Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

IMT30A Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 88

Instruction MI 021-517 en

FEB 2016

Foxboro® Model IMT30A Magnetic Flow Signal


Converter

Master Instruction
: IMPRINT ::::::::::::::::::::::::::::::::::::::::::::

All rights reserved. It is prohibited to reproduce this documentation, or any part thereof, without
the prior written authorisation of Invensys Systems, Inc.

Copyright 2016 Invensys Systems Inc.

2 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A CONTENTS

1 Safety instructions 6

1.1 Software history ............................................................................................................... 6


1.2 Intended use ..................................................................................................................... 6
1.3 Certifications .................................................................................................................... 7
1.4 Safety instructions from the manufacturer ..................................................................... 8
1.4.1 Copyright and data protection ................................................................................................ 8
1.4.2 Disclaimer ............................................................................................................................... 8
1.4.3 Product liability and warranty ................................................................................................ 9
1.4.4 Information concerning the documentation........................................................................... 9
1.4.5 Warnings and symbols used................................................................................................. 10
1.5 Safety instructions for the operator............................................................................... 10

2 Device description 11

2.1 Scope of delivery............................................................................................................. 11


2.2 Device description .......................................................................................................... 12
2.3 Nameplates .................................................................................................................... 13

3 Installation 14

3.1 General notes on installation ......................................................................................... 14


3.2 Storage ........................................................................................................................... 14
3.3 Transport ........................................................................................................................ 14
3.4 Installation specifications .............................................................................................. 15
3.5 Mounting of the compact version................................................................................... 15
3.6 Mounting of the wall housing, remote version .............................................................. 15

4 Electrical connections 17

4.1 Safety instructions.......................................................................................................... 17


4.2 Important notes on electrical connection...................................................................... 17
4.3 Electrical cables for remote device versions, notes...................................................... 18
4.3.1 Notes on signal cable A ........................................................................................................ 18
4.3.2 Notes on field current cable C.............................................................................................. 18
4.3.3 Requirements for signal cables provided by the customer ................................................. 19
4.4 Preparing the signal and field current cables ............................................................... 20
4.4.1 Signal cable A (type DS 300), construction........................................................................... 20
4.4.2 Preparing signal cable A, connection to signal converter ................................................... 21
4.4.3 Length of signal cable A........................................................................................................ 22
4.4.4 Preparing field current cable C, connection to signal converter......................................... 23
4.4.5 Preparing signal cable A, connection to flow sensor........................................................... 25
4.4.6 Preparing field current cable C, connection to flow sensor ................................................ 26
4.5 Connecting the signal and field current cables ............................................................. 27
4.5.1 Connecting the signal and field current cables to the signal converter, remote version... 28
4.5.2 Connection diagram for signal and field current cable ....................................................... 29

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 3


CONTENTS IMT30A

4.6 Grounding the flow sensor ............................................................................................. 30


4.7 Connecting the power supply ......................................................................................... 30
4.8 Inputs and outputs, overview ......................................................................................... 32
4.8.1 Description of the CG number .............................................................................................. 32
4.8.2 Fixed, non-alterable output versions ................................................................................... 32
4.9 Description of the inputs and outputs............................................................................ 33
4.9.1 Current output ...................................................................................................................... 33
4.9.2 Pulse output and frequency output ...................................................................................... 34
4.9.3 Status output and limit switch .............................................................................................. 35
4.10 Electrical connection of the outputs ............................................................................ 36
4.10.1 Electrical connection of the outputs................................................................................... 36
4.10.2 Laying electrical cables correctly....................................................................................... 37
4.11 Connection diagrams of outputs .................................................................................. 37
4.11.1 Important notes................................................................................................................... 37
4.11.2 Description of the electrical symbols ................................................................................. 38
4.11.3 Basic and Modbus outputs.................................................................................................. 39
4.11.4 HART® connection .............................................................................................................. 44

5 Start-up 45

5.1 Switching on the power .................................................................................................. 45


5.2 Starting the signal converter ......................................................................................... 45

6 Operation 46

6.1 Safety instructions for the use of the bar magnet ......................................................... 46
6.2 Display and operating elements .................................................................................... 46
6.2.1 Display in measuring mode with 2 or 3 measured values ................................................... 48
6.2.2 Display for selection of submenu and functions, 3 lines ..................................................... 48
6.2.3 Display when setting parameters, 4 lines ............................................................................ 49
6.2.4 Display when previewing parameters, 4 lines...................................................................... 49
6.3 Menu structure ............................................................................................................... 50
6.4 Function tables ............................................................................................................... 52
6.4.1 Menu A, quick setup.............................................................................................................. 52
6.4.2 Menu B, test .......................................................................................................................... 54
6.4.3 Menu C, setup ....................................................................................................................... 55
6.4.4 Set free units......................................................................................................................... 66
6.5 Description of functions ................................................................................................. 66
6.5.1 Reset counter in the menu "quick setup" ............................................................................ 66
6.5.2 Deleting error messages in the menu "quick setup"........................................................... 67
6.6 Status messages and diagnostic information................................................................ 67

4 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A CONTENTS

7 Service 71

7.1 Spare parts availability................................................................................................... 71


7.2 Availability of services .................................................................................................... 71
7.3 Returning the device to the manufacturer..................................................................... 71
7.3.1 General information.............................................................................................................. 71
7.3.2 Preapproval form - Customer returned process-wetted products..................................... 72
7.4 Disposal .......................................................................................................................... 73

8 Technical data 74

8.1 Measuring principle........................................................................................................ 74


8.2 Technical data................................................................................................................. 75
8.3 Dimensions and weights ................................................................................................ 82
8.3.1 Housing ................................................................................................................................. 82
8.3.2 Mounting plate, wall version................................................................................................. 84
8.4 Flow tables ..................................................................................................................... 85
8.5 Measuring accuracy ....................................................................................................... 87

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 5


1 SAFETY INSTRUCTIONS IMT30A

1.1 Software history


The "Electronic Revision" (ER) is consulted to document the revision status of electronic
equipment according to NE 53 for all GDC devices. It is easy to see from the ER whether
troubleshooting or larger changes in the electronic equipment have taken place and how that
has affected the compatibility.

Changes and effect on compatibility


1 Downwards compatible changes and fault repair with no effect on operation (e.g. spelling
mistakes on display)
2-_ Downwards compatible hardware and/or software change of interfaces:
H HART®
M Modbus
X all interfaces
3-_ Downwards compatible hardware and/or software change of inputs and outputs:
I Current output
F, P Frequency / pulse output
S Status output
L Limit switch
X all inputs and outputs
4 Downwards compatible changes with new functions
5 Incompatible changes, i.e. electronic equipment must be changed.

INFORMATION!
In the table below, "x" is a placeholder for possible multi-digit alphanumeric combinations,
depending on the available version.

Release date Electronic revision Changes and Documentation


compatibility
2016 ER3.0.3_ Initial version Issue date: FEB 2016

1.2 Intended use


The electromagnetic flowmeters are designed exclusively to measure the flow and conductivity
of electrically conductive, liquid media.

WARNING!
If the device is not used according to the operating conditions (refer to chapter Technical data),
the intended protection could be affected.

INFORMATION!
This device is a Group 1, Class A device as specified within CISPR11:2009. It is intended for use in
industrial environment. There may be potential difficulties in ensuring electromagnetic
compatibility in other environments, due to conducted as well as radiated disturbances.

6 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A SAFETY INSTRUCTIONS 1

1.3 Certifications
CE marking

The device fulfils the statutory requirements of the following EC directives:


• Low voltage directive
• EMC directive

as well as

• EN 61010
• NAMUR recommendations NE 21 and NE 43

The manufacturer certifies successful testing of the product by applying the CE marking.
A CE declaration of conformity regarding the directives in question and the associated
harmonised standards can be downloaded from our internet site.

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 7


1 SAFETY INSTRUCTIONS IMT30A

1.4 Safety instructions from the manufacturer


1.4.1 Copyright and data protection
The contents of this document have been created with great care. Nevertheless, we provide no
guarantee that the contents are correct, complete or up-to-date.

The contents and works in this document are subject to copyright. Contributions from third
parties are identified as such. Reproduction, processing, dissemination and any type of use
beyond what is permitted under copyright requires written authorisation from the respective
author and/or the manufacturer.

The manufacturer tries always to observe the copyrights of others, and to draw on works created
in-house or works in the public domain.

The collection of personal data (such as names, street addresses or e-mail addresses) in the
manufacturer's documents is always on a voluntary basis whenever possible. Whenever
feasible, it is always possible to make use of the offerings and services without providing any
personal data.

We draw your attention to the fact that data transmission over the Internet (e.g. when
communicating by e-mail) may involve gaps in security. It is not possible to protect such data
completely against access by third parties.

We hereby expressly prohibit the use of the contact data published as part of our duty to publish
an imprint for the purpose of sending us any advertising or informational materials that we have
not expressly requested.

1.4.2 Disclaimer
The manufacturer will not be liable for any damage of any kind by using its product, including,
but not limited to direct, indirect or incidental and consequential damages.

This disclaimer does not apply in case the manufacturer has acted on purpose or with gross
negligence. In the event any applicable law does not allow such limitations on implied warranties
or the exclusion of limitation of certain damages, you may, if such law applies to you, not be
subject to some or all of the above disclaimer, exclusions or limitations.

Any product purchased from the manufacturer is warranted in accordance with the relevant
product documentation and our Terms and Conditions of Sale.

The manufacturer reserves the right to alter the content of its documents, including this
disclaimer in any way, at any time, for any reason, without prior notification, and will not be liable
in any way for possible consequences of such changes.

8 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A SAFETY INSTRUCTIONS 1

1.4.3 Product liability and warranty


The operator shall bear responsibility for the suitability of the device for the specific purpose.
The manufacturer accepts no liability for the consequences of misuse by the operator. Improper
installation or operation of the devices (systems) will cause the warranty to be void. The
respective "Standard Terms and Conditions" which form the basis for the sales contract shall
also apply.

1.4.4 Information concerning the documentation


To prevent any injury to the user or damage to the device it is essential that you read the
information in this document and observe applicable national standards, safety requirements
and accident prevention regulations.

If this document is not in your native language and if you have any problems understanding the
text, we advise you to contact your local office for assistance. The manufacturer can not accept
responsibility for any damage or injury caused by misunderstanding of the information in this
document.

This document is provided to help you establish operating conditions, which will permit safe and
efficient use of this device. Special considerations and precautions are also described in the
document, which appear in the form of icons as shown below.

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 9


1 SAFETY INSTRUCTIONS IMT30A

1.4.5 Warnings and symbols used


Safety warnings are indicated by the following symbols.

DANGER!
This warning refers to the immediate danger when working with electricity.

DANGER!
This warning refers to the immediate danger of burns caused by heat or hot surfaces.

DANGER!
This warning refers to the immediate danger when using this device in a hazardous atmosphere.

DANGER!
These warnings must be observed without fail. Even partial disregard of this warning can lead to
serious health problems and even death. There is also the risk of seriously damaging the device
or parts of the operator's plant.

WARNING!
Disregarding this safety warning, even if only in part, poses the risk of serious health problems.
There is also the risk of damaging the device or parts of the operator's plant.

CAUTION!
Disregarding these instructions can result in damage to the device or to parts of the operator's
plant.

INFORMATION!
These instructions contain important information for the handling of the device.

LEGAL NOTICE!
This note contains information on statutory directives and standards.

• HANDLING
This symbol designates all instructions for actions to be carried out by the operator in the specified sequence.
i RESULT
This symbol refers to all important consequences of the previous actions.
1.5 Safety instructions for the operator
WARNING!
In general, devices from the manufacturer may only be installed, commissioned, operated and maintained by
properly trained and authorized personnel.
This document is provided to help you establish operating conditions, which will permit safe and efficient use of
this device.

10 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A DEVICE DESCRIPTION 2

2.1 Scope of delivery


INFORMATION!
Inspect the packaging carefully for damages or signs of rough handling. Report damage to the
carrier and to the local office of the manufacturer.

INFORMATION!
Do a check of the packing list to make sure that you have all the elements given in the order.

INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order.
Check for the correct supply voltage printed on the nameplate.

Figure 2-1: Scope of delivery


1 Device in the version as ordered
2 Bar magnet (to operate the signal converter when the housing is closed)
3 Documentation (calibration report, FoxDoc DVD with product documentation for flow sensor and signal converter)
4 Signal cable (only for remote version)

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 11


2 DEVICE DESCRIPTION IMT30A

2.2 Device description


Electromagnetic flowmeters are designed exclusively to measure the flow and conductivity of
electrically conductive, liquid media.

