Schroedahl Arv
Schroedahl Arv
Schroedahl Arv
Pump Protection
ENGINEERING LETTER
Pump Protection
Introducion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 5
3.0 Schematic arrangement for control valve solution with venturi nozzle
ENGINEERING LETTER
Pump Protection
5
ENGINEERING LETTER
Pump Protection
Introduction
Because of necessary cost reductions and a higher degree of system efficiency and risk management, a
reliable system that ensures a minimum flow through the pump is an essential requirement, especially for
high pressure applications.
Besides protecting the pump against overheating, a well-engineered, modulating, controlled bypass
system improves the stable operation of the complete system. The system itself is usually a closed loop
application and therefore consists of a suction and recirculation line from the tank and back to the tank.
The materials used for the valves are carefully chosen in order to minimise corrosion and erosion under
high velocity conditions or special medium applications.
Important note
Especially for high pressure applications, all equipment including the valves should fulfil the following
requirements:
Reliable operation
Production stops are very costly. A higher initial investment will pay off in the long run than opting for the
most inexpensive solution (inexpensive can be very expensive!).
ENGINEERING LETTER
Pump Protection
Tank
Also, a pressure reduction system has to be 150-200 m3/h). At a pump head of 2150 m the
provided with orifice plates that are subject to ca- extra power consumption of the larger pumps
vitation and wear. would be 950 kW per hour.
An additional check valve is needed! In continuous operation (say 300 days per year)
Pay attention to saving costs for high pressure and energy costs of 3 cents per kW/h, the extra
applications! energy costs would be roughly $200,000.
In a typical high pressure injection system with a This system is therefore very costly and it is bad
normal flow of 625 m3/h (per pump), the bypass engineering practice.
flow required is a minimum of 125 m3/h (usually
7
ENGINEERING LETTER
Pump Protection
Tank
A flow sensor in the suction line, which senses the The check valve is located on the pump outlet
low flow conditions to the pump. Also available in to prevent back flow if the pump is not running.
a material as specified. Again, the availability of the correct material for this
A control loop which transmits the signal from check valve should be taken into consideraton.
the flow sensor to the control valve actuator. This system has been applied (and still is) in many
This requires an air or electrical supply system and high pressure systems. It offers a good control
requires regular maintenance and calibration. of the bypass flow but has some drawbacks
when compared to the system of an Automatic
An additional check valve is needed!
Recirculation Valve.
8
ENGINEERING LETTER
Pump Protection
The Automatic Recirculation Valve, manufactured years, combines the 4 functions as outlined earlier
and marketed by SCHROEDAHL for almost 50 in one simple unit (see below).
Tank
Q
P2
Suction
tank
QA Qmin
PA PN
Q P
Bypass
PV
Manual-start-up*
P1
Pump
*Manual-start-up on request/optional
Explanation
and a special control device for the minimum flow
The Automatic Recirculation Valve (ARV) pro-
recirculation (the bypass control system). The
tects centrifugal pumps against overheating and
general valve functioning is related to the process
cavitation problems by automatically maintaining a
flow quantity – all SCHROEDAHL ARVs are flow
minimum flow when the system flow is in low load
sensitive.
condition. The application itself is usually a closed
loop application and consists of a suction and Simplified function explanation: An increasing
recirculation line from the tank and back to the process flow will automatically reduce the bypass
tank. Typically the ARV is directly mounted on the flow. At a certain level of process flow (the valve
pump discharge flange. switch point), the recirculating bypass is closed.
ENGINEERING LETTER
Pump Protection
Definitions:
Q100 - (m3/h, US GPM) Rated process flow (for ARV valve design)
QM - (m3/h, US GPM) Pump minimum flow (for ARV bypass design)
HM - (m, feed) Pump differential pressure at minimum flow
Pv - (bar g, psi g) Pump suction pressure
Pn - (bar g, psi g) Bypass back pressure (at bypass flange of ARV)
100 %
Pump head (in %)
Minimum flow
point Valve bypass
80 % PM (QM; HM) switch point SP
60 %
40 %
20 %
A) Special application
0%
0% 20 % 40 % 60 % 80 % 10 % 120 % 140 %
ENGINEERING LETTER
Pump Protection
A) Normal Application is defined when the process Special: The Special Application (B) (> 120 bar
flow is typically not below 40% of the rated flow / > 1740 psi) needs information about the static
(beside short start-up phases). and dynamic bypass back pressure Pn (stat.
B) Special Application is defined when the system / dyn.) as well as a check about the correct
flow range is from 0% to 100% of the range bypass piping system with incorporation of the
specified. If the pump pressure is also greater medium temperature rise at minimum flow.
than 120 bar / 1740 psi, then a Back Pressu- B) High Pressure Applications
re Valve (BPV) is required, as a simple orifice
For applications with ≥ 120 bar / > 1740 psi
cannot ensure that the back pressure Pn will
differential pressure, a Back Pressure Valve
be a minimum of 4 bar / 58 psi higher than the
(BPV) is recommended. The BPV should
saturation pressure (guide value, value range is
be installed directly before the inlet into
4 to 10 bar / 58 to 145 psi).
the tank to keep the pressure in the
recirculation line (Pn) at a minimum of 4 bar
Note:
/ 58 psi higher (rough thermodynamic safety
A) Differentiation between Normal and Special: margin, maximum up to 10 bar / 145 psi
Normal: An application will be classified as possible and confirmed by SCHROEDAHL).
Normal (A), when no operation range informa-
tion is given.
ENGINEERING LETTER
Pump Protection
ARV
Tank
Note: Vertical installaion of the ARV directly on the pump discharge is best!
Installation Conditions
• Vertical installation is preferred, horizontal on •
Downstream of the bypass should be in a
request. straight pipe run of 3 x DN (no elbows).
• Preferred installation is directly on the pump • Standard filter mesh size should be 0.3 to
discharge flange. Otherwise, if possible, no 0.5 mm (pump suction side). For commission-
farther downstream than about 3 metres after ing we recommend using a smaller mesh size
the pump (depends on the application). (of 0.1 mm).
• The recommended straight pipe run at the inlet •
After commissioning a valve inspection is
should then be at least 2 x DN (no elbows at recommended.
the inlet).
13
ENGINEERING LETTER
Pump Protection
High Low
pressure pressure
piping piping possible
BPV
ENGINEERING LETTER
Pump Protection
SUL
• Max. class 300 / PN 63
• Cast body
• Economic and efficient design
TDL
• Max. class 900 / PN 160
• Forged body
• Check valve in the bypass
• Venturi ring design
TDM
• Max. class 2500 / PN 400
• Forged body
• High pressure reduction bypas device
(up to 5 stages)
• Non-return function in bypass
MRK
• Max. class 4500 / PN 640
• Forged body
• High pressure reduction bypass
system for pressure reduction
up to 500 bar.
15
ENGINEERING LETTER
Pump Protection
100 1,100 R
90
0,900
80
P
Pressure drop (in bar)
70
P
Main flow (in m3/h)
0,700
60
Switch point
50 SP 0,500
40
Bypass flow
0,300
30
R Pump flow P
20
Bypass 0,100
10
Process flow R
0
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Pressure drop
Lift of check valve (in %)
Above flow curve shows the valve behaviour for the flow reduction process (shut-down event).
Example curve with design conditions: 30 % of the rated pump flow, the valve switch point is
about 25 % higher than the specified minimum flow:
Q100% = 100 m3/h
Q min = 30 m3/ h SP ~ Qm x 1,25
Valve switch point (SP) This very low switch point is one of the advantages
For normal operation conditions with TDM-Valves, of SCHROEDAHL valves!
where the bypass flow is not higher than about
16
ENGINEERING LETTER
Pump Protection
Please refer to the following principal pump curve according to the typical pump curve (pressure
to understand the characteristics of an ARV head over pump flow).
100%
Pump head (in %)
Minimum flow
point Valve bypass
80% PM (QM; HM) switch point SP
60%
40%
20%
0%
0% 20% 40% 60% 80% 10% 120% 140%
Definition
For the curve, the normal operation point (rated Usually, the system operation is between 40% to
point) is stated as the 100% case with H = 100% 100 % and therefore above the valve switch point
at Q = 100% (see graph above: normal operation).
ENGINEERING LETTER
Pump Protection
2300
Min. speed curve
2100
1900
1700
1500
1300
1100
900
700
500
0 50 100 150 200 250 300 350 400 450 500 550
Flow (in m ) 3
Note: Please also inform us about the load data if a booster pump with constant speed is installed.
18
ENGINEERING LETTER
Pump Protection
Materials
Installation Conditions
ENGINEERING LETTER
Pump Protection
Data Sheet
ARV Data Sheet
Valve Design
Connection Size Class Standard Schedule Surface
P Inlet
R Outlet
B Bypass
A Start-Up
Installation P-R
Painting
Certificates
Design Data
Design Temp. Design Pressure
Material
Body Internals Gaskets
Medium
Medium
Operating Temp. min. max.
S.G. min. max.
Operating Data
Case 1 Case 2 Case 3
QM
HM
Q100
H100
Qmax
Hmax
H0
QA
HA
pv
pN
DpBypass
kv-Bypass
RPM
Remarks
SCHROEDAHL
SCHROEDAHL GmbH GmbH
AlteSchönenbacher
Alte Schönenbacher
Str. 4 · 51580Straße 4 | 51580
Reichshof-Mittelagger Reichshof-Mittelagger
Telefon +49 2265 9927-0 · Telefax +49 2265 9927-927
circor.com
eMail: | www.schroedahl.com
schroedahl@circor.com · www.schroedahl.com Version 1.07 / 20.03.2019
ENGINEERING LETTER
Pump Protection
SCHROEDAHL GmbH
Alte Schönenbacher Straße 4
51580 Reichshof-Mittelagger
Telephone + 49 22 65 99 27 - 0
Fax + 49 22 65 99 27 - 927
www.schroedahl.com
schroedahl@circor.com