DCKV Technology Profile
DCKV Technology Profile
DCKV Technology Profile
Technology Description
Commercial kitchen ventilation removes the heat and effluent generated by the cooking process from the
kitchen space, ensuring the comfort and safety of the cooking staff and preventing cooking odors from
spreading beyond the kitchen. Commercial kitchen ventilation is composed of an average of two hoods
suspended above the cooking appliances, and ducting and fans necessary to expel the heat and effluent
outside [2]. To replace the air lost through this process, make-up air (MUA) must be provided by the
building’s heating ventilation and air-conditioning (HVAC) system or a MUA system dedicated to the
kitchen, which is composed of its own fans, ducts, and potentially heating or cooling, depending on the
climate.
DCKV provides control over the ventilation system by modulating the speed depending on cooking
activity. Traditionally commercial kitchen ventilation systems would operate at their maximum designed
speed/volume throughout the duration of a kitchen’s operating hours or provide manual control over two
speeds [3]. DCKV, in contrast, provides automatic, continuous control over fan speed in response to
1
Demand control ventilation (DCV) has broader application beyond commercial kitchens (e.g., venting in multi-family
buildings), therefore DCKV is used to describe commercial kitchen systems throughout this report.
Page 1 of 9
temperature, optical, or infrared (IR) sensors that monitor cooking activity or direct communication with
cooking appliances. [4]
Technical Potential
DCKV provides the following benefits over traditional commercial kitchen ventilation:
Figure 1, below, illustrates these two factors. Please note that these two factors, and therefore the majority
of the energy savings, are installation dependent.
Savings due to
oversizing
Savings due to
schedule
Figure 1: Typical power demand and savings from one exhaust fan due to a DCKV retrofit in a
hotel kitchen [5].
Figure 1 shows a reduction in average power (and therefore energy savings) of 57%. Due to the large size
of the (hotel) kitchen where the system was installed (there were several similar exhaust systems), this
translated to 60,439 kWh/year or $9,066 using local electricity rates [5] ($5,814 using the 2013 U.S.
average commercial rate). The percentage savings are typical of kitchens where all the appliances are not
typically used (oversizing) and that have appliances with heat loads that increase when cooking
(scheduling), for example:
Page 2 of 9
• Multiple cooklines, only some of which are typically used;
• Appliances that heat up quickly and produce a heat load only when being actively used (e.g., woks,
light-duty and medium-duty appliances),
• Appliances that produce a low heat load, but that produce changing amount of effluent when
cooking (e.g., fryers)
In contrast, where appliances produce a constant heat load and are used all the time, the savings are lower.
An example of a kitchen with lower savings is one with charbroilers that are on constant heat throughout
the day, and the savings can only be achieved during warm-up and cool-down. The savings achieved in this
case was 37%. [5]
An additional factor, not specifically noted in Figure 1, is the minimum energy consumption of the system.
This is the lowest point of the brown dashed line Figure 1 and occurs when all appliances are idle. This,
together with the other two factors will impact the average power and energy consumption of the final
DCKV system, and is itself impacted by:
• The minimum fan speed for safe operation: Fan speeds below 500 fpm (3 m/s) could lead to
deposition of grease in the duct and fire danger; [4]
• The responsiveness of the system: Systems that respond more slowly to cooking activity may delay
exhausting cooking effluent and heat; therefore, to prevent this initial accumulation of effluent and
user dissatisfaction, their minimum fan speed may be increased relative to more responsive
systems, decreasing savings during idle periods and therefore average savings. [6]
This last factor is worth highlighting as it is the only one that is controlled by the manufacturer and is not
installation-dependent. Manufacturers can increase the responsiveness of their systems through one of four
methods:
• Placing the thermometer(s) closer to the cooking appliance;
• Providing an optical sensor to detect effluent;
• Using an infrared sensor to detect temperature changes remotely rather than waiting for the heat or
effluent to waft up ; and
• Directly communicating with the cooking appliances [4].
In the past two years, the number of DCKV systems with multiple thermometers (for placement closer to
the cooking appliances) and remote sensors has increased. [7] This has led to further energy savings in
some installations where the cooking load is highly variable and the fan speed was decreased significantly
during idle periods. [4] A diagram of a system using infrared sensors is shown in Figure 2, below.
Page 3 of 9
Figure 2: Diagram of a DCKV system with infrared sensors that remotely monitor
the cooking surfaces [8].