Your measuring device is supplied ready for operation. The factory settings for the operating
data have been made in accordance with your order specifications.

The following versions are available:


• Compact version (the signal converter is mounted directly on the flow sensor)
• Remote version (electrical connection to the flow sensor via field current and signal cable)

Figure 2-2: Device versions


1 Compact version
2 Flow sensor with connection box
3 Wall version

12 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A DEVICE DESCRIPTION 2

2.3 Nameplates
INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order.
Check for the correct supply voltage printed on the nameplate.

Figure 2-3: Example of a nameplate


1 Manufacturer
2 Power supply data
3 Electronic version (Electronic Revision)
4 Maximum working pressure
5 GK/GKL values (flow sensor constants); size (mm/inch); field frequency; protection category; materials of wetted parts
6 Product designation, serial number and manufacturing date

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 13


3 INSTALLATION IMT30A

3.1 General notes on installation


INFORMATION!
Inspect the packaging carefully for damages or signs of rough handling. Report damage to the
carrier and to the local office of the manufacturer.

INFORMATION!
Do a check of the packing list to make sure that you have all the elements given in the order.

INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order.
Check for the correct supply voltage printed on the nameplate.

3.2 Storage
• Store the device in a dry, dust-free location.
• Avoid continuous direct sunlight.
• Store the device in its original packing.
• Storage temperature: -40...+70°C / -40...+158°F

3.3 Transport
Signal converter
• No special requirements.

Compact version
• Do not lift the device by the signal converter housing.
• Do not use lifting chains.
• To transport flange devices, use lifting straps. Wrap these around both process connections.

14 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A INSTALLATION 3

3.4 Installation specifications


INFORMATION!
The following precautions must be taken to ensure reliable installation.
• Make sure that there is adequate space to the sides.
• Protect the signal converter from direct sunlight and install a sun shade if necessary.
• Signal converters installed in control cabinets require adequate cooling, e.g. by fan or heat
exchanger.
• Do not expose the signal converter to intense vibrations. The measuring devices are tested
for a vibration level in accordance with IEC 68-2-64.

3.5 Mounting of the compact version


INFORMATION!
The signal converter is mounted directly on the flow sensor. For installation of the flowmeter,
please observe the instructions in the supplied product documentation for the flow sensor.

3.6 Mounting of the wall housing, remote version


INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.

Figure 3-1: Mounting of the wall housing

1 Prepare the holes with the aid of the mounting plate. For further information refer to Mounting
plate, wall version on page 84.
2 Fasten the device securely to the wall with the mounting plate.

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 15


3 INSTALLATION IMT30A

Mounting multiple devices next to each other

[mm] [inch]
a Ø6.5 Ø0.26
b 80 3.15
c 248 9.76
d 310 12.2
e 257 10.1

16 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A ELECTRICAL CONNECTIONS 4

4.1 Safety instructions


DANGER!
All work on the electrical connections may only be carried out with the power disconnected. Take
note of the voltage data on the nameplate!

DANGER!
Observe the national regulations for electrical installations!

WARNING!
Observe without fail the local occupational health and safety regulations. Any work done on the
electrical components of the measuring device may only be carried out by properly trained
specialists.

INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order.
Check for the correct supply voltage printed on the nameplate.

4.2 Important notes on electrical connection


DANGER!
Electrical connection is carried out in conformity with the VDE 0100 directive "Regulations for
electrical power installations with line voltages up to 1000 V" or equivalent national
specifications.

CAUTION!
• Use suitable cable entries for the various electrical cables.
• The flow sensor and signal converter have been configured together at the factory. For this
reason, please connect the devices in pairs. Ensure that the flow sensor constant GKL (refer
to information on the nameplates) are identically set.
• If delivered separately or when installing devices that were not configured together, set the
signal converter to the DN size and GKL of the flow sensor, refer to Function tables on page
52.

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 17


4 ELECTRICAL CONNECTIONS IMT30A

4.3 Electrical cables for remote device versions, notes


4.3.1 Notes on signal cable A
INFORMATION!
Signal cable A (type DS 300) with double shield ensures proper transmission of measured
values.

Observe the following notes:


• Lay the signal cable with fastening elements.
• It is permissible to lay the signal cable in water or in the ground.
• The insulating material is flame-retardant to EN 50265-2-1: 1997 and IEC 60322-1-2: 2005.
• The signal cable does not contain any halogens and is unplasticized, and remains flexible at
low temperatures.
• The connection of the inner shield (10) is carried out via the stranded drain wire (1).
• The connection of the outer shield (60) is carried out via the stranded drain wire (6).

4.3.2 Notes on field current cable C


DANGER!
A shielded 2-wire copper cable is used for the field current cable. The shielding MUST be
connected in the housing of the flow sensor and signal converter.

INFORMATION!
The field current cable is not part of the scope of delivery.

18 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A ELECTRICAL CONNECTIONS 4

4.3.3 Requirements for signal cables provided by the customer


INFORMATION!
If the signal cable was not ordered, it is to be provided by the customer. The following
requirements regarding the electrical values of the signal cable must be observed:

Electrical safety
• To EN 60811 (Low Voltage Directive) or equivalent national regulations.

Capacitance of the insulated conductors


• Insulated conductor / insulated conductor < 50 pF/m
• Insulated conductor / shield < 150 pF/m

Insulation resistance
• Riso > 100 GΩ x km
• Umax < 24 V
• Imax < 100 mA

Test voltages
• Insulated conductor / inner shield 500 V
• Insulated conductor / insulated conductor 1000 V
• Insulated conductor / outer shield 1000 V

Twisting of the insulated conductors


• At least 10 twists per meter, important for screening magnetic fields.

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 19


4 ELECTRICAL CONNECTIONS IMT30A

4.4 Preparing the signal and field current cables


INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.

4.4.1 Signal cable A (type DS 300), construction


• Signal cable A is a double-shielded cable for signal transmission between the flow sensor
and signal converter.
• Bending radius: ≥ 50 mm / 2"

Figure 4-1: Construction of signal cable A


1 Stranded drain wire (1) for the inner shield (10), 1.0 mm2 Cu / AWG 17 (not insulated, bare)
2 Insulated wire (2), 0.5 mm2 Cu / AWG 20
3 Insulated wire (3), 0.5 mm2 Cu / AWG 20
4 Outer sheath
5 Insulation layers
6 Stranded drain wire (6) for the outer shield (60)

20 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A ELECTRICAL CONNECTIONS 4

4.4.2 Preparing signal cable A, connection to signal converter


INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.

• Connection of the two shields in the signal converter is carried out via the stranded drain
wires.
• Bending radius: ≥ 50 mm / 2"

Required materials
• PVC insulating tube, Ø2.5 mm / 0.1"
• Heat-shrinkable tubing
• 2 wire end ferrules to DIN 46 228: E 1.5-8 for the stranded drain wires (1, 6)
• 2 wire end ferrules to DIN 46 228: E 0.5-8 for the insulated conductors (2, 3)

Figure 4-2: Preparation of signal cable A


a = 80 mm / 3.15"

1 Strip the conductor to dimension a.


2 Cut off the inner shield (10) and the outer shield (60). Make sure not to damage the stranded
drain wires (1, 6).
3 Slide the insulating tubes over the stranded drain wires (1, 6).
4 Crimp the wire end ferrules onto the stranded drain wire.
5 Crimp the wire end ferrules onto the conductors (2, 3).
6 Pull the heat-shrinkable tubing over the prepared signal cable.

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 21


4 ELECTRICAL CONNECTIONS IMT30A

4.4.3 Length of signal cable A


INFORMATION!
For temperatures of the medium above 150°C / 300°F, a special signal cable and a ZD
intermediate socket are necessary. These are available including the changed electrical
connection diagrams.

Flow sensor Nominal size Min. electrical Curve for signal


conductivity cable A
DN [mm] [inch] [µS/cm]
9500A 25...150 1...6 20 A1
200...1200 8...48 20 A2
9600A 10...150 3/8...6 20 A1

Figure 4-3: Maximum length of signal cable A


1 Maximum length of signal cable A between the flow sensor and signal converter [m]
2 Maximum length of signal cable A between the flow sensor and signal converter [ft]
3 Electrical conductivity of the medium being measured [μS/cm]

22 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A ELECTRICAL CONNECTIONS 4

4.4.4 Preparing field current cable C, connection to signal converter


DANGER!
A shielded 2-wire copper cable is used as the field current cable. The shielding MUST be
connected in the housing of the flow sensor and signal converter.

INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.

• Field current cable C is not part of the scope of delivery.


• Bending radius: ≥ 50 mm / 2"

Required materials:
• Shielded, at least 2-wire copper cable with suitable heat-shrinkable tubing
• Insulating tube, size according to the cable being used
• Wire end ferrules to DIN 46 228: size according to the cable being used

Length and cross-section of field current cable C


Length Cross-section AF (Cu)

[m] [ft] [mm2] [AWG]

0...150 0...492 2 x 0.75 Cu 1 2 x 18


150...300 492...984 2 x 1.5 Cu 1 2 x 14
300...600 984...1968 2 x 2.5 Cu 1 2 x 12
1 Cu = copper cross-section

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 23


4 ELECTRICAL CONNECTIONS IMT30A

Figure 4-4: Field current cable C, preparation for the signal converter
a = 80 mm / 3.15"

1 Strip the conductor to dimension a.


2 If a stranded drain wire is present, remove the shield that is present. Make sure not to damage
the stranded drain wire.
3 Slide an insulating tube over the stranded drain wire.
4 Crimp a wire end ferrule onto the stranded drain wire.
5 Crimp the wire end ferrules on the conductors.
6 Pull a shrinkable tube over the prepared cable.

24 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A ELECTRICAL CONNECTIONS 4

4.4.5 Preparing signal cable A, connection to flow sensor


INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.

• The outer shield (60) is connected in the terminal compartment of the flow sensor directly via
the shield and a clip.
• Bending radius: ≥ 50 mm / 2"

Required materials
• PVC insulating tube, Ø2.0...2.5 mm / 0.08...0.1"
• Heat-shrinkable tubing
• Wire end ferrule to DIN 46 228: E 1.5-8 for the stranded drain wire (1)
• 2 wire end ferrules to DIN 46 228: E 0.5-8 for the insulated conductors (2, 3)

Figure 4-5: Preparing signal cable A, connection to flow sensor


a = 50 mm / 2"
b = 10 mm / 0.39"

1 Strip the conductor to dimension a.


2 Trim the outer shield (60) to dimension b and pull it over the outer sheath.
3 Remove the stranded drain wire (6) of the outer shield and the inner shield. Make sure not to
damage the stranded drain wire (1) of the inner shield.
4 Slide an insulating tube over the stranded drain wire (1).
5 Crimp the wire end ferrules onto conductors 2 and 3 and the stranded drain wire (1).
6 Pull the heat-shrinkable tubing over the prepared signal cable.

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 25


4 ELECTRICAL CONNECTIONS IMT30A

4.4.6 Preparing field current cable C, connection to flow sensor


INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.

• The field current cable is not included in delivery.


• The shield is connected in the terminal compartment of the flow sensor directly via the shield
and a clip.
• Bending radius: ≥ 50 mm / 2"

Required materials
• Shielded 2-wire insulated copper cable
• Insulating tube, size according to the cable being used
• Heat-shrinkable tubing
• Wire end ferrules to DIN 46 228: size according to the cable being used

Figure 4-6: Preparation of field current cable C


a = 50 mm / 2"
b = 10 mm / 0.4"

1 Strip the conductor to dimension a.


2 Trim the outer shield to dimension b and pull it over the outer sheath.
3 Crimp wire end ferrules onto both conductors.
4 Pull a shrinkable tube over the prepared cable.

26 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A ELECTRICAL CONNECTIONS 4

4.5 Connecting the signal and field current cables


DANGER!
Cables may only be connected when the power is switched off.

DANGER!
The device must be grounded in accordance with regulations in order to protect personnel
against electric shocks.

WARNING!
Observe without fail the local occupational health and safety regulations. Any work done on the
electrical components of the measuring device may only be carried out by properly trained
specialists.

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 27


4 ELECTRICAL CONNECTIONS IMT30A

4.5.1 Connecting the signal and field current cables to the signal converter, remote
version
INFORMATION!
The compact version is supplied pre-assembled from the factory.

Connect the electrical conductors as follows:


1 Press with a screwdriver in the slot on the spring terminal.
2 Insert the electrical conductor into the plug.
3 The conductor will be clamped as soon as the screwdriver is pulled out of the slot.

Figure 4-7: Connecting the signal and field current cables


1 Cable entry for field current cable
2 Cable entry for signal cable
3 Electrical conductor (7)
4 Electrical conductor (8)
5 Connecting the field current cable shield
6 Stranded drain wire (1) of the inner shield (10) of the signal cable
7 Electrical conductor (2)
8 Electrical conductor (3)
9 Stranded drain wire (S) of the outer shield (60)

28 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A ELECTRICAL CONNECTIONS 4

4.5.2 Connection diagram for signal and field current cable


DANGER!
The device must be grounded in accordance with regulations in order to protect personnel
against electric shocks.

• A shielded 2-wire copper cable is used as the field current cable. The shielding MUST be
connected in the housing of the flow sensor and signal converter.
• The outer shield (60) is connected in the terminal compartment of the flow sensor directly via
the shield and a clip.
• Bending radius of signal and field current cable: ≥ 50 mm / 2"
• The following illustration is schematic. The positions of the electrical connection terminals
may vary depending on the housing version.

Figure 4-8: Connection diagram for signal and field current cable
1 Electrical terminal compartment in the signal converter
2 Signal cable A
3 Field current cable C
4 Electrical terminal compartment in the flow sensor
5 Functional ground FE

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 29


4 ELECTRICAL CONNECTIONS IMT30A

4.6 Grounding the flow sensor


CAUTION!
There should be no difference in potential between the flow sensor and the housing or protective
earth of the signal converter!

• The flow sensor must be properly grounded.


• The grounding cable should not transmit any interference voltages.
• Do not use the grounding cable to connect any other electrical devices to ground at the same
time.
• The flow sensors are connected to ground by means of a functional grounding conductor FE.
• Special grounding instructions for the various flow sensors are provided in the separate
documentation for the flow sensor.
• The documentation for the flow sensor also contain descriptions on how to use grounding
rings and how to install the flow sensor in metal or plastic pipes or in pipes which are coated
on the inside.

4.7 Connecting the power supply


DANGER!
• To protect operators from electrical shock, during installation the cable for the power supply
must be run with sheathing insulation up to the mains cover. The insulated individual wires
have to be only below the mains cover!
• If there is no mains cover or if it has been lost, the 100...230 VAC device may only be operated
from the outside (with a bar magnet) while closed!

• The housings of the devices, which are designed to protect the electronic equipment from
dust and moisture, should be kept well closed at all times. Creepage distances and
clearances are dimensioned to VDE 0110 and IEC 664 for pollution severity 2. Supply circuits
are designed for overvoltage category III and the output circuits for overvoltage category II.
• Fuse protection (IN ≤ 16 A) for the infeed power circuit, and also a separator (switch, circuit
breaker) to isolate the signal converter must be provided.

30 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A ELECTRICAL CONNECTIONS 4

Figure 4-9: Terminal compartment for power


1 Cable entry for power supply
2 Mains cover
3 Ground terminal
4 100...230 VAC (-15% / +10%)
5 24 VDC (-30% /+30%)

• To open the cover of the electrical terminal compartment, lightly press in the side walls of the
mains cover 2.
• Flip the mains cover up.
• Connect the power supply.
• Close the mains cover again by flipping it down.

100...230 VAC (tolerance range: -15% / +10%)


• Note the power supply voltage and frequency (50...60 Hz) on the nameplate.

INFORMATION!
240 VAC + 5% is included in the tolerance range.

24 VDC (tolerance range: -30% / +30%)


• Note the data on the nameplate!
• When connecting to functional extra-low voltages, provide a facility for protective separation
(PELV) (acc. to VDE 0100 / VDE 0106 and/or IEC 364 / IEC 536 or relevant national
regulations).

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 31


4 ELECTRICAL CONNECTIONS IMT30A

4.8 Inputs and outputs, overview


4.8.1 Description of the CG number

Figure 4-10: Marking (CG number) of the electronics module and output variants
1 ID number: 0
2 ID number: 0 = standard; 9 = special
3 Power supply
4 Display (language versions)
5 Output version

4.8.2 Fixed, non-alterable output versions


This signal converter is available with various output combinations.

• The grey boxes in the tables denote unassigned or unused connection terminals.
• In the table, only the final digits of the CG no. are depicted.
• Terminals D- and A- are connected for active pulse/frequency output (no galvanic isolation
anymore).
• Available are an active or passive pulse/frequency output, or the active or passive status/limit
output. It's not possible to use both at the same time!

Basic outputs (I/Os)


CG no. Connection terminals

S D- D D+ A- A A+
100 1 Pp / Sp passive Ip + HART® passive 2
R00
connected to Pa active connected to Ia + HART® active 2
A- D-
Pp / Sp passive Ia + HART® active 2
1 Shielding
2 Function changed by reconnecting

Modbus (I/O) (option)


CG no. Connection terminals

B- B B+ S
R00 Sign. A (D0-) Common Sign. B (D1+) Shielding

32 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A ELECTRICAL CONNECTIONS 4

Description of used abbreviations


Ia Ip Current output active or passive
Pa Pp Pulse/frequency output active or passive
Sa Sp Status output/limit switch active or passive

4.9 Description of the inputs and outputs


4.9.1 Current output
INFORMATION!
Depending on the version, the outputs must be connected passively or actively!

• All outputs are electrically isolated from each other and from all other circuits.
• All operating data and functions can be adjusted.
• Passive mode: external power Uext ≤ 32 VDC at I ≤ 22 mA
• Active mode: load impedance RL ≤ 750 Ω at I ≤ 22 mA
• Self-monitoring: interruption or load impedance too high in the current output loop
• Error message possible via status output, error indication on LC display.
• Current value error detection can be adjusted.
• Automatic range conversion via threshold. The setting range for the threshold is between 5
and 80% of Q100%, ± 0...5% hysteresis (corresponding ratio from smaller to larger range of
1:20 to 1:1.25).
Signaling of the active range possible via a status output (adjustable).
• Forward / reverse flow measurement (F/R mode) is possible.

INFORMATION!
For further information refer to Connection diagrams of outputs on page 37 and refer to
Technical data on page 75.

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 33


4 ELECTRICAL CONNECTIONS IMT30A

4.9.2 Pulse output and frequency output


INFORMATION!
Depending on the version, the outputs must be connected passively or actively!

• All outputs are electrically isolated from each other and from all other circuits.
• All operating data and functions can be adjusted.
• Passive mode:
External power supply required: Uext ≤ 32 VDC
I ≤ 100 mA at f ≤ 10 kHz (over range up to fmax ≤ 12 kHz)
• Active mode:
Use of the internal power supply: Unom = 20 VDC
IPeak < 100 mA
IAverage≤ 10 mA at f ≤ 10 kHz (over range up to fmax ≤ 10 kHz)
• Scaling:
Frequency output: in pulses per time unit (e.g. 1000 pulses/s at Q100%);
Pulse output: quantity per pulse.
• Pulse width:
symmetric (pulse duty factor 1:1, independent of output frequency)
automatic (with fixed pulse width, duty factor approx. 1:1 at Q100%) or
fixed (pulse width adjustable as required from 0.05 ms...2 s)
• Forward / reverse flow measurement (F/R mode) is possible.
• The pulse and frequency output can also be used as a status output / limit switch.

INFORMATION!
For further information refer to Connection diagrams of outputs on page 37 and refer to
Technical data on page 75.

34 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A ELECTRICAL CONNECTIONS 4

4.9.3 Status output and limit switch


INFORMATION!
Depending on the version, the outputs must be connected passively or actively!

• The status outputs / limit switches are electrically isolated from each other and from all
other circuits.
• The output stages of the status outputs/limit switches during simple active or passive
operation behave like relay contacts and can be connected with any polarity.
• All operating data and functions can be adjusted.
• Passive mode: external power supply required:
Uext ≤ 32 VDC; I ≤ 100 mA
• Active mode: use of the internal power supply:
Unom = 20 VDC; I ≤ 20 mA
• For information on the adjustable operating states refer to Function tables on page 52.

INFORMATION!
For further information refer to Connection diagrams of outputs on page 37 and refer to
Technical data on page 75.

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 35


4 ELECTRICAL CONNECTIONS IMT30A

4.10 Electrical connection of the outputs


INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.

4.10.1 Electrical connection of the outputs


DANGER!
All work on the electrical connections may only be carried out with the power disconnected. Take
note of the voltage data on the nameplate!

Figure 4-11: Electrical connection of the outputs


1 Cable entry, remote version
2 Cable entry, compact version (right cable entry is optional)
3 Terminal block for the connection of outputs

• Open the housing cover


• Push the prepared cables through the cable entries and connect the necessary conductors.
• Connect the shield.
• Close the housing cover.

INFORMATION!
Ensure that the housing gasket is properly fitted, clean and undamaged.

36 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A ELECTRICAL CONNECTIONS 4

4.10.2 Laying electrical cables correctly

Figure 4-12: Protect housing from dust and water

1 For compact versions with nearly horizontally-oriented cable entries, lay the necessary elec-
tric cables with a drip loop as shown in the illustration.
2 Tighten the screw connection of the cable entry securely.
3 Seal cable entries that are not needed with a plug.

4.11 Connection diagrams of outputs


4.11.1 Important notes
INFORMATION!
Depending on the version, the outputs must be connected passively or actively!

• All groups are electrically isolated from each other and from all other output circuits.
• Passive mode: An external power supply is necessary to operate (activation) the subsequent
devices (Uext).
• Active mode: The signal converter supplies the power for operation (activation) of the
subsequent devices, observe max. operating data.
• Terminals that are not used should not have any conductive connection to other electrically
conductive parts.

Description of used abbreviations


Ia Ip Current output active or passive
Pa Pp Pulse/frequency output active or passive
Sa Sp Status output/limit switch active or passive

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 37


4 ELECTRICAL CONNECTIONS IMT30A

4.11.2 Description of the electrical symbols

mA meter
0...20 mA or 4...20 mA and other
RL is the internal resistance of the measuring point including the cable
resistance
DC voltage source (Uext), external power supply, any connection polarity

DC voltage source (Uext), observe connection polarity according to


connection diagrams

Internal DC voltage source

Controlled internal power source in the device

Electronic or electromagnetic counter


At frequencies above 100 Hz, shielded cables must be used to connect the
counters.
Ri Internal resistance of the counter

Button, NO contact or similar

Table 4-1: Description of symbols

38 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A ELECTRICAL CONNECTIONS 4

4.11.3 Basic and Modbus outputs


CAUTION!
Observe connection polarity.

INFORMATION!
For further information refer to Description of the inputs and outputs on page 33 and refer to
HART® connection on page 44.

Current output active (HART®)


• Uint, nom = 20 VDC
• I ≤ 22 mA
• RL ≤ 750 Ω
• HART® at connection terminals A

Figure 4-13: Current output active Ia

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 39


4 ELECTRICAL CONNECTIONS IMT30A

Current output passive (HART®)


• Uext ≤ 32 VDC
• I ≤ 22 mA
• U0 ≤ 2 V at I = 22 mA
• RL, max = (Uext - U0) / Imax
• HART® at connection terminals A

Figure 4-14: Current output passive Ip

40 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A ELECTRICAL CONNECTIONS 4

INFORMATION!
• For frequencies above 100 Hz, shielded cables are to be used in order to reduce effects from
electrical interferences (EMC).
• Shielding takes place at the electrical connection (S) of the output terminal block.

INFORMATION!
• Independent of connection polarity.
• The output is open if the signal converter is not powered.

Pulse/frequency output passive


• Uext ≤ 32 VDC
• fmax in the operating menu set to fmax ≤ 100 Hz:
I ≤ 100 mA
RL ≤ 47 kΩ
closed:
U0 ≤ 0.2 V at I = 10 mA
U0 ≤ 2 V at I = 100 mA
open:
I ≤ 0.05 mA at Uext = 32 V
• fmax in operating menu set to 100 Hz < fmax ≤ 10 kHz:
(over range up to fmax ≤ 12 kHz)
I ≤ 20 mA
RL ≤ 10 kΩ for f ≤ 1 kHz
RL ≤ 1 kΩ for f ≤ 10 kHz
closed:
U0 ≤ 1.5 V at I = 1 mA
U0 ≤ 2.5 V at I = 10 mA
U0 ≤ 5 V at I = 20 mA
open:
I ≤ 0.05 mA at Uext = 32 V
Use shielded cables!
• The minimum load impedance RL, min is calculated as follows:
RL, min = (Uext - U0) / Imax
• Can also be set as status output; for the electrical connection refer to status output connection diagram.

Figure 4-15: Pulse/frequency output passive Pp

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 41


4 ELECTRICAL CONNECTIONS IMT30A

INFORMATION!
• The active output is galvanically coupled with the current output.
• This output is intended to drive directly mechanical or electronic counters.

Pulse/frequency output active


• Uint, nom ≤ 20 V
• RV = 1 kΩ
• C = 1000 µF
• High current mechanical counter
fmax ≤ 1 Hz
• Low current mechanical counter
I ≤ 20 mA
RL ≤ 10 kΩ for f ≤ 1 kHz
RL ≤ 1 kΩ for f ≤ 10 kHz
closed:
U0 ≥ 12.5 V at I = 10 mA
open:
I ≤ 0.05 mA at Unom = 20 V

Figure 4-16: Pulse/frequency output active Pa

42 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A ELECTRICAL CONNECTIONS 4

INFORMATION!
• Independent of connection polarity.
• The output is open if the signal converter is not powered.

Status output / limit switch passive


• Uext ≤ 32 VDC
• I ≤ 100 mA
• RL = 47 kΩ
• closed:
U0 ≤ 0.2 V at I = 10 mA
U0 ≤ 2 V at I = 100 mA
open:
I ≤ 0.05 mA at Uext = 32 V

Figure 4-17: Status output / limit switch passive Sp

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 43


4 ELECTRICAL CONNECTIONS IMT30A

4.11.4 HART® connection


INFORMATION!
The current output always has HART® capability and is connected at connection terminals A+/A-
/A.
All HART® connections (point-to-point and multi-drop operation) both work actively and
passively.

Example for active HART® connection (point-to-point)

Figure 4-18: HART® connection active (Ia)

1 HART® communicator

The parallel resistance to the HART® communicator must be R ≥ 230 Ω.

Example for passive HART® connection (multi-drop mode)


• I: I0% ≥ 4 mA
• Multi-drop mode I: Ifix ≥ 4 mA = I0%
• Uext ≤ 32 VDC
• R ≥ 230 Ω

Figure 4-19: HART® connection passive (Ip)

1 HART® communicator
2 Other devices with HART® capability

44 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A START-UP 5

5.1 Switching on the power


Before connecting to power, please check that the system has been correctly installed.
This includes:
• The device must be mechanically safe and mounted in compliance with the regulations.
• Remove the bar magnet and keep it on a save place (is only valid for the display version).
• The power connections must have been made in compliance with the regulations.
• The electrical terminal compartments must be secured and the covers have been screwed
on.
• Check that the electrical operating data of the power supply are correct.

• Switching on the power.

5.2 Starting the signal converter


The measuring device, consisting of the measuring sensor and the signal converter, is supplied
ready for operation. All operating data have been set at the factory in accordance with your order
specifications.

When the power is switched on, a self test is carried out. After that the device immediately
begins measuring, and the current values are displayed.

Figure 5-1: Displays in measuring mode (examples for 2 or 3 measured values)


x, y and z denote the units of the measured values displayed

It is possible to change between the two measured value windows, the trend display and the list
with the status messages by pressing the keys ↑ and ↓. For possible status messages, their
meaning and cause refer to Status messages and diagnostic information on page 67.

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 45


6 OPERATION IMT30A

6.1 Safety instructions for the use of the bar magnet


To operate the signal converter when the housing is closed, 4 magnetic keys are available. They
are activated by a bar magnet.

WARNING!
The bar magnet can be dangerous for people with cardiac pacemakers or other metal implants.
Make sure that these people do not use the bar magnet or meet minimum clearances! Observe
the relevant national and local regulations and requirements!

6.2 Display and operating elements

Figure 6-1: Display and operating elements (Example: flow indication with 2 measuring values)
1 Indicates a possible status message in the status list
2 Tag number (is only indicated if this number was entered previously by the operator)
3 Indicates when a key has been pressed
4 1st measured variable in large representation
5 Bargraph indication
6 Push buttons for operation with open housing (see table below for function and representation in text)
7 Magnet keys for operation with closed housing (see table below for function and representation in text)

INFORMATION!
• After 5 minutes of inactivity, there is an automatic return to measuring mode. Previously
changed data is not saved.

46 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A OPERATION 6

Key Measuring mode Menu mode Submenu or function Parameter and data
mode mode
> Switch from measuring Access to displayed Access to displayed For numerical values,
mode to menu mode; menu, then 1st submenu or function move cursor one
press key for 2.5 s, submenu is displayed position to the right
"quick start" menu is
then displayed
^ Reset of display Return to measuring Press 1 to 3 times, Return to submenu or
mode but prompt return to menu mode, function, data saved
whether the data should data saved
be saved
↓ or ↑ Switch between display Select menu Select submenu or Use highlighted cursor
pages: measured function to change number, unit,
value 1 + 2, trend page property and to move
and status page the decimal point
Esc (> + ↑) - - Return to menu mode Return to submenu or
without acceptance of function without
data acceptance of data
Table 6-1: Description of key functionality

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 47


6 OPERATION IMT30A

6.2.1 Display in measuring mode with 2 or 3 measured values

Figure 6-2: Example for display in measuring mode with 2 or 3 measured values
1 Indicates a possible status message in the status list
2 Tag number (is only indicated if this number was entered previously by the operator)
3 1st measured variable in large representation
4 Bargraph indication
5 Depiction with 3 measured values

6.2.2 Display for selection of submenu and functions, 3 lines

Figure 6-3: Display for selection of submenu and functions, 3 lines


1 Indicates a possible status message in the status list
2 Menu, submenu or function name
3 Number relating to 6
4 Indicates position within menu, submenu or function list
5 Next menu(s), submenu or function
(_ _ _ signalise in this line the end of the list)
6 Current menu(s), submenu or function
7 Previous menu(s), submenu or function
(_ _ _ signalise in this line the beginning of the list)

48 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A OPERATION 6

6.2.3 Display when setting parameters, 4 lines

Figure 6-4: Display when setting parameters, 4 lines


1 Current menu(s), submenu or function
2 Number relating to 7
3 Denotes factory setting
4 Denotes permissible value range
5 Permissible value range for numeric values
6 Currently set value, unit or function (when selected, appears with white text, blue background)
This is where the data is changed.
7 Current parameter
8 Factory setting of parameter

6.2.4 Display when previewing parameters, 4 lines

Figure 6-5: Display when previewing parameters, 4 lines


1 Current menu(s), submenu or function
2 Number relating to 6
3 Denotes a changed parameter (simple check of changed data when browsing through lists)
4 Next parameter
5 Currently set data from 6
6 Current parameter (for selection press key >; then see previous chapter)
7 Factory setting of parameter

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 49


6 OPERATION IMT30A

6.3 Menu structure


INFORMATION!
• The menu structure for the standard device is described.
• Special functions for Modbus are described in detail in the corresponding supplementary
instructions.
• Note the key function within and between the columns.

Measuring mode Select ↓ Select menu and/or submenu Select


menu ↑ ↓↑ function
and set
data
↓↑>
^ Press
> 2.5 s
A quick setup > A1 language > - >
^ ^ ^
A2 HART > A2.1 tag
^
A3 RS 485 / Modbus > A3.1 tag
^
A3.2 slave address
A4 reset > A4.1 reset errors
^
A4.2 counter 1
A4.3 counter 2
A5 analogue outputs > A5.1 range
^
A5.2 time constant
A5.3 low flow cutoff
A6 digital outputs > A6.1 max. pulse rate
^
A6.2 pulse value unit
A6.3 value p. pulse
A7 process input > A7.1 device serial no.
^
A7.2 zero calibration
A7.3 size
A7.4 GKL
A7.5 field frequency
A7.6 flow direction
^ B test > B1 simulation > For details about the >
^ ^ submenus refer to Menu ^
B2 actual values B, test on page 54
B3 information
↓↑ ↓↑ ↓↑ ↓↑>

50 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A OPERATION 6

Measuring mode Select ↓ Select menu and/or submenu Select


menu ↑ ↓↑ function
and set
data
↓↑>
^ Press
> 2.5 s
C setup > C1 process input > C1.1 calibration >
^ ^ ^
C1.2 filter
C1.3 empty pipe detect
C1.4 information
C1.5 simulation
^ > C2 I/O (input/output) > C2.1 hardware >
^ ^ ^
C2.1 - 1
C2.1 current output A 1
C2.5 - 1
C2.5 frequency out D 1
C2.5 pulse output D 1
C2.5 status output D 1
C2.5 limit switch D 1
^ > C3 I/O counter > C3.1 counter 1 >
^ ^ ^
C3.2 counter 2
^ > C4 HART > C4.1 HART (on/off) >
^ ^ ^
C4.2 address
C4.3 message
C4.4 description
C4.5 HART units
^ > C6 device > C6.1 device info >
^ ^ ^
C6.2 display
C6.3 1. meas. page
C6.4 2. meas. page
C6.5 graphic page
C6.6 special functions
C6.7 units
C6.8 quick setup
↓↑ ↓↑ ↓↑ ↓↑>
1 Depending on settings in Fct. C2.2 hardware

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 51


6 OPERATION IMT30A

6.4 Function tables


INFORMATION!
• The functions for the standard device are described in the following tables.
• Special functions for Modbus are described in detail in the corresponding supplementary
instructions.
• Depending on the device version, not all functions are available.

6.4.1 Menu A, quick setup

No. Function Setting / Description

A1 language
A1 language Language selection depends on the device version.

A2 HART
A2.1 tag Measuring point identifier (Tag no.) appears in the LC display header (up to 8
digits).

A3 RS485/Modbus
A3.1 tag Measuring point identifier (Tag no.) appears in the LC display header (up to
16 digits). The first 8 digits are identical to the HART® measuring point (see
above).
A3.2 slave address Setting the device address at the Modbus interface.

A4 reset
A4.1 reset errors reset errors?
Select: no/yes
A4.2 counter 1 reset counter?
Select: no / yes (available if activated in C5.9.1)
A4.3 counter 2 reset counter?
Select: no / yes (available if activated in C5.9.2)

A5 analogue outputs
A5.1 range Measuring range for the analogue outputs (current output, frequency output
and display)
A5.2 time constant Time constant for the analogue outputs (current output, frequency output
and display)
A5.3 low flow cutoff Low flow cutoff for the analogue outputs (current output and frequency
output)

52 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A OPERATION 6

A6 digital outputs
A6.1 max. pulse rate Setting the maximum pulse rate.
Limit is 120% of this pulse rate.
A6.2 pulse value unit Selection of the unit from a list, depending on the measurement
A6.3 value p. pulse Setting for pulse output D (volume or mass value per pulse)
Setting: xxx.xxx in l or kg or the unit selected in A6.2

A7 process input
A7.1 device serial no. Serial no. of the system (Fct. C5.1.3)
The following process input parameters are only available, if the quick access has been activated in the menu "setup /
device / quick setup" (Fct. C6.8.3).
A7.2 zero calibration Display of actual zero calibration value.
Query: calibrate zero?
Settings see Fct. C1.1.1.
A7.3 size Select from size table.
A7.4 GKL Set value acc. to nameplate; range: 0.5…20
A7.5 field frequency Setting as on measuring sensor nameplate =
line frequency x value (from the following list):
1/2; 1/4; 1/6; 1/8; 1/12; 1/18; 1/36; 1/50
A7.6 flow direction Define polarity of flow direction.
Forwards (according to the arrow on the measuring sensor) or backwards
(in the opposite direction to the arrow)

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 53


6 OPERATION IMT30A

6.4.2 Menu B, test

No. Function Setting / Description

B1 simulation
B1.1 volume flow Depending on the selection, simulation of the volume or mass flow
mass flow according to the following sequence:
Select:
set value /
break (exit function without simulation)
Query: start simulation?
Select:
no (exit function without simulation) / yes (start simulation)
B1.2 current output A simulation X
[X stands for one of the connection terminals A or D]
B1.3 pulse output D Sequence and settings similar to B1.2, see above!
B1.3 frequency out X
For pulse output a set number of pulses are output in 1 s!
B1.3 limit switch D
B1.3 status output D

B2 actual values
B2.1 operating hours Display the actual operating hours; exit the displayed function with key ^.
B2.2 act. flow speed Display the actual flow speed; exit the displayed function with key ^.
B2.3 electr. temperature Display the actual electronics temperature; exit the displayed function with
key ^.
B2.4 act. coil resistance Display the actual resistance of the field coils.

