Daikin Vision Air Handler Manual IM 672-15 LR
Daikin Vision Air Handler Manual IM 672-15 LR
Daikin Vision Air Handler Manual IM 672-15 LR
Table of Contents
Introduction
Nomenclature
CAH 003 G D A C
Unit Storage
• Store on a level surface in a clean, dry location where Belt-Driven fans
temperature can be controlled if possible.
• Reduce belt tension by at least 50% or remove the belts.
• Pack fan and motor bearings (unless motor bearings are
Remove belts if they will be subjected to temperatures
sealed) with compatible grease with the shaft stationary.
exceeding 85° F to avoid deterioration.
After grease has been installed, rotate shaft about 10
rotations. • Remove belt guard when adjusting belts
• Isolate unit from shock and vibration. • Reduce belt tension prior to removing or installing belts.
• Once a month, rotate shaft a minimum of 10 revolutions. • Removing or installing tensioned belts may cause
Insure the stopped position is different than the original personal injury and damage to the sheaves, belts,
position. bearings or shafts.
• Coat shafts with lubricant as needed to prevent corrosion. • Adjustable sheaves should be opened as wide as
possible and the adjustment threads lubricated so they
• A descant bag may be hung in the interior of the unit to
do not corrode. Be careful not to put lubricant on the belt
minimize corrosion in humid storage environments. Do
running surface
not clean galvanized steel surfaces with oil dissolving
chemicals. This may remove the protective coating and
accelerate corrosion.
Prior to start up
• Do not allow coverings to trap moisture on galvanized • Set screws on bearings, fan wheels, and sheaves need to
surfaces. be checked for proper torque. Also check bolt torque for
any taper lock hubs either on the wheel or sheaves.
• Check sheaves for corrosion. Significant corrosion can
cause belt or sheave failure.
• Purge old grease from fan bearings while rotating the
shaft to distribute the new grease evenly and prevent
bearing seal failure.
• Correctly align and tension belts. See on page 64.
Mechanical Installation
Service Clearances
In addition to providing adequate space around the unit for Figure 1: Servicing Space Requirements
piping coils and drains, access to at least one side of the unit
is always required to allow for regular service and routine
maintenance, which includes filter replacement, drain pan
inspection and cleaning, fan bearing lubrication, and belt
adjustment. Provide sufficient space—at least equal to the
length of the coil—on the side of the unit for shaft removal and
coil removal. Space, at least equal to the length of the side
coil, is required for coil removal. Space, at least equal to the
fin height, is required for top coil removal. See Figure 1 for
servicing space requirements.
Rigging
WARNING Figure 4: Units on Skids
Use all lifting points. Improper lifting can cause severe personal injury and
property damage.
CAUTION
Lifting points may not be symmetrical to the center of gravity of the unit.
Ballast or unequal cable lengths maybe required.
DANGER
DO NOT LIFT FROM 2" HOLES AT ENDS OF UNIT. Failure to comply may
result in personal injury or death.
Class II plenum fans that are stacked on another section may Figure 7: Direct-Drive Class II Plenum Fan Stacked Unit
be lifted using the methods shown in the following figures. The
shipping brackets must remain in place and be tight in order to
lift using this method. Figure 6 shows a belt-drive fan with field
supplied eye bolts that are screwed into factory installed hex
AVK fasteners in the main channels supporting the fan. Figure
7 shows a direct-drive fan with field supplied eye bolts on the
motor end and straps around the spring bracket on the inlet
end. When factory installed hex AVK fasteners are installed,
they should be used for lifting. When they are not installed, it is
acceptable to lift from the shipping brackets on the fan. Figure
8 shows dual fans being lifted in a similar manner as the single
direct-drive fan. An eight point lift must be used for dual fans
to make sure both fans are supported properly and the cabinet
structure does not become overloaded along the center.
If the fan section is connected to another section such as a
plenum or access section, then DO NOT attempt to lift both
sections using just the fan section. The other section(s) must
be supported separately using straps.
Figure 15: Base Plate Detail Figure 17: Frame Channel Detail
Figure 16: Base Section Detail Figure 18: D-Gasket Placement Detail (Custom Air Handler
Units only)
Figure 19: Internal Fastening Ceiling Hung Using Angle Iron Channel
Install field-provided angle iron or channels per SMACNA
guidelines. When a unit is unitized (ships in one piece), channel
support each component under the unit width (Figure 21).
NOTE: The supporting angle iron must fully support the 2"
frame channel at each section joint.
When a unit is sectionalized (ships in multiple sections),
channel support each component under the unit width and
provide support under the full length of the unit base (Figure
22). Locate hanger rods so they do not interfere with access
into the unit.
Ceiling suspension using the unit base rails is limited
to unit cabinet widths less than 108". Support units with
cabinets 108" wide and greater with structural members
designed to support the unit at the ends and at intermediate
points along the base rails.
Prop 65—Substances in fuel or from fuel combustion can cause personal injury or death,
and are known to the State of California to cause cancer, birth defects or other reproductive harm.
Bypass Into a Vertical Fan Section External Face and Bypass Duct
Vertical coil sections and the top mounted fan section always Assembly (Sizes 040 to 090)
ship separately and must be mounted together at the job site. When unit sizes 040 to 090 are ordered with external face
The vertical coil section and the bypass duct each has a joining and bypass, the bypass duct ships separately and must be
collar mounted on the leaving air side of the section and duct, attached to the unit in the field. The joining of the bypass duct
respectively (Figure 26). The mounting collar fits into the side to the unit must be done after the unit is assembled. Also, if
(bypass) and bottom (vertical coil section) openings in the fan the bypass duct is over 90" long, the duct does not ship in one
section. To correctly position the collars in the fan openings, piece and must be field assembled. The field assembly of the
assemble the fan and coil section first. Use the steps below for bypass duct to the unit requires the following steps (also refer
assembly. to Figure 27).
1. Place the vertical coil section in position. If an access 1. Position the unit shipping sections together and
section is positioned downstream from the coil section assemble in the equipment room.
and not already assembled to the coil section, secure the
two sections together. 2. After the unit is assembled, lift the duct into position over
the unit. Joining collars are shipped factory assembled
2. Lift the fan section on top of the vertical coil section, to the unit and duct. There is a joining collar located in
taking care to line up the joining collar in the bottom of the top of the bypass opening and in the leaving air side
the fan section. of the bypass duct. These joining collars are used to
3. For sizes 003 to 035, the bypass duct is integral to the provide air seals. Line up the duct with the top openings
unit construction and does not require attachment to in the unit.
the bypass section. For sizes 040 to 090, position and 3. If the bypass duct is longer than 90", the duct ships in
assemble the bypass duct to the bypass section before more than one piece and must be field assembled. Place
joining to the fan. the piece of duct that has the joining collar on the bottom
4. Once the fan is positioned on top of the vertical coil on top of the unit first. Once it is in place, position the
section and the bypass duct and bypass section are other piece of duct. Take care to fit the splice collar into
assembled, position the two assemblies and line up the the first piece of duct and then lower the other end into
joining collars with the openings in the fan and vertical the bypass opening.
coil section. 4. Once the duct is positioned correctly, fasten the duct
5. Once the sections are lined up and in position, secure pieces together with the joining plate provided. To do
the unit together by fastening joining plates to the unit. this, remove the fasteners in the corners of the duct
assemblies, place the plate over the holes in the corners,
and then replace the fasteners (Figure 10 on page 9).
