415 volts ± 10%, 50Hz ± 5 %, three phases A.C. supply. The Outdoor Unit as
described above shall be in line with specifications. 4 139400 557600
MAKE: Carrier R410A
1. The Material shall have Fire Approval from CBRI - Roorkie & no toxicity
under flaming and non- flaming condition as per AITM 3.000 (1993) .Adhesive
used for setting the insulation shall be non - flammable, Vapors Proof. All Joints
should be sealed with 3 mm thick 50 mm wide PE tape and Flange to be
overlapped by 6" width of the same material thickness. Finally Duct insulated
should be strapped by 12mm Plastic Packing strip at every random meter &