B3 information
B3.1 C number This number clearly identifies the electronics.
B3.2 Electronic Revision ER Reference identification number, electronic revision and production date of
the device; includes all hardware and software changes
B3.3 device serial no. Serial no. of the system.
B3.4 electronic serial no. Serial no. of the electronics

54 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A OPERATION 6

6.4.3 Menu C, setup

No. Function Settings / descriptions

C1 process input

C1.1 calibration
C1.1.1 zero calibration Display of actual zero calibration value.
calibrate zero?
Select:
break (return with ^ key) /
standard (factory setting) /
manual (display last value, set new value,
range: -1.00…+1 m/s) /
automatic (shows the current value as the new zero calibration value)
C1.1.2 size Select from size table.
C1.1.3 GKL Set value acc. to nameplate; range: 0.5…20
C1.1.4 measurement Select:
volume flow (default setting) /
mass flow (using the fixed density, the volume flow is converted into mass
flow)
C1.1.5 range Range for the analogue outputs (current output, frequency output and
display)
range: 0.0…100%
C1.1.6 density For calculating the mass flow from the volume flow
range: 0.1…5 kg/l
C1.1.7 target conduct. Reference value for on-site calibration; range: 1.000...50000 μS/cm
C1.1.8 EF electr. factor For calculation of the conductivity based on the electrode impedance.
Query: calibrate EF?
Select:
break (return with ^ key) /
standard (with factory setting) /
manual (set desired value) /
automatic (determines EF according to the setting in Fct. C1.1.10)
C1.1.9 field frequency Setting as on measuring sensor nameplate =
line frequency x value (from the following list):
1/2; 1/4; 1/6; 1/8; 1/12; 1/18; 1/36; 1/50
C1.1.10 select settling Select settling (special function)
Select:
standard (fixed allocation) /
manual (manual time setting for the settling time for the field current)
C1.1.11 settling time Only when "manual" selected in Fct. C1.1.10; range: 1.0…250 ms
C1.1.12 line frequency Setting the line frequency.
Select: 50 Hz or 60 Hz
C1.1.13 act. coil resistance Display of the actual resistance of the field coil.

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 55


6 OPERATION IMT30A

C1.2 filter
C1.2.1 limitation Limitation of all flow values, before smoothing by time constant, affects all
outputs
Settings: -xxx.x / +xxx.x m/s; condition: 1st value < 2nd value
Range 1st value: -100.0 m/s ≤ value ≤ -0.001 m/s
Range 2nd value: +0.001 m/s ≤ value ≤ +100 m/s
C1.2.2 flow direction Define the polarity of the flow direction.
forwards (according to the arrow on the measuring sensor) or backwards (in
the opposite direction to the arrow)
C1.2.3 time constant Time constant of all flow measurements.
xxx.x s; range: 0.0…100 s
C1.2.4 pulse filter Suppresses noise due to solids, air/gas bubbles and sudden changes in pH.
Select:
off (without pulse filter) /
on (with pulse filter) /
automatic (with new pulse filter)
Pulse filter "on": The change from one measurement value to the next one is
limited to the value "pulse limitation" for the total time "pulse width".
This filter allows a faster signal tracking for slowly changing flow values.
Pulse filter "automatic": The raw flow values are collected into a buffer,
covering two times the "pulse width" values. This filter is called "median"
filter.
This filter allows a better suppression of pulse shaped disturbances
(particles or air bubbles in very noisy environment).
C1.2.5 pulse width Length of interference and delays to be suppressed on sudden changes in
flow.
Only available, if pulse filter (Fct. C1.2.4) is "on" or "automatic"
xx.x s; range for "on": 0.01…10 s or for "automatic": 0.1...20 s
C1.2.6 pulse limitation Dynamic limitation from one measured value to the next; only if pulse filter
(Fct. C1.2.4) is "on".
xx.x m/s; range: 0.01...100 m/s
C1.2.7 low flow cutoff Sets low flow values to "0"; affects all outputs
x.xxx ± x.xxx m/s (ft/s); range: 0.0…10 m/s (0.0...32.8 ft/s)
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value

C1.3 empty pipe detection


C1.3.1 empty pipe detect Select:
off / empty pipe [F]; empty pipe [S]; empty pipe [I]

Flow indication "= 0" when pipe is empty


C1.3.2 limit empty pipe Only available when empty pipe activated [..] in Fct. C1.3.1.
Range: 0.0…9999 μS (set about 50% of the lowest occurring conductivity in
operation. Conductivity below this value = signal as empty pipe)
C1.3.3 act. conductivity Only available when empty pipe activated [..] in Fct. C1.3.1.
Actual conductivity is indicated. Activation takes place only after setting
mode is exited!

56 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A OPERATION 6

C1.3.4 time constant Only available when empty pipe activated [..] in Fct. C1.3.1.
range: xxx.x s; 0.1...100 s
A damping is set for empty pipe detection.

C1.4 information
C1.4.1 liner Shows material of the liner
C1.4.2 electr. material Shows material of the electrodes.
C1.4.3 calibration date Date on which the measuring sensor was calibrated
C1.4.4 serial no. sensor Shows serial no. of the measuring sensor
C1.4.5 V no. sensor Shows the order number of the measuring sensor
C1.4.6 sensor electr. info Shows serial number of circuit board, software version number and
calibration date of circuit board

C1.5 simulation
C1.5.2 volume flow Sequence see Fct. B1.1
mass flow

No. Function Settings / descriptions

C2 I/O (Inputs/Outputs)

C2.1 hardware
C2.1.1 terminal A Select:
off (switched off) / current output
C2.1.2 terminal D Select:
off (switched off) / frequency output / pulse output / status output / limit
switch

C2.2 current output A


C2.2.1 range 0%…100% Current range for the selected "measurement", e.g. 4...20 mA,
corresponds to 0…100%
xx.x … xx.x mA;
range: 0.00…20 mA (condition: 0 mA ≤ 1st value ≤ 2nd value ≤ 20 mA)
C2.2.2 extended range Min. and max. limits of current values. If the current range is exceeded, the
current is set to these limits.
xx.x…xx.x mA; range: 03.5…21.5 mA (condition: 0 mA ≤ 1st value ≤ 2nd value
≤ 21.5 mA and out of current range)
C2.2.3 error current Specify error current
xx.x mA; range: 3…22 mA (condition: outside of extended range)
C2.2.4 error condition The following error conditions can be selected:
Select:
error in device (error category [F]) /
application error (error category [F]) /
out of specification (error category [F] & [S])

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 57


6 OPERATION IMT30A

No. Function Settings / descriptions


C2.2.5 polarity Set polarity, please note flow direction in C1.2.2!
Select:
both polarities (plus and minus values are displayed) /
positive polarity (display for negative values = 0) /
negative polarity (display for positive values = 0) /
absolute value (always displays positive, with both negative and positive
values)
C2.2.6 low flow cutoff Sets the measurement to "0" for low values
x.xxx ± x.xxx%; range: 0.0…20%
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
C2.2.7 time constant Range: 000.1…100 s
C2.2.8 information Serial no. of the I/O board, software version no. and production date of the
circuit board
C2.2.9 simulation Sequence see B1.2 current output A
C2.2.10 4mA trimming Trimming of the current at 4 mA
Reset to 4 mA restores the factory calibration.
Used for HART® setting.
C2.2.11 20mA trimming Trimming of the current at 20 mA
Reset to 20 mA restores the factory calibration.
Used for HART® setting.

C2.3 frequency out X


C2.3.1 pulse shape Specify the pulse shape
Select:
symmetric (about 50% on and 50% off) /
automatic (constant pulse with about 50% on and 50% off at 100% pulse rate)
/
fixed (fixed pulse rate, setting see below Fct. C2.3.3 100% pulse rate)
C2.3.2 pulse width Only available if set to "fixed" in Fct. C2.3.1
Range: 0.05…500 ms
Note: max. setting value Tp [ms] ≤ 500 / max. pulse rate [1/s], gives the pulse
width = time where the output is activated
C2.3.3 100 % pulse rate Pulse rate for 100% of the measuring range
Range: 1…10000 Hz
Limitation 100% pulse rate ≤ 100/s: Imax ≤ 100 mA
Limitation 100% pulse rate > 100/s: Imax ≤ 20 mA
C2.3.4 polarity Set polarity, please note flow direction in C1.2.2!
Select:
both polarities (plus and minus values are displayed) /
positive polarity (display for negative values = 0) /
negative polarity (display for positive values = 0) /
absolute value (always displays positive, with both negative and positive
values)

58 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A OPERATION 6

No. Function Settings / descriptions


C2.3.5 low flow cutoff Sets the measurement to "0" for low values
x.xxx ± x.xxx%; range: 0.0…20%
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
C2.3.6 time constant Range: 000.1…100 s
C2.3.7 invert signal Select:
off (activated output: switch closed) /
on (activated output: switch open)
C2.3.8 information Serial no. of the I/O board, software version no. and production date of the
circuit board
C2.3.9 simulation Sequence see B1.3 frequency out D

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 59


6 OPERATION IMT30A

C2.3 pulse output D


C2.3.1 pulse shape Specify the pulse shape
Select:
symmetric (about 50% on and 50% off) /
automatic (constant pulse with about 50% on and 50% off at max. pulse rate)
/
fixed (fixed pulse rate, setting see below Fct. C2.3.3 max. pulse rate)
C2.3.2 pulse width Only available if set to "fixed" in Fct. C2.3.1
Range: 0.05…500 ms
Note: max. setting value Tp [ms] ≤ 500 / max. pulse rate [1/s], gives the pulse
width = time where the output is activated
C2.3.3 max. pulse rate Setting the maximum pulse rate.
Limit is 120% of this pulse rate
C2.3.4 pulse value unit Selection of the unit from a list, depending on the measurement
C2.3.5 value p. pulse Set value for volume or mass per pulse.
xxx.xxx, measured value
C2.3.6 polarity Set polarity, please note flow direction in C1.2.2!
Select:
both polarities (plus and minus values are displayed) /
positive polarity (display for negative values = 0) /
negative polarity (display for positive values = 0) /
absolute value (always displays positive, with both negative and positive
values)
C2.3.7 invert signal Select:
off (activated output: switch closed) /
on (activated output: switch open)
C2.3.8 information Serial no. of the I/O board, software version no. and production date of the
circuit board
C2.3.9 simulation Sequence see B1.3 pulse output D

C2.3 status output D


C2.3.1 mode The output shows the following measuring conditions:
out of specification (output set, signals status of category "error in device" or
"application error" or "out of specification" refer to Status messages and
diagnostic information on page 67) /
application error (output set, signals status of the category "error in device" or
"application error" refer to Status messages and diagnostic information on page
67) /
polarity flow (polarity of the current flow) /
over range flow (over range of the flow) /
counter 1 preset (activates counter 1 when preset value is reached) /
counter 2 preset (activates counter 2 when preset value is reached) /
output A (displays the polarity at output A) /
off (switched off) /
empty pipe (when pipe empty, output activated) /
error in device (output set, signals status of the category "error in device" refer
to Status messages and diagnostic information on page 67)
C2.3.2 invert signal Select:
off (activated output: switch closed) /
on (activated output: switch open)
C2.3.3 information Serial no. of the I/O board, software version no. and production date of the circuit
board
C2.3.4 simulation Sequence see B1.3 status output D

60 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A OPERATION 6

C2.3 limit switch D


C2.3.1 threshold Switching level, set threshold with hysteresis
C2.3.2 polarity Set polarity, please note flow direction in C1.2.2!
Select:
both polarities (plus and minus values are displayed) /
positive polarity (display for negative values = 0) /
negative polarity (display for positive values = 0) /
absolute value (always displays positive, with both negative and positive
values)
C2.3.3 time constant Range: 000.1…100 s
C2.3.4 invert signal Select:
off (activated output: switch closed) /
on (activated output: switch open)
C2.3.5 information Serial no. of the I/O board, software version no. and production date of the
circuit board
C2.3.6 simulation For sequence, see B1.3 limit switch D

No. Function Settings / descriptions

C3 I/O counter
C3.1 counter 1 Set function of counter.
_ stands for 1, 2 (= counter 1, 2)
C3.2 counter 2
C3._.1 funct. of counter Select:
sum counter (counts positive + negative values) /
+counter (counts only the positive values) /
-counter (counts only the negative values) /
off (counter is switched off)
C3._.2 preset value If this value is reached, positive or negative, a signal is generated that can be
used for a status output at which "preset counter X" has to be set.
Preset value (max. 8 digits) x.xxxxx in selected unit, see C5.7.10 and C5.7.13
C3._.3 reset counter reset counter?
Select:
no / yes (available if activated in C5.9.1)
C3._.4 set counter Set counter _ to the desired value
Select:
break (exit function) /
set value (opens the editor to make the entry)
Query: set counter?
Select:
no (exit function without setting the value) /
yes (sets the counter and exits the function)
C3._.5 stop counter Counter _ stops and holds the current value
Select:
no (exits the function without stopping the counter) /
yes (stops the counter and exits the function)

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 61


6 OPERATION IMT30A

No. Function Settings / descriptions


C3._.5 start counter Start counter _ after that counter is stopped
Select:
no (exits the function without starting the counter) /
yes (starts the counter and exits the function)
C3._.7 information Serial no. of the I/O board, software version no. and production date of the
circuit board

No. Function Settings / descriptions

C4 I/O HART
The dynamic variables are fixed to the following values:
PV: flow (volume flow or mass flow, depending on the selection of "measurement" in Fct. C1.1.4)
SV: counter 1
TV: counter 2
4V: operating time
C4.1 HART HART® communication is activated or deactivated.
Select:
on (HART® is activated; default setting) /
off (HART® is disabled)
C4.2 address Setting the address for multi-drop operation.
If "address 0" is selected, the current output is in normal operation. For all
other addresses, the current at the output is set to the 0% value.
C4.3 message Input of individual text.
C4.4 description Input of individual text.
C4.5 HART units Unit change of dynamic variables in the display.
Select:
break (cancels copying process) /
display - HART (copies the settings for the display units to the settings for
the dynamic variables) /
load defaults (HART® dynamic variables are reset to defaults)

62 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A OPERATION 6

No. Function Settings / descriptions

C6 device

C6.1 device info


C6.1.1 tag Settable characters (max. 8 digits):
A…Z; a…z; 0…9; / - , .
C6.1.2 C number CG number, cannot be changed; describes the signal converter version
C6.1.3 device serial no. Serial no. of the system, cannot be changed
C6.1.4 electronic serial no. Serial no. of the electronic assembly, cannot be changed
C6.1.5 SW.REV.MS Serial no. of the circuit board, version no. of the main software, production
date of the circuit board
C6.1.6 Electronic Revision ER Reference identification number, electronic revision and production date of
the device; includes all hardware and software changes

C6.2 display
C6.2.1 language Language selection depends on the device version.
C6.2.2 contrast Adjust display contrast for extreme temperatures.
Setting: -9…0…+9
This change takes place immediately, not just when setting mode is exited!
C6.2.3 default display Specification of the default display page that is returned to after a short delay
period.
Select:
none (current page is always active) /
1. meas. page (shows this page) /
2. meas. page (shows this page) /
status page (shows only status messages) /
graphic page (trend of the 1st measurement)
C6.2.4 magnet keys For activating or deactivating the magnet keys.
Select:
on (magnet keys are enabled) /
off (magnet keys are disabled)
C5.2.5 status indication LED This menu function is only available for device versions without display.
Status display via a green or red LED (in case of device error, application error or
out of specification)
C6.2.6 SW.REV.UIS Serial no. of the circuit board, version no. of user interface software, production
date of the circuit board

C6.3 1. meas. page


C6.3.1 format 1.line Number of decimal places specified (depending on available space) for 1.line
of 1.meas. page.

C6.4 2. meas. page


C6.4.1 format 1.line Number of decimal places specified (depending on available space) for 1.line
of 2.meas. page.
C6.4.2 format 2.line Number of decimal places specified (depending on available space) for 2.line
of 2.meas. page.
C6.4.3 format 3.line Number of decimal places specified (depending on available space) for 3.line
of 2.meas. page.

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 63


6 OPERATION IMT30A

C6.5 graphic page


C6.5.1 select range Select:
manual (set range in Fct. C6.5.2) /
automatic (automatic depiction based on the measured values)

Reset only after parameter change or after switching off and on.
C6.5.2 range Set the scaling for the Y axis. Only available if "manual" is set in C6.5.1.
±xxx ±xxx%; range: -100…+100%
(1st value = lower limit / 2nd value = upper limit),
condition: 1st value ≤ 2nd value
C6.5.3 time scale Set the time scaling for the X axis, trend curve
xxx min; range: 0…100 min

C6.6 special function


C6.6.1 reset errors reset errors?
Select: no / yes
C6.6.2 save settings Save current settings.
Select:
break (exit function without saving) /
backup 1 (saves the settings in the backup 1 storage place) /
backup 2 (saves the settings in the backup 2 storage place)
Query: go on with copy? (cannot be undone)
Select:
no (exit the function without saving /
yes (copy current settings to storage backup 1 or backup 2)
C6.6.3 load settings Load saved settings
Select:
break (exit function without loading) /
factory settings (reload factory settings) /
backup 1 (loads the settings from the backup 1 storage place) /
backup 2 (loads the settings from the backup 2 storage place) /
load sensor data (restore factory setting of the values for the measuring
sensor. Display and I/O settings are retained!)
Query: go on with copy? (cannot be undone)
Select:
no (exit the function without saving) /
yes (load data from the selected storage place)
C6.6.4 password quick set Password required to change data in the quick setup menu.
0000 (= to quick setup menu without password)
xxxx (password required); range 4 digits: 0001…9999
C6.6.5 password setup Password required to change data in the setup menu
0000 (= to quick setup menu without password)
xxxx (password required); range 4 digits: 0001…9999

C6.7 units
C6.7.1 volume flow m³/h; m³/min; m³/s; L/h; L/min; L/s (L = litres);
cf/h; cf/min; cf/s; gal/h; gal/min; gal/s;
IG/h; IG/min; IG/s;
free unit (set factor and text in the next two functions, sequence see below)

64 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A OPERATION 6

C6.7.2 text free unit For text to be specified refer to Set free units on page 66:
C6.7.3 [m³/s]*factor Specification of the conversion factor, based on m³/s:
xxx.xxx refer to Set free units on page 66
C6.7.4 mass flow kg/s; kg/min; kg/h; t/min; t/h; g/s; g/min; g/h;
lb/s; lb/min; lb/h; ST/min; ST/h (ST = Short Ton); LT/h (LT = Long Ton);
free unit (set factor and text in the next two functions, sequence see below)

C6.7.5 text free unit For text to be specified refer to Set free units on page 66:
C6.7.6 [kg/s]*factor Specification of the conversion factor, based on kg/s:
xxx.xxx refer to Set free units on page 66
C6.7.7 volume m³; L; hL; mL; gal; IG; in³; cf; yd³;
free unit (set factor and text in the next two functions, sequence see below)
C6.7.8 text free unit For text to be specified refer to Set free units on page 66:
C6.7.9 [m³]*factor Specification of the conversion factor, based on m³:
xxx.xxx refer to Set free units on page 66
C6.7.10 mass kg; t; mg; g; lb; ST; LT; oz;
free unit (set factor and text in the next two functions, sequence see below)
C6.7.11 text free unit For text to be specified refer to Set free units on page 66:
C6.7.12 [kg]*factor Specification of the conversion factor, based on kg:
xxx.xxx refer to Set free units on page 66
C6.7.13 flow speed m/s; ft/s
C6.7.14 density kg/L; kg/m³; lb/cf; lb/gal;
free unit (set factor and text in the next two functions, sequence see below)
C6.7.15 text free unit For text to be specified refer to Set free units on page 66:
C6.7.16 [kg/m³]*factor Specification of the conversion factor, based on kg/m³:
xxx.xxx refer to Set free units on page 66

C6.8 quick setup


Activate quick access in quick setup menu; default setting: quick setup is active (yes)
Select: yes (activated) / no (not activated)
C6.8.1 reset counter 1 Reset counter 1 in menu "quick setup"
Select: yes (activated) / no (not activated)
C6.8.2 reset counter 2 Reset counter 2 in menu "quick setup"
Select: yes (activated) / no (not activated)
C6.8.3 process input Activate quick access to the important process input parameters
Select: yes (activated) / no (not activated)

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 65


6 OPERATION IMT30A

6.4.4 Set free units

Free units Sequences to set texts and factors


Texts
Volume flow, mass flow and density 3 digits before and after the slash
xxx/xxx (max. 6 characters plus a "/")
Permissible characters A…Z; a…z; 0…9; / - + , . *; @ $ % ~ () [] _
Conversion factors
Desired unit = [unit see above] * conversion factor
Conversion factor Max. 9 digits
Shift decimal point ↑ to the left and ↓ to the right

6.5 Description of functions


6.5.1 Reset counter in the menu "quick setup"
INFORMATION!
It may be necessary to activate resetting of the counter in the menu "quick setup".

Key Display Description and setting


> quick setup Press and hold for 2.5 s, then release the key.
> language -
3x↓ reset -
> reset errors -
↓ counter 1 Select desired counter.
↓ counter 2
> reset counter -
no
↓ or ↑ reset counter -
Yes
^ counter 1, 2 Counter has been reset.
3x^ Measuring mode -

66 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A OPERATION 6

6.5.2 Deleting error messages in the menu "quick setup"


INFORMATION!
For the detailed list of the possible error messages refer to Status messages and diagnostic
information on page 67.

Key Display Description and setting


> quick setup Press and hold for 2.5 s, then release the key.
> language -
3x↓ reset -
> reset errors -
> reset? -
no
↓ or ↑ reset? -
yes
^ reset errors Error has been reset.
3x^ Measuring mode -

6.6 Status messages and diagnostic information


Operational faults in device
Messages on the display Description Actions

Status: F _ _ _ _ _ Operational fault in device, mA output ≤ Repair necessary.


3.6 mA or set fault current (depending
on the seriousness of the fault), status
output open, pulse / frequency output:
no pulses
F error in device Error or failure of device. Parameter or Group message, when one of the following
hardware error. No measurement possible. or some other severe error occurs.
F IO 1 Error, operational fault in IO 1. Parameter Load settings (Fct. C4.6.3) (backup 1,
or hardware error. No measurement backup 2 or factory settings). If status
possible. message still does not disappear, replace
electronic unit.
F parameter Error, operational fault of data manager,
electronic unit, parameter or hardware
error. Parameters no longer usable.
F configuration Invalid configuration: display software, bus If device configuration unchanged:
parameter or main software do not match defective, replace electronic unit.
existing configuration.
F display Error, operational fault in display. Defective, replace electronic unit.
Parameter or hardware error. No
measurement possible.
F sensor electronic Error, operational fault in sensor Defective, replace electronic unit.
electronics. Parameter or hardware error.
No measurement possible.
F sensor global Data error in the global data of the Load settings (Fct. C5.6.3) (backup 1,
measuring sensor electronic equipment. backup 2 or factory settings). If status
message still does not disappear, replace
electronic unit.

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 67


6 OPERATION IMT30A

Messages on the display Description Actions

Status: F _ _ _ _ _ Operational fault in device, mA output ≤ Repair necessary.


3.6 mA or set fault current (depending
on the seriousness of the fault), status
output open, pulse / frequency output:
no pulses
F sensor local Data error in the local data of the measuring Defective, replace electronic unit.
sensor electronic equipment.
F field current local Data error in the local data of the field Defective, replace electronic unit.
current supply.
F current output A Error, operational fault in current output. Defective, replace electronic unit.
Parameter or hardware error. No
F current output C measurement possible.
F software user interface Fault revealed by CRC check of operation Replace electronic unit.
software.
F hardware settings The set hardware parameters do not match Answer queries in dialogue mode, follow
the identified hardware. A dialogue appears directions.
in the display. Defective, replace electronic unit.
F hardware detection Existing hardware cannot be identified. Defective, replace electronic unit.
F RAM/ROM error IO1 A RAM or ROM error is detected during the Defective, replace electronic unit.
CRC check.