Multizone Assembly
The multizone section may ship completely assembled or Multizone Damper Assembly
it may ship in numerous pieces. Whether the section ships
in a single piece or multiple pieces depends on customer When a multizone unit is ordered with dampers, depending
requirements and the unit size. When a multizone section is on the multizone configuration and size, the damper assembly
over 90" high or 90" wide, split it into sections for shipping. may ship separately (all horizontal and units with a total height
over 90").
The unit may ship in 1, 2, 3, 4, or 5 separate pieces, see Figure
29. Typically, the multizone damper assembly ships separately When the dampers are not factory assembled to the unit, they
(see Multizone Damper Assembly and Figure 29) and must ship to the job site on a skid. An assembly kit with screws and
be attached at the job site. Attach the damper after the other an instruction drawing are included with the damper for field
components are assembled. Use the instructions below for assembly to the unit.
assembling the multizone section (also refer to Figure 29). To assemble:
1. If the diffuser and the cold deck section ship separately, 1. First remove the side plate that encloses insulation from
join them together first. The joining collar mounted in the both sides of the damper assembly.
diffuser fits into the entering air side of the coil section.
2. Lift the damper assembly into position (Figure 29).
Line up the two sections and fasten together.
3. Fasten the assembly to the frame channels within the
2. Once the diffuser and cold deck sections are joined, lift
multizone openings.
the hot deck and bypass sections in place on top of the
diffuser/ cold deck section. If possible, assemble the 4. Use caulking to seal up the areas around the unit frame
hot deck and bypass section (if there is one) together channel to prevent any air leakage.
before lifting on top. There always is a joining collar in 5. After caulking, put the side plates back in place and
the diffuser. The joining collar provides the seal between secure. Damper shaft extensions are provided on both
the sections joints. It is important to line up and fit the ends of the damper assembly for actuation. The dampers
collar in the hot deck and bypass section. For vertical are linked together by a linkage bar on both ends of the
applications, the cold deck also has a joining collar in the damper. The linkage bar is cut at the time of installation
discharge opening. This collar fits in the bottom of the to divide the damper into the required number of zones
vertical bypass section. (refer to Multizone Damper Adjustment on page 17).
3. After the components in the multizone are fitted together,
fasten the joining plates to the corners in the unit exterior. Figure 29: Multizone Damper Assembly
4. If a damper was ordered, assemble it to the section (see
Multizone Damper Assembly and Figure 29).
NOTE: Verify that the joining collars are aligned to seat into
the gasket. Straighten any collars distorted from
shipping or from rigging.
Upper unit—heating
(and optional bypass)
Joining
collars
Duct Connections
Use flexible connectors on the outlet and inlet duct connections Figure 31: Bell Arms at 45° Angle to Vertical Center
of all units. Each zone divider has a W-shaped duct clip. Insert
ductwork into this clip (Figure 30).
Traps Valves
• Size traps in accordance with the manufacturers’ • Do not use modulating steam valves on high pressure
recommendations. Make sure that the required pressure systems.
differential is always available. Do not undersize. • Properly size modulating valves. Do not undersize.
• Use float and thermostatic or bucket traps for low • Freezing conditions (entering air temperatures below
pressure steam. On high pressure steam, use bucket 35°F).
traps. Use thermostatic traps only for air venting.
• Daikin strongly recommends 5JA, 8JA, 5RA and 8RA
• Use bucket traps for on/off control only. coils.
• Locate traps at least 12 inches below the coil return • Supply 5 psi steam to coils at all times.
connection.
• Do not use modulating valves. Provide control by face
• Multiple coil installation and bypass dampers.
• Individually trap each coil or group of coils that is • Consider using two or three coils in series with two
controlled individually trapped. position steam control valves on the coil or coils that
• Coils in series—use separate traps for each coil, or bank handle 35°F or colder air. Use a modulating valve on the
of coils. downstream coil to provide the desired degree of control.
• Coils in parallel—a single trap can be used, but an • Thoroughly mix fresh air and return air before it enters the
individual trap for each coil is preferred. coil. Also, to obtain true air mixture temperatures, properly
• Do not attempt to lift condensate when using modulating locate temperature control elements.
or on/off control. • As additional protection against freeze-up, install the
• With coils arranged for series airflow, use a separate trap sufficiently below the coil to provide an adequate
control on each bank or coil in the direction of airflow. hydrostatic head to remove condensate during an
interruption in the steam pressure. Estimate three feet for
each 1 psi of trap differential required.
• On startup, admit steam to coil ten minutes before
admitting outdoor air.
• Close fresh air dampers if steam supply pressure falls
below the minimum specified.
Control valve
Float and modulating
thermostatic trap Check Valve Strainer Gate Valve
two position
5GA or 8GA coils. Note that the 5TA, 8TA, or 5HA coils. Conden-
addition of a vacuum breaker to sate is lifted to overhead return
permit the coil to drain during main
shutdown.
Table 1: Motor Beside Fan Spring Mount Adjustments Width ≥ 108 All 6.75
Spring Mount Adjustment at Rest Table 5: Class II Direct-Drive Plenum Fan Spring Height
Top or Bottom
Isolator Position Downblast H Upblast H
Horizontal H Fan Size Isolator Type Operating Height (in.)
Unit Sizes 003 – 035 11–36 All 4.0
1 3.75 3.75 4.25 40–44 All 6.75
2 4.25 3.75 4.25
3 4.25 3.75 4.25 Figure 35: Adjusting Large Spring Mount Assembly
4 3.75 3.75 4.25
Unit Sizes 040 – 090
1 6.00 6.00 6.50
2 6.50 6.00 6.50
3 6.50 6.00 6.50
4 6.00 6.00 6.50
Figure 36: Removing “Motor Behind” Shipping Brackets Figure 37: Removing “Motor Beside” Shipping Brackets
Shipping bracket -
Remove and discard - 4 places
Electrical Installation
Wiring
• When the unit is provided with a VFD only, refer to the
DANGER VFD manual for wire size and torque requirements. For
Capacitor Hazardous Voltage! Failure to disconnect power and instances where multiple motors are being driven by a
discharge capacitors before servicing will result in serious injury or death. single VFD, be sure to set up the VFD and size the wiring
Disconnect all electric power (including remote disconnects)before according to the power requirements of all motors that
servicing. Perform lockout/tagout procedures to ensure that power can are being driven by that VFD.
not be energized. For variable frequency drives,or other energy storing • When not being serviced, close and secure electrical
components that have been furnished and mounted by either Daikin, or by panel doors to prevent ingress of moisture and airborne
others, refer to the specific manufacturer’s literature for allowable waiting
contaminants.
periods For discharge of capacitors. Verify capacitors have been discharged
using an appropriate voltmeter.
