T.L. = 10.32 KVA T.L. = 4.19 KVA T.L. = 4.19 KVA T.L. = 3.61 KVA T.L. = 3.

9 KVA T.L. = 3.61 KVA T.L. = 3.61 KVA T.L. = 3.61 KVA T.L. = 3.61 KVA T.L. = 10.17 KVA T.L. = 2.92 KVA T.L. = 2.92 KVA T.L. = 2.92 KVA T.L. = 3.49 KVA T.L. = 3.49 KVA
D.L. = 8.26KVA D.L. = 3.35KVA D.L. = 3.35KVA D.L. = 2.89 KVA D.L. = 2.89 KVA D.L. = 2.89 KVA D.L. = 2.89 KVA D.L. = 8.13 KVA D.L. = 2.33 KVA D.L. = 2.33 KVA D.L. = 2.33 KVA D.L. = 2.79 KVA D.L. = 2.79 KVA
IN OFF-201 IN OFF-202 IN OFF-203 IN OFF-204 IN OFF-205 IN OFF-206 IN OFF-207 IN OFF-208 IN OFF-209 IN OFF-210 IN OFF-211 IN OFF-212 IN OFF-213
AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR

40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO.

2
4Cx16mm CU/PVC/PVC
2
+ 1Cx16mm CU/PVC/ECC SPARE

Note:-
1- * WIRED AS SINGLE PHASE.
FOR OFF-201 FOR OFF-202 FOR OFF-203 FOR OFF-204 FOR OFF-205 FOR OFF-206 FOR OFF-207 FOR OFF-208 FOR OFF-209 FOR OFF-210 FOR OFF-211 FOR OFF-212 FOR OFF-213 2- THE CONTRACTOR SHALL VERIFY THE FINAL LOADS IN COORDINATION WITH OTHER
HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0
TRADES. ACCORDINGLY FINAL SIZES OF CABLES AND CIRCUIT BREAKERS SHALL
HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0
BE ADJUSTED.
3- ALL CIRCUIT BREAKER RATINGS SHOWN ON DRAWING ARE PRESENTING THE THERMAL
TRIP SETTING AND FRAME SIZE. CIRCUIT BREAKERS RATED 100A AND ABOVE SHALL BE
EQUIPPED WITH ADJUSTABLE TRIP SETTING.

4- THE CONTRACTOR SHALL SUBMIT THE FOLLOWING CALCULATIONS AND STUDIES


FOR APPROVAL :
- LOAD SCHEDULES FOR ALL DISTRIBUTION BOARDS FOR RETAILS AND
AND SERVICES (IF ANY CHANGES)
- CABLE SIZING AND VOLTAGE DROP CALCULATIONS (IF ANY CHANGES)
- SHORT CIRCUIT CALCULATIONS AT EACH BUS (IF ANY CHANGES)
40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP - DISCRIMINATION STUDY & CIRCUIT BREAKERS SETTING VALUES
OBTAINED FROM THE MANUFACTURER.
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA

100A TP
MCCB
18 KA

2 2

T.L. = 3.49 KVA T.L. = 3.49 KVA T.L. = 4.38 KVA T.L. = 5.54 KVA T.L. = 4.01 KVA T.L. = 4.01 KVA T.L. = 4.01 KVA T.L. = 4.01 KVA T.L. = 4.01 KVA T.L. = 4.01 KVA T.L. = 4.01 KVA T.L. = 6.1 KVA T.L. = 4.82 KVA
D.L. = 2.79 KVA D.L. = 2.79 KVA D.L. = 3.5 KVA D.L. = 4.43 KVA D.L. = 3.21 KVA D.L. = 3.21 KVA D.L. = 3.21 KVA D.L. = 3.21 KVA D.L. = 3.21 KVA D.L. = 3.21 KVA D.L. = 3.21 KVA D.L. = 4.88 KVA D.L. = 3.86 KVA
IN OFF-214 IN OFF-215 IN OFF-216 IN OFF-217 IN OFF-218 IN OFF-219 IN OFF-220 IN OFF-221 IN OFF-222 IN OFF-223 IN OFF-224 IN OFF-225 IN OFF-226
AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR

40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO.

2
4Cx16mm CU/PVC/PVC
2
+ 1Cx16mm CU/PVC/ECC SPARE

FOR OFF-214 FOR OFF-215 FOR OFF-216 FOR OFF-217 FOR OFF-218 FOR OFF-219 FOR OFF-220 FOR OFF-221 FOR OFF-222 FOR OFF-223 FOR OFF-224 FOR OFF-225 FOR OFF-226
HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0
HWK 0000.0

40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA

100A TP
MCCB
18 KA
SMDB-2ND-OFF1 SMDB-2ND-OFF2 SMDB-2ND-OFF3
IN ELEC. RM IN ELEC. RM IN ELEC. RM
AT SECOND FL AT SECOND FL AT SECOND FL
2 2
LIGHTING, S.POWER LIGHTING, S.POWER LIGHTING, S.POWER

2 SPARE

2
T.L. = 3.58 KVA
D.L. = 2.86 KVA
T.L. = 3.58 KVA
D.L. = 2.86 KVA
T.L. = 3.58 KVA
D.L. = 2.86 KVA
T.L. = 3.58 KVA
D.L. = 2.86 KVA
T.L. = 3.58 KVA
D.L. = 2.86 KVA
T.L. = 3.58 KVA
D.L. = 2.86 KVA
T.L. = 3.58 KVA
D.L. = 2.86 KVA
T.L. = 3.00 KVA
D.L. = 2.4 KVA
T.L. = 3.01 KVA
D.L. = 2.40 KVA
T.L. = 3.00 KVA
D.L. = 2.40 KVA
T.L. = 3.01 KVA
D.L. = 2.40 KVA
T.L. = 2.96 KVA
D.L. = 2.37 KVA
For Tender
IN OFF-227 IN OFF-228 IN OFF-229 IN OFF-230 IN OFF-231 IN OFF-232 IN OFF-233 IN OFF-234 IN OFF-235 IN OFF-236 IN OFF-237 IN OFF-238
AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR AT SECOND FLOOR

40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO.

100A TP 100A TP 80A TP 100A TP So a 2 O ICE BUILDING


MCCB MCCB MCCB MCCB
25 KA 25 KA 25 KA 25 KA 24B. -
2
4Cx16mm CU/PVC/PVC
2
+ 1Cx16mm CU/PVC/ECC SPARE SPACE

250A TP
FOR OFF-227 FOR OFF-228 FOR OFF-233
MCCB MOBIL :01024440717
FOR OFF-229 FOR OFF-230 FOR OFF-231 FOR OFF-232 FOR OFF-234 FOR OFF-235 FOR OFF-236 FOR OFF-237 FOR OFF-238 E-MAIL : m.amer@mod-eg.com
HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0
25 KA WEB SITE : WWW.mod-eg.com
26 JULY CORRIDOR
AVENUE MALL, SHEIKH ZAYED, GIZA, EGYPT

40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP
MCCB 2 2
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA

80A TP
MCCB
18 KA

2 2

---- ---- N.T.S @ A1