Rosemount 644H and 644R Smart Temperature Transmitters: Quick Installation Guide
Rosemount 644H and 644R Smart Temperature Transmitters: Quick Installation Guide
Rosemount 644H and 644R Smart Temperature Transmitters: Quick Installation Guide
Start
End
www.rosemount.com
¢00825-0100-4728[¤
4728 Rev BB.fm Page 2 Thursday, June 3, 2010 11:50 AM
© 2010 Rosemount Inc. All rights reserved. All marks property of owner. Rosemount and the Rosemount logotype are
registered trademarks of Rosemount Inc.
IMPORTANT NOTICE
This installation guide provides basic guidelines for the Rosemount 644. It does not
provide instructions for detailed configuration, diagnostics, maintenance, service,
troubleshooting, or installation. Refer to the 644 Reference Manual (document number
00809-0100-4728) for more instruction. The manual and this QIG are also available
electronically on www.rosemount.com.
WARNING
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with the
appropriate local, national, and international standards, codes, and practices. Please
review the Product Certifications for any restrictions associated with a safe installation. In
an Explosion-Proof/Flame-Proof installation, do not remove the transmitter covers when
power is applied to the unit.
Process leaks may cause harm or result in death
• Install and tighten thermowells or sensors before applying pressure.
• Do not remove the thermowell while in operation.
Electrical shock can result in death or serious injury
• Avoid contact with the leads and terminals. High voltage that may be present on leads
can cause electrical shock.
2
4728 Rev BB.fm Page 3 Thursday, June 3, 2010 11:50 AM
Field Communicator
AMS Power Supply
Field Communicator
AMS
Power Supply
3
4728 Rev BB.fm Page 4 Thursday, June 3, 2010 11:50 AM
STEP 1 CONTINUED...
Verify Transmitter Configuration
From the Home Screen, enter the HART Fast Keys listed below to verify if the transmitter is
configured correctly. This table contains the minimum functions required for configuration.
Refer to the 644 Reference Manual (document number 00809-0100-4728) for a complete
list.
Communicator Functions HART Fast Keys
LRV (Lower Range Value) 1, 1, 6
Sensor 1 Setup 1, 3, 2, 1, 2
Sensor Type 1, 3, 2, 1, 1
URV (Upper Range Value) 1, 1, 7
Variable Mapping 1, 3, 1
Verify Callendar Van-Dusen Constants (f applicable) 1, 3, 2, 1, 3
4
4728 Rev BB.fm Page 5 Thursday, June 3, 2010 11:50 AM
B
A
C
E F
A = 644H Transmitter D = Transmitter Mounting Screws
B = Connection Head E = Integral Mount Sensor with Flying Leads
C = Thermowell F = Extension
5
4728 Rev BB.fm Page 6 Thursday, June 3, 2010 11:50 AM
STEP 3 CONTINUED...
Typical Universal Head Installation
Head Mount Transmitter with Threaded Sensor
1. Attach the thermowell to the pipe or process container wall. Install and tighten
thermowells before applying process pressure.
2. Attach necessary extension nipples and adapters to the thermowell. Seal the nipple and
adapter threads with silicone tape.
3. Screw the sensor into the thermowell. Install drain seals if required for severe
environments or to satisfy code requirements.
4. Verify the transmitter failure mode switch.
5. Pull the sensor wiring leads through the universal head and transmitter. Mount the
transmitter in the universal head by threading the transmitter mounting screws into the
universal head mounting holes.
6. Mount the transmitter-sensor assembly into the thermowell. Seal adapter threads with
silicone tape.
7. Install conduit for field wiring to the conduit entry of the universal head. Seal conduit
threads with silicone tape.
8. Pull the field wiring leads through the conduit into the universal head. Attach the sensor
and power leads to the transmitter. Avoid contact with other terminals.
9. Install and tighten the universal head cover. Enclosure covers must be fully engaged to
meet explosion-proof requirements.
A B D
E
A = Threaded Thermowell D = Universal Head (transmitter inside)
B = Threaded Style Sensor E = Conduit Entry
C = Standard Extension
6
4728 Rev BB.fm Page 7 Thursday, June 3, 2010 11:50 AM
STEP 3 CONTINUED...