Control Wiring
• Access to the VFD is through the fan cabinet access door
CAUTION
for single fans. Provide shielded cable only as described
Use copper conductors only! Failure to use copper conductors in the provided VFD manual. Route wire through
can result equipment damage. the panel so that it does not interfere with an other
components or access doors. Do not drill through drip
• Electrical service to each fan must correspond to the pans or drain pans. Refer to the provided VFD installation
rated voltage on the motor or electrical panel nameplate manual for detailed control wiring instructions.
and conform to the National Electric Code and local
• For multiple fans in parallel, the VFD(s) are mounted
restrictions.
inside of the electrical enclosure, which is mounted on
• Connect each fan section metal frame to the building the exterior of the fan section. When multiple fan sections
electrical ground. are provided with multiple VFDs, they must be set up
• A door electrical interlock is not provided as standard. so that the fans always start simultaneously and are set
• Thermal motor protection is external to the unit. Unless to ramp up and down together. Do not attempt to run
the unit is provided with a variable frequency drive fans in parallel at different speeds as this can result in
(VFD) or a unit mounted starter, thermal protection and uneven airflow that can cause performance, sound, and
a disconnect switch provision per electric codes are vibration problems that can lead to failure. Provided that
provided by others. the fan is capable of running fast enough and the motor
• When the unit is factory provided with a disconnect is sized appropriately, VFDs may be operated up to a
switch, starter or a variable frequency drive (VFD), the maximum recommended frequency of 90 Hertz for 1800
components are mounted on the outside of the unit RPM and slower motors. Motors that are 3600 RPM may
cabinet. Factory wiring is provided from the device to the be operated up to a maximum speed of 4000 RPM or
unit internal motor. 66.7 Hertz provided the fan is rated that high. Operation
above 4000 RPM can damage motor bearings and is not
• All electrical components must be grounded to the
recommended.
building central ground. Suitable ground wires and/or
(bonding) lugs are provided for all motors, disconnect
switches, starters, and variable frequency drives. Provide
dedicated ground (bonding) copper conductors in
accordance with local and national codes.
• For units provided with a motor only or with an external
junction box, wire connections are made with suitable
wire nuts or connectors for the gauge wires provided.
• For units provided with a disconnect switch or starter, field
wiring will be terminated to lugs. Wire size and lug torque
requirements are shown on the unit electrical schematic
provided in the component print pocket. All power supply
wire connections must be torqued as shown.
Operation
Startup Checks
WARNING Before Starting the Unit
ROTATING FAN CAUTION
Can cause severe injury or death. Before servicing fans,lockout and tag Equipment damage due to loose fasteners represents improper start-up
out power. and equipment abuse. It is not covered by the warranty.
WARNING Before entering fan section, make sure that fan electrical power
source is disconnected and locked in the OFF position.
FIRE/ELECTRIC SHOCK HAZARD
1. Check that the unit is completely and properly installed
Can cause property damage, personal injury or death. Wire fan power with ductwork connected.
supply and ground motor frame in accordance with local electric codes.
2. Check that all constru tion debris is removed and filters
are clean.
WARNING
3. Check that all electrical work is complete and properly
Fan motor requires overload protection.
terminated.
Failure to provide motor overload protection can result in fire,property
4. Check that all electrical connections are tight and that
damage, electric shock, personal injury, or death. Connect motor to an
the proper voltage is connected. Phase imbalance must
overload protective device rated incompliance with local electric codes.
not exceed 2%.
5. Do not grease ball bearings on the fan shaft and motor
CAUTION
before startup. They are prelubricated.
DO NOT OVERHEAT FAN MOTOR
6. Check tightness of crews in bearings and fan wheel(s).
High air temperatures in the fan section can cause the fan motor to burnout. If retightening is needed, position the fan wheel(s) per
On draw-through air handlers or air handlers with the fan section down the Table 7, page 29 through Table 9, page 30 and
air stream from the heating section, the discharge air temperature of the Table 10 through Table 12, page 31. Torque set
heating section must not exceed 104°F (40°C). screws per Table 13 and , page 31.
7. Check alignment of fan and motor sheaves and belt
When performing startup and service, always take thorough
tension. Adjust if necessary. Check tightness of sheave
safety precautions. Only trained, experienced personnel should
setscrews and/or capscrews (refer to , page 31).
perform these functions.
8. Leak test the thermal system to verify that connections
are tight.
9. Check that the condensate drain is trapped.
10. Rotate the shaft by hand to be sure it is free.
11. If multiple fans are supplied with a block off plate and it is
installed on one of the fans, make sure to only start the
fans without the block off plate. Do not start any fan that
has the block off plate installed on it.
12. If multiple fans are supplied with isolation dampers, make
sure the isolation dampers are fully open before starting
the fans.
Can cause severe injury or death. Before servicing fans,lockout and tag 16.18 5.62 (143) 0.21 (5.33) 24.50 8.56 (217) 0.31 (7.87)
out power. 17.69 6.90 (175) 0.22 (5.59) 27.00 9.47 (241) 0.63 (16.00)
21.56 7.59 (193) 0.24 (6.10) 30.00 10.47 (266) 0.39 (9.91)
Start and run fan. See on page 30 for proper fan rotation. 24.00 8.45 (215) 0.23 (5.84) 33.00 11.75 (298) 0.38 (9.65)
Observe the rotation. If the fan operates backward, reverse two — — — 36.50 325 (12.78) 0.38 (9.65)
legs of the three-phase supply power. — — — 40.25 363 (14.31) 0.50 (12.70)
Note:
NOTE: Variable pitch fan drives usually are provided for 1
To obtain rated air performance, dimensional relationship must be held.
Figure 45: Wheel-to-Inlet Funnel Relationship— Figure 46: Wheel-to-Inlet Funnel Relationship—
13 to 36 Belt-Drive Plenum Fans 40 to 60 Belt-Drive Plenum Fans
Cross Section Reference Cross Section Reference
EQUALLY SPACED
AROUND DIAMETER
A
FUNNEL END TO FAN
WHEEL OPENING
Figure 48: Wheel-to-Inlet Funnel Relationship— Table 11: Wheel-to-Inlet Funnel Relationship—
Inline Fans Overlap Direct-Drive Fans Only Class II fans
Fan Size Overlap (in.)
Overlap 11 0.25
12 0.25
15 0.25
16 0.38
18 0.38
20 0.41
22 0.45
24 0.50
27 0.55
30 0.61
33 0.67
36 0.75
40 0.82
44 0.91
Table 13: Setscrew Torque Specifications— Table 14: Bearing Collar and Wheel Hub Set Screw Torque
Class II Plenum (All Fans Except Class II Plenum Fans)
Torque (ft.-lb) Set Screw Diameter (in) Minimum torque ft/lbs (kg/m)
Fan Size Setscrew Size
Aluminum Steel 1/4 5.5 (0.76)
11/12/13 3/8 19.2 N/A 1/16 10.5 (1.45)
15 3/8 19.2 N/A 3/8 19.0 (2.63)
16 3/8 19.2 N/A 7/16 29.0 (4.01)
18 3/8 19.2 N/A 1/2 42.0 (5.81)
20 3/8 19.2 N/A 5/8 92.0 (12.72)
22 3/8 19.2 N/A
24 3/8 19.2 N/A
27 3/8 19.2 22
30 1/2 41.7 55
33 1/2 41.7 55
36 1/2 41.7 55
40 1/2 41.7 55
44 1/2 41.7 55
49 1/2 41.7 55
54 1/2 41.7 55
60 3/4 115 150
of a lost fan motor, the block off plate is installed on the non-
functional fan to prevent air re-circulation. This is designed to
be a temporary measure unit this fan and/or motor is replaced. Figure 50: Fan Array with Block Off Plate
After fan and/or motor replacement the block off plate is to be
removed and stored outside of the air tunnel.
The Daikin Fan Array has an optional gravity actuated block off
damper. These dampers are equipped with counter weights.
The Daikin Fan Array has an optional actuated block
off damper. These dampers are designed to prevent air
recirculation in the event of a lost fan. Care should be taken
that the damper actuator only be given a close signal if the fan
is not operational (motor burnout for example).
The Daikin Fan Array can be equipped with a fan blank off plate.
See Figure 50 with a block off plate mounted to fan 3C. If the
unit is ordered with the manual block off plate, it will be installed
to fan 1A. This plate has to be removed before start up.
Table 17: DDPL Factors for Free and Ducted Inlet – Optional Transducer for Piezometer Rings
Non-Standard Density Method, Daikin Piezo Ring
A transducer is available for Piezometer rings. Factory
DDPL Size C1 Free Inlet C1 Ducted Inlet mounting locations for the fan transducer is shown in Figure 52
12 783.66 792.43 for direct-drive plenum fans. Figure 53 shows the installation
15 767.48 763.62 for fan array. Wiring for the transducer is field-supplied and
16 732.77 757.40 installed.
18 612.29 619.65
20 653.83 652.65
22 674.42 673.16
24 679.53 681.34
27 656.57 660.15
30 691.07 692.12
33 675.26 677.89
36 675.83 676.67
40 699.51 694.22
44 681.07 681.01
NOTE:
Never drill or screw through
the inlet funnel.
Fan Installed
with (4) ½" Hex
AVK Bolts
BLOCK-OFF PLATE KIT
PART NO FAN SIZE
910199478 355
910199479 450
Operating Limits
Do not exceed the operating limits in Table 21 through Table
25. A fan wheel operated beyond the rpm and temperature
limits shown can suffer permanent distortion or fracture. The
resulting unbalance can cause severe unit vibration.
Gas Furnace
The Daikin unit can be ordered with the optional separated Condensate Drain Lines
combustion feature. Vent and combustion air pipes must
terminate in the same pressure zone. The maximum vent WARNING
length is the equivalent length of pipe including any elbows Failure to connect condensate drains can result in accumulation of
and fittings. Combustion air pipe should be approximately the condensate during heater operation and result in hazardous operation and
same length as the vent pipe and should not exceed 30 ft. in can damage the heat exchanger.
length. The vent and combustion air piping must be properly
supported. Horizontal vent sections must be installed with an
WARNING
upward pitch of not less than ¼ in/ft. (21 mm/m) and securely
supported every 3 ft. Vent and combustion pipe sizes are given Failure to connect and properly install candensate drains can result in water
in Figure 30. flow into the building causing structural damage, injury, and death.
Outdoor Units
Where condensate drains are located outside a heated space
or in a space where temperatures may fall below freezing,
the drain line must be protected. Use a 2.5 to 5 watt per foot
(0.003 to 0.005 kW per meter) at 115 VAC, 40° F (4.4° C) self-
regulating, shielded and waterproof heat tape. Wrap the drain
trap and drain line with heat tape and secure with ties. Follow
the heat tape manufacturer’s installation recommendations.
Disposal of condensate is subject to local codes and
ordinances. In some locals the condensate drain system may
be connected to a sanitary drain within the building. Some
municipalities require that the acidic condensate produced be
neutralized before being discharged into the sanitary sewer. A
condensate neutralizer kit should be used. Refer to installation
instructions provided with the kit. Locate neutralizer where it
is readily accessible for inspection and maintenance. When
a drain is not readily available, a condensate pump might be
needed. Installer is responsible for providing the neutralization
kit and condensate pump.
Wiring/Controls
Single Furnace Recovery from Lockout
1. If the thermostat (controller) is still calling for heat one
2-Stage Controls hour after a lockout occurs, the control will automatically
Sequence reset and initiate a call for heat sequence.
When system is powered up 24 VAC will be applied to the 2. The ignition control may also be manually reset, by
ignition control (IC) terminals 24VAC / GND. The control will turning the thermostat (controller) down and back up to
reset, perform a self-check routine, initiate full time flame previous temperature setting or removing power (24V) to
sensing, flash the diagnostic LED for up to four seconds and IC terminal 24VAC.
enter the thermostat scan standby state. Call for Heat
LED Indications, Normal Operation
1. Thermostat (controller) closes on call for heat powering
terminal T2. • Green, ½ sec on, ½ sec off: Pre-purge, Inter-purge, Post-
purge
2. 24 VAC is supplied to IC terminal T’stat, provided limit
switch is in closed position. • Green, blinking rapidly: Trial for ignition
• Green, on solid: Flame detected, pilot/main burners on
3. The control will check that pressure switch contacts are
open (IC terminal APS (PSW) is not powered).
ERROR CODES - Red Flashes Error Definition Error Type
4. The Induced Draft Fan (ID Fan) is then energized at high
• 1 flash, then pause No flame in trial time Lockout
speed through IC terminal IND.
• 2 flashes, then pause Flame sense stuck on Lockout
5. When the Air Switch (APS-1) closes, a 15 second pre-
purge period begins. • 3 flashes, then pause Pilot/Main relay failure Lockout
• 4 flashes, then pause Repetitive flame loss error Lockout
6. At end of pre-purge period, the spark commences and
either 1st stage or both 1st and 2nd stage gas valves • 5 flashes, then pause Rollout error Lockout
(depending on status of call for heat) are energized for • 6 flashes, then pause APS Airflow error Lockout
the trial for ignition period. • 7 flashes, then pause Internal control error Lockout On
7. If the thermostat (controller) is calling for 1st stage Solid Red Line Voltage/Freq Error Standby
heat only, the 1st stage valve will open (1.0 to 1.4" w.c.
manifold pressure on Natural Gas or 2.5 to 3.0" w.c. on
Propane Gas). If the thermostat (controller is calling for
high heat, both 1st and 2nd stage valves will open (3.3
to 3.5" w.c. manifold pressure on Natural Gas or 9.5 to
10.0" w.c. on Propane Gas).
8. Burners ignite and cross light.
9. When flame is detected by flame sensor the spark is
shut-off immediately and gas valve(s) and combustion
blower remain energized.
10. During heating operation, the thermostat, pressure
switch and main burner flame are constantly monitored
to assure proper system operation.
11. If the 2nd stage thermostat (controller) is satisfied, the 2nd
stage contact opens, de-energizing the 2nd stage valve.
Heater will continue to operate at 1st stage (low fire).
12. When the thermostat (controller) is satisfied and the
demand for heat ends, the 1st stage valve is de-
energized immediately, the control senses loss of flame
and a 30 second post-purge occurs before de-energizing
the ID Fan.
1 115 VAC 2
IGNITION CONTROL
BLK BLK
L1 IND
DRAFT INDUCER
WHT
Not Used
RED
BLK WHT
40VA
1/2 3/4
BLU R 24V C YEL
Factory APS-1 4
Jumper
PUR ORG
PUR AIR SWITCH -HI
YEL YEL
BLU GRY
24VAC Alarm
Indicator
BLU LO YEL
5
2 STG GAS VALVE
GRY YEL
6 HI COM
DRAFT INDUCER
IGNITION CONTROL
BLK BLK 4 2 BLK HI
L1 IND WHT
RED
LO
CR1
XFMR 1
BLK WHT (Com)
40 VA
1 CR1 3
(+) (-) (+) (-) Br/W YEL
BLU 24V SIG
Valve
EXA
Customer
Interlocks
BLU (See Note) T' STAT ORG ORG
T1 T2
HI LIMIT ROLL OUT ROLL OUT
BLU
Factory SWITCH SWITCH (2) ORG
Jumper
ORG APS-1
PUR
PUR
AIR SWITCH -LO
BLU
24V T-Stat APS
(PSW)
Series 5 Ignition Control FLAME
WHT
Gnd Sense SENSOR
Gnd
BLU BLU Syst .
Alarm (V2) Spark
5 MV
ROR
SPARK
IGNITER
YEL YEL
GRY
BLU
24VAC Alarm
YEL Indicator
BLU YEL
LO
2 STG GAS VALVE
YEL
GRY
HI COM
LEGEND: Notes:
1 .) If Customer safety interlocks provided,
CUSTOMER PROVIDED COMPONENT
wire in series from Terminal 3 to T1&
CUSTOMER / FIELD WIRING remove factory jumper
ON
1 INTERNAL TERMINAL CONNECTION 2 .) Dip Switch setting for 0-10VDC Analog
1 2 34
3 EXTERNAL TERMINAL CONNECTION
4. Section A IC Blower (IND) relay contacts close, 15. For analog inputs less than 7.6 VDC, Modulating Section
powering the Induced Draft Fan (ID Fan) which A input will be reduced proportional to the analog input
operates at high speed. voltage signal and will modulate gas input from 25 to
50% of total heater input.
5. Combustion Air Switch (APS-1 Low) closes powering
terminal APS (PSW) initiating a 15 second pre-purge 16. For analog inputs between 7.7 – 10.0 VDC, the SC30-
period. SM2A relay R3 is energized closing contacts between
T10 & T11, powering Section B 2nd stage gas valve.
6. At end of pre-purge period, main gas valve and spark Section B operates at high fire (50% of total heater
igniter are energized to initiate a trial for ignition. input) and ID Fan remains in high speed. LED’s PWR
Burners ignite. (Blue), MOD (Green) R2 (Red), R3 (Red) and AFS
7. The SC30-SM2A will output 8.5 VDC to the M Series (Green) are lit.
modulating valve for a pre-programmed 30 second 17. For analog inputs less than 9.9 VDC, Modulating Section
warm-up period (Yellow (SU) and Green (AFS) LED’s lit) A input will be reduced proportional to the analog input
while maintaining the ID Fan at high speed (Green AFS voltage signal and will modulate the gas input from 25 to
LED remains lit) and heater Section A operates at preset 50% of total heater input.
mid-fire input (30% of total heater input).
18. At an analog input 10.0 VDC, both Section A and Section
8. During this warm-up period, the SC30-SM2A ignores the B will operate at maximum input.
analog input signal to terminals T12 / T13.
19. During heater operation, the thermostat, pressure
9. When the initial timer in SC30-SM2A times out, control switches and main burner flame of both sections are
will respond to analog input at terminals T12 and T13. constantly monitored by their IC’s and SC30-SM2A to
Green (Mod) LED is lit. assure proper system operation.
10. If the controller is providing an analog signal between 20. Section B operation continues to operate at high fire
0.5 and 5.0 VDC to the SC30-SM2A control, only the until the analog input signal to the SC30SM2A control
modulating section (Section A) will operate from 10%- drops below 7.4 VDC. At this point the SC30SM-2A R3
50% of total heater input. relay opens (Red R3 LED off). Section B will operate at
low fire.
21. Modulation will continue on the modulating Section A for
analog input voltages from 7.4 to 4.9 VDC.
22. Section B operation continues until the analog input Recovery from Lockout
signal to the SC30SM2A control drops below 4.8 VDC. At 1. If the thermostat (controller) is still calling for heat one
this point the SC30SM-2A R2 relay opens (Red R2 LED hour after a lockout occurs, the control will automatically
OFF). Section B switches OFF. reset and initiate a call for heat sequence.
23. Modulation will continue on the modulating Section A for 2. The ignition control may also be manually reset,
analog input voltages from 4.8 down to .0.5 VDC. removing power (24V) to IC terminal 24VAC for 5
24. When the thermostat (temperature controller) is seconds then restoring power.
satisfied and the demand for heat ends, the heat enable
(thermostat) contact opens, power is removed from the Capable Controls Status Indicator LED
T’stat terminal on Section A IC and the combination gas
valve is de-energized immediately and a 30 second LED Indications, Normal Operation
post-purge occurs (at high speed) before de-energizing • Green, ½ sec on, ½ sec OFF: Pre-purge, Inter-purge,
the ID Fan. Post-purge
• Green, blinking rapidly: Trial for ignition
Ignition Control Operational Features • Green, on solid: Flame detected, pilot/main burners on
Ignition and Operational failures during a call for heat result in
“lockout” of the ignition control. ERROR CODES - Red Flashes Error Definition Error Type
1. If flame is lost during an operational cycle, the ignition • 1 flash, then pause - No flame in trial time Lockout
control will respond within 0.8 seconds. The spark will • 2 flashes, then pause - Flame sense stuck on Lockout
be energized for a trial for ignition period to attempt to • 3 flashes, then pause - Pilot/Main relay failure Lockout
relight burners and prove flame sensor. If flame is re-
established, normal operation resumes • 4 flashes, then pause - Repetitive flame loss error Lockout
• 5 flashes, then pause - Rollout error Lockout
2. If the burners fail to light or carryover during a trial for
ignition, the control will attempt two additional ignition • 6 flashes, then pause - APS Airflow error Lockout
trials. If no flame is present at the flame sensor within 10 • 7 flashes, then pause - Internal control error Lockout On
seconds, the spark and gas valve will be de-energized. A Solid Red - Line Voltage/Frequency Error Standby
15 second interpurge period begins and the combustion
blower continues to run. After the inter-purge period
another ignition trial will take place.
3. If burner fails to light or prove the flame sensor following
the two additional trials the control will go into lockout.
The valve relay in the IC will be de-energized shutting
of the gas valve immediately and the induced draft fan
following a 30 second post-purge.
WHT
240T6T15
S1 SRTN F L L N WHT
BLK BLK
IGNITION CONTROL
BLK
BLK
L1 IND T5 T6
WHT 7062-6797
SC30-SM2AN DRAFT NDUCER
XFMR 1
BLK WHT (Com)
24V 40 VA
R C
BLU YEL
T2 COM
Section A
HI LIMIT (2)
24VAC Alarm
BLU YEL Indicator
M 36J22
GRY Gas Valve
YEL
COM
BLU
PUR/W
T15 T8 T1
Control Panel 2
PUR/W
T14 T9 T2
APS-2 GRY
RED/W
(Hi) Maxitrol T10 5
Control Panel 2
SC30-SM T11
RED/W
6
M420 RED
Mod
T3 - T13
BLK
0 – 10 VDC
Valve T4 + T12 Input
BLK
RED
40VA
BLU
3 YEL
4
R 24V C
ROLL OUT
SC30-SM2AN Ignition Control (B)
SWITCH (B)
BLU PUR/W ORG APS-3
PUR/W ORG L1
T1 T8 T9 T2 IND
ORG
ORG
PUR
Series 5 Ignition Control
Section B
T-Stat APS
BLU WHT FLAME
24V SENSE SENSOR
BLU
Gnd Gnd
5 MV Alarm (V2) Syst . SPARK
ROR
SPARK
IGNITER
YEL YEL
LEGEND:
24VAC Alarm
CUSTOMER PROVIDED COMPONENT BLU YEL Indicator
LO
RED/W
36J54
CUSTOMER / FIELD WIRING SC30-SM2AN 2 STG GAS VALVE
RED/W GRY YEL
1 INTERNAL TERMINAL CONNECTION
T10 T11 6 HI COM
Rack Furnace
HD Rack assemblies employ a Vernier staging modulating Figure 63: Typical Rack Distribution Wiring
control that modulate gas flow up and down to a lead
modulating furnace to account for varying heat requirements
during operation. Additional slave furnaces have two stage
controls which are activated by relays on the staging control to
meet higher heating requirements. As slave units are brought
on line, the modulating heater gas supply is reduced to meet
the system heat demand. Controls are pre-programmed
depending on the number of furnaces in the system. The
modulating heater is always the top heater.
