ELECTRICAL DESIGN CALCULATION

SIZING CALCULATION OF CABLES

INPUT:
Equipment name : Chiller Unit -01
Motor tag no : CU-01
Cable tag no : CU-01
Voltage : 415 Volts
Connected load : 44.00 KW
Cable length : 10 mtrs
cable laid between : FROM Chiller Room MCC Panel to CU-01
Derating factor : 0.93
Conductor operating temperature : 70 deg
Efficiency Factor : 85.0%
Power Factor : 80%
Cable :
Conductor current rating : 92 Amps
No of Runs : 2
Selected cable size
-Core : 3 core
-Sqmm : 35.0 sqmm
Method of starting :
Allowable voltage drop at running condition : 5%
Allowable voltage drop at starting condition : 15%

CALCULATION:
44kwx1000/{v/3 x0.85efx0.8pf x415volts}
Full load current of the motor : 90 Amps

Current carrying capacity of the cable : 171 Amps

Hence 1 run of 4/c -16sqmm.Al. Conductorpvc insulated armoured cable is accepted for this purpose.

DC Resistance of cable at 20 c : 0.8680 ohms/km only for reference


AC resistance of cable at 70 c ® : 1.0400 ohms/km
Reactance value at 50Hz for 35sqmm (X) : 0.0860 ohms/km
Impedance value (Z) : 1.0435 ohms/km

Voltage drop at running condition 1.63

% Voltage drop at running condition 0.39% WITHIN THE LIMITS

voltage drop at starting current 4.07

% voltage drop at starting current 0.98% WITHIN THE LIMITS

Hence , the selected cable is within the limits and it is acceptable.