, & III, Division 1, Groups A,B,C,D,E,F & G, Entity, FISCO.
Factory Mutual (FM) Class I, Zone 0, AEx ia IIC,
Enclosure: "NEMA 4X", Temp. Class: T4, Amb. Temp.: 40 to 60°C (40 to 140°F).
Intrinsically Apparatus Parameters :
[FISCO (IIC)] Ui=17.5 V, Ii=380 mA, Pi=5.32 W, Ci=1.76 nF, Li=0 µH
FS15
[FISCO (IIB)] Ui=17.5 V, Ii=460 mA, Pi=5.32 W, Ci=1.76 nF, Li=0 µH
[Entity] Ui=24 V, Ii=250 mA, Pi=1.2 W, Ci=1.76 nF, Li=0 µH
Nonincendive for Class I, Division 2, Groups A, B, C and D, NIFW, FNICO
Class I, Zone 2, Group IIC, NIFW, FNICO
Class II, Division 2, Groups F&G, and Class III, Division 1
Enclosure: “NEMA 4X”, Temp. Class: T4, Amb. Temp.: 40 to 60°C (40 to 140°F)
Nonincendive Apparatus Parameters : Vmax.= 32 V, Ci = 1.76 nF, Li = 0
ATEX (KEMA) Flameproof Approval *1
Applicable Standard: EN 50014, EN 50018, EN 50281-1-1
Certificate: KEMA 03ATEX2570
II 2G, 1D EExd IIC T4, T5, T6
Amb. Temp. (Tamb) for gas-proof: T4; 50 to 75C (58 to 167F),
T5; –50 to 80°C (–58 to 176°F), T6; 50 to 70C (58 to 158F) KF2
Max. process Temp. (Tp): T4; 120C (248F), T5; 100C (212F), T6; 85C (185F)
Max. surface Temp. for dust-proof:
T80°C (Tamb: –40 to 40°C, Tp: 80°C), T100°C (Tamb: –40 to 60°C, Tp: 100°C),
T120°C (Tamb: –40 to 80°C, Tp: 120°C)
CENELEC ATEX (KEMA) Intrinsically safe Approval *1
Certificate: KEMA 04ATEX1116X
CENELEC ATEX
Applicable standards: EN 50014, EN 50020, EN 50284, EN 50291-1-1
II 1GD EEx ia IIB/IIC T4 Amb. Temp. : 40 to 60°C (40 to 140°F)
Max. Process Temp. (Tp) : 120°C (248°F)
Max. Surface Temp. for dust-proof: T85°C (Tp:80°C), T100°C (Tp:100°C), T120°C (Tp:120°C) KS25
Enclosure : IP66 and IP67
[FISCO (IIC)] Ui=17.5V, Ii=380mA, Pi=5.32W, Ci=1.76nF, Li=0µH
[FISCO (IIB)] Ui=17.5V, Ii=460mA, Pi=5.32W, Ci=1.76nF, Li=0µH
[Entity] Ui=24V, Ii=250mA, Pi=1.2W, Ci=1.76nF, Li=0µH
CENELEC ATEX Type n Approval *1
Applicable standards: EN 50021, EN 60529
KN25
EEx nL IIC T4 Amb. Temp. : 40 to 60°C (40 to 140°F), Enclosure : IP66 and IP67
Ui=32V, Ci=1.76nF, Li=0
CSA Explosionproof Approval *2
Certificate: 1589701
[For CSA C22.2]
Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25, C22.2
No.30, C22.2 No.94
Explosion-Proof for Class I, Groups B, C and D.
Dust-ignitionproof for Class II/III, Groups E, F and G.
When installed in Division 2, “SEAL NOT REQUIRED”
Canadian Standards Enclosure: TYPE 4X, Temp. Code: T6...T4 CF1
Association (CSA) Max.Process Temp.: T4;135°C (275°F), T5;100°C (212°F), T6; 85°C (185°F)
Amb.Temp.: 50 to 80°C (58 to 176°F) for T5 & T4, 50 to 75 °C (58 to 167°F) for T6
[For CSA E60079]
Applicable Standard: CAN/CSA E60079-0, CAN/CSA E60079-1
Flameproof for Zone 1, Ex d IIC T6...T4 Enclosure: IP66 and IP67
Max.Process Temp.: T4;120°C (248°F), T5;100°C (212°F), T6; 85°C (185°F)
Amb.Temp.: 50 to 75°C (58 to 167°F) for T4, 50 to 80 °C (58 to 176°F) for T5,
50 to 70°C (58 to 158°F) for T6
T02.EPS
Contact Yokogawa representative for the codes indicated as ‘-’.
*1: Applicable for Electrical connection code 2, 4, 7 and 9.
*2: Applicable for Electrical connection code 2 and 7.
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25T02-01E Sep. 22, 2006-00
<<Contents>> <<Index>> 4
<Ordering Information> Calibration range:
Specify the following when ordering Higher value 1000
1. Model, suffix codes, and optional codes Lower value 50
2. Calibration range and unit (XD_SCALE of AI1); Calibration unit: mmH2O
1) Calibration range can be specified with range Output range:
value specifications up to 5 digits (excluding any Higher value 100
decimal point) for low or high range limits within Lower value 0
the range of –32000 to 32000. Unit of output range: %
2) Specify only one unit from the table, ‘Factory Output mode: Indirect Linear
Setting’.
3. Output mode (L_TYPE of AI1); Explanation of Fieldbus parameters:
Select ‘Direct’, ‘Indirect Linear’ or ‘Indirect SQRT’. (1) XD_SCALE: Set the input value from Transducer
4. Output scale and unit (OUT_SCALE of AI1); block (input range of sensor) which
When digital indicator is required, the scale range corresponds to 0% value and 100% value
can be specified with range limit specifications up to of the calculation in the AI function block.
5 digits (excluding any decimal point) for low or high In the case of EJX series, the value set as
range limits within the range of –32000 to 32000. Unit calibration range should be entered to this
display consists of 6-digit, therefore, if the specified parameter.
scaling unit excluding ‘/’ is longer than 6-characters, (2) OUT_SCALE: Output scaling parameter. Set the
the first 6 characters will be displayed on the unit output value which corresponds to 0%
display. When L_TYPE is Direct, these setting does value and 100% value of the calculation in
not affect the output of the AI block the AI function block. In the case of
5. Tag Number; EJXseries, the value set as output scale
Specify software tag (up to 30 letters) to be written on should be entered to this parameter.
the amplifier memory and Tag number (up to 18 When integral indicator is required, this
letters) to be engraved on the tag plate separately. output is shown on LCD.
6. Node Address (3) L_TYPE: Determines if the values passed by the
7. Operation Functional Class tranducer block to the AI block may be
Select ‘BASIC’ or ‘LINK MASTER’ used directly (Direct) or if the value is in
different units and must be converted
[When /CC option is specified] linearly (Indirect Linear) or with square
8. Software damping (PRIMARY_VALVE_FTIME of TB); root (Indirect SQRT), using the input
Specify software damping : 0.00 to 100.00 (sec) range defined by XD_SCALE and the
Example; When 50 to 1000 mmH2O for calibration associated output range (OUT_SCALE).
range and 0 to 100% output range is required,
specify the values as follows: < Related Instruments >
The customer should prepare instrument maintenance
tool, terminator, fieldbus power supply etc.
<Reference>
FOUNDATION; Trademark of Fieldbus Foundation.
< Factory Setting >
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25T02-01E Sep. 22, 2006-00
Subject to change without notice.