FlowMaster User Manual V2.0
FlowMaster User Manual V2.0
FlowMaster User Manual V2.0
User Manual
Rev 2.0
Safety First
Warning: Several safety rules must be followed throughout the operation of
FlowMaster. Severe damages will occur to the product or personnel in charge if
the safety rules are not strictly obeyed.
Please note:
Safety precautions must be followed and adhered at all times. There are more
safety rules will be listed in next few pages in the manual.
2
Rev 2.0
CONTENT
1. INTRODUCTION 4
1.1 Product Description 4
1.2 Available Language 5
1.3 FlowMaster Connection 6
1.4 Basic Pin Connection 7
2. DISPLAY 11
2.1 Main Display 11
2.2 Information Display 12
2.3 Alarm Display 15
3. SETUP 17
3.1 Configuration 18
3.2 Alarm Setup 21
3.3 Analog Setting 22
3.4 Program Setting 23
3.5 Calibration 24
4. CONTROL PROCEDURES 25
4.1 Analog Mode aka Remote Control 26
4.2 Program Mode aka Local Control 27
4.3 Manual Mode 29
4.4 Factory Default Setting 30
4.5 Factory Default Password 30
5. INSTALLATION 31
5.1 Connection of Cable 32
5.2 Dimension of Flow Master 34
6. SPECIFICATIONS 34
7. FLOWMASTER WARRANTY 35
3
Rev 2.0
1.0 INTRODUCTION
1.1 Product Description
4
Rev 2.0
English
German
Simplified Chinese
Japanese
French
Spanish
5
Rev 2.0
Example of display page for one (1) UltimateValve & four (4) UltimateValve:
1 UltimateValve 4 UltimateValve
6
Rev 2.0
7
Rev 2.0
The signal names corresponding to the connecting terminals are as shown in the
following diagram.
Note that valve1, valve 2, valve3 and valve4 in the signal names are indicating
the respective valves that are installed with this controller, as a maximum of four
(4) valves can be connected to a single controller. The use of connecting terminal
will be depends on the number of valves that are connected, for example if only
one (1) valve is installed, the terminal of which contains the name of valve1 will
only be use, whilst terminal of valve2 to valve4 will be non-applicable for this
case.
For Digital Inputs section, DI1 – DI4 are correspond to the input valve power on
where each represent valve 1 to valve 4 respectively. DI5 – DI10 are correspond
to product select bit or known as recipe/program, it is listed out in table form in
section 4.2.
For Digital Outputs section, DO1 – DO4 are correspond for each respective
valve output indicator. DO5 – DO8 are correspond to the alarm output of each
valve, the alarming type is listed out in section 3.2.
For Analog Inputs section, AI1 – AI4 are the input terminal of each respective
valve to control the flowrate of the valve from 0 – 10V, which could be
correspond to specific flowrate, for example 0 – 10 V are correspond to 1 – 13 kg
respectively, depends on the maximum flowrate the valve could achieve.
For Analog Outputs section, AO1 – AO4 are the output terminal of each
respective valve to provide feedback signal back to the PLC to display the real
time actual flowrate.
8
Rev 2.0
Digital Inputs
DI1 Valve1 Enable Input
DI2 Valve2 Enable Input
DI3 Valve3 Enable Input
DI4 Valve4 Enable Input
DI5 Product Select Bit 5
DI6 Product Select Bit 4
DI7 Product Select Bit 3
DI8 Product Select Bit 2
DI9 Product Select Bit 1
DI10 Product Select Bit 0
DIC Digital Inputs Ground
Digital Outputs
DO1 Valve1 On Indicator Output
DO2 Valve2 On Indicator Output
DO3 Valve3 On Indicator Output
DO4 Valve4 On Indicator Output
DO5 Valve1 Alarm
DO6 Valve2 Alarm
DO7 Valve3 Alarm
DO8 Valve4 Alarm
DOC Digital Outputs Ground
Analog Inputs
AI1 Flowrate Analog Input 1 (Valve1)
AI2 Flowrate Analog Input 2 (Valve2)
AI3 Flowrate Analog Input 3 (Valve3)
AI4 Flowrate Analog Input 4 (Valve4)
AIC Analog Inputs Ground
9
Rev 2.0
Analog Outputs
AO1 Flowrate Feedback Analog Output 1 (Valve1)
AO2 Flowrate Feedback Analog Output 2 (Valve2)
AO3 Flowrate Feedback Analog Output 3 (Valve3)
AO4 Flowrate Feedback Analog Output 4 (Valve4)
AOC Analog Outputs Ground
10
Rev 2.0
2.0 DISPLAY
11
Rev 2.0
FlowMaster Information
Contact Us
UltimateValve Information
Each information pages have been displayed in the following page of this manual.
12
Rev 2.0
FlowMaster Information
13
Rev 2.0
UltimateValve Information
Contact Us
14
Rev 2.0
Alarm
To check the alarm information in terms of date, time and faulty
message
– To proceed to alarm history page
Alarm History
To view back the alarm history
15
Rev 2.0
16
Rev 2.0
3.0 SETUP
All of the FlowMaster functions can be set up through the setup page, which
includes Configuration, Alarm Setup, Analog Setting, Program Setting, and
Calibration.
