Operation manual of solar water controller SR208C

Contents
Contents----------------------------------------------------------------------------------------------------1 1. Safety information ----------------------------------------------------------------------------------3 1.1 Installation and commissioning -----------------------------------------------------------------3 1.2 About this manual ----------------------------------------------------------------------------------3 1.3 Liability waiver ---------------------------------------------------------------------------------------3 1.4 Important remark------------------------------------------------------------------------------------4 1.5 Description of symbols----------------------------------------------------------------------------4 1.6 Description of operation button------------------------------------------------------------------4 2. Installation --------------------------------------------------------------------------------------------5 2.1 Installing the controller------------------------------------------------------------------- 5 2.2 Power connection ----------------------------------------------------------------------------------6 2.3Terminal connection --------------------------------------------------------------------------------6 3. Commissioning--------------------------------------------------------------------------------------8 3.1 Set time/ week-----------------------------------------------------------------------------------8 3.2 Menu structure-------------------------------------------------------------------------------------9 3.3Menu description-----------------------------------------------------------------------------------10 3.4 System description--------------------------------------------------------------------------------10 4. Controller functions-----------------------------------------------------------------------11 4.1 Access main menu -------------------------------------------------------------------------------11 4.2 Access submenu ---------------------------------------------------------------------------------12 4.3 Main menu DT O & DT F Temperature difference function-----------------------------12 4.4 Main menu-THET timing heating-------------------------------------------------------13 4.5 TEMP Temperature main menu----------------------------------------------------------------16 4.5.1 EM Emergency collector temperature emergency switch-off temperature of collector ----------------------------------17 4.5.2 CMX Maximum limited collector temperature (collector cooling function)---18 4.5.3 CMN low temperature protection of collector---------------------------------------19 4.5.4 CFR frost protection of collector --------------------------------------------------20 4.5.5 SMX Maximum temperature of tank ----------------------------------------21 4.5.6 REC Tank re-cooling function----------------------------------------------------------21 4.5.7 C-F Celsius and Fahrenheit temperature transferring --------------------------22 4.6 HND Manual mode---------------------------------------------------------------------------------22 4.7 PASS Password setting-------------------------------------------------------------------------23 4.8 LOAD Recovery to factory setting------------------------------------------------------------24

---------------------------------------------------------------------------------------------------------------------------------------------------

-1-

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

4.9 Manual heating-----------------------------------------------------------------------------------24 4.10 Temperature query function-------------------------------------------------------25 5. Protection function ------------------------------------------------------------------------------25 5.1 Memory Protection-------------------------------------------------------------------------25 5.2 Screen protection----------------------------------------------------------------------------------25 6. Troubles Shooting--------------------------------------------------------------------------------25 6.1 Trouble protection ---------------------------------------------------------------------------------25 6.2 Trouble checking ----------------------------------------------------------------------------------26 7. Quality Guarantee ---------------------------------------------------------------------------------28 8. Technical data --------------------------------------------------------------------------------------29 9. Delivery scope--------------------------------------------------------------------------------------29 10. Device matchable to this controller---------------------------------------------------------30

---------------------------------------------------------------------------------------------------------------------------------------------------

-2-

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

1. Safety information
1.1 Installation and commissioning When laying cables, please ensure that no damage occurs to any of the constructional fire safety measures presented in the building. The controller must not be installed in rooms where easily inflammable gas mixtures are present or may occur. The permissible environmental conditions cant be exceeded at the site of installation. Before connecting the device, make sure that the energy supply matches the All devices connected to the controller must conform to the technical specifications All operations on an open regulator are only to be conducted cleared from the power Connecting and /or all operations that require opening the regulator (e.g. changing specifications that controller requires. of the controller. supply. All safety regulations for working on the power supply are valid. the fuse) are only to be conducted by specialists. 1.2 About this manual This manual describes the installation, function and operation of a solar thermal controller. When installing the remaining components e.g. the solar collectors, pump assemblies and the storage unit, are sure to observe the appropriate installation instructions provided by each manufacturer. Only trained professional personnel may only perform installation, electrical connection, commissioning and maintenance of the device. The professional personnel must be familiar with this manual and follow the instructions contained herein. 1.3 Liability waiver The manufacturer cannot monitor the compliance with these instructions or the circumstances and methods used for installation, operation, utilization and maintenance of this controller. Improper installation can cause damages to material and persons. This is the reason why we do not take over responsibility and liability for losses, damages or cost that might arise due to improper installation, operation or wrong utilization and maintenance or that occurs in some connection with the aforementioned. Moreover we do not take over liability for patent infringements or

---------------------------------------------------------------------------------------------------------------------------------------------------

