1 Water Cooled Ewwp
1 Water Cooled Ewwp
1 Water Cooled Ewwp
technical data
Applied Systems
Water-cooled
EWWP014-065KAW1N
16Hp - 72Hp
EEDEN09-411
technical data
Applied Systems
Water-cooled
EWWP014-065KAW1N
16Hp - 72Hp
• Chillers • R-407C • EWWP-KAW1N
Cooling only
Heating only
Heat pump
TABLE OF CONTENTS
EWWP-KAW1N
1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2 Specification text . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5 Control systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Cooling/Heating capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Capacity correction factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
8 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
9 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
10 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Sound power spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
11 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
12 Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Water pressure drop curve evaporator/condenser . . . . . . . . . . . . . . . . . . 52
1 Features
s y SN 1 s Wd r A e eCK i l7 - l 0 P p4iW pWh- •EACR Daikin scroll compressor • Easy installation and maintenance
• Optimised for use with R-407C • Stainless steel plate heat exchanger
• Electronic DDC controller • Remote cooling or heating selection
• Low operating sound level • Water/water heat pump, with water reversibility
1 • Low energy consumption • Compatible with hydraulic module
1 • Extension possible up to 72hp • For EWWP014-065KAW1N following components are standard
included: main switch, pressure ports, flow switch, filter, shut-off
• Compact dimensions and low refrigerant volume
valves and air purge.
2 Specification text
Unit construction
1
Compact, modular design water-cooled chiller for indoor installation IP20 - manufactured according to the lSO 9001
2
quality standard. The EWWP-KAW1N range has been designed for both air conditioning and process cooling
applications. The use of state-of-the-art technologies and high quality materials ensures efficiency, reliability and an
extended service life.
Each DAlKIN chiller is subjected to many hours of test runs in the factory allowing for standard requirements.
Casing / Colour
Powder coated, galvanised steel plate. Fully factory assembled on a base frame. Colour ivory white ( ± RAL 7044) /
Munsell code 5Y7.5/1
Compressor
One R-407C optimised fully hermetically sealed DAlKIN scroll type compressor per refrigerant circuit. As a design
requirement, this compressor characteristically offers extremely smooth performance, efficiency and operational
reliability. Each compressor is mounted in the unit with vibration isolation and fitted with a compressor motor
overcurrent (Klixon).
Condenser
R-407C optimised counter flow plate heat exchanger made of stainless steel, plates brazed gastight with copper, for
water and glycol mixtures. The water pressure may not exceed the maximum permissible operating pressure of 10 bar!
Evaporator
R-407C optimised DX counter flow plate heat exchanger made of stainless steel, plates brazed gastight with copper, for
water and glycol mixtures. A special refrigerant distribution system has been incorporated into the plate duct for
optimal capacity of the complete heat transmission surface. As well as an additional increase in efficiency, this is also
responsible for stable control behaviour in the heat exchanger. The plate heat exchanger is heat-insulated to ensure it is
diffusion-proof to prevent any heat loss. Electronic contactor and water filter as standard. The water pressure may not
exceed the maximum permissible operating pressure of 10 bar!
Piping
Consisting of Cu pipe with all the necessary cooling fittings such as:
The plate heat exchanger is cased with galvanised steel.
2 Specification text
1
2 Switching and control device
In addition to the fully automated -Chiller digital controller (manufactured by CARREL), the control cabinet
manufactured in accordance with the valid EN directives (CE) contains all the required switching and control
components such as:
Main switch, load, auxiliary and control cut-outs, transformers, control fuses, relay and auxiliary relay, sensors, .-
Chiller digital controller.
The electronics have an automatic restart after power failure and provide the following digital inputs and outputs hard-
wired to terminals for incorporating the GLT:
The following functions are supported by the electronics, amongst other things:
- Allocation of the set point and the desired switching hysteresis
- Cold water return controller (cooling mode)
- Chilled water return controller (heating mode)
- Allocation of pump lead times / overrun times
- Allocation of service intervals
- Displaying the current operating parameter such as flow and return temperatures
- Recording operating hours (compressor / pump)
- Fault code query
- Password protection
As an option this chiller can be fitted with an interface for integrating it into a Building Management System (BMS),
which either supports
the MODbus / J-bus or BACnet protocol.