3.1 Configuration
- Configuration of FlowMaster and UltimateValve
3.2 Alarm Setup
- Setup page for alarm
3.3 Analog Setting
- Adjust analog output offset (± 1V)
3.4 Program Setting (Local Mode)
- Setup page for each program auto flowrate
3.5 Calibration
- Setup for calibration mode and media equation
17
Rev 2.0
3.1 Configuration
Controller Setting
18
Rev 2.0
System Setting
19
Rev 2.0
Media Type
Maximum of four (4) media types available on one (1) valve
Frequency
To key in the desired frequency in Hertz (Hz)
Gain Select
Refer to UltimateValve user manual (page 7-8)
Follow the hardware number for gain select
Proportional
To adjust response time of valve
Integral
To adjust flowrate output
Derivative
To increase damping effect of valve
Speed
To adjust the increment step of response
20
Rev 2.0
Alarm Band
Key in the percentage (%) to decide the upper and lower limit to
trigger the alarm
Particular Point alarm percentage is used. (PT %)
Default Value is 5%.
Alarm Delay
To set the desired alarm delay (in seconds)
The specification is 1 second for alarm delay according to AMS2430
User will need to take own responsibility if alarm delay is set
according to user-preference
Default Value is 5s.
Startup Delay
To set the desired startup delay (in seconds)
Acts as a buffer timing period that will not trigger the alarm even if
the flowrate is out of the preset alarm band within the buffer period.
Default Value is 10s.
21
Rev 2.0
Flowrate – 3 lbs/min
Alarm Band – 10 %
Alarm Delay – 1 second
Startup Delay – 10 seconds
The alarm will not be triggered within first ten (10) seconds albeit of any
faulty issue found including the flowrate is exceeding the alarm band of
10% which is either higher than 3.3 lbs/min or lower than 2.7 lbs/min. After
the first ten (10) seconds, if the flowrate is exceeding the alarm band of 10%
for 1 second (alarm delay) continuously, then the alarm will be triggered.
Input Range(3700-3800)
Insert Value respective to 10V shown in 3.5 Calibration
in order to have correct 10V to flow limit.
22
Rev 2.0
Selection Box
To select which line of program to be edited or created
Product Name
To set the specific name for each program
Flowrate
To set the flowrate for each program
It is available in both measurement unit of kg/min and lbs/min
Once the selected program is started, the the process will be carried out
based on the pre-set flowrate value until it is completed.
Changing of program/flowrate value in the mid of process will not
changing the process outcome.
Program Select by Product Select Bits Digital Input from behind of
FlowMaster Controller
23
Rev 2.0
3.5 Calibration
24
Rev 2.0
Mode
Auto Manual
Analog Program
There are two different operation modes can be selected which is auto mode and
manual mode whereby auto consists of two sub-modes which are analog and
program while manual mode setting can be adjusted from the main page.
25
Rev 2.0
26
Rev 2.0
Program Mode is used when user want to control UltimateValve without remote
control by any PLC. The procedure is listed below:
27
Rev 2.0
8) Select the correct recipe with correct Product Select Bits selected as shown
in table below.
9) Product Name will be show in the main page to verify correct recipe selected.
10) Make sure the UltimateValve is calibrated and configured. If not please
refer to UltimateValve Calibration Manual for further calibration
procedures.
11) Activate the UltimateValve by supply 24V and 0V
into DI1 and DIC or long press 3sc Valve On button in
Main Screen. Flow rate will be regulated afterward.
12) Deactivate the UltimateValve by supply 0V into DI1
or long press 3sc Valve On button in Main Screen when
valve is regulating the flow rate.
13) Flow rate’s voltage feedback can be obtain from AO1
and reference to AOC, the formula shown as below:
𝑉𝑜𝑢𝑡
𝐴𝑐𝑡𝑢𝑎𝑙 𝐹𝑙𝑜𝑤 𝑅𝑎𝑡𝑒 = 𝑥𝐹𝑙𝑜𝑤 𝐿𝑖𝑚𝑖𝑡
10𝑉
Note: AIC and AOC must separate from the power’s
ground for more accurate reading.
14) Alarm and ValveOn Status can also be obtained from
DO5 and DO1 respectively, remember to connect DOC
when using Digital Output.
28
Rev 2.0
Manual Mode is open loop system control of UltimateValve. Open loop mean no
sensor feedback to control valve’s flow rate. Thus, no alarm in this mode.
Note: After manual mode is selected, analog and program mode will
be ignored.
29
Rev 2.0
Note:
x represent 1, 2, 3, and 4 only.
FlowMaster’s have two default passwords can be used by users, which are
configuration password and calibration password. For secure reason, the
password won’t be written down anywhere in this manual.
Note: The only way to get the password is to contact the manufacturer.
30
Rev 2.0
5.0 INSTALLATION
There are two (2) types of fixing method for the FlowMaster as shown:
31
Rev 2.0
1 cable
32
Rev 2.0
33
Rev 2.0
6.0 SPECIFICATIONS
34
Rev 2.0
Warranty Period
One year from shipping date of the product.
Scope of Warranty
Labor and parts costs.
Prior to making a claim under this warranty, please contact the manufacturer by email or telephone with the
following information:
35
Rev 2.0
Retails Purchasing Date
If a valid claim is made on a valid warranty during the Warranty Period, manufacturer will repair any defective
parts free of charges within a reasonable period of time, and restore the product to its proper condition. If the
defective product cannot be repaired, it will be replaced with a new unit and the original warranty date will be
continue from previous product. The product should be properly packed to prevent damage in return transit.
Manufacturer will not responsible for any risk of loss or damage during return shipment.
If the product is out of its warranty period, customer need to issue purchase order to manufacturer prior to repair.
If the product cannot be repaired, customer can purchase new unit of valve or refurbished unit at a discount price
with six (6) month warranty.
Manufacturer reserved the right to vary the warranty of this Products from state to state.
36