-3-

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

infringements occurring in connection with the use of this controller- on third parties rights. The manufacturer preserves the right to put changes to product, technical date or installation and operation instructions without prior notice. As soon as it becomes evident that safe operation is no longer possible (e.g. visible damage). Please immediate take the device out of operation. Note: ensure that the device cannot be accidentally placed into operation. 1.4 Important remark We have carefully checked the text and pictures of this manual and provided the best of our knowledge and ideas, however inevitable errors maybe exist. Please note that we can not guarantee that this manual is given in the integrity of image and text, they are just some examples, and they apply only to our own system. Incorrect, incomplete and erroneous information and the resulting damage we do not take responsibility. 1.5 Description of symbols Safety instruction: The safety instructions in the manual are marked with a warning triangle. They indicate measures, which can lead to personal injury and safety risks. Operation steps: small triangle is used to indicate operation step. Notes: Contains important information about operation or function. 1.6 Description of operation button

---------------------------------------------------------------------------------------------------------------------------------------------------

-4-

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

No. 1 2 3 4 5 6 7

Button description - Parameter adjust button + Parameter adjust button ESC, exit program setup SET confirm button Heating- manual heating button Clock button Clock button LCD display screen

2Installation
Controller can only be installed indoors, far away from dangerous place and away from the electromagnetic field. Controller should be equipped with an additional plug, which should have minimum 3mm distance between the pole of the plug or effective compliance with the provisions of the installation. For example, switch or fuse, please note that it should be separated between the wires, and use AC power.

Fixing the hang-panel of controller Choose a suitable site Mark the position of hole Drill the fixing hole, insert the expansion screw Take away the cover Put bottom plate one the position of Market the hole of and Then take away of bottom plate again. Drill the fixing hole. Rehang the bottom plate and fixing on Insert the screw,fixing hole and on the

bottom plate.

---------------------------------------------------------------------------------------------------------------------------------------------------

-5-

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

2.2 Power connection Power can only be switched on when the house of controller is closed, an installer must make sure that the IP protection class of the controller is not damaged during installation. Depending on the type of installation, the cables may enter the device through the rear hole of the case or the lower side hole of the case Cable come from the rear : remove the plastic flaps from the rear side of the case using an appropriate tool. Cable come from the below: cut the left and right plastic flaps using an appropriate tool (e.g. knife) and break them out of the case. Notes: the flexible wire must be fastened on the case using the clamps provided

2.3 Terminal connection Before to open the terminal, please be sure to switch-off the power supplier and pay attention to the local electricity supply rules. Terminal layout

---------------------------------------------------------------------------------------------------------------------------------------------------

-6-

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

Reset buttonThis button is on the terminal connection panel, when system program is out of working, press Reset to recover the program of system to the factory settings. Power connection Power connection terminal is: Input ports Ground line terminal is GND Sensor input ports

Input sensor ports T1: for Pt1000 sensor, used for measuring the temperature of collector. Input sensor ports T2 and T3: for NTC10K, B=3950 sensors, used for measuring the temperature of tank. Advice regarding the installation of temperature sensors:

Only original factory equipped Pt1000 temperature sensors are approved for use with the collector, it is equipped with 1.5meter silicon cable and suitable for all weather conditions, the temperature sensor and cable are temperature resistant up to 280 C, not necessary to distinguish the positive and negative polarity of the sensor connection. Only original factory equipped NTC10K,B=3950 temperature sensors are approved for use with tank and pipe, it is equipped with 1.5meter PVC cable, and they are temperature resistant up to 105 C, not necessary to distinguish the positive and negative polarity of the sensor connection. All sensor cables carry low voltage, and to avoid inductive effects, must not be laid close to 230 volt or 400-volt cables (minimum separation of 100mm) If external inductive effects are existed, e.g. from heavy current cables, overhead train cables, transformer substations, radio and television devices, amateur radio stations, microwave devices etc, then the cables to the sensors must be adequately shielded.
o o

---------------------------------------------------------------------------------------------------------------------------------------------------

-7-

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

Sensor cables may be extended to a maximum length of ca. 100 meter, when cables length is up to 50m, and then 0.75mm cable should be used. When cables length is up to 100m, and then 1.5mm cable should be used. Output ports
2 2

Output R1for hot water circuit pump, electromagnetic relay, and max. switching current 3.5A, R1 ports are always open, Output H1for back-up electrical heater, electromagnetic relay, and max. switching current 3.5A, H1 connection ports are always open.

3. Commissioning
Connect the sensors, pumps or switching valves to the controller before you connect the power supply! After switching on power to the controller, firstly it will ask for to set the time, password and parameters of system.