3 Specifications
3-1
Capacity
TECHNICAL SPECIFICATIONS
Cooling Nominal kW
EWWP014KAW1N
13.0
EWWP022KAW1N
21.5
EWWP028KAW1N
28.0
EWWP035KAW1N
32.5
EWWP045KAW1N
43.0
EWWP055KAW1N
56.0
3
(Eurovent)
Capacity Steps % 1 1 1 1 2 2
Nominal input
(Eurovent)
Cooling kW 3.61 5.79 7.48 8.75 11.80 15.50 1
Casing Material Polyester painted steel plate
3
Dimensions Unit Height mm 600 600 600 600 600 600
Width mm 600 600 600 600 600 600
Depth mm 600 600 600 600 1200 1200
Weight Unit kg 118 155 165 172 300 320
Water Heat Type Brased plate
Exchanger Minimum water volume in l 62 103 134 155 205 268
Evaporator the system
Water flow rate Min l/min 19 31 40 47 62 80
Nominal l/min 37 62 80 93 123 161
Max l/min 75 123 161 186 247 321
Insulation material Polyethylene foam
Model Quantity 1 1 1 1 1 1
Water Heat Type Brased plate
Exchanger Water flow rate Min l/min 24 39 51 59 79 102
Condenser Nominal l/min 48 78 102 118 157 205
Max l/min 95 157 203 237 314 410
Model Quantity 1 1 1 1 1 1
Compressor Type Hermetically sealed scroll compressor
Refrigerant oil type Daphne FVC68D
Refrigerant oil charge l 1.5 2.7 2.7 2.7 2.7 2.7
l 2.7 2.7
Model Quantity 1 1 1 1 2 2
Model JT140BF-YE JT212DA-YE JT300DA-YE JT335DA-YE JT212DA-YE JT300DA-YE
Speed rpm 2900 2900 2900 2900 2900 2900
Sound level Sound Power Cooling dBA 64 64 64 71 67 67
Refrigerant Refrigerant type R-407C
circuit Refrigerant charge kg 1.2 2 2.5 3.1 4.6 4.6
No of circuits 1 1 1 1 2 2
Refrigerant control Thermostatic expansion valve
Piping Evaporator water inlet/outlet FBSP 25 FBSP 25 FBSP 25 FBSP 25 FBSP 40 FBSP 40
connections Evaporator water drain field installation
Condensor water inlet/outlet FBSP 25 FBSP 25 FBSP 25 FBSP 25 FBSP 40 FBSP 40
field installation
Notes Capacity is for chilled water range Dt = 2~5°C
Power input is total input (kW) : compressor + control circuit + pumps
Water flow rate (WFR) = (860 x CC)/(60 x Dt) in (l/min) = ((860 x CC)/(60 x Dt)) x (1/60000) in m³/s (CC = cooling
capacity from table (kW)/ Dt = chilled water temperature rise within 2~5°C / WFR should always be within the limits).
No pumps are supplied with the unit, so the added power input for the pumps is calculated as (WFR (m³/s) x Dp (Pa))/
0.3 (as fixed by 6/C/003). This is for the cooled and cooling water (DP = pressure drop from pressure drop curves).
A filter strainer must be added in the water circuit of the evaporator and the condensor. A flow switch must be provided
at the evaporator side. Min. water volume system applicable at nominal conditions.
Nominal cooling capacities are based on the following conditions: Evaporator : 12°C/7°C ; condenser : 30°C/35°C
The sound power level is an absolute value indicating the ’’power’’ which a sound source generates.
The sound data is valid at nominal operation condition
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 1pW
Measured according to ISO9614
3 Specifications
3-1 TECHNICAL SPECIFICATIONS EWWP065KAW1N 90kw (32hp) 100kw (36hp) 110kw (40hp) 120kw (44hp) 130kw (48hp)
Capacity Cooling Nominal kW 65.0 86.0 99.0 112 121 130
(Eurovent)
Capacity Steps % 2 4 4 4 4 4
1 Nominal input
(Eurovent)
Cooling kW 17.60 23.6 27.3 31.0 33.1 35.2
3 Specifications
3-1
Notes
TECHNICAL SPECIFICATIONS EWWP065KAW1N 90kw (32hp) 100kw (36hp) 110kw (40hp)
Capacity is for chilled water range Dt = 2~5°C
120kw (44hp) 130kw (48hp)
3
Power input is total input (kW) : compressor + control circuit + pumps
Water flow rate (WFR) = (860 x CC)/(60 x Dt) in (l/min) = ((860 x CC)/(60 x Dt)) x (1/60000) in m³/s (CC = cooling
capacity from table (kW)/ Dt = chilled water temperature rise within 2~5°C / WFR should always be within the limits).
No pumps are supplied with the unit, so the added power input for the pumps is calculated as (WFR (m³/s) x Dp (Pa))/
1
0.3 (as fixed by 6/C/003). This is for the cooled and cooling water (DP = pressure drop from pressure drop curves). 3
A filter strainer must be added in the water circuit of the evaporator and the condensor. A flow switch must be provided
at the evaporator side. Min. water volume system applicable at nominal conditions.
Nominal cooling capacities are based on the following conditions: Evaporator : 12°C/7°C ; condenser : 30°C/35°C
The sound power level is an absolute value indicating the ’’power’’ which a sound source generates.
The sound data is valid at nominal operation condition
dBA = A-
weighted sound
power level (A- -
scale according
to IEC)
Reference acoustic pressure 0dB = 1pW
Measured according to ISO9614
3-1 TECHNICAL SPECIFICATIONS 145kw (52hp) 155kw (56hp) 165kw (60hp) 175kw (64hp) 185kw (68hp) 195kw (72hp)
Capacity Cooling Nominal kW 142 155 168 177 186 195
(Eurovent)
Capacity Steps % 6 6 6 6 6 6
Nominal input Cooling kW 39.1 42.8 46.5 48.6 50.7 52.8
(Eurovent)
Casing Colour Ivory white/Munsell code 5Y7.5/1
Material Polyester painted steel plate
Dimensions Unit Height mm 1800 1800 1800 1800 1800 1800
Width mm 600 600 600 600 600 600
Depth mm 1200 1200 1200 1200 1200 1200
Weight Unit kg 920 940 960 974 988 1002
Water Heat Type Brased plate
Exchanger Minimum water volume in l 205 205 268 268 268 311
Evaporator the system
Water flow rate Min l/min 204 222 241 254 267 280
Nominal l/min 407 444 482 507 533 559
Max l/min 814 889 963 1015 1066 1118
Insulation material Polyethylene foam
Model Quantity 2 2 2 2 2 2
Water Heat Type Brased plate
Exchanger Water flow rate Min l/min 260 283 307 323 339 355
Condenser
Nominal l/min 519 567 614 647 679 711
Max l/min 1038 1133 1229 1293 1357 1422
Model Quantity 2 2 2 2 2 2
Compressor Type Hermetically sealed scroll compressor
Refrigerant oil type Daphne FVC68D
Refrigerant oil charge l 2.7 2.7 2.7 2.7 2.7 2.7
l 2.7 2.7 2.7 2.7 2.7 2.7
l 2.7 2.7 2.7 2.7 2.7 2.7
l 2.7 2.7 2.7 2.7 2.7 2.7
l 2.7 2.7 2.7 2.7 2.7 2.7
l 2.7 2.7 2.7 2.7 2.7 2.7
Model Quantity 4 4 6 4 4 6
Model JT212DA-YE JT300DA-YE JT300DA-YE JT300DA-YE JT335DA-YE JT335DA-YE
Speed rpm 2900 2900 2900 2900 2900 2900
Quantity 2 2 2 2
Model JT300DA-YE JT212DA-YE - JT335DA-YE JT300DA-YE -
Speed rpm 2900 2900 2900 2900
Sound level Sound Power Cooling dBA 73 73 73 76 78 79
3 Specifications
3-1 TECHNICAL SPECIFICATIONS 145kw (52hp) 155kw (56hp) 165kw (60hp) 175kw (64hp) 185kw (68hp) 195kw (72hp)
Refrigerant Refrigerant type R-407C
circuit Refrigerant charge kg 13.8 13.8 13.8 14.8 15.8 16.8
No of circuits 6 6 6 6 6 6
1 Refrigerant control Thermostatic expansion valve
Piping Evaporator water inlet/outlet 3 x 2 x FBSP 38
3 connections Evaporator water drain field installation
Condensor water inlet/outlet 3 x 2 x FBSP 38
field installation
Notes Capacity is for chilled water range Dt = 2~5°C
Power input is total input (kW) : compressor + control circuit + pumps
Water flow rate (WFR) = (860 x CC)/(60 x Dt) in (l/min) = ((860 x CC)/(60 x Dt)) x (1/60000) in m³/s (CC = cooling
capacity from table (kW)/ Dt = chilled water temperature rise within 2~5°C / WFR should always be within the limits).
No pumps are supplied with the unit, so the added power input for the pumps is calculated as (WFR (m³/s) x Dp (Pa))/
0.3 (as fixed by 6/C/003). This is for the cooled and cooling water (DP = pressure drop from pressure drop curves).
A filter strainer must be added in the water circuit of the evaporator and the condensor. A flow switch must be provided
at the evaporator side. Min. water volume system applicable at nominal conditions.
Nominal cooling capacities are based on the following conditions: Evaporator : 12°C/7°C ; condenser : 30°C/35°C
The sound power level is an absolute value indicating the ’’power’’ which a sound source generates.
The sound data is valid at nominal operation condition
Reference acoustic pressure 0dB = 1pW
Measured according to ISO9614
3-2 ELECTRICAL SPECIFICATIONS EWWP065KAW1N 90kw (32hp) 100kw (36hp) 110kw (40hp) 120kw (44hp) 130kw (48hp)
Power Supply Name W1
Phase 3N~
Frequency Hz 50 50 50 50 50 50
Voltage V 400 400 400 400 400 400
Voltage Minimum % -10%
Tolerance Maximum % +10%
Unit Starting Current A 149 121 155 163 185 189
Zmax text 0.17 + j0.11
Nominal Running Current A 30 41.6 47 52.4 56.2 60
Cooling
Maximum Running Current A 40 56 64 72 76 80
Recommended fuses according to 3x50aM 3x63aM 3x63aM 3x80aM 3x80aM 3x80aM
IEC standard 269-2
3 Specifications
3-2 ELECTRICAL SPECIFICATIONS 145kw (52hp) 155kw (56hp) 165kw (60hp) 175kw (64hp) 185kw (68hp) 195kw (72hp)
Power Supply Name W1
Phase 3N~
Frequency Hz 50 50 50 50 50 50
Voltage V 400 400 400 400 400 400
Voltage Minimum % -10%
Tolerance Maximum % +10%
Unit Starting Current A 183 191 199 221 225 229
Nominal Running Current A 67.8 73.2 78.6 82.4 86.2 90
Cooling
Maximum Running Current A 92 100 108 112 116 120
Recommended fuses according to 3x100aM 3x100aM 3x125aM 3x125aM 3x125aM 3x125aM
IEC standard 269-2
Compressor Phase 3~
Voltage V 400 400 400 400 400 400
Starting current A 79 79 109 109 109 129
Nominal running current A 10.4 10.4 13.1 13.1 13.1 15
(RLA)
Maximum Running Current A 14 14 18 18 18 20
Starting Method Direct on line
Phase 3~ 3~ 3~ 3~
Voltage V 400 400 400 400
Starting current A 109 109 129 129
Nominal running current A 13.1 13.1 - 15 15 -
(RLA)
Maximum Running Current A 18 18 20 20
Starting Method Direct on line Direct on line Direct on line Direct on line
14
1
Number Option description Unit size 4
014WC 022WC 028WC 035WC 045WC 055WC 065WC Availability
012RC 020RC 026RC 030RC 040RC 055RC 065RC
Standard unit V V V V V V V
Available kit
4TW55259-1D
NOTES SYMBOLS
* = Option number std = standard on unit
- To install EKBMSMBA, EKBMSBNA and EKRUMC V Available
=> EKAC10B needs to be installed on the unit. Vx Available and a quantity of x is needed for this unit size
− Not available
Hatched area = preliminary data
4
Number Option description Unit size
045 055 065 Availability DT
W1 W1 W1
Standard unit V V V
Available kit
4TW53449-4B
NOTES SYMBOLS
* = Option number std = standard on unit
- To install EKBMSMBA, EKBMSBNA and EKRUMC V Available
=> EKAC10B needs to be installed on the unit. Vx Available and a quantity of x is needed for this unit
Supplementary available options: size
EWWP045-065KAW1M (x1) + ECB1MUW
EWWP045-065KAW1M (x2) + ECB2MUW − Not available
EWWP045-065KAW1M (x1) + ECB3MUW Hatched area = preliminary data
4
1
3
15
• Chillers • R-407C • EWWP-KAW1N
5 Control systems
1
5
Digital controller
comp PRG
mute
clear
SEL
x 100
i
a parameter modification and to return to normal LED, indicates that heating mode is active.
operation.
k Key, to de-activate the buzzer in the case of an alarm. b LED, indicates that cooling mode is active.
n
– Temperature readout tolerance: ±1°C.
Key, to enter the scroll list of direct parameters or to – Legibility of the numeric display may decrease in direct sunlight.
switch between a parameter’s code and its value.
5 Control systems
Note:
– Temperature readout tolerance: ±1°C.
– Legibility of the alphanumeric display may decrease in direct
sunlight.
6 Capacity tables
6-1 Cooling/Heating capacity tables
LWC 20 25 30 35 40 45 50 55
MODEL
LWE CC HC PI CC HC PI CC HC PI CC HC PI CC HC PI CC HC PI CC HC PI CC HC PI
1
6
4TW57192-1
SYMBOLS NOTES
CC : Cooling capacity (kW) 1 Cooling capacity is according to Eurovent rating standard 6/C/003-2003
and valid for chilled water range Dt = 3∼8°C.
HC : Heating capacity (kW) 2 Heating capacity is according to Eurovent rating standard 6/C/003-2003
PI : Power input (kW) and valid for chilled water range Dt = 3∼8°C.
LWE : Leaving Water Evaporator (°C) 3 Power input is total input according to Eurovent rating standard
6/C/003-2003.
LWC : Leaving Water Condenser (°C)
6 Capacity tables
6-1 Cooling/Heating capacity tables
LWC 20 25 30 35 40 45 50 55 3
MODEL
LWE CC HC PI CC HC PI CC HC PI CC HC PI CC HC PI CC HC PI CC HC PI CC HC PI
1
6
4TW57232-1
SYMBOLS NOTES
CC : Cooling capacity (kW) 1 Cooling capacity is according to Eurovent rating standard 6/C/003-2003
and valid for chilled water range Dt = 3∼8°C.
HC : Heating capacity (kW) 2 Heating capacity is according to Eurovent rating standard 6/C/003-2003
PI : Power input (kW) and valid for chilled water range Dt = 3∼8°C.
LWE : Leaving water evaporator (°C) 3 Power input is total input according to Eurovent rating standard
6/C/003-2003.
LWC : Leaving water condenser (°C)
6 Capacity tables
6-1 Cooling/Heating capacity tables
LWC 20 25 30 35 40 45 50 55
MODEL
LWE CC HC PI CC HC PI CC HC PI CC HC PI CC HC PI CC HC PI CC HC PI CC HC PI
1
6
4TW53472-2C
SYMBOLS NOTES
CC : Cooling capacity (kW) 1 Cooling capacity is according to Eurovent rating standard 6/C/003-2003
and valid for chilled water range Dt = 3∼8°C.
HC : Heating capacity (kW) 2 Heating capacity is according to Eurovent rating standard 6/C/003-2003
PI : Power input (kW) and valid for chilled water range Dt = 3∼8°C.
LWE : Leaving Water Evaporator (°C) 3 Power input is total input according to Eurovent rating standard
6/C/003-2003.
LWC : Leaving Water Condenser (°C)
6 Capacity tables
6-1 Cooling/Heating capacity tables
LWC 20.0 25.0 30.0 35.0 40.0 45.0 50.0 55.0 3
MODEL
LWE CC HC PI CC HC PI CC HC PI CC HC PI CC HC PI CC HC PI CC HC PI CC HC PI
1
6
4TW53472-3C
SYMBOLS
CC : Cooling capacity (kW)
HC : Heating capacity (kW)
PI : Power input (kW)
LWE : Leaving water evaporator (°C)
LWC : Leaving water condenser (°C)
6 Capacity tables
6-1 Cooling/Heating capacity tables
LWC 20 25 30 35 40 45 50 55
MODEL
LWE CC HC PI CC HC PI CC HC PI CC HC PI CC HC PI CC HC PI CC HC PI CC HC PI
1
6
4TW53472-4C
SYMBOLS
CC : Cooling capacity (kW)
HC : Heating capacity (kW)
PI : Power input (kW)
LWE : Leaving water evaporator (°C)
LWC : Leaving water condenser (°C)
6 Capacity tables
6-2 Capacity correction factor
CORRECTION FACTOR FOR GLYCOL
3
Required glycol concentration
Type Concentration (wt%)
Freezing point °C
0
0
10
-4
20
-9
30
-16
40
-23
1
Ethylene glycol
Minimum LWE °C 4 2 0 -5 -11 6
Freezing point °C 0 -3 -7 -13 -22
Propylene glycol
Minimum LWE °C 4 3 -2 -4 -10
% Glycol
Legend
Ethylene glycol
Propylene glycol
EWWP014-035KAW1N
1
7
View A-A
3TW55254-1B
EWWP045-065KAW1N
3
1
7
View A-A
3TW55304-1B
1 2
j
3
j
4
j
Evaporator
Condenser
Switchbox
7 5
j Chilled water in
6
j Chilled water out
7
j Condenser water out
8
j Condenser water in
9
j Evaporator entering water temperature sensor Scale: 1/18
10
j Freeze-up sensor
11
j Condenser entering water temperature sensor Required service space around the unit
12
j Digital display controller
13
j Power supply intake (J48)
Backside
3TW53474-2B
EWWP090-130KAW1N (32-48hp)
3
1
7
Scale 1/18
backside
3TW53474-3B
EWWP145-195KAW1N (52-72hp)
1
7
3TW53474-4B
1
7
4TW53479-2
EWWP045-065KAW1N
4TW53479-3
1
7
4TW53479-4
EWWP145-195KAW1N (52-72hp)
4TW53479-5
8 Piping diagram
EWWP014-035KAW1N
3
1
8
Air
purge Air purge
Shut off
Shut off valve Filter Evaporator Condenser valve
Water inlet
Water outlet
Shut off
Shut off valve Flow switch Filter valve
- - - - - - Field piping
M1C Compressor motor 1 O Check valve
R3T Outlet water evap. temp. sensor
L Flare connection
R5T Inlet water cond. temp. sensor
S1HP High pressure switch M Screw connection
S4LP Low pressure switch N Flange connection
R4T Freeze-up protection
S33T Discharge temperature controller Z Pinched pipe
P Spinned pipe
3TW55255-1B
8 Piping diagram
EWWP045-065KAW1N
1
8
Air
purge Air purge
Filter
Expansion valve
- - - - - - Field piping
M1-2C Compressor motor O Check valve
R4T Freeze-up protection
R5T Inlet water cond. temp. sensor L Flare connection
S1HP High pressure switch M Screw connection
S2HP High pressure switch
N Flange connection
S4LP Low pressure switch
S5LP Low pressure switch Z Pinched pipe
R3T Inlet water evap. temp. sensor
P Spinned pipe
Q1D Discharge temperature controller
Q2D Discharge temperature controller
3TW55305-1B
8 Piping diagram
EWWP045-065KAW1M 3
SYMBOLS
Condenser Evaporator
Water Water
Inlet Outlet
Water Water
Outlet Inlet
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
3TW53475-2
8 Piping diagram
EWWP090-130KAW1N (32-48hp)
1 Filter
Condenser Evaporator
Filter
Water inlet Water outlet
Filter
Condenser Evaporator
Filter
Water inlet Water outlet
O Check valve
3TW53475-3
8 Piping diagram
EWWP145-195KAW1N (52-72hp)
3
Water outlet 1
Water outlet
Water outlet
Water inlet
Water inlet
Water inlet
8
Evaporator
Evaporator
Evaporator
Filter
Filter
Filter
Filter
Filter
Filter
Condenser
Condenser
Condenser
Water inlet
Water outlet
Water inlet
Water outlet
Water inlet
Water outlet
O Check valve
M1C-M2C Compressor motor
L Flare connection
R4T Freeze-up protection
R5T Inlet water cond. temp. sensor M Screw connection
S1HP High pressure switch
N Flange connection
S2HP High pressure switch
S4LP Low pressure switch Z Pinched pipe
S5LP Low pressure switch P Spinned pipe
R3T Inlet water evap. temp. sensor
Q1D Discharge temperature controller
