Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Filtro Desecante 023Z4824

Download as pdf or txt
Download as pdf or txt
You are on page 1of 21

Data Sheet

Hermetic filter drier


Type DML/DMLE and DCL/DCLE

For uniflow liquid line

All ELIMINATOR® driers have a solid core with


binding material held to an absolute minimum.

There are two types of ELIMINATOR® cores. Type


DML/DMLE driers have a core composition of
100% Molecular Sieve, while type DCL/DCLE
contain 80% Molecular Sieve with 20%
activated alumina.

ELIMINATOR® type DML/DMLE driers are


designed for applications requiring the highest
moisture capacity.

ELIMINATOR® type DML/DMLE driers are


designed for applications requiring high
moisture capacity and acid adsorption capacity.

Available with solder (cu-plated steel


connectors) and flare connections.

For other connections please contact your


Danfoss Sales Representative.

AI192386435941en-001404
Hermetic filter drier Type DML/DMLE and DCL/DCLE

Features

The Core type DML/DMLE


• 100% Molecular Sieve core
• High drying capacity minimizing the risk of acid formation (hydrolysis)

The Core type DCL/DCLE


• 80% Molecular Sieve with 20% activated alumina
• Perfect core blend for systems that operate at high condensing temperatures and require high drying capacity

The Shell
• DML and DCL are PED approved for PS 46 bar
• DMLE and DCLE are PED approved for PS 50 bar
• Available with solder (Cu-plated steel connectors) and flare connections
• Corrosion resistant powder-painted finish. Special coating for marine applications available upon request
• Allows installation with any orientation provided the arrow is in the flow direction
• Available in sizes 1.5 – 75 cubic inches

The Filter
• 25 μm (0.001 in.) filter provides high retention with minimal pressure drop
• Thermally stable up to 120 °C

© Danfoss | Climate Solutions | 2023.02 AI192386435941en-001404 | 2


Hermetic filter drier Type DML/DMLE and DCL/DCLE

Application

Intro-diagram
ELIMINATOR® Hermetic filter driers protect refrigeration and air-conditioning systems from moisture, acids, and solid
particles.

With these contaminants eliminated, systems are safer from harmful chemical reactions and from abrasive
impurities.

Figure 1: Application

R64-2107.10
Danfoss
AKS EKC
EVR

TCAE

SGN GBC
DML / DMLE / DCL / DCLE GBC

DML/DMLE Filter drier


Recommended for use with R23, R32, R134a, R290, R404A, R407C, R407f, R410A, R444B, R448A, R449A, R450A,
R452A, R600, R600a, R1234yf and R1234ze refrigerants. Will not deplete oil additives.

DCL/DCLE Filter drier


Recommended for use with R23, R32, R134a, R290, R404A, R407C, R407f, R410A, R444B, R448A, R449A, R450A,
R452A, R600, R600a, R1234yf and R1234ze refrigerants.

© Danfoss | Climate Solutions | 2023.02 AI192386435941en-001404 | 3


Hermetic filter drier Type DML/DMLE and DCL/DCLE

Product specification

Technical data
Table 1: Technical data
Flare connection Solder connection(cu-plated steel connectors) Solder connector(pure copper)

Table 2: Surface and volume DML / DCL


Filter drier volume (shell vol‐ Filter drier volume (net vol‐
Filter Solid core surface[cm2] Solid core volume[cm3]
ume)[l] ume)[l]
DML/DCL 1.5 46 16 0.05 0.034
DML/DCL 03 82 29 0.08 0.051
DML/DCL 05 95 35 0.12 0.085
DML/DCL 08 131 56 0.17 0.114
DML/DCL 16 220 134 0.36 0.226
DML/DCL 30 378 256 0.72 0.464
DML/DCL 41 510 350 0.97 0.62
DML/DCL 60 756 513 1.34 0.827
DML/DCL 75 1019 702 1.81 1.108

Table 3: Surface and volume DMLE / DCLE


Filter drier volume (shell vol‐ Filter drier volume (net vol‐
Filter Solid core surface[cm2] Solid core volume[cm3]
ume)[l] ume)[l]
DMLE / DCLE 1.5 46 16 0.05 0.034
DMLE / DCLE 03 82 29 0.08 0.051
DMLE / DCLE 05 95 35 0.12 0.085
DMLE / DCLE 08 131 56 0.17 0.114

Table 4: Acid capacity DCL


Filter Acid capacity(1) [g]
DCL 1.5 0.3
DCL 03 0.5
DCL 05 0.8
DCL 08 1.3
DCL 16 2.9
DCL 30 6.1
DCL 41 8.3
DCL 60 12.2
DCL 75 16.6

(1)
Adsorption capacity of oleic acid at 0.05 TAN (Total Acid Number).
Temperature range:
-40 – 70 °C
Maximum working pressure DML/DCL: 46 bar

Table 5: Acid capacity DML


Filter Acid capacity(1) [g]
DML 1.5 0.13
DML 03 0.2
DML 05 0.3
DML 08 0.5

© Danfoss | Climate Solutions | 2023.02 AI192386435941en-001404 | 4


Hermetic filter drier Type DML/DMLE and DCL/DCLE

(1)
Adsorption capacity of oleic acid at 0.05 TAN (Total Acid Number).
Temperature range:
-40 – 70 °C
Maximum working pressure DML/DCL: 46 bar

Table 6: Acid capacity DCLE


Filter Acid capacity(1) [g]
DCLE 1.5 0.3
DCLE 03 0.5
DCLE 05 0.8
DCLE 08 1.3

(1)
Adsorption capacity of oleic acid at 0.05 TAN (Total Acid Number).
Temperature range:
-40 – 70 °C
Maximum working pressure DMLE/DCLE: 50 bar

Table 7: Acid capacity DMLE


Filter Acid capacity(1) [g]
DMLE 1.5 0.13
DMLE 03 0.2
DMLE 05 0.3
DMLE 08 0.5

(1)
Adsorption capacity of oleic acid at 0.05 TAN (Total Acid Number).
Temperature range:
-40 – 70 °C
Maximum working pressure DMLE/DCLE: 50 bar

Conversions
[1 kg of refrigerant × (Initial PPM of water − Final PPM of water)]
Drops of water =
50

See ARI standard 710-86 for recommended initial and final PPM values for different refrigerants.

Identification
Table 8: Identification
Type Codes Description
Filter drier D Drier
C 80% Molecular Sieve / 20% activated alumina
Solid core
M 100% Molecular Sieve core
L Liquid line
Application
E Flammable refrigerants
3 3 in.3
5 5 in.3
8 8 in.3
16 16 in.3
Size (volume) 30 30 in.3
38 38 in.3
41 41 in.3
60 60 in.3
75 75 in.3

© Danfoss | Climate Solutions | 2023.02 AI192386435941en-001404 | 5


Hermetic filter drier Type DML/DMLE and DCL/DCLE

Type Codes Description


2 1⁄4 in. / 6 mm
2.5 5⁄16 in. / 8 mm
3 3⁄8 in. / 10 mm
Connection (filter connection in 1⁄8 of an inch incre- 4 1⁄2 in. / 12 mm
ments) 5 5⁄8 in. / 16 mm
6 3⁄4 in. / 18 (19) mm
7 7⁄8 in. / 22 mm
9 11⁄8 in. / 28 mm
(blank) Flare connection
Connection type
s Solder connection

Example for type codes


D C L 05 3 s

D Filter drier
C Solid core
L Application
05 Size (volume)
3 Connection (filter connection in 1⁄8 of an inch increments)
s Connection type

Selection
Type selection is made considering the application

Table 9: Selection
Refrigerant and oil types DCL DML
HFO Recommended Recommended
HC (1) Recommended Recommended
Refrigerant
HFC Recommended Recommended
HCFC Recommended Recommended
Mineral or AB Recommended Recommended
Oil POE or PAG, pure Recommended Recommended
POE or PAG, with additives Not recommended (2) Recommended

(1)
Only solder versions (cu-plated / pure copper) and connection sizes below 25 mm are approved for flammable refrigerants now.
(2)
DCL Hermetic filter driers contain activated alumina, which is a polar material used for acid adsorption. Many oil additives are also polar
substances and can be adsorbed by the activated alumina, rendering them useless, and reducing the drier’s acid capacity, though this is not
harmful to the system.

Filter drier selection based on capacity calculation


Drier selection based on capacities and refrigerants, please refer to Coolselector®2. Rated and extended capacities
are calculated with the Coolselector®2 calculation engine to ARI standards with the ASEREP equations based on
laboratory measurements of selected valves.

Download Coolselector®2 for free at coolselector.danfoss.com.

© Danfoss | Climate Solutions | 2023.02 AI192386435941en-001404 | 6


Hermetic filter drier Type DML/DMLE and DCL/DCLE

Design
Table 10: Design
DML / DMLE / DCL / DCLE 1.5 DML / DMLE / DCL / DCLE 1.5
1 2 3 4 5 7

1 2 3 4 5 7

23Z7012
Danfoss
23Z74.10
Danfoss

DML / DMLE / DCL / DCLE 03 DML / DMLE / DCL / DCLE 05

DML / DMLE / DCL / DCLE 08, DML / DCL 16 DML / DCL 30, DML / DCL 41
23Z22.11.13
Danfoss

DML / DCL 60, DML / DCL 75

1 Inlet 5 Perforated plate


2 Spring 6 Seal cap, flare connection
3 Solid core 7 Seal cap, solder connection
4 Polyester mat

The relatively large diameter of the hermetic filter drier means that the liquid flow velocity is suitably low and the
pressure drop minimal.

Powder formation is eliminated because the solid core grains are bonded and cannot move against each other.

© Danfoss | Climate Solutions | 2023.02 AI192386435941en-001404 | 7


Hermetic filter drier Type DML/DMLE and DCL/DCLE

Dimensions and weights


Flare connections
Figure 2: DML / DMLE / DCL / DCLE 032

Table 11: DML / DMLE / DCL / DCLE 032


Type A A1 A2 L D1 D2 Net weight
[mm] [mm] [mm] [mm] [mm] [mm] [Kg]
DML / DMLE / DCL / DCLE 032 66 33 33 110 46 43 0.17
DML / DMLE / DCL / DCLE 033 66 33 33 123 46 43 0.19

Figure 3: DML / DMLE / DCL / DCLE 053

Table 12: DML / DMLE / DCL / DCLE 053


Type A A1 A2 L D1 D2 Net weight
[mm] [mm] [mm] [mm] [mm] [mm] [Kg]
DML / DMLE / DCL / DCLE 052 75 24.5 50.5 119 58 54 0.24
DML / DMLE / DCL / DCLE 053 75 24.5 50.5 132 58 54 0.27

Figure 4: DML / DCL 083

© Danfoss | Climate Solutions | 2023.02 AI192386435941en-001404 | 8


Hermetic filter drier Type DML/DMLE and DCL/DCLE

Table 13: DML / DCL 083


Type A A1 A2 L D1 D2 Net weight
[mm] [mm] [mm] [mm] [mm] [mm] [Kg]
DCL / DML 082 101 50.5 50.5 145 58 54 0.31
DCL / DML 083 101 50.5 50.5 158 58 54 0.35
DCL / DML 084 101 50.5 50.5 166 58 54 0.37
DCL / DML 085 101 50.5 50.5 175 58 54 0.4
DCL / DML 162 110 55 55 154 80 76 0.65
DCL / DML 163 110 55 55 167 80 76 0.67
DCL / DML 164 110 55 55 175 80 76 0.74
DCL / DML 165 110 55 55 184 80 76 0.74
DCL / DML 166 110 55 55 182 80 76 0.84

Figure 5: DML / DCL 303

Table 14: DML / DCL 303


Type A L D1 D2 Net weight
[mm] [mm] [mm] [mm] [Kg]
DCL / DML 303 186 243 80 76 1.28
DCL / DML 304 186 251 80 76 1.32
DCL / DML 305 186 260 80 76 1.35
DCL / DML 306 186 258 80 76 1.45
DML 385 151 225 93 89 1.59
DCL / DML 413 187 244 93 89 1.79
DCL / DML 414 187 252 93 89 1.82
DCL / DML 415 187 261 93 89 1.87

Solder connection (cu-plated steel connectors)


Figure 6: DML /DCL 033s
23Z80.10
Danfoss

© Danfoss | Climate Solutions | 2023.02 AI192386435941en-001404 | 9


Hermetic filter drier Type DML/DMLE and DCL/DCLE

Table 15: DML /DCL 033s


Type A A1 A2 B L D1 D2 Net weight
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [Kg]
DML / DMLE / DCL / DCLE 032s 66 33 33 84 98 46 43 0.17
DCL / DML 032.5s 66 33 33 85 101 46 43 0.16
DCL / DML 033s 66 33 33 86 104 46 43 0.16
DML / DMLE / DCL / DCLE 034s 66 33 33 84 108 46 43 0.16

Figure 7: DML / DCL 053s

23Z81.10
Danfoss

Table 16: DML / DCL 053s


Type A A1 A2 B L D1 D2 Net weight
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [Kg]
DML / DMLE / DCL / DCLE 052s 75 24.5 50.5 93 107 58 54 0.24
DCL / DML 052.5s 75 24.5 50.5 94 110 58 54 0.24
DCL / DML 053s 75 24.5 50.5 95 113 58 54 0.23
DML / DMLE / DCL / DCLE 054s 75 24.5 50.5 97 117 58 54 0.24
DML / DMLE / DCL / DCLE 055s 75 24.5 50.5 101 125 58 54 0.26

Figure 8: DML / DCL 085s


23Z82.10
Danfoss

Table 17: DML / DCL 085s


Type A A1 A2 B L D1 D2 Net weight
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [Kg]
DCL / DML 082s 101 50.5 50.5 119 133 58 54 0.3
DCL / DML 082.5s 101 50.5 50.5 120 136 58 54 0.3
DCL / DML 083s 101 50.5 50.5 121 139 58 54 0.3
DCL / DML 084s 101 50.5 50.5 123 143 58 54 0.31
DCL / DML 085s 101 50.5 50.5 127 151 58 54 0.32
DCL / DML 162s 110 55 55 128 142 80 76 0.64
DCL / DML 162.5s 110 55 55 129 145 80 76 0.64

© Danfoss | Climate Solutions | 2023.02 AI192386435941en-001404 | 10


Hermetic filter drier Type DML/DMLE and DCL/DCLE

Type A A1 A2 B L D1 D2 Net weight


[mm] [mm] [mm] [mm] [mm] [mm] [mm] [Kg]
DCL / DML 163s 110 55 55 130 148 80 76 0.65
DCL / DML 164s 110 55 55 132 152 80 76 0.65
DCL / DML 165s 110 55 55 136 160 80 76 0.66
DCL / DML 166s 110 55 55 136 164 80 76 0.69
DCL / DML 167s 110 55 55 136 170 80 76 0.7

Figure 9: DML / DCL 305s

23Z83.10
Danfoss

Table 18: DML / DCL 305s


Type A B L D1 D2 Net weight
[mm] [mm] [mm] [mm] [mm] [Kg]
DCL / DML 303s 186 206 224 80 76 1.28
DCL / DML 304s 186 208 228 80 76 1.26
DCL / DML 305s 186 212 236 80 76 1.27
DCL / DML 306s 186 212 240 80 76 1.3
DCL / DML 307s 186 212 246 80 76 1.32
DCL / DML 309s 186 196 250 80 76 1.37
DCL / DML 414s 187 209 229 93 89 1.84
DCL / DML 415s 187 213 237 93 89 1.85
DCL / DML 417s 187 213 247 93 89 1.88
DCL / DML 419s 187 197 251 93 89 1.9
DCL / DML 604s 337 359 379 80 76 2.98
DCL / DML 606s 337 363 391 80 76 2.21
DCL / DML 607s 337 363 397 80 76 2.21
DCL / DML 609s 337 347 401 80 76 2.32
DCL / DML 757s 338 364 398 93 89 3.1
DCL / DML 759s 338 348 402 93 89 3.1

© Danfoss | Climate Solutions | 2023.02 AI192386435941en-001404 | 11


Hermetic filter drier Type DML/DMLE and DCL/DCLE

Solder connections
Figure 10: DML/DMLE 1.52s Figure 11: DCL 1.52x2/2s

23Z7018.10

23Z7011.10
L L

Danfoss
Danfos
B B

A A

A2 A2

D2

D2
D1

D1

Figure 12: DCL 1.52XL/2.8mm s


23Z7009

L
Danfoss

A2
D1

D2

A A2 B L D1 D2 Net weight
Type
[in.] [in.] [in.] [in.] [in.] [in.] [lbs]
DML/DMLE 1.52s 1.77 1.3 2.48 3 1.81 1.69 0.26
DML 1.52x2/2s 1.77 1.3 2.48 3 1.81 1.69 0.26
DCL 1.52XL/2.8mm s 1.77 1.3 – 4.17 1.81 1.69 0.26

Figure 13: DML / DCL 033s

© Danfoss | Climate Solutions | 2023.02 AI192386435941en-001404 | 12


Hermetic filter drier Type DML/DMLE and DCL/DCLE

Table 19: DML / DCL 033s


A A1 A2 B L D1 D2 Net weight
Type
[in.] [in.] [in.] [in.] [in.] [in.] [in.] [lbs]
DCL/DML 032s 2.6 1.3 1.3 3.23 3.86 1.81 1.69 0.33
DCL/DML 032.5s 2.6 1.3 1.3 3.31 4.02 1.81 1.69 0.33
DCL/DML 033s 2.6 1.3 1.3 3.35 4.09 1.81 1.69 0.33
DCL/DML 034s 2.6 1.3 1.3 3.43 4.25 1.81 1.69 0.33

Figure 14: DML / DCL 053s

Table 20: DML / DCL 053s


A A1 A2 B L D1 D2 Net weight
Type
[in.] [in.] [in.] [in.] [in.] [in.] [in.] [lbs]
DCL/DML 052s 2.95 0.96 1.99 3.58 4.21 2.28 2.13 0.52
DCL/DML 052.5s 2.95 0.96 1.99 3.66 4.37 2.28 2.13 0.52
DCL/DML 053s 2.95 0.96 1.99 3.7 4.45 2.28 2.13 0.52
DML 054s 2.95 0.96 1.99 3.78 4.61 2.28 2.13 0.52
DML 055s 2.95 0.96 1.99 3.9 4.84 2.28 2.13 0.53

Figure 15: DML / DCL 083s

Table 21: DML / DCL 083s


A A1 A2 B L D1 D2 Net weight
Type
[in.] [in.] [in.] [in.] [in.] [in.] [in.] [lbs]
DCL/DML 082s 3.98 1.99 1.99 4.61 5.24 2.28 2.13 0.74
DCL/DML 082.5s 3.98 1.99 1.99 4.69 5.39 2.28 2.13 0.67
DCL/DML 083s 3.98 1.99 1.99 4.72 5.47 2.28 2.13 0.67
DCL/DML 084s 3.98 1.99 1.99 4.8 5.63 2.28 2.13 0.67
DML 085s 3.98 1.99 1.99 4.92 5.87 2.28 2.13 0.77
DCL/DML 162s 4.33 2.17 2.17 4.96 5.59 3.15 2.99 1.36
DCL/DML 162.5s 4.33 2.17 2.17 5.04 5.75 3.15 2.99 1.39
DCL/DML 163s 4.33 2.17 2.17 5.08 5.83 3.15 2.99 1.39
DCL/DML 164s 4.33 2.17 2.17 5.16 5.98 3.15 2.99 1.43

© Danfoss | Climate Solutions | 2023.02 AI192386435941en-001404 | 13


Hermetic filter drier Type DML/DMLE and DCL/DCLE

A A1 A2 B L D1 D2 Net weight
Type
[in.] [in.] [in.] [in.] [in.] [in.] [in.] [lbs]
DCL/DML 165s 4.33 2.17 2.17 5.28 6.22 3.15 2.99 1.45
DCL/DML 166s 4.33 2.17 2.17 5.51 6.69 3.15 2.99 1.47
DCL/DML 167s 4.33 2.17 2.17 5.35 6.77 3.15 2.99 1.49

Figure 16: DML / DCL 304s

Table 22: DML / DCL 304s


A B L D1 D2 Net weight
Type
[in.] [in.] [in.] [in.] [in.] [lbs]
DCL/DML 303s 7.32 8.07 8.82 3.15 2.99 2.74
DCL/DML 304s 7.32 8.15 8.98 3.15 2.99 2.74
DCL/DML 305s 7.32 8.27 9.21 3.15 2.99 2.74
DCL/DML 306s 7.32 8.5 9.69 3.15 2.99 2.74
DCL/DML 307s 7.32 8.35 9.76 3.15 2.99 2.74
DCL/DML 309s 7.32 8.15 9.8 3.15 2.99 3.16
DCL/DML 414s 7.36 8.19 9.02 3.66 3.5 3.83
DCL/DML 415s 7.36 8.31 9.25 3.66 3.5 3.83
DCL/DML 417s 7.36 8.39 9.8 3.66 3.5 3.84
DCL/DML 419s 7.36 8.19 9.84 3.66 3.5 3.84
DCL/DML 604s 13.27 14.09 14.92 3.15 2.99 6.4
DCL/DML 607s 13.27 14.29 14.71 3.15 2.99 6.45
DCL/DML 609s 13.27 14.09 14.75 3.15 2.99 6.49
DCL/DML 757s 13.31 14.33 15.75 3.66 3.5 9.03
DCL/DML 759s 13.31 14.13 15.79 3.66 3.5 9.07

© Danfoss | Climate Solutions | 2023.02 AI192386435941en-001404 | 14


Hermetic filter drier Type DML/DMLE and DCL/DCLE

Ordering

Type DCL Flare


Figure 17: DCL Flare
23Z8403
Danfoss

Table 23: DCL Flare


Type Connection size Multi pack Industrial pack for OEM only
[in.] [mm] Code no. Qty. Code no. Qty.
DCL 032 1⁄4 6 023Z5000(1)(2) 32 – –
DCL 032 1⁄4 6 023Z5075 (2) 32 – –
DCL 033 3⁄8 10 023Z5001(1) (2) 32 – –
DCL 033 3⁄8 10 023Z5089(2) 32 – –
DCL 052 1⁄4 6 023Z5002(2) 24 023Z8002(2) 16
DCL 053 3⁄8 10 023Z5003(2) 24 023Z8003(2) 16
DCL 082 1⁄4 6 023Z5004(2) 24 023Z8004(2) 16
DCL 083 3⁄8 10 023Z5005(2) 24 023Z8005(2) 16
DCL 084 1⁄2 12 023Z5006(2) 24 – –
DCL 162 1⁄4 6 023Z5007(2) 12 023Z8007(2) 12
DCL 163 3⁄8 10 023Z5008(2) 12 023Z8008(2) 12
DCL 164 1⁄2 12 023Z5009(2) 12 023Z8009(2) 12
DCL 165 5⁄8 16 023Z5010(2) 12 023Z8010(2) 12
DCL 166 3⁄4 19 023Z5011(2) 12 – –
DCL 303 3⁄8 10 023Z0012 8 – –
DCL 304 1⁄2 12 023Z0013 8 023Z3013 8
DCL 305 5⁄8 16 023Z0014 8 023Z3014 8
DCL 306 3⁄4 19 023Z0156 8 – –
DCL 414 1⁄2 12 023Z0102 8 – –
DCL 415 5⁄8 16 023Z0103 8 – –

(1)
Wire mesh in filter drier outlet
(2)
India make is available with code 023ZXXXX91

Type DML Flare


Figure 18: DML Flare
23Z8403
Danfoss

Table 24: DML Flare


Type Connection size Multi pack Industrial pack for OEM only
[in.] [mm] Code no. Qty. Code no. Qty.
DML 032 1⁄4 6 023Z5035(1) (2) 32 023Z8035 (1) (2) 28
DML 033 3⁄8 10 023Z5036 (1) (2) 32 023Z8036(1) 28
DML 033 3⁄8 10 023Z5090(2) 32 – –
DML 052 1⁄4 6 023Z5037(2) 24 023Z8037(2) 16
DML 053 3⁄8 10 023Z5038(2) 24 023Z8038(2) 16
DML 082 1⁄4 6 023Z5039(2) 24 023Z8039(2) 16
DML 083 3⁄8 10 023Z5040(2) 24 023Z8040(2) 16
DML 084 1⁄2 12 023Z5041(2) 24 023Z8041(2) 16
DML 085 5⁄8 16 023Z5073(2) 24 – –
DML 162 1⁄4 6 023Z5042(2) 12 023Z8042(2) 12
DML 163 3⁄8 10 023Z5043(2) 12 023Z8043(2) 12
DML 164 1⁄2 12 023Z5044(2) 12 023Z8044(2) 12
DML 165 5⁄8 16 023Z5045(2) 12 023Z8045(2) 12
DML 166 3⁄4 19 023Z5046(2) 12 – –

© Danfoss | Climate Solutions | 2023.02 AI192386435941en-001404 | 15


Hermetic filter drier Type DML/DMLE and DCL/DCLE

Type Connection size Multi pack Industrial pack for OEM only
[in.] [mm] Code no. Qty. Code no. Qty.
DML 303 3⁄8 10 023Z0049 8 023Z3049 8
DML 304 1⁄2 12 023Z0050 8 023Z3050 8
DML 305 5⁄8 16 023Z0051 8 023Z3051 8
DML 306 3⁄4 19 023Z0193 8 023Z3193 8
DML 385 5⁄8 16 023Z0189 8 – –
DML 413 3⁄8 10 023Z0108 8 – –
DML 414 1⁄2 12 023Z0109 8 – –
DML 415 5⁄8 16 023Z0110 8 023Z3110 6
DML 416 3⁄4 19 023Z0195 8 023Z0210 6

(1)
Wire mesh in filter drier outlet
(2)
India make is available with code 023ZXXXX91

Type DCL Solder (cu-plated steel connectors)


Figure 19: DCL Solder
23Z8405
Danfoss

Table 25: DCL Solder


Type Conn. Size Multi pack Industrial pack for OEM Conn. Size Multi pack Industrial pack for OEM
only only
[in.] Code no. Qty. Code no. Qty. [mm] Code no. Qty. Code no. Qty.
DCL 032s 1⁄4 023Z4501(1) 32 023Z4801(1) 28 6 023Z4500(1) 32 023Z4800(1) 28
DCL 032.5s 5⁄16 023Z4502(1) 32 023Z4803(1) 28 8 – – – –
DCL 033s 3⁄8 023Z4504(1) 32 – – 10 023Z4503(1) 32 – –
DCL 052s 1⁄4 023Z4506(1) 24 023Z4805 2) 16 6 023Z4505(1) 24 023Z4804(1) 16
DCL 052s 5⁄16 023Z4507(1) 24 – – 10 – – – –
DCL 053s 3⁄8 023Z4509(1) 24 023Z4807(1) 16 10 023Z4508(1) 24 – –
DCL 082s 1⁄4 023Z4511(1) 24 – – 6 023Z4510(1) 24 – –
DCL 082s 5⁄16 023Z4512(1) 28 – – 6 – – – –
DCL 083s 3⁄8 023Z4514(1) 24 023Z4811(1) 16 10 023Z4513(1) 24 023Z4809(1) 16
DCL 084s 1⁄2 023Z4516 (1) 24 023Z4813 (1) 16 12 023Z4515 (1) 24 – –
DCL 162s 1⁄4 023Z4518(1) 12 – – 6 023Z4517(1) 12 – –
DCL 163s 3⁄8 023Z4521(1) 12 – – 10 023Z4519(1) 12 023Z4814 12
DCL 164s 1⁄2 023Z4523 (1)
12 023Z4815 (1)
12 12 023Z4522(1) 12 – –
DCL 165s 5⁄8 023Z4524(1) 12 023Z4816(1) 12 12 – – – –
DCL 166s 3⁄4 023Z4525(1) 12 – – – – – – –
DCL 167s 7⁄8 023Z4526(1) 12 – – – – – – –
DCL 303s 3⁄8 023Z4528 8 023Z4817 8 10 023Z4527 8 – –
DCL 304s 1⁄2 023Z4530 8 – – 12 023Z4529 8 – –
DCL 305s 5⁄8 023Z4531 8 023Z4819 8 16 – 8 – –
DCL 306s 3⁄4 023Z4533 8 – – 18 023Z4532 8 – –
DCL 307s 7⁄8 023Z4534 8 023Z4820 8 22 – 8 – –
DCL 309s 11⁄8 023Z4536 8 – – 28 023Z4535 8 – –
DCL 414s 1⁄2 023Z4538 8 – – 12 – 8 – –
DCL 415s 5⁄8 023Z4539 8 – – 16 – 8 – –
DCL 417s 7⁄8 023Z4540 8 – – 22 – 8 – –
DCL 419s 11⁄8 023Z4542 8 – – 28 023Z4541 8 – –
DCL 604s 1⁄2 023Z4544 12 – – 22 – – – –
DCL 607s 7⁄8 023Z4545 6 – – 22 – – – –
DCL 609s 11⁄8 – 12 – – 28 023Z4546 6 – –
DCL 757s 7⁄8 023Z4548 12 – – 22 – – – –
DCL 759s 11⁄8 023Z4550 12 – – 28 023Z4549 12 – –

(1)
India make is available with code 023ZXXXX91

© Danfoss | Climate Solutions | 2023.02 AI192386435941en-001404 | 16


Hermetic filter drier Type DML/DMLE and DCL/DCLE

Type DML Solder (cu-plated steel connectors)


Figure 20: DML Solder
23Z8405
Danfoss

Table 26: DML Solder


Type Conn. Size Multi pack Industrial pack for OEM Conn. Size Multi pack Industrial pack for OEM
only only
[in.] Code no. Qty. Code no. Qty. [mm] Code no. Qty. Code no. Qty.
DML 032s 1⁄4 023Z4552(1) 32 023Z4822(1) 28 6 023Z4551(1) 32 023Z4821(1) 28
DML 032.5s 5⁄16 023Z4553(1) 32 023Z4823(1) 28 8 – – – –
DML 033s 3⁄8 023Z4555(1) 32 023Z4825(1) 28 10 023Z4554(1) 32 023Z4824(1) 28
DML 034s 1⁄2 023Z4556(1) 32 – – 12 023Z4557 32 – –
DML 052s 1⁄4 023Z4559(1) 24 023Z4849(1) 16 6 023Z4558(1) 24 023Z4826(1) 16
DML 052.5s 5⁄16 023Z4560(1) 24 – – 6 – – – –
DML 053s 3⁄8 023Z4562(1) 24 023Z4828(1) 16 10 023Z4561 28 023Z4827(1) 16
DML 054s 1⁄2 023Z4564(1) 24 – – 12 023Z4563(1) 12 023Z4845(1) 16
DML 055s 5⁄8 023Z4565(1) 24 023Z4838(1) 16 16 – – – –
DML 082s 1⁄4 023Z4567(1) 24 023Z4847(1) 16 6 023Z4566(1) 24 023Z4866(1) 16
DML 083s 3⁄8 023Z4570(1) 24 023Z4835(1) 16 10 023Z4569 24 023Z4839(1) 16
DML 084s 1⁄2 023Z4572(1) 24 023Z4829(1) 16 12 023Z4571(1) 24 023Z4840(1) 16
DML 085s 5⁄8 023Z4573(1) 24 – – 16 – – – –
DML 162s 1⁄4 023Z4575(1) 12 – – 6 023Z4574(1) 12 – –
DML 163s 3⁄8 023Z4578(1) 12 023Z4836(1) 12 10 023Z4577(1) 12 023Z4842(1) 12
DML 164s 1⁄2 023Z4580(1) 12 023Z4830(1) 12 12 023Z4579(1) 12 023Z4843(1) 12
DML 165s 5⁄8 023Z4581(1) 12 023Z4831(1) 12 16 – – – –
DML 166s 3⁄4 023Z4582(1) 12 023Z4832(1) 12 19 – – – –
DML 167s 7⁄8 023Z4583(1) 12 – – 22 – – – –
DML 303s 3⁄8 023Z4585 8 – – 10 023Z4584 8 – –
DML 304s 1⁄2 023Z4587 8 023Z4837 8 12 023Z4586 8 023Z4844 8
DML 305s 5⁄8 0023Z4588 8 023Z4833 8 16 – – – –
DML 306s 3⁄4 023Z4589 8 023Z4848 8 19 – – – –
DML 307s 7⁄8 023Z4590 8 023Z4834 8 22 – – – –
DML 309s 11⁄8 023Z4592 8 – – 28 023Z4591 8 – –
DML 414s 1⁄2 023Z4594 8 – – 12 023Z4593 8 – –
DML 415s 5⁄8 023Z4595 8 – – 16 – – – –
DML 417s 7⁄8 023Z4596 8 023Z4896 6 22 – – – –
DML 419s 11⁄8 023Z4598 8 023Z4898 6 28 023Z4597 8 – –
DML 604s 1⁄2 023Z4600 12 – – 12 023Z4599 12 – –
DML 605s 1⁄2 – – – – 18 023Z4601 6 – –
DML 607s 7⁄8 023Z4602 6 023Z4902 – 22 – – – –
DML 609s 11⁄8 023Z4604 12 – – 28 023Z4603 12 – –
DML 757s 7⁄8 023Z4605 12 023Z4905 4 22 – – – –
DML 759s 11⁄8 023Z4607 12 023Z4907 4 28 023Z4606 12 – –

(1)
India make is available with code 023ZXXXX91

© Danfoss | Climate Solutions | 2023.02 AI192386435941en-001404 | 17


Hermetic filter drier Type DML/DMLE and DCL/DCLE

Type DCL Solder (copper) connectors)

Table 27: Type DCL Solder (copper)


Industrial pack for OEM on‐
Conn. Multi pack Conn. Multi pack
Type ly
[in.] Code no. Qty. Code no. Qty. [mm] Code no. Qty.
DCL 1.52XL/2.8mm s 1⁄4 – – 023Z8252 36 – – –
DML 1.52X2/2.8mm 1/4 – – 023Z8257 36 – – –
DCL 032s 1⁄4 023Z5013 (1) 32 023Z8013 1) 28 3 – –
DCL 032.5s 5⁄16 023Z5014 32 – – 8 – –
DCL 033s 3⁄8 023Z5015 32 – – 10 023Z5016 32
DCL 052s 1⁄4 023Z5018 24 – – 6 – –
DCL 053s 3⁄8 023Z5019 24 023Z8011 16 10 023Z5020 24
DCL 082s 1⁄4 023Z5022 24 – – 6 – –
DCL 083s 3⁄8 023Z5023 24 023Z8023 16 10 023Z5024 24
DCL 084s 1⁄2 023Z5026 24 023Z8026 16 – – –
DCL 162s 1⁄4 023Z5028 12 – – – – –
DCL 163s 3⁄8 023Z5029 12 – – 10 023Z5030 12
DCL 164s 1⁄2 023Z5032 12 023Z8032 12 12 023Z5031 12
DCL 165s 5⁄8 023Z5033 12 – – 12 – –
DCL 166s 3⁄4 023Z5070 12 – – – – –
DCL 167s 7⁄8 023Z5034 12 – – – – –
DCL 303s 3⁄8 023Z0030 8 – – 10 – –
DCL 304s 1⁄2 023Z0031 8 – – 12 – –
DCL 305s 5⁄8 023Z0032 8 023Z3032 8 16 – –
DCL 306s 3⁄4 023Z0033 8 – – – – –
DCL 307s 7⁄8 023Z0034 8 – – 22 – –
DCL 309s 11⁄8 023Z0035 8 – – 28 – –
DCL 414s 1⁄2 023Z0104 8 – – 12 – –
DCL 415s 5⁄8 023Z0105 8 – – 16 – –
DCL 417s 7⁄8 023Z0106 8 – – 22 – –
DCL 419s 11⁄8 023Z0107 8 – – 28 – –
DCL 607s 7⁄8 023Z0036 12 – – 22 – –
DCL 609s 11⁄8 023Z0037 12 – – 28 – –
DCL 757s 7⁄8 023Z0115 12 – – 22 – –
DCL 759s 11⁄8 023Z0116 12 – – 28 – –

(1)
Wire mesh in filter drier outlet

Type DML Solder (copper)


Table 28: Type DML Solder (copper)
Industrial pack for OEM Industrial pack for OEM
Conn. Multi pack Conn. Multi pack
Type only only
[in.] Code no. Qty. Code no. Qty. [mm] Code no. Qty. Code no. Qty.
DML 1.52s 1⁄4 – – 023Z8253 36 – – – – –
DML 1.52x2/2s 1⁄4 – – 023Z8250 36 – – – – –
DML 032s 1⁄4 023Z5048 1) 32 023Z8048 1) 28 6 – – 023Z8047 28
DML 032.5s 5⁄16 023Z5049 32 – – 8 – – – –