3.1 Set time/week Press Clock button, time displays on screen, hour selection area 00 blinks on display screen. Press +- button to set hour of clock Press Clock button again, minute area00blinks Press +- button to set minute of clock. Press ESC button to exit set program, or wait for 20 seconds to exit program automatically.

---------------------------------------------------------------------------------------------------------------------------------------------------

-8-

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

3.2 Menu structure

Submenu: Through submenu, customer can set the parameter as desired value, please check it carefully.

---------------------------------------------------------------------------------------------------------------------------------------------------

-9-

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

3.3 Menu description Code Code Code (Subme Menu Description (Submenu) Mainmenu nu) DT O Switch-on temperature difference DT F Switch-off temperature difference THET Timing heating Temperature Limited temperature of collector EM (Emergency turnoff temperature of collector) Maximum temperature of collector CMX (Collector cooling function) CMN Low temperature protection of collector CFR Frost protection of collector SMX Maximum temperature of tank REC Tank re-cooling function Celsius and Fahrenheit temperature C-F transferring HDN Manual controlling PASS Password set LOAD Recovery to factory set

3.4 System description Note: T3 is alternative sensor, when no sensor (T3) is installed in the top part of tank, controller will use the signal of sensor T2 automatically to control the auxiliary heating or the circulation pump. 1 collector array 1 storage tank 1 pump and auxiliary heating Description: The solar circuit pump (R1) is switched on as soon as the switch-on temperature difference (Ton) between the collector array (T1) and the storage tank (T2) is reached. If the temperature difference between the collector array (T1) and storage tank (T2) drops below the switch-off temperature difference (Toff), or the temperature of storage tank (T3) reaches the preset maximum storage temperature, then the solar circuit pump ( R1) is switched off. Back-up heating by auxiliary boiler (detailed see paragraph 4.3): Within the preset time section of back-up heating, if the temperature T3 is below the

---------------------------------------------------------------------------------------------------------------------------------------------------

- 10 -

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

switch-on temperature, then the circulation pump ( H1) of back-up heating is triggered, when T3 is heated to the switch-off temperature, circulation pump H1 of back-up heating is ceased.

T1: Temperature sensor for collector array T2: Temperature sensor in the top part of tank (optional sensor) T3: Temperature sensor on hot water circulation pipe (optional sensor) R1: Solar circuit pump H1: output for back-up electrical heater

4
4.1 Access main menu Under standby status, doing like following access main menu Press SET button, PWD 0000displays on screen, the left first digital blinks, ask for entering password, factory default set password is 0000 Press +- button to enter first digital of password. Press SET button again, the second digital blinks

---------------------------------------------------------------------------------------------------------------------------------------------------

- 11 -

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

Press +- button button, to enter second digital of password Press SET button again, the third digital blinks Press +- button to enter the third digital of password Press SET button again, the fourth digital blinks Press +- button, to enter the fourth digital of password Press SET button again to access main menu Press +- button, can select the main menu Press ESC button to exit main menu 4.2 Access submenu After selecting main menu, do like following access submenu Press SET button, to access submenu Press +- button to select submenu Press SET button again to access program can adjust parameter value now Press +- button, to adjust the value of parameter Press ESC button, exit program of submenu Press ESC button again, to exit main menu. 4.3 Main menu DT O & DT F Temperature difference function Description: Solar circuit pump R1 is triggered by the temperature difference function, so long as the temperature difference between collector and tank reaches the switch-on DT, solar circuit pump is triggered. For example: the switch-on DT is 8oC, switch-off DT is 4oC, if the temperature in the bottom part of tank is 20oC, then just when collector temperature rises up to 28 oC, pump is triggered, and when collector temperature drops to 24 oC, pump is ceased. Note: the switch-on/off DT of 8 oC and 4 oC are standard system setting according to many years experience, only in special application cases it needs to be changed, (e.g far distance heat transferring), normally it is recommend to use default set. Switch-on and switch-off DT are alternating set. To avoid mistake the minimum difference between two temperature differences (Ton Toff) is set as 2 C. Setup the switch-on temperature difference:
--------------------------------------------------------------------------------------------------------------------------------------------------o