Q2D Discharge temperature controller
3TW53475-4
9 Wiring diagram
9-1 Wiring diagram
0 1 2 3 4 5 6 7 8 9 10 11
For WC 0
For
WC 014-035
RC012-030
1 For
For WC 0
9 WC 045-065
RC 040-065
To microchil er compact
Address cards
Remote user
interface
Only for
WC 045-065 / RC 040-0
Only for
NOTES
(1) Terminal 1
(2) Wire 2
9 Wiring diagram
9-1 Wiring diagram
12
014-035 / RC 012-030
13 14 15 16 17 18 19 20
3
C 045-065 / RC 040-065
1
9
A2P A1P
Digital inputs
0-065 Dl1 Reverse phase detection (L1-N)
Dl2 Reverse phase detection (N-L3) Digital inputs
Dl3 M1C ON detection X1 (lD1-GND): Flow switch
Dl4 M2C ON detection X1 (lD2-GND): Remote C/H selection
Only for Only for Dl5 Safety device detection X1 (lD3-GND): High pressure switch + discharge protector
RC Units RC Units Dl6 Pump ON detection + overcurrent
Dl7 -- X1 (lD4-GND): Low pressure switch
Only for WC 045-065 / RC 040-065 Dl8 -- X1 (lD5-GND): Remote On/Off
Dl9 --
Dl10 Reverse valve request
Digital outputs (Relays) Digital outputs (Relays)
RY1 Reversed phase protector X2 (C1/2-N01): Compressor M1C on
RY3 Pump / general operation X2 (C1/2-N02): Compressor M2C on
RY9 M1C Off (during defrost) X2 (C3/4-N03): Voltage free contact for pump
RY10 M2C Off (during defrost) X2 (C3/4-N04): Reversing valve
RY27 Reversing valve of water circuit X2 (C5-N05): Alarm voltage free contact
(13) Pump contact Others Analog inputs
HAP Light emitting diode (service monitor green) X1 (B1-GND): Evaporator inlet water t°
H1P,H2P Light emitting diode (service monitor red) X1 (B2-GND): Evaporator outlet water t°
X1 (B3-GND): Cond. inlet water t°
S1A Dipswitch (unit setting) Analog output
S2A Dipswitch (defr. & fan settting) X1 (Y-GND)
38
1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
9
9-1
A
B
Wiring diagram
C
Wiring diagram
(6) If compressor rotates reversely, it may be damaged. WC 16-20-24HP K5S Overcurrent relay M2C
WC 32-48HP K4S Overcurrent relay M1C
WC 52-72HP
K2M Compressor M2C contactor
K1M Compressor M1C contactor
3TW53476-5A
• Chillers • R-407C • EWWP-KAW1N
9 Wiring diagram
9-1 Wiring diagram
1
9
16
15
To microchiller compact
Address card
Power supply
controller
11
10
9
8
7
6
5
4
3
2
1
3TW53476-2C (1/2)
A
H
C
B
40
1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
9
9-1
A
B
Wiring diagram
C
400V Not standard included
Wiring diagram
Fuses + overcurrent 16HP 20HP 24HP Not poss. as option Poss. as option
Obligatory # ##
F1U,F2U,F3U 35gG 40gG 50gG
Not obligatory ∗ ∗∗
F5B 1AgG 1AgG 1AgG
F8U 315mAT 315mAT 315mAT
D
Operation
compressor M1C
Operation
compressor M2C
Alarm
(F1U,F2U,F3U = gL/gG)
E
• Chillers • R-407C • EWWP-KAW1N
NOTES
EWWP045-065KAW1M (16-24hp) - Wiring diagram control switch box
(1) d1 Terminal 1
(2) W Wire 2
X6A Interconnection connector main <> Control switchbox (16)
(3) F Field wiring, to be in accordance with the local X4A/X5A Interconnection connector main <> Control switchbox (2*4)
G electrical regulations Connector in terminal unit for digital inputs, analog inputs, analog outputs and
X1 for power supply controller(A1P)
(4) C Earth wiring A1P: Digital inputs X2 Connector for digital output (A1P)
X1 (ID1-GND): Flow switch On page 1 Y1R Reversing valve
(5) Option TR1 Transfo 230V -> 24V for supply of controllers
X1 (ID2-GND): Remote cooling/heating selection
X1 (ID3-GND): High pressure switch + discharge protector + S12S # Main isolator switch
(6) PCB-display overcurrent S11L # Contact that closes if the pump is working
X1 (ID4-GND): Low pressure switch S10L # Flowswitch
X1 (ID5-GND): Remote On/Off S9S ∗ Switch for remote start/stop
H (7) Outside switchbox S7S Switch for remote cooling / heating selection
R1P Reverse phase protector
A1P: Digital outputs (relays) PE Main earth terminal
(8) If compressor rotates reversely, it may be damaged. X2 (C1/2-NO1): Compressor M1C on M2C Compressor motor 2
X2 (C1/2-NO2): Compressor M2C on M1C Compressor motor 1
X2 (C3/4-NO3): Voltage free contact for pump K1P ∗ Pumpcontactor
X2 (C3/4-NO4): Voltage free contact for reversing valve H4P ∗ Indication lamp operation compressor
X2 (C5-NO5): Alarm voltage free contact H3P ∗ Indication lamp operation compressor
H1P ∗ Indication lamp alarm
F8U Surge proof fuse
A1P: Analog inputs
F5B Fuse for the control circuit
X1 (B1-GND): Evaporator inlet water t° F1U,F2U,F3U # Main fuses for the unit
X1 (B2-GND): Evaporator outlet water t° A1P PCB: terminal unit
X1 (B3-GND): Cond. inlet water t°
3TW53476-2C (2/2)
• Chillers • R-407C • EWWP-KAW1N
9 Wiring diagram
9-1 Wiring diagram
1
9
16
15
14
Main switchbox
13
Main switchbox B
12
11
10
Main switchbox
A
9
Main switchbox A
Main switchbox B
8
7
6
5
Main switchbox A
4
3
2
1
3TW53476-3D (1/3)
A
H
C
B
42
1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
9
9-1
A
C
Wiring diagram
Power supply
F
Main switchbox B
Main switchbox A
EWWP090-130KAW1N (32-48hp) - Wiring diagram control switch box
Changeable output
(i.e. reversing valve)
3TW53476-3D (2/3)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
9
9-1
A1P: Digital inputs A1P: Analog output
A J5 (ID1-IDC1): Module safety A active (Converted to digital outputs)
J5 (ID2-IDC1): Module safety B active J4 (VG0-Y1): −−
J5 (ID3-IDC1): −− J4 (VG0-Y2): −−
J5 (ID4-IDC1): Reverse phase protector J4 (VG0-Y3): −−
J5 (ID5-IDC1): Flowswitch J4 (VG0-Y4): Changeable digital output 1xx
J5 (ID6-IDC1): Changeable digital input 1x xx Reversing valve / 2nd evaporator pump / condenser pump /
J5 (ID7-IDC1): Changeable digital input 2x 100% capacity / free cooling / condenser pump / 100%
J5 (ID8-IDC1): Changeable digital input 3x capacity
B x dual setpoint/ Remote start/stop / remote cooling-heating /
capacity limitation 1-2-3-4
A1P: Analog inputs
J2 (GND-B1): Evaporator inlet t° measurement
A1P: Digital outputs (relays) J2 (GND-B2): Evaporator A outlet t° measurement
J12 (C1-NO1): Compressor 1 of module A on J2 (GND-B3): Condenser inlet t° measurement
Wiring diagram
electrical regulations TC04 Optocoupler (analog to digital signal), changeable output (reversing
Main switchbox A valve, 2nd evap. pump, comd. pump, 100% cap.)
(4) C Earth wiring
Ctrl-unit power supply S12S # Main isolator switch
(5) Option S11L # Contact that closes if the pump is working
F
S10L # Flowswitch
(6) PCB-display
Main switchbox B
S7S,S8S,S9S Changeable switch for remote function (dual setpoint, rem. start-
EWWP090-130KAW1N (32-48hp) - Wiring diagram control switch box
3TW53476-3D (3/3)
9
1
3
43
• Chillers • R-407C • EWWP-KAW1N
9 Wiring diagram
9-1 Wiring diagram
1
9
16
Main switchbox
15
Main switchbox C
14
13
Main switchbox C
12
11
Main switchbox
B
Main switchbox B
10
9
Main switchbox B
Main switchbox
A
8
Main switchbox A
7
6
5
Main switchbox A
4
3
2
1
3TW53476-4E (1/3)
A
H
C
B
9
A
9-1
C
Wiring diagram
Power supply
3TW53476-4E (2/3)
9
1
3
45
9
46
1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
9
A1P: Digital inputs A1P: Analog output 9-1
A J5 (ID1-IDC1): Module safety A active (Converted to digital outputs)
J5 (ID2-IDC1): Module safety B active J4 (VG0-Y1): LP bypass on module A
J5 (ID3-IDC1): Module safety C active J4 (VG0-Y2): LP bypass on module B
J5 (ID4-IDC1): Reverse phase protector J4 (VG0-Y3): LP bypass of module C
J5 (ID5-IDC1): Flowswitch J4 (VG0-Y4): Changeable digital output 1xx
J5 (ID6-IDC1): Changeable digital input 1x xx Reversing valve / 2nd evaporator pump / condenser pump /
J5 (ID7-IDC1): Changeable digital input 2x 100% capacity / free cooling / condenser pump / 100%
J5 (ID8-IDC1): Changeable digital input 3x capacity
B x dual setpoint/ Remote start/stop / remote cooling-heating /
capacity limitation 1-2-3-4
A1P: Analog inputs
J2 (GND-B1): Evaporator inlet t° measurement
A1P: Digital outputs (relays) J2 (GND-B2): Evaporator A outlet t° measurement
J12 (C1-NO1): Compressor 1 of module A on J2 (GND-B3): Condenser inlet t° measurement
Wiring diagram
(3) F Field wiring, to be in accordance with the local Ctrl-unit power supply
electrical regulations valve, 2nd evap. pump, comd. pump, 100% cap.)