11 12
GRN GRN
G G
WHT
WHT 6
L2
Provide Disconnect N 4
and Overload BLOWER
Protection as
120V/1/60
BLK
WHT 10 BLK WHT 120 V BK/W
required . H 6 Alarm Output
3
BLK
WHT WHT BLK
5 WHT
9
2
120V COM 13
3
14
4
YEL
7 8 SCEBM-2 YEL BLOWER
Level Sw . BLK BLK 15
SCEBM-2
24V BLU
24V 120V 8 BLK WHT 16
5
YEL On / Off
Switch
BLK PUR BLK BLK
OR/W 14
4
15 12
1
SCEBM-2
PUR 2-10V 13
3
YEL 1 6 11
4 2
Relay A
RED R/W 120V
Hi Limit 1 4 YEL
1 0
CAFS 4 2 Relay B
Heat
T1 PUR
PUR RED 120V WHT
WHT
Enable 1 1 0
PUR/W PUR/W 4
T2
BV RED Low A/S R/BK
Switch 1 7
WHT
WHT
F
+ ORG
BRN
+
Legend
Factory Wiring
Field Wiring
Component Terminal
+
- Building Management System
-
BLK
GND GD
L2
WHT
L1
BLK
WHT WHT
L2
WHT WHT
L2
WHT WHT
L2
WHT WHT 115V Line
L2 L2
Voltage Supply
Mod . BLK
N
Htr .
L1 L1 L1
BLK BLK
12A
Slave 1
L1
BLK L1
N 1
Htr . BLK
Slave 2 12A BLK
N
Htr .
L1 L1
BLK
12A WC-HDR-HXT-FDP-12A-VCB-1M-3SL
Slave 3 BLK L1
N L1
Htr . BLK
12A
WARNING
Improper installation, adjustment, alteration, service, or maintenance can
cause property damage, injury, or death. Read the installation, operating
and maintenance instructions thoroughly before installing or servicing this
equipment.
CAUTION
The use and storage of gasoline or other flammable liquids and vapors in
open containers in the vicinity of this appliance is hazardous.
DANGER
If you smell gas:
1. Open windows.
2. Do Not touch electrical switches.
3. Extinguish any open flames.
4. Immediately call your gas supplier.
WARNING
Failure to provide proper venting could result in property damage, serious
injury, or death.
The unit must have the desiccant reactivation exhaust properly vented to
the outside of the building.
PCO: 000 oF
1. When you first power up the controller you will first see
this on the screen.
Time/Date
Burner Diff: 0.000"wc
Setpt: .600"wc
T0i 0m: e0 /0D: a0 t0e
Time:
Loading.... Date:
00:00:00 M Damper Cmd: 0%
set
time/date: NO
Time:
00:00:00
T0i 0m: e0 /0D: 0a 0t e
Date: M
Loading....
set
t i m e / d a t9. e :o If you
N O arrow down ▼ once again it will take you to the
PCO: 000 F
Time: 0 0 : 0 0 : 0 0 screen above showing the actual “Time” and “Date” if not
Loading.... D a t e : S0 0 o this
o0 f: t0w0 a: 0r e M can be changed by pressing the enter „ button until
2. Then it#will
# # change
# # # # #over # # #self-test mode. s e t Pt iCmOe:/ d0 a0 t0e : Fyou
# # #to# this NOget down to the “set time/date” and then press either
selftest the up ▲ or down ▼ buttons to change the NO to a YES
please wait Software
############### and press the enter „ button again.
############## PCO: 000 oF
selftest 10801091 Rev1
please wait Time/Date
## ## ## ## ## ## ## ## ## ## ## ## ## ## # Software
10801091 Rev1
selftest Time: 00:00:00
please wait Date: 00:00:00 M
Loading....
############## set time/date: NO
Burner 10801091 Rev1
Input Signal: 0%
B u completed
rner PCO: 000 oF
3. After the unit has the self-test, it will change to
H e a t e
the following r E n a b le Inpt: OFF
I n pscreen.
ut Signal: 0% Software
Burner Enable: OFF
###############
M aui n r nl eFe lrIanmp et :: O FF
H e a t e r EB nab OFF selftest
Burner Enable: OFF
In
please wait
B pu ur nt eSr i gCnmadl : 0%
Main Flame: O ## ############
FF
10801091 Rev1
Heater Enable Inpt: OFF
Burner Cmd: 0%
Burner Enable: OFF
Main Flame: OFF
Burner Cmd: 0%
Burner Diff: 0.000"wc Burner
Setpt: .600"wc
Input Signal: 0%
Burner Diff: 0.000"wc
Damper Cmd: 0%
Setpt: .60
H 0e "a w
t ec r E n a b l e I n p t : O F F
Burner Enable: OFF
Damper Cmd: 0%
Burner Diff: 0.000"wc Main Flame: OFF
Setpt: .600"wc
IM 672-15 • VISION AIR HANDLING UNIT B u r n e r C m d : 0 %56 www.DaikinApplied.com
Damper Cmd: 0%
Gas Furnace
10. This will take you to the screen above that should be 15. To view the alarms;
and will have the cursor on the hour, use the up ▲ or a. Push the Alarm Bell button and then scroll
down ▼ buttons to change this number to the using the up ▲ and down ▼ arrow buttons to view
appropriate hour (this is in 24 hour format) example all the alarms before resetting.
9PM would be “21”. Next press the enter „ button
again to place the cursor on the “Min” number, then b. Next, press the Enter button „ if you want to
use the up ▲ or down ▼ arrow buttons to change this reset all of the alarms before viewing them.
number to the actual minute. c. If you press the Enter button „ before pushing
Set Time/Date the up ▲ and down ▼ arrow buttons to scroll
through the alarms you will not know if the unit was
down on more than one alarm.
Time: 13:08 (24hr)
Date: 1/03/18 16. To view what Alarms the unit has faulted on press the
up ▲ or down ▼ arrow to see what alarm that has
caused the unit to shut down. Then press the escape
e button to exit this screen and it will take you to the
top level screen.
*****ALARM*****
11. Next press the enter „ button again to place the Press Enter to
cursor on the “Day” number, then use the up ▲ or Reset ALL Alarms
down ▼ arrow buttons to change this number to the Arrow to View Alarms
actual day of the month. Next press the enter „ button
again to place the cursor on the “Month” number, then
use the up ▲ or down ▼ arrow buttons to change this
number to the actual month. Next press the enter „
button again to place the cursor on the “Year” number,
then use the up ▲ or down ▼ arrow buttons to change
this numberT to 17. If you happen to press the Program button fi you will
i mthee/Dactual
a t e year. Then press the escape
need to have the Service Password to proceed, or just
e button to exit this screen and it will take you to the press the escape e button to exit this screen and it will
top level screen. By using the down ▼ arrow button
Time:
until you get0to0 :the
00:00
screen showing the time and date to take you to the top level screen.
Date: 00:00:00 M
make sure they are changed.
set time/date: NO Enter Password
12. If you arrow down ▼ once again it will take you to the For Configuration
screen above right displaying the program part number 0
P C O : 0 0 0 oF
and rev information.