Forexamplesubmenu

- 12 -

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

Under standby status, access main menu DT O, Press SET button, to access settings program of DT O, DT O 08 displays on screen, 08 blinks, the switch-on temperature difference can be set. Press +- button, to adjust the value of switch-on DT, adjustable range (OFF+2 20 factory setting is 8 Press ESC button to exit this setting, parameter is saved automatically. Setup the switch-off temperature difference: Under standby status, access main menu DT F Press SET button, to access settings program of DT F, DT F 04 displays on screen, 04 blinks, the switch-off temperature difference can be set. Press +- button to adjust the value of switch-off DT, adjustable range 0 ONfactory set is 4. Press ESC to exit menu, or wait for 20 seconds to exit automatically, the setup parameters are saved automatically. 4.4 Main menu - THET timing heating Description: Electrical heater, gas boiler or oil boiler can be integrated into solar system used as back-up of system, and they can be triggered automatically at preset time by preset temperature. Within a preset time section, when the temperature (T3) of top part of tank drops below the preset switching-on temperature of this function, back-up heating starts to work, when T3 rises up to the preset turning off temperature, back-up heating is stopped. Within 24 hours, three time sections can be set with this controller. Factory set: The first time section: back-up heating function starts at 4:00 and ends at 5:00 am. Within this time section, switch-on temperature is 40, switch-off temperature is 45. The second time section: from 10:00 to 10:00 am, it means there is no back-up heating in this time. The third time section: back-up heating function starts at 17:00 and ends at 22:00 pm. Within this time section, the switch-on temperature is 50, switch-off temperature is 55. The switch-on temperature adjustable range: 10 ~ (OFF-2 ) The switch-off temperature adjustable range: (ON+2 ) ~ 80 If you want to shut off one timing heating, then you can set the turning on time and turning off time same value (for example, the second time section no this function, then
---------------------------------------------------------------------------------------------------------------------------------------------------

- 13 -

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

you can set turning on/off time is 10:00 ~ 10:00) When time is outside of the preset time section, back-up heating doesnt work automatically even when the tank temperature reaches the switch on temperature of heating. Note: When there is no sensor installed in the top part of tank (no T3 sensor), controller will take the signal of T2 (sensor in bottom of tank) automatically to control this function. The time in this controlled is 24 hours, when you set time section, the switch-off time of heating should be larger than switch-on time. For example: if you set the switch-on time of heating is at 17:00, but switch-off time of heating is 6:00, then this setting doesnt take effect, that means within this time section, heating function doesnt work. The correct set is like flowing: it should be divided into two time sections, one time section is from 17:00 to 23:59, the other time section is from 00:00 to 06:00.

Setup steps: Under standby status, access main menu tHET Press SET button, access THET program to set parameter, tH 1o 04:00 displays on screen, the switch-on time and temperature for first time section of heating function can be set Repress SET button, 04 of hour time blinks on screen Press +- button to adjust hour of time Repress SET button again, 00 of minute time blinks on screen Press +- button to adjust minute of time Repress SET button, temperature 40 blinks on screen Press +- button, to set the switch-on temperature of heating Then, Press ESC to exit this set and to access the switch-off time and temperature set Press + button, tH 1F 05:00 displays on screen, the switch-off time and temperature for first time section of heating function can be set Press SET button, 05 of hour time blinks on screen. Press +- button to adjust hour of time

---------------------------------------------------------------------------------------------------------------------------------------------------

- 14 -

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

Repress SET button, 00 of minute time blinks on screen Press +- button to set minute of time Repress SET button, temperature 45 blinks on screen Press +- button, to set switch-off temperature of heating Press ESC to exit this set program, parameters are saved automatically ------------------------------------------------------------------------------------------------------------------Press+ button, tH 2o 10:00 displays on screen, the switch-on time and temperature for the second time section of heating function can be set Press SET button, 10 of hour time blinks on screen Press +- button to adjust hour of time Repress SET button, 00 of minute time blinks on screen Press +- button to adjust minute of time Repress SET button, temperature 50 blinks on screen Press +- button to adjust switch-on temperature of heating Then press ESC to exit this set and to access the switch-off time and temperature set Press + button, tH 2F 10:00 displays on screen, set the switch-off time and temperature of second time section of heating function Press SET button, 10 of hour time blinks on screen Press +- button to adjust hour of time Repress SET button, 00 of minute time blinks on screen Press +- button to adjust minute of time Repress SET button, temperature 55blinks on screen Press +- button, to adjust switch-off temperature of heating Press ESC to exit this set program, parameter is saved automatically ----------------------------------------------------------------------------------------------------------------- Press + button, tH 3o 17:00 displays on screen, set the switch-on time and temperature of the third time section of heating function Press SET button, 17 of hour time blinks on screen Press +- button, to adjust hour of time

---------------------------------------------------------------------------------------------------------------------------------------------------