(4) C Earth wiring TC01,TC02,TC03 Optocoupler (Analog to digital signal), LP bypass
S12S # Main isolator switch
(5) Option S11L # Contact that closes if the pump is working
F Main switchbox B
S10L # Flowswitch
(6) PCB-display
S7S,S8S,S9S Changeable switch for remote function (dual setpoint, rem. start-stop,
EWWP145-195KAW1N (52-72hp) - Wiring diagram control switch box
3TW53476-4E (3/3)
• Chillers • R-407C • EWWP-KAW1N
10 Sound data
10 - 1 Sound power spectrum
EWWP014-028KAW1N (5-10hp) EWWP035KAW1N (12hp) 3
Sound power level (dB)
Linear Linear
Octave band center frequency (Hz) Octave band center frequency (Hz)
4TW57197-1 4TW57197-2
NOTES NOTES
Option low noise = -3dBa Option low noise = -3dBa
Linear Linear
Octave band center frequency (Hz) Octave band center frequency (Hz)
4TW57197-3 4TW57197-4
NOTES NOTES
Option low noise = -3dBa Option low noise = -3dBa
10 Sound data
10 - 1 Sound power spectrum
EWWP090-110KAW1N (32-40hp) EWWP120KAW1N (44hp)
Sound power level (dB)
Linear Linear
Octave band center frequency (Hz) Octave band center frequency (Hz)
4TW57197-5 4TW57197-6
NOTES NOTES
Option low noise = -3dBa Option low noise = -3dBa
Linear Linear
Octave band center frequency (Hz) Octave band center frequency (Hz)
4TW57197-7 4TW57197-8
NOTES NOTES
Option low noise = -3dBa Option low noise = -3dBa
10 Sound data
10 - 1 Sound power spectrum
EWWP175KAW1N (64hp) EWWP185KAW1N (68hp) 3
Sound power level (dB)
Linear Linear
Octave band center frequency (Hz) Octave band center frequency (Hz)
4TW57197-9 4TW57197-10
NOTES NOTES
Option low noise = -3dBa Option low noise = -3dBa
EWWP195KAW1N (72hp)
Sound power level (dB)
Linear
Octave band center frequency (Hz)
4TW57197-11
NOTES
Option low noise = -3dBa
11 Operation range
EWWP014-035KAW1N
1
11
Glycol Water
4TW57193-1
11 Operation range
EWWP045-065KAW1N
3
90kW (32hp) - 195kW (72hp)
1
11
Glycol Water
4TW53473-1B
12 Hydraulic performance
12 - 1 Water pressure drop curve evaporator/condenser
EWWP014-035KAW1N
12
Pressure drop (mH2O)
4TW57199-1A
12 Hydraulic performance
12 - 1 Water pressure drop curve evaporator/condenser
EWWP045-065KAW1N
3
Pressure drop evaporator
1
12
Pressure drop (mH2O)
4TW57239-1
12 Hydraulic performance
12 - 1 Water pressure drop curve evaporator/condenser
EWWP090-130KAW1N (32-48hp)
12
Pressure drop (mH2O)
Warning: Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also
minimum and maximum allowed water flowrate in the technical specifications.
4TW53479-1A
12 Hydraulic performance
12 - 1 Water pressure drop curve evaporator/condenser
EWWP145-195KAW1N (52-72hp)
3
Pressure drop evaporator
1
12
Pressure drop (mH2O)
Warning: Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also
minimum and maximum allowed water flowrate in the technical specifications.
4TW53479-1A
Daikin’s unique position as a man- ISO14001 assures an effective environmental “The present publication is drawn up by way of information only and
ufacturer of air conditioning equip- management system in order to help protect does not constitute an offer binding upon Daikin Europe N.V.. Daikin
ment, compressors and refrige- human health and the environment from Europe N.V. has compiled the content of this publication to the best
rants has led to its close involve- potential impact of our activities, products and of its knowledge. No express or implied warranty is given for the
ment in environmental issues. For services and to assist in maintaining and completeness, accuracy, reliability or fitness for particular purpose of
several years Daikin has had the in- improving the quality of the environment. its content and the products and services presented therein. Specifi-
tention to become a leader in the cations are subject to change without prior notice. Daikin Europe N.V.
provision of products that have explicitly rejects any liability for any direct or indirect damage, In the
limited impact on the environ- broadest sense, arising from or related to the use and/or interpreta-
ment. This challenge demands the tion of this publication. All content is copyrighted by Daikin Europe
eco design and development of a Daikin Europe N.V. is approved by LRQA for its N.V..”
wide range of products and an en- Quality Management System in accordance
ergy management system, result- with the ISO9001 standard. ISO9001 pertains
ing in energy conservation and a to quality assurance regarding design,
reduction of waste. development, manufacturing as well as to
services related to the product.
www.daikin.eu
BTW: BE 0412 120 336
RPR Oostende EEDEN0 9 - 4 1 1