Software
#####
it
####
10801091 Rev1
18. The Program password is used to enter other parts
of the program, like the Service Menu. (This is not
recommended for the basic user, only for a qualified
trained service technicians)
13. If you arrow down ▼ once again it will take you to back
al: 0% to the first screen (see #3).
14. The Alarm button will light up red when the unit is in
npt: OFF alarm.
ble: OFF
ame: OFF
md: 0%
0.000"wc
.600"wc
BACnet Points
Table 31: Analog Variables
BMS Address Description Read/Write Variable name
2 Burner Cmd Signal to burner R Burner_cmd
3 command to VAV dampers R BurnerDamperCmd
4 Customer Burner Cmd input Signal R Burner_cmd_in
13 pco board temp R pcoTemp
Maintenance
Periodic Maintenance
1. Check all moving parts for wear every six months. Fan Shaft Bearings
2. Check bearing collar, sheave, and wheel hub setscrews,
sheave capscrews, and bearing hold-down bolts for CAUTION
tightness every six months.
For safety, stop rotating quipment. Add one half of the recommended amount
3. Annually check and snug all electrical connections. shown in Figure 24. Start bearing, and run for a few minu Stop bearing
Inspect for signs of water damage such as corrosion and add the second half of the recommended amount. A temperature rise,
and repair if necessary. Check ground conductor and sometimes 30°F (1°C after lubrication is normal. Bearing should operate at
connection integrity and correct if needed. tempe ature less than 200°F (94°C) and should not exceed 225 (107°C)
for intermittent operation. For a lubrication schedule, see Table 22. For
Ball Bearing Lubrication applications that are not in the range of the table, contact Daikin.
CAUTION CAUTION
Bearing overheating potential. Can damage the equipment. Do not over Table 35, Table 36 and Table 37 state general lubrication recommendations
lubricate bearings. Use only a high grade mineral grease with a 200°F safe based on our experience and are intended as suggested or starting points
operating temperature. See below for specific recommended lubricants. only. For best results, specific applications should be monitored regularly
and lubrication intervals and amounts adjusted accordingly.
Motor Bearings
Any good quality lithium or lithium complex base grease, using
Supply and return fans—Supply and return fan motors should
mineral oil, conforming to NLGI grade 2 consistency, and an oil
have grease added after every 2000 hours of operation. Using
viscosity of 455-1135 SUS at 100°F (100-200 cSt at 40°C) may
the following procedure, re-lubricate the bearings while the
be used for re-lubrication.
motor is warm, but not running. Use one of the greases shown
in Table 34. Compatibility of grease is critical. Lubricatable bearings are
supplied with grease fittings or zerks for ease of lubrication with
1. Remove and clean upper and lower grease plugs.
hand or automatic grease guns. Always wipe the fitting and
2. Insert a grease fitting into the upper hole and add clean grease nozzle clean.
grease (Table 34) with a low pressure gun.
3. Run the motor for five minutes before replacing the plugs. Table 35: Lubrication Intervals
NOTE: Direct-Drive Class II fans that are supplied with TECO Bearing Lubrication
Speed Cleanliness
motors have double shielded bearings on frame sizes Temperature Intervals
140T-280T. These bearings are pre-packed with a (Use NLGI #2 Lithium or Lithium Complex Grease)
long life grease and are not regreaseable. Larger 100 RPM Up to 120°F (50°C) Clean 6 to 12 months
frame size TECO motors are regreaseable and follow 500 RPM Up to 150°F (65°C) Clean 2 to 6 months
the same lubrication recommendations as all other 1000 RPM Up to 210°F (100°C) Clean 2 weeks to 2 months
motors. Over 210°F (100°C)
1500 RPM Clean Weekly
to 250°F (120°C)
Table 34: Recommended Lubricants and Amounts for Fan Above 1500 RPM Up to 150°F (65°C) Dirty/Wet 1 week to 1 month
Motor Bearings Max Catalog Over 150°F (65°C) to Dirty/Wet Daily to 2 weeks
Rating 250°F (120°C)
Manufacturers’ Grease NEMA Size Amount to Add (oz.)
Above 250°F
56 to 140 0.08 Contact Browning
(120°C)
140 0.15
180 0.19
Texaco, Polystar or 210 0.30
Polyrex EM (Exxon Mobile) or 250 0.47
Rykon Premium #2 or 280 0.61
Table 36: Recommended Lubricants for Fan Shaft Ball VM/VP Variable Pitch Key Type Sheaves
Bearings
NLGI Mounting:
Name Temperature Base Thickener Grade
1. Mount all sheaves on the motor or driving shaft with the
Texaco, Premium 30° to 350°F Parafinic Lithium 2 setscrews A toward the motor.
RB (34° to 177°C) Mineral Oil
Mobil, AW2 40° to 437°F Mineral Oil Lithium 2 2. Verify that both driving and driven sheaves are in
(40° to 175°C)
alignment and that shafts are parallel.
68° to 356°F
Mobil, SHC 100 Synthetic Lithium 2
(50° to 180°C) 3. Fit internal key D between sheave and shaft and lock
Chevron, Altiplex 60° to 450°F Synthetic Lithium 2 setscrew A securely in place.
Synthetic (51° to 232°C)
40° to 300°F
Exxon, Ronex MP (40° to 149°C) Mineral Oil Lithium 2 Adjusting:
Note:
Temperature ranges over 225°F are shown for lubricants only. High temperature applications
1. Loosen setscrews B and C in moving parts of sheave
are not suitable for standard air handler components. and pull out external key E. (This key projects a small
amount to provide a grip for removing.)
Table 37: Recommended Fan Lubrication Grease Charge 2. To adjust sheave pitch diameter for desired speed, open
moving parts by half or full turns from closed position. Do
Shaft Size in Inches (mm) Weight in Ounces (grams)
not open more than five full turns for A belts or six
1/2 to 3/4 (20) 0.03 (0.85)
full turns for B belts.
7/8 to 1-3/16 (25-30) 0.10 (2.84)
3. Replace external key E and securely tighten setscrews B
1-1/4 to 1-1/2 (35-40) 0.15 (4.25)
over key and setscrews C into keyway in fixed half of the
1-11/16 to 1-15/16 (45-50) 0.20 (5.67)
2 to 2-7/16 (55-60) 0.30 (8.51)
sheave.
2-1/2 to 2-15/16 (65-70) 0.50 (15.59) 4. Put on belts and adjust tension. Do not force belts over
3 to 3-7/16 (75-80) 0.85 (24.10) grooves. See Fan Drive Belt on page 64.
3-1/2 to 4 (85-105) 1.50 (42.53) 5. Make future adjustments by loosening the belt tension
and increasing or decreasing the pitch diameter of the
Fan Drive Adjustments sheave by half or full turns as required. Readjust belt
tension before starting drive.
WARNING 6. To provide the same pitch diameter, adjust both halves
of the two-groove sheaves by the same number of turns
Before servicing fans, lock out and tag out all power to the unit. Fans or from closed position.
belts can cause severe personal injury or death.
7. Verify that all keys are in place and that all se screws
are tight before starting drive. Check setscrews and belt
WARNING tension after 24 hours service.
Do not open the hinged access door and screw-fastenerd access panels
Figure 69: VP Type Sheave Adjustment
while the unit is operating. Moving parts and strong suction forces can
cause severe personal injury or death. A D
C C
E E
E
C C
F
A
F
D D D
Motor
Outer
Locking Ring
Holes (3) for
Capscrews
Spanner
Must be (Do Not Remove) Inner Wrench or Drift
parallel Locking Ring
Center lines
must coincide Stationary
Must be End-Flange Adjustable Fixed
parallel Center-Flange Center-Flange
Bearing
Filters
Front Load Filter Option Table 40: Filter Pressure Drops
Front loaded filter options require that the filters be removed Bag filters—DriPak 2000
and replaced from inside the unit. Efficiency 45% 65% 85% 95%
Rated velocity 625 500 500 500
To remove filters, rotate the wire clips. This releases both the (FPM)
prefilter and the final filter. When installing clean filters, check to Initial 0.20–0.26 0.21–0.30 0.34–0.48 0.50–0.70
pressure drop
verify the filters are fully seated in the frame (Figure 73).
Initial 1.0 1.0 1.0 1.0
pressure drop
Figure 73: Frame and Filters with Holding Clips Cartridge filters—Varicel II MH, 4.25" deep
Efficiency 65% 85% 95%
Rated velocity 500 500 500
(FPM)
Initial 0.43 0.61 0.70
pressure drop
Final pressure 1.5 1.5 1.5
drop
Cartridge filters—Varicel SH, 12" deep
Efficiency 70%
Rated velocity 500
(FPM)
Initial 0.39
pressure drop
Final pressure 1.2
drop
Pleated panel filters
Type Perfect pleat AMAir 1300 4"
Efficiency 30% 30%
Rated Velocity 500 625
(FPM)
Initial
Pressure 0.36 0.36
Drop
Final
Pressure 1.0 1.0
Drop
Filter Gauges 5700 filters
Filter gauges indicate pressure drop for installed filters. If Efficiency N/A
Rated velocity
prefilters are present, the gauge will indicate the pressure drop (FPM) 500
for both pre- and final filters. Initial 0.25
pressure drop
Table 40 shows the typical filter pressure drop for clean filters
Final pressure
at rated air flow. The tables also show a final pressure drop for drop 1.0
front loaded filters. Pleated 62 Plus filters
Where a single filter gauge is used, the prefilters can be Size 2" 4"
removed to check the pressure drop of the final filters. Efficiency 70% 70%
Initial 0.42 0.37
pressure drop
Figure 74: Filter Gauge Final pressure 1.0 1.0
drop
Coils
CAUTION Removing and Replacing Components
Sharp fin edges are a potential injury hazard. Avoid contact with them.
WARNING
1. To obtain maximum performance, the coil must be clean. Before removing any component, lock out and tag out all power to the unit.
Check once a year under normal operating conditions Fans and belts can cause severe personal injury or death.
and, if dirty, brush or vacuum clean. Use a chemical
coil cleaner on multiple row coils. Read and follow the
chemical cleaner’s instructions as some cleaners may Removing a Side or Top Panel
contain harsh chemicals. Take care not to damage fins 1. Remove the flat head fasteners located along the sides
while cleaning. CAUTION—Fin edges are sharp. of the panel.
2. Drain pans in any air conditioning unit may have some 2. Once all fasteners are removed, lift off the panel.
moisture. Algae, etc., can grow due to airborne spores
and bacteria. Periodic cleaning is necessary to prevent Removing a Frame Channel
this buildup from plugging the drain and causing the
drain pan to overflow. Also, keep the drain pans clean Frame channels that run the length of the unit along the top
to prevent the spread of disease. Cleaning should be can be removed to allow access to both the side and top of the
performed by qualified personnel. unit.
3. Dirt and lint can clog the condensate drain, especially 1. First remove any adjoining side and top panel(s).
with dirty filters. Inspect twice a year to help avoid 2. Once the side panel is off, remove the flat head fasteners
overflow. in the corner of the frame channels.
3. Pull the frame channel out the side.
Winterizing Water Coils
4. If any top panel fastens into the frame channel (when
the frame channel is 24” or wider in direction of air flow),
WARNING
remove the fasteners in the top panel before pulling out
Mold can cause personal injury. Clean drain pan regularly so mold does the channel.
not develop.
Parts
Replacement Parts
When writing to Daikin for service or replacement parts, refer to the model number and serial number of the unit stamped on the
serial plate attached to the unit. If replacement parts are required, mention the date of installation of the unit and date of failure,
along with an explanation of the malfunctions and a description of the replacement parts required.
Air Handling
Equipment Warranty Registration Form
To comply with the terms of Daikin Applied Warranty, complete and return this form
within 10 days to the Warranty Department of Daikin Applied.
Check, test, and start procedure for air handling units with or without heat recovery and roof
mounted air handlers.
GENERAL INFORMATION
UNIT INFORMATION
Select Yes or No. If not applicable to the type of unit, select N/A.
I. INITIAL CHECK
B. Are fan drives properly aligned and belts properly adjusted? . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
D. Have the hold-down bolts been backed off on spring mounted fan isolators? . . . . . . . . . . . . . . . . . Yes No N/A
E. With the power off, do fans turn freely by hand?. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
G. Is the main disconnect adequately fused and are fuses installed? . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
H. Are all electrical power connections tight? (Check compressor, electrical box.) . . . . . . . . . . . . . . . . Yes No N/A
J. Fill the drain pan. Does water drain freely? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
C. Supply fan motor amp draw per phase: . . . . . . . . . . . . . . . L1 _____________ L2 _____________ L3 _____________
H. Return fan motor amp draw per phase: . . . . . . . . . . . . . . . L1 _____________ L2 _____________ L3 _____________
L. Record return static pressure at unit (with outside air dampers closed) in inches of H20: . . . . . . . . . . . . . . . _____________
III. DAMPERS
13F-4153 (03/15) 2
Select Yes or No. If not applicable to the type of unit, select N/A.
B. Are there any signs of physical damage to the electric heat coils? . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
H. Operate electric heat with fans off. Electric heat must cycle on high limit control . . . . . . . . . . . . . . . Yes No N/A
13F-4153 (03/15) 3
Select Yes or No. If not applicable to the type of unit, select N/A.
A. Verify power is supplied to the MicroTech III unit controller . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
B. Verify that the shipping screws have been removed from the measuring station vane . . . . . . . . . . . . Yes No N/A
NOTE: This is viewed in the MicroTech III controller, in the Min OA setup menu.
13F-4153 (03/15) 4
Select Yes or No. If not applicable to the type of unit, select N/A.
Thank you for completing this form. Please sign and date below.
13F-4153 (03/15) 5
Installation address:____________________________________________________________________________________________________
Purchasing contractor:__________________________________________________________________________________________________
Address: ____________________________________________________________________________________________
City/State/Zip: _______________________________________________________________________________________
2. How would you rate the overall appearance of the product; i.e., paint, fin damage, etc.?
Excellent Good Fair Poor
3. Did all sections of the unit fit together properly? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
4. Did the cabinet have any air leakage? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
Comments _______________________________________________________________________________________
8. Did the labeling and schematics provide adequate information? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
Comments _______________________________________________________________________________________
Please list any additional comments which could affect the operation of this unit; i.e., shipping damage, failed components, adverse installation applications, etc. If additional comment
space is needed, write the comment(s) on a separate sheet, attach the sheet to this completed Quality Assurance Survey Report, and return it to the Warranty Department with the
completed preceding “Equipment Warranty Registration Form”.
Warranty
All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited
Product Warranty. Consult your local Daikin Applied Representative for warranty details. To find your
local Daikin Applied Representative, go to www.DaikinApplied.com.
Aftermarket Services
To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.DaikinApplied.com.