- 15 -

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

Repress SET button, 00 of minute time blinks on screen Press +- button, to adjust minute of time Repress SET button, temperature 50 blinks on screen Press +- button, to adjust switch-on temperature of heating Press ESC to exit this set program and to the switch-off time and temperature set Press + button, tH 3F 22:00 displays on screen, the switch-off time and temperature of the third time section of heating function can be set Press SET button, 22 of hour time blinks on screen Press +- button, to adjust hour of time Repress SET button, 00 of minute time blinks on screen Press +- button to adjust minute of time Repress SET button, temperature 55 blinks on screen Press +- button to adjust switch-off temperature of heating Press ESC to exit menu, or wait for 20 seconds, set parameters are saved automatically Note: when no gas or oil boiler is installed in system, electrical heater can be installed as back-up device, when electrical heater is in operation status, signal blinks on screen. If customer use electrical heater as back-up, please according to the power of electrical heater to equip corresponding safety devices like contactor and breaker with this controller, we strongly recommend equipping with SR802 device with this controller, (SR802 detailed technical data see paragraph 10 spare parts)

4.5 TEMP Temperature main menu For every system, the factory set parameters are in the best condition that is fully integrated into the entire solar system. But these parameters can also be set individually to cater the special requirements, please carefully observe the operation data of system components after setting. Note: parameters that can be set depend on the selected system, not all the parameters can be adjusted in a solar system. Following submenu can be access though TEMP main menu.

---------------------------------------------------------------------------------------------------------------------------------------------------

- 16 -

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

EM Emergency collector temperature Emergency switch-off temperature of collector------------------------------------------4.5.1 CMX Maximum limited collector temperature (collector cooling function) ----------- 4.5.2 CMN low temperature protection of collector ----------------------------------------------4.5.3 CFR frost protection of collector -----------------------------------------------------------------4.5.4 SMX Maximum temperature of tank-------------------------------------------------------------4.5.5 REC Tank re-cooling function --------------------------------------------------------------------4.5.6 C-F Celsius and Fahrenheit temperature transferring--------------------------------------4.5.7 Function EM Emergency collector temperature Emergency switch-off temperature of collector CMX Maximum limited collector temperature (collector cooling function) CMN low temperature protection of collector CFR frost protection of collector SMX Maximum temperature of tank REC Tank re-cooling function C-F Celsius and Fahrenheit temperature transferring Adjustable range 200 Factory set 130 Function exit temperature 127

110190 090 -1010 295


o

110 OFF OFF 60 OFF


o

107

58

C ~ oF

4.5.1 EM Emergency collector temperature(Emergency switch-off function) Function description: When temperature of collector rises up to the preset maximum switch-off temperature, collector emergency switch-off function is activated. As the result of this function, solar circulation pump is stopped,it avoids the damage of system components caused by over-heated temperature. EMOF parameter is for set maximum switch-off temperature of collector (factory set: 130oC), if the collector temperature rises up to preset EMOF temperature, solar pump is stopped;EMON parameter is for set maximum switch-on temperature of collector (factory set: 120oC),when the collector temperature drops to EMON temperature, solar pump can be triggered again, collector emergency switch-off function is deactivated automatically. EMOF collector maximum switch-off temperature

Select submenu EMOF, EMOF 130oC displays on the screen.


---------------------------------------------------------------------------------------------------------------------------------------------------

- 17 -

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

Press SET button, parameter 130oC blinks on the screen. Press +, - button, to adjust the EMOF temperature, adjustable range: ( ON +3oC)~200oC, factory set is 130oC. Repress SET button, activate and deactivate this function, if deactivate the function, EMOF - - - displays on screen. Press ESC button to exit menu, or wait for 20 seconds to exit automatically, set parameter is saved automatically. EMON collector maximum switch-on temperature

Select submenu EMON, EMON 120oC displays on the screen. Press SET button, parameter 120oC blinks on the screen. Press +,- button, to adjust the EMON temperature, adjustable range: ( OFF-3oC)~200oC, factory set is 120oC. Repress SET button, activate and deactivate this function, if deactivate the function, EMON- - - displays on screen. Press ESC button to exit menu, or wait for 20 seconds to exit automatically, set parameter is saved automatically. These two signals display on the screen, means collector emergency switch-off function is activated, and tank temperature rises up to its maximum permitted temperature. Only this signal displays on the screen, means this function is activated, but tank temperature doesnt rise up to its maximum temperature.

