TemperatureControllerAI208v78 191003
TemperatureControllerAI208v78 191003
TemperatureControllerAI208v78 191003
"oFF" to "on", then press to active the auto-tuning process. During auto tuning,
L Relay contact output module (Capacity: 2A/250VAC, normal open)
the instrument executes on-off control. After 2-3 times of on-off action, the instrument
G SSR voltage output module (30mA/5VDC)
will obtain the optimal control parameter value. If you want to escape from auto tuning
ARTIFICIAL INTELLIGENCE TEMPERATURE Part 4 indicates Auxiliary alarm output status, press and hold the key for about 2 seconds until the "At" parameter appear
CONTROLLER N (or none) no module installed again. Change "At" from "on" to "oFF", press to confirm, then the auto tuning
L0 Relay contact output module (Capacity: 2A/250VAC, normal open / normal close)
AI-207/208 (V7.8) User Manual process will be cancelled.
L2 Relay output module omron brand(1A/250VAC) Note : If the setpoint is different, the parameters obtained from auto-tuning are possible
L3 Dual relay Output module (Capacity: 2A/250VAC, normal open, support AU1 different. So you'd better set setpoint to an often-used value or middle value first, and
and AU2 alarm output) then start auto-tuning. Depending on the system, the auto-tuning time can be from
Remark: For D1-size instrument, OUTP (output module) is SSR mounted with
several seconds to several hours.
driving voltage 30mA/5VDC. AU1 is also selectable as relay alarm ouput
I. Main features (NO+NC, 2A/250VAC). D1 is not in modular design.
PV PV PV PV
auto tuning
III. Technical Specification
2 seconds
industry, oven, furnace, lab equipment, cooling/heating equipments. Easy to AI RUN STOP
AI
AI RUN STOP
AI
AI RUN STOP
AI
AI RUN STOP
AI
2 seconds
Part 1 (Series) Part 2 (Size) Part 3 (Oupt) Part 4 (AUX)
SV SV SV SV
2 seconds
AI RUN STOP AI RUN STOP AI RUN STOP AI RUN STOP
AI AI AI AI
Part 1 stands for Model series When powered on, it shows the basic display status, upper window displays real
AI-207, standard artificial intelligence temperature controller 0.5%FS±1℃ accuracy. process value (PV) while lower window displays the set value (SV). If the real
value overruns measure range(thermocouple breaks for example), upper window
VI. Parameters and settings
1℃ display resolution.
will display "orA" and the highest and lowest values, at this time, controller will Field parameter table (Press and hold for 2 seconds to access)
AI-208, temperature controller 0.3%FS±1℃ accuracy. 1℃ or 0.1℃ display
automatically stop controlling the output. Setting
resolution. Code Name Description
In controller's face, basically there are four LED lights,OP1,AU1,AU2,RUN which Range
Part 2 stands for Front panel dimension respectively stand for output, first alarm, second alarm, and working condition. High limit Alarm on when PV (Process Value) >HIA;
HIA
alarm alarm off when PV<HIA-AHY 0~999℃
Size
Front Panel Cut Out Depth Behind V. Operation Description Lower limit Alarm on when PV (Process Value) <LoA;
width×height width×height Mounting Surface LoA 0~999℃
1.Change given Set Value: alarm alarm off when PV>LoA-AHY
A 96×96mm 92×92mm 100mm In basal display status, if the parameter lock "Loc" isn't locked, we can set setpoint Deviation Alarm on when PV-SV>HdA; alarm off
HdA -199~999℃
high alarm when PV-SV<HdA-AHY
(SV) by pressing 、 、 . Press key to decrease the value, key
A1 96×96mm 92×92mm 70mm
Deviation low Alarm on when PV-SV<LdA; alarm off
to increase the value, and key to move to the digit expected to modify. Keep LdA -199~999℃
B 160×80mm 152×76mm 100mm alarm when PV-SV>HdA-AHY
pressing or the speed of decreasing or inscreasing value get quick.
Loc=0, allowed to modify parameters
D 72×72mm 68×68mm 95mm HIA,LoA,HdA,LdA and SV.
PV PV PV
F1 96×48mm 92×45mm 70mm When AI artificial intelligence control method is chosen (CtrL=AI), the PID parameters Avoid frequent alarm on-off action because
can be obtained by running auto-tuning. In basal display status, press for 2 AHY Hysteresis of the fluctuation of PV 0~200
seconds, the "At" parameter will appear. Press to change the value of "At" from usually sets to AHY=2
AOP is to define the output place of CHY is used for on-off control, if PV > SV,
Control
HIA,LOA,HdA as following: CHY output turns off; PV<SV-CHYS, output 0~200 Wiring graph for instruments with dimension A1, E1 and F1:
Hysteresis
AOP = C B A turns on.