© Danfoss | Climate Solutions | 2023.02 AI192386435941en-001404 | 18


Hermetic filter drier Type DML/DMLE and DCL/DCLE

Industrial pack for OEM Industrial pack for OEM


Conn. Multi pack Conn. Multi pack
Type only only
[in.] Code no. Qty. Code no. Qty. [mm] Code no. Qty. Code no. Qty.
DML 033s 3⁄8 023Z5050 32 – – 10 023Z5051 32 – –
DML 034s 3⁄8 023Z5121 32 – – 12 – – – –
DML 052s 1⁄4 023Z5053 24 — — 6 – – – –
DML 053s 3⁄8 023Z5054 24 023Z8054 16 10 023Z5055 24 023Z8055 16
DML 054s 1⁄2 023Z5101 24 – – – – – – –
DML 082s 1⁄4 023Z5057 24 – – 6 – – – –
DML 082.5s 5⁄16 023Z5117 24 – – 8 – – – –
DML 083s 3⁄8 023Z5058 24 – – 10 023Z5059 24 – –
DML 084s 1⁄2 023Z5061 24 – – 12 023Z5060 24 – –
DML 085s 5⁄8 023Z5072 24 – – 16 – – – –
DML 162s 1⁄4 023Z5063 12 – – 6 – – – –
DML 163s 3⁄8 023Z5064 12 – – 10 023Z5065 12 – –
DML 164s 1⁄2 023Z5067 12 023Z8067 12 12 023Z5066 12 – –
DML 165s 5⁄8 023Z5068 12 023Z8068 12 16 – – – –
DML 166s 3⁄4 023Z5071 12 – – 19 – – – –
DML 167s 8-Jul 023Z5069 12 – – 22 – – – –
DML 303s 3⁄8 023Z0067 8 – – 10 – – – –
DML 304s 1⁄2 023Z0068 8 – – 12 – – – –
DML 305s 5⁄8 023Z0069 8 – – 16 – – – –
DML 306s 3⁄4 023Z0070 8 – – 19 – – – –
DML 307s 7⁄8 023Z0071 8 – – 22 – – – –
DML 309s 11⁄8 023Z0072 8 – – 28 – – – –
DML 414s 1⁄2 023Z0111 8 – – 12 – – – –
DML 415s 5⁄8 023Z0112 8 – – 16 – – – –
DML 416s 3⁄4 – – – – 19 – – – –
DML 417s 7⁄8 023Z0113 8 – – 22 – – – –
DML 419s 11⁄8 023Z0114 8 023Z3114 6 28 – – – –
DML 604s 1⁄2 – – – – 12 – – – –
DML 607s 7⁄8 023Z0073 12 – – 22 – – – –
DML 609s 11⁄8 023Z0074 12 – – 28 – – – –
DML 757s 7⁄8 023Z0117 12 – – 22 – – – –
DML 759s 11⁄8 023Z0118 12 – – 28 – – – –

Type DMLE / DCLE Copper / Cu-plated / Flare


Connector size Multi pack Industrial pack for OEM only
Type
[in] Code Qty Code Qty
DMLE 032S 1/4 - - 023Z8199 28
DMLE 053S 3/8 - - 023Z8200 16
DMLE 1.52S 1/4 - - 023Z8201 36
DMLE 052S 1/4 023Z8202 24 - -
DMLE 083 3/8 023Z8203 12 - -
DCLE 032S 1/4 023Z8317 12 - -
DCLE 053S 3/8 023Z8318 24 - -
DCLE 083 3/8 023Z8319 12 - -

© Danfoss | Climate Solutions | 2023.02 AI192386435941en-001404 | 19


Hermetic filter drier Type DML/DMLE and DCL/DCLE

Certificates, declarations, and approvals

The list contains all certificates, declarations, and approvals for this product type. Individual code number may have
some or all of these approvals, and certain local approvals may not appear on the list.

Some approvals may change over time. You can check the most current status at danfoss.com or contact your local
Danfoss representative if you have any questions.

Table 29: Certificates, declarations, and approvals


Document type Approval authority
Manufacturer declaration for PED/ROHS/ATEX Danfoss
UL certificate UL(1)
EAC document EAC
Manufacturer declaration for china ROHS Danfoss

(1)
UL approval currently only form DML / DCL

 WARNING:
Only solder versions (cu-plated / pure copper) and connection sizes below 25 mm are approved for for A3
refrigerants.
Only connection sizes below 25 mm are approved for A2L.
Filter sizes above 60 cu.in shall not be used with A3 refrigerants.

© Danfoss | Climate Solutions | 2023.02 AI192386435941en-001404 | 20


Online support

Danfoss offers a wide range of support along with our products, including digital product information, software,
mobile apps, and expert guidance. See the possibilities below.

The Danfoss Product Store


The Danfoss Product Store is your one-stop shop for everything product related—no matter where
you are in the world or what area of the cooling industry you work in. Get quick access to essential
information like product specs, code numbers, technical documentation, certifications, accessories,
and more.
Start browsing at store.danfoss.com.

Find technical documentation


Find the technical documentation you need to get your project up and running. Get direct access to
our official collection of data sheets, certificates and declarations, manuals and guides, 3D models
and drawings, case stories, brochures, and much more.

Start searching now at www.danfoss.com/en/service-and-support/documentation.

Danfoss Learning
Danfoss Learning is a free online learning platform. It features courses and materials specifically
designed to help engineers, installers, service technicians, and wholesalers better understand the
products, applications, industry topics, and trends that will help you do your job better.

Create your Danfoss Learning account for free at www.danfoss.com/en/service-and-support/learning.

Get local information and support


Local Danfoss websites are the main sources for help and information about our company and
products. Find product availability, get the latest regional news, or connect with a nearby expert—all
in your own language.

Find your local Danfoss website here: www.danfoss.com/en/choose-region.

Coolselector®2 - find the best components for you HVAC/R system


Coolselector®2 makes it easy for engineers, consultants, and designers to find and order the best
components for refrigeration and air conditioning systems. Run calculations based on your operating
conditions and then choose the best setup for your system design.

Download Coolselector®2 for free at coolselector.danfoss.com.

© Danfoss | Climate Solutions | 2023.02 AI192386435941en-001404 | 21

You might also like