4.5.2 CMX Maximum limited collector temperature (collector cooling function) Function description: The collector cooling function delays the vaporization of the heat transfer fluid. Shortly before reaching the maximum temperature of the collector, the solar pump starts working in order to cool down the heat transfer fluid using the heat losses occurring in pipelines and storage cylinder. When tank temperature rises to its preset maximal temperature, solar circuit pump is ceased compulsively even the temperature difference is satisfied. If the sunshine is very good, as a result collector temperature will rise continuously, when collector temperature rises up to its maximal temperature, solar pump will be triggered again even at the case that tank temperature is already to its maximal temperature. And solar
---------------------------------------------------------------------------------------------------------------------------------------------------

- 18 -

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

pump works until the temperature of collector drops since this reversed circulation or when tank temperature rises its emergency temperature (95 oC). When displays, and blinks on the screen, it indicates that tank emergency

temperature reaches, tank temperature is 95 Setup steps: To access main menu TEMP, then select submenu CMX CMX 110 displays on screen Press SET button, parameter 110 blinks. Press +- button, to adjust the collector protection temperature, adjustable range (100 190, factory set is 110 Repress SET button, activate and deactivate this function, if deactivate the function, CMX - - - displays on screen. Press ESC button to exit the menu or wait for 20 seconds to exit automatically, parameters are saved automatically. CMX signal displays on screen, it indicates that this function is in activated.

4.5.3 CMN low temperature protection of collector Description: When the temperature of collector is below preset CMN temperatures, solar circuit pump is ceased, even when the temperature difference between collector and tank exceeds switch-on temperature difference, solar pump doesnt work yet. When temperature of collector is 3oC higher that the preset CMN temperature, solar circuit pump is restarted, controller exits this program. Setup steps: To access main menu TEMP, then select submenu CMN, CMN----- displays on screen, default set is off. Press SET button, default off signal - - - blinks on screen. Repress SET button, to activate and deactivate this function Press +- button, to adjust the low protection temperature of collector CMN, adjustable range (0090), after activate the function, factory set is 10 Press ESC button to exit the menu or wait for
---------------------------------------------------------------------------------------------------------------------------------------------------

- 19 -

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

20 seconds to exit automatically, parameters are saved automatically. CMN signal displays on screen, it indicates that this function is in activated.

4.5.4 CFR frost protection of collector Description: In winter when the temperature of collector is below the preset frost protection temperature (factory set is 4 C), Solar circuit pump is triggered. Besides when tank temperature (T2) drops to 4oC, electrical heater is triggered automatically and it is in operation until T2 is heated up to 20 C or it is stopped when program of CFR is exited. When collector temperature rises up to 7 C, solar circuit pump is ceased, program of CFR exits automatically. This function is used in system, which use water as heat transfer liquid, to avoid the freezing of solar heat transfer fluid. Setup steps: To access main menu TEMP, then select submenu CFR, CFR ---- displays on screen, default set is off. Press SET button, default off - - - blinks. Repress SET button, to activate or deactivate this function Press +- button, to adjust the frost protection function, adjustable range is -1010 after function activated, default set is 4 Press ESC button to exit the menu or wait for 20 seconds to exit automatically, parameters are saved automatically. CFR signal displays on screen, it indicates that this function is in activated.
o o o

---------------------------------------------------------------------------------------------------------------------------------------------------

- 20 -

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

4.5.5 SMX Maximum temperature of tank Description: When the DT between collector T1 and Tank 2 caters the switch-on DT of circulation, solar pump is triggered, but in order to avoid the high temperature inside tank, controller will check whether the temperature (T3) of top part of tank is higher than maximum temperature of tank, when T3 is higher than preset SMX temperature, solar pump is ceased even at the case that DT caters condition. When tank temperature drops and is 2oC below the SMX, solar pump restarts when DT caters condition. Setup steps: To access main menu TEMP, then select submenu SMX, SMX 60 displays on screen. Press SET button, parameter 60blinks Press + button to adjust the value of maximum temperature of tank1 adjustable range is 295, default set is 60 Repress SET button to activate and deactivate this function, if function deactivated, SMX - - - displays on the screen. Press ESC button to exit the menu or wait for 20 seconds to exit automatically, parameters are saved automatically. SMX signal displays on screen, it indicates that this function is in activated.

4.5.6 REC Tank re-cooling function Description: If tank temperature is over tanks maximum temperature, and at the same time, collector temperature is 5oC lower than tank temperature, then solar pump is triggered, through this reversed circulation, tank temperature is reduced by heat loss occurs in collector, solar pump keep in working until tank temperature drops below its maximum temperature. Setup steps: To access main menu TEMP, then select submenu REC, REC OFF displays on screen, default set is off. Press SET button, parameter OFF blinks on screen Repress SET button to activate or deactivate

---------------------------------------------------------------------------------------------------------------------------------------------------

- 21 -

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

this function, after function activated; factory set is REC ON Press ESC button to exit the menu or wait for 20 seconds to exit automatically, parameters are saved automatically. REC signal displays on screen, it indicates that this function is in activated.

4.5.7 C- F Celsius and Fahrenheit temperature transferring Setup steps: To access main menu TEMP, then select submenu C-F, CF displays on screen. Press SET button, parameter blinks on the screen. Press + button, to select between Celsius and Fahrenheit temperature, factory set is Press ESC button to exit menu or wait for 20 seconds to exit automatically, parameters are saved automatically.