Continuous Monitoring
One additional benefit of some DCKV systems is that their controllers are network-connected, allowing
outside parties to monitor the system’s operation. This ensures correct installation, and can help prevent
degradation of performance over time. [7]
One factor that may increase the awareness and spread of DCKV is that the 2013 California Title 24
building efficiency regulations (effective January 1, 2014) now require commercial kitchens greater than
5,000 cfm to decrease the amount of conditional MUA they require, and DCKV is one option to meet the
requirement (see Appendix 2) . For example, a Panda Express restaurant analyzed in [5] had a total exhaust
capacity of 6,000 cfm, while a Westin hotel kitchen had a total capacity of 21,594 cfm. Most new and
renovated kitchens in California will therefore be subject to the requirements and may elect DCKV, raising
the market share past 10% (Californians make up 12% of the U.S. population).
Page 4 of 9
Education
Several sources noted that education of installers and end-users is a barrier. While larger institutions and
their food-service equipment consultants are aware of DCKV and are employing the technology, it has yet
to reach other market segments:
• Chain restaurants are aware of the technology, but have not yet seen a business case for employing
it. Widespread adoption could take 5 years.
• Independent restaurants are not aware of the technology and neither are their dealers. Widespread
adoption could take 10–20 years. [7]
Also, installing DCKV requires mechanical and electrical contractors to integrate several different systems:
the ventilation system, variable speed drives and controls, the building’s HVAC system. Doing so
competently to ensure performance across the full range of speeds is difficult, so there is opportunity to
simplify installation [4].
Lastly, although DCKV has been promoted through organizations such as ASTM International and the
American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) [6], a wider
spotlight via organizations that engage commercial kitchen operators and designers directly, such as the
National Restaurant Association (NRA) and the Foodservice Consultants Society International (FSCI),
could be beneficial.
Differing/Uncertain Criteria
As mentioned above, there are currently 30 utility programs that promote DCKV systems [10]; however,
the total number of systems incented to date in the United States and Canada is low. One factor
contributing to this lack of uptake may be the differing criteria that utility programs use to determine which
DCKV systems can receive incentives, which could make it difficult to market DCKV across utility
territories. See Table 1, below, for a summary of the differing program requirements.
Table 1: Number of utility programs that have criteria requiring specific components [10].
Variability in Savings
Due to the variations in kitchen design and operation and local climate, the savings due to DCKV will vary
for each installation. One source describes the savings as:
a function of the actual exhaust ventilation rate, geographic location, operating hours of the system,
static pressure and fan efficiencies, makeup air heating setpoint, makeup air cooling setpoint and
level of dehumidification, efficiency of heating and cooling systems, level of interaction with
kitchen HVAC system, appliances under the hood and associated heat gain to space, and applied
utility rates. [4]
This variability in installed savings and lack of a standardized test procedure (described below) may make
purchasers hesitant; however, the Consortium for Energy Efficiency (CEE) is in the process of compiling
DCKV test data in a variety of settings, including data by different manufacturers in similar facilities, the
Page 5 of 9
same manufacturer in similar facilities, and the same manufacturer in different facilities. These case studies
could be used to more confidently estimate potential savings.
Table 2: Percentage and annual cost savings due to DCKV retrofits compared to install cost [5].
ASTM F1704-12, Standard Test Method for Capture and Containment Performance of Commercial
Kitchen Exhaust Ventilation Systems, does specify idle and cooking conditions for test, and may provide a
path forward toward developing a laboratory test method for DCKV. [6]
In the meantime, manufacturers and utilities are using ASTM F2976-13, Standard Practice for Determining
the Field Performance of Commercial Kitchen Demand Control Ventilation Systems [12]. This is a field-
test protocol originally developed by the Consortium for Energy Efficiency (CEE), which can be used for
evaluating new-construction and retrofit systems. Under this protocol, a baseline is first established as
follows:
• New-install systems: The DCKV system is put into a manual override, such that it operates as its
maximum design speed, and a one-time power measurement is conducted;
• Retrofit systems: Prior to the installation of the DCKV system, the performance (in kW and kWh)
of the existing non-DCKV system is monitored for two weeks or more.
This baseline can then be compared to the performance (in kW and kWh) of the new-install or retrofit
DCKV systems, which is monitored for two weeks or more.
Page 6 of 9
Appendix 1: References
Bibliography
[1] Consortium for Energy Efficiency, "Commercial Kitchen Ventilation: An Energy Efficiency
Program Administrator’s Guide to Demand Control Ventilation," Boston, 2010.
[2] R. Swierczyna, Interviewee, CKV Lab Manager, Fisher-Nickel, inc.. [Interview]. 23 October
2013.
[3] J. Hermias, Interviewee, Chef, Thally Restaurant, Washington, DC. [Interview]. 29 September
2013.
[4] D. Fischer, R. Swirerczyna and A. Karas, "Future of DCV for Commercial Kitchens," ASHRAE
Journal, pp. 48-54, February 2013.
[5] Southern California Edison, "Demand Control Ventilation for Commercial Kitchen Hoods," 2009.
[6] R. Swierczyna, Interviewee, CKV Lab Manager, Fisher-Nickel, inc.. [Interview]. 29 October
2013.
[7] K. Erickson, Interviewee, Program Manager, Commercial Kitchens Committee, Consortium for
Energy Efficiency. [Interview]. 25 October 2013.
[8] Halton, "13 Coins Case Study: Airflow and Energy Savings with the Halton MARVEL System,"
Halton, 2013.
[9] Food Service Technology Center, "Demand Ventilation in Commercial Kitchens: An Emerging
Technology Case Study," Pacific Gas and Electric Company, San Francisco, CA, 2004.
[10] Consortium for Energy Efficiency, "CEE 2013 Commercial Kitchens Program Summary," 21
June 2013. [Online]. Available: http://library.cee1.org/content/cee-2013-commercial-kitchens
program-summary/. [Accessed 23 October 2013].
[11] ASTM International F26.07 Task Group on Demand Control Kitchen Ventilation, Update to the
F26 Committee, Chicago, May 20, 2014.
[12] Consortium for Energy Efficiency, "Commercial Kitchen Ventilation Demand Control Ventilation
Field Test Protocol Version 1.0," 23 January 2012. [Online]. Available:
http://library.cee1.org/content/cee-ckv-dcv-field-test-protocol-version-10/.
Appendix 2: DCKV Excerpt of 2013 California Title 24 Building Energy Efficiency Regulations
* * *
Page 7 of 9
rating under the hood or hood section. Refer to ASHRAE Standard 154-2011 for definitions of hood type,
appliance duty and next exhaust flow rate.
EXCEPTION 1 to Section 140.9(b)1B: 75 percent of the total Type I and Type II exhaust
replacement air is transfer air that would otherwise be exhausted.
EXCEPTION 2 to Section 140.9(b)1B: Existing hoods not being replaced as part of an addition or
alteration.
Type of Hood Light Duty Medium Duty Heavy Duty Extra Heavy
Equipment Equipment Equipment Duty Equipment
Wall-mounted 140 210 280 385
Canopy
Single Island 280 350 420 490
Double Island 175 210 280 385
Eyebrow 175 175 Not Allowed Not Allowed
Backshelf / Passover 210 210 280 Not Allowed
TABLE 140.9-A MAXIMUM NET EXHAUST FLOW RATE, CFM PER LINEAR FOOT OF HOOD LENGTH
2. Kitchen ventilation.
A. Mechanically cooled or heated makeup air delivered to any space with a kitchen hood shall not exceed the
greater of:
i. The supply flow required to meet the space heating and cooling load; or
ii. The hood exhaust flow minus the available transfer air from adjacent spaces. Available transfer air is
that portion of outdoor ventilation air serving adjacent spaces not required to satisfy other exhaust
needs, such as restrooms, not required to maintain pressurization of adjacent spaces, and that would
otherwise be relieved from the building.
EXCEPTION to Section 140.9(b)2A: Existing kitchen makeup air units not being replaced as part of an
addition or alteration.
B. A kitchen/dining facility having a total Type I and Type II kitchen hood exhaust airflow rate greater than
5,000 cfm shall have one of the following:
i. At least 50 percent of all replacement air is transfer air that would otherwise be exhausted; or
ii. Demand ventilation system(s) on at least 75 percent of the exhaust air. Such systems shall:
a. Include controls necessary to modulate airflow in response to appliance operation and to
maintain full capture and containment of smoke, effluent and combustion products during
cooking and idle; and
b. Include failsafe controls that result in full flow upon cooking sensor failure; and
c. Include an adjustable timed override to allow occupants the ability to temporarily override the
system to full flow; and
d. Be capable of reducing exhaust and replacement air system airflow rates to the larger of:
(c) 50 percent of the total design exhaust and replacement air system airflow rates; or
(d) The ventilation rate required per Section 120.1.
iii. Listed energy recovery devices with a sensible heat recovery effectiveness of not less than 40
percent on at least 50 percent of the total exhaust airflow; and
iv. A minimum of 75 percent of makeup air volume that is:
a. Unheated or heated to no more than 60°F; and
b. Uncooled or cooled without the use of mechanical cooling.
EXCEPTION to Section 140.9(b)2B: Existing hoods not being replaced as part of an addition or alteration.
Page 8 of 9
3. Kitchen Exhaust System Acceptance. Before an occupancy permit is granted for a commercial kitchen subject to
Section 140.9(b), the following equipment and systems shall be certified as meeting the Acceptance Requirements
for Code Compliance, as specified by the Reference Nonresidential Appendix NA7. A Certificate of Acceptance
shall be submitted to the enforcement agency that certifies that the equipment and systems meet the acceptance
requirements specified in NA7.11.
* * * * *
Page 9 of 9