Application failure
Messages on the display Description Actions

Status: F _ _ _ _ _ Application-dependent fault, device OK, Application test or operator action


but measured values affected. necessary.
F application error Application-dependent fault, but device is Group message, when errors as described
okay. below or other application errors occur.
F empty pipe 1 or 2 measuring electrodes are not in Measuring pipe not filled, function
contact with the medium; measured value is dependent on C1.3.2. Check installation. Or
set to zero. No measurement possible. electrodes completely insulated e.g. by oil
film. Clean!
F flow exceeding limit Measuring range exceeded, filter setting Limitation fct. C1.2.1, increase values.
limits measured values. No message if
empty pipe.
If this limit occurs sporadically in processes with air pockets, solid contents or low
conductivity, then either the limit has to be increased or a pulse filter used so as to quell
the error messages and also reduce the measurement errors.
F field frequency too high Field frequency is not reaching steady state, If Fct. C1.1.14 settling time is on "manual",
a measured flow value is still being supplied increase the value in Fct. C1.1.15. If it is set
but may have errors. Measured values are to "standard", set the field frequency in Fct.
still supplied, but they are always too low. C1.1.13 according to the signal converter
No message if coil broken or bridged. nameplate.
F DC offset ADC over-ranged by DC offsets. No For remote signal converters, check the
measurement can be performed, the flow is connection of the signal cable.
set to zero. No message if empty pipe.
F open circuit A Load on current output A too high, effective Current not correct, mA output cable has
current too low. open circuit or load too high. Check cable,
F open circuit C reduce load (set < 750 ohm).

68 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A OPERATION 6

Messages on the display Description Actions

Status: F _ _ _ _ _ Application-dependent fault, device OK, Application test or operator action


but measured values affected. necessary.
F over range A The current or the corresponding measured Check with Fct. C2.1 hardware or sticker in
value is limited by a filter setting. terminal compartment, which output is
F over range C connected to the terminal.
F over range D The pulse rate or the corresponding If current output: extend Fct. C2.x.6 range
measured value is limited by a filter setting. and Fct. C2.x.8 limitation.
Or the demanded pulse rate is too high. If frequency output: extend values in
Fct. C2.x.5 and Fct. C2.x.7.
F active settings Error during the CRC check of the active Upload backup 1 or backup 2 settings, check
settings. and adjust if necessary.
F factory settings Error during the CRC check of the factory -
settings.
F backup 1 settings Error during the CRC check of the backup 1 Save active settings in backup 1 or 2.
or 2 settings.
F Backup 2 Settings

Measurements out of specification


Messages on the display Description Actions

Status: S _ _ _ _ _ Out of specification, measurement Maintenance required.


continues, accuracy possibly less.
S uncertain measurement Device maintenance necessary; measured Group message, when errors as described
values only conditionally usable. below or other influences occur.
S empty pipe 1 or 2 measuring electrodes are not in Measuring pipe not filled, function
contact with the medium; measured value is dependent on Fct. C1.3.2. Check
set to zero. No measurement possible. installation. Or electrodes completely
insulated e.g. by oil film. Clean!
S field coil broken Field coil resistance too high. Check field coil connections to the
electronic module (for remote versions:
S field coil bridged Field coil resistance too low. field current cable) for open circuit / short
circuit
S electronic temperature Upper limit for the permissible electronic Ambient temperature too high, direct solar
temperature has been exceeded. radiation or, for C version, process
temperature too high.
S overflow counter 1 This is counter 1. Counter has overrun and -
started again at zero.
S overflow counter 2 This is counter 2. Counter has overrun and -
started again at zero.
S backplane invalid The data record on the backplane is invalid. No data can be loaded from the backplane
The CRC check has revealed a fault. when replacing electronics. Save the data to
the backplane again (Service).
S field frequency too high The field frequency is set so high that the Set field frequencey lower, see Fct. C1.1.13.
field current cannot settle. The measured
values displayed are too low.

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 69


6 OPERATION IMT30A

Simulation of the measured values


Messages on the display Description Actions

Status: C _ _ _ _ _ Output values partially simulated or Maintenance required.


fixed
C checks in progress Test mode of the device. Measured values Message depending on the situation via
are possibly simulated values or values with HART® or FDT.
fixed settings.
C test sensor Test function of the measuring sensor -
electronics is active.

Information
Messages on the display Description Actions

Status: I _ _ _ _ _ Information (current measurement OK)


I counter 1 stopped This is counter 1. The counter has stopped. If counter to continue counting, activate
"yes" in Fct. C2.y.9 (start counter).
I counter 2 stopped This is counter 2. The counter has stopped.
I power fail The device was not in operation for an Temporary power failure. Counters did not
unknown period of time, because the power run during it.
was switched off. This message is for
information only.
I over range display 1 1st line on page 1 (2) of display limited by Select in menu "display" Fct. C4.3 and/or
filter setting. C4.4 the 1st or 2nd meas. page and increase
I over range display 2 values in functions C4.z.3 range and/or
C4.z.4 limitation.
I over range conductivity The limits for the conductivity measurement If the measuring sensor has been properly
have been exceeded (>10000 µS/cm) or are connected and filled with medium, this does
lower than permitted (<0.1 µS/cm). not affect the flow measurement. The
conductivity measured values cannot be
used.
I backplane sensor The data on the backplane are not usable -
because they have been generated with an
incompatible version.
I backplane settings The global settings on the backplane are not -
usable because they have been generated
with an incompatible version.
I backplane difference The data on the backplane differ from the -
data in the display. If the data are usable, a
dialogue is indicated in the display.
I conductivity off Conductivity measurement switched off. Change the settings in Fct. C1.3.1.
I empty pipe 1 or 2 measuring electrodes are not in Measuring pipe not filled, function
contact with the medium; measured value is dependent on Fct. C1.3.2. Check
set to zero. No measurement possible. installation. Or electrodes completely
insulated e.g. by oil film. Clean!
I diagnosis channel off Diagnosis value switched off. Change the settings in Fct. C1.3.17.

70 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A SERVICE 7

7.1 Spare parts availability


The manufacturer adheres to the basic principle that functionally adequate spare parts for each
device or each important accessory part will be kept available for a period of 3 years after
delivery of the last production run for the device.

This regulation only applies to spare parts which are subject to wear and tear under normal
operating conditions.

7.2 Availability of services


The manufacturer offers a range of services to support the customer after expiration of the
warranty. These include repair, maintenance, technical support and training.

INFORMATION!
For more precise information, please contact your local sales office.

7.3 Returning the device to the manufacturer


7.3.1 General information
This device has been carefully manufactured and tested. If installed and operated in accordance
with these operating instructions, it will rarely present any problems.

CAUTION!
Should you nevertheless need to return a device for inspection or repair, please pay strict
attention to the following points:
• Due to statutory regulations on environmental protection and safeguarding the health and
safety of the personnel, the manufacturer may only handle, test and repair returned devices
that have been in contact with products without risk to personnel and environment.
• This means that the manufacturer can only service this device if it is accompanied by the
following certificate (see next section) confirming that the device is safe to handle.

CAUTION!
If the device has been operated with toxic, caustic, flammable or water-endangering products,
you are kindly requested:
• to check and ensure, if necessary by rinsing or neutralising, that all cavities are free from
such dangerous substances,
• to enclose a certificate with the device confirming that is safe to handle and stating the
product used.

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 71


7 SERVICE IMT30A

7.3.2 Preapproval form - Customer returned process-wetted products


CAUTION!
In compliance with U.S. Federal OSHA Standard 29CFR1910.1200 process information must be
reviewed previous to receiving authorization to return material to Invensys Systems Inc.

NO PRODUCT EXPOSED TO HYDROFLUORIC ACID OR MERCURY WILL BE ACCEPTED!


Date: ________________
Customer information
Customer’s name:
Address:
Phone no:
Fax no.:
Contact’s name:
Rep information
Rep’s name:
Address:
Phone no:
Fax no.:
Contacts’ name:
Product being returned:
Model No.:
Serial no.:
Under warranty? YES NO
Copies of MSDS sheets for all processes including cleaning solutions may be required.
Type of process (what chemicals/materials were processed through the unit):

Explain what steps were taken to decontaminate the unit: (was unit steam cleaned, rinsed out with water,
chemically cleaned etc.)
Form completed by: _________________________ _________________________
Print name Signature
Date: ________________

CLEANING STATEMENT
(Note: Your item will not be serviced unless the following cleaning statement has been signed):

I certify that the above referenced item has been properly purged and cleaned, complies with U.S.
Department of Transportation shipping requirements and DOES NOT present a health and/or safety hazard
(as defined by OSHA) to our Customer Repair personnel.

Print name: _________________________ Signature: _________________________


Print title: ___________________________ Date: _____________________________
Please fax the completed form to the Customer Satisfaction Center (508) 549-4999

72 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A SERVICE 7

7.4 Disposal
CAUTION!
Disposal must be carried out in accordance with legislation applicable in your country.

Separate collection of WEEE (Waste Electrical and Electronic Equipment) in the European Union:
According to the directive 2012/19/EU, the monitoring and control instruments marked with the
WEEE symbol and reaching their end-of-life must not be disposed of with other waste
waste.
The user must dispose of the WEEE to a designated collection point for the recycling of WEEE or
send them back to our local organisation or authorised representative.

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 73


8 TECHNICAL DATA IMT30A

8.1 Measuring principle


An electrically conductive fluid flows inside an electrically insulated pipe through a magnetic
field. This magnetic field is generated by a current, flowing through a pair of field coils.
Inside of the fluid, a voltage U is generated:
U=v*k*B*D

in which:
v = mean flow velocity
k = factor correcting for geometry
B = magnetic field strength
D = inner diameter of flowmeter

The signal voltage U is picked off by electrodes and is proportional to the mean flow velocity v
and thus the flow rate q. A signal converter is used to amplify the signal voltage, filter it and
convert it into signals for totalizing, recording and output processing.

Figure 8-1: Measuring principle


1 Field coils
2 Magnetic field
3 Electrodes
4 Induced voltage (proportional to flow velocity)

74 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A TECHNICAL DATA 8

8.2 Technical data


INFORMATION!
• The following data is provided for general applications. If you require data that is more
relevant to your specific application, please contact us or your local sales office.
• Additional information (certificates, special tools, software,...) and complete product
documentation can be downloaded free of charge from the website.

Measuring system
Measuring principle Faraday's law of induction
Application range Continuous measurement of current volume flow, flow velocity, conductivity,
mass flow (at constant density), coil temperature of the flow sensor

Design
Modular construction The measuring system consists of a flow sensor and a signal converter.
Flow sensor
9500A DN25...1200 / 1…48"
9600A DN10...150 / 3/8...6"
Signal converter
Compact version (C) 9500A & 9600A with IMT30A C
Wall-mounted remote version (W) IMT30A W
Options
Outputs Current output (incl. HART®), pulse output, frequency output, status output
and/or limit switch
Note: It's not possible to use the pulse/frequency output with the status output
at the same time!
Counter 2 internal counters with a max. of 10 counter places (e.g. for counting volume
and/or mass units)
Verification Integrated verification, diagnostic functions: measuring device, empty pipe
detection, stabilisation
Communication interfaces HART®
Modbus

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 75


8 TECHNICAL DATA IMT30A

Display and user interface


Graphic display LC display
Size: 128 x 64 pixels, corresponds to 59 x 31 mm = 2.32" x 1.22"
Ambient temperatures below -25°C / -13°F may affect the readability of the
display.
Operating elements 4 push buttons for operating the signal converter when the housing is open.
4 magnet keys for operating the signal converter when the housing is closed.
Remote control Only generic and not device-specific DDs and DTMs available!
PACTwareTM (including Device Type Manager (DTM))
HART® Communicator
AMS®
All DTMs and drivers are available free of charge from the manufacturer's
website.
Display functions
Operating menu Setting the parameters using 2 measuring pages, 1 status page, 1 graphic page
(measured values and graphics are freely adjustable)
Language display texts (as language Standard: English, French, German, Dutch, Portuguese, Swedish, Spanish,
package) Italian
Eastern Europe: English, Slovenian, Czech, Hungarian
Northern Europe: English, Danish, Polish, Finnish
Southern Europe: English, Turkish
China: English, German, Chinese
Russia: English, German, Russian
Units Metric, British and US units selectable as required from lists for volume / mass
flow and counting, flow velocity, electrical conductivity, temperature

Measuring accuracy
Reference conditions Medium: water
Temperature: +20°C / +68°F
Pressure: 1 bar / 14.5 psi
Inlet section: ≥ 5 DN
Maximum measuring error ±0.5% of the measured value above 0.5 m/s; depending on the flow sensor
±2.5 mm/s below 0.5 m/s; independent of the flow sensor
For detailed information and accuracy curves, refer to chapter "Accuracy".
Current output electronics: ±10 µA; ±100 ppm/°C (typically: ±30 ppm/°C)
Repeatability ±0.1%

76 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A TECHNICAL DATA 8

Operating conditions
Temperature
Process temperature Refer to technical data for the flow sensor.
Ambient temperature Depending on the version and combination of outputs.
It is a good idea to protect the converter from external heat sources such as
direct sunlight as higher temperatures reduce the life cycle of all electronic
components.
Ambient temperatures below -25°C / -13°F may affect the readability of the
display.
Storage temperature -40…+70°C / -40…+158°F
Pressure
Medium Refer to technical data for the flow sensor.
Ambient pressure Atmosphere
Chemical properties
Electrical conductivity All media except for water: ≥ 5 µS/cm
(also refer to the technical data for the flow sensor)
Water: ≥ 20 µS/cm
State of aggregation Conductive, liquid media
Solid content (volume) ≤ 10%
Gas content (volume) ≤ 3%
Flow rate For detailed information, refer to chapter "Flow tables".
Other conditions
Protection category acc. to IEC 529 / IP66/67 (acc. to NEMA 4/4X)
EN 60529

Installation conditions
Installation For detailed information, refer to chapter "Installation conditions".
Inlet / outlet sections Refer to technical data for the flow sensor.
Dimensions and weight For detailed information refer to chapter "Dimensions and weight".