4.6 HND Manual mode When using this controller first time or when debugging this controller, output of this controller (R1,H1)can be triggered manually. On, OFF control. Setup steps: To access main menu HND, Press SET button, HND1 off displays on the screen, R1 output manually set Repress SET button, HND1 on displays on the screen, R1 output is switched-on Repress SET again, HND1 off displays, R1 output is switched-off Press ESC to exit R1 set program -----------------------------------------------------------------------------------------------------------------Press + button, HND2 off displays on the screen, H1 output manually set Press SET button, HND2on displays on the screen, H1 output is switched-on Repress SET again, HND2off displays, H1 output is switched-off

---------------------------------------------------------------------------------------------------------------------------------------------------

- 22 -

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

-----------------------------------------------------------------------------------------------------------------Note: when manual mode is activatedsignal displays on the screen, after 15 minutes all outputs are switched-off, controller exits manual mode automatically.

4.7 PASS Password setting Setup steps: To access main menu PASS, Press SET button, PWDC 0000, the left digital blinks, ask for to enter the password, factory set is 0000 Press +- button to enter the first digital Repress SET button, the second digital blinks Press +- button to enter the second digital Repress SET button, the third digital blinks Press +- button to enter the third digital Repress SET button, the fourth digital blinks Press +- button to enter the fourth digital Press SET button, PWDN 0000 displays on the screen, ask for entering a new password, doing like above to enter the new password Press SET button, PWDG 0000 displays on the screen, ask for reentering the new password, doing like above to reenter the new password, PWOK displays on the screen to indicate reentering password successfully. Press ESC button to exit set program or wait for 20 seconds to exit automatically.

If the password is forgot, it is not possible to recover, but you can recover the password to factory set, then you can reedit a password like above descript steps, doing like following to recover to factory set. Open the connection terminal cover, plate.

Press - and hold down, then repress the reset button, which is on the terminal

---------------------------------------------------------------------------------------------------------------------------------------------------

- 23 -

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

Buzzer makes du----- 3 times, then release - button. factory set, a new password can be reset now. 4.8 LOAD Recovery factory setting Setup steps: To access main menu REST, Press SET button, YES displays on the screen. Hold down SET button, buzzer makes du----- 3 times, then release SET button. Controller recovers to factory set,

Controller recovers to

new paramters can be reset now.

Press ESC button to exit set program or wait for 20 seconds to exit automatically. 4.9 Manual heating Description: Electrical heater, gas or oil boiler can be as back-up devices in a solar system, this controller can achieve constant temperature controlling, when controller gets temperature signal of top part tank (T3) is 2oC below the preset temperature, back-up heating will be triggered. When temperature of top part tank (T3) reaches to the preset temperature, heating is ceased. Conditions for triggering manual heating function: the setting temperature should be 2oC higher than tank temperature. Activate/deactivate the function: Press Heating button, temperature 60 blinks on the screen. Press +- button to adjust switch-on temperature, adjustable range 1080, factory set is 60. After 20 seconds, this function is activated, signal heating signal blinks also. displays on the screen, and

Press Heating button again, to switch-off manual heating function. Note: manual heating can only heat tank one time, after manual heating is triggered, when temperature of tank rises up to the preset temperature, manual heating ceases, and manual heating function will be deactivated automatically, if customer wants to heat again, you need redo according to above steps.

---------------------------------------------------------------------------------------------------------------------------------------------------

- 24 -

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

4.10 Temperature query function Error message on LCD screen Meaning Cause of error Error rectification

Under standby status, Press +- button can check the value of temperature sensors T1~ T3. When checking temperature, T1 T3 will displays one by one, corresponding sensor signal blinks. Press ESC button, clock and tank temperature can be displayed.

5. Protection function
5.1. Memory protection In case power failure occurs, controller keeps the parameter settings unchanged.

5.2 Screen protection When no any press on button for 3 minutes, screen protection is activated automatically, and then LCD lighting lamp is switched-off. Through press any button to light LCD lamp again.

6. Trouble shooting
6.1 Trouble protection When there is a break or short circuit between the connection of temperature sensors, controller switches off the corresponding functions and no more output signals are given, at the same time error signals Press +- button to check error code, are showed on the display. If control unit signal displays on the LCD screen

does not work correctly, please check following points.