Rail Mount Transmitter and Sensor
1. Attach the transmitter to a suitable rail or panel.
2. Attach the thermowell to the pipe or process container wall. Install and tighten the
thermowell, according to plant standards, before applying pressure.
3. Attach the sensor to the connection head and mount the entire assembly to the
thermowell.
4. Attach and connect sufficient lengths of sensor lead wire from the connection head to the
sensor terminal block.
5. Tighten the connection head cover. Enclosure covers must be fully engaged to meet
explosion-proof requirements.
6. Run sensor lead wires from the sensor assembly to the transmitter.
7. Verify the transmitter failure mode switch.
8. Attach the sensor wires to the transmitter (see Step 4: Connect the Wiring for more
information).
C
A A = Rail Mount Transmitter
B = Sensor Leads with Cable Glands
B
C = Integral Mount Sensor with Terminal Block
D D = Connection Head
B E = Standard Extension
F = Threaded Thermowell
7
4728 Rev BB.fm Page 8 Thursday, June 3, 2010 11:50 AM
STEP 3 CONTINUED...
Rail Mount Transmitter with Threaded Sensor
1. Attach the transmitter to a suitable rail or panel.
2. Attach the thermowell to the pipe or process container wall. Install and tighten the
thermowell before applying pressure.
3. Attach necessary extension nipples and adapters. Seal the nipple and adapter threads
with silicone tape.
4. Screw the sensor into the thermowell. Install drain seals if required for severe
environments or to satisfy code requirements.
5. Screw the connection head to the sensor.
6. Attach the sensor lead wires to the connection head terminals.
7. Attach additional sensor lead wires from the connection head to the transmitter.
8. Attach and tighten the connection head cover. Enclosure covers must be fully engaged
to meet explosion-proof requirements.
9. Set the transmitter failure mode switch
10. Attach the sensor wires to the transmitter (see Step 4: Connect the Wiring for more
information).
A B C
D E
8
4728 Rev BB.fm Page 9 Thursday, June 3, 2010 11:50 AM
* The transmitters must be configured for at least a 3-wire RTD in order to recognize an RTD with a
compensation loop.
** Rosemount Inc. provides 4-wire sensors for all single element RTDs. Use these RTDs in 3-wire
configurations by leaving the unneeded leads disconnected and insulated with electrical tape.
9
4728 Rev BB.fm Page 10 Thursday, June 3, 2010 11:50 AM
STEP 4 CONTINUED...
Ground the Transmitter
Ungrounded Thermocouple, mV, and RTD/Ohm Inputs
Each process installation has different requirements for grounding. Use the grounding
options recommended by the facility for the specific sensor type, or begin with grounding
Option 1 (the most common).
Option 1:
1. Connect sensor wiring shield to the transmitter housing.
2. Ensure the sensor shield is electrically isolated from surrounding fixtures that may be
grounded.
3. Ground signal wiring shield at the power supply end.
Transmitter
4–20 mA loop
Sensor Wires
10
4728 Rev BB.fm Page 11 Thursday, June 3, 2010 11:50 AM
STEP 4 CONTINUED...
Option 3:
1. Ground sensor wiring shield at the sensor, if possible.
2. Insure that the sensor wiring and signal wiring shields are electrically isolated from the
transmitter housing.
3. Do not connect the signal wiring shield to the sensor wiring shield.
4. Ground signal wiring shield at the power supply end.
Transmitter
Sensor Wires 4–20 mA loop
11
4728 Rev BB.fm Page 12 Thursday, June 3, 2010 11:50 AM
PRODUCT CERTIFICATIONS
Approved Manufacturing Locations
Emerson Process Management Rosemount Division. – Chanhassen, Minnesota, USA
Rosemount Temperature GmbH – Germany
Emerson Process Management Asia Pacific – Singapore
• 0.5 kV line–line
Surge None
• 1 kV line–ground (I.O. tool)
Conducted • 150 kHz to 80 MHz at 10 V < 0.5%
CE Mark
The 644H and 644R meet all requirements listed under IEC 61326:Amendment 1, 1998
Hazardous Locations Certificates
North American Certifications
Factory Mutual (FM) Approvals
I5 FM Intrinsic Safety and Non-incendive:
Intrinsically Safe for Class I/II/III, Division 1, Groups A, B, C, D, E, F, and G.
Non-incendive for Class I, Division 2, Groups A, B, C, and D. Intrinsically Safe and
non-incendive when installed in accordance with Rosemount drawing 00644-0009.
12
4728 Rev BB.fm Page 13 Thursday, June 3, 2010 11:50 AM
Note
K6 is only available with 644H option code J6.
13
4728 Rev BB.fm Page 14 Thursday, June 3, 2010 11:50 AM
European Certifications
CENELEC ATEX Approvals
I1 CENELEC Intrinsic Safety:
Certificate Number: BAS00ATEX1033X
ATEX Marking: II 1 G EEx ia IIC T4/T5/T6
1180
Table 3. Temperature Code
Pi Temperature Code
0.67 W T6 (Tamb = – 60 °C to 40 °C)
0.67 W T5 (Tamb = – 60 °C to 50 °C)
1.0 W T5 (Tamb = – 60 °C to 40 °C)
1.0 W T4 (Tamb = – 60 °C to 80 °C)
E1 CENELEC Flame-Proof:
Certificate Number: KEMA99ATEX8715
ATEX Marking: II 2 G EEx d IIC T6
1180
Temperature Code: T6 (Tamb=–40°C to 65°C)
Max Input Voltage: Ui=55Vdc
N1 CENELEC Type n:
Certificate Number: BAS00ATEX3145
ATEX Marking: II 3 G EEx nL IIC T5
Temperature Code: T5 (Tamb=–40°C to 70°C)
Max Input Voltage: Ui=45Vdc
NC CENELEC Type n Component:
Certificate Number: BAS99ATEX3084U
ATEX Marking: II 3 G EEx nL IIC T5
Temperature Code: T5 (Tamb=–40°C to 70°C)
Max Input Voltage: Ui=45Vdc
Note
The equipment must be installed in an enclosure meeting the requirements of IP54 and
the requirements of the impact tests described in EN50021.
14
4728 Rev BB.fm Page 15 Thursday, June 3, 2010 11:50 AM
IECEx Certifications
E7 IECEx Flameproof and Dust
Certificate No.: IECEx KEM 09.0015X
Ex d IIC T6 (Flameproof)
Ex tD A20 IP 66 T 95 ºC (Dust)
Vmax = 42.4V
Special Conditions for Safe Use (X):
For information on the dimensions of the flameproof joints the manufacturer shall be
contacted.
Table 5. Electrical Data
Transmitter Sensor
Umax = 42.4 Vdc Umax = 5 V
Imax = 24.0 mA Imax = 2.0 mA
N7 IECEx Type n
Certificate Number: IECEx BAS 07.0055
Ex nA nL IIC T5 (-40 °C < Ta < 70 °C)
Table 8. Electrical Data
Sensor
Transmitter RTD Thermocouple
Ui = 42.4 V Ui = 5 V Ui = 0
15
4728 Rev BB.fm Page 16 Thursday, June 3, 2010 11:50 AM
Brazilian Certifications
Centro de Pesquisas de Energia Eletrica (CEPEL) Approval
I2 CEPEL Intrinsic Safety. Not available, consult factory
Japanese Certifications
Japanese Industrial Standard (JIS) Approvals
E4 JIS Explosion-Proof
Russian Certifications
Gostandart
Tested and approved by the Russian Metrological Institute GOSTANDART.
16
4728 Rev BB.fm Page 17 Thursday, June 3, 2010 11:50 AM
EC Declaration of Conformity
No: RMD 1016 Rev. F
We,
Rosemount Inc.
8200 Market Boulevard
Chanhassen, MN 55317-6985
USA
declare under our sole responsibility that the product,
Assumption of conformity is based on the application of the harmonized standards and, when
applicable or required, a European Community notified body certification, as shown in the
attached schedule.