Materials
Signal converter housing Aluminum with a polyester topcoat
Flow sensor For housing materials, process connections, liners, grounding electrodes and
gaskets, refer to technical data for the flow sensor.

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 77


8 TECHNICAL DATA IMT30A

Electrical connection
General Electrical connection is carried out in conformity with the VDE 0100 directive
"Regulations for electrical power installations with line voltages up to 1000 V" or
equivalent national specifications.
Power supply 100…230 VAC (-15% / +10%), 50/60 Hz;
240 VAC + 5% is included in the tolerance range.
24 VDC (-30% / +30%)
Power consumption AC: 15 VA
DC: 5.6 W
Signal cable Only necessary for remote versions.
DS 300 (type A)
Max. length: 600 m / 1968 ft (depending on electrical conductivity and flow
sensor version)
Cable entries Standard: M20 x 1.5 (8...12 mm)
Option: ½ NPT, PF ½

Outputs
General All outputs are electrically isolated from each other and from all other circuits.
All operating data and output values can be adjusted.
Description of abbreviations Uext = external voltage; RL = load + resistance;
Uo = terminal voltage; Inom = nominal current

78 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A TECHNICAL DATA 8

Current output
Output data Flow
Settings Without HART®
Q = 0%: 0…20 mA; Q = 100%: 10…21.5 mA
Error identification: 20…22 mA
With HART®
Q = 0%: 4…20 mA; Q = 100%: 10…21.5 mA
Error identification: 3…22 mA
Operating data Basic I/Os
Active Observe connection polarity.
Uint, nom = 20 VDC

I ≤ 22 mA

RL ≤ 750 Ω

HART® at terminals A
Passive Observe connection polarity.
Uext ≤ 32 VDC

I ≤ 22 mA

U0 ≤ 2 V at I = 22 mA

RL, max = (Uext - U0) / Imax

HART® at terminals A
HART®
Description HART® protocol via active and passive current output
HART® version: V5
Universal Common Practice HART® parameter: completely supported
Load ≥ 250 Ω at HART® test point;
Note maximum load for current output!
Multi-drop mode Yes, current output = 4 mA
Multi-drop address adjustable in operation menu 1…15

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 79


8 TECHNICAL DATA IMT30A

Pulse or frequency output


Output data Flow
Function Can be set as a pulse output or frequency output
Pulse rate/frequency 0.01...10000 pulses/s or Hz
Settings Pulses per volume or mass unit or max. frequency for 100% flow
Pulse width: adjustable as automatic, symmetric or fixed (0.05...500 ms)
Operating data Basic I/Os + Modbus
Active This output is intended to drive mechanical or electronic counters directly.
Uint, nom ≤ 20 V

RV = 1 kΩ

C = 1000 µF
High current mechanical counter
fmax ≤ 1 Hz
Low current mechanical counter
I ≤ 20 mA

RL ≤ 10 kΩ for f ≤ 1 kHz
RL ≤ 1 kΩ for f ≤ 10 kHz

closed:
U0 ≥ 12.5 V at I = 10 mA

open:
I ≤ 0.05 mA at Unom = 20 V
Passive Independent of connection polarity.
Uext ≤ 32 VDC
fmax in operating menu set to
fmax ≤ 100 Hz:

I ≤ 100 mA

open:
I ≤ 0.05 mA at Uext = 32 VDC

closed:
U0, max = 0.2 V at I ≤ 10 mA
U0, max = 2 V at I ≤ 100 mA
fmax in operating menu set to
100 Hz < fmax ≤ 10 kHz:

I ≤ 20 mA

open:
I ≤ 0.05 mA at Uext = 32 VDC

closed:
U0, max = 1.5 V at I ≤ 1 mA
U0, max = 2.5 V at I ≤ 10 mA
U0, max = 5.0 V at I ≤ 20 mA

80 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A TECHNICAL DATA 8

Low flow cut off


Function Switching point and hysteresis separately adjustable for each output, counter
and the display
Switching point Set in increments of 0.1%.
0…20% (current output, frequency output) or 0...±9.999 m/s (pulse output)
Hysteresis Set in increments of 0.1%.
0...5% (current output, frequency output) or 0...5 m/s (pulse output)
Time constant
Function The time constant corresponds to the elapsed time until 67% of the end value
has been reached according to a step function.
Settings Set in increments of 0.1 seconds.
0…100 seconds
Status output / limit switch
Function and settings Adjustable as automatic measuring range conversion, display of flow direction,
counter overflow, error, switching point or empty pipe detection
Valve control with activated dosing function
Status and/or control: ON or OFF
Operating data Basic I/Os + Modbus
Passive Independent of connection polarity.
Uext ≤ 32 VDC

I ≤ 100 mA

open:
I ≤ 0.05 mA at Uext = 32 VDC

closed:
U0 = 0.2 V at I ≤ 10 mA
U0 = 2 V at I ≤ 100 mA
Modbus
Description Modbus RTU, Master / Slave, RS485
Address range 1…247
Broadcast Supported with function code 16
Supported Baud rate 1200, 2400, 3600, 4800, 9600, 19200, 38400, 57600, 115200 Baud

Approvals and certificates


CE The device fulfils the statutory requirements of the EC directives. The
manufacturer certifies that these requirements have been met by applying the
CE marking.
Other standards and approvals
Shock and vibration resistance IEC 60068-2-3; EN 60068-2-6 and EN 60068-2-27; IEC 61298-3
Electromagnetic compatibility (EMC) 2004/108/EC in conjunction with EN 61326-1 (A1, A2)
European pressure equipment PED 97/23 (only for compact versions)
directive
NAMUR NE 21, NE 43, NE 53

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 81


8 TECHNICAL DATA IMT30A

8.3 Dimensions and weights


8.3.1 Housing

Wall version

Dimensions and weights in mm and kg


Dimensions [mm] Weight
[kg]
a b c d e f g h k
Version with & 157 40 80 120 248 111.7 260 28.4 51.3 1.9
without display

Dimensions and weights in inch and lb


Dimensions [inch] Weight
[lb]
a b c d e f g h k
Version with & 6.18 1.57 3.15 4.72 9.76 4.39 10.24 1.12 2.02 4.2
without display

82 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A TECHNICAL DATA 8

Compact version

Dimensions and weights in mm and kg


Dimensions [mm] Weight
[kg]
a b c d e f g
Version with & 157 40 80 148.2 101 260 95.5 1.8
without display

Dimensions and weights in inch and lb


Dimensions [inch] Weight
[lb]
a b c d e f g
Version with & 6.18 1.57 3.15 5.83 3.98 10.24 3.76 4.0
without display

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 83


8 TECHNICAL DATA IMT30A

8.3.2 Mounting plate, wall version

Dimensions in mm and inch


[mm] [inch]
a Ø6.5 Ø0.26
b 80 3.15
c 248 9.76

84 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A TECHNICAL DATA 8

8.4 Flow tables


Flow rate in m/s and m3/h

Q100 % in m3/h

v [m/s] 0.3 1 3 12

DN [mm] Min. flow Nominal flow Max. flow


2.5 0.005 0.02 0.05 0.21
4 0.01 0.05 0.14 0.54
6 0.03 0.10 0.31 1.22
10 0.08 0.28 0.85 3.39
15 0.19 0.64 1.91 7.63
20 0.34 1.13 3.39 13.57
25 0.53 1.77 5.30 21.21
32 0.87 2.90 8.69 34.74
40 1.36 4.52 13.57 54.29
50 2.12 7.07 21.21 84.82
65 3.58 11.95 35.84 143.35
80 5.43 18.10 54.29 217.15
100 8.48 28.27 84.82 339.29
125 13.25 44.18 132.54 530.15
150 19.09 63.62 190.85 763.40
200 33.93 113.10 339.30 1357.20
250 53.01 176.71 530.13 2120.52
300 76.34 254.47 763.41 3053.64
350 103.91 346.36 1039.08 4156.32
400 135.72 452.39 1357.17 5428.68
450 171.77 572.51 1717.65 6870.60
500 212.06 706.86 2120.58 8482.32
600 305.37 1017.90 3053.70 12214.80
700 415.62 1385.40 4156.20 16624.80
800 542.88 1809.60 5428.80 21715.20
900 687.06 2290.20 6870.60 27482.40
1000 848.22 2827.40 8482.20 33928.80
1200 1221.45 3421.20 12214.50 48858.00

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 85


8 TECHNICAL DATA IMT30A

Flow rate in ft/s and US gallons/min


Q100 % in US gallons/min

v [ft/s] 1 3.3 10 40

DN [inch] Min. flow Nominal flow Max. flow


1/10 0.02 0.09 0.23 0.93
1/8 0.06 0.22 0.60 2.39
1/4 0.13 0.44 1.34 5.38
3/8 0.37 1.23 3.73 14.94
1/2 0.84 2.82 8.40 33.61
3/4 1.49 4.98 14.94 59.76
1 2.33 7.79 23.34 93.36
1.25 3.82 12.77 38.24 152.97
1.5 5.98 19.90 59.75 239.02
2 9.34 31.13 93.37 373.47
2.5 15.78 52.61 159.79 631.16
3 23.90 79.69 239.02 956.09
4 37.35 124.47 373.46 1493.84
5 58.35 194.48 583.24 2334.17
6 84.03 279.97 840.29 3361.17
8 149.39 497.92 1493.29 5975.57
10 233.41 777.96 2334.09 9336.37
12 336.12 1120.29 3361.19 13444.77
14 457.59 1525.15 4574.93 18299.73
16 597.54 1991.60 5975.44 23901.76
18 756.26 2520.61 7562.58 30250.34
20 933.86 3112.56 9336.63 37346.53
24 1344.50 4481.22 13445.04 53780.15
28 1829.92 6099.12 18299.20 73196.79
32 2390.23 7966.64 23902.29 95609.15
36 3025.03 10082.42 30250.34 121001.37
40 3734.50 12447.09 37346.00 149384.01
48 5377.88 17924.47 53778.83 215115.30

86 www.fielddevices.foxboro.com MI 021-517 en - FEB 2016


IMT30A TECHNICAL DATA 8

8.5 Measuring accuracy


Reference conditions
• Medium: water
• Temperature: +20°C / +68°F
• Pressure: 1 bar / 14.5 psi
• Inlet section: ≥ 5 DN

X [m/s]: flow velocity


Y [%]: deviation from the actual measured value (mv)

DN [mm] DN [inch] Accuracy Curve


9500A 25…1200 1…48 0.5% of measured value 1
above 0.5 m/s 1
9600A 10…150 3/8…6
1 below 0.5 m/s, deviation of ±2.5 mm/s

MI 021-517 en - FEB 2016 www.fielddevices.foxboro.com 87


MI 021-517 en - FEB 2016

ISSUE DATES
FEB 2016

Invensys Systems, Inc. Copyright 2015-2016 Invensys Systems, Inc.


38 Neponset Avenue All rights reserved.
Foxboro, MA 02035
United States of America
http://www.fielddevices.foxboro.com Invensys and Foxboro are trademarks of
Invensys Limited, its subsidiaries, and
affiliates. All other trademarks are the
property of their respective owners.

Global Customer Support


Inside U.S.: 1-866-746-6477 Invensys is now part of Schneider Electric.
Outside U.S.: 1-508-549-2424
Website: http://support.ips.invensys.com FEB 2016

You might also like