---------------------------------------------------------------------------------------------------------------------------------------------------

- 25 -

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

Sensor wiring interrupted, T1 - - T1 sensor problem not connected or short circuit Sensor wiring interrupted, T2 - - T2 sensor problem not connected or short circuit

Check resistance value, replace

Check resistance value, replace

6.2 Trouble checking The controller is quality product, conceived for years of continuous trouble-free operation. If a problem occurs, the cause of the problem very often lies not in the controller but in the peripheral components. The following description of some well-known problems should help the installer and operator to isolate the problem, so that the system can be place back into operation as quickly as possible and to avoid unnecessary costs. Of course, not all possible problems can be listed here. However, most of the normal problems encountered with the controller can be found in the list below, only return the controller to seller when you are absolutely sure that none of the problems listed below is responsible for the fault.

---------------------------------------------------------------------------------------------------------------------------------------------------

- 26 -

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

Symptoms Controller does not appear to function at all

Secondary symptoms Display shows nothing, no display illumination

Possible cause Controller power supply is interrupted or program is out of work

Procedure Check the controller power cable Press reset button

The solar pump doesnt operate, despite the fact that switch-on conditions are satisfied Pump doesnt operate

The pump symbol in the display blinks

Pump power supply is interrupted

Check the pump power cable

The pump symbol in the display doesnt blink. Lighted or blinks

The maximum storage tank temperature (SMX) has been reached The maximum collector temperature (EM) has been reached. Fault (short circuit

No fault

On the controller, request the current values from all connected temperature sensors, replace all defective sensors and /or cabling.

T1-----Error message displays on the screen

or open circuit) in a temperature sensor

The solar pumps operated, despite the fact that the switch-on conditions are not satisfied.

The pump symbol in the display blinks.

Frost protection function or tank re-cooling function is activated.

No problem, it is normal. If necessary to deactivate the corresponding functions.

---------------------------------------------------------------------------------------------------------------------------------------------------

- 27 -

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

Warning Remove the device from the mains supply before opening the case A potentially defective sensor can be checked using an ohmmeter. To do this, the sensor must be disconnected, its resistance measured, and the value compared with the figures in the table below, small deviation ( 1%) is acceptable, PT1000 resistance value
0 1000 10 1039 20 1077 30 1116 40 1155 50 1194 60 1232 70 1270 80 1309 90 1347 100 1385

NTC 10K B=3950 resistance value


0 33620 10 20174 20 12535 30 8037 40 5301 50 3588 60 2486 70 1759 80 1270 90 933 100 697

7. Quality Guarantee
Manufacturer provides following quality responsibilities to end-users: within the period of quality responsibilities, manufacturer will exclude the failure caused by production and material selection. A correct installation will not lead to failure. When a user takes incorrect handling way, incorrect installation, improper or crud handling, wrong connection of sensor in system and incorrect operation, the quality responsibility is invalid for them. The warrantee expires within 24 months after the date of purchasing the controller.

---------------------------------------------------------------------------------------------------------------------------------------------------

- 28 -

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

8. Technical data
Type Specification Appearance of controller Power supply Power consumption Accuracy of temperature measuring Range of collector temperature measuring Range of tank temperature measuring Suitable power of pump cable280oC), 2 x NTC10K, B3950 sensor ( 135oC) for tank, (PVC cable 105oC), Outputs Ambient temperature Water proof grade 1 relays, for circulation pumps, power: 600W 1 relay for electrical heater, power: 600W -1050 oC IP40 Technical Data 178mm120mm43mm AC200V240V 3W oC 2 -10220oC 0110oC 2 1 x Pt1000 sensor (500oC) for collector (silicon Inputs

9. Delivery scope
Lists Type Quanlity 1 1 1 2 3 3 1

Controller Operation manual PT1000 sensor (size6*50mm,cable length1.5m NTC10Ksize6*50mm,cable length1.5m Plastic expansion screw Screw Strain-relief clamp

---------------------------------------------------------------------------------------------------------------------------------------------------

- 29 -

office@ratioterm.ro; www.ratioterm.ro

+4 (0)261 770 224

Operation manual of solar water controller SR208C

10. Device matchable to this controller


Sensor for collector: high accuracy PT1000 sensor(A01) Parameter: PT1000, 6X50mm

Sensor for tank: high accuracy NTC 10K sensor (A02) Parameter: NTC10K,B=3950, 6X50mm

Thermowell of sensor: stainless thermowell ( A05) Parameter: 1/2' male thread, 8X200mm.

Contactor unit of high power: SR802 When user selects electrical heater as back-up device, we recommend using SR802 unit connecting controller and electrical heater. Technical data of SR802 Dimension: 100mmx100mmx65mm Power supply:180V264V/AC 50/60Hz Suitable power: 4000W Available ambient temperature: -10 ~ 50 C Water proof grade: IP43 SR802 CONNECTION DIAGRAM: