DRYERS

PROdry ASD
REFRIGERATED DRYERS
BY DEVAIR
> Patented refrigerant circuit designed to adjust
cooling capacity to suit volume and temperature
of treated air.
> Two-stage heat exchanger to improve
efficiency and energy savings.
> High-efficiency stainless steel moisture separator
guarantees an extremely low pressure-drop and
smooth operation even under heavy working
conditions.
> Microprocessor controls on all models keep
stable dewpoint and eliminate the risk of freezing.
> Thermally protected cooling fans, and a safety
system to prevent compressor damage due
to malfunction or high working temperatures.
> Self adjusting controls to provide extremely low
and constant dew point, while preventing icing.
> Powder coated, rugged steel cabinet with
removable side panels.
> Automatic electronic drain standard with each unit.

PROTECT YOUR COMPRESSED AIR SYSTEM with PROdry ASD

AIR COMPRESSORS YOU KNOW YOU CAN TRUST


DRYERS

PROdry ASD
REFRIGERATED DRYERS BY DEVAIR
THESE COMPACT, EASILY SERVICEABLE DRYERS remove moisture by lowering the temperature of the compressed
air, and forcing moisture to condense out. This condensed water is then drained off. The net impact is a lessening
of the chances that “rogue” moisture will find its way into critical work areas downstream of the compressor,
and an overall improvement in the quality of your compressed air.
IN SIZES RANGING FROM 10CFM THROUGH 400CFM, these dryers meet the exacting standards that allow them
to complement all Devair air compressors. A one year limited liability warranty is supplied with each unit.
ALL PRODRY ASD DRYERS are microprocessor controlled, and are equipped with an energy saving heat exchanger,
high efficiency condensate separator, and a large surface area freon condenser. A built in safety shut-off protects
the compressor in the unlikely case of a dryer malfunction or operating at temperatures above set limits.

CONTROLLER PANELS display dewpoint and details of internal


operation (compressor and condensate drain). Dewpoint
temperature may be digitally set. Larger models (150 CFM
and over are equipped with a manual “On/Off” override switch.

CORRECTION FACTORS FOR HTD DRYERS


Correction factors for working pressure
PSI 73 87 102 116 131 145 160 174 188 203
FC1 0.85 0.93 1 1.06 1.11 1.15 1.18 1.2 1.22 1.24
Correction factors for ambient temperature
Deg.F/C 80/26 90/32 100/37 105/40 110/43 122/50
FC2 1.1 1.05 1 0.98 0.83 0.65
Correction factors for inlet air temperature
Deg.F/C 80/26 90/32 100/37 110/43 120/49 130/54 140/60
FC3 1.3 1.18 1 0.8 0.6 0.42 0.25
Calculations using correction factors; Actual Dryer Flow Rate = nominal dryer flow rate x FC1 x FC2 x FC3

Devair Capacity* Voltage Pipe Size Dimensions (in) Weight


Model # CFM 1phase 60 Hz NPT H W L (lbs)
ASD10 10 115 3/8 tube 16.75 14.625 19.5 64
ASD15 15 115 3/8 tube 16.75 14.625 19.8 64
ASD30 30 115 1/2 22.75 14.625 19.8 66
ASD40 40 115 3/4 22.75 16.54 21.5 104
ASD60 60 115 3/4 22.75 16.54 21.5 110
ASD100 100 115 1 38.5 16.54 21.5 198
ASD150 150 230 1 1/2 38.5 19.8 23.8 187
ASD200 200 230 1 1/2 38.5 19.8 23.8 203
ASD320 320 230 2 56.1 29.53 28.35 242
ASD400 400 **230 2 56.1 29.53 28.35 286
* Capacity at 100°F, 100psi ** 3 phase

DEVAIR INC. 490 Welham Rd. Barrie Ontario L4N 8Z4


Phone: 705 728-5657 • Fax: 705 728-4974
Toll free: 1 800 668-8558 (Canada) • 1 800 552-7954 (U.S.A.)
Email: sales@devair.ca • www.dvair.ca
©Devair Inc. 2008
As we are continually trying to improve our products, specifications are subject to change without notice. ProDry ASD-05-08-3 Printed in Canada