Fire Resistant Cables

FIRECEL SR 114E Enhanced Cable 300/500 V


BS 5839-1:2017 Clause 26.2e
Mica/Silicone Insulation / Overall Screen BS EN 50200:2015 (PH 120)
Solid & Stranded conductor 830°C fire and mechanical shocks
BS 8434-2:2003 +A2:2009 930°C - 120 min. (60 min.
fire and mechanical shocks + 60 min. fire mechanical
shocks and water spray)
BS 6387:2013
Cat. C fire @ 950°C - 180 min
Cat. W fire 15 min. + fire and water spray 15 min.
Cat. Z fire and mechanical shocks
@ 950°C - 15 min.fire

APPLICATIONS OPERATING TEMPERATURE

FIRECEL SR 114E are primarily intended for -40°C to +90°C


use in fire detection and fire alarm systems,
emergency lighting circuits or if cables need to MINIMUM BENDING RADIUS
LPCB ref. 217g properly operate when fire resistance improve-
(cables up to 4 cores) ment is required. 6 times the outer diameter.
For the scope of the LPCB Typical applications are:
Approval see BS 5839-1 for enhanced fire resistant cables in
www.redbooklive.com fire detection and fire alarm systems for building
BS 5839-8 for voice alarm systems
BS 5839-9 for emergency voice communication
systems.
BS 5266-1 for emergency lighting of premises
BS 8519 for fire-resistant control cable systems
For the scope of the BASEC for life safety and fire-fighting application - Cat-
Approval see www.basec.org.uk egory 2

CABLE CONSTRUCTION COLOUR CODE UP TO 4 CORES N° of cond. Outer diameter Weight


TO HD 308 x cross section (mm2) (mm) (kg/km)
Conductors
Plain annealed copper wire, solid class 1 1 mm2 solid SR 114H
2 cores: 2x1.0 7.9 85
or stranded class 2 according to
3 cores: 3x1.0* 8.4 105
EN 60228.
4 cores: 4x1.0* 9.3 125
Insulation 7 cores: centre 7x1.0 10.9 175
Mica/Glass fire resistant tape covered by 1st layer - 4 cores 12x1.0 14.5 300
high performance fire resistant silicone 12 cores: centre 19x1.0 17.0 470
rubber type EI2 to BS EN 50363-1.
1st layer - 7 cores 1.5 mm2 solid SR 114H
Cabling 19 cores: centre 2x1.5 8.8 105
Insulated cores are cabled together. 1st layer - 4 cores 3x1.5 9.3 130
Overall screen 2nd layer - 10 cores 4x1.5 10.3 165
Aluminium/polyester tape. 7x1.5 12.1 230
(on request the cores can be one colour
12x1.5 16.0 380
Circuit protective conductor or drain wire only, identified by printed numbers)
19x1.5 19.0 590
Uninsulated tinned copper conductor 1.5 mm2 stranded SR 114H-R
of the same section and class as the APPLICABLE STANDARDS
2x1.5 9.2 110
insulated conductors in the 2-, 3- and
Basic design 3x1.5 9.7 135
4-core cables. Drain wire of 0.5 mm2
BS 7629-1 4x1.5 10.5 170
tinned copper conductor is provided in
Fire resistant 2.5 mm2 solid SR 114H
cables with more than 4 conductors.
BS 6387 (cat. C-W-Z) 2x2.5 10.2 150
Outer sheath BS EN 50200 (PH120) 3x2.5 10.8 190
LSZH thermoplastic material type LTS3 BS EN 50200 annex E (fire, mechanical 4x2.5 12.0 240
to BS 7655-6.1. shock and water spray) 2.5 mm2 stranded SR 114H-R
Colour red or white (other colours on BS 8434-2 (120 min) 2x2.5 10.6 155
request). IEC 60331 3x2.5 11.3 190
Flame retardant
4x2.5 12.5 250
BS EN 60332-1-2
Fire retardant 4 mm2 stranded SR 114H-R
BS EN 60332-3-24 (cat. C) 2x4 12.2 220
Acid gas emission 3x4 13.0 280
BS EN 60754-1 4x4 14.4 350
Smoke density approximate values
*
not included in BS 7629-1:2015 and in LPCB/BASEC
BS EN 61034-2 approval.