HdA + LdA LoA HIA ;
Input Input
A.B value range is 0-2,0 or other number InP InP
spec spec Note:The graph suits for
means never alarm. 1 and 2 means the
alarms come out from AU2 and AU2. C 0 K 3 T upright instruments with
Input
value has below definitions: InP 4 E 5 J 0~21 dimension A1 or E1
specification
C HdA LdA 6 Spare 7 N
Alarm Output 0 - -
AOP assignment 0~922 8-20 Spare 21 Pt100
1 AU1 -
2 AU2 - dPt For instruments with
(only
5 AU1 AU1 Resolution To choose display resolution, 0 or 0.0 0 dimension B1 or F1
for AI-
6 AU2 AU1 208) size,just clockwise rotate
7 - AU1 the graph 90 degree.
Scb is used to make input shift to compensate
8 - AU2 the error produced by sensor or input signal.
Scb Input Shift -99 ~ +99
9 AU1 AU2 PV_after_compensation= PV_before_
eg:AOP=901 means , HIA ,HdA gives compensation + Scb. Wiring graph for D dimension(72X72mm)instruments:
output from AU1,LdA from AU2. The value of FIL will determine the ability of
o n F : O n - o ff c o n t r o l W h e n P V = S V, filtering noise.
output stop, When PV < SV-CHY,start When a large value is set, the measurement
output input is stabilized but the response speed is
AI : AI PID control, high precision and the slow. Generally, it can be set to 1 to 3.
CrL Control mode AI
output time proportion can set by parameter
If great interference exists, then you can
Ctl. FIL PV input filter 0~40
PID: Standard PID algorithm with anti- increase parameter "FIL" gradually to make
integral-saturation function. momentary fluctuation of measured value less
than 2 to 5.
Fon: Mode frozen. Changing mode (Run/stop)
run from panel is prohibited. When the instrument is being metrological
(only Running Run: Run Mode. Press to verified, "FIL" s can be set to 0 or 1 to shorten
Fon the response time.
for AI- mode switch to Stop Mode.
208) Stp: Stop Mode. Press to Selection of
switch to Run Mode Fru power 50Cmeans 50Hz,display unit is ℃。
rE:Reverse acting.Increase in measured (only frequency 50F,means 50Hz,display unit is ℉。 Wiring graph for D1/D2 dimension(48X48mm)instruments:
50C
variable causes a decrease in the output,such for AI- and 60Cmeans 60Hz,display unit is ℃。
as heating control. 208) temperature 60Fmeans 60Hz, display unit is ℉。
dr:Direct acting.Increase in measured scale
variable causes an increase in the output,such
Acting as refrigerating control. Upper limit of Maximum value that SV allowed to be.When
Act rE SPH 0~999℃
method rEb:Reverse acting with low limit alarm SV SPH=400,the SV range will 0~400℃ .
and deviation low alarm blocking at the
beginning of power on.
drb:Direct acting with high limit alarm VII. Installation and wiring
and deviation high alarm blocking at the
beginning of power on. Wiring graph for instruments with dimension A, B, E and F:
Proportional Note:The graph suits for Note:
P Proportional band in PID with unit℃ 1~999 1. After the connection of thermocouple with compensation wire and the cover of
band upright instruments with
Time of Time of integral in PID.No integral effect 0~999 dimension A or E plastic panel, it cannot change with common wire. Pay attention to the correct
I
Integral when I=0 Sec connection of wire and lead.
Time of Time of derivative in PID.No derivative 0~999 2.As CE requires, please use product that can stand over 2300V when controller is
d
Derivative effect when d=0 Sec connected with extra Solid state relay.
Small value can improve control accuracy.
For SSR output, generally 0.5 to 3 seconds.
For Relay output, generally 15 to 40 For instruments with
seconds, because small value will cause the dimension B or F size,just
Control frequent On-Off of mechanical switch and 0.5~300
Ctl clockwise rotate the graph
period shorten its service life. CtI is recommended Sec
to be 1/4 - 1/10 of derivative time. When 90 degree.
control under on-off control,Ctl use as restart
delay time affer off,for protect compressor
www.yudian.com Yudian Copyright